"dataType": "CVE_RECORD",
"dataVersion": "5.1",
"cveMetadata": {
"cveId": "CVE-2022-2502",
"assignerOrgId": "e383dce4-0c27-4495-91c4-0db157728d17",
"state": "PUBLISHED",
"assignerShortName": "Hitachi Energy",
"dateReserved": "2022-07-21T06:25:31.199Z",
"datePublished": "2023-07-26T05:25:27.002Z",
"dateUpdated": "2025-03-05T18:47:06.707Z"
},
"containers": {
"cna": {
"affected": [
{
"defaultStatus": "unaffected",
"product": "RTU500 series",
"vendor": "Hitachi Energy",
"versions": [
{
"status": "affected",
"version": "RTU500 series CMU Firmware version 13.3.1"
},
{
"status": "affected",
"version": "RTU500 series CMU Firmware version 13.3.2"
},
{
"status": "unaffected",
"version": "RTU500 series CMU Firmware version 13.3.3"
},
{
"status": "unaffected",
"version": "RTU500 series CMU Firmware version 13.4.1"
}
]
}
],
"configurations": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "RTU500 series with HCI IEC 60870-5-104 and IEC 62351-5 configured and enabled.
"
}
],
"value": "RTU500 series with HCI IEC 60870-5-104 and IEC 62351-5 configured and enabled."
}
],
"descriptions": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "A vulnerability exists in the HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-5 and the CMU contains the license feature ‘Advanced security’ which must be ordered separately. If these preconditions are fulfilled, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the targeted RTU500 CMU to reboot. The vulnerability is caused by a missing input data validation which eventually if exploited causes an internal buffer to overflow in the HCI IEC 60870-5-104 function."
}
],
"value": "A vulnerability exists in the HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-5 and the CMU contains the license feature ‘Advanced security’ which must be ordered separately. If these preconditions are fulfilled, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the targeted RTU500 CMU to reboot. The vulnerability is caused by a missing input data validation which eventually if exploited causes an internal buffer to overflow in the HCI IEC 60870-5-104 function."
}
],
"impacts": [
{
"capecId": "CAPEC-100",
"descriptions": [
{
"lang": "en",
"value": "CAPEC-100 Overflow Buffers"
}
]
}
],
"metrics": [
{
"cvssV3_1": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"format": "CVSS",
"scenarios": [
{
"lang": "en",
"value": "GENERAL"
}
]
}
],
"problemTypes": [
{
"descriptions": [
{
"cweId": "CWE-20",
"description": "CWE-20 Improper Input Validation",
"lang": "en",
"type": "CWE"
}
]
}
],
"providerMetadata": {
"orgId": "e383dce4-0c27-4495-91c4-0db157728d17",
"shortName": "Hitachi Energy",
"dateUpdated": "2024-09-24T15:29:49.528Z"
},
"references": [
{
"tags": [
"vendor-advisory"
],
"url": "https://publisher.hitachienergy.com/preview?DocumentID=8DBD000121&LanguageCode=en&DocumentPartId=&Action=Launch"
}
],
"solutions": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "Update to CMU Firmware versions 13.3.3 or 13.4.1.
"
}
],
"value": "Update to CMU Firmware versions 13.3.3 or 13.4.1."
}
],
"source": {
"discovery": "UNKNOWN"
},
"workarounds": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "Disable the HCI IEC 60870-5-104 function or its IEC 62351-5 feature if it is not used.
"
}
],
"value": "Disable the HCI IEC 60870-5-104 function or its IEC 62351-5 feature if it is not used."
}
],
"x_generator": {
"engine": "Vulnogram 0.1.0-dev"
}
},
"adp": [
{
"providerMetadata": {
"orgId": "af854a3a-2127-422b-91ae-364da2661108",
"shortName": "CVE",
"dateUpdated": "2024-08-03T00:39:07.853Z"
},
"title": "CVE Program Container",
"references": [
{
"url": "https://search.abb.com/library/Download.aspx?DocumentID=8DBD000121&LanguageCode=en&DocumentPartId=&Action=Launch",
"tags": [
"x_transferred"
]
}
]
},
{
"metrics": [
{
"other": {
"type": "ssvc",
"content": {
"timestamp": "2025-03-05T18:38:29.193487Z",
"id": "CVE-2022-2502",
"options": [
{
"Exploitation": "none"
},
{
"Automatable": "yes"
},
{
"Technical Impact": "partial"
}
],
"role": "CISA Coordinator",
"version": "2.0.3"
}
}
}
],
"title": "CISA ADP Vulnrichment",
"providerMetadata": {
"orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
"shortName": "CISA-ADP",
"dateUpdated": "2025-03-05T18:47:06.707Z"
}
}
]
}
}