FILEVERSION "3.2"
#STEP7_VERSION V5.5 + SP4
#CREATED "Wednesday, April 22, 2026   10:01:14"

STATION S7300 , "Product1Production"
BEGIN 
  ASSET_ID "083C17BB93D44B3CA95A91921BEBEC99"
  USED_S7_VERSIONS "35 2E 34 2E 33 2E 31 5F 33 2E 34 2E 30 2E 31 7C 30 35 2E 30 34 2E 30 34 2E 30 30 5F 32 32 2E 30 34 2E 30 30 2E 30 31 7C 35 2E 34 2E 35 2E 30 5F 31 32 2E 36 2E 30 2E 31 7C 35 2E 35 2E 34 2E 30 5F 33 31 2E 31 2E 30 2E 31 7C 00"
  REPORT_SYSTEM_ERRORS "0"
  OBJECT_REMOVEABLE "1"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  CREATOR ""
  COMMENT ""
END 

SUBNET INDUSTRIAL_ETHERNET , "Ethernet(ganze Fabrik)"
BEGIN 
  CREATOR ""
  COMMENT ""
  NET_ID_2 "00 3F 00 00 00 06"
  NET_ID "003F00000006"
END 

SUBNET MPI , "MPI(Factory)"
BEGIN 
  MPI_HSA "31"
  MPI_BAUDRATE "187.5_KBPS"
  MPI_GAP "5"
  MPI_READY "20"
  MPI_RETRIES "2"
  MPI_IDLE1 "60"
  MPI_IDLE2 "400"
  MPI_TQUI "0"
  MPI_TSL "415"
  MPI_TTR "9984"
  CREATOR ""
  COMMENT ""
  NET_ID_2 "00 3F 00 00 00 01"
  NET_ID "003f00000001"
END 

SUBNET PROFIBUS , "PROFIBUS(Factory)"
BEGIN 
  PROFIBUS_HSA "126"
  PROFIBUS_BAUDRATE "1.5_MBPS"
  PROFIBUS_RETRIES "1"
  PROFIBUS_GAP "10"
  PROFIBUS_READY "11"
  PROFILE_SELECTION "DP"
  NETCONFIG_ENABLE "0"
  NETCONFIG_AKTIV "1"
  NETCONFIG_PASSIV "9"
  NETCONFIG_XYZ "1"
  CNT_ACT_NODES "0"
  CNT_PAS_NODES "0"
  CNT_XYZ_NODES "0"
  OLM_CONFIG_ENABLE "0"
  AEQU_ENABLE "0"
  BROADCAST_ENABLE "0"
  NETCONFIG_BUSLAST "MEDIUM"
  PROFILE_OPTIMIZATION "0"
  OPTIMIZE_TSLOT "0"
  OPTIMIZE_CONF "0"
  AEQU_CLOCK_ENABLE "0"
  AEQU_CLOCK_TI "0"
  AEQU_CLOCK_TO "0"
  AEQU_DP_BASE "0.001_MS"
  AEQU_SLAVE_BASE "0.001_MS"
  AEQU_CLOCK_TI_MIN "0"
  AEQU_CLOCK_TO_MIN "0"
  AEQU_CLOCK_DP_MAX "32000000"
  AEQU_CLOCK_TITO_MIN "0"
  AEQU_CLOCK_DP_MIN "0"
  AEQU_PROFILE "1"
  CNT_OLM "0"
  CNT_REPEATER "0"
  CU_WIRE_LENGTH "0"
  LWL_WIRE_LENGTH "0"
  PROFIBUS_TQUI "0"
  PROFIBUS_IDLE1 "37"
  PROFIBUS_IDLE2 "150"
  PROFIBUS_TSL "300"
  DLG_TSL_INIT "300"
  TSET "1"
  MIN_TSDR "11"
  MAX_TSDR "150"
  AEQU_PAUSE_TIME "0"
  PROFIBUS_TTR "47367"
  WATCHDOG "126960"
  MIN_SLAVE "750"
  TTR_SLAVE_INT "9005"
  DLG_CNT_REPEATER "0"
  DLG_CU_WIRE_LENGTH "0"
  DLG_CNT_OLM "0"
  DLG_LWL_WIRE_LENGTH "0"
  AEQU_PG_CNT "0"
  AEQU_MASTER_TIME_INP "0"
  AEQU_PG_TIME_INP "0"
  AEQU_DP_TIME_INP "0"
  DDB_TIME_PCI "26"
  TTH_STD "0"
  TAEQ_STD "0"
  AEQU_TDE "8709"
  OPTICAL_RING "0"
  CREATOR ""
  COMMENT ""
  NET_ID_2 "00 0F 00 00 00 39"
  NET_ID "000F00000039"
  NET_CIR_LOCKED "0"
  TIME_SHORTCUT_OUTOF_RING "26"
  TIME_SHORTCUT_OUTOF_RING_V5SP3 "430"
  TIME_SHORTCUT_IN_RING "26"
  TIME_SHORTCUT_IN_RING_V5SP3 "10"
  BUSPROFILE_INTERVAL "0"
  BUSPROFILE_INTERVAL_V5SP3 "0"
  RETRY_IMMEDIATE "1"
  DCI_COUNTER "43"
  NONCYCLIC_REQUEST_CTR "2"
  NONCYCLIC_REQUEST_CTR_DIAG2 "2"
END 

RACK 0, "6ES7 390-1???0-0AA0", "UR"
BEGIN 
  ASSET_ID "7BF17B4B34594CFABB57975DD8B564AC"
  OBJECT_REMOVEABLE "1"
  POS_X "48"
  POS_Y "54"
  SIZE_X "210"
  SIZE_Y "150"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  CREATOR ""
  COMMENT ""
END 

RACK 0, SLOT 2, "6ES7 318-2AJ00-0AB0" "V1.2", "CPU 318-2"
BEGIN 
  ASSET_ID "9F12B8AB9DA949DAB0BAA81757820986"
  ALARM_OB_NO "40"
  _ATTR4_112411 ""
  _ATTR0_112412 "0"
  CBA_USAGE "0"
  OBJECT_REMOVEABLE "1"
  CAPABLE_FAILSAFE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  SIZE_Y "0"
  KSS_CONNECTION "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  CREATOR ""
  MPI_ADDRESS "2"
  COMMENT ""
PARAMETER 
  COMMUNICATION, "20"
  UPDATE_PROCESS_IMAGE_TABLE_CYCLICALLY, "1"
  SIZE_OF_PROCESS_IMAGE, "0"
  CALL_OB85_ON_IO_ACCESS_ERROR, "DONT_CALL_OB85"
  SCAN_CYCLE_MONITORING_TIME, "150"
  MINIMUM_SCAN_CYCLE_TIME, "10"
  SELF_TEST, "0"
  CLOCK_MEMORY, "1"
  MEMORY_BYTE, "0"
END 

RACK 0, SLOT 2, SUBSLOT 1, "_S7H_DP_ETCR_INTEGR_318_2_FW1_2_CT", "DP"
AUTOCREATED 
MASTER DPSUBSYSTEM 1, "PROFIBUS(Factory)", DPADDRESS 2
BEGIN 
  ASSET_ID "55EDFA60F4344C5BB8DEE5819B8293DA"
  PROFIBUSADDRESS "2"
  LINKED_SUBNETNAME "PROFIBUS(Factory)"
  ALARM_OB_NO "40"
  _ATTR4_112411 ""
  DP_CLOCK_MODE "0"
  SLAVE_ACTIVE_PASSIVE "0"
  _ATTR0_112412 "0"
  DP_CLOCK_INT "0"
  OPT_BUSPAR "0"
  DP_MASTER_MODE "DP_MASTER"
  OBJECT_REMOVEABLE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  SIZE_Y "0"
  DP_VERSION "5"
  CAX_APP_ID ""
  L2_ADDR_EQUI_MASTER "255"
  OBJECT_COPYABLE "0"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  8191, 0, 0, 0, 0, 0
END 

RACK 0, SLOT 2, SUBSLOT 2, "_S7H_MPI_DP_318_2_FW1_2_CT", "MPI/DP"
AUTOCREATED 
BEGIN 
  ASSET_ID "7D1AD822B7D745B6A4FB5FA80C2370A6"
  LINKED_SUBNETNAME "MPI(Factory)"
  ALARM_OB_NO "40"
  _ATTR4_112411 ""
  DP_CLOCK_MODE "0"
  SLAVE_ACTIVE_PASSIVE "0"
  _ATTR0_112412 "0"
  DP_CLOCK_INT "0"
  DP_MASTER_MODE "DP_MASTER"
  OBJECT_REMOVEABLE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  SIZE_Y "0"
  DP_VERSION "5"
  CAX_APP_ID ""
  L2_ADDR_EQUI_MASTER "255"
  OBJECT_COPYABLE "0"
  CREATOR ""
  MPI_ADDRESS "2"
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  8190, 0, 0, 0, 0, 0
END 

RACK 0, SLOT 4, "6GK7 343-1CX10-0XE0" "V2.0", "CP 343-1 Lean"
BEGIN 
  ASSET_ID "A7B6EE4A6EAC47B68F540D126E4B2D92"
  MACADDRESS "080006010000"
  IPACTIVE "1"
  IPADDRESS "C0A870C9"
  SUBNETMASK "FFFFFF00"
  ROUTERADDRESS "C0A870C9"
  ROUTERACTIVE "0"
  LINKED_SUBNETNAME "Ethernet(ganze Fabrik)"
  ISOACTIVE "0"
  CPU_NO "1"
  SNDRCV_DATALEN_GR240 "0"
  ALARM_OB_NO "40"
  PRAL_NOT_SUPPORTED "1"
  IP_ADDRESS_VALIDATION_ID "0"
  IP_DHCP_CLIENT_ID ""
  _ATTR4_112411 ""
  _ATTR0_112412 "0"
  H_PROFILE "0"
  COUPLING_UID ""
  MAX_FDL_CON "0"
  MAX_FMS_CON "0"
  SDB_CARRIER "0"
  ETHERNET_MEDIUM_DUPLEX2 "8"
  TIME_SYNC_DIR "0"
  SNDRCV_CONN_PREFIX "0"
  TIME_SYNC_CORRECTION "0"
  SNMP_ACTIVE "1"
  OBJECT_REMOVEABLE "1"
  CP_FAST_SEND_RECV "0"
  POS_X "0"
  TIME_SYNC_PASSING "0"
  POS_Y "0"
  ETHERNET_MEDIUM_DUPLEX "8"
  SIZE_X "0"
  ETHERNET_KEEP_ALIVE "30"
  MODULE_ADD_FLAGS "0"
  SIZE_Y "0"
  TIMESYNC_NTP_ACTIVE "0"
  KSS_CONNECTION "0"
  DEVICE_NAME "CP-343-1-Lean"
  TIMESYNC_NTP_SERVER_ADDR ""
  TIMESYNC_NTP_TIMEZONE "60"
  CAX_APP_ID ""
  PNIO_DEVICE_MODE "0"
  TIMESYNC_NTP_INTERVAL "60"
  SIMATIC_TAKEOVER "0"
  OBJECT_COPYABLE "1"
  DEVICE_MUST_BE_COUPLED "0"
  CREATOR ""
  COMMENT ""
  TIMESYNC_NTP_ACTIVE_NEW "0"
LOCAL_IN_ADDRESSES 
  ADDRESS  256, 0, 16, 0, 1, 0
LOCAL_OUT_ADDRESSES 
  ADDRESS  256, 0, 16, 0, 1, 0
END 

DPSUBSYSTEM 1, "PROFIBUS(Factory): DP-Mastersystem (1)"
BEGIN 
  GROUP_IDENT_SUM_ALL_SLAVES "255"
  GROUP_SYNC_PROP "255"
  GUI_HIDE "0"
  GROUP_FREEZE_PROP "255"
  OBJECT_REMOVEABLE "1"
  GROUP_COMMENT_1 ""
  GROUP_COMMENT_2 ""
  POS_X "27"
  GROUP_COMMENT_3 ""
  POS_Y "18"
  GROUP_COMMENT_4 ""
  SIZE_X "839"
  LAST_USED_PROFIBUS_ADDR "18"
  GROUP_COMMENT_5 ""
  SIZE_Y "16"
  GROUP_COMMENT_6 ""
  GROUP_COMMENT_7 ""
  GROUP_COMMENT_8 ""
  CAX_APP_ID ""
  SUBNET_NAME "PROFIBUS(Factory)"
  OBJECT_COPYABLE "0"
  CREATOR ""
  COMMENT ""
END 

DPSUBSYSTEM 1, DPADDRESS 10, "B754_S34.GSG", "Hauptschrank"
BEGIN
  ASSET_ID "7228565DEFC64F1D99A7EE326A4D452C"
  PNO_IDENT_NO "46932"
  WD_ON "0"
  PDM_PARAM "0"
  CBA_USAGE "0"
  GROUP_IDENT "0"
  NORMSLAVE_DP_MODE "0"
  OBJECT_REMOVEABLE "1"
  NORMSLAVE_PARAM_DATA "C0 00 C4 00 00 00 00 00 00 03 00 CB 43 00 00 00 01 00 00 00 00 80 21 00 20 6B 00 00 20 43 11 06 20 43 11 06 20 83 00 00 00 00 00 00 00 00 20 83 00 00 00 00 00 00 00 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 02 00 23 02 00 23 02 00 23 02 00 23 02 00 23 02 00 23 02 00 23 02 00 23 02 00 23 02 00 23 02 00"
  POS_X "302"
  GATEWAY_COMMENT ""
  POS_Y "55"
  SIZE_X "78"
  SIZE_Y "64"
  MODULE_ADD_FLAGS "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  CREATOR ""
  COMMENT ""
  PHYSICAL_INTERFACE "0"
  CIR_STATE "0"
LOCAL_IN_ADDRESSES 
  ADDRESS  8189, 0, 0, 0, 2, 0
END

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 1, "750-333 Kein Prozessdatenkanal", "0"
BEGIN 
  ASSET_ID "9DBE626F7CBA4C618ECF3E8CEB6FBF65"
  SLAVE_CFG_DATA "01 00 00"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 80 21 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "3330"
  CREATOR ""
  COMMENT ""
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 2, "75x-493 3AI/3-Phasen-Messung", "6AX"
BEGIN 
  ASSET_ID "C4FB7412B99545669DDF0A172BB16AC2"
  SLAVE_CFG_DATA "01 00 F5"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "04 00 20 6B 00 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4930"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  272, 0, 12, 0, 7, 0
LOCAL_OUT_ADDRESSES 
  ADDRESS  272, 0, 12, 0, 7, 0
SYMBOL  I , 0, "HS_Wago_493_PEW272", ""
SYMBOL  I , 2, "HS_Wago_493_PEW274", ""
SYMBOL  I , 4, "HS_Wago_493_PEW276", ""
SYMBOL  I , 6, "HS_Wago_493_PEW278", ""
SYMBOL  I , 8, "HS_Wago_493_PEW280", ""
SYMBOL  I , 10, "HS_Wago_493_PEW282", ""
SYMBOL  O , 0, "HS_Wago_493_PAW272", ""
SYMBOL  O , 2, "HS_Wago_493_PAW274", ""
SYMBOL  O , 4, "HS_Wago_493_PAW276", ""
SYMBOL  O , 6, "HS_Wago_493_PAW278", ""
SYMBOL  O , 8, "HS_Wago_493_PAW280", ""
SYMBOL  O , 10, "HS_Wago_493_PAW282", ""
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 3, "75x-453 4AI/0-20mA/SE", "4AE"
BEGIN 
  ASSET_ID "3D2AFE1AF541434EBDB4CA7C7DF314E2"
  SLAVE_CFG_DATA "01 00 53"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "04 00 20 43 11 06"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4530"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  284, 0, 8, 0, 2, 0
SYMBOL  I , 0, "B13_L_IST", "Füllstandsmessung"
SYMBOL  I , 2, "B8_L_IST", "Füllstandsmessung"
SYMBOL  I , 4, "H19_N_IST", "Istwert H19  - FU"
SYMBOL  I , 6, "H3012_N_IST", "Istwert H3012  - FU"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 4, "75x-453 4AI/0-20mA/SE", "4AE"
BEGIN 
  ASSET_ID "8AED20F2934B432EB43CF37D8DBF52DD"
  SLAVE_CFG_DATA "01 00 53"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "04 00 20 43 11 06"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4530"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  292, 0, 8, 0, 2, 0
SYMBOL  I , 0, "H35_T_IST", "Temperatur H35"
SYMBOL  I , 2, "H27_1_N_IST", "Istwert H27.1  - FU"
SYMBOL  I , 4, "Z2_I_IST", "Strommessung"
SYMBOL  I , 6, "RES_E298", "0-20"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 5, "75x-553 4AO/0-20mA", "4AA"
BEGIN 
  ASSET_ID "0DE02F4215084CECBF48D4A9DF7685E5"
  SLAVE_CFG_DATA "01 00 63"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "0A 00 20 83 00 00 00 00 00 00 00 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "5530"
  CREATOR ""
  COMMENT ""
LOCAL_OUT_ADDRESSES 
  ADDRESS  284, 0, 8, 0, 2, 0
SYMBOL  O , 0, "H24_N_SOLL", "Sollwertvorgabe H24  - FU"
SYMBOL  O , 2, "H19_N_SOLL", "Sollwertvorgabe H19  - FU"
SYMBOL  O , 4, "H3012_N_SOLL", "Sollwertvorgabe H3012  - FU"
SYMBOL  O , 6, "S36_SOLL", "Sollwertvorgabe S36 Dampfregelventil"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 6, "75x-553 4AO/0-20mA", "4AA"
BEGIN 
  ASSET_ID "1C847233B4F445AB83ED429403746DCC"
  SLAVE_CFG_DATA "01 00 63"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "0A 00 20 83 00 00 00 00 00 00 00 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "5530"
  CREATOR ""
  COMMENT ""
LOCAL_OUT_ADDRESSES 
  ADDRESS  292, 0, 8, 0, 2, 0
SYMBOL  O , 0, "H27_1_N_SOLL", "Sollwertvorgabe H27.1  - FU"
SYMBOL  O , 2, "RES_A294", "0-20"
SYMBOL  O , 4, "RES_A296", "0-20"
SYMBOL  O , 6, "RES_A298", "0-20"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 7, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "7190E582BA9A48FD9E31259340B60F13"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  0, 0, 1, 0, 2, 0
SYMBOL  I , 0, "STSP_NA", "Steuerspannung Not-Aus vorhanden -L60.2-F4"
SYMBOL  I , 1, "STSP_HS_INT", "Steuerspannung Hauptschrank Intern vorhanden -L61.2-F1"
SYMBOL  I , 2, "STSP_HS_EXT", "Steuerspannung Hauptschrank Extern vorhanden -L61.3-F2"
SYMBOL  I , 3, "NA_HS_INT", "Not-Aus Hauptschrank Intern betätigt -3S1"
SYMBOL  I , 4, "NA_HS_EXT1", "Not-Aus Hauptschrank Extern 1 betätigt -3S2"
SYMBOL  I , 5, "NA_HS_EXT2", "Not-Aus Hauptschrank Extern 2 betätigt -3S3"
SYMBOL  I , 6, "HS_HS", "Hauptschalter Hauptschrank OK -1Q1"
SYMBOL  I , 7, "NA_HS_LS", "Not-Aus Hauptschrank Leitstand -5S2"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 8, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "EE6BC22FB8144BFFB26AC1D1A9D26071"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  1, 0, 1, 0, 2, 0
SYMBOL  I , 0, "NA_HS_R", "Not-Aus Hauptschrank Not-Aus-Relais OK -6A3"
SYMBOL  I , 1, "STSP230_HS", "Steuerspannung 230V Hauptschrank OK -L10-F11"
SYMBOL  I , 2, "STSP230_HACK", "Steuerspannung 230V Hackschnitzel OK -L10-F12"
SYMBOL  I , 3, "STSP230_P1", "Steuerspannung 230V Presse 1 OK -L10-F13"
SYMBOL  I , 4, "STSP230_P2", "Steuerspannung 230V Presse 2 OK -L10-F14"
SYMBOL  I , 5, "HS_MESS_ESB", "Einschaltbereitschaft Messung Hauptschrank -4Q1"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 9, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "6186A313287B414497D8CFAC2B35AA14"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  2, 0, 1, 0, 2, 0
SYMBOL  I , 0, "H8_ESB", "Einschaltbereitschaft"
SYMBOL  I , 1, "H8_ERM", "Einschaltrückmeldung"
SYMBOL  I , 2, "H8_UEBERF", "Überfüllung"
SYMBOL  I , 3, "S13_ESB", "Overload Switch Diverter"
SYMBOL  I , 4, "S13_C_WEND", "Limit Switch Product2 Direction"
SYMBOL  I , 5, "H9_UEBERF", "Überfüllung-SPARE"
SYMBOL  I , 6, "H26_P_ERM", "Screwconveyor Feedback Product1 Direction"
SYMBOL  I , 7, "H26_C_ERM", "Screwconveyor Feedback Product2 Direction"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 10, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "701FFDE0D58142B89A30CF0FF760FAF1"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  3, 0, 1, 0, 2, 0
SYMBOL  I , 0, "H26_C_P_UEBERF", "Überfüllung"
SYMBOL  I , 1, "H24_3_ESB", "Einschaltbereitschaft"
SYMBOL  I , 2, "H24_3_ERM", "Einschaltrückmeldung"
SYMBOL  I , 3, "H24_4_ESB", "Einschaltbereitschaft"
SYMBOL  I , 4, "H24_4_ERM", "Einschaltrückmeldung"
SYMBOL  I , 5, "B9_1_MIN", "Füllstandgrenzschalter"
SYMBOL  I , 6, "H27_ESB", "Einschaltbereitschaft"
SYMBOL  I , 7, "H27_ERM", "Einschaltrückmeldung"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 11, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "560A1D98EF8A4244BE8386B18A23F991"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  4, 0, 1, 0, 2, 0
SYMBOL  I , 0, "B9_MAX", "Füllstandgrenzschalter"
SYMBOL  I , 1, "B9_MIN", "Füllstandgrenzschalter"
SYMBOL  I , 2, "S4_ESB", "Einschaltbereitschaft"
SYMBOL  I , 3, "S4_WEND1", "Wegendschalter B5"
SYMBOL  I , 4, "S4_WEND2", "Wegendschalter H28"
SYMBOL  I , 5, "H12_ESB", "Einschaltbereitschaft"
SYMBOL  I , 6, "H12_ERM", "Einschaltrückmeldung"
SYMBOL  I , 7, "H12_UEBERF", "Überfüllung"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 12, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "F76D5261192A467A9F4807E5E3B7E3BC"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  5, 0, 1, 0, 2, 0
SYMBOL  I , 0, "H13_ESB", "Einschaltbereitschaft"
SYMBOL  I , 1, "H13_ERM", "Einschaltrückmeldung"
SYMBOL  I , 2, "H13_SLF_TR", "Schieflaufschalter"
SYMBOL  I , 3, "H13_SLF_TL", "Schieflaufschalter"
SYMBOL  I , 4, "H13_SLF_DR", "Schieflaufschalter"
SYMBOL  I , 5, "H13_SLF_DL", "Schieflaufschalter"
SYMBOL  I , 6, "H13_MAN_ON", "Ein-Vor-Ort"
SYMBOL  I , 7, "H13_MAN_OFF", "Aus-Vor-Ort"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 13, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "16C6F4170A63436AA43FEC98A9559314"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  6, 0, 1, 0, 2, 0
SYMBOL  I , 0, "H13_DREHW", "Drehwächter"
SYMBOL  I , 1, "S3_ESB", "Einschaltbereitschaft"
SYMBOL  I , 2, "S3_WEND1", "Wegendschalter H14"
SYMBOL  I , 3, "S3_WEND2", "Wegendschalter H29"
SYMBOL  I , 4, "H14_ESB", "Einschaltbereitschaft"
SYMBOL  I , 5, "H14_ERM", "Einschaltrückmeldung"
SYMBOL  I , 6, "H15_2_ESB", "Einschaltbereitschaft (vormals S3.1)"
SYMBOL  I , 7, "H15_2_ERM", "Einschaltrückmeldung (vormals S3.1)"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 14, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "FA8DE4770AF44C56B40C17F68DFE61F8"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  7, 0, 1, 0, 2, 0
SYMBOL  I , 0, "B14_MIN", "Verladesilo Leer"
SYMBOL  I , 1, "H15_ESB", "Einschaltbereitschaft"
SYMBOL  I , 2, "H15_ERM", "Einschaltrückmeldung"
SYMBOL  I , 3, "H16_ESB", "Einschaltbereitschaft"
SYMBOL  I , 4, "H16_ERM", "Einschaltrückmeldung"
SYMBOL  I , 5, "H16_UEBERF", "Überfüllung"
SYMBOL  I , 6, "H17_ESB", "Einschaltbereitschaft"
SYMBOL  I , 7, "H17_ERM", "Einschaltrückmeldung"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 15, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "F74A1B4C2AEE4D4689E552074AC6D701"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  8, 0, 1, 0, 2, 0
SYMBOL  I , 0, "H17_SLF_TR", "Schieflaufschalter"
SYMBOL  I , 1, "H17_SLF_TL", "Schieflaufschalter"
SYMBOL  I , 2, "H17_SLF_DR", "Schieflaufschalter"
SYMBOL  I , 3, "H17_SLF_DL", "Schieflaufschalter"
SYMBOL  I , 4, "H17_MAN_ON", "Ein-Vor-Ort"
SYMBOL  I , 5, "H17_MAN_OFF", "Aus-Vor-Ort"
SYMBOL  I , 6, "H17_DREHW", "Drehwächter"
SYMBOL  I , 7, "H18_ESB", "Einschaltbereitschaft"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 16, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "18E0CF275DD24C078C1B80BC04ACB55D"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  9, 0, 1, 0, 2, 0
SYMBOL  I , 0, "H18_ERM", "Einschaltrückmeldung"
SYMBOL  I , 1, "H25_1_ESB", "Einschaltbereitschaft"
SYMBOL  I , 2, "H25_1_ERM", "Wegendschalter Close"
SYMBOL  I , 3, "E9.3", "Wegendschalter Open"
SYMBOL  I , 4, "H33_1_ESB", "Einschaltbereitschaft"
SYMBOL  I , 5, "H33_1_ERM", "Wegendschalter Close"
SYMBOL  I , 6, "E9.6", "Wegendschalter Open"
SYMBOL  I , 7, "H43_ESB", "Einschaltbereitschaft"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 17, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "33173BC84FE048BEA886CBD05DC427C5"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  10, 0, 1, 0, 2, 0
SYMBOL  I , 0, "H43_ERM1", "Einschaltrückmeldung >H45"
SYMBOL  I , 1, "H43_ERM2", "Einschaltrückmeldung >B15"
SYMBOL  I , 2, "H45_ESB", "Einschaltbereitschaft"
SYMBOL  I , 3, "H45_ERM", "Einschaltrückmeldung"
SYMBOL  I , 4, "H45_SLF_TR", "Schieflaufschalter"
SYMBOL  I , 5, "H45_SLF_TL", "Schieflaufschalter"
SYMBOL  I , 6, "H45_SLF_DR", "Schieflaufschalter"
SYMBOL  I , 7, "H45_SLF_DL", "Schieflaufschalter"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 18, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "42F2309559CE4560BE2B56D2A4E92A0C"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  11, 0, 1, 0, 2, 0
SYMBOL  I , 0, "H45_MAN_ON", "Ein-Vor-Ort"
SYMBOL  I , 1, "H45_MAN_OFF", "Aus-Vor-Ort"
SYMBOL  I , 2, "H45_DREHW", "Drehwächter"
SYMBOL  I , 3, "S10_ESB", "Einschaltbereitschaft"
SYMBOL  I , 4, "S10_WEND1", "Wegendschalter >H46"
SYMBOL  I , 5, "S10_WEND2", "Wegendschalter >S11"
SYMBOL  I , 6, "S11_ESB", "Einschaltbereitschaft"
SYMBOL  I , 7, "S11_WEND1", "Wegendschalter >H43"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 19, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "B9EF7346746845E1ACBD5D0115EC9B7B"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  12, 0, 1, 0, 2, 0
SYMBOL  I , 0, "S11_WEND2", "Wegendschalter >B16"
SYMBOL  I , 1, "H46_ESB", "Einschaltbereitschaft"
SYMBOL  I , 2, "H46_ERM", "Einschaltrückmeldung"
SYMBOL  I , 3, "B13_MAXMAX", "Füllstandgrenzschalter"
SYMBOL  I , 4, "S8_ESB", "Einschaltbereitschaft"
SYMBOL  I , 5, "S8_WEND1", "Wegendschalter Close"
SYMBOL  I , 6, "S8_WEND2", "Wegendschalter Open"
SYMBOL  I , 7, "H44_ESB", "Einschaltbereitschaft"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 20, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "DBBB55C23A734A409AF0583AE16F3F59"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  13, 0, 1, 0, 2, 0
SYMBOL  I , 0, "H44_ERM", "Einschaltrückmeldung"
SYMBOL  I , 1, "S9_ESB", "Einschaltbereitschaft"
SYMBOL  I , 2, "S9_WEND1", "Wegendschalter >H45"
SYMBOL  I , 3, "S9_WEND2", "Wegendschalter >B17"
SYMBOL  I , 4, "H47_ESB", "Einschaltbereitschaft"
SYMBOL  I , 5, "H47_ERM", "Einschaltrückmeldung"
SYMBOL  I , 6, "H47_SLF_TR", "Schieflaufschalter"
SYMBOL  I , 7, "H47_SLF_TL", "Schieflaufschalter"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 21, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "A51450835A104065BD47E0AB9006A0CD"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  14, 0, 1, 0, 2, 0
SYMBOL  I , 0, "H47_SLF_DR", "Schieflaufschalter"
SYMBOL  I , 1, "H47_SLF_DL", "Schieflaufschalter"
SYMBOL  I , 2, "H47_MAN_ON", "Ein-Vor-Ort"
SYMBOL  I , 3, "H47_MAN_OFF", "Aus-Vor-Ort"
SYMBOL  I , 4, "H47_DREHW", "Drehwächter"
SYMBOL  I , 5, "F7_ESB", "Einschaltbereitschaft"
SYMBOL  I , 6, "F7_ERM", "Einschaltrückmeldung"
SYMBOL  I , 7, "H23_ESB", "Einschaltbereitschaft"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 22, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "C6ED21AE37C8438B81046BC034CB556B"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  15, 0, 1, 0, 2, 0
SYMBOL  I , 0, "H23_ERM", "Einschaltrückmeldung"
SYMBOL  I , 1, "H23_UEBERF", "Überfüllung"
SYMBOL  I , 2, "H24_ESB", "Motorschutz H24-Q1  - NC"
SYMBOL  I , 3, "H24_DOOR", "Revisionstür-Abschaltung H24-K2  - NC"
SYMBOL  I , 4, "H24_VERSTOPFUNG", "Verstopfung Fahne H24  - NC"
SYMBOL  I , 5, "H24_OL_MECH", "Überlast mechanisch H24  - NO"
SYMBOL  I , 6, "H24_OL_FU", "Überlast FU H24  - ??"
SYMBOL  I , 7, "H24_FU_BTB", "Betriebsbereitschaft FU H24  - ??"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 23, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "08CD0B07ED534F0EBFC0F0715953C47E"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  16, 0, 1, 0, 2, 0
SYMBOL  I , 0, "S16_ESB", "Einschaltbereitschaft Winde - Rest integriert, also für uns extern"
SYMBOL  I , 1, "H25_ESB", "Einschaltbereitschaft"
SYMBOL  I , 2, "H25_ERM", "Einschaltrückmeldung"
SYMBOL  I , 3, "H19_ESB", "Motorschutz H19-Q1  - NC"
SYMBOL  I , 4, "H19_FU_FAULT", "Störung FU H19"
SYMBOL  I , 5, "H19_FU_RUN", "Läuft-Meldung FU H19"
SYMBOL  I , 6, "B5_MIN", "Füllstandgrenzschalter"
SYMBOL  I , 7, "B5_MAX", "Füllstandgrenzschalter"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 24, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "6B1CE12D04CE465A99FDD4426362756A"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  17, 0, 1, 0, 2, 0
SYMBOL  I , 0, "B5_MAXMAX", "Füllstandgrenzschalter"
SYMBOL  I , 1, "H28_ESB", "Einschaltbereitschaft"
SYMBOL  I , 2, "H28_ERM", "Einschaltrückmeldung"
SYMBOL  I , 3, "H28_SLF_TR", "Schieflaufschalter"
SYMBOL  I , 4, "H28_SLF_TL", "Schieflaufschalter"
SYMBOL  I , 5, "H28_SLF_DR", "Schieflaufschalter"
SYMBOL  I , 6, "H28_SLF_DL", "Schieflaufschalter"
SYMBOL  I , 7, "H28_MAN_ON", "Ein-Vor-Ort"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 25, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "724C3C1546F54329BEC892584A865133"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  18, 0, 1, 0, 2, 0
SYMBOL  I , 0, "H28_MAN_OFF", "Aus-Vor-Ort"
SYMBOL  I , 1, "H28_DREHW", "Drehwächter"
SYMBOL  I , 2, "H29_ESB", "Einschaltbereitschaft"
SYMBOL  I , 3, "H29_ERM", "Einschaltrückmeldung"
SYMBOL  I , 4, "RES_E18.4", ""
SYMBOL  I , 5, "RES_E18.5", ""
SYMBOL  I , 6, "S5_ESB", "Einschaltbereitschaft"
SYMBOL  I , 7, "S5_WEND1", "Wegendschalter >B10"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 26, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "47DC54E377DA4E4388E7A805F26E1491"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  19, 0, 1, 0, 2, 0
SYMBOL  I , 0, "S5_WEND2", "Wegendschalter >B7"
SYMBOL  I , 1, "H3012_ESB", "Motorschutz H30/H31/H32 FU-Q1  - NC"
SYMBOL  I , 2, "H3012_FU_FAULT", "Störung  H30/H31/H32 FU"
SYMBOL  I , 3, "H3012_FU_RUN", "Läuft-Meldung  H30/H31/H32 FU"
SYMBOL  I , 4, "H30_ESB", "Einschaltbereitschaft"
SYMBOL  I , 5, "H31_ESB", "Einschaltbereitschaft"
SYMBOL  I , 6, "H32_ESB", "Einschaltbereitschaft"
SYMBOL  I , 7, "B10_MIN", "Füllstandgrenzschalter"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 27, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "31AB082C0FD2466183BC3208ABA51D2B"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  20, 0, 1, 0, 2, 0
SYMBOL  I , 0, "B10_MAX", "Füllstandgrenzschalter"
SYMBOL  I , 1, "B10_MAXMAX", "Füllstandgrenzschalter"
SYMBOL  I , 2, "H33_ESB", "Einschaltbereitschaft"
SYMBOL  I , 3, "H33_ERM", "Einschaltrückmeldung"
SYMBOL  I , 4, "H33_UEBERF", "Überfüllung"
SYMBOL  I , 5, "H34_ESB", "Einschaltbereitschaft"
SYMBOL  I , 6, "H34_ERM", "Einschaltrückmeldung"
SYMBOL  I , 7, "H34_SLF_TR", "Schieflaufschalter"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 28, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "60AD8BBF3251467A9250381D877C61ED"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  21, 0, 1, 0, 2, 0
SYMBOL  I , 0, "H34_SLF_TL", "Schieflaufschalter"
SYMBOL  I , 1, "H34_SLF_DR", "Schieflaufschalter"
SYMBOL  I , 2, "H34_SLF_DL", "Schieflaufschalter"
SYMBOL  I , 3, "H34_MAN_ON", "Ein-Vor-Ort"
SYMBOL  I , 4, "H34_MAN_OFF", "Aus-Vor-Ort"
SYMBOL  I , 5, "H34_DREHW", "Drehwächter"
SYMBOL  I , 6, "H38_ESB", "Einschaltbereitschaft"
SYMBOL  I , 7, "H38_ERM", "Einschaltrückmeldung"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 29, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "E82D004932BD41EAA8D1B53839EB10DA"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  22, 0, 1, 0, 2, 0
SYMBOL  I , 0, "S13_P_WEND", "Limit Switch Product1 Direction"
SYMBOL  I , 1, "H29_1_ESB", "Einschaltbereitschaft"
SYMBOL  I , 2, "H29_1_ERM", "Einschaltrückmeldung"
SYMBOL  I , 3, "H29_1_UEBERF", "Überfüllung"
SYMBOL  I , 4, "H42_ESB", "Einschaltbereitschaft"
SYMBOL  I , 5, "H42_ERM", "Einschaltrückmeldung"
SYMBOL  I , 6, "H42_SLF_TR", "Schieflaufschalter"
SYMBOL  I , 7, "H42_SLF_TL", "Schieflaufschalter"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 30, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "51ACC19DA9564FB08B70E1D033A8E16A"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  23, 0, 1, 0, 2, 0
SYMBOL  I , 0, "H42_SLF_DR", "Schieflaufschalter"
SYMBOL  I , 1, "H42_SLF_DL", "Schieflaufschalter"
SYMBOL  I , 2, "H42_MAN_ON", "Ein-Vor-Ort"
SYMBOL  I , 3, "H42_MAN_OFF", "Aus-Vor-Ort"
SYMBOL  I , 4, "H42_DREHW", "Drehwächter"
SYMBOL  I , 5, "H15_1_ESB", "Einschaltbereitschaft (Ehemals S6)"
SYMBOL  I , 6, "H15_1_ERM", "Einschaltrückmeldung (Ehemals S6)"
SYMBOL  I , 7, "E23.7", "(Ehemals S6)"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 31, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "EBC9402F31E0433981A47B606E7A1F60"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  24, 0, 1, 0, 2, 0
SYMBOL  I , 0, "S7_ESB", "Einschaltbereitschaft"
SYMBOL  I , 1, "S7_WEND1", "Wegendschalter Close"
SYMBOL  I , 2, "S7_WEND2", "Wegendschalter Open"
SYMBOL  I , 3, "S14_ESB", "Einschaltbereitschaft"
SYMBOL  I , 4, "S14_WEND1", "Wegendschalter >B14"
SYMBOL  I , 5, "S14_WEND2", "Wegendschalter >H45"
SYMBOL  I , 6, "S14_1_ESB", "Einschaltbereitschaft"
SYMBOL  I , 7, "S14_1_WEND1", "Wegendschalter Close"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 32, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "D7A5DDC754D8492ABE8F28F351AD1F9E"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  25, 0, 1, 0, 2, 0
SYMBOL  I , 0, "S14_1_WEND2", "Wegendschalter Open"
SYMBOL  I , 1, "B14_MAX", "Füllstandgrenzschalter"
SYMBOL  I , 2, "H35_ESB", "Einschaltbereitschaft"
SYMBOL  I , 3, "H35_ERM", "Einschaltrückmeldung"
SYMBOL  I , 4, "H35_DOOR", "Revisionstür-Abschaltung"
SYMBOL  I , 5, "H35_DREHW", "Drehwächter"
SYMBOL  I , 6, "H35_TERM", "Termistor"
SYMBOL  I , 7, "H36_ESB", "Einschaltbereitschaft"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 33, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "BA2FAADDB0EB4D45A17DF57A45D16461"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  26, 0, 1, 0, 2, 0
SYMBOL  I , 0, "H36_ERM", "Einschaltrückmeldung"
SYMBOL  I , 1, "H36_DOOR", "Revisionstür-Abschaltung"
SYMBOL  I , 2, "B11_FULL", "Füllstandgrenzschalter Voll"
SYMBOL  I , 3, "B11_WORK", "Füllstandgrenzschalter Arbeit"
SYMBOL  I , 4, "B11_EMPTY", "Füllstandgrenzschalter Leer"
SYMBOL  I , 5, "S36_1_ESB", "Einschaltbereitschaft"
SYMBOL  I , 6, "S36_1_ERM", "Einschaltrückmeldung"
SYMBOL  I , 7, "H24_1_ESB", "Motorschutz H24.1-Q1  - NC"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 34, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "5E7DC1451BEB460B9327B1E04263DFC2"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  27, 0, 1, 0, 2, 0
SYMBOL  I , 0, "H24_1_DOOR", "Revisionstür-Abschaltung H24.1-K2  - NC"
SYMBOL  I , 1, "H24_1_FU_BTB", "Betriebsbereitschaft FU H24.1  - ??"
SYMBOL  I , 2, "H27_1_ESB", "Motorschutz H27.1-Q1  - NC"
SYMBOL  I , 3, "H27_1_FU_RES", "Reserve FU H27.1"
SYMBOL  I , 4, "H27_1_FU_FAULT", "Störung FU H27.1"
SYMBOL  I , 5, "H24_2_ESB", "Einschaltbereitschaft - Fremdlüfter H24.1"
SYMBOL  I , 6, "H24_2_ERM", "Einschaltrückmeldung - Fremdlüfter H24.1"
SYMBOL  I , 7, "H27_2_ESB", "Einschaltbereitschaft - Fremdlüfter H27.1"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 35, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "3ACFABF5B9F94C3BB0DCCEBF0CBBD70D"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  28, 0, 1, 0, 2, 0
SYMBOL  I , 0, "H27_2_ERM", "Einschaltrückmeldung - Fremdlüfter H27.1"
SYMBOL  I , 1, "H40_ESB", "Einschaltbereitschaft"
SYMBOL  I , 2, "H40_ERM", "Einschaltrückmeldung"
SYMBOL  I , 3, "H40_DOOR", "Revisionstür-Abschaltung"
SYMBOL  I , 4, "H40_ES", "Endschalter"
SYMBOL  I , 5, "H40_MAX", "Füllstandgrenzschalter"
SYMBOL  I , 6, "H40_MAXMAX", "Füllstandgrenzschalter"
SYMBOL  I , 7, "H40_1_ESB", "Einschaltbereitschaft"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 36, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "3FB435EFB5B7414891634283230746BA"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  29, 0, 1, 0, 2, 0
SYMBOL  I , 0, "H40_1_ERM", "Einschaltrückmeldung"
SYMBOL  I , 1, "H40_2_ESB", "Einschaltbereitschaft"
SYMBOL  I , 2, "H40_2_ERM", "Einschaltrückmeldung"
SYMBOL  I , 3, "F40_ESB", "Einschaltbereitschaft"
SYMBOL  I , 4, "F40_ERM", "Einschaltrückmeldung"
SYMBOL  I , 5, "V40_ESB", "Einschaltbereitschaft"
SYMBOL  I , 6, "V40_ERM", "Einschaltrückmeldung"
SYMBOL  I , 7, "S40_ESB", "Einschaltbereitschaft Feuerklappe"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 37, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "122976AC57CF4291922D0072B0B31380"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  30, 0, 1, 0, 2, 0
SYMBOL  I , 0, "S40_WEND", "Wegendschalter Feuerklappe"
SYMBOL  I , 1, "S40_THERMOSTAT", "Thermostat Feuerklappe"
SYMBOL  I , 2, "F5_ESB", "Einschaltbereitschaft Filtersteuergerät"
SYMBOL  I , 3, "F5_KONTAKT", "Kontakt Filtersteuergerät"
SYMBOL  I , 4, "V3_ESB", "Einschaltbereitschaft"
SYMBOL  I , 5, "V3_ERM", "Einschaltrückmeldung"
SYMBOL  I , 6, "Z2_ESB", "Einschaltbereitschaft"
SYMBOL  I , 7, "Z2_ERM1", "Einschaltrückmeldung"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 38, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "4C853610449F49B7A2AD5494AF5C1CF3"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  31, 0, 1, 0, 2, 0
SYMBOL  I , 0, "Z2_ERM2", "Einschaltrückmeldung"
SYMBOL  I , 1, "S2_ESB", "Einschaltbereitschaft"
SYMBOL  I , 2, "S2_WEND1", "Wegendschalter"
SYMBOL  I , 3, "S2_WEND2", "Wegendschalter"
SYMBOL  I , 4, "S2_1_ESB", "Einschaltbereitschaft"
SYMBOL  I , 5, "S2_1_WEND1", "Wegendschalter"
SYMBOL  I , 6, "S2_1_WEND2", "Wegendschalter"
SYMBOL  I , 7, "Z2_ES_DR", "Initiator Drehrichtung Rechts"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 39, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "877637A8465845798E79C7CEB927640F"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  32, 0, 1, 0, 2, 0
SYMBOL  I , 0, "F3_1_ESB1", "Sieb F3.1 Motor 1"
SYMBOL  I , 1, "F3_1_ERM1", "Sieb F3.1 Motor 1"
SYMBOL  I , 2, "E32.2", "Schutztürüberwachung 1=OK (Tür Zu)"
SYMBOL  I , 3, "Z2_FL1", "Funkenlöschanlage"
SYMBOL  I , 4, "Z2_FL2", "Funkenlöschanlage"
SYMBOL  I , 5, "F3_1_ESB2", "Sieb F3.1 Motor 2"
SYMBOL  I , 6, "F3_1_ERM2", "Sieb F3.1 Motor 2"
SYMBOL  I , 7, "Z2_FL5", "Funkenlöschanlage"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 40, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "808542877F0E4BAE87F2D6785FC137DA"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  33, 0, 1, 0, 2, 0
SYMBOL  I , 0, "B15_MIN", "Füllstandgrenzschalter"
SYMBOL  I , 1, "B15_MAX", "Füllstandgrenzschalter"
SYMBOL  I , 2, "B15_MAXMAX", "Füllstandgrenzschalter"
SYMBOL  I , 3, "RES_E33_3", ""
SYMBOL  I , 4, "H41_ESB", ""
SYMBOL  I , 5, "H41_ERM", ""
SYMBOL  I , 6, "RES_E33_6", ""
SYMBOL  I , 7, "RES_E33_7", ""
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 41, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "2388751ABD5F4CBCBBF7821C5A2995EF"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  34, 0, 1, 0, 2, 0
SYMBOL  I , 0, "S12-Q1_ESB", "S12 flap ESB"
SYMBOL  I , 1, "S12-S1_from_Z2", "S12-S1 limit switch from Z2"
SYMBOL  I , 2, "S12-S2_from_Hall2", "S12-S2 limit switch from Hall2"
SYMBOL  I , 3, "H26_ESB", "Screwconveyor Overload Switch"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 42, "75x-530 8DO/24V DC/0.5A", "8DA"
BEGIN 
  ASSET_ID "72EF261D5DC542A2924F73DD4C8B1841"
  SLAVE_CFG_DATA "01 00 20"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 02 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "5300"
  CREATOR ""
  COMMENT ""
LOCAL_OUT_ADDRESSES 
  ADDRESS  2, 0, 1, 0, 2, 0
SYMBOL  O , 0, "H8_EBE", "Einschaltbefehl"
SYMBOL  O , 1, "S13_C_EBE", "Diverter Product2 Direction Cmd"
SYMBOL  O , 2, "S13_P_EBE", "Diverter Product1 Direction Cmd"
SYMBOL  O , 3, "H24_3_EBE", "Einschaltbefehl"
SYMBOL  O , 4, "H24_4_EBE", "Einschaltbefehl"
SYMBOL  O , 5, "H27_EBE", "Einschaltbefehl"
SYMBOL  O , 6, "S4_EBE1", "Einschaltbefehl >B5"
SYMBOL  O , 7, "S4_EBE2", "Einschaltbefehl >H28"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 43, "75x-530 8DO/24V DC/0.5A", "8DA"
BEGIN 
  ASSET_ID "A91DD06A667B479F9B15CCA21B0B0074"
  SLAVE_CFG_DATA "01 00 20"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 02 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "5300"
  CREATOR ""
  COMMENT ""
LOCAL_OUT_ADDRESSES 
  ADDRESS  3, 0, 1, 0, 2, 0
SYMBOL  O , 0, "H12_EBE", "Einschaltbefehl"
SYMBOL  O , 1, "H13_EBE", "Einschaltbefehl"
SYMBOL  O , 2, "S3_EBE1", "Einschaltbefehl >H14"
SYMBOL  O , 3, "S3_EBE2", "Einschaltbefehl >H29"
SYMBOL  O , 4, "H14_EBE", "Einschaltbefehl"
SYMBOL  O , 5, "H15_2_EBE", "Einschaltbefehl (vormals S3.1)"
SYMBOL  O , 6, "A3.6", "Reserve (vormals S3.1)"
SYMBOL  O , 7, "H15_EBE", "Einschaltbefehl"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 44, "75x-530 8DO/24V DC/0.5A", "8DA"
BEGIN 
  ASSET_ID "0ABF4F3B453D47B9BB656DD01F533D43"
  SLAVE_CFG_DATA "01 00 20"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 02 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "5300"
  CREATOR ""
  COMMENT ""
LOCAL_OUT_ADDRESSES 
  ADDRESS  4, 0, 1, 0, 2, 0
SYMBOL  O , 0, "H16_EBE", "Einschaltbefehl"
SYMBOL  O , 1, "H17_EBE", "Einschaltbefehl"
SYMBOL  O , 2, "H18_EBE", "Einschaltbefehl"
SYMBOL  O , 3, "H25_1_EBE", "Einschaltbefehl >Close"
SYMBOL  O , 4, "H33_1_EBE", "Einschaltbefehl >Open"
SYMBOL  O , 5, "S12_EBE1_from_Z2", "Flap move (from Z2)"
SYMBOL  O , 6, "S12_EBE2_from_hall2", "Flap move (from Hall 2)"
SYMBOL  O , 7, "H43_EBE1", "Einschaltbefehl >H45"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 45, "75x-530 8DO/24V DC/0.5A", "8DA"
BEGIN 
  ASSET_ID "6B82F8CA8CA74DBF97E0FB827B3EC9CF"
  SLAVE_CFG_DATA "01 00 20"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 02 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "5300"
  CREATOR ""
  COMMENT ""
LOCAL_OUT_ADDRESSES 
  ADDRESS  5, 0, 1, 0, 2, 0
SYMBOL  O , 0, "H43_EBE2", "Einschaltbefehl >B15"
SYMBOL  O , 1, "H45_EBE", "Einschaltbefehl"
SYMBOL  O , 2, "S10_EBE1", "Einschaltbefehl >H46"
SYMBOL  O , 3, "S10_EBE2", "Einschaltbefehl >S11"
SYMBOL  O , 4, "S11_EBE1", "Einschaltbefehl >H43"
SYMBOL  O , 5, "S11_EBE2", "Einschaltbefehl >B16"
SYMBOL  O , 6, "H46_EBE", "Einschaltbefehl"
SYMBOL  O , 7, "S8_EBE1", "Einschaltbefehl >Close"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 46, "75x-530 8DO/24V DC/0.5A", "8DA"
BEGIN 
  ASSET_ID "624A4D5D99724F1B8032F765F4D39D65"
  SLAVE_CFG_DATA "01 00 20"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 02 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "5300"
  CREATOR ""
  COMMENT ""
LOCAL_OUT_ADDRESSES 
  ADDRESS  6, 0, 1, 0, 2, 0
SYMBOL  O , 0, "S8_EBE2", "Einschaltbefehl >Open"
SYMBOL  O , 1, "H44_EBE", "Einschaltbefehl"
SYMBOL  O , 2, "S9_EBE1", "Einschaltbefehl >H45"
SYMBOL  O , 3, "S9_EBE2", "Einschaltbefehl >B17"
SYMBOL  O , 4, "H47_EBE", "Einschaltbefehl"
SYMBOL  O , 5, "F7_EBE", "Einschaltbefehl"
SYMBOL  O , 6, "H23_EBE", "Einschaltbefehl"
SYMBOL  O , 7, "H24_EBE", "Einschaltbefehl H24  - FU über K1 Relais"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 47, "75x-530 8DO/24V DC/0.5A", "8DA"
BEGIN 
  ASSET_ID "97B88DBE25D048A394A363BF2297F7EC"
  SLAVE_CFG_DATA "01 00 20"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 02 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "5300"
  CREATOR ""
  COMMENT ""
LOCAL_OUT_ADDRESSES 
  ADDRESS  7, 0, 1, 0, 2, 0
SYMBOL  O , 0, "H25_EBE", "Einschaltbefehl"
SYMBOL  O , 1, "H19_EBE", "Einschaltbefehl H19  - FU über K1 Relais"
SYMBOL  O , 2, "H28_EBE", "Einschaltbefehl"
SYMBOL  O , 3, "H29_EBE", "Einschaltbefehl"
SYMBOL  O , 4, "S5_EBE1", "Einschaltbefehl >B10"
SYMBOL  O , 5, "S5_EBE2", "Einschaltbefehl >B7"
SYMBOL  O , 6, "H3012_EBE", "Einschaltbefehl H30/H31/H32  - FU über K1 Relais"
SYMBOL  O , 7, "H33_EBE", "Einschaltbefehl"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 48, "75x-530 8DO/24V DC/0.5A", "8DA"
BEGIN 
  ASSET_ID "613CB4313E5E49C1B27B24C5C1FCAEFA"
  SLAVE_CFG_DATA "01 00 20"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 02 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "5300"
  CREATOR ""
  COMMENT ""
LOCAL_OUT_ADDRESSES 
  ADDRESS  8, 0, 1, 0, 2, 0
SYMBOL  O , 0, "H34_EBE", "Einschaltbefehl"
SYMBOL  O , 1, "H38_EBE", "Einschaltbefehl"
SYMBOL  O , 2, "H29_1_EBE", "Einschaltbefehl"
SYMBOL  O , 3, "H42_EBE", "Einschaltbefehl"
SYMBOL  O , 4, "H15_1_EBE", "Einschaltbefehl (vormals S6)"
SYMBOL  O , 5, "A8.5", "Reserve (vormals S6)"
SYMBOL  O , 6, "S7_EBE1", "Einschaltbefehl >Close"
SYMBOL  O , 7, "S7_EBE2", "Einschaltbefehl >Open"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 49, "75x-530 8DO/24V DC/0.5A", "8DA"
BEGIN 
  ASSET_ID "482762D38A01466F82BEBBE9BCD7CE79"
  SLAVE_CFG_DATA "01 00 20"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 02 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "5300"
  CREATOR ""
  COMMENT ""
LOCAL_OUT_ADDRESSES 
  ADDRESS  9, 0, 1, 0, 2, 0
SYMBOL  O , 0, "S14_EBE1", "Einschaltbefehl >B14"
SYMBOL  O , 1, "S14_EBE2", "Einschaltbefehl >H45"
SYMBOL  O , 2, "S14_1_EBE1", "Einschaltbefehl >Close"
SYMBOL  O , 3, "S14_1_EBE2", "Einschaltbefehl >Open"
SYMBOL  O , 4, "H35_EBE", "Einschaltbefehl"
SYMBOL  O , 5, "H36_EBE", "Einschaltbefehl"
SYMBOL  O , 6, "S36_1_EBE", "Einschaltbefehl Dampf öffnen"
SYMBOL  O , 7, "H24_1_EBE", "Einschaltbefehl H24.1  - FU über K1 Relais"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 50, "75x-530 8DO/24V DC/0.5A", "8DA"
BEGIN 
  ASSET_ID "9689FEE6F4AC46FC931F7AAD6D19F02E"
  SLAVE_CFG_DATA "01 00 20"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 02 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "5300"
  CREATOR ""
  COMMENT ""
LOCAL_OUT_ADDRESSES 
  ADDRESS  10, 0, 1, 0, 2, 0
SYMBOL  O , 0, "H27_1_EBE", "Einschaltbefehl H27.1  - FU über K1 Relais"
SYMBOL  O , 1, "H24_2_EBE", "Einschaltbefehl - Fremdlüfter H24.1"
SYMBOL  O , 2, "H27_2_EBE", "Einschaltbefehl - Fremdlüfter H27.1"
SYMBOL  O , 3, "H40_EBE", "Einschaltbefehl"
SYMBOL  O , 4, "H40_1_EBE", "Einschaltbefehl"
SYMBOL  O , 5, "H40_2_EBE", "Einschaltbefehl"
SYMBOL  O , 6, "F40_EBE", "Einschaltbefehl"
SYMBOL  O , 7, "V40_EBE", "Einschaltbefehl"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 51, "75x-530 8DO/24V DC/0.5A", "8DA"
BEGIN 
  ASSET_ID "2FBB72394837480091189DBEE4277534"
  SLAVE_CFG_DATA "01 00 20"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 02 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "5300"
  CREATOR ""
  COMMENT ""
LOCAL_OUT_ADDRESSES 
  ADDRESS  11, 0, 1, 0, 2, 0
SYMBOL  O , 0, "S40_EBE", "Einschaltbefehl Feuerklappe"
SYMBOL  O , 1, "F5_START_FERN", "Filtersteuergerät Fernstart"
SYMBOL  O , 2, "V3_EBE", "Einschaltbefehl"
SYMBOL  O , 3, "H26_P_EBE", "Screwconveyor Start Cmd Product1 Direction"
SYMBOL  O , 4, "H26_C_EBE", "Screwconveyor Start Cmd Product2 Direction"
SYMBOL  O , 5, "S2_EBE", "Einschaltbefehl"
SYMBOL  O , 6, "S2_1_EBE", "Einschaltbefehl"
SYMBOL  O , 7, "Z2_SSW_R", "Stillstandswächter Fehler Reset"
END 

DPSUBSYSTEM 1, DPADDRESS 10, SLOT 52, "75x-530 8DO/24V DC/0.5A", "8DA"
BEGIN 
  ASSET_ID "5A4BDD2395C24495B0DA410E500170BD"
  SLAVE_CFG_DATA "01 00 20"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 02 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "5300"
  CREATOR ""
  COMMENT ""
LOCAL_OUT_ADDRESSES 
  ADDRESS  12, 0, 1, 0, 2, 0
SYMBOL  O , 0, "FRG_AN_VECOPLAN", "Freigabe an Vecoplan D1"
SYMBOL  O , 1, "FRG_AN_VECOPLAN_2", "Freigabe an Vecoplan H11"
SYMBOL  O , 2, "F3_1_EBE1", "Sieb F3_1 Motor 1"
SYMBOL  O , 3, "F3_1_EBE2", "Sieb F3_1 Motor 2"
SYMBOL  O , 4, "H41_EBE", ""
SYMBOL  O , 5, "F5-Enable", "-F5-Enable"
SYMBOL  O , 6, "F5-post-clean", "-F5-post.clean"
SYMBOL  O , 7, "HUP", "Anfahrhupe"
END 

DPSUBSYSTEM 1, DPADDRESS 12, "B757_S23.GSG", "Hackschnitzel"
BEGIN
  ASSET_ID "EA78EBD1DF3C4F90AE8754F6D131A386"
  PNO_IDENT_NO "46935"
  WD_ON "0"
  PDM_PARAM "0"
  CBA_USAGE "0"
  GROUP_IDENT "0"
  NORMSLAVE_DP_MODE "0"
  OBJECT_REMOVEABLE "1"
  NORMSLAVE_PARAM_DATA "49 00 44 00 00 00 00 00 00 03 00 C3 40 00 00 00 01 00 00 00 00 80 2B 00 20 6B 00 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 02 00 23 02 00 23 02 00 20 43 11 06 20 83 00 00 00 00 00 00 00 00"
  POS_X "390"
  GATEWAY_COMMENT ""
  POS_Y "55"
  SIZE_X "78"
  SIZE_Y "64"
  MODULE_ADD_FLAGS "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  CREATOR ""
  COMMENT ""
  PHYSICAL_INTERFACE "0"
  CIR_STATE "0"
LOCAL_IN_ADDRESSES 
  ADDRESS  8188, 0, 0, 0, 2, 0
END

DPSUBSYSTEM 1, DPADDRESS 12, SLOT 1, "750-343 Kein Prozessdatenkanal", "0"
BEGIN 
  ASSET_ID "234B02B13FDE4ADD9EAB99446246BD29"
  SLAVE_CFG_DATA "01 00 00"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 80 2B 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "3430"
  CREATOR ""
  COMMENT ""
END 

DPSUBSYSTEM 1, DPADDRESS 12, SLOT 2, "75x-493 3AI/3-Phasen-Messung", "6AX"
BEGIN 
  ASSET_ID "196998B237574973A859CBD53DBD1889"
  SLAVE_CFG_DATA "01 00 F5"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "04 00 20 6B 00 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4930"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  322, 0, 12, 0, 7, 0
LOCAL_OUT_ADDRESSES 
  ADDRESS  322, 0, 12, 0, 7, 0
SYMBOL  I , 0, "Hack_Wago_493_PEW   322", ""
SYMBOL  I , 2, "Hack_Wago_493_PEW   324", ""
SYMBOL  I , 4, "Hack_Wago_493_PEW   326", ""
SYMBOL  I , 6, "Hack_Wago_493_PEW   328", ""
SYMBOL  I , 8, "Hack_Wago_493_PEW   330", ""
SYMBOL  I , 10, "Hack_Wago_493_PEW   332", ""
SYMBOL  O , 0, "Hack_Wago_493_PAW   322", ""
SYMBOL  O , 2, "Hack_Wago_493_PAW   324", ""
SYMBOL  O , 4, "Hack_Wago_493_PAW   326", ""
SYMBOL  O , 6, "Hack_Wago_493_PAW   328", ""
SYMBOL  O , 8, "Hack_Wago_493_PAW   330", ""
SYMBOL  O , 10, "Hack_Wago_493_PAW   332", ""
END 

DPSUBSYSTEM 1, DPADDRESS 12, SLOT 3, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "C4EB5D654892432CA8CFBA27399F0ECE"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  50, 0, 1, 0, 2, 0
SYMBOL  I , 0, "HS_HACK", "Hauptschalter Schaltschrank Kollermühle OK -1Q1"
SYMBOL  I , 1, "STSP_HACK_24V", "Steuerspannung Schaltschrank Kollermühle -L60.3 vorhanden"
SYMBOL  I , 2, "STSP_HACK_INT", "Steuerspannung Schaltschrank Kollermühle Intern vorhanden -L60.4-F1"
SYMBOL  I , 3, "STSP_HACK_EXT", "Steuerspannung Schaltschrank Kollermühle Extern vorhanden -L60.5-F2"
SYMBOL  I , 4, "NA_HACK_INT", "Not-Aus Schaltschrank Kollermühle Intern betätigt -3S1"
SYMBOL  I , 5, "NA_HACK_EXT1", "Not-Aus Schaltschrank Kollermühle Extern 1 betätigt -3S2"
SYMBOL  I , 6, "NA_HACK_EXT2", "Not-Aus Schaltschrank Kollermühle Extern 2 betätigt -3S3"
SYMBOL  I , 7, "F50_ESB_FU", "Vibrorinne vor Z1 FU OK"
END 

DPSUBSYSTEM 1, DPADDRESS 12, SLOT 4, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "EF3D9F603C67416FBB9360728C4BFA3B"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  51, 0, 1, 0, 2, 0
SYMBOL  I , 0, "P1_ESB", "Pumpe Umlaufschmierung Z1 Motorschutz"
SYMBOL  I , 1, "P1_ERM", "Pumpe Umlaufschmierung Z1 Rückmeldung"
SYMBOL  I , 2, "F50_M1_ESB", "Vibrorinne vor Z1 Motor 1 Motorschutz"
SYMBOL  I , 3, "P2_ESB", "Hydraulikpumpe Spannmutter Z1 Motorschutz"
SYMBOL  I , 4, "P2_ERM", "Hydraulikpumpe Spannmutter Z1 Rückmeldung"
SYMBOL  I , 5, "F50_ERM_FU", "Vibrorinne vor Z1 Einschaltrückmeldung von FU"
SYMBOL  I , 6, "F50_M2_ESB", "Vibrorinne vor Z1 Motor 2 Motorschutz"
SYMBOL  I , 7, "S30.0_ESB", "Hydraulikventil Spannmutter Z1 lösen Motorschutz"
END 

DPSUBSYSTEM 1, DPADDRESS 12, SLOT 5, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "2DF9C604D2474226B67144D623028244"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  52, 0, 1, 0, 2, 0
SYMBOL  I , 0, "H56.1_ERM", "H56.1 agitator for B7.1 contactor"
SYMBOL  I , 1, "H56.1_ESB", "H56.1 agitator for B7.1 motor protection"
SYMBOL  I , 2, "H15_3_ERM", "H15.3 agitator for silo B6.1 contactor"
SYMBOL  I , 3, "H51.1_ESB", "Vor-Ort Taster Hydraulik Mutter spannen"
SYMBOL  I , 4, "V1_ERM", "Vor-Ort Taster Hydraulik Mutter entspannen"
SYMBOL  I , 5, "H15_3_ESB", "H15.3 agitator for B6.1 silo motor protection"
SYMBOL  I , 6, "P3_ERM", "Fettpumpe Zentralschmierung Z1 Rückmeldung"
SYMBOL  I , 7, "V1_ESB", "Fettpumpe Zentralschmierung Z1 Behälter leer"
END 

DPSUBSYSTEM 1, DPADDRESS 12, SLOT 6, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "C1D0986A9D8C45D49322F721A624EB3A"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  53, 0, 1, 0, 2, 0
SYMBOL  I , 0, "Flap_H4", "H4 flap too much material, 1=OK"
SYMBOL  I , 1, "H15_4_ESB", "H15.4 screw conveyor motor protection"
SYMBOL  I , 2, "Flap_H12", "H12 flap too much material, 1=OK"
SYMBOL  I , 3, "H3_ESB", "Zutransportschnecke Z1 Motorschutz"
SYMBOL  I , 4, "H3_ERM", "Zutransportschnecke Z1 Rückmeldung"
SYMBOL  I , 5, "H15_4_ERM", "H15.4 screw conveyor contactor"
SYMBOL  I , 6, "Z1_ESB", "Überlastrelais Mühle Z1"
SYMBOL  I , 7, "Z1_DOOR1", "Türschalter 1 Z1 1=offen"
END 

DPSUBSYSTEM 1, DPADDRESS 12, SLOT 7, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "EACB82985C4A42829D92C711EB28B343"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  54, 0, 1, 0, 2, 0
SYMBOL  I , 0, "Z1_DOOR2", "Türschalter 2 Z1 1=offen"
SYMBOL  I , 1, "Z1_DREHW", "Drehwächter Z1"
SYMBOL  I , 2, "Z1_A1_ERM", "Hauptantrieb Sanftanlauf Z1 Läuft"
SYMBOL  I , 3, "Z1_A1_BYPASS", "Hauptantrieb Sanftanlauf Z1 Bypass"
SYMBOL  I , 4, "Z1_A1_STOER", "Hauptantrieb Sanftanlauf Z1 Störung"
SYMBOL  I , 5, "Z1_F1_ESB", "Hauptantrieb NH Trenner offen 1=OK"
SYMBOL  I , 6, "Z1_TEMP", "Termistor Motor Hauptantrieb Z1"
SYMBOL  I , 7, "HACK_MESS_ESB", "Leistungsklemme 750-493 überwachung Motorschutz"
END 

DPSUBSYSTEM 1, DPADDRESS 12, SLOT 8, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "727F506B0ECB42FC9BE01F90C59A79A0"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  55, 0, 1, 0, 2, 0
SYMBOL  I , 0, "H4_ESB", "Zutransportschnecke Z1 Motorschutz"
SYMBOL  I , 1, "H4_ERM", "Zutransportschnecke Z1 Rückmeldung"
SYMBOL  I , 2, "H4_DREHW", "Zutransportschnecke Z1 Drehwächter"
SYMBOL  I , 3, "H4_UEBERF", "Zutransportschnecke Z1 Klappe geöffnet"
SYMBOL  I , 4, "H51.1_ERM", "Meldung 1 von Vecoplan"
SYMBOL  I , 5, "ST_VON_VECOPLAN_2", "Meldung 2 von Vecoplan"
SYMBOL  I , 6, "B7_MIN", "B7 Leer"
SYMBOL  I , 7, "B7_MAX", "B7 Voll"
END 

DPSUBSYSTEM 1, DPADDRESS 12, SLOT 9, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "B5921B0071DC4C09997C5798E41314AC"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  56, 0, 1, 0, 2, 0
SYMBOL  I , 0, "H50_ESB", "Einschaltbereitschaft"
SYMBOL  I , 1, "H50_ERM", "Einschaltrückmeldung"
SYMBOL  I , 2, "H51_ESB", "Einschaltbereitschaft"
SYMBOL  I , 3, "H51_ERM", "Einschaltrückmeldung"
SYMBOL  I , 4, "H52_ESB", "Einschaltbereitschaft"
SYMBOL  I , 5, "H52_ERM", "Einschaltrückmeldung"
SYMBOL  I , 6, "H53_ESB", "Einschaltbereitschaft"
SYMBOL  I , 7, "H53_ERM", "Einschaltrückmeldung"
END 

DPSUBSYSTEM 1, DPADDRESS 12, SLOT 10, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "CF723302697C4A0EBA060BABC05E65CF"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  57, 0, 1, 0, 2, 0
SYMBOL  I , 0, "H54_ESB", "Einschaltbereitschaft"
SYMBOL  I , 1, "H54_ERM", "Einschaltrückmeldung"
SYMBOL  I , 2, "H55_ESB", "Einschaltbereitschaft"
SYMBOL  I , 3, "H55_ERM", "Einschaltrückmeldung"
SYMBOL  I , 4, "H56_ESB", "Einschaltbereitschaft"
SYMBOL  I , 5, "H56_ERM", "Einschaltrückmeldung"
SYMBOL  I , 6, "B7_1_MIN", "B7.1 Leer"
SYMBOL  I , 7, "B7_1_MAX", "B7.1 Voll"
END 

DPSUBSYSTEM 1, DPADDRESS 12, SLOT 11, "75x-530 8DO/24V DC/0.5A", "8DA"
BEGIN 
  ASSET_ID "857D7DC68E93461883DA97FDB0379FC0"
  SLAVE_CFG_DATA "01 00 20"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 02 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "5300"
  CREATOR ""
  COMMENT ""
LOCAL_OUT_ADDRESSES 
  ADDRESS  50, 0, 1, 0, 2, 0
SYMBOL  O , 0, "P1_EBE", "Pumpe Umlaufschmierung Z1 Einschalten"
SYMBOL  O , 1, "P2_EBE", "Hydraulikpumpe Spannmutter Z1 Einschalten"
SYMBOL  O , 2, "F50_EBE", "Hydraulikventil Spannmutter Z1 lösen"
SYMBOL  O , 3, "H56.1_EBE", "H56.1 agitator for B7.1 enable operation"
SYMBOL  O , 4, "UNLOCK_DOOR_Z1", ""
SYMBOL  O , 5, "RESET_SOFTST_Z1", ""
SYMBOL  O , 6, "H3_EBE", "Zutransportschnecke Z1 Einschalten"
SYMBOL  O , 7, "Z1_EBE", "Hauptantrieb Sanftanlauf Z1 Einschalten"
END 

DPSUBSYSTEM 1, DPADDRESS 12, SLOT 12, "75x-530 8DO/24V DC/0.5A", "8DA"
BEGIN 
  ASSET_ID "8F2DE10FCA4D4DD989D4CDB3536AE5C5"
  SLAVE_CFG_DATA "01 00 20"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 02 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "5300"
  CREATOR ""
  COMMENT ""
LOCAL_OUT_ADDRESSES 
  ADDRESS  51, 0, 1, 0, 2, 0
SYMBOL  O , 0, "H4_EBE", "Zutransportschnecke Z1 Einschalten"
SYMBOL  O , 1, "ST_AN_VECOPLAN_1", "Befehl 1 an Vecoplan"
SYMBOL  O , 2, "V1_EBE", "Befehl 1 an Vecoplan"
SYMBOL  O , 3, "H15_3_EBE", "H15.3 agitator for silo B6.1 enable operation"
SYMBOL  O , 4, "H51.1_EBE", "Reserve"
SYMBOL  O , 5, "H15_4_EBE", "H15.4 screw conveyor enable operation"
SYMBOL  O , 6, "RES_A51.6", "Reserve"
SYMBOL  O , 7, "RES_A51.7", "Reserve"
END 

DPSUBSYSTEM 1, DPADDRESS 12, SLOT 13, "75x-530 8DO/24V DC/0.5A", "8DA"
BEGIN 
  ASSET_ID "D97F3AC176104FC09D7C8413587EEAE8"
  SLAVE_CFG_DATA "01 00 20"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 02 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "5300"
  CREATOR ""
  COMMENT ""
LOCAL_OUT_ADDRESSES 
  ADDRESS  52, 0, 1, 0, 2, 0
SYMBOL  O , 0, "H50_EBE", "Einschaltbefehl"
SYMBOL  O , 1, "H51_EBE", "Einschaltbefehl"
SYMBOL  O , 2, "H52_EBE", "Einschaltbefehl"
SYMBOL  O , 3, "H53_EBE", "Einschaltbefehl"
SYMBOL  O , 4, "H54_EBE", "Einschaltbefehl"
SYMBOL  O , 5, "H55_EBE", "Einschaltbefehl"
SYMBOL  O , 6, "H56_EBE", "Einschaltbefehl"
SYMBOL  O , 7, "Z1_FRG_DOOR", "Reserve"
END 

DPSUBSYSTEM 1, DPADDRESS 12, SLOT 14, "75x-453 4AI/0-20mA/SE", "4AE"
BEGIN 
  ASSET_ID "DB9BA574621542AF9B453F0FBC639F56"
  SLAVE_CFG_DATA "01 00 53"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "04 00 20 43 11 06"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4530"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  334, 0, 8, 0, 2, 0
SYMBOL  I , 0, "Z1_Diff_Press_PEW334", "Differential Pressure Sensor for Z1"
SYMBOL  I , 2, "Hack_PEW   336", ""
SYMBOL  I , 4, "Hack_PEW   338", ""
SYMBOL  I , 6, "Hack_PEW   340", ""
END 

DPSUBSYSTEM 1, DPADDRESS 12, SLOT 15, "75x-553 4AO/0-20mA", "4AA"
BEGIN 
  ASSET_ID "FF5CC33583974265B356F055C4860791"
  SLAVE_CFG_DATA "01 00 63"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "0A 00 20 83 00 00 00 00 00 00 00 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "5530"
  CREATOR ""
  COMMENT ""
LOCAL_OUT_ADDRESSES 
  ADDRESS  300, 0, 8, 0, 2, 0
SYMBOL  O , 0, "F50_N_SOLL", "Vibrorinne Aufgabe Z1"
END 

DPSUBSYSTEM 1, DPADDRESS 14, "B754_S34.GSG", "Presse 1"
BEGIN
  ASSET_ID "32B812D67651460A9D1A32D65CD8CE6B"
  PNO_IDENT_NO "46932"
  WD_ON "0"
  PDM_PARAM "0"
  CBA_USAGE "0"
  GROUP_IDENT "0"
  NORMSLAVE_DP_MODE "0"
  OBJECT_REMOVEABLE "1"
  NORMSLAVE_PARAM_DATA "44 00 C4 00 00 00 00 00 00 03 00 CB 40 00 00 00 01 00 00 00 00 80 21 00 20 6B 00 00 20 43 11 06 20 43 11 06 20 83 00 00 00 00 00 00 00 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 02 00 23 02 00"
  POS_X "475"
  GATEWAY_COMMENT ""
  POS_Y "55"
  SIZE_X "78"
  SIZE_Y "64"
  MODULE_ADD_FLAGS "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  CREATOR ""
  COMMENT ""
  PHYSICAL_INTERFACE "0"
  CIR_STATE "0"
LOCAL_IN_ADDRESSES 
  ADDRESS  8187, 0, 0, 0, 2, 0
END

DPSUBSYSTEM 1, DPADDRESS 14, SLOT 1, "750-333 Kein Prozessdatenkanal", "0"
BEGIN 
  ASSET_ID "8640CD8E773E43FAA519B46A568C5B3B"
  SLAVE_CFG_DATA "01 00 00"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 80 21 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "3330"
  CREATOR ""
  COMMENT ""
END 

DPSUBSYSTEM 1, DPADDRESS 14, SLOT 2, "75x-493 3AI/3-Phasen-Messung", "6AX"
BEGIN 
  ASSET_ID "5AF2EDB3524749E5BA9F5213B30CD42D"
  SLAVE_CFG_DATA "01 00 F5"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "04 00 20 6B 00 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4930"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  362, 0, 12, 0, 7, 0
LOCAL_OUT_ADDRESSES 
  ADDRESS  362, 0, 12, 0, 7, 0
SYMBOL  I , 0, "P1_Wago_493_PEW   362", ""
SYMBOL  I , 2, "P1_Wago_493_PEW   364", ""
SYMBOL  I , 4, "P1_Wago_493_PEW   366", ""
SYMBOL  I , 6, "P1_Wago_493_PEW   368", ""
SYMBOL  I , 8, "P1_Wago_493_PEW   370", ""
SYMBOL  I , 10, "P1_Wago_493_PEW   372", ""
SYMBOL  O , 0, "P1_Wago_493_PAW   362", ""
SYMBOL  O , 2, "P1_Wago_493_PAW   364", ""
SYMBOL  O , 4, "P1_Wago_493_PAW   366", ""
SYMBOL  O , 6, "P1_Wago_493_PAW   368", ""
SYMBOL  O , 8, "P1_Wago_493_PAW   370", ""
SYMBOL  O , 10, "P1_Wago_493_PAW   372", ""
END 

DPSUBSYSTEM 1, DPADDRESS 14, SLOT 3, "75x-453 4AI/0-20mA/SE", "4AE"
BEGIN 
  ASSET_ID "B044214614374FFCBA2103DE7044AB2B"
  SLAVE_CFG_DATA "01 00 53"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "04 00 20 43 11 06"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4530"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  374, 0, 8, 0, 2, 0
SYMBOL  I , 0, "P37_T_PRESSK", "Temperatur P37 Presskammer"
SYMBOL  I , 2, "P37_T_KOLLER1", "Temperatur P37 Koller 1"
SYMBOL  I , 4, "P37_T_KOLLER2", "Temperatur P37 Koller 2"
SYMBOL  I , 6, "P37_T_KOLLER3", "Temperatur P37 Koller 3"
END 

DPSUBSYSTEM 1, DPADDRESS 14, SLOT 4, "75x-453 4AI/0-20mA/SE", "4AE"
BEGIN 
  ASSET_ID "4F266FB1B8EA46B2B74FBAE5B935D108"
  SLAVE_CFG_DATA "01 00 53"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "04 00 20 43 11 06"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4530"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  382, 0, 8, 0, 2, 0
SYMBOL  I , 0, "H37_N_IST", "Istwert H37  - FU"
SYMBOL  I , 2, "RES_E384", "0-20"
SYMBOL  I , 4, "DURCHSATZ_WAAGE", "0-20 0-20t/h"
SYMBOL  I , 6, "RES_E388", "0-20"
END 

DPSUBSYSTEM 1, DPADDRESS 14, SLOT 5, "75x-553 4AO/0-20mA", "4AA"
BEGIN 
  ASSET_ID "53063BEDF6C643A9AF9B94C310DC94D5"
  SLAVE_CFG_DATA "01 00 63"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "0A 00 20 83 00 00 00 00 00 00 00 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "5530"
  CREATOR ""
  COMMENT ""
LOCAL_OUT_ADDRESSES 
  ADDRESS  374, 0, 8, 0, 2, 0
SYMBOL  O , 0, "H37_N_SOLL", "Sollwertvorgabe H37  - FU"
SYMBOL  O , 2, "RES_A376", "0-20"
SYMBOL  O , 4, "RES_A378", "0-20"
SYMBOL  O , 6, "RES_A380", "0-20"
END 

DPSUBSYSTEM 1, DPADDRESS 14, SLOT 6, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "25B068B6494F428890F6A432AD878441"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  70, 0, 1, 0, 2, 0
SYMBOL  I , 0, "STSP_P1_IN", "Steuerspannung vorhanden -L60.6-F4"
SYMBOL  I , 1, "STSP_P1_INT", "Steuerspannung Presse 1 Intern vorhanden -L60.7-F1"
SYMBOL  I , 2, "STSP_P1_EXT", "Steuerspannung Presse 1 Extern vorhanden -L60.8-F2"
SYMBOL  I , 3, "NA_P1_INT", "Not-Aus Presse 1 Intern betätigt -3S1"
SYMBOL  I , 4, "NA_P1_EXT1", "Not-Aus Presse 1 Extern 1 betätigt -3S2"
SYMBOL  I , 5, "NA_P1_EXT2", "Not-Aus Presse 1 Extern 2 betätigt -3S3"
SYMBOL  I , 6, "P1_HS", "Hauptschalter Presse 1 OK -1Q1"
SYMBOL  I , 7, "P1_MESS_ESB", "Einschaltbereitschaft Messung Presse 1 -4Q1"
END 

DPSUBSYSTEM 1, DPADDRESS 14, SLOT 7, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "2CD177E8240C4DAFA9842C7ACE10E144"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  71, 0, 1, 0, 2, 0
SYMBOL  I , 0, "P37_A1_RUN", "Läuft-Meldung Sanftanlauf P37-A1"
SYMBOL  I , 1, "P37_A1_BYPASS", "Bypass-Meldung Sanftanlauf P37-A1"
SYMBOL  I , 2, "P37_A1_FAULT", "Störung-Meldung Sanftanlauf P37-A1"
SYMBOL  I , 3, "P37_ESB", "Einschaltbereitschaft"
SYMBOL  I , 4, "P37_TERM", "Termistor"
SYMBOL  I , 5, "P37_1_A1_RUN", "Läuft-Meldung Sanftanlauf P37.1-A1"
SYMBOL  I , 6, "P37_1_A1_BYPASS", "Bypass-Meldung Sanftanlauf P37.1-A1"
SYMBOL  I , 7, "P37_1_A1_FAULT", "Störung-Meldung Sanftanlauf P37.1-A1"
END 

DPSUBSYSTEM 1, DPADDRESS 14, SLOT 8, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "BFEB24AC25AD487D97DECB055DB913F7"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  72, 0, 1, 0, 2, 0
SYMBOL  I , 0, "P37_1_ESB", "Einschaltbereitschaft"
SYMBOL  I , 1, "P37_1_TERM", "Termistor"
SYMBOL  I , 2, "P37_SSW", "Stillstandswächter 1=Stillstand"
SYMBOL  I , 3, "P37_DREHW", "Drehwächter"
SYMBOL  I , 4, "P37_OL", "Überlast/Overload"
SYMBOL  I , 5, "P37_DOOR", "Schutztürüberwachung 1=OK (Tür Zu)"
SYMBOL  I , 6, "H37_FU_FAULT", "Störung FU H37"
SYMBOL  I , 7, "H37_FU_RUN", "Läuft-Meldung FU H37"
END 

DPSUBSYSTEM 1, DPADDRESS 14, SLOT 9, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "46CA253FDEE841FFA3A3BABCBC2CAB7C"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  73, 0, 1, 0, 2, 0
SYMBOL  I , 0, "H37_ESB", "Motorschutz H37-Q1  - NC"
SYMBOL  I , 1, "H37_DREHW", "Drehwächter"
SYMBOL  I , 2, "H37_1_ESB", "Einschaltbereitschaft"
SYMBOL  I , 3, "H37_1_ERM", "Einschaltrückmeldung"
SYMBOL  I , 4, "H37_2_ESB", "Einschaltbereitschaft"
SYMBOL  I , 5, "H37_2_ERM", "Einschaltrückmeldung"
SYMBOL  I , 6, "S37_ESB", "Einschaltbereitschaft"
SYMBOL  I , 7, "S37_WEND1", "Wegendschalter"
END 

DPSUBSYSTEM 1, DPADDRESS 14, SLOT 10, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "FEC5C9175AB14FDA90C82A98ABD7B944"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  74, 0, 1, 0, 2, 0
SYMBOL  I , 0, "S37_WEND2", "Wegendschalter"
SYMBOL  I , 1, "S37_1_ESB", "Einschaltbereitschaft"
SYMBOL  I , 2, "S37_1_ERM", "Wegendschalter"
SYMBOL  I , 3, "S37_1_ZYKL", "Wegendschalter"
SYMBOL  I , 4, "P37_SSW_Y1", "Stillstandwächter Meldung Freigabe"
SYMBOL  I , 5, "P37_SSW_Y2", "Stillstandwächter Meldung Störung"
SYMBOL  I , 6, "S37_2_ERM", "Schmierung Fett nachfüllen zentrales Ventil"
SYMBOL  I , 7, "S37_2_MIN", "Schmierung Fett nachfüllen Min Tonne"
END 

DPSUBSYSTEM 1, DPADDRESS 14, SLOT 11, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "BC35951E4C3B46A1B72F40F31A5D829C"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  75, 0, 1, 0, 2, 0
SYMBOL  I , 0, "RES_E75_0", ""
SYMBOL  I , 1, "RES_E75_1", ""
SYMBOL  I , 2, "RES_E75_2", ""
SYMBOL  I , 3, "RES_E75_3", ""
SYMBOL  I , 4, "RES_E75_4", ""
SYMBOL  I , 5, "RES_E75_5", ""
SYMBOL  I , 6, "RES_E75_6", ""
SYMBOL  I , 7, "10KG_IMP_WAAGE", "10 Kg pro Impuls"
END 

DPSUBSYSTEM 1, DPADDRESS 14, SLOT 12, "75x-530 8DO/24V DC/0.5A", "8DA"
BEGIN 
  ASSET_ID "33BFB9B724F4429185068C5DDA83F542"
  SLAVE_CFG_DATA "01 00 20"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 02 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "5300"
  CREATOR ""
  COMMENT ""
LOCAL_OUT_ADDRESSES 
  ADDRESS  70, 0, 1, 0, 2, 0
SYMBOL  O , 0, "P37_EBE", "Einschaltbefehl"
SYMBOL  O , 1, "P37_1_EBE", "Einschaltbefehl"
SYMBOL  O , 2, "P37_SSW_RES", "Stillstandwächter Reset"
SYMBOL  O , 3, "H37_EBE", "Einschaltbefehl H37  - FU über K1 Relais"
SYMBOL  O , 4, "H37_1_EBE", "Einschaltbefehl"
SYMBOL  O , 5, "H37_2_EBE", "Einschaltbefehl"
SYMBOL  O , 6, "S37_EBE", "Einschaltbefehl"
SYMBOL  O , 7, "S37_1_EBE", "Einschaltbefehl"
END 

DPSUBSYSTEM 1, DPADDRESS 14, SLOT 13, "75x-530 8DO/24V DC/0.5A", "8DA"
BEGIN 
  ASSET_ID "B677F2FE299C4475AEF090A75B99CC90"
  SLAVE_CFG_DATA "01 00 20"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 02 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "5300"
  CREATOR ""
  COMMENT ""
LOCAL_OUT_ADDRESSES 
  ADDRESS  71, 0, 1, 0, 2, 0
SYMBOL  O , 0, "P37_SSW_STILL", "Stillstandswächter Stillstand"
SYMBOL  O , 1, "S37_2_EBE", "Schmierung Fett nachfüllen Tonne"
SYMBOL  O , 2, "RES_A71_2", ""
SYMBOL  O , 3, "RES_A71_3", ""
SYMBOL  O , 4, "RES_A71_4", ""
SYMBOL  O , 5, "RES_A71_5", ""
SYMBOL  O , 6, "RES_A71_6", ""
SYMBOL  O , 7, "FRG_WAAGE", "Freigeben der Waage"
END 

DPSUBSYSTEM 1, DPADDRESS 16, "B754_S34.GSG", "Presse 2"
BEGIN
  ASSET_ID "C1DA642DAB9A4A1290148970AA4244D8"
  PNO_IDENT_NO "46932"
  WD_ON "0"
  PDM_PARAM "0"
  CBA_USAGE "0"
  GROUP_IDENT "0"
  NORMSLAVE_DP_MODE "0"
  OBJECT_REMOVEABLE "1"
  NORMSLAVE_PARAM_DATA "44 00 C4 00 00 00 00 00 00 02 00 CB 40 00 00 00 01 00 00 00 00 80 21 00 20 6B 00 00 20 43 11 06 20 43 11 06 20 83 00 00 00 00 00 00 00 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 02 00 23 02 00"
  POS_X "561"
  GATEWAY_COMMENT ""
  POS_Y "55"
  SIZE_X "78"
  SIZE_Y "64"
  MODULE_ADD_FLAGS "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  CREATOR ""
  COMMENT ""
  PHYSICAL_INTERFACE "0"
  CIR_STATE "0"
LOCAL_IN_ADDRESSES 
  ADDRESS  8186, 0, 0, 0, 2, 0
END

DPSUBSYSTEM 1, DPADDRESS 16, SLOT 1, "750-333 Kein Prozessdatenkanal", "0"
BEGIN 
  ASSET_ID "B876041C16BF407EB5826364A1225A5E"
  SLAVE_CFG_DATA "01 00 00"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 80 21 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "3330"
  CREATOR ""
  COMMENT ""
END 

DPSUBSYSTEM 1, DPADDRESS 16, SLOT 2, "75x-493 3AI/3-Phasen-Messung", "6AX"
BEGIN 
  ASSET_ID "B3AADE0301564913BB2AC6186F7F26BD"
  SLAVE_CFG_DATA "01 00 F5"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "04 00 20 6B 00 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4930"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  412, 0, 12, 0, 7, 0
LOCAL_OUT_ADDRESSES 
  ADDRESS  412, 0, 12, 0, 7, 0
SYMBOL  I , 0, "P2_Wago_493_PEW   412", ""
SYMBOL  I , 2, "P2_Wago_493_PEW   414", ""
SYMBOL  I , 4, "P2_Wago_493_PEW   416", ""
SYMBOL  I , 6, "P2_Wago_493_PEW   418", ""
SYMBOL  I , 8, "P2_Wago_493_PEW   420", ""
SYMBOL  I , 10, "P2_Wago_493_PEW   422", ""
SYMBOL  O , 0, "P2_Wago_493_PAW   412", ""
SYMBOL  O , 2, "P2_Wago_493_PAW   414", ""
SYMBOL  O , 4, "P2_Wago_493_PAW   416", ""
SYMBOL  O , 6, "P2_Wago_493_PAW   418", ""
SYMBOL  O , 8, "P2_Wago_493_PAW   420", ""
SYMBOL  O , 10, "P2_Wago_493_PAW   422", ""
END 

DPSUBSYSTEM 1, DPADDRESS 16, SLOT 3, "75x-453 4AI/0-20mA/SE", "4AE"
BEGIN 
  ASSET_ID "36C88EB58D5B4938BB801E41A0931CB9"
  SLAVE_CFG_DATA "01 00 53"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "04 00 20 43 11 06"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4530"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  424, 0, 8, 0, 2, 0
SYMBOL  I , 0, "P39_T_PRESSK", "Temperatur P39 Presskammer"
SYMBOL  I , 2, "P39_T_KOLLER1", "Temperatur P39 Koller 1"
SYMBOL  I , 4, "P39_T_KOLLER2", "Temperatur P39 Koller 2"
SYMBOL  I , 6, "P39_T_KOLLER3", "Temperatur P39 Koller 3"
END 

DPSUBSYSTEM 1, DPADDRESS 16, SLOT 4, "75x-453 4AI/0-20mA/SE", "4AE"
BEGIN 
  ASSET_ID "9F91D64A9F694E16B1732EA1A9F3F6D9"
  SLAVE_CFG_DATA "01 00 53"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "04 00 20 43 11 06"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4530"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  432, 0, 8, 0, 2, 0
SYMBOL  I , 0, "H39_N_IST", "Istwert H39  - FU"
SYMBOL  I , 2, "P39_Vibration", "P39 vibration 0-20"
SYMBOL  I , 4, "H39.4_actual_speed", "Aroma FU conveyor actual speed 0-20"
SYMBOL  I , 6, "RES_E438", "0-20"
END 

DPSUBSYSTEM 1, DPADDRESS 16, SLOT 5, "75x-553 4AO/0-20mA", "4AA"
BEGIN 
  ASSET_ID "74E56095CAAD4EAB9C3B30E3247311DC"
  SLAVE_CFG_DATA "01 00 63"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "0A 00 20 83 00 00 00 00 00 00 00 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "5530"
  CREATOR ""
  COMMENT ""
LOCAL_OUT_ADDRESSES 
  ADDRESS  424, 0, 8, 0, 2, 0
SYMBOL  O , 0, "H39_N_SOLL", "Sollwertvorgabe H39  - FU"
SYMBOL  O , 2, "H39.4_setpoint", "aroma FU conveyor setpoint 0-20"
SYMBOL  O , 4, "RES_A428", "0-20"
SYMBOL  O , 6, "RES_A430", "0-20"
END 

DPSUBSYSTEM 1, DPADDRESS 16, SLOT 6, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "4115576299B942E880C3986B6810FAEE"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  90, 0, 1, 0, 2, 0
SYMBOL  I , 0, "STSP_P2_IN", "Steuerspannung vorhanden -L60.9-F4"
SYMBOL  I , 1, "STSP_P2_INT", "Steuerspannung Presse 2 Intern vorhanden -L61.0-F1"
SYMBOL  I , 2, "STSP_P2_EXT", "Steuerspannung Presse 2 Extern vorhanden -L61.1-F2"
SYMBOL  I , 3, "NA_P2_INT", "Not-Aus Presse 2 Intern betätigt -3S1"
SYMBOL  I , 4, "NA_P2_EXT1", "Not-Aus Presse 2 Extern 1 betätigt -3S2"
SYMBOL  I , 5, "NA_P2_EXT2", "Not-Aus Presse 2 Extern 2 betätigt -3S3"
SYMBOL  I , 6, "P2_HS", "Hauptschalter Presse 2 OK -1Q1"
SYMBOL  I , 7, "P2_MESS_ESB", "Einschaltbereitschaft Messung Presse 2 -4Q1"
END 

DPSUBSYSTEM 1, DPADDRESS 16, SLOT 7, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "4329C3550D1C4BB3AB315E48557AFA78"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  91, 0, 1, 0, 2, 0
SYMBOL  I , 0, "P39_A1_RUN", "Läuft-Meldung Sanftanlauf P39-A1"
SYMBOL  I , 1, "P39_A1_BYPASS", "Bypass-Meldung Sanftanlauf P39-A1"
SYMBOL  I , 2, "P39_A1_FAULT", "Störung-Meldung Sanftanlauf P39-A1"
SYMBOL  I , 3, "P39_ESB", "Einschaltbereitschaft"
SYMBOL  I , 4, "P39_TERM", "Termistor"
SYMBOL  I , 5, "P39_1_A1_RUN", "Läuft-Meldung Sanftanlauf P39.1-A1"
SYMBOL  I , 6, "P39_1_A1_BYPASS", "Bypass-Meldung Sanftanlauf P39.1-A1"
SYMBOL  I , 7, "P39_1_A1_FAULT", "Störung-Meldung Sanftanlauf P39.1-A1"
END 

DPSUBSYSTEM 1, DPADDRESS 16, SLOT 8, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "2D4C2E3BC63E4442BE220BECEAAAEE1F"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  92, 0, 1, 0, 2, 0
SYMBOL  I , 0, "P39_1_ESB", "Einschaltbereitschaft"
SYMBOL  I , 1, "P39_1_TERM", "Termistor"
SYMBOL  I , 2, "P39_SSW", "Stillstandswächter 1=Stillstand"
SYMBOL  I , 3, "P39_DREHW", "Drehwächter"
SYMBOL  I , 4, "P39_OL", "Überlast/Overload"
SYMBOL  I , 5, "P39_DOOR", "Schutztürüberwachung 1=OK (Tür Zu)"
SYMBOL  I , 6, "H39_FU_FAULT", "Störung FU H39"
SYMBOL  I , 7, "H39_FU_RUN", "Läuft-Meldung FU H39"
END 

DPSUBSYSTEM 1, DPADDRESS 16, SLOT 9, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "8E5015B6B6794A34A7D5972E40F09410"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  93, 0, 1, 0, 2, 0
SYMBOL  I , 0, "H39_ESB", "Motorschutz H39-Q1  - NC"
SYMBOL  I , 1, "H39_DREHW", "Drehwächter"
SYMBOL  I , 2, "H39_1_ESB", "Einschaltbereitschaft"
SYMBOL  I , 3, "H39_1_ERM", "Einschaltrückmeldung"
SYMBOL  I , 4, "H39_2_ESB", "Einschaltbereitschaft"
SYMBOL  I , 5, "H39_2_ERM", "Einschaltrückmeldung"
SYMBOL  I , 6, "S39_ESB", "Einschaltbereitschaft"
SYMBOL  I , 7, "S39_WEND1", "Wegendschalter"
END 

DPSUBSYSTEM 1, DPADDRESS 16, SLOT 10, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "4C0D4C181CD945819DB531120BC3D567"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  94, 0, 1, 0, 2, 0
SYMBOL  I , 0, "S39_WEND2", "Wegendschalter"
SYMBOL  I , 1, "S39_1_ESB", "Einschaltbereitschaft"
SYMBOL  I , 2, "S39_1_ERM", "Wegendschalter"
SYMBOL  I , 3, "S39_1_ZYKL", "Wegendschalter"
SYMBOL  I , 4, "P39_SSW_Y1", "Stillstandwächter Meldung Freigabe"
SYMBOL  I , 5, "P39_SSW_Y2", "Stillstandwächter Meldung Störung"
SYMBOL  I , 6, "H39.3_ESB", "Aroma agitator motor protection ESB"
SYMBOL  I , 7, "H39.3_ERM", "Aroma agitator contactor ERM"
END 

DPSUBSYSTEM 1, DPADDRESS 16, SLOT 11, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "4776F7F7DE494349BD519163C1DE9E2E"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  95, 0, 1, 0, 2, 0
SYMBOL  I , 0, "H39.4_FU_fault", "Aroma conveyor FU fault"
SYMBOL  I , 1, "H39.4_FU_runing", "Aroma conveyor FU is running"
SYMBOL  I , 2, "H39.4_ESB", "Aroma conveyor motor protection tripped"
SYMBOL  I , 3, "RES_E95_3", ""
SYMBOL  I , 4, "RES_E95_4", ""
SYMBOL  I , 5, "RES_E95_5", ""
SYMBOL  I , 6, "RES_E95_6", ""
SYMBOL  I , 7, "RES_E95_7", ""
END 

DPSUBSYSTEM 1, DPADDRESS 16, SLOT 12, "75x-530 8DO/24V DC/0.5A", "8DA"
BEGIN 
  ASSET_ID "00CB4421C59243E5922EB4415752A431"
  SLAVE_CFG_DATA "01 00 20"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 02 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "5300"
  CREATOR ""
  COMMENT ""
LOCAL_OUT_ADDRESSES 
  ADDRESS  90, 0, 1, 0, 2, 0
SYMBOL  O , 0, "P39_EBE", "Einschaltbefehl"
SYMBOL  O , 1, "P39_1_EBE", "Einschaltbefehl"
SYMBOL  O , 2, "P39_SSW_RES", "Stillstandwächter Reset"
SYMBOL  O , 3, "H39_EBE", "Einschaltbefehl H37  - FU über K1 Relais"
SYMBOL  O , 4, "H39_1_EBE", "Einschaltbefehl"
SYMBOL  O , 5, "H39_2_EBE", "Einschaltbefehl"
SYMBOL  O , 6, "S39_EBE", "Einschaltbefehl"
SYMBOL  O , 7, "S39_1_EBE", "Einschaltbefehl"
END 

DPSUBSYSTEM 1, DPADDRESS 16, SLOT 13, "75x-530 8DO/24V DC/0.5A", "8DA"
BEGIN 
  ASSET_ID "08F7BCF4BD4D4CA08FF5585E171BCDFB"
  SLAVE_CFG_DATA "01 00 20"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 02 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "5300"
  CREATOR ""
  COMMENT ""
LOCAL_OUT_ADDRESSES 
  ADDRESS  91, 0, 1, 0, 2, 0
SYMBOL  O , 0, "P39_SSW_STILL", "Stillstandswächter Stillstand"
SYMBOL  O , 1, "H93.3_EBE", "Aroma agitator enable/start"
SYMBOL  O , 2, "H39.4-FU-EBE", "Aroma FU conveyor enable/start"
SYMBOL  O , 3, "H39.4_FU_reset_fault", ""
SYMBOL  O , 4, "RES_A91_4", ""
SYMBOL  O , 5, "RES_A91_5", ""
SYMBOL  O , 6, "RES_A91_6", ""
SYMBOL  O , 7, "RES_A91_7", ""
END 

DPSUBSYSTEM 1, DPADDRESS 18, "B757_S23.GSG", "Tritec Presse"
BEGIN
  ASSET_ID "37F8B591165E427EB527F59CA11342B6"
  PNO_IDENT_NO "46935"
  WD_ON "0"
  PDM_PARAM "0"
  CBA_USAGE "0"
  GROUP_IDENT "0"
  NORMSLAVE_DP_MODE "0"
  OBJECT_REMOVEABLE "1"
  NORMSLAVE_PARAM_DATA "4F 00 44 00 00 00 00 00 00 02 00 C3 43 00 00 00 01 00 00 00 00 80 2B 00 20 83 00 00 00 00 00 00 00 00 20 43 11 06 20 4A 01 06 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 01 00 23 02 00 23 02 00 23 02 00"
  POS_X "601"
  GATEWAY_COMMENT ""
  POS_Y "153"
  SIZE_X "78"
  SIZE_Y "64"
  MODULE_ADD_FLAGS "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  CREATOR ""
  COMMENT ""
  PHYSICAL_INTERFACE "0"
  CIR_STATE "0"
LOCAL_IN_ADDRESSES 
  ADDRESS  8180, 0, 0, 0, 2, 0
END

DPSUBSYSTEM 1, DPADDRESS 18, SLOT 1, "750-343 Kein Prozessdatenkanal", "0"
BEGIN 
  ASSET_ID "C68DE793DCAA4A44ACBF094A1BD72359"
  SLAVE_CFG_DATA "01 00 00"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 80 2B 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "3430"
  CREATOR ""
  COMMENT ""
END 

DPSUBSYSTEM 1, DPADDRESS 18, SLOT 2, "75x-553 4AO/0-20mA", "4AA"
BEGIN 
  ASSET_ID "93A699769BEB4CE4976101AA3B5C23CD"
  SLAVE_CFG_DATA "01 00 63"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "0A 00 20 83 00 00 00 00 00 00 00 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "5530"
  CREATOR ""
  COMMENT ""
LOCAL_OUT_ADDRESSES 
  ADDRESS  440, 0, 8, 0, 2, 0
SYMBOL  O , 0, "H60_N_SOLL", "Sollwertvorgabe H60  - FU"
SYMBOL  O , 2, "1M14_N_soll", "1M14 - frecv, conv.  setpoint copied from H60"
END 

DPSUBSYSTEM 1, DPADDRESS 18, SLOT 3, "75x-453 4AI/0-20mA/SE", "4AE"
BEGIN 
  ASSET_ID "8AED737DB6A548E9AA9B226EBA15EF0A"
  SLAVE_CFG_DATA "01 00 53"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "04 00 20 43 11 06"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4530"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  300, 0, 8, 0, 2, 0
SYMBOL  I , 0, "RES_E300", "0-20"
SYMBOL  I , 2, "RES_E302", "0-20"
SYMBOL  I , 4, "RES_E304", "0-20"
SYMBOL  I , 6, "RES_E306", "0-20"
END 

DPSUBSYSTEM 1, DPADDRESS 18, SLOT 4, "75x-460 4AI/RTD", "4AE"
BEGIN 
  ASSET_ID "506EE4B9C076472EAF35B55C60E22876"
  SLAVE_CFG_DATA "01 00 53"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "04 00 20 4A 01 06"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4600"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  440, 0, 8, 0, 2, 0
SYMBOL  I , 0, "H60_N_IST", ""
SYMBOL  I , 2, "P62_I_IST", ""
END 

DPSUBSYSTEM 1, DPADDRESS 18, SLOT 5, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "017664CEE2A04581933523DBD6F82A69"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  150, 0, 1, 0, 2, 0
SYMBOL  I , 0, "P3_HS", "Hauptschalter Schrank Tritec Presse"
SYMBOL  I , 1, "STSP_P3_IN", "Steuerspannung vorhanden Tritec Presse"
SYMBOL  I , 2, "STSP_P3_INT", "Steuerspannung Presse 2 Intern vorhanden Tritec Presse"
SYMBOL  I , 3, "STSP_P3_EXT", "Steuerspannung Presse 2 Extern vorhanden Tritec Presse"
SYMBOL  I , 4, "NA_P3_INT", "Not-Aus Presse Tritec Presse Intern betätigt"
SYMBOL  I , 5, "NA_P3_EXT1", "Not-Aus Presse Tritec Presse Extern 1 betätigt"
SYMBOL  I , 6, "NA_P3_EXT2", "Not-Aus Presse Tritec Presse Extern 2 betätigt"
SYMBOL  I , 7, "E150.7", "Reserve"
END 

DPSUBSYSTEM 1, DPADDRESS 18, SLOT 6, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "66425A2AABBC4D9C85FEAB51362E0B45"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  151, 0, 1, 0, 2, 0
SYMBOL  I , 0, "H60_FU_FAULT", "FU Störung H60"
SYMBOL  I , 1, "H60_FU_ERM", "FU Läuft H60"
SYMBOL  I , 2, "H60_ESB", "Motorschutz H60"
SYMBOL  I , 3, "H60_DREHW", "Impulsdrehwächter H60"
SYMBOL  I , 4, "H60_UEBERF", "Stauklappe an H60"
SYMBOL  I , 5, "H61_ESB", "Motorschutz H61"
SYMBOL  I , 6, "H61_ERM", "H61 Läuft"
SYMBOL  I , 7, "P62_A1_RUN", "P62 Sanftstart gestartet"
END 

DPSUBSYSTEM 1, DPADDRESS 18, SLOT 7, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "486DC4B054E0443CAC06E17DF71C5E85"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  152, 0, 1, 0, 2, 0
SYMBOL  I , 0, "P62_A1_BYPASS", "P62 Sanftstart Bypass"
SYMBOL  I , 1, "P62_A1_FAULT", "P62 Sanftstart Fehler"
SYMBOL  I , 2, "P62_ESB", "P62 Sicherungstrenner gezogen"
SYMBOL  I , 3, "P62_THERM", "P62 Motor Thermistor"
SYMBOL  I , 4, "P62_DOOR", "P62 Tür offen"
SYMBOL  I , 5, "E152.5", "Reserve"
SYMBOL  I , 6, "P62_DREHW", "P62 Impulsdrehwächter"
SYMBOL  I , 7, "P62_OVERL", "P62 Überlastsicherung"
END 

DPSUBSYSTEM 1, DPADDRESS 18, SLOT 8, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "3B9279BF86C0418CAAC4F12636447FD5"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  153, 0, 1, 0, 2, 0
SYMBOL  I , 0, "P62_RESERVE", "P62 Reserve Schalter"
SYMBOL  I , 1, "P63_ESB", "P63 Fettpumpe Sicherung"
SYMBOL  I , 2, "P63_ERM", "P63 Fettpumpe Läuft"
SYMBOL  I , 3, "P63_MIN", "P63 Fettpumpe Behälter leer"
SYMBOL  I , 4, "P63_IMP", "P63 Fettpumpe Impuls vo Progressiv verteiler"
SYMBOL  I , 5, "S64_ESB", "S64 Klappe Sicherung"
SYMBOL  I , 6, "S64_WEND1", "S64 Klappe Richtung Kühler Groß"
SYMBOL  I , 7, "S64_WEND2", "S64 Klappe Richtung Kühler Klein"
END 

DPSUBSYSTEM 1, DPADDRESS 18, SLOT 9, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "B7311832E1274A80AA6EB82918E2B6BC"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  154, 0, 1, 0, 2, 0
SYMBOL  I , 0, "H65_ESB", "H65 Schnecke Motorschutz"
SYMBOL  I , 1, "H65_ERM", "H65 Schnecke Läuft"
SYMBOL  I , 2, "H65_DREHW", "H65 Impulsdrehwächter"
SYMBOL  I , 3, "H65_UEBERF", "H65 Stauklappe"
SYMBOL  I , 4, "H66_ESB", "H66 Motorschutz"
SYMBOL  I , 5, "H66_ERM", "H66 Läuft"
SYMBOL  I , 6, "H66_DREHW", "H66 Impulsdrehwächter"
SYMBOL  I , 7, "S67_ESB", "S67 Sicherung"
END 

DPSUBSYSTEM 1, DPADDRESS 18, SLOT 10, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "795F7CE571BE4FE3B098F76A17FE9EF8"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  155, 0, 1, 0, 2, 0
SYMBOL  I , 0, "S67_WEND1", "S67 Richtung Material Ausschleusen"
SYMBOL  I , 1, "S67_WEND2", "S67 Richtung Kühler klein"
SYMBOL  I , 2, "H68_ESB", "H68 Motorschutz"
SYMBOL  I , 3, "H68_ERM", "H68 Läuft"
SYMBOL  I , 4, "H68_DREHW", "H68 Impulsdrehwächter"
SYMBOL  I , 5, "S69_ESB", "S69 Sicherung"
SYMBOL  I , 6, "S69_WEND1", "S69 Auf"
SYMBOL  I , 7, "S69_WEND2", "S69 Mitte"
END 

DPSUBSYSTEM 1, DPADDRESS 18, SLOT 11, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "EBC93FC9C7D54772AF2DF82117108D04"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  156, 0, 1, 0, 2, 0
SYMBOL  I , 0, "S69_WEND3", "S69 Zu"
SYMBOL  I , 1, "S69_MAX", "S69 Kühler Max"
SYMBOL  I , 2, "S69_MAX_MAX", "S69 Kühler Max-Max"
SYMBOL  I , 3, "S69_RESERVE1", "S69 Reserve 1"
SYMBOL  I , 4, "S69_RESERVE2", "S69 Reserve 2"
SYMBOL  I , 5, "F70_ESB1", "F70 Motorschutz Motor 1"
SYMBOL  I , 6, "F70_ERM1", "F70 Läuft Motor 1"
SYMBOL  I , 7, "F70_ESB2", "F70 Motorschutz Motor 2"
END 

DPSUBSYSTEM 1, DPADDRESS 18, SLOT 12, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "178FE11D290D40638F81B94A6E65B698"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  157, 0, 1, 0, 2, 0
SYMBOL  I , 0, "F70_ERM2", "F70 Läuft Motor 2"
SYMBOL  I , 1, "H71_ESB", "H71 Motorschutz"
SYMBOL  I , 2, "H71_ERM", "H71 Läuft"
SYMBOL  I , 3, "H71_DREHW", "H71 Impulsdrehwächter"
SYMBOL  I , 4, "V73_ESB", "V73 Motorschutz"
SYMBOL  I , 5, "V73_ERM", "V73 Läuft"
SYMBOL  I , 6, "Z2N_A1_RUN", "Z2 90KW Motor Sanftstarter gestartet"
SYMBOL  I , 7, "Z2N_A1_BYPASS", "Z2 90KW Motor Sanftstarter Bypass"
END 

DPSUBSYSTEM 1, DPADDRESS 18, SLOT 13, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "7F4B0EE4F1084177A067CA7F32A5BFD7"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  158, 0, 1, 0, 2, 0
SYMBOL  I , 0, "Z2N_A1_FAULT", "Z2 90KW Motor Sanftstarter Fehler"
SYMBOL  I , 1, "Z2N_ESB", "Z2 90KW Motor Sanftstarter Sicherungstrenner"
SYMBOL  I , 2, "Z2N_THERM", "Z2 90KW Motor Thermistor"
SYMBOL  I , 3, "Z2N_ERM1", "Z2 90KW Motor Drehrichtung 1 läuft"
SYMBOL  I , 4, "Z2N_ERM2", "Z2 90KW Motor Drehrichtung 2 läuft"
SYMBOL  I , 5, "Z2N_DOOR", "Z2 90KW Motor Tür"
SYMBOL  I , 6, "Z2N_SSW", "Z2 90KW Motor Stillstandswächter"
SYMBOL  I , 7, "Z2N_ES_DR", "Z2 90KW Motor Einlaufklappe rechts"
END 

DPSUBSYSTEM 1, DPADDRESS 18, SLOT 14, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "72C7629D21B948C19EEC8EDB9FC6C331"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  159, 0, 1, 0, 2, 0
SYMBOL  I , 0, "Z2N_ES_DL", "Z2 90KW Motor Einlaufklappe links"
SYMBOL  I , 1, "1M18_ERM", "CatLitter Section 1M18 Started (ERM)"
SYMBOL  I , 2, "1M24_ERM", "CatLitter Section 1M24 Started (ERM)"
SYMBOL  I , 3, "E159.3", "Reserve im Schrank Tritec Presse"
SYMBOL  I , 4, "E159.4", "Reserve im Schrank Tritec Presse"
SYMBOL  I , 5, "E159.5", "Reserve im Schrank Tritec Presse"
SYMBOL  I , 6, "E159.6", "Reserve im Schrank Tritec Presse"
SYMBOL  I , 7, "E159.7", "Reserve im Schrank Tritec Presse"
END 

DPSUBSYSTEM 1, DPADDRESS 18, SLOT 15, "75x-530 8DO/24V DC/0.5A", "8DA"
BEGIN 
  ASSET_ID "3FB5517FC29D4CE8B03D660A1F122A2F"
  SLAVE_CFG_DATA "01 00 20"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 02 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "5300"
  CREATOR ""
  COMMENT ""
LOCAL_OUT_ADDRESSES 
  ADDRESS  150, 0, 1, 0, 2, 0
SYMBOL  O , 0, "H60_EBE", "H60 Starten"
SYMBOL  O , 1, "H61_EBE", "H61 Starten"
SYMBOL  O , 2, "P62_EBE", "P62 Starten"
SYMBOL  O , 3, "P62_DOOR_FRG", "P62 Tür öffnen"
SYMBOL  O , 4, "P63_EBE", "P63 Fettpumpe Starten"
SYMBOL  O , 5, "S64_EBE", "S64 Klappe Umfahren"
SYMBOL  O , 6, "H65_EBE", "H65 Starten"
SYMBOL  O , 7, "H66_EBE", "H66 Starten"
END 

DPSUBSYSTEM 1, DPADDRESS 18, SLOT 16, "75x-530 8DO/24V DC/0.5A", "8DA"
BEGIN 
  ASSET_ID "3D49F91E56954749BA132E5998F331CD"
  SLAVE_CFG_DATA "01 00 20"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 02 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "5300"
  CREATOR ""
  COMMENT ""
LOCAL_OUT_ADDRESSES 
  ADDRESS  151, 0, 1, 0, 2, 0
SYMBOL  O , 0, "S67_EBE", "S67 Klappe Umfahren"
SYMBOL  O , 1, "H68_EBE", "H68 Starten"
SYMBOL  O , 2, "S69_EBE", "S69 Starten Kühler entleeren"
SYMBOL  O , 3, "F70_EBE1", "F70 Motor 1 Starten"
SYMBOL  O , 4, "F70_EBE2", "F70 Motor 2 Starten"
SYMBOL  O , 5, "H71_EBE", "H71 Starten"
SYMBOL  O , 6, "V73_EBE", "V73 Starten"
SYMBOL  O , 7, "Z2N_EBE", "Z2 90KW Motor Sanftanlauf Starten"
END 

DPSUBSYSTEM 1, DPADDRESS 18, SLOT 17, "75x-530 8DO/24V DC/0.5A", "8DA"
BEGIN 
  ASSET_ID "89ECCD96FAAA40D88CA6D4160A9CB5A6"
  SLAVE_CFG_DATA "01 00 20"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 02 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "5300"
  CREATOR ""
  COMMENT ""
LOCAL_OUT_ADDRESSES 
  ADDRESS  152, 0, 1, 0, 2, 0
SYMBOL  O , 0, "Z2N_EBE1", "Z2 90KW Motor Rechtslauf Schütz Starten"
SYMBOL  O , 1, "Z2N_EBE2", "Z2 90KW Motor Linkslauf Schütz Starten"
SYMBOL  O , 2, "Z2N_SSW_R", "Z2 Stillstandswächter reset"
SYMBOL  O , 3, "Start.to.1M14", "Start to 1M14 condition for Product2 Litter"
SYMBOL  O , 4, "Start to 1M25", ""
SYMBOL  O , 5, "H25_runs_(for_Cat_Litter", "Reserve Ausgang Tritec Presse"
SYMBOL  O , 6, "A152.6", "Reserve Ausgang Tritec Presse"
SYMBOL  O , 7, "A152.7", "Reserve Ausgang Tritec Presse"
END 

DPSUBSYSTEM 1, DPADDRESS 20, "B756_S33.GSG", "Aco"
BEGIN
  ASSET_ID "6A8EF2E98C2A4AD6B573088AA0E96AAC"
  PNO_IDENT_NO "46934"
  WD_ON "0"
  PDM_PARAM "0"
  CBA_USAGE "0"
  GROUP_IDENT "0"
  NORMSLAVE_DP_MODE "0"
  OBJECT_REMOVEABLE "1"
  NORMSLAVE_PARAM_DATA "19 00 C4 00 00 00 00 00 00 03 00 C3 40 C3 7F 02 01 00 00 00 00 80 21 00 60 D7 00"
  POS_X "644"
  GATEWAY_COMMENT ""
  POS_Y "56"
  SIZE_X "78"
  SIZE_Y "64"
  MODULE_ADD_FLAGS "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  CREATOR ""
  COMMENT ""
  PHYSICAL_INTERFACE "0"
  CIR_STATE "0"
LOCAL_IN_ADDRESSES 
  ADDRESS  8184, 0, 0, 0, 2, 0
END

DPSUBSYSTEM 1, DPADDRESS 20, SLOT 1, "750-833 Kein Prozessdatenkanal", "0"
BEGIN 
  ASSET_ID "A8448FE331FA457FA27FCB322D1EEC8D"
  SLAVE_CFG_DATA "01 00 00"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 80 21 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "8330"
  CREATOR ""
  COMMENT ""
END 

DPSUBSYSTEM 1, DPADDRESS 20, SLOT 2, "PFC 75x-653 RS485-Interface", "0"
BEGIN 
  ASSET_ID "6D85F2646BD842DE818DE4715B85C271"
  SLAVE_CFG_DATA "01 00 00"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 60 D7 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "6532"
  CREATOR ""
  COMMENT ""
END 

DPSUBSYSTEM 1, DPADDRESS 20, SLOT 3, "10 Byte PFC-Eing. (Integer16)", "129"
BEGIN 
  ASSET_ID "4D61D3DABB8E40E9B5DB87F9C360A287"
  SLAVE_CFG_DATA "03 00 81 89 22"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "00 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "853"
  CREATOR ""
  COMMENT ""
LOCAL_OUT_ADDRESSES 
  ADDRESS  512, 0, 10, 0, 9, 0
END 

DPSUBSYSTEM 1, DPADDRESS 20, SLOT 4, "28 Byte PFC-Ausg. (Integer16)", "65"
BEGIN 
  ASSET_ID "57A7F8E557B8400AAA8147FB5502DF8E"
  SLAVE_CFG_DATA "03 00 41 9B 22"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "00 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "1278"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  512, 0, 28, 0, 8, 0
END 

DPSUBSYSTEM 1, DPADDRESS 22, "B757_S23.GSG", "Fluidspiele"
BEGIN
  ASSET_ID "0DC832AE675A4B059AA76A6710F07ED4"
  PNO_IDENT_NO "46935"
  WD_ON "0"
  PDM_PARAM "0"
  CBA_USAGE "0"
  GROUP_IDENT "0"
  NORMSLAVE_DP_MODE "0"
  OBJECT_REMOVEABLE "1"
  NORMSLAVE_PARAM_DATA "3A 00 44 00 00 00 00 00 00 03 00 C3 40 00 00 00 01 00 00 00 00 80 2B 00 20 83 00 00 00 00 00 00 00 00 20 76 01 00 20 76 01 00 23 01 00 23 01 00 23 02 00 23 02 00 20 02 00 20 02 00"
  POS_X "727"
  GATEWAY_COMMENT ""
  POS_Y "55"
  SIZE_X "78"
  SIZE_Y "64"
  MODULE_ADD_FLAGS "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  CREATOR ""
  COMMENT ""
  PHYSICAL_INTERFACE "0"
  CIR_STATE "0"
LOCAL_IN_ADDRESSES 
  ADDRESS  8183, 0, 0, 0, 2, 0
END

DPSUBSYSTEM 1, DPADDRESS 22, SLOT 1, "750-343 Kein Prozessdatenkanal", "0"
BEGIN 
  ASSET_ID "9DE79018E3704E75B201E2CA954CF12C"
  SLAVE_CFG_DATA "01 00 00"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 80 2B 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "3430"
  CREATOR ""
  COMMENT ""
END 

DPSUBSYSTEM 1, DPADDRESS 22, SLOT 2, "75x-553 4AO/0-20mA", "4AA"
BEGIN 
  ASSET_ID "DB6346958FEC4F8B96DED30D21FEDB3F"
  SLAVE_CFG_DATA "01 00 63"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "0A 00 20 83 00 00 00 00 00 00 00 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "5530"
  CREATOR ""
  COMMENT ""
LOCAL_OUT_ADDRESSES 
  ADDRESS  572, 0, 8, 0, 2, 0
SYMBOL  O , 0, "Fluid AO0-20 PAW   572", "Propventil Betonsilo"
SYMBOL  O , 2, "Fluid AO0-20 PAW   574", "Propventil Brikettseite"
SYMBOL  O , 4, "Fluid AO0-20 PAW   576", "Reserve"
SYMBOL  O , 6, "Fluid AO0-20 PAW   578", "Reserve"
END 

DPSUBSYSTEM 1, DPADDRESS 22, SLOT 3, "75x-404 V/R-Zaehler", "3AX"
BEGIN 
  ASSET_ID "E608A2137FF0409992EE5710F3778446"
  SLAVE_CFG_DATA "01 00 F2"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "04 00 20 76 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4040"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  560, 0, 6, 0, 7, 0
LOCAL_OUT_ADDRESSES 
  ADDRESS  560, 0, 6, 0, 7, 0
SYMBOL  I , 0, "Fluid Durchfl PEW   560", "STATW Durchflussmessung Betonsilo"
SYMBOL  O , 0, "Fluid Durchfl PAW   560", "STW Durchflussmesser Betonsilo"
SYMBOL  O , 2, "Fluid Durchfl PAW   562", "STW Durchflussmesser Betonsilo"
SYMBOL  O , 4, "Fluid Durchfl PAW   564", "STW Durchflussmesser Betonsilo"
END 

DPSUBSYSTEM 1, DPADDRESS 22, SLOT 4, "75x-404 V/R-Zaehler", "3AX"
BEGIN 
  ASSET_ID "EF0C844154AB48018233AE95B6C9F119"
  SLAVE_CFG_DATA "01 00 F2"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "04 00 20 76 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4040"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  566, 0, 6, 0, 7, 0
LOCAL_OUT_ADDRESSES 
  ADDRESS  566, 0, 6, 0, 7, 0
SYMBOL  I , 0, "Fluid Durchfl PEW   566", "STATW Durchflussmessung Brikettseite"
SYMBOL  O , 0, "Fluid Durchfl PAW   566", "STW Durchflussmesser Brikettseite"
SYMBOL  O , 2, "Fluid Durchfl PAW   568", "STW Durchflussmesser Brikettseite"
SYMBOL  O , 4, "Fluid Durchfl PAW   570", "STW Durchflussmesser Brikettseite"
END 

DPSUBSYSTEM 1, DPADDRESS 22, SLOT 5, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "5D0C1332A1A446038E5F3353790BD829"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  110, 0, 1, 0, 2, 0
SYMBOL  I , 0, "Fluid E     110.0", "Stauklappe H18"
SYMBOL  I , 1, "Fluid E     110.1", "Stauklappe H14"
SYMBOL  I , 2, "Fluid E     110.2", "Stauklappe H43"
SYMBOL  I , 3, "Fluid E     110.3", "Stauklappe H29"
SYMBOL  I , 4, "Fluid E     110.4", "Stauklappe H25"
SYMBOL  I , 5, "Fluid E     110.5", "Stauklappe H44"
SYMBOL  I , 6, "Fluid E     110.6", "Stauklappe H46"
SYMBOL  I , 7, "Fluid E     110.7", "Reserve"
END 

DPSUBSYSTEM 1, DPADDRESS 22, SLOT 6, "75x-430 8DI/24V DC/3.0ms", "8DE"
BEGIN 
  ASSET_ID "7ED67AEFAA2A427894CCBCCE6EAA8544"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "30"
  POS_Y "30"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4300"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  111, 0, 1, 0, 2, 0
SYMBOL  I , 0, "Fluid E     111.0", "Handbedienung Bigpack Oeffnen"
SYMBOL  I , 1, "Fluid E     111.1", "Handbedienung Bigpack Schliessen"
SYMBOL  I , 2, "Min Fluid E     111.2", "Trockenlauf Relais Fluidtank 1=OK"
SYMBOL  I , 3, "Max Fluid E     111.3", "Warnung Relais Fluidtank 1=OK"
SYMBOL  I , 4, "Fluid E     111.4", "Nachfüllen Fluidtank 1=Nachfüllen"
SYMBOL  I , 5, "Fluid E     111.5", "Störung Brunnenpumpe"
SYMBOL  I , 6, "Fluid E     111.6", "Reserve"
SYMBOL  I , 7, "Fluid E     111.7", "Reserve"
END 

DPSUBSYSTEM 1, DPADDRESS 22, SLOT 7, "75x-530 8DO/24V DC/0.5A", "8DA"
BEGIN 
  ASSET_ID "B8E4F6914A8B46A89C1142A9F026B684"
  SLAVE_CFG_DATA "01 00 20"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 02 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "5300"
  CREATOR ""
  COMMENT ""
LOCAL_OUT_ADDRESSES 
  ADDRESS  110, 0, 1, 0, 2, 0
SYMBOL  O , 0, "Well Water     110.0", "Start Brunnenpumpe ( well water )"
SYMBOL  O , 1, "Fluid A     110.1", "Reserve"
SYMBOL  O , 2, "City Water     110.2", "Start Water from the City ( valve )"
SYMBOL  O , 3, "Fluid A     110.3", "Reserve"
SYMBOL  O , 4, "Fluid A     110.4", "Reserve"
SYMBOL  O , 5, "Fluid A     110.5", "Reserve"
SYMBOL  O , 6, "Fluid A     110.6", "Reserve"
SYMBOL  O , 7, "Fluid A     110.7", "Reserve"
END 

DPSUBSYSTEM 1, DPADDRESS 22, SLOT 8, "75x-530 8DO/24V DC/0.5A", "8DA"
BEGIN 
  ASSET_ID "34AF3D5C3EA14C329894F865E30D4DA8"
  SLAVE_CFG_DATA "01 00 20"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 23 02 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "5300"
  CREATOR ""
  COMMENT ""
LOCAL_OUT_ADDRESSES 
  ADDRESS  111, 0, 1, 0, 2, 0
SYMBOL  O , 0, "Fluid A     111.0", "Reserve"
SYMBOL  O , 1, "Fluid A     111.1", "Reserve"
SYMBOL  O , 2, "Fluid A     111.2", "Reserve"
SYMBOL  O , 3, "Fluid A     111.3", "Reserve"
SYMBOL  O , 4, "Fluid A     111.4", "Reserve"
SYMBOL  O , 5, "Fluid A     111.5", "Reserve"
SYMBOL  O , 6, "Fluid A     111.6", "Reserve"
SYMBOL  O , 7, "Fluid A     111.7", "Reserve"
END 

DPSUBSYSTEM 1, DPADDRESS 22, SLOT 9, "75x-512 2DO Relay/250V AC", "8DA"
BEGIN 
  ASSET_ID "F77B52B08A124B60B0A321CD5C39CFE2"
  SLAVE_CFG_DATA "01 00 20"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 20 02 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "5120"
  CREATOR ""
  COMMENT ""
LOCAL_OUT_ADDRESSES 
  ADDRESS  112, 0, 1, 0, 2, 0
SYMBOL  O , 0, "Fluid A     112.0", "Y Ventil Fluidbeimischung Betonsilo"
SYMBOL  O , 1, "Fluid A     112.1", "Y Ventil Fluidbeimischung Betonsilo"
SYMBOL  O , 2, "Fluid A     112.2", "Y Ventil Fluidbeimischung Brikettseite"
SYMBOL  O , 3, "Fluid A     112.3", "Y Ventil Fluidbeimischung Brikettseite"
SYMBOL  O , 4, "Fluid A     112.4", "Y Ventil Fluidbeimischung Brikettseite (Luftventil?)"
SYMBOL  O , 5, "Fluid A     112.5", "Reserve"
END 

DPSUBSYSTEM 1, DPADDRESS 22, SLOT 10, "*75x-512 2DO Relay/250V AC", "0"
BEGIN 
  ASSET_ID "E6D6952D432E46D9B3B47FFF6DE012FD"
  SLAVE_CFG_DATA "01 00 00"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 20 02 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "5121"
  CREATOR ""
  COMMENT ""
END 

DPSUBSYSTEM 1, DPADDRESS 24, "B757_S23.GSG", "Heizungssteuerung Kessel"
BEGIN
  ASSET_ID "C34A6E39DC3E4FEA9190CF24647B3A76"
  PNO_IDENT_NO "46935"
  WD_ON "0"
  PDM_PARAM "0"
  CBA_USAGE "0"
  GROUP_IDENT "0"
  NORMSLAVE_DP_MODE "0"
  OBJECT_REMOVEABLE "1"
  NORMSLAVE_PARAM_DATA "26 00 44 00 00 00 00 00 00 03 00 C3 43 00 00 00 01 00 00 00 00 80 2B 00 20 4A 01 06 20 01 00 20 01 00 20 02 00 20 02 00"
  POS_X "346"
  GATEWAY_COMMENT ""
  POS_Y "155"
  SIZE_X "78"
  SIZE_Y "64"
  MODULE_ADD_FLAGS "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  CREATOR ""
  COMMENT ""
  PHYSICAL_INTERFACE "0"
  CIR_STATE "0"
LOCAL_IN_ADDRESSES 
  ADDRESS  8182, 0, 0, 0, 2, 0
END

DPSUBSYSTEM 1, DPADDRESS 24, SLOT 1, "750-343 Kein Prozessdatenkanal", "0"
BEGIN 
  ASSET_ID "A0AEEDED6C674D70AF4DC4B935E27202"
  SLAVE_CFG_DATA "01 00 00"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 80 2B 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "3430"
  CREATOR ""
  COMMENT ""
END 

DPSUBSYSTEM 1, DPADDRESS 24, SLOT 2, "75x-460 4AI/RTD", "4AE"
BEGIN 
  ASSET_ID "E1E1877C8573455BAAE1A4F037812E25"
  SLAVE_CFG_DATA "01 00 53"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "04 00 20 4A 01 06"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4600"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  312, 0, 8, 0, 2, 0
END 

DPSUBSYSTEM 1, DPADDRESS 24, SLOT 3, "75x-405 2DI/230V AC/10ms", "8DE"
BEGIN 
  ASSET_ID "AAF619039C474EE1B633E9466D5C561F"
  SLAVE_CFG_DATA "01 00 10"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 20 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4050"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  120, 0, 1, 0, 2, 0
END 

DPSUBSYSTEM 1, DPADDRESS 24, SLOT 4, "*75x-405 2DI/230V AC/10ms", "0"
BEGIN 
  ASSET_ID "1A6E5E8433534A5C96FEAC7D3559EE4A"
  SLAVE_CFG_DATA "01 00 00"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 20 01 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4051"
  CREATOR ""
  COMMENT ""
END 

DPSUBSYSTEM 1, DPADDRESS 24, SLOT 5, "75x-512 2DO Relay/250V AC", "8DA"
BEGIN 
  ASSET_ID "99694BE5198449E3BCCAD2E00F2FB7D7"
  SLAVE_CFG_DATA "01 00 20"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 20 02 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "5120"
  CREATOR ""
  COMMENT ""
LOCAL_OUT_ADDRESSES 
  ADDRESS  120, 0, 1, 0, 2, 0
END 

DPSUBSYSTEM 1, DPADDRESS 24, SLOT 6, "*75x-512 2DO Relay/250V AC", "0"
BEGIN 
  ASSET_ID "2AB8EF72696C4A299BE8F960612A0CA8"
  SLAVE_CFG_DATA "01 00 00"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 20 02 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "5121"
  CREATOR ""
  COMMENT ""
END 

DPSUBSYSTEM 1, DPADDRESS 26, "_S7H_DP_S7_ISLAVE_CT", "Vecoplan Slave"
BEGIN
  ASSET_ID "2E03B400A8DF4C69B35700C92CAE0E52"
  GROUP_SYNC_BYTE "0"
  GROUP_FREEZE_BYTE "0"
  L2INTERNAL "255"
  WD_ON "0"
  PDM_PARAM "0"
  SLAVE_ACTIVE_PASSIVE "0"
  MODULE_EXCHANGE_ON_OPERATION_ENABLED "0"
  CBA_USAGE "0"
  GROUP_IDENT "0"
  OBJECT_REMOVEABLE "1"
  DP_TYPE "2"
  POS_X "432"
  POS_Y "153"
  SIZE_X "78"
  SIZE_Y "64"
  MODULE_ADD_FLAGS "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  CREATOR ""
  COMMENT ""
  ISLAVE_STATUS "1"
  CIR_STATE "0"
LOCAL_IN_ADDRESSES 
  ADDRESS  8181, 0, 0, 0, 1, 0
END

DPSUBSYSTEM 1, DPADDRESS 26, SLOT 4, "_S7H_DP_S7_IMODULE_CT", "S7-300 CPU 315-2 DP"
BEGIN 
  ASSET_ID "2A555CC4E2F74E4D9505EF1CD978A5B7"
  IMODULE_BGRZUORDNUNG "0"
  IMODE_MAPDATA "00 00 00 00 02 00 00 00 82 00 04 00 01 00 00 00 01 00 00 00"
  CPU_NO "1"
  ALARM_OB_NO "40"
  _ATTR4_112411 ""
  _ATTR0_112412 "0"
  IMODULE_CONFIG_ADDRESS_V51 "02 00 00 00 01 00 00 00 18 00 00 00 14 00 00 00 2C 00 00 00 14 00 00 00 00 00 00 00 02 00 00 00 82 00 04 00 01 00 00 00 01 00 00 00 01 00 00 00 FF FF FF FF 00 00 00 00 28 00 00 00 01 00 00 00"
  OBJECT_REMOVEABLE "1"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  SIZE_Y "0"
  F_MSDX_DATA ""
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  CREATOR ""
  COMMENT ""
  IMODULE_BGRADRESSE "0"
LOCAL_OUT_ADDRESSES 
  ADDRESS  130, 0, 4, 0, 2, 0
END 

DPSUBSYSTEM 1, DPADDRESS 26, SLOT 5, "_S7H_DP_S7_IMODULE_CT", "S7-300 CPU 315-2 DP"
BEGIN 
  ASSET_ID "9D1865C56A4A46CC83CCDAE30A4E67F0"
  IMODULE_BGRZUORDNUNG "0"
  IMODE_MAPDATA "01 00 00 00 02 00 00 00 86 00 04 00 01 00 00 00 01 00 00 00"
  CPU_NO "1"
  ALARM_OB_NO "40"
  _ATTR4_112411 ""
  _ATTR0_112412 "0"
  IMODULE_CONFIG_ADDRESS_V51 "02 00 00 00 01 00 00 00 18 00 00 00 14 00 00 00 2C 00 00 00 14 00 00 00 01 00 00 00 02 00 00 00 86 00 04 00 01 00 00 00 01 00 00 00 02 00 00 00 FF FF FF FF 00 00 00 00 28 00 00 00 01 00 00 00"
  OBJECT_REMOVEABLE "1"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  SIZE_Y "0"
  F_MSDX_DATA ""
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  CREATOR ""
  COMMENT ""
  IMODULE_BGRADRESSE "0"
LOCAL_OUT_ADDRESSES 
  ADDRESS  134, 0, 4, 0, 2, 0
END 

DPSUBSYSTEM 1, DPADDRESS 26, SLOT 6, "_S7H_DP_S7_IMODULE_CT", "S7-300 CPU 315-2 DP"
BEGIN 
  ASSET_ID "5FFB7D58CF8448DA8B0B31770855D3E0"
  IMODULE_BGRZUORDNUNG "0"
  IMODE_MAPDATA "02 00 00 00 02 00 00 00 8A 00 04 00 01 00 00 00 01 00 00 00"
  CPU_NO "1"
  ALARM_OB_NO "40"
  _ATTR4_112411 ""
  _ATTR0_112412 "0"
  IMODULE_CONFIG_ADDRESS_V51 "02 00 00 00 01 00 00 00 18 00 00 00 14 00 00 00 2C 00 00 00 14 00 00 00 02 00 00 00 02 00 00 00 8A 00 04 00 01 00 00 00 01 00 00 00 03 00 00 00 FF FF FF FF 00 00 00 00 28 00 00 00 01 00 00 00"
  OBJECT_REMOVEABLE "1"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  SIZE_Y "0"
  F_MSDX_DATA ""
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  CREATOR ""
  COMMENT ""
  IMODULE_BGRADRESSE "0"
LOCAL_OUT_ADDRESSES 
  ADDRESS  138, 0, 4, 0, 2, 0
END 

DPSUBSYSTEM 1, DPADDRESS 26, SLOT 7, "_S7H_DP_S7_IMODULE_CT", "S7-300 CPU 315-2 DP"
BEGIN 
  ASSET_ID "D047EC331ABD44E2B6CFE344721F720E"
  IMODULE_BGRZUORDNUNG "0"
  IMODE_MAPDATA "03 00 00 00 01 00 00 00 82 00 04 00 01 00 00 00 01 00 00 00"
  CPU_NO "1"
  ALARM_OB_NO "40"
  _ATTR4_112411 ""
  _ATTR0_112412 "0"
  IMODULE_CONFIG_ADDRESS_V51 "02 00 00 00 01 00 00 00 18 00 00 00 14 00 00 00 2C 00 00 00 14 00 00 00 03 00 00 00 01 00 00 00 82 00 04 00 01 00 00 00 01 00 00 00 04 00 00 00 FF FF FF FF 00 00 00 00 28 00 00 00 01 00 00 00"
  OBJECT_REMOVEABLE "1"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  SIZE_Y "0"
  F_MSDX_DATA ""
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  CREATOR ""
  COMMENT ""
  IMODULE_BGRADRESSE "0"
LOCAL_IN_ADDRESSES 
  ADDRESS  130, 0, 4, 0, 2, 0
END 

DPSUBSYSTEM 1, DPADDRESS 26, SLOT 8, "_S7H_DP_S7_IMODULE_CT", "S7-300 CPU 315-2 DP"
BEGIN 
  ASSET_ID "970674FA0B3A478D8627E3875FC50330"
  IMODULE_BGRZUORDNUNG "0"
  IMODE_MAPDATA "04 00 00 00 01 00 00 00 86 00 04 00 01 00 00 00 01 00 00 00"
  CPU_NO "1"
  ALARM_OB_NO "40"
  _ATTR4_112411 ""
  _ATTR0_112412 "0"
  IMODULE_CONFIG_ADDRESS_V51 "02 00 00 00 01 00 00 00 18 00 00 00 14 00 00 00 2C 00 00 00 14 00 00 00 04 00 00 00 01 00 00 00 86 00 04 00 01 00 00 00 01 00 00 00 05 00 00 00 FF FF FF FF 00 00 00 00 28 00 00 00 01 00 00 00"
  OBJECT_REMOVEABLE "1"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  SIZE_Y "0"
  F_MSDX_DATA ""
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  CREATOR ""
  COMMENT ""
  IMODULE_BGRADRESSE "0"
LOCAL_IN_ADDRESSES 
  ADDRESS  134, 0, 4, 0, 2, 0
END 

DPSUBSYSTEM 1, DPADDRESS 26, SLOT 9, "_S7H_DP_S7_IMODULE_CT", "S7-300 CPU 315-2 DP"
BEGIN 
  ASSET_ID "0AB3719EF19844BAAA1CB5B20AFF00DD"
  IMODULE_BGRZUORDNUNG "0"
  IMODE_MAPDATA "05 00 00 00 01 00 00 00 8A 00 04 00 01 00 00 00 01 00 00 00"
  CPU_NO "1"
  ALARM_OB_NO "40"
  _ATTR4_112411 ""
  _ATTR0_112412 "0"
  IMODULE_CONFIG_ADDRESS_V51 "02 00 00 00 01 00 00 00 18 00 00 00 14 00 00 00 2C 00 00 00 14 00 00 00 05 00 00 00 01 00 00 00 8A 00 04 00 01 00 00 00 01 00 00 00 06 00 00 00 FF FF FF FF 00 00 00 00 28 00 00 00 01 00 00 00"
  OBJECT_REMOVEABLE "1"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  SIZE_Y "0"
  F_MSDX_DATA ""
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  CREATOR ""
  COMMENT ""
  IMODULE_BGRADRESSE "0"
LOCAL_IN_ADDRESSES 
  ADDRESS  138, 0, 4, 0, 2, 0
END 

DPSUBSYSTEM 1, DPADDRESS 26, SLOT 10, "_S7H_DP_S7_IMODULE_CT", "S7-300 CPU 315-2 DP"
BEGIN 
  ASSET_ID "36050F4FC67741209B2AACB6EDB25336"
  IMODULE_BGRZUORDNUNG "0"
  IMODE_MAPDATA "06 00 00 00 01 00 00 00 44 02 04 00 02 00 00 00 01 00 00 00"
  CPU_NO "1"
  ALARM_OB_NO "40"
  _ATTR4_112411 ""
  _ATTR0_112412 "0"
  IMODULE_CONFIG_ADDRESS_V51 "02 00 00 00 01 00 00 00 18 00 00 00 14 00 00 00 2C 00 00 00 14 00 00 00 06 00 00 00 01 00 00 00 44 02 04 00 02 00 00 00 01 00 00 00 07 00 00 00 FF FF FF FF 00 00 00 00 28 00 00 00 01 00 00 00"
  OBJECT_REMOVEABLE "1"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  SIZE_Y "0"
  F_MSDX_DATA ""
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  CREATOR ""
  COMMENT ""
  IMODULE_BGRADRESSE "0"
LOCAL_IN_ADDRESSES 
  ADDRESS  580, 0, 8, 0, 2, 0
END 

DPSUBSYSTEM 1, DPADDRESS 26, SLOT 11, "_S7H_DP_S7_IMODULE_CT", "S7-300 CPU 315-2 DP"
BEGIN 
  ASSET_ID "3B16DEACF488476AB5B38A17E5DEE955"
  IMODULE_BGRZUORDNUNG "0"
  IMODE_MAPDATA "07 00 00 00 02 00 00 00 44 02 04 00 02 00 00 00 01 00 00 00"
  CPU_NO "1"
  ALARM_OB_NO "40"
  _ATTR4_112411 ""
  _ATTR0_112412 "0"
  IMODULE_CONFIG_ADDRESS_V51 "02 00 00 00 01 00 00 00 18 00 00 00 14 00 00 00 2C 00 00 00 14 00 00 00 07 00 00 00 02 00 00 00 44 02 04 00 02 00 00 00 01 00 00 00 08 00 00 00 FF FF FF FF 00 00 00 00 28 00 00 00 01 00 00 00"
  OBJECT_REMOVEABLE "1"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  SIZE_Y "0"
  F_MSDX_DATA ""
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  CREATOR ""
  COMMENT ""
  IMODULE_BGRADRESSE "0"
LOCAL_OUT_ADDRESSES 
  ADDRESS  580, 0, 8, 0, 2, 0
END 

DPSUBSYSTEM 1, DPADDRESS 28, "B757_S23.GSG", "Vecoplan"
BEGIN
  ASSET_ID "18CB5AD4285241CE8694FF36EF93EA7B"
  PNO_IDENT_NO "46935"
  WD_ON "0"
  PDM_PARAM "0"
  CBA_USAGE "0"
  GROUP_IDENT "0"
  NORMSLAVE_DP_MODE "0"
  OBJECT_REMOVEABLE "1"
  NORMSLAVE_PARAM_DATA "28 00 44 00 00 00 00 00 00 03 00 C3 43 00 00 00 01 00 00 00 00 80 2B 00 20 43 11 06 20 83 00 00 00 00 00 00 00 00 20 4B 01 06"
  POS_X "516"
  GATEWAY_COMMENT ""
  POS_Y "152"
  SIZE_X "78"
  SIZE_Y "64"
  MODULE_ADD_FLAGS "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  CREATOR ""
  COMMENT ""
  PHYSICAL_INTERFACE "0"
  CIR_STATE "0"
LOCAL_IN_ADDRESSES 
  ADDRESS  8185, 0, 0, 0, 2, 0
END

DPSUBSYSTEM 1, DPADDRESS 28, SLOT 1, "750-343 Kein Prozessdatenkanal", "0"
BEGIN 
  ASSET_ID "0E3AA80B3D7B493890FCDAC71360CCA9"
  SLAVE_CFG_DATA "01 00 00"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "03 00 80 2B 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "3430"
  CREATOR ""
  COMMENT ""
END 

DPSUBSYSTEM 1, DPADDRESS 28, SLOT 2, "75x-453 4AI/0-20mA/SE", "4AE"
BEGIN 
  ASSET_ID "DC6DDC6CC91741C09047CF7D9B70A3B5"
  SLAVE_CFG_DATA "01 00 53"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "04 00 20 43 11 06"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4530"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  600, 0, 8, 0, 2, 0
SYMBOL  I , 0, "L_IST_H1", "Füllstand Vibrorinne H1"
SYMBOL  I , 2, "I_IST_FU_H1", "Strom Vibrorinne H1"
SYMBOL  I , 4, "L_IST_H11", "Füllstand Vibrorinne H11"
END 

DPSUBSYSTEM 1, DPADDRESS 28, SLOT 3, "75x-553 4AO/0-20mA", "4AA"
BEGIN 
  ASSET_ID "5DA0AC6C8B2B47EFA52C94491E012A47"
  SLAVE_CFG_DATA "01 00 63"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "0A 00 20 83 00 00 00 00 00 00 00 00"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "5530"
  CREATOR ""
  COMMENT ""
LOCAL_OUT_ADDRESSES 
  ADDRESS  600, 0, 8, 0, 2, 0
SYMBOL  O , 0, "V_SOLL_H1", "Sollgeschwindigkeit Vibrorinne H1"
SYMBOL  O , 2, "V_SOLL_H11", "Sollgeschwindigkeit Vibrorinne H11"
END 

DPSUBSYSTEM 1, DPADDRESS 28, SLOT 4, "75x-461 2AI/RTD", "2AE"
BEGIN 
  ASSET_ID "7A90148EE86844A987BEEC7BEDE8F75E"
  SLAVE_CFG_DATA "01 00 51"
  OBJECT_REMOVEABLE "1"
  RETAIN_LAST_VALUE "0"
  POS_X "0"
  POS_Y "0"
  SIZE_X "0"
  MODULE_ADD_FLAGS "0"
  NORMMODULE_PARAM_DATA "04 00 20 4B 01 06"
  SIZE_Y "0"
  CAX_APP_ID ""
  OBJECT_COPYABLE "1"
  NORMMODULE_REFERENCE "4610"
  CREATOR ""
  COMMENT ""
LOCAL_IN_ADDRESSES 
  ADDRESS  608, 0, 4, 0, 2, 0
END 
