{ "title": "template_title", "device_type": "ONOKOM-AIR-LG-8-MB-B", "group": "g-air-conditioning", "hw": [ { "signature": "LG-8-MB-B" } ], "device": { "name": "ONOKOM-AIR-LG-8-MB-B", "id": "ONOKOM-AIR-LG-8-MB-B", "groups": [ { "title": "General", "id": "general", "order": 1 }, { "title": "Temperature control", "id": "temperatureControl", "order": 2 }, { "title": "Vanes", "id": "vanes", "order": 3 }, { "title": "Additional", "id": "additional", "order": 4 }, { "title": "HW Info", "id": "hw_info", "order": 6 }, { "title": "Errors", "id": "errors", "order": 8 }, { "title": "Debug", "id": "debug", "order": 9 } ], "parameters": [ { "id": "Allow_the_use_of_an_external_temperature_sensor", "title": "Allow the use of an external temperature sensor", "address": 100, "reg_type": "coil", "enum": [ 0, 1 ], "enum_titles": [ "No", "Yes" ], "group": "temperatureControl", "default": 0, "order": 1 }, { "id": "Show_modes_as_range", "title": "Show modes as range", "address": 95, "default": 0, "reg_type": "coil", "enum": [ 0, 1 ], "enum_titles": [ "No", "Yes" ], "group": "general", "order": 1 }, { "id": "Show_fan_as_range", "title": "Show fan as range", "address": 92, "default": 0, "reg_type": "coil", "enum": [ 0, 1 ], "enum_titles": [ "No", "Yes" ], "group": "general", "order": 1 }, { "id": "Show_vanes_as_range", "title": "Show vanes as range", "address": 94, "default": 0, "reg_type": "coil", "enum": [ 0, 1 ], "enum_titles": [ "No", "Yes" ], "group": "vanes", "order": 1 }, { "id": "Show_thermostat_state_as_range", "title": "Show thermostat state as range", "address": 94, "default": 0, "reg_type": "coil", "enum": [ 0, 1 ], "enum_titles": [ "No", "Yes" ], "group": "temperatureControl", "order": 1 }, { "title": "Show error switches", "id": "Show_error_switches", "address": 100, "reg_type": "coil", "default": 0, "enum": [ 0, 1 ], "enum_titles": [ "No", "Yes" ], "group": "errors", "order": 1 }, { "id": "baud_rate", "title": "Baud rate", "description": "baud_rate_description", "address": 110, "reg_type": "holding", "enum": [ 96, 192, 384, 576, 1152 ], "default": 96, "enum_titles": [ "9600", "19200", "38400", "57600", "115200" ], "group": "hw_info", "order": 1 }, { "id": "parity_bit", "title": "Parity bit", "description": "parity_bit_description", "address": 111, "reg_type": "holding", "enum": [ 0, 1, 2 ], "default": 0, "enum_titles": [ "none (N)", "odd (O)", "even (E)" ], "group": "hw_info", "order": 1 } ], "channels": [ { "name": "Active", "reg_type": "coil", "address": 1, "type": "switch", "format": "u16", "sporadic": true, "group": "general" }, { "name": "Mode", "reg_type": "holding", "address": 1, "type": "range", "format": "u16", "min": 1, "max": 5, "sporadic": true, "group": "general", "condition": "Show_modes_as_range==1" }, { "name": "Mode", "reg_type": "holding", "address": 1, "type": "value", "format": "u16", "sporadic": true, "group": "general", "enum": [ 1, 2, 3, 4, 5 ], "enum_titles": [ "Heat", "Cool", "Auto", "Dry", "Fan" ], "condition": "Show_modes_as_range!=1" }, { "name": "Active mode", "reg_type": "holding", "address": 2, "type": "range", "format": "u16", "min": 0, "max": 5, "sporadic": true, "group": "general", "condition": "Show_modes_as_range==1" }, { "name": "Active mode", "reg_type": "holding", "address": 2, "type": "value", "format": "u16", "sporadic": true, "group": "general", "enum": [ 0, 1, 2, 3, 4, 5 ], "enum_titles": [ "Off", "Heat", "Cool", "Auto", "Dry", "Fan" ], "condition": "Show_modes_as_range!=1" }, { "name": "Fan speed", "reg_type": "holding", "address": 7, "type": "range", "format": "u16", "min": 0, "max": 6, "sporadic": true, "group": "general", "condition": "Show_fan_as_range==1" }, { "name": "Fan speed", "reg_type": "holding", "address": 7, "type": "value", "format": "u16", "sporadic": true, "group": "general", "enum": [ 0, 1, 2, 3, 4, 5, 6 ], "enum_titles": [ "Auto", "1 Speed", "2 Speed", "3 Speed", "4 Speed", "5 Speed", "6 Speed" ], "condition": "Show_fan_as_range!=1" }, { "name": "Smart fan speed", "reg_type": "holding", "address": 8, "type": "range", "format": "u16", "min": 0, "max": 7, "sporadic": true, "group": "general", "condition": "Show_fan_as_range==1" }, { "name": "Smart fan speed", "reg_type": "holding", "address": 8, "type": "value", "format": "u16", "min": 0, "max": 8, "sporadic": true, "group": "general", "enum": [ 0, 2, 3, 4, 5, 6, 7, 8 ], "enum_titles": [ "Auto", "1 Speed", "2 Speed", "3 Speed", "4 Speed", "5 Speed", "6 Speed", "Turbo mode" ], "condition": "Show_fan_as_range!=1" }, { "name": "Outdoor air supply", "reg_type": "coil", "address": 15, "type": "switch", "sporadic": true, "group": "general" }, { "name": "External air temperature", "reg_type": "holding", "address": 30, "type": "value", "format": "s16", "min": -30, "max": 30, "scale": 0.01, "sporadic": true, "group": "temperatureControl", "condition": "Allow_the_use_of_an_external_temperature_sensor==1" }, { "name": "External temperature sensor validity period", "reg_type": "holding", "address": 40, "type": "value", "format": "s16", "min": 0, "max": 100, "sporadic": true, "group": "temperatureControl", "condition": "Allow_the_use_of_an_external_temperature_sensor==1" }, { "name": "Indoor air temperature", "reg_type": "holding", "address": 3, "type": "value", "format": "s16", "scale": 0.01, "sporadic": true, "group": "temperatureControl", "readonly": true, "units": "deg C", "condition": "Allow_the_use_of_an_external_temperature_sensor!=1" }, { "name": "Indoor air temperature", "reg_type": "holding", "address": 3, "type": "value", "format": "s16", "min": -50, "max": 50, "scale": 0.01, "sporadic": true, "group": "temperatureControl", "readonly": true, "units": "deg C", "condition": "Allow_the_use_of_an_external_temperature_sensor==1" }, { "name": "Target temperature", "reg_type": "holding", "address": 5, "type": "range", "format": "s16", "min": 18, "max": 30, "scale": 0.01, "sporadic": true, "group": "temperatureControl", "units": "deg C" }, { "name": "Temperature correction", "reg_type": "holding", "address": 20, "type": "value", "format": "s16", "min": -30, "max": 30, "sporadic": true, "group": "temperatureControl", "condition": "Allow_the_use_of_an_external_temperature_sensor==1" }, { "name": "Thermostat state", "reg_type": "holding", "address": 6, "type": "range", "format": "u16", "min": 0, "max": 2, "sporadic": true, "group": "temperatureControl", "readonly": true, "condition": "Show_thermostat_state_as_range==1" }, { "name": "Thermostat state", "reg_type": "holding", "address": 6, "type": "value", "format": "u16", "sporadic": true, "group": "temperatureControl", "enum": [ 0, 1, 2 ], "enum_titles": [ "Idle", "Heating", "Cooling" ], "readonly": true, "condition": "Show_thermostat_state_as_range!=1" }, { "name": "Horizontal vanes", "reg_type": "holding", "address": 9, "type": "range", "format": "u16", "min": 0, "max": 7, "sporadic": true, "group": "vanes", "condition": "Show_vanes_as_range==1" }, { "name": "Horizontal vanes", "reg_type": "holding", "address": 9, "type": "value", "format": "u16", "sporadic": true, "group": "vanes", "enum": [ 0, 1, 2, 3, 4, 5, 6, 7 ], "enum_titles": [ "Stop", "Swing", "Lowest", "Low", "Middle Low", "Middle", "High", "Highest" ], "condition": "Show_vanes_as_range!=1" }, { "name": "Vanes swing", "reg_type": "holding", "address": 11, "type": "range", "format": "u16", "min": 0, "max": 3, "sporadic": false, "group": "vanes", "condition": "Show_vanes_as_range==1" }, { "name": "Vanes swing", "reg_type": "holding", "address": 11, "type": "value", "format": "u16", "sporadic": false, "group": "vanes", "enum": [ 0, 1, 2, 3 ], "enum_titles": [ "Stop", "Horizontal and vertical vanes swing", "Horizontal vanes swing", "Vertical vanes swing" ], "condition": "Show_vanes_as_range!=1" }, { "name": "Vertical vanes", "reg_type": "holding", "address": 10, "type": "range", "format": "u16", "min": 0, "max": 1, "sporadic": true, "group": "vanes", "condition": "Show_vanes_as_range==1" }, { "name": "Vertical vanes", "reg_type": "holding", "address": 10, "type": "value", "format": "u16", "sporadic": true, "group": "vanes", "enum": [ 0, 1 ], "enum_titles": [ "Stop", "Swing" ], "condition": "Show_vanes_as_range!=1" }, { "name": "Defrosting", "enabled": false, "reg_type": "coil", "address": 12, "type": "switch", "sporadic": true, "group": "additional" }, { "name": "Eco mode", "enabled": false, "reg_type": "coil", "address": 6, "type": "switch", "sporadic": true, "group": "additional" }, { "name": "Ionization", "enabled": false, "reg_type": "coil", "address": 9, "type": "switch", "sporadic": true, "group": "additional" }, { "name": "Self cleaning", "enabled": false, "reg_type": "coil", "address": 10, "type": "switch", "sporadic": true, "group": "additional" }, { "name": "Turbo mode", "enabled": false, "reg_type": "coil", "address": 7, "type": "switch", "sporadic": true, "group": "additional" }, { "name": "FW Version", "enabled": false, "reg_type": "holding", "address": 250, "type": "text", "format": "string", "sporadic": true, "group": "hw_info", "readonly": true, "string_data_size": 16 }, { "name": "HW Version", "enabled": false, "reg_type": "holding", "address": 200, "type": "text", "format": "string", "sporadic": true, "group": "hw_info", "readonly": true, "string_data_size": 20 }, { "name": "MCU Temperature", "enabled": false, "reg_type": "input", "address": 124, "type": "temperature", "format": "s16", "scale": 0.1, "group": "hw_info" }, { "name": "PROTO Version", "enabled": false, "reg_type": "input", "address": 400, "type": "text", "format": "string", "sporadic": true, "group": "hw_info", "readonly": true, "string_data_size": 16 }, { "name": "Reboot Device", "enabled": false, "reg_type": "holding", "address": 120, "type": "pushbutton", "group": "hw_info" }, { "name": "Serial", "enabled": false, "reg_type": "holding", "address": 270, "type": "text", "format": "u32", "group": "hw_info", "readonly": true }, { "name": "Signature", "enabled": false, "reg_type": "input", "address": 290, "type": "text", "format": "string", "sporadic": true, "group": "hw_info", "readonly": true, "string_data_size": 12 }, { "name": "Uptime", "enabled": false, "reg_type": "input", "address": 104, "type": "text", "format": "u32", "group": "hw_info" }, { "name": "Error code", "enabled": false, "reg_type": "input", "address": 1, "type": "value", "group": "errors", "enum": [ 0, 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 21, 22, 23, 24, 25, 26, 27, 28, 32, 33, 34, 35, 40, 41, 42, 43, 44, 45, 46, 47, 48, 49, 51, 52, 54, 57, 60, 61, 62, 65, 67, 70 ], "enum_titles": [ "No error", "Error 1", "Error 2", "Error 3", "Error 4", "Error 5", "Error 6", "Error 7", "Error 8", "Error 9", "Error 10", "Error 11", "Error 21", "Error 22", "Error 23", "Error 24", "Error 25", "Error 26", "Error 27", "Error 28", "Error 32", "Error 33", "Error 34", "Error 35", "Error 40", "Error 41", "Error 42", "Error 43", "Error 44", "Error 45", "Error 46", "Error 47", "Error 48", "Error 49", "Error 51", "Error 52", "Error 54", "Error 57", "Error 60", "Error 61", "Error 62", "Error 65", "Error 67", "Error 70" ], "readonly": true, "order": 0 }, { "name": "AC connected", "reg_type": "coil", "address": 20, "type": "switch", "sporadic": true, "group": "debug", "readonly": true } ], "translations": { "en": { "template_title": "ONOKOM AIR LG-8-MB-B (Adapter for household LG systems)", "Error 1": "CH01 - Indoor unit return air sensor fault", "Error 2": "CH02 - Indoor Pipe Sensor or Outdoor Sensor Assy fault, Open or Short", "Error 3": "CH03 - Remote controller comms error", "Error 4": "CH04 - RAC Product: Heat Sink Sensor Error / Commercial Product: Condensate pump float switch risen", "Error 5": "CH05 - Comms Error, check your wiring", "Error 6": "CH06 - Indoor unit coil sensor fault", "Error 7": "CH07 - Multi Splits/Multi V: indoor unit is set to run in a different mode / RAC: Indoor unit BLDC Fan problem", "Error 8": "CH08 - Check the fan motor turns freely / AC Voltage issue", "Error 9": "CH09 - Split: Outdoor unit fan problem / Multi V: indoor PCB failure", "Error 10": "CH10 - RAC Product: Compressor discharge sensor fault", "Error 11": "CH11 - Multi V indoor unit not connected to an outdoor unit", "Error 21": "CH21 - Inverter compressor run current high", "Error 22": "CH22 - Inverter compressor run current high", "Error 23": "CH23 - Inverter dc voltage low", "Error 24": "CH24 - Splits and Multi Splits = High or low pressure trip", "Error 25": "CH25 - Check power supply voltage to the outdoor unit is correct", "Error 26": "CH26 - Inverter compressor seized", "Error 27": "CH27 - Inverter current irregularity", "Error 28": "CH28 - Inverter dc voltage too high", "Error 32": "CH32 - Inverter compressor discharge temperature too high", "Error 33": "CH33 - Excessive rise of standard compressor discharge temperature", "Error 34": "CH34 - Excessive high pressure rise, over 35 bar at HP sensor", "Error 35": "CH35 - Excessive low pressure drop under 1 Bar at LP sensor", "Error 40": "CH40 - Inverter ac current abnormal", "Error 41": "CH41 - Inverter compressor discharge sensor fault", "Error 42": "CH42 - Low pressure sensor fault", "Error 43": "CH43 - High pressure sensor fault", "Error 44": "CH44 - Outdoor unit air sensor fault", "Error 45": "CH45 - Outdoor unit coil sensor fault", "Error 46": "CH46 - Outdoor unit suction sensor fault", "Error 47": "CH47 - Compressor discharge sensor fault", "Error 48": "CH48 - Outdoor unit discharge and air sensor both unplugged", "Error 49": "CH49 - Check power supply voltage to the outdoor unit is correct", "Error 51": "CH51 - Unit mismatch. Check model number of units", "Error 52": "CH52 - Communication error between inverter PCB and main outdoor unit PCB", "Error 54": "CH54 - Comms error indoor to outdoor unit", "Error 57": "CH57 - Comms error between outdoor main PCB and inverter PCB", "Error 60": "CH60 - Outdoor unit PCB EEPROM failure", "Error 61": "CH61 - Condenser coil over 65°C", "Error 62": "CH62 - Inverter over 85°C", "Error 65": "CH65 - Outdoor unit inverter fin temperature sensor fault", "Error 67": "CH67 - Outdoor Fan Motor seized, or rotation sensing circuit failure", "Error 70": "Gateway error – line is noisy" }, "ru": { "General": "Основные режимы и функции", "Temperature control": "Контроль температуры", "Vanes": "Жалюзи", "Additional": "Дополнительные режимы и функции", "HW Info": "Данные модуля", "Errors": "Ошибки", "Debug": "Диагностика", "Allow the use of an external temperature sensor": "Разрешить использование внешнего датчика температуры", "No": "Нет", "Yes": "Да", "Show modes as range": "Отображать режимы как ползунок", "Show fan as range": "Отображать вентилятор как ползунок", "Show vanes as range": "Отображать жалюзи как ползунок", "Show thermostat state as range": "Отображать состояние термостата как ползунок", "Show error switches": "Показать переключатели ошибок", "Baud rate": "Скорость обмена", "baud_rate_description": "Перед изменением параметра убедитесь, что связь с устройством установлена. Выберите нужную скорость обмена, сохраните конфигурацию, а затем укажите в настройках порта эту же скорость.", "Parity bit": "Бит чётности", "parity_bit_description": "Перед изменением параметра убедитесь, что связь с устройством установлена. Выберите нужный бит четности, сохраните конфигурацию, а затем укажите в настройках порта этот же бит четности.", "Active": "Состояние", "Mode": "Режим", "Heat": "Нагрев", "Cool": "Охлаждение", "Auto": "Авто", "Dry": "Осушение", "Fan": "Вентиляция", "Active mode": "Состояние и режим", "Off": "Выключен", "Fan speed": "Скорость вентилятора", "1 Speed": "1 Скорость", "2 Speed": "2 Скорость", "3 Speed": "3 Скорость", "4 Speed": "4 Скорость", "5 Speed": "5 Скорость", "6 Speed": "6 Скорость", "Smart fan speed": "Скорость вентилятора расширенная", "Turbo mode": "Режим турбо", "Outdoor air supply": "Подача воздуха с улицы", "External air temperature": "Температура с внешнего датчика", "External temperature sensor validity period": "Время ожидания данных с внешнего датчика температуры", "Indoor air temperature": "Температура воздуха в помещении", "Target temperature": "Целевая температура", "Temperature correction": "Коррекция температуры", "Thermostat state": "Состояние термостата", "Idle": "Простаивает", "Heating": "Нагрев", "Cooling": "Охлаждение", "Horizontal vanes": "Горизонтальные жалюзи", "Stop": "Остановлены", "Swing": "Качание", "Lowest": "Самое низкое", "Low": "Низкое", "Middle Low": "Среднее низкое", "Middle": "Среднее", "High": "Высокое", "Highest": "Самое высокое", "Vanes swing": "Качание жалюзи", "Horizontal and vertical vanes swing": "Качание горизонтальных и вертикальных жалюзи", "Horizontal vanes swing": "Качание горизонтальных жалюзи", "Vertical vanes swing": "Качание вертикальных жалюзи", "Vertical vanes": "Вертикальные жалюзи", "Defrosting": "Разморозка", "Eco mode": "Режим эко", "Ionization": "Ионизация", "Self cleaning": "Самоочистка", "FW Version": "Версия прошивки", "HW Version": "Версия устройства", "MCU Temperature": "Температура МК", "PROTO Version": "Версия протокола", "Reboot Device": "Перезагрузить устройство", "Serial": "Серийный номер", "Signature": "Сигнатура устройства", "Uptime": "Время работы с момента включения (с)", "Error code": "Код ошибки", "No error": "Нет ошибки", "Error 1": "CH01 - Неисправность датчика входящего (рециркуляционного) воздуха внутреннего блока", "Error 2": "CH02 - Неисправность датчика трубы внутреннего блока или датчиков наружного блока (обрыв или короткое замыкание)", "Error 3": "CH03 - Ошибка связи с проводным пультом управления", "Error 4": "CH04 - RAC: Ошибка датчика радиатора охлаждения / Commercial: Сработал поплавковый выключатель дренажного насоса", "Error 5": "CH05 - Ошибка связи между блоками, проверьте проводку", "Error 6": "CH06 - Неисправность датчика температуры теплообменника внутреннего блока", "Error 7": "CH07 - Multi V: Внутренний блок работает в несогласованном режиме / RAC: Неисправность мотора вентилятора внутреннего блока (BLDC)", "Error 8": "CH08 - Блокировка вращения мотора вентилятора / Проблема с напряжением переменного тока", "Error 9": "CH09 - Split: Неисправность мотора вентилятора наружного блока / Multi V: Сбой платы внутреннего блока", "Error 10": "CH10 - Неисправность датчика температуры нагнетания компрессора", "Error 11": "CH11 - Внутренний блок Multi V не подключен к наружному блоку", "Error 21": "CH21 - Высокий рабочий ток инверторного компрессора", "Error 22": "CH22 - Высокий рабочий ток инверторного компрессора", "Error 23": "CH23 - Слишком низкое напряжение постоянного тока инвертора", "Error 24": "CH24 - Срабатывание защиты по высокому или низкому давлению", "Error 25": "CH25 - Неправильное напряжение питания наружного блока", "Error 26": "CH26 - Заклинивание инверторного компрессора", "Error 27": "CH27 - Аномальный ток инвертора", "Error 28": "CH28 - Слишком высокое напряжение постоянного тока инвертора", "Error 32": "CH32 - Слишком высокая температура нагнетания инверторного компрессора", "Error 33": "CH33 - Чрезмерный перегрев нагнетания стандартного компрессора", "Error 34": "CH34 - Чрезмерное повышение высокого давления (более 35 бар по датчику HP)", "Error 35": "CH35 - Чрезмерное падение низкого давления (менее 1 бар по датчику LP)", "Error 40": "CH40 - Аномальный переменный ток инвертора", "Error 41": "CH41 - Неисправность датчика нагнетания инверторного компрессора", "Error 42": "CH42 - Неисправность датчика низкого давления", "Error 43": "CH43 - Неисправность датчика высокого давления", "Error 44": "CH44 - Неисправность датчика температуры наружного воздуха", "Error 45": "CH45 - Неисправность датчика теплообменника наружного блока", "Error 46": "CH46 - Неисправность датчика трубы всасывания наружного блока", "Error 47": "CH47 - Неисправность датчика температуры нагнетания компрессора", "Error 48": "CH48 - Отключены оба датчика наружного блока (нагнетания и наружного воздуха)", "Error 49": "CH49 - Проверьте правильность напряжения питания наружного блока", "Error 51": "CH51 - Несовпадение блоков (проверьте номера моделей)", "Error 52": "CH52 - Ошибка связи между инверторной платой и главной платой наружного блока", "Error 54": "CH54 - Ошибка связи между внутренним и наружным блоками", "Error 57": "CH57 - Ошибка связи между главной платой наружного блока и инверторной платой", "Error 60": "CH60 - Сбой памяти EEPROM платы наружного блока", "Error 61": "CH61 - Перегрев теплообменника конденсатора (выше 65°C)", "Error 62": "CH62 - Перегрев инвертора (выше 85°C)", "Error 65": "CH65 - Неисправность датчика температуры радиатора инвертора наружного блока", "Error 67": "CH67 - Заклинил мотор вентилятора наружного блока или сбой цепи контроля вращения", "Error 70": "Ошибка шлюза - линия зашумлена", "AC connected": "Кондиционер подключен", "template_title": "ONOKOM AIR LG-8-MB-B (Адаптер для бытовых систем LG)" } } } }