{ "containers": { "cna": { "providerMetadata": { "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens", "dateUpdated": "2023-08-08T09:20:03.377Z" }, "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.3), Nucleus ReadyStart V4 (All versions < V4.1.0), Nucleus Source Code (Versions including affected DNS modules), SIMOTICS CONNECT 400 (All versions < V0.5.0.0), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). The DNS domain name label parsing functionality does not properly validate the null-terminated name in DNS-responses. The parsing of malformed responses could result in a read past the end of an allocated structure. An attacker with a privileged position in the network could leverage this vulnerability to cause a denial-of-service condition or leak the read memory." } ], "affected": [ { "vendor": "Siemens", "product": "APOGEE PXC Compact (BACnet)", "versions": [ { "version": "All versions < V3.5.5", "status": "affected" } ], "defaultStatus": "unknown" }, { "vendor": "Siemens", "product": "APOGEE PXC Compact (P2 Ethernet)", "versions": [ { "version": "All versions < V2.8.20", "status": "affected" } ], "defaultStatus": "unknown" }, { "vendor": "Siemens", "product": "APOGEE PXC Modular (BACnet)", "versions": [ { "version": "All versions < V3.5.5", "status": "affected" } ], "defaultStatus": "unknown" }, { "vendor": "Siemens", "product": "APOGEE PXC Modular (P2 Ethernet)", "versions": [ { "version": "All versions < V2.8.20", "status": "affected" } ], "defaultStatus": "unknown" }, { "vendor": "Siemens", "product": "Nucleus NET", "versions": [ { "version": "All versions", "status": "affected" } ], "defaultStatus": "unknown" }, { "vendor": "Siemens", "product": "Nucleus ReadyStart V3", "versions": [ { "version": "All versions < V2017.02.3", "status": "affected" } ], "defaultStatus": "unknown" }, { "vendor": "Siemens", "product": "Nucleus ReadyStart V4", "versions": [ { "version": "All versions < V4.1.0", "status": "affected" } ], "defaultStatus": "unknown" }, { "vendor": "Siemens", "product": "Nucleus Source Code", "versions": [ { "version": "Versions including affected DNS modules", "status": "affected" } ], "defaultStatus": "unknown" }, { "vendor": "Siemens", "product": "SIMOTICS CONNECT 400", "versions": [ { "version": "All versions < V0.5.0.0", "status": "affected" } ], "defaultStatus": "unknown" }, { "vendor": "Siemens", "product": "TALON TC Compact (BACnet)", "versions": [ { "version": "All versions < V3.5.5", "status": "affected" } ], "defaultStatus": "unknown" }, { "vendor": "Siemens", "product": "TALON TC Modular (BACnet)", "versions": [ { "version": "All versions < V3.5.5", "status": "affected" } ], "defaultStatus": "unknown" } ], "metrics": [ { "cvssV3_1": { "version": "3.1", "vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:L/I:N/A:H/E:P/RL:O/RC:C", "baseScore": 6.5, "baseSeverity": "MEDIUM" } } ], "problemTypes": [ { "descriptions": [ { "lang": "en", "cweId": "CWE-170", "description": "CWE-170: Improper Null Termination", "type": "CWE" } ] } ], "references": [ { "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-705111.pdf" }, { "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-669158.pdf" }, { "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-180579.pdf" } ] }, "adp": [ { "providerMetadata": { "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE", "dateUpdated": "2024-08-04T16:18:45.573Z" }, "title": "CVE Program Container", "references": [ { "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-705111.pdf", "tags": [ "x_transferred" ] }, { "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-669158.pdf", "tags": [ "x_transferred" ] }, { "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-180579.pdf", "tags": [ "x_transferred" ] } ] } ] }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2020-27736", "datePublished": "2021-04-22T20:42:19.000Z", "dateReserved": "2020-10-26T00:00:00.000Z", "dateUpdated": "2024-08-04T16:18:45.573Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }