{ "containers": { "cna": { "affected": [ { "product": "Intelligent Power manager (IPM)", "vendor": "Eaton", "versions": [ { "lessThan": "1.69", "status": "affected", "version": "unspecified", "versionType": "custom" } ] } ], "credits": [ { "lang": "en", "value": "Amir Preminger from Claroty research" } ], "datePublic": "2021-04-01T00:00:00.000Z", "descriptions": [ { "lang": "en", "value": "Eaton Intelligent Power Manager (IPM) prior to 1.69 is vulnerable to unauthenticated remote code execution vulnerability. IPM software does not sanitize the date provided via coverterCheckList action in meta_driver_srv.js class. Attackers can send a specially crafted packet to make IPM connect to rouge SNMP server and execute attacker-controlled code." } ], "metrics": [ { "cvssV3_1": { "attackComplexity": "LOW", "attackVector": "NETWORK", "availabilityImpact": "HIGH", "baseScore": 10, "baseSeverity": "CRITICAL", "confidentialityImpact": "HIGH", "integrityImpact": "HIGH", "privilegesRequired": "NONE", "scope": "CHANGED", "userInteraction": "NONE", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H", "version": "3.1" } } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-94", "description": "CWE-94 Improper Control of Generation of Code ('Code Injection')", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2021-04-13T18:03:54.000Z", "orgId": "63703b7d-23e2-41ef-94b3-a3c6333f7759", "shortName": "Eaton" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://www.eaton.com/content/dam/eaton/company/news-insights/cybersecurity/security-bulletins/eaton-intelligent-power-manager-ipm-vulnerability-advisory.pdf" } ], "solutions": [ { "lang": "en", "value": "upgrade the software to latest version 1.69" } ], "source": { "advisory": "ETN-VA-2021-1000", "defect": [ "ETN-VA-2021-1000" ], "discovery": "EXTERNAL" }, "title": "Remote Code execution", "workarounds": [ { "lang": "en", "value": "To prevent the exploitation of the issues and safeguard the software from malicious entities, Eaton recommends blocking ports 4679 & 4680 at the enterprise network or home network where Intelligent Power Manager (IPM) software is installed and used" } ], "x_generator": { "engine": "Vulnogram 0.0.9" }, "x_legacyV4Record": { "CVE_data_meta": { "AKA": "Code Injection", "ASSIGNER": "CybersecurityCOE@eaton.com", "DATE_PUBLIC": "2021-04-01T07:00:00.000Z", "ID": "CVE-2021-23281", "STATE": "PUBLIC", "TITLE": "Remote Code execution" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "Intelligent Power manager (IPM)", "version": { "version_data": [ { "version_affected": "<", "version_value": "1.69" } ] } } ] }, "vendor_name": "Eaton" } ] } }, "credit": [ { "lang": "eng", "value": "Amir Preminger from Claroty research" } ], "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "Eaton Intelligent Power Manager (IPM) prior to 1.69 is vulnerable to unauthenticated remote code execution vulnerability. IPM software does not sanitize the date provided via coverterCheckList action in meta_driver_srv.js class. Attackers can send a specially crafted packet to make IPM connect to rouge SNMP server and execute attacker-controlled code." } ] }, "generator": { "engine": "Vulnogram 0.0.9" }, "impact": { "cvss": { "attackComplexity": "LOW", "attackVector": "NETWORK", "availabilityImpact": "HIGH", "baseScore": 10, "baseSeverity": "CRITICAL", "confidentialityImpact": "HIGH", "integrityImpact": "HIGH", "privilegesRequired": "NONE", "scope": "CHANGED", "userInteraction": "NONE", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H", "version": "3.1" } }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-94 Improper Control of Generation of Code ('Code Injection')" } ] } ] }, "references": { "reference_data": [ { "name": "https://www.eaton.com/content/dam/eaton/company/news-insights/cybersecurity/security-bulletins/eaton-intelligent-power-manager-ipm-vulnerability-advisory.pdf", "refsource": "MISC", "url": "https://www.eaton.com/content/dam/eaton/company/news-insights/cybersecurity/security-bulletins/eaton-intelligent-power-manager-ipm-vulnerability-advisory.pdf" } ] }, "solution": [ { "lang": "en", "value": "upgrade the software to latest version 1.69" } ], "source": { "advisory": "ETN-VA-2021-1000", "defect": [ "ETN-VA-2021-1000" ], "discovery": "EXTERNAL" }, "work_around": [ { "lang": "en", "value": "To prevent the exploitation of the issues and safeguard the software from malicious entities, Eaton recommends blocking ports 4679 & 4680 at the enterprise network or home network where Intelligent Power Manager (IPM) software is installed and used" } ] } }, "adp": [ { "providerMetadata": { "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE", "dateUpdated": "2024-08-03T19:05:55.648Z" }, "title": "CVE Program Container", "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://www.eaton.com/content/dam/eaton/company/news-insights/cybersecurity/security-bulletins/eaton-intelligent-power-manager-ipm-vulnerability-advisory.pdf" } ] } ] }, "cveMetadata": { "assignerOrgId": "63703b7d-23e2-41ef-94b3-a3c6333f7759", "assignerShortName": "Eaton", "cveId": "CVE-2021-23281", "datePublished": "2021-04-13T18:03:54.932Z", "dateReserved": "2021-01-08T00:00:00.000Z", "dateUpdated": "2024-09-17T02:41:57.724Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }