{ "dataType": "CVE_RECORD", "dataVersion": "5.1", "cveMetadata": { "cveId": "CVE-2025-36535", "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6", "state": "PUBLISHED", "assignerShortName": "icscert", "dateReserved": "2025-05-14T16:57:44.359Z", "datePublished": "2025-05-21T19:52:13.068Z", "dateUpdated": "2025-05-22T18:49:49.738Z" }, "containers": { "cna": { "affected": [ { "defaultStatus": "unaffected", "product": "MB-Gateway", "vendor": "AutomationDirect", "versions": [ { "status": "affected", "version": "All" } ] } ], "credits": [ { "lang": "en", "type": "finder", "value": "Souvik Kandar reported this vulnerability to AutomationDirect." } ], "datePublic": "2025-05-20T16:00:00.000Z", "descriptions": [ { "lang": "en", "supportingMedia": [ { "base64": false, "type": "text/html", "value": "The embedded web server lacks authentication and access controls, allowing unrestricted remote access. This could lead to configuration changes, operational disruption, or arbitrary code execution depending on the environment and exposed functionality." } ], "value": "The embedded web server lacks authentication and access controls, allowing unrestricted remote access. This could lead to configuration changes, operational disruption, or arbitrary code execution depending on the environment and exposed functionality." } ], "metrics": [ { "cvssV4_0": { "Automatable": "NOT_DEFINED", "Recovery": "NOT_DEFINED", "Safety": "NOT_DEFINED", "attackComplexity": "LOW", "attackRequirements": "NONE", "attackVector": "NETWORK", "baseScore": 10, "baseSeverity": "CRITICAL", "privilegesRequired": "NONE", "providerUrgency": "NOT_DEFINED", "subAvailabilityImpact": "HIGH", "subConfidentialityImpact": "HIGH", "subIntegrityImpact": "HIGH", "userInteraction": "NONE", "valueDensity": "NOT_DEFINED", "vectorString": "CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H", "version": "4.0", "vulnAvailabilityImpact": "HIGH", "vulnConfidentialityImpact": "HIGH", "vulnIntegrityImpact": "HIGH", "vulnerabilityResponseEffort": "NOT_DEFINED" }, "format": "CVSS", "scenarios": [ { "lang": "en", "value": "GENERAL" } ] }, { "cvssV3_1": { "attackComplexity": "LOW", "attackVector": "NETWORK", "availabilityImpact": "HIGH", "baseScore": 10, "baseSeverity": "CRITICAL", "confidentialityImpact": "HIGH", "integrityImpact": "HIGH", "privilegesRequired": "NONE", "scope": "CHANGED", "userInteraction": "NONE", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H", "version": "3.1" }, "format": "CVSS", "scenarios": [ { "lang": "en", "value": "GENERAL" } ] } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-306", "description": "CWE-306 Missing Authentication for Critical Function", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6", "shortName": "icscert", "dateUpdated": "2025-05-21T19:52:13.068Z" }, "references": [ { "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-25-140-09" }, { "url": "https://www.automationdirect.com/adc/shopping/catalog/communications/protocol_gateways/modbus_gateways/eki-1221-ce" } ], "source": { "advisory": "ICSA-25-140-09", "discovery": "EXTERNAL" }, "tags": [ "unsupported-when-assigned" ], "title": "AutomationDirect MB-Gateway Missing Authentication for Critical Function", "workarounds": [ { "lang": "en", "supportingMedia": [ { "base64": false, "type": "text/html", "value": "
The hardware limitation of MB-Gateway does not provide for the implementation of proper access control update. AutomationDirect recommends that users plan for replacement of MB-Gateway with EKI-1221-CE.
If an immediate replacement is not feasible, AutomationDirect recommends considering the following interim steps until the programming software can be updated: