{ "dataType": "CVE_RECORD", "dataVersion": "5.1", "cveMetadata": { "cveId": "CVE-2024-5988", "assignerOrgId": "b73dd486-f505-4403-b634-40b078b177f0", "state": "PUBLISHED", "assignerShortName": "Rockwell", "dateReserved": "2024-06-13T20:56:08.636Z", "datePublished": "2024-06-25T15:53:33.899Z", "dateUpdated": "2025-08-27T20:42:59.382Z" }, "containers": { "cna": { "affected": [ { "defaultStatus": "unaffected", "product": "ThinManager® ThinServer™", "vendor": "Rockwell Automation", "versions": [ { "status": "affected", "version": "11.1.0" }, { "status": "affected", "version": "11.2.0" }, { "status": "affected", "version": "12.0.0" }, { "status": "affected", "version": "12.1.0" }, { "status": "affected", "version": "13.0.0" }, { "status": "affected", "version": "13.1.0" }, { "status": "affected", "version": "13.2.0" } ] } ], "datePublic": "2024-06-25T13:00:00.000Z", "descriptions": [ { "lang": "en", "supportingMedia": [ { "base64": false, "type": "text/html", "value": "Due to an improper input validation, an unauthenticated threat actor can send a malicious message to invoke a local or remote executable and cause a remote code execution condition on the Rockwell Automation ThinManager® ThinServer™." } ], "value": "Due to an improper input validation, an unauthenticated threat actor can send a malicious message to invoke a local or remote executable and cause a remote code execution condition on the Rockwell Automation ThinManager® ThinServer™." } ], "impacts": [ { "capecId": "CAPEC-153", "descriptions": [ { "lang": "en", "value": "CAPEC-153 Input Data Manipulation" } ] } ], "metrics": [ { "cvssV4_0": { "Automatable": "NOT_DEFINED", "Recovery": "NOT_DEFINED", "Safety": "NOT_DEFINED", "attackComplexity": "LOW", "attackRequirements": "NONE", "attackVector": "NETWORK", "baseScore": 9.3, "baseSeverity": "CRITICAL", "privilegesRequired": "NONE", "providerUrgency": "NOT_DEFINED", "subAvailabilityImpact": "NONE", "subConfidentialityImpact": "NONE", "subIntegrityImpact": "NONE", "userInteraction": "NONE", "valueDensity": "NOT_DEFINED", "vectorString": "CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N", "version": "4.0", "vulnAvailabilityImpact": "HIGH", "vulnConfidentialityImpact": "HIGH", "vulnIntegrityImpact": "HIGH", "vulnerabilityResponseEffort": "NOT_DEFINED" }, "format": "CVSS", "scenarios": [ { "lang": "en", "value": "GENERAL" } ] } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-20", "description": "CWE-20 Improper Input Validation", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "orgId": "b73dd486-f505-4403-b634-40b078b177f0", "shortName": "Rockwell", "dateUpdated": "2024-06-25T16:03:05.556Z" }, "references": [ { "url": "https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1677.html" } ], "solutions": [ { "lang": "en", "supportingMedia": [ { "base64": false, "type": "text/html", "value": "
Affected Product | CVE | First Known in software version | Corrected in software version (Available Here) |
ThinManager® ThinServer™ | 2024-5988 2024-5989
| 11.1.0 11.2.0 12.0.0 12.1.0 13.0.0 13.1.0 13.2.0 | |
2024-5990 | 11.1.0 11.2.0 12.0.0 12.1.0 13.0.0 13.1.0 |
Customers using the affected software are encouraged to apply the risk mitigations from the list below, if possible. Additionally, we encourage customers to implement our suggested security best practices to minimize the potential risk of vulnerability.
· Update to the corrected software versions via the ThinManager® Downloads Site
· Limit remote access for TCP Port 2031 to known thin clients and ThinManager® servers.
· Security Best Practices
\n\n