A DC converter have DC converter terminals. A converter has two DC converter terminals.
DCTerminals
{419FDA84-5AD0-409d-BAAA-27B90163DA73}.ClientEnd
Point of common coupling terminal for this converter DC side. It is typically the terminal on the power transformer or switch closest to the AC network.
PccTerminal
{6880D3F9-475B-4887-8B4A-332FABFC8F47}.SupplierEnd
Base apparent power of the converter pole. The attribute shall be a positive value.
baseS
{20F0D1ED-6CE8-471e-8E4B-DCC6C4B46AA5}
Converter DC current also called Id. It is converters state variable result from power flow.
idc
{180F58C1-0E50-4bb2-B496-E88864AF033A}
Active power loss in pole at no power transfer. It is converters configuration data used in power flow. The attribute shall be a positive value.
idleLoss
{E9ED1BC9-CA40-4d1f-91E4-5425A18765DD}
Maximum active power limit. The value is overwritten by values of VsCapabilityCurve if present.
maxP
{082E98FF-DDF7-4a42-A993-2A10F8464960}
The maximum voltage on the DC side at which the converter should operate. It is converters configuration data used in power flow. The attribute shall be a positive value.
maxUdc
{75897B30-EAA3-486e-AA11-DA02461454EE}
Minimum active power limit. The value is overwritten by values of VsCapabilityCurve if present.
minP
{8019FADD-6C6B-4979-A784-0513A1C08CB9}
The minimum voltage on the DC side at which the converter should operate. It is converters configuration data used in power flow. The attribute shall be a positive value.
minUdc
{C442EC69-4FD8-4b00-A7A5-9356A9E1C4BF}
Active power at the point of common coupling. Load sign convention is used i.e. positive sign means flow out from a node.Starting value for a steady state solution in the case a simplified power flow model is used.
p
{A2886699-3439-4510-98E7-990FB4691BF3}
The active power loss at a DC Pole idleLoss switchingLossIdc resitiveLossIdc2.For lossless operation PdcPac.For rectifier operation with losses PdcPaclossP.For inverter operation with losses PdcPaclossP.It is converters state variable used in power flow. The attribute shall be a positive value.
poleLossP
{AD13092B-56F5-4cc6-8225-93F6DFD49D2E}
Reactive power at the point of common coupling. Load sign convention is used i.e. positive sign means flow out from a node.Starting value for a steady state solution in the case a simplified power flow model is used.
q
{3BADAA72-01DD-4d34-99E4-FF5E7E2DD77C}
Rated converter DC voltage also called UdN. The attribute shall be a positive value. It is converters configuration data used in power flow. For instance a bipolar HVDC link with value 200 kV has a 400kV difference between the dc lines.
ratedUdc
{85D36F1D-363A-42a6-ACDB-87AE5511D72F}
It is converters configuration data used in power flow. Refer to poleLossP. The attribute shall be a positive value.
resistiveLoss
{170A8A5E-A487-4e0a-A458-C5CEA87D3624}
Switching losses relative to the base apparent power baseS. Refer to poleLossP. The attribute shall be a positive value.
switchingLoss
{09B85C15-1584-4b82-AC15-9A4C7BAD2F8C}
Real power injection target in AC grid at point of common coupling. Load sign convention is used i.e. positive sign means flow out from a node.
targetPpcc
{517A2014-C002-4bcc-A490-1878A4D3DC40}
Target value for DC voltage magnitude. The attribute shall be a positive value.
targetUdc
{393D548F-14FB-4ae1-9269-0B18F64E442D}
Linetoline converter voltage the voltage at the AC side of the valve. It is converters state variable result from power flow. The attribute shall be a positive value.
uc
{BDE610FA-7E72-4605-9A95-67DED66E25C1}
Converter voltage at the DC side also called Ud. It is converters state variable result from power flow. The attribute shall be a positive value.
udc
{2546662D-C210-4dd7-9137-FF80B3B9D15C}
Valve threshold voltage also called Uvalve. Forward voltage drop when the valve is conducting. Used in loss calculations i.e. the switchLoss depend on numberOfValves valveU0.
valveU0
{BCE61CD4-9E6A-4c28-892B-64EADC865EFF}
A DC converter terminal belong to an DC converter.
DCConductingEquipment
{419FDA84-5AD0-409d-BAAA-27B90163DA73}.SupplierEnd
Represents the normal network polarity condition. Depending on the converter configuration the value shall be set as follows For a monopole with two converter terminals use DCPolarityKind positive and negative. For a bipole or symmetric monopole with three converter terminals use DCPolarityKind positive middle and negative.
polarity
{48F3E203-BD33-4146-B839-2EC1080B0020}
The bus name marker used to name the bus topological node.
BusNameMarker
{EE3B8B0F-5740-4380-91F9-563BFD5783D7}.ClientEnd
Measurements associated with this terminal defining where the measurement is placed in the network topology. It may be used for instance to capture the sensor position such as a voltage transformer PT at a busbar or a current transformer CT at the bar between a breaker and an isolator.
Measurements
{9C2962C4-F1BE-4c1a-9577-DB6E59B8FB49}.ClientEnd
The operational limit sets at the terminal.
OperationalLimitSet
{E741C3E3-646B-4238-BE21-DFE9B0A603C1}.ClientEnd
The line segment phases which belong to the line segment.
ACLineSegmentPhases
{445FD290-7977-4f2a-AC68-646609336C93}.ClientEnd
The clamps connected to the line segment.
Clamp
{2B7C9922-26A9-4218-8BDD-1098869C8600}.SupplierEnd
Cuts applied to the line segment.
Cut
{62963E89-E891-4b03-8000-C14788BD8E57}.ClientEnd
The line faults of the line segment.
LineFaults
{BBA661BB-92B7-4934-988B-DF65931690EE}.ClientEnd
Ground action involving clamp usage for the case when the ground is applied along the line segment instead of at its terminals.
LineGroundingAction
{1E3F8223-0B92-4d7f-B4A8-4D976F915A99}.ClientEnd
Jumper action involving clamp usage for the case when the jumper is applied along the line segment instead of at its terminals.
LineJumpingAction
{9581D491-DFD1-477b-A1F8-56207CB6A28F}.ClientEnd
Perlength impedance of this line segment.
PerLengthImpedance
{741AE432-C721-4a8d-92F4-C8B96FA98A3A}.ClientEnd
WireSpacingInfo
{F29D4402-D392-434d-9E98-8C35F21BD856}.SupplierEnd
Zero sequence shunt charging susceptance uniformly distributed of the entire line section.
b0ch
{5EE8B645-9FB5-4985-8930-6CB5CAA29CE2}
Positive sequence shunt charging susceptance uniformly distributed of the entire line section. This value represents the full charging over the full length of the line.
bch
{FFCA602E-D6F0-4fed-BAE6-D02A2C04BB65}
Zero sequence shunt charging conductance uniformly distributed of the entire line section.
g0ch
{59D23066-ADB0-4369-BD9D-95AB3B53376F}
Positive sequence shunt charging conductance uniformly distributed of the entire line section.
gch
{7780580B-437B-45bf-8C1E-AF5F03086378}
Positive sequence series resistance of the entire line section.
r
{57B0CDE3-FEB1-4d13-8906-A9C7AF3C5482}
Zero sequence series resistance of the entire line section.
r0
{DDBBA03D-E40D-4200-941D-CFB4E24253A0}
Maximum permitted temperature at the end of SC for the calculation of minimum shortcircuit currents. Used for short circuit data exchange according to IEC 60909.
shortCircuitEndTemperature
{5BD9D924-26C6-4f14-AB49-6D3A0C16D6BB}
Positive sequence series reactance of the entire line section.
x
{78292BCA-9CCD-4a7a-8E36-7F7CA0D1C0BB}
Zero sequence series reactance of the entire line section.
x0
{14CCC61E-8CFF-4748-BB34-30167D45B278}
The line segment to which the phase belongs.
ACLineSegment
{445FD290-7977-4f2a-AC68-646609336C93}.SupplierEnd
WireInfo
{B5F55F86-9C19-4914-99C2-1ACBA0197A2E}.SupplierEnd
The phase connection of the wire at both ends.
phase
{38F4F39B-9236-46fa-9B1C-D7356BDE2E54}
ReserveDemandCurve
{6B2BD6A2-CC2E-4cf3-BCDE-BB717B4A931B}.SupplierEnd
Edition of ASTM standard.
standardEdition
{DD924D6E-3005-46f7-A900-83EFD91D2B36}
ASTM standard number.
standardNumber
{1E7A832F-80DC-4f20-8507-E960495C0EF6}
Total cost of permit.
payment
{982DB00B-813C-4d51-AD03-3C043B628C5E}
Amount that was credited todebited from an account. For example payment receivedinterest charge on arrears.
amount
{EE2260B6-9167-458d-9885-02A57E1DD569}
CustomerAccount
{FC0059FF-913A-472a-9717-BA43E0EC7EA1}.ClientEnd
Unit of service.
energyUnit
{E9744D2F-64EF-47b5-A2D3-E531F5963CE3}
Unit of currency.
monetaryUnit
{4E43FB70-E650-4127-8A7A-C6D6AE71A885}
Multiplier for the energyUnit or monetaryUnit.
multiplier
{29FF04FF-B792-414a-9DBD-2E3804AEAFD7}
The values connected to this measurement.
AccumulatorValues
{FD856524-A775-4757-941C-AF8347AF28E6}.SupplierEnd
A measurement may have zero or more limit ranges defined for it.
LimitSets
{F88250FD-AF28-4716-BE9E-FC0C3E099E19}.SupplierEnd
The set of limits.
LimitSet
{89D44FA0-A7BB-420d-B5B7-57A18801CE94}.ClientEnd
The limit values used for supervision of Measurements.
Limits
{89D44FA0-A7BB-420d-B5B7-57A18801CE94}.SupplierEnd
The Measurements using the LimitSet.
Measurements
{F88250FD-AF28-4716-BE9E-FC0C3E099E19}.ClientEnd
The accumulator value that is reset by the command.
AccumulatorValue
{67E9A9B6-4DEA-46a1-AEFA-0FB2969ED0B8}.SupplierEnd
Measurement to which this value is connected.
Accumulator
{FD856524-A775-4757-941C-AF8347AF28E6}.ClientEnd
The command that resets the accumulator value.
AccumulatorReset
{67E9A9B6-4DEA-46a1-AEFA-0FB2969ED0B8}.ClientEnd
MarketDocument
{17256E85-4394-4e3a-95AC-8ECE9214CA71}.SupplierEnd
Point
{BABB4FDB-5AA4-4c38-80B1-35F9E79D3BAE}.ClientEnd
Unit
{ED2E671C-C32B-4348-BE5F-95F220417E34}.SupplierEnd
Bid
{FCF33735-6427-4091-BCD8-269E10C726B2}.SupplierEnd
Trade
{54A2C406-8667-40cf-88A9-3A48629020FE}.SupplierEnd
Action name type for the action request.
actionName
{9BEE1FF9-F843-4e3b-A3FB-EC0C034E8A31}
multiplier
{A3961E95-7DD0-4d68-A41A-FDC07295CD2B}
unit
{8C27ACD4-E6D7-407f-B0AF-B545966B9337}
multiplier
{127E7AD6-A19D-4a00-84C2-6DE69D31A319}
unit
{2AF6CD50-07D6-4a91-A069-542109925F94}
The normal value of active power limit. The attribute shall be a positive value or zero.
normalValue
{18EB554B-128C-4b2d-A121-5A56540922AC}
Value of active power limit. The attribute shall be a positive value or zero.
value
{42566851-EDFE-4e41-B43F-685B06099B2D}
multiplier
{F35C1985-6CCA-44a7-898A-AC5460E4319D}
unit
{860D073A-9544-41bc-BD10-66C21C8B2C88}
multiplier
{4325598F-25F9-4cd6-BF6E-5C862888172C}
unit
{971E19EB-1560-4869-B75E-DE4120218C87}
All assets for which this activity record has been created.
Assets
{D26C382F-6EE5-4987-B802-F3F3C2EBBEC9}.ClientEnd
Author of this activity record.
Author
{C7B3A827-5B49-4da5-95A3-4EE7D07568AA}.ClientEnd
Information on consequence of event resulting in this activity record.
status
{EA243F71-81FB-4946-8745-A91B1F263D70}
BidSelfSched
{B2038A6D-F6D7-42bf-BD3F-0D4F0A7C79E4}.SupplierEnd
HostControlArea
{8E4B9C0F-0498-44a7-BFE9-8CB6884935B0}.ClientEnd
RTO
{E7E0DD2A-8D53-4ec2-BEE0-BFCCE3D2E252}.ClientEnd
RegisteredResource
{886205D7-4ADB-42fe-A010-F455E9A5B54F}.ClientEnd
SubControlArea
{6E3CCC1F-13F4-4f39-8628-7EAC38F18D74}.SupplierEnd
multiplier
{368DCBAB-6DFC-4a81-AC07-6A40EC161ED6}
unit
{F9B6C9EF-4266-4494-BF85-5C9C2DF35ECF}
AreaLoadCurve
{A5505C4B-57CC-4a61-B752-D3A8A9F07A25}.ClientEnd
CnodeDistributionFactor
{423960E1-ADF0-47a5-B371-AA4201541FC9}.SupplierEnd
Instruction
{917AB6A6-8808-4d28-B5EB-217844E5D8B1}.ClientEnd
Pnode
{CAB06BAC-94AA-411c-9272-D4C6EB676F32}.SupplierEnd
RTO
{95DFE9B0-18E0-4c05-9AC1-211693BB8524}.ClientEnd
A RegisteredResource can be associated to only one AggregateNode if not connected to a Pnode or MktConnectivityNode.
RegisteredResource
{E4F5F679-427A-4403-B876-8642E8E03574}.ClientEnd
SubControlArea
{95FCC4C7-2611-4267-9EF0-B7A30B49ECE8}.SupplierEnd
Type of aggregated node
anodeType
{A373A6B5-0BFD-44e5-A5A1-5BBBF79E5396}
Analytic score contributing to this aggregate score.
AnalyticScore
{2FCAEC38-A13E-4208-ADE2-DC5AC84B417A}.SupplierEnd
GenDistributionFactor
{909A546B-EA82-4f60-8B44-1E47722DB03E}.SupplierEnd
LoadDistributionFactor
{1E748A16-16A1-4251-B7F2-5AB41F4B8AB1}.SupplierEnd
MPMTestResults
{C0382101-491D-471a-B6BD-412F2E2BEFE1}.SupplierEnd
MPMTestThreshold
{3A9890C7-0792-48c5-BE74-53A2FA81C59A}.ClientEnd
MktCombinedCyclePlant
{667EE2EC-BAF5-4e35-9AEA-070E69E9AACF}.ClientEnd
PnodeDistributionFactor
{C455B6B7-BDE8-4036-B32B-EFD8413FD6B7}.SupplierEnd
TACArea
{172CCB30-32D5-4d42-90DE-5FC85FCBF6C3}.SupplierEnd
TradingHubValues
{28734C41-4653-42fe-A8E1-178A7444F6EC}.ClientEnd
Aggregate Price Node Types
apnodeType
{185E4E21-BBA4-4b3d-8FBE-19BDACF891C8}
Designated Control Area participation in LMP price measurementY Participates in both Local Market Power Mitigation LMPM and System Market Power Mitigation SMPMN Not included in LMP price measuresS Participatesin SMPM price measuresL Participatesin LMPM price measures
participationCategory
{8554C802-56CF-413c-BF46-14F48C1A8EE2}
Date and time interval this agreement is valid from going into effect to termination.
validityInterval
{3A6C2397-7AD8-4787-9146-43E299D419C9}
An air compressor may be a member of a compressed air energy storage plant.
CAESPlant
{3B7A359B-1CB5-47fc-A551-592BDCAF20F2}.ClientEnd
A CAES air compressor is driven by combustion turbine.
CombustionTurbine
{F30399A8-ACB2-4f18-8D1C-F38C8427C14D}.ClientEnd
An alert whose type is drawn from this alert type list.
EnvironmentalAlert
{47BAF174-F27B-42ab-8162-CA6C1C444323}.ClientEnd
The environmental data authority responsible for publishing this list of alert types.
EnvironmentalDataAuthority
{2A299E0C-C0CE-4200-AE97-FBD32E1BCFE0}.SupplierEnd
AllocationResultValues
{9B469FC0-7C86-4fe8-B462-C045847DDD66}.SupplierEnd
AllocationResult
{9B469FC0-7C86-4fe8-B462-C045847DDD66}.ClientEnd
RegisteredResource
{5074A0CF-AF43-4460-BC17-3037761F765B}.ClientEnd
The specific analog value used as a source.
AnalogValue
{234361E4-CD30-4f2c-BFED-521DBDF85CB9}.SupplierEnd
The specific analog value used as a source.
AnalogValue
{9E09D035-D269-408f-B4BA-CF36416D09C0}.SupplierEnd
The group of alternate models for which one alternate is used.
AlternateModelGroup
{EDA739BD-2531-485d-95AF-5B703DC34258}.SupplierEnd
The data belonging to the alternate model.
Dataset
{CF5D1E33-0F2F-40d6-B260-30258F4FBA0D}.SupplierEnd
An alternate model that can be one possiblity among alternates.
AlternateModel
{EDA739BD-2531-485d-95AF-5B703DC34258}.ClientEnd
The values connected to this measurement.
AnalogValues
{434DE6F0-FCF7-4c76-9BCF-D564B2D0AB6B}.SupplierEnd
A measurement may have zero or more limit ranges defined for it.
LimitSets
{06914CE2-9FCC-4a08-AED5-C30E3623AE01}.SupplierEnd
The MeasurementValue that is controlled.
AnalogValue
{8D3DFD64-B2F7-4a60-AE01-416DBF5137A2}.ClientEnd
The set of limits.
LimitSet
{EB6BDFA4-8613-420a-A583-63C11A93EF29}.ClientEnd
The limit values used for supervision of Measurements.
Limits
{EB6BDFA4-8613-420a-A583-63C11A93EF29}.SupplierEnd
The Measurements using the LimitSet.
Measurements
{06914CE2-9FCC-4a08-AED5-C30E3623AE01}.ClientEnd
The alternate generating unit for which this measurement value applies.
AltGeneratingUnit
{234361E4-CD30-4f2c-BFED-521DBDF85CB9}.ClientEnd
The usage of the measurement within the control area specification.
AltTieMeas
{9E09D035-D269-408f-B4BA-CF36416D09C0}.ClientEnd
Measurement to which this value is connected.
Analog
{434DE6F0-FCF7-4c76-9BCF-D564B2D0AB6B}.ClientEnd
The Control variable associated with the MeasurementValue.
AnalogControl
{8D3DFD64-B2F7-4a60-AE01-416DBF5137A2}.SupplierEnd
Analytic score produced by this analytic.
AnalyticScore
{76956539-74D1-490a-9E7B-3CFB8A08570E}.SupplierEnd
Asset on which this analytic can be performed.
Asset
{5EFCAC67-8919-46cc-BBF4-2FADDF364B72}.SupplierEnd
Asset group on which this analytic can be performed.
AssetGroup
{E4171B20-7CF4-4438-BF2B-4B594B8F9704}.SupplierEnd
Asset health event which can be generated by this analytic.
AssetHealthEvent
{77520F55-DB58-40be-AADD-146E07A79BF4}.SupplierEnd
Kind of analytic this analytic is.
kind
{31BCCAF8-9E06-4c60-8DD2-AEC9675F37A3}
The scoring scale kind.
scaleKind
{707B9DEE-9687-4727-9D36-95A6FFD0B1BD}
Analytic which was executed to arrive at this analytic score..
Analytic
{76956539-74D1-490a-9E7B-3CFB8A08570E}.ClientEnd
Asset to which this analytic score applies.
Asset
{46666DB4-FABB-4df7-85BE-D672C18455E9}.SupplierEnd
Aggregate score to which this analytic score contributed.
AssetAggregateScore
{2FCAEC38-A13E-4208-ADE2-DC5AC84B417A}.ClientEnd
Asset group to which this analytic score applies..
AssetGroup
{B95F72B4-FBDD-4755-A947-DC49BE3749E0}.ClientEnd
MarketCaseClearing
{193E6A14-52CA-4269-A05F-CC3FCD23A162}.SupplierEnd
MarketRegionResults
{F1B3EB5C-675E-4790-95CC-79C38272C39C}.SupplierEnd
multiplier
{8FDF9698-E454-4c56-B58E-BFEBE384F311}
unit
{58D1D28E-ADAB-4417-A5F4-D089FF60AE02}
multiplier
{6023067B-C576-43bb-8474-6B6A763AD6D2}
unit
{C0911890-BF89-4edd-A9AD-F0E170B0BC6A}
DependentOnStage
{DA34DBEB-9B66-47df-B464-9D7E5EC7EA99}.SupplierEnd
DependingStage
{66BEEFB3-CC6F-4eb4-B3FF-8D386E2F2D98}.SupplierEnd
dependencyType
{339D188B-866F-4be1-9C95-356B8C3419FC}
multiplier
{C363463C-85C7-487f-BE31-B6444DAB07DD}
unit
{C93DE952-5AF9-40cc-9792-4D2372DC5EEF}
The normal apparent power limit. The attribute shall be a positive value or zero.
normalValue
{9698296C-5CC4-49bc-BC45-8CE841D6F3CC}
The apparent power limit. The attribute shall be a positive value or zero.
value
{B56E8750-1658-48df-A5ED-13F144E45F95}
All persons for this appointment.
Persons
{C9DF52B7-89D3-4d66-8D7F-13A02C9F8C6A}.ClientEnd
All works for this appointment.
Works
{A1F0785E-E4E6-4ce3-8297-16F47D531998}.SupplierEnd
Date and time reserved for appointment.
meetingInterval
{ADBCCBB6-CFAE-4d02-8A3E-3578942BE6DD}
All documents for this approver.
Documents
{E773805D-E6AC-4d17-9B2A-5E6338923314}.SupplierEnd
multiplier
{7A1160C2-A913-4954-A9BE-9DB145518EC1}
unit
{46AED7DB-6F91-477e-BF3D-92F640E352E9}
LoadBid
{66BF4185-41CD-43e2-8659-871C1A781082}.SupplierEnd
AggregateNode
{A5505C4B-57CC-4a61-B752-D3A8A9F07A25}.SupplierEnd
TACArea
{825890F9-E350-40bd-AAE5-57E92CB28556}.ClientEnd
Load forecast area type.
forecastType
{B4E89A91-66EF-4f3c-926F-7B31574DE439}
SubControlArea
{F6EC071D-A9FE-4972-8340-7B298A3F59EF}.SupplierEnd
Lower regulating margin requirement in MW the amount of generation that can be dropped by control in 10 minutes
lowerRegMarginReqt
{66A8703B-B9C9-434b-B785-ACCC50DE5A11}
Operating reserve requirement in MW where operating reserve is the generating capability that is fully available within 30 minutes. Operating reserve is composed of primary reserve t less than 10 min and secondary reserve 10 less than t less than 30 min.
opReserveReqt
{2F2727BE-61A6-4718-96C8-1604EB020AE4}
Primary reserve requirement in MW where primary reserve is generating capability that is fully available within 10 minutes. Primary reserve is composed of spinning reserve and quickstart reserve.
primaryReserveReqt
{F163BA39-7D1F-4675-8357-F61225891C68}
Raise regulating margin requirement in MW the amount of generation that can be picked up by control in 10 minutes
raiseRegMarginReqt
{E53A6FC9-0E3D-4415-9BE6-1BE06DF0B3CE}
Spinning reserve requirement in MW spinning reserve is generating capability that is presently synchronized to the network and is fully available within 10 minutes
spinningReserveReqt
{E07262D7-1BAF-4f4a-8190-9584A2D4A280}
The models that are part of the assembly descrption.
ModelSpecification
{63DD40D8-8901-4fa0-B3DA-04BEDB15C589}.SupplierEnd
CompleteModelToBeDeleted
{ABA7248F-7487-4c32-811C-B708158136CB}.SupplierEnd
ModelPartVersion
{181112F7-C48F-44b9-B4D1-249851E26CBA}.SupplierEnd
All activity records created for this asset.
ActivityRecords
{D26C382F-6EE5-4987-B802-F3F3C2EBBEC9}.SupplierEnd
Analytic performed on this asset.
Analytic
{5EFCAC67-8919-46cc-BBF4-2FADDF364B72}.ClientEnd
Analytic result related to this asset.
AnalyticScore
{46666DB4-FABB-4df7-85BE-D672C18455E9}.ClientEnd
Container of this asset.
AssetContainer
{84A53CE3-0404-43bd-AE48-68E902A89267}.SupplierEnd
This assets deployment.
AssetDeployment
{3E85DBF1-9694-4145-B671-2867557FE27C}.SupplierEnd
AssetFunction
{B8F5E4FF-B800-45b0-88BA-6C8C4BB96BE9}.SupplierEnd
Asset group of which this asset is a part.
AssetGroup
{D768ADB9-10E4-444c-A72E-BB74B3DBC81A}.ClientEnd
Data applicable to this asset.
AssetInfo
{089B8A18-9B8E-4fc5-B298-9CFB28624527}.SupplierEnd
AssetPropertyCurves
{7B58C937-A11B-4960-AD54-6431B15F1A97}.SupplierEnd
Breaker operation information for this breaker.
BreakerOperation
{D39D36F1-D054-4dbc-8E93-564DC921D2DB}.ClientEnd
All configuration events created for this asset.
ConfigurationEvents
{71EA796A-141A-445d-9B0E-EF0075BFAFD2}.SupplierEnd
ErpInventory
{ED3450A6-CFCF-4eb3-95A3-E3511D9B6178}.SupplierEnd
ErpItemMaster
{84B973F4-8888-4cf6-920A-BD61CD559A80}.ClientEnd
ErpRecDeliveryItems
{69D45AA1-C24F-4329-AABF-24C5B1CC8A51}.SupplierEnd
Financial information related to this asset.
FinancialInfo
{1B0E0E88-6371-4ed9-AD31-7E0799CB9AD6}.ClientEnd
Location of this asset.
Location
{1547DDC4-B4CB-4406-B642-4E0337FC4594}.SupplierEnd
Measurement related to this asset.
Measurements
{016DD996-A1EA-4bb6-8349-AF38EEDFF7AD}.SupplierEnd
Medium with which this asset is filled.
Medium
{C899B2C5-BB4D-4ce8-A659-85956A304887}.ClientEnd
All operational tags placed on this asset.
OperationalTags
{6C60E3EC-3A0D-400d-BFBB-48BE5355B286}.ClientEnd
All roles an organisation plays for this asset.
OrganisationRoles
{D423536D-C2FE-462e-A473-046027941335}.SupplierEnd
All ownerships of this asset.
Ownerships
{7323F8B4-3F0F-40c7-8BCA-72BFFF4394A9}.ClientEnd
All power system resources used to electrically model this asset. For example transformer asset is electrically modelled with a transformer and its windings and tap changer.
PowerSystemResources
{9709C87C-3A85-4ce4-BA02-CEBB104E7DB5}.SupplierEnd
Procedure data set that applies to this asset.
ProcedureDataSet
{F1E16F01-CC4F-4170-9610-3C1C6E17A43F}.ClientEnd
All procedures applicable to this asset.
Procedures
{3458C266-F6A0-4e72-8A55-BFFF83421DE2}.ClientEnd
The model of this asset.
ProductAssetModel
{24E0529D-66B4-4bd0-BE95-E9F7A501079C}.SupplierEnd
Reconditionings
{0EDF1A71-1F5E-42e5-9A94-8DFC165669B6}.SupplierEnd
ReliabilityInfos
{2FBB4D9A-182E-47c5-8227-76C599CC4086}.ClientEnd
All work tasks on replacement of this old asset.
ReplacementWorkTasks
{DEDB052F-30DA-4503-94F8-99F03155CB7F}.ClientEnd
Scheduled event related to this asset.
ScheduledEvents
{E182BB37-0828-425d-B4E7-9C8FE6B40993}.ClientEnd
All nonreplacement work tasks performed on this asset.
WorkTasks
{7D2E82EC-1CC5-4b1b-8FF3-DFA1835C7E49}.ClientEnd
Information on acceptance test.
acceptanceTest
{F1B2BD3C-7915-4d5c-B635-6D8F5CBFB492}
Percentage of initial life expectancy that has been lost as of the last life expectancy baseline. Represents initial life expectancy current life expectancy initial life expectancy.
baselineLossOfLife
{C9057137-8AB2-4a74-94D4-E08DE8026332}
Electronic address.
electronicAddress
{C4E4A775-1726-4b5f-AC3E-015B65E2B08F}
In use dates for this asset.
inUseDate
{7B3EECE8-9580-4735-807D-E4943F216640}
Indication of whether asset is currently deployed in use ready to be put into use or not available for use.
inUseState
{FDE23E7A-5534-4875-AE41-3608A2D1AA24}
Kind of asset. Used in description of asset components in asset instance templates.
kind
{B01C2DC7-EF72-44c8-9B89-12F5EC808B78}
was lifecycleLifecycle dates for this asset.
lifecycleDate
{95C2B3F1-CD1D-4b69-8062-A67BA4FFBB7B}
Current lifecycle state of asset.
lifecycleState
{1AEA2D5B-07CF-4e49-8C00-1F7FDB5E430B}
Purchase price of asset.
purchasePrice
{6BF8B4B9-C3A6-415c-9BAE-625A5AB0964C}
Reason asset retired.
retiredReason
{DD8583BB-9AFA-4c53-95FB-18C39507DFDA}
Status of this asset.
status
{8225FD52-D587-46bc-8E67-501C8255515B}
The lab test standard to which this asset health analog is related.
TestStandard
{2E6CE9AA-C3EE-4729-8DE4-6CB4B1AC3E42}.SupplierEnd
Reporting temperature of related analog value if different from reporting temperature of test standard or if there is no test standard. Reporting temperature is what gas volumes are normalized to. Different reporting temperatures are used by different sources. For example ASTM specifies 0C whereas IEC specifies 20C. Online monitors often have their own unique reporting temperatures.
reportingTemperature
{B72D35A3-123B-4c6c-B5CE-4541B5F9C3CB}
All assets within this container asset.
Assets
{84A53CE3-0404-43bd-AE48-68E902A89267}.ClientEnd
LandProperties
{658256E1-9CC7-4618-861D-E2D5F2458763}.ClientEnd
All seals applied to this asset container.
Seals
{FDAAA9DF-09C4-4044-B2F9-0C70CD16B243}.SupplierEnd
Asset in this deployment.
Asset
{3E85DBF1-9694-4145-B671-2867557FE27C}.ClientEnd
Base voltage of this network asset deployment.
BaseVoltage
{EEECBAA7-1891-4130-A184-0EB99FA07C16}.SupplierEnd
Type of network role breaker is playing in this deployment applies to breaker assets only.
breakerApplication
{05648883-CA13-4504-85C4-84E5205C8E78}
Dates of asset deployment.
deploymentDate
{9DA43971-BCDD-4284-8C7A-DA45FFB48F32}
Current deployment state of asset.
deploymentState
{31CA4F11-29C2-4170-ACAC-B2B5C0110073}
Kind of facility like substation or pole or building or plant or service center at which asset deployed.
facilityKind
{696A681B-73B3-431a-8E99-68312B0B55EE}
Type of network role transformer is playing in this deployment applies to transformer assets only.
transformerApplication
{319660F4-7A63-445a-A1E8-D4502FBF9AE1}
The lab test standard to which this asset health discrete is related.
TestStandard
{7AF83EF1-4332-45fc-ADCA-D6AC1324070C}.SupplierEnd
Asset
{B8F5E4FF-B800-45b0-88BA-6C8C4BB96BE9}.ClientEnd
Analytic which can be performed on this asset group.
Analytic
{E4171B20-7CF4-4438-BF2B-4B594B8F9704}.ClientEnd
Analytic score for this asset group.
AnalyticScore
{B95F72B4-FBDD-4755-A947-DC49BE3749E0}.SupplierEnd
Asset which is a part of this asset group.
Asset
{D768ADB9-10E4-444c-A72E-BB74B3DBC81A}.SupplierEnd
Kind of asset group this asset group is.
kind
{93FB62F0-247C-4f9c-865D-BE98FA23AC24}
Analytic that initiated this asset health event.
Analytic
{77520F55-DB58-40be-AADD-146E07A79BF4}.ClientEnd
All assets described by this data.
Assets
{089B8A18-9B8E-4fc5-B298-9CFB28624527}.ClientEnd
Asset information nameplate for this catalog asset type.
CatalogAssetType
{9B683AA4-C622-4998-B81E-A7467D326D7B}.SupplierEnd
All power system resources with this datasheet information.
PowerSystemResources
{009BA3E8-B2DD-4bef-B118-F700692FC9EA}.SupplierEnd
Product asset model which conforms to this catalog asset type.
ProductAssetModel
{C53749B6-0642-4045-81C7-6DC6CDBC280D}.ClientEnd
The location of this hazard.
Locations
{A7C698DB-6096-423a-918E-5D26CD309E44}.SupplierEnd
Kind of hazard.
kind
{5D92A8E3-8FA0-418f-ACB1-3B0BE65D6268}
AssetModelCatalogueItems
{0DA534C6-ACF6-48ab-A8DB-496BB661F459}.ClientEnd
status
{9E490DCF-DD54-475b-B583-3F1ABC4FFA74}
AssetModel
{4AAC30DE-2757-4a42-BD3F-E6C4713581FA}.ClientEnd
AssetModelCatalogue
{0DA534C6-ACF6-48ab-A8DB-496BB661F459}.SupplierEnd
ErpPOLineItems
{6A15A364-6A16-4777-8E7A-E9C7ECF79B32}.SupplierEnd
ErpQuoteLineItems
{CE08E4FC-401D-4b25-B35D-68179BF78BEE}.SupplierEnd
Unit cost for an asset model from a specific supplier either for a unit cost or cost per unit length. Cost is for material or asset only and does not include labor to installconstruct or configure it.
unitCost
{DC8E5B7D-59BC-442b-BC44-1B7A7CC87F13}
All assets for this organisation role.
Assets
{D423536D-C2FE-462e-A473-046027941335}.ClientEnd
All ownerships of this owner.
Ownerships
{4276D5C7-95E8-44db-84E8-C01DA2834B6C}.ClientEnd
Assets
{7B58C937-A11B-4960-AD54-6431B15F1A97}.ClientEnd
Specification
{54F87E6E-39D6-413c-AF0C-2BC67DD4F008}.ClientEnd
Test standard which describes this asset string measurement.
TestStandard
{12941279-B146-4307-A6F4-220520C33D5E}.SupplierEnd
Kind of string useful in asset domain.
kind
{AE564014-FF5C-4981-AC45-326E6D774FB2}
Kind of analog representing temperature or pressure related to an asset.
kind
{AD9D9896-7DF5-4793-8CAF-73105F4ACEB6}
A set of lab test results produced by this test lab.
LabTestDataSet
{2E1C1072-F34D-447f-A661-8FC9A06E3F6D}.ClientEnd
Specimen taken by this sample taker.
Specimen
{B057FDCC-0EE2-422a-A257-ADAE38F4BB01}.ClientEnd
All Crews having this Assignment.
Crews
{B597E5EE-DEFD-46c2-9B5C-1B4B22EA8086}.ClientEnd
Period between the assignment becoming effective and its expiration.
effectivePeriod
{82CE2EE1-A6EA-4d87-B8B7-32893B2D3F52}
Asynchronous machine dynamics model used to describe dynamic behaviour of this asynchronous machine.
AsynchronousMachineDynamics
{BA360C66-0AA8-4cb9-9E9B-1BF747B40AFC}.ClientEnd
Indicates the type of Asynchronous Machine motor or generator.
asynchronousMachineType
{826DCE19-F54E-424d-A189-2396769F998F}
Efficiency of the asynchronous machine at nominal operation as a percentage. Indicator for converter drive motors. Used for short circuit data exchange according to IEC 60909.
efficiency
{51FACBB4-CB35-46a8-A0B9-6482118D1FC7}
Nameplate data indicates if the machine is 50 Hz or 60 Hz.
nominalFrequency
{F054A7B9-4A3B-4482-A339-AB83085A29F1}
Nameplate data. Depends on the slip and number of pole pairs.
nominalSpeed
{6D8C09B8-E824-41d6-8492-1D59EA766F20}
Rated mechanical power Pr in IEC 609090. Used for short circuit data exchange according to IEC 60909.
ratedMechanicalPower
{78EDFD71-FC20-44e4-AE1C-99B5C285C54E}
Damper 1 winding resistance.
rr1
{40B6255C-EC7A-4349-9F87-08C0A093611A}
Damper 2 winding resistance.
rr2
{6F5C5A3A-C7FA-42b8-83A1-430D4EB4EA9A}
Transient rotor time constant greater than tppo.
tpo
{5CE90029-71A1-495b-BA37-BC57015E6E18}
Subtransient rotor time constant greater than 0.
tppo
{B2EFC713-160B-4eb9-82D7-4D72F4628850}
Damper 1 winding leakage reactance.
xlr1
{2D9587B7-651E-41fd-BC62-06E2568BE5B5}
Damper 2 winding leakage reactance.
xlr2
{9148BA51-4D09-4ab6-8E8D-EFE8A9657B75}
Magnetizing reactance.
xm
{9327DEB3-9DF5-4261-ABB1-3EFBCB396B51}
Transient reactance unsaturated greater than or equal to xpp.
xp
{766CAB36-4AC9-46b8-ADA8-306DA127FE42}
Subtransient reactance unsaturated.
xpp
{1AAA2103-E4D1-4668-84AF-F50E88A5D4CF}
Synchronous reactance greater than xp.
xs
{DFA22160-690B-4e57-A11B-5A823C1A37EA}
Asynchronous machine to which this asynchronous machine dynamics model applies.
AsynchronousMachine
{BA360C66-0AA8-4cb9-9E9B-1BF747B40AFC}.SupplierEnd
Mechanical load model associated with this asynchronous machine model.
MechanicalLoadDynamics
{2E5B6ACA-CE14-4ff7-A95C-1961DD872622}.ClientEnd
Turbinegovernor model associated with this asynchronous machine model.
TurbineGovernorDynamics
{6884320E-0E98-4316-859C-B1DF18D6ED2A}.ClientEnd
Wind generator type 1 or type 2 model associated with this asynchronous machine model.
WindTurbineType1or2Dynamics
{28333A44-C128-4d1f-91A9-C4815D05A17C}.ClientEnd
Damper 1 winding resistance.
rr1
{52C7D4CA-BCD4-46ab-AABD-67ADA4E8E80C}
Damper 2 winding resistance.
rr2
{6E788D7D-119B-4b41-879E-A561AC49CA86}
Damper 1 winding leakage reactance.
xlr1
{FC3820FB-E7D7-45de-859C-1B6AD4FC148F}
Damper 2 winding leakage reactance.
xlr2
{7855AF2E-4E4F-4595-B225-A678B577EA3A}
Magnetizing reactance.
xm
{872CD8BF-EA9E-4395-A522-4803021DEA77}
Transient rotor time constant iToi gt AsynchronousMachineTimeConstantReactance.tppo. Typical value 5.
tpo
{60FE5275-E98C-4dda-BC25-2AB8939ED89E}
Subtransient rotor time constant iToi gt 0. Typical value 003.
tppo
{9AF6DF73-4546-4e1f-B24B-F4D820C2E4E6}
Transient reactance unsaturated iXi gt AsynchronousMachineTimeConstantReactance.xpp. Typical value 05.
xp
{4E9DA366-FEC5-4e63-8D7F-4B1CC21E3FB3}
Subtransient reactance unsaturated iXi gt RotatingMachineDynamics.statorLeakageReactance. Typical value 02.
xpp
{F9E7E7CF-9390-47fd-AD96-379A21668D71}
Synchronous reactance iXsi gt AsynchronousMachineTimeConstantReactance.xp. Typical value 18.
xs
{BDD25953-4C09-4ca8-9B66-836E93830D62}
Parameter of this proprietary userdefined model.
ProprietaryParameterDynamics
{D22E87BF-F1D2-49ef-B02C-1F3F666251B8}.ClientEnd
Kind of atmospheric analog.
kind
{39FDC1D5-CFCE-48f0-B0BF-48A227DFBF65}
The maximum altitude of the phenomenon.
altitude
{206D7D27-D0FB-48ad-9158-6963F4CBF74F}
The base altitude of the phenomenon.
base
{876230B5-9A30-49d1-A573-51D2748B4E2B}
The direction the phenomenon is moving.
direction
{BE89CE8A-A3C2-4637-9B02-E71891B34168}
The maximum percentage coverage
maxCoverage
{F3C0D1A0-EDB0-4ba2-B329-4963A90CBC9E}
The minimum percentage coverage
minCoverage
{CAB91E48-503C-4d29-B281-7B9015933461}
The speed of the phenomenon
speed
{CDEFD06D-00FA-4ccc-A063-FB35C849460D}
MarketDocument
{56078672-F984-4496-A0EE-E53993207A8C}.ClientEnd
TimeSeries
{12A8F6B9-95CA-4bbd-9E17-5C2026B33D51}.SupplierEnd
MktUserAttribute
{3FB05567-9270-4fcb-8976-9ADA1813AE21}.SupplierEnd
TimeSeries
{5894E7F6-D7B8-4658-85C7-272AEC744D46}.SupplierEnd
All activity records with this author.
ActivityRecords
{C7B3A827-5B49-4da5-95A3-4EE7D07568AA}.SupplierEnd
All documents of this this author.
Documents
{335F0BDA-9420-40ee-B636-5FAD6485F1BB}.SupplierEnd
Auxiliary agreement regulating this account.
AuxiliaryAgreement
{0C6F4AB9-5500-4b13-8C5F-C6441811D257}.ClientEnd
All charges levied on this account.
Charges
{76534BC8-9FAC-414b-8310-44B6AD265341}.SupplierEnd
All payments against this account.
PaymentTransactions
{DF6F03CB-FADB-4f4b-BE70-872C51D6376A}.SupplierEnd
The total amount currently remaining on this account that is required to be paid in order to settle the account to zero. This excludes any due amounts not yet paid.
balance
{AC8E0A15-A0A8-4f12-9563-974C3DBE619D}
Current amounts now due for payment on this account.
due
{15F66F3A-7CE9-49b1-AD61-C593D32E8F4B}
Details of the last credit transaction performed on this account.
lastCredit
{3DE6E5F8-C1CA-4883-8AFC-90361B6D1A12}
Details of the last debit transaction performed on this account.
lastDebit
{55597EAA-BEF0-4615-87B6-823B1FB2B83C}
The initial principle amount with which this account was instantiated.
principleAmount
{B0C1A99C-CE88-4c6c-A4FE-DDE0E7842611}
All auxiliary accounts regulated by this agreement.
AuxiliaryAccounts
{0C6F4AB9-5500-4b13-8C5F-C6441811D257}.SupplierEnd
Customer agreement this nonservice related auxiliary agreement refers to.
CustomerAgreement
{4B0AFE27-A288-4e9f-A8F4-CA0675EB971D}.ClientEnd
The interest per annum to be charged prorata on AuxiliaryAccount.dueArrears at the end of each payCycle.
arrearsInterest
{8D725569-1FF9-4abc-B4C2-EBA502183CE8}
The fixed amount that has to be collected from each vending transaction towards settlement of this auxiliary agreement. Note that there may be multiple tokens vended per vending transaction but this is not relevant.
fixedAmount
{324167D0-1FEF-4817-99D1-93CD403EB07D}
The minimum amount that has to be paid at any transaction towards settling this auxiliary agreement or reducing the balance.
minAmount
{F72DC552-EDE8-4c72-8414-837C1372D8A8}
The percentage of the transaction amount that has to be collected from each vending transaction towards settlement of this auxiliary agreement when payments are not in arrears. Note that there may be multiple tokens vended per vending transaction but this is not relevant.
vendPortion
{C9437D9A-8E1E-4cac-8491-C8AD1C7E4B13}
The percentage of the transaction amount that has to be collected from each vending transaction towards settlement of this auxiliary agreement when payments are in arrears. Note that there may be multiple tokens vended per vending transaction but this is not relevant.
vendPortionArrear
{2442CFE1-3D65-466c-9830-32079DA6D711}
AuxillaryValues
{F527F4CB-0C66-43c2-A209-EF39AAF43B83}.SupplierEnd
marketType
{A0C6602F-B884-4df3-A509-A83D8865DBFD}
The Terminal at the equipment where the AuxiliaryEquipment is attached.
Terminal
{43A2A194-FB7E-4b55-8C73-A2E6C7AA2BF4}.SupplierEnd
RegisteredGenerator
{B773A97C-0734-453a-BE6C-701847C433D6}.SupplierEnd
RegisteredLoad
{E8E1ADFD-2A7D-4748-8265-3F63BD1FED9B}.SupplierEnd
AuxillaryCost
{F527F4CB-0C66-43c2-A209-EF39AAF43B83}.ClientEnd
FiveMinAuxillaryData
{6B36C00F-62F3-49c3-998C-F5EDD88A0CA8}.ClientEnd
TenMinAuxillaryData
{FBA403AA-DCD7-404a-9D19-752C36A45A12}.ClientEnd
noLoadCostEligibilityFlag
{629AD235-91A2-4581-88FE-459530081573}
startUpCostEligibilityFlag
{86402FE6-5A7A-4b51-B437-4D7DB00B9AB2}
UnavailablitySchedule
{A2312A8D-C0CB-4b47-98F8-79E9ADD45A56}.ClientEnd
The period of time for which the plan is valid.
validPeriod
{A088B182-984A-4ac1-BD52-816F4BA9968F}
High power limit.
highPowerLimit
{FD4F7DF7-0B32-44d4-9009-7700422B72C0}
Incore thermal time constant.
inCoreThermalTC
{550DE289-6D8D-424c-AB23-9B8B8CEFB1BA}
Low power limit.
lowPowerLimit
{7D7217B4-DDF4-49f6-A098-6F7BADF39FD9}
Initial lower limit.
lowerLimit
{3AC86890-00F9-41d5-BC36-AEA2A28920F7}
Pressure limit.
pressureLimit
{EDEA4C55-F054-4c74-BDE5-C776643DDABD}
Pressure setpoint time constant.
pressureSetpointTC1
{0CA605BA-5591-4f91-9D49-0BD0DCD5F3E5}
Pressure setpoint time constant.
pressureSetpointTC2
{1EE021B1-4FDC-459e-B0B1-1E514971B80E}
Coefficient for modelling the effect of offnominal frequency and voltage on recirculation and core flow which affects the BWR power output.
rfAux1
{E1BCDE63-3368-463c-8FAC-C6A8180163E4}
Coefficient for modelling the effect of offnominal frequency and voltage on recirculation and core flow which affects the BWR power output.
rfAux2
{C67C15E0-7617-4cef-8350-73C4AF657ECF}
Coefficient for modelling the effect of offnominal frequency and voltage on recirculation and core flow which affects the BWR power output.
rfAux3
{002B51A6-6E50-475a-A8E5-E4CEDB943AAF}
Coefficient for modelling the effect of offnominal frequency and voltage on recirculation and core flow which affects the BWR power output.
rfAux4
{BBECA461-4205-4612-B787-A46C3EB8CB63}
Coefficient for modelling the effect of offnominal frequency and voltage on recirculation and core flow which affects the BWR power output.
rfAux5
{F274E3B5-011E-4dea-BD43-618A502EE99E}
Coefficient for modelling the effect of offnominal frequency and voltage on recirculation and core flow which affects the BWR power output.
rfAux6
{38D7F89E-3572-44f0-88CA-44FF830E36AD}
Coefficient for modelling the effect of offnominal frequency and voltage on recirculation and core flow which affects the BWR power output.
rfAux7
{D221528C-1320-47a6-8863-14BD29F64411}
Coefficient for modelling the effect of offnominal frequency and voltage on recirculation and core flow which affects the BWR power output.
rfAux8
{6113CAF7-7FDA-4431-88E5-F2A5C2B65ACC}
Rod pattern.
rodPattern
{61FA6DC6-92D1-4a4d-AB74-2EB660BABF38}
Initial upper limit.
upperLimit
{7D050333-09EF-487e-92E8-E1603CFD27FD}
All BankAccounts this Bank provides.
BankAccounts
{239365BB-20C7-41e5-B131-81EC3DE7F529}.ClientEnd
Bank that provides this BankAccount.
Bank
{239365BB-20C7-41e5-B131-81EC3DE7F529}.SupplierEnd
ServiceSupplier that is owner of this BankAccount.
ServiceSupplier
{A4F61027-A9D2-47ab-AAEA-74678D39E4DE}.ClientEnd
SecurityConstraintSum
{8FF929E3-7DF8-484e-9AE6-E78FD919B4C1}.SupplierEnd
The base frequency.
frequency
{80C75B75-855F-44af-9846-BE082114E41E}
Value used as base power.
basePower
{9F2DC83B-B801-4b29-BD57-4781BD53A50A}
All qualities of this reading.
ReadingQualities
{DD6190AA-B446-4216-8E50-3E7421E80344}.ClientEnd
Start and end of the period for those readings whose type has a time attribute such as billing seasonal or forTheSpecifiedPeriod.
timePeriod
{C25B71A6-CEC6-4dec-B290-ABF3D327854F}
All conducting equipment with this base voltage. Use only when there is no voltage level container used and only one base voltage applies. For example not used for transformers.
ConductingEquipment
{B21687D9-2B46-4880-B016-06CCFA215EC3}.SupplierEnd
A network asset deployment at this base voltage level.
NetworkAssetDeployment
{EEECBAA7-1891-4130-A184-0EB99FA07C16}.ClientEnd
The topological nodes at the base voltage.
TopologicalNode
{6F37A2BE-FB37-4a6c-8BB1-CFC6690C1867}.ClientEnd
Transformer ends at the base voltage. This is essential for PU calculation.
TransformerEnds
{DEF1E6AE-B7B9-43bf-9A91-E4BFC453DC4D}.ClientEnd
The voltage levels having this base voltage.
VoltageLevel
{F610FDC8-D98D-4367-99A9-E9CA1C8A8CC5}.ClientEnd
The power system resources base voltage. Shall be a positive value and not zero.
nominalVoltage
{D37DA22A-916B-4a33-88AB-B77C229DB882}
All time schedules for this work or work task.
TimeSchedules
{43F7FE4D-DD21-436e-B70A-E2FCDD0B6928}.SupplierEnd
All activity records for this work or work task.
WorkActivityRecords
{916C5FEE-0A53-4844-A34C-EA28BF6FA153}.SupplierEnd
Location for this worktask.
WorkLocation
{4674DC66-FC6D-4b4e-B78A-2BA63838F75D}.SupplierEnd
Kind of work.
kind
{DA7282A1-DD17-4914-B04D-33479EB8974D}
Priority of work.
priority
{4CE5B82E-879A-46f3-9D6E-19F44D97084B}
Kind of work status.
statusKind
{A4C16162-A8D5-4e82-840B-700281305CCE}
Multiplier for value1.
value1Multiplier
{BC6A428D-4EE4-4fbf-A1FA-686812174A74}
Value1 units of measure.
value1Unit
{37C7E9FF-F129-44a3-BCCA-37E3777EBA36}
Multiplier for value2.
value2Multiplier
{333B8BA1-3E71-485a-A261-F73256259651}
Value2 units of measure.
value2Unit
{4925B79C-CB74-46be-8D24-939D06B46582}
The current state of the battery charging full etc..
batteryState
{4333D713-5396-457b-9CA8-E9472945B301}
Full energy storage capacity of the battery. The attribute shall be a positive value.
ratedE
{EB8342BE-510F-4246-935B-61E05FCC80DF}
Amount of energy currently stored. The attribute shall be a positive value or zero and lower than BatteryUnit.ratedE.
storedE
{A40F9768-CA75-4ded-AC08-E3FBA589CF1F}
Circuit
{38C0C28C-00BF-4529-940D-5007F17FBB86}.ClientEnd
Substation containing the bay.
Substation
{51152F4A-1B03-451f-BA84-6A05A6AE1630}.SupplierEnd
The voltage level containing this bay.
VoltageLevel
{5E328091-5BC1-4fa8-9BA3-F087A215492A}.ClientEnd
Breaker configuration.
breakerConfiguration
{94BB9838-29AB-4afe-853A-3BD683EF6B09}
Busbar configuration.
busBarConfiguration
{696CC695-DE24-423a-9CD6-A9FED27803F8}
multiplier
{0866792E-8BCF-46b9-B5EB-78A00420DC3C}
unit
{03C0AF47-48E3-4a55-ADCF-9F68085984AC}
ActionRequest
{FCF33735-6427-4091-BCD8-269E10C726B2}.ClientEnd
BidHourlySchedule
{A5FE93CE-0535-412b-BE49-3124C08220F0}.ClientEnd
ChargeProfiles
{ADDC9B96-D85F-46b2-A697-B0712376B748}.SupplierEnd
EnergyMarket
{728667DC-DD4E-4059-AE1B-FBA6AD106FDB}.SupplierEnd
MarketParticipant
{4483FC15-4087-4afd-8766-1D708647568D}.SupplierEnd
MitigatedBid
{41CDA34B-D1DA-4d10-BD9C-9ACD84F95C4F}.ClientEnd
MitigatedBidSegment
{BB5D09A6-5901-41e0-9C70-FEA07F4C897A}.SupplierEnd
A bid comprises one or more product bids of market products
ProductBids
{BCC6B1A9-977E-41f0-9C3A-DDB18F4AA27F}.ClientEnd
RMRDetermination
{20A022E9-69A4-4231-A566-82296460EFB1}.ClientEnd
The market type DAM or RTM.
marketType
{0AD79637-6091-4791-A753-5B49A0506242}
PnodeDistributionFactor
{92BD0FDA-3BFA-4ea4-9233-9C19F31CCB39}.SupplierEnd
ProductBid
{566D5A4B-E23C-4c3e-81A6-C484F10859CC}.ClientEnd
MarketProduct
{9E7BFD17-29EA-44f9-8314-8B82238242CC}.ClientEnd
ResourceBid
{1733E069-3742-4625-B384-DB2661EDD78B}.ClientEnd
ProductBid
{ED4A9CB4-F670-45e4-B569-BC258596026F}.SupplierEnd
Bid
{A5FE93CE-0535-412b-BE49-3124C08220F0}.SupplierEnd
MarketProduct
{82238162-E851-4fa8-8103-3D73229CE310}.ClientEnd
Bid Ceiling MWH
bidCeiling
{F9E6D809-182F-4c9a-B035-F1D3D54BDA72}
Bid Ceiling MWH for generic AS versus a specific market product
bidCeilingAS
{3FB7D4D0-E85F-47fc-AE95-55335F2E35C1}
Bid Floor MWH
bidFloor
{DAE1C9D9-9034-42fe-8D9F-4C70AA4EC969}
Bid Floor MWH for generic AS versus a specific market product
bidFloorAS
{8F6EE80C-171F-4501-953C-53A40DB2663A}
Bid Default PriceMWH
defaultPrice
{D88F9B8A-638B-4ae3-81E1-7AD10C0BD999}
Market Type of the cap DAM or RTM
marketType
{82B18371-981D-420b-8A6A-C52BFF3C835A}
BidSchedule
{BD02A659-7286-4690-A25C-BEBAA6BBC2F8}.SupplierEnd
BidPriceCurve
{BD02A659-7286-4690-A25C-BEBAA6BBC2F8}.ClientEnd
ProductBid
{E6A900FF-246B-49e3-8F19-A2DBF2BB4BB5}.ClientEnd
BID Type I Initial Bid F Final Bid
bidType
{83CAD08F-2EFA-4e2b-9F65-0D3711119AAC}
Mitigation StatusS Mitigated by SMPM because of misconductL Mitigated by LMPM because of misconductR Modified by LMPM because of RMR rulesM Mitigated because of misconduct both by SMPM and LMPMB Mitigated because of misconduct both by SMPM and modified by LMLM because of RMR rulesO original
mitigationStatus
{1468C65A-F2D8-4810-B207-F5FEAB9684AB}
AdjacentCASet
{B2038A6D-F6D7-42bf-BD3F-0D4F0A7C79E4}.ClientEnd
HostControlArea
{A54AFE0A-D986-4114-B72E-9243C90ABC98}.ClientEnd
ProductBid
{62141B29-E60E-480d-B668-C305C09264D7}.ClientEnd
SubControlArea
{8B909238-F00E-4f58-A22C-21C482041260}.ClientEnd
TransmissionContractRight
{C020B2A4-890F-455d-8C69-8B0612C789BB}.ClientEnd
This is a YN flag for a selfschedule of a resource per market per date and hour using a specific TR ID. It indicates whether a selfschedule using a TR is balanced with another selfschedule using the same TR ID.
balancingFlag
{AC993C70-50CE-483f-A753-C385580DB4C8}
bidType has two types as the required output of requirements and qualified predispatch.
bidType
{C1025F35-7D45-4883-853E-0B0D92857365}
This is a YN flag for a selfschedule of a resource per market per date and hour using a specific TR ID. It indicates whether a selfschedule using a TR has scheduling priority in DAMRTM.
priorityFlag
{1FE4E4F1-482A-4383-B4AB-BDDE2FE75BD2}
Indication of which type of self schedule is being referenced.
referenceType
{29891CC3-A678-4649-AC69-557165041C41}
This attribute is used to specify if a bid includes a self sched bid. If so what self sched type is it. The possible values are shown as follow but not limited toETC Existing transmission contractTOR Transmission ownership rightRMR Reliability must runRGMR Regulatory must runRMT Relaiability must takePT Price takerLPT Low price takerSP Self provisionRA Resource adequacyThis attribute is originally defined in the BidSelfSched class
selfSchedType
{2D4244FF-52C3-46dd-B19F-1D2CD73F8D3D}
updateType
{B7BC95D2-EFDB-428e-AF3E-12D9F2518CF4}
GeneratingBids
{DBBF1D0E-B376-4e47-A369-EB0EB0F211C5}.ClientEnd
Communication addressing for a Bilateral Table used by a ICCP data provider or consumer.
CommunicationLink
{F8B558CB-826C-44f6-8B37-E168629E4395}.ClientEnd
Agreement to information subscriber.
ConsumerBilateralExchange
{11CB6E16-3BAB-4d1f-A946-6B01C61E757D}.ClientEnd
ICCP information in a Bilateral table that will be exposed to a remote peer.
ProvidedBilateralIOPoint
{D71D178C-4ECF-4cf5-A2F9-02324DC52065}.ClientEnd
Agreement to information provider.
ProviderBilateralExchange
{82F28F28-5401-456b-9A8A-F036863F7A07}.SupplierEnd
Subscriber of information from a remote peer.
Consumer
{11CB6E16-3BAB-4d1f-A946-6B01C61E757D}.SupplierEnd
Provider of information to a remote peer.
Provider
{82F28F28-5401-456b-9A8A-F036863F7A07}.ClientEnd
Maximum total transmission congestion charges in monetary units
totalTranChargeMax
{0F8E9ADB-54D9-4632-96FC-B4DBAB322F47}
A BillDeterminant can have 0n ChargeComponent and a ChargeComponent can associate to 0n BillDeterminant.
ChargeComponents
{57B8DDF0-7B94-45b0-B5EF-5CDB1744BC85}.ClientEnd
ChargeProfile
{1ACFDE89-AF63-4cb5-830B-04C1DDECED28}.ClientEnd
ChargeProfileData
{AB69F7A6-CE60-4b02-AA54-24E729B7293B}.SupplierEnd
MktUserAttribute
{3D3E108F-27E6-46ff-B50B-1A3A9365B887}.SupplierEnd
BlockDispatchOrder
{255D77CC-5A1D-4514-B6F4-972B9DFEDB7F}.ClientEnd
EnergyGroup
{3BC3FBEE-55AB-447d-A7C2-53E7591E1DC1}.SupplierEnd
BlockDispatchComponent
{255D77CC-5A1D-4514-B6F4-972B9DFEDB7F}.SupplierEnd
p
{5C507EF2-C628-49a1-B4C3-EC7C12ACC184}
Delay
{5B3BF302-273E-40f1-A888-A5FFEDE8F08F}.ClientEnd
VSCtype1
{EA954A70-DF63-404b-98A9-063F5571B46A}.SupplierEnd
MktACLineSegmentEndAFlow
{C683E41C-A3EC-4316-BD46-D25F17ED532B}.SupplierEnd
MktACLineSegmentEndBFlow
{977B9C6C-1464-4035-A670-FC92869C7E0B}.SupplierEnd
MktPowerTransformerEndAFlow
{6B82670E-C342-4f85-A215-9BB510562254}.SupplierEnd
MktPowerTransformerEndBFlow
{D9B28EF9-4971-4bb7-B90B-5D0EF7D92756}.SupplierEnd
MktSeriesCompensatorEndBFlow
{A6C6B3F9-7B48-423b-99F5-774083959E01}.SupplierEnd
MktSeriresCompensatorEndAFlow
{5C0AAF99-2DB3-4ce7-8154-9C37E518CB30}.SupplierEnd
PinBranchGroup
{CB739CC6-8BA5-4ceb-BD00-62D8654B263A}.ClientEnd
The maximum active power flow.
maximumActivePower
{9BE347F3-B589-40b6-A23A-7C14B8A90CB8}
The maximum reactive power flow.
maximumReactivePower
{3E4B96F3-6FD4-497e-9C9A-23719BCDA9C8}
The minimum active power flow.
minimumActivePower
{211199A7-23ED-4b64-9F0B-1982FE3432C9}
The minimum reactive power flow.
minimumReactivePower
{5FCBF43B-F5AB-4f14-95DD-45D4AACCF477}
The terminal to be summed.
Terminal
{D1FC8C2B-42F2-4d32-95B9-1C5FE76F9BAD}.SupplierEnd
The transition time from open to close.
inTransitTime
{9F9445D9-22B1-4328-A4D5-C3B872F33DE2}
Phase trip rating.
phaseTrip
{B3341220-BC03-4cbf-9EDD-9CC98BC08B3F}
The reporting group to which this bus name marker belongs.
ReportingGroup
{37254491-51A1-43fd-8EA9-325A03BB2B8F}.SupplierEnd
The terminals associated with this bus name marker.
Terminal
{EE3B8B0F-5740-4380-91F9-563BFD5783D7}.SupplierEnd
A user defined topological node that was originally defined in a planning model not yet having topology described by ConnectivityNodes. Once ConnectivityNodes has been created they may linked to user defined ToplogicalNdes using BusNameMarkers.
TopologicalNode
{33820695-1C8F-47c2-96B4-E770AF9728EF}.SupplierEnd
A VoltageControlZone is controlled by a designated BusbarSection.
VoltageControlZone
{77D2F437-1BDA-463c-AC93-F25EAC4B04AF}.SupplierEnd
Maximum allowable peak shortcircuit current of busbar Ipmax in IEC 609090. Mechanical limit of the busbar in the substation itself. Used for short circuit data exchange according to IEC 60909.
ipMax
{2E32481A-0F4F-4da0-B81F-8C1E6543F0CD}
Rated current.
ratedCurrent
{3B7D026A-7745-455d-B83E-893E1E2164B8}
Rated voltage.
ratedVoltage
{3F29B322-3264-420a-A5D5-5467777BBEBB}
BushingInsulationPFs
{77D3489A-738D-47cf-B225-42A2975A2FF3}.SupplierEnd
Fixed contact of interrupter to which this bushing is attached.
FixedContact
{C2A54CC4-02E6-4205-BF7A-A8BAE99CDBAA}.ClientEnd
Moving contact of interrupter to which this bushing is attached.
MovingContact
{04E4A3E7-BA8B-450c-A235-995CEAB16935}.ClientEnd
Terminal to which this bushing is attached.
Terminal
{1E353A86-0A4E-4184-8B22-CE084F0A6AA8}.SupplierEnd
Factory measured capacitance measured between the power factor tap and the bushing conductor.
c1Capacitance
{242160B4-1253-47f0-8CE8-259BD0368A40}
Factory measured insulation power factor measured between the power factor tap and the bushing conductor.
c1PowerFactor
{A938536A-EEBD-4afe-99B3-EAF67D499ADA}
Factory measured capacitance measured between the power factor tap and ground.
c2Capacitance
{27BB799E-BC81-4e20-9101-79D8C755030B}
Factory measured insulation power factor measured between the power factor tap and ground.
c2PowerFactor
{6731CC9D-A0C1-45f5-B228-31AC10CA3A54}
Kind of insulation.
insulationKind
{29CE8562-3D27-47a0-879E-7C180E0AB035}
Rated current for bushing as installed.
ratedCurrent
{1C13CB85-F589-4a6f-83C4-2FB8A15F355D}
Rated impulse withstand voltage also known as BIL Basic Impulse Level.
ratedImpulseWithstandVoltage
{5FBE3610-C895-4087-B528-DD760BF513B9}
Rated linetoground voltage. Also referred to as Uy on bushing nameplate.
ratedLineToGroundVoltage
{C2C35B35-C556-4613-A060-B6B59752A5AE}
Rated voltage. Can be referred to as Um system voltage or class on bushing nameplate.
ratedVoltage
{40F3B551-C8F3-4cb5-BBD3-47CDE5F3F1AC}
Bushing
{77D3489A-738D-47cf-B225-42A2975A2FF3}.ClientEnd
TransformerObservation
{DE9B5DD5-948F-45ee-967F-41C9BA2892AE}.SupplierEnd
status
{1F38BFA9-0F10-4b5e-B377-52D9F803F29F}
Kind of test for this bushing.
testKind
{93705AD4-9DF6-4d8e-A55E-BCC4ECED0BB1}
Projects
{3E0CE628-2617-4405-B164-788B1A9E8408}.SupplierEnd
Works
{9F2397D7-15D3-42a6-9C58-F7D06A58CEAF}.SupplierEnd
status
{959E6488-8643-413b-86C3-E47079565E8D}
An air compressor may be a member of a compressed air energy storage plant.
AirCompressor
{3B7A359B-1CB5-47fc-A551-592BDCAF20F2}.SupplierEnd
A thermal generating unit may be a member of a compressed air energy storage plant.
ThermalGeneratingUnit
{22CD9D0F-3294-4b03-B8CD-2834FB574022}.SupplierEnd
The rated energy storage capacity. The attribute shall be a positive value.
energyStorageCapacity
{8D0F81BA-B2B9-4e48-A3FD-10B5F6DDCBAD}
The CAES plants gross rated generating capacity. The attribute shall be a positive value.
ratedCapacityP
{A0B5E346-09F5-4fe5-8003-8F3DD9772334}
CSCtype1
{C028CE96-6309-4883-89A5-E1B91BD9EF2D}.SupplierEnd
Delay
{CBF65696-C189-4ab1-A0C3-34B7539B34A1}.ClientEnd
CSCtype1
{AF476A35-E037-4efb-9B03-02299D031FDA}.SupplierEnd
Delay
{AF4309DA-72A5-4b21-80EC-9653AF6D0620}.ClientEnd
Edition of CIGRE standard.
standardEdition
{D03822B4-79F1-4d29-9471-176EDB767B40}
CIGRE standard number.
standardNumber
{76DAA2A9-DD76-45e3-A650-D088B3607FD3}
CongestionRevenueRight
{A6EF647F-83D1-46c2-83BA-498C5AC0EE5D}.ClientEnd
CongestionRevenueRight
{80E51726-F69E-4014-ACD6-C80A45B842AE}.SupplierEnd
Kind of role the organisation is with regards to the congestion revenue rights.
kind
{817F0F6C-32E3-428e-AF3D-E177CD4B0ABB}
Status of congestion revenue rights organisation role.
status
{D6062590-97D9-433a-902E-EF85BB9A46CD}
CongestionRevenueRight
{02556F1B-1A48-4bb0-A787-9F04C918321D}.ClientEnd
Sink
{6840ECDE-F677-428f-9118-D01BDF989AE0}.ClientEnd
Source
{C97DA9A4-D136-4894-A6A2-CA207A447300}.ClientEnd
Dollar amount quantity x clearingPrice
amount
{A6570274-EA82-4585-B682-BA080CABD479}
Clearing price of a CRR
clearingPrice
{9D3642DA-F58B-4d4c-84D6-0B30CE29E38D}
Current source converter to which current source converter dynamics model applies.
CSConverter
{923E9B98-7F14-449a-BFFF-B62D5A7D53DF}.SupplierEnd
Parameter of this proprietary userdefined model.
ProprietaryParameterDynamics
{BDBA0EFE-6EA8-41c4-B3E1-5DE008753AF0}.SupplierEnd
CCAinverter
{C028CE96-6309-4883-89A5-E1B91BD9EF2D}.ClientEnd
CCArectifierControl
{AF476A35-E037-4efb-9B03-02299D031FDA}.ClientEnd
IdcInverterControl
{339D9BE1-B6FE-4ebd-B884-707C77DA6C91}.ClientEnd
IgnAngleContInverter
{2F9E4B3A-A9A7-43b4-8FAD-55865942D1B6}.ClientEnd
A combustion turbine may have an active power versus ambient temperature relationship.
CombustionTurbine
{BA81A687-7485-4703-80D8-BDAF921D5E98}.SupplierEnd
CompatibleUnits
{7E14ED1F-0F2B-406f-8316-5676CAE2C27A}.SupplierEnd
status
{CDA6347F-4E54-4cfe-8B8E-B1E8A9B89F34}
CompatibleUnits
{53544586-E3BD-4bd3-9885-4857731939B8}.SupplierEnd
The amount that a given contractor will charge for performing this unit of work.
bidAmount
{91FD99D5-6C69-41ef-9EDB-57A269F7ECBA}
status
{0727D6EF-8BF0-4d38-8E0D-AECD7DF306E5}
ChildCUGroups
{F2337009-71FC-4039-AA2C-3883E6E5090F}.SupplierEnd
CompatibleUnits
{8FAE377F-EEE5-44eb-962C-214341F7F3FE}.ClientEnd
DesignLocationCUs
{324E1A81-07DF-4842-8F2C-ED32F058D0AD}.ClientEnd
ParentCUGroups
{F2337009-71FC-4039-AA2C-3883E6E5090F}.ClientEnd
status
{93D57A4B-103F-4d7a-9D99-5BE2A6857863}
CULaborItems
{86DE1A8D-1A39-4b4c-ACFB-82676C3A39CC}.ClientEnd
status
{1E8FF0B9-AE52-4fa9-972E-5F4A7937CBA8}
CULaborCode
{86DE1A8D-1A39-4b4c-ACFB-82676C3A39CC}.SupplierEnd
CompatibleUnits
{289D7D61-564F-42e9-B83D-CB11520403E4}.SupplierEnd
QualificationRequirements
{5E0A5A68-F3A6-4607-B782-EC1790EB274A}.SupplierEnd
Estimated time to perform work.
laborDuration
{ED6A9917-8BFF-49de-ADCC-2FCCFE1DDFD0}
The labor rate applied for work.
laborRate
{96B902E1-9183-4316-BDA9-96E36A8FD113}
status
{07B6AF2C-70B7-45df-A5DE-90A1D7B32C79}
CompatibleUnits
{7B6A93BA-1EDF-4a37-AE20-76A155009833}.SupplierEnd
PropertyUnits
{EBAAAA49-96BE-4f07-8F12-EAF5BDD82A20}.ClientEnd
TypeMaterial
{5FD8B251-F630-475d-9DE8-4E62B3FDAF21}.SupplierEnd
Quantity of the TypeMaterial for this CU used to determine estimated costs based on a per unit cost or a cost per unit length specified in the TypeMaterial.
quantity
{B7865C97-BCCF-43a9-9374-C25AD5592D79}
status
{93FE8899-6378-464e-9825-65D411C30197}
CompatibleUnits
{05F15D8B-35FF-4170-9657-52306B692CE3}.SupplierEnd
TypeAsset
{855EE031-A0C0-4d02-9660-78C8C2427736}.SupplierEnd
Standard usage rate for the type of vehicle.
rate
{D035D616-0916-471c-8F7D-AE78C8E86312}
status
{B124700B-0497-4f85-BC8B-0DBDC8198770}
Kind of construction of this cable.
constructionKind
{4D9F5894-8A3B-4c56-9F9E-BFF1D7145990}
Diameter over the core including any semicon screen should be the insulating layers inside diameter.
diameterOverCore
{05C91266-DD15-4752-9B4B-290CCEDA7AAC}
Diameter over the insulating layer excluding outer screen.
diameterOverInsulation
{F57940EC-27FA-4a95-8C42-931C440DF9A2}
Diameter over the outermost jacketing layer.
diameterOverJacket
{36EA38E6-9187-4dce-AC76-EC5152CA0FC2}
Diameter over the outer screen should be the shields inside diameter.
diameterOverScreen
{4DCB270F-79BA-4b23-BE0D-F55312E45AD1}
Maximum nominal design operating temperature.
nominalTemperature
{691CB804-F1A4-43ed-A282-4C8A5DBE1C2A}
Kind of outer jacket of this cable.
outerJacketKind
{0F5A1D1C-E044-4a8e-841B-BAF54FBAB5F0}
Material of the shield.
shieldMaterial
{97FE3C2C-5C0F-43be-A86D-CAB3A36C9B69}
Order of a statistical calculation associated with this calculation method hierarchy.
CalculationMethodOrder
{00BBCC2C-664B-492b-A281-9999BD00D8C8}.ClientEnd
Measurement to which this calculation method hierarchy applies.
Measurement
{F91A2D8A-DA8C-4273-9073-224DE84F0F21}.ClientEnd
Measurement value to which this calculation method hierarchy applies.
MeasurementValue
{54A8E767-B481-4e4a-947E-047AC60B5490}.SupplierEnd
The calculation method hierarchy of which this order of statistical calculation is a member.
CalculationMethodHierarchy
{00BBCC2C-664B-492b-A281-9999BD00D8C8}.SupplierEnd
The statistical calculation done at this order.
StatisicalCalculation
{3472E24D-F0B4-42fa-AC2A-06A47816E2D7}.ClientEnd
Crafts
{921FF0C0-21D9-4312-8288-1512B1E7B653}.SupplierEnd
Crew
{A3C41283-0A33-4ee9-A5AA-105826F2A3B8}.SupplierEnd
WorkTasks
{99651776-E1FC-4685-A904-70049BEA9646}.SupplierEnd
status
{47F71C50-8EE5-4e39-A501-3EB1B1951763}
Date and time interval for which this capability is valid when it became effective and when it expires.
validityInterval
{03816E14-5056-49e1-9FAE-0577BE620316}
multiplier
{6B627C28-A1CA-4e5d-973E-F3AD555F9CCB}
unit
{20932C4A-6600-416b-B9C4-DCC7BD3FAA98}
multiplier
{D62CFC12-58FC-4949-A5A3-4AD5F5F76DB8}
unit
{25F43457-2958-4551-82D0-499592D2953A}
Payment tender this card is being used for.
Tender
{61A73D4C-E942-43c5-8D12-F351276DE012}.SupplierEnd
All shifts operated by this cashier.
CashierShifts
{C62261F0-61D6-4139-B0DA-87CAB071505B}.SupplierEnd
Electronic address.
electronicAddress
{1448C660-7C05-4dde-AB7A-593FDF7BE83E}
Cashier operating this shift.
Cashier
{C62261F0-61D6-4139-B0DA-87CAB071505B}.ClientEnd
Point of sale that is in operation during this shift.
PointOfSale
{5F23BDB7-8C52-4be9-BDFD-61927D2EA76C}.SupplierEnd
All Receipts recorded for this Shift.
Receipts
{3CC80665-07B4-4a5d-9D19-56F2B340FE1D}.SupplierEnd
All transactions recorded during this cashier shift.
Transactions
{2D10DF39-BE65-4644-A37D-1155967E0230}.SupplierEnd
The amount of cash that the cashier brings to start the shift and that will be taken away at the end of the shift i.e. the cash float does not get banked.
cashFloat
{499AA4FB-1471-4210-B0DA-21CD21E8AC1A}
Generic nameplate information associated with this catalog asset type.
AssetInfo
{9B683AA4-C622-4998-B81E-A7467D326D7B}.ClientEnd
CompatibleUnits
{29224EFF-E858-46a4-AF56-8007409442DC}.ClientEnd
ErpBomItemDatas
{3FB0DAAA-9E8C-499f-81CE-3F538433A48D}.SupplierEnd
ErpInventoryIssues
{AECF6503-964C-41a1-AA24-93AF8EF31369}.ClientEnd
ErpReqLineItems
{7F453A7B-93B5-4f12-8984-2FC06DB80EED}.SupplierEnd
Product asset model conforming to this catalog asset type.
ProductAssetModel
{2558E36F-4A9B-4eab-B70C-B1D8802138AE}.ClientEnd
TypeAssetCatalogue
{C03D47F2-A60F-4e08-BAA2-09494FC4FFE5}.SupplierEnd
Estimated unit cost or cost per unit length of this type of asset. It does not include labor to install construct or configure it.
estimatedUnitCost
{B4F70823-2AC7-4c7b-BBB7-8C1793012C79}
Kind of asset from enumerated list.
kind
{63B2EAF2-BBD6-4d65-BE9E-0DD758F0AFAF}
The value unit of measure and multiplier for the quantity.
quantity
{389C6A93-611C-4e9c-B2A6-3A3AEFEB9B7A}
Data objects contained in the dataset.
ChangeSetMember
{D718248A-D448-492a-AE40-8C6ED4992EB3}.ClientEnd
IncrementalDatasetArg
{4727D339-3136-4719-B7FF-3F8D5D00B334}.ClientEnd
NMProjectStage
{5C7D89EE-E6F6-4bc7-9B55-013A14F63C05}.ClientEnd
The project of the details of model changes.
NetworkModelProjectChangeVersion
{D0FD1813-3105-4ab3-AA49-9C2E1C71624E}.ClientEnd
Dataset containing the data objects.
Changeset
{D718248A-D448-492a-AE40-8C6ED4992EB3}.SupplierEnd
The CIM object holding the properties of this dataset context. Sometimes properties are not required and only the reference to the registered object is required.
PropertiesObject
{F527D24E-59B1-4748-B31A-660841060493}.SupplierEnd
The registered CIM object.
TargetObject
{950EB9DD-F3F6-405e-81C4-3D00B3ABD338}.SupplierEnd
Reading type for register values reportedcollected by this channel.
ReadingType
{D4257F98-65DB-49d2-B38F-C912709EE1BE}.ClientEnd
Register whose values are collectedreported by this channel.
Register
{BDCC2E66-6842-4911-B918-FE7BEF381847}.ClientEnd
All auxiliary accounts to which this charge has to be levied.
AuxiliaryAccounts
{76534BC8-9FAC-414b-8310-44B6AD265341}.ClientEnd
All subcomponents of this complex charge.
ChildCharges
{08FE2110-76C1-4a9f-B98F-426253A4F91B}.SupplierEnd
Tariff intervals to which this consumptionbased charge has to be levied.
ConsumptionTariffIntervals
{3C4455D4-C34E-4001-A555-8912924EE287}.ClientEnd
Parent of this charge subcomponent.
ParentCharge
{08FE2110-76C1-4a9f-B98F-426253A4F91B}.ClientEnd
Tariff intervals to which this timebased charge has to be levied.
TimeTariffIntervals
{0A0C819B-B021-48a1-BE23-8DEE728FFA6C}.ClientEnd
The fixed portion of this charge element.
fixedPortion
{15E75850-C511-4c5c-838E-29D81E275C75}
The kind of charge to be applied.
kind
{97CEDF1B-DFBB-4bec-A7D9-7E9C8847EA81}
The variable portion of this charge element calculated as a percentage of the total amount of a parent charge.
variablePortion
{0177EE2C-2DDD-4b9d-80E4-BBAC93AA2155}
A BillDeterminant can have 0n ChargeComponent and a ChargeComponent can associate to 0n BillDeterminant.
BillDeterminants
{57B8DDF0-7B94-45b0-B5EF-5CDB1744BC85}.SupplierEnd
A ChargeType can have 0n ChargeComponent and a ChargeComponent can associate to 0n ChargeType
ChargeTypes
{AB9918D4-8D8B-4024-A3BF-3455722AFD23}.ClientEnd
A ChargeGroup instance can have relationships with other ChargeGroup instances.
ChargeGroupChild
{0DEF88A8-6EA6-48a3-AC80-C41AB6B06EB2}.ClientEnd
A ChargeGroup instance can have relationships with other ChargeGroup instances.
ChargeGroupParent
{0DEF88A8-6EA6-48a3-AC80-C41AB6B06EB2}.SupplierEnd
A ChargeGroup can have 0n ChargeType. A ChargeType can associate to 0n ChargeGroup.
ChargeType
{26B46C92-D1DF-4b3a-8924-D21D9D817976}.ClientEnd
MktUserAttribute
{7E99E40A-D085-4ca0-9CA9-3E9E0C539B2A}.SupplierEnd
Bid
{ADDC9B96-D85F-46b2-A697-B0712376B748}.ClientEnd
BillDeterminant
{1ACFDE89-AF63-4cb5-830B-04C1DDECED28}.SupplierEnd
ChargeProfileData
{D009347D-F669-4ca5-8477-6551DC761278}.SupplierEnd
PassTroughBill
{7A4358BC-7C4E-4235-A405-C2C839499AA8}.SupplierEnd
BillDeterminant
{AB69F7A6-CE60-4b02-AA54-24E729B7293B}.ClientEnd
ChargeProfile
{D009347D-F669-4ca5-8477-6551DC761278}.ClientEnd
A ChargeType can have 0n ChargeComponent and a ChargeComponent can associate to 0n ChargeType
ChargeComponents
{AB9918D4-8D8B-4024-A3BF-3455722AFD23}.SupplierEnd
A ChargeGroup can have 0n ChargeType. A ChargeType can associate to 0n ChargeGroup.
ChargeGroup
{26B46C92-D1DF-4b3a-8924-D21D9D817976}.SupplierEnd
A MajorChargeGroup can have 0n ChargeType. A ChargeType can associate to 0n MajorChargeGroup.
MajorChargeGroup
{90202EBC-584B-4461-94E0-1F697B9901DA}.ClientEnd
MktUserAttribute
{FA4D0F9A-CFBA-4b39-8AF5-D8EDA0559E55}.SupplierEnd
Payment tender the cheque is being used for.
Tender
{96162BCD-6CF6-40e7-B42A-5D0EB89F2B16}.SupplierEnd
Details of the account holder and bank.
bankAccountDetail
{526A3707-985E-462e-8FFA-F383ECBAB845}
Kind of cheque.
kind
{7A48158E-EB1D-43ec-B568-545424B8E4E2}
EndBay
{38C0C28C-00BF-4529-940D-5007F17FBB86}.SupplierEnd
EndTerminal
{6876E705-D5F6-4c77-9072-D14AF881DA08}.SupplierEnd
The line segment to which the clamp is connected.
ACLineSegment
{2B7C9922-26A9-4218-8BDD-1098869C8600}.ClientEnd
ClampAction
{74C6F744-E53A-4fd0-BBA8-3531659CCC10}.SupplierEnd
JumperAction
{74BBE709-CFEF-40a9-A120-33F704608576}.SupplierEnd
The length to the place where the clamp is located starting from side one of the line segment i.e. the line segment terminal with sequence number equal to 1.
lengthFromTerminal1
{812CAF19-BD75-4aff-829A-B0D38FEC4817}
Clamp
{74C6F744-E53A-4fd0-BBA8-3531659CCC10}.ClientEnd
Switching action to perform
kind
{C5150C6B-F9FB-4f05-A614-AFFC5ADE5CFC}
multiplier
{CAB91FF9-BEA3-4206-8453-D957703207E5}
unit
{38101F30-DA56-4a03-8A0D-9206BC8363D5}
Analog which contributes to the definition of this classification condition.
EnvironmentalAnalog
{8B13B03E-D662-45ec-9CC3-71515B9D13CA}.ClientEnd
String measurement which contributes to the definition of this classification condition.
EnvironmentalStringMeasurement
{71F9989B-6173-4d71-B9F1-2184FCC3CEF5}.ClientEnd
Phenomenon classification to which this condition relates.
PhenomenonClassification
{0E97F0E1-C420-4b89-983A-670FE0F14582}.SupplierEnd
The duration of the of the condition in seconds
duration
{4E9DA946-BA47-490b-A874-477F89446371}
The test applied to the value.
test
{9BDE53DB-F87F-41b2-9085-73E4492D22CD}
Clearance associated with this clearance action.
Clearance
{DC4663C9-511F-45f1-93ED-28032F3DAC73}.SupplierEnd
Clearance action to perform.
kind
{AB65507D-9450-4d89-8138-EE69C858E7B9}
Clearance action associated with this clearance.
ClearanceAction
{DC4663C9-511F-45f1-93ED-28032F3DAC73}.ClientEnd
All power system resources tagged through this clearance.
TaggedPSRs
{65134A4B-0FD0-4c17-A353-8696C19D36F6}.SupplierEnd
The type of the cloud as defined by the CloudKind enumeration.
kind
{1D7D13FE-44D4-48f6-9D80-C9A9D6F77FD1}
AggregateNode
{423960E1-ADF0-47a5-B371-AA4201541FC9}.ClientEnd
HostControlArea
{334067AA-47A1-45ec-86D0-469477F304C9}.ClientEnd
MktConnectivityNode
{2E462F8F-23E2-41eb-8C60-ECC38D2C21A2}.SupplierEnd
SubControlArea
{69BC43A4-9AD8-4639-A0FA-43901913DEDB}.SupplierEnd
A cogeneration plant has a steam sendout schedule.
SteamSendoutSchedule
{29FFC448-2620-47ba-BE72-7DE2E8858FD0}.ClientEnd
A thermal generating unit may be a member of a cogeneration plant.
ThermalGeneratingUnits
{E1908858-346B-40b8-9CAB-D6DDC55C0455}.SupplierEnd
The rated output active power of the cogeneration plant.The attribute shall be a positive value.
ratedP
{030FEBF1-8B94-4387-B87A-4A07DC971BF1}
Module performing this communication function.
ComModule
{1E15681F-E00C-4dcf-BBE6-C8C9BD4C8E71}.ClientEnd
Kind of communication direction.
direction
{85AAA47A-AA87-476f-B356-2A80B9E1EC45}
Kind of communication technology.
technology
{FBCD2058-994B-456b-8124-04942073D708}
All functions this communication module performs.
ComFunctions
{1E15681F-E00C-4dcf-BBE6-C8C9BD4C8E71}.SupplierEnd
Time zone offset relative to GMT for the location of this com module.
timeZoneOffset
{C194C2FE-468E-46c7-9EE3-11E21A1987FE}
CombinedCycleConfigurationMember
{BB1E7ACE-B3AF-4ca3-BD88-721B2DC11DB7}.SupplierEnd
CombinedCycleLogicalConfiguration
{A4A1B572-6C63-40e3-9CEF-94B37E4A2FA0}.ClientEnd
FromTransitionState
{6C3E95A9-66C1-4edc-AC13-E0A6C0EE70FF}.SupplierEnd
ToTransitionState
{82AF9D43-F3A7-43bb-955C-D1232C819B99}.SupplierEnd
CombinedCycleConfiguration
{BB1E7ACE-B3AF-4ca3-BD88-721B2DC11DB7}.ClientEnd
MktThermalGeneratingUnit
{DF15B386-08F6-4c78-95AD-B7B10FCC1AB9}.SupplierEnd
CombinedCycleConfiguration
{A4A1B572-6C63-40e3-9CEF-94B37E4A2FA0}.SupplierEnd
MktCombinedCyclePlant
{E85573FF-D877-4da8-AD0E-F1D7EBBB5773}.SupplierEnd
A thermal generating unit may be a member of a combined cycle plant.
ThermalGeneratingUnits
{1A607D5D-0E44-490a-B14D-8A8B2A3D7057}.SupplierEnd
The combined cycle plants active power output rating.
combCyclePlantRating
{F3CA2ADD-B19D-4adf-A42B-1A150DE08571}
FromConfiguration
{6C3E95A9-66C1-4edc-AC13-E0A6C0EE70FF}.ClientEnd
ToConfiguration
{82AF9D43-F3A7-43bb-955C-D1232C819B99}.ClientEnd
A CAES air compressor is driven by combustion turbine.
AirCompressor
{F30399A8-ACB2-4f18-8D1C-F38C8427C14D}.SupplierEnd
A combustion turbine may have an active power versus ambient temperature relationship.
CTTempActivePowerCurve
{BA81A687-7485-4703-80D8-BDAF921D5E98}.ClientEnd
A combustion turbine may have a heat recovery boiler for making steam.
HeatRecoveryBoiler
{C08435B8-5EEA-4a1c-84DE-0253F3F7AC68}.ClientEnd
Default ambient temperature to be used in modelling applications.
ambientTemp
{32064CA8-B772-450e-B8E6-7645496A085F}
Offnominal frequency effect on turbine auxiliaries. Per unit reduction in auxiliary active power consumption versus per unit reduction in frequency from rated frequency.
auxPowerVersusFrequency
{7AC2EB60-47A7-4ccf-BA11-18AF1C401E71}
Offnominal voltage effect on turbine auxiliaries. Per unit reduction in auxiliary active power consumption versus per unit reduction in auxiliary bus voltage from a specified voltage level.
auxPowerVersusVoltage
{FB8443FC-B138-41de-B6C2-2FD6F45B183C}
Offnominal frequency effect on turbine capability. Per unit reduction in unit active power capability versus per unit reduction in frequency from rated frequency.
capabilityVersusFrequency
{B67CE496-747A-4adc-9851-9208F3DDD5EB}
Per unit change in power per versus unit change in ambient temperature.
powerVariationByTemp
{C8658500-A01B-4d0c-9BE6-C33C8EF0511C}
Reference temperature at which the output of the turbine was defined.
referenceTemp
{A5EEFE8D-8EEC-4e8c-9AF1-329A6E210EDE}
The time constant for the turbine.
timeConstant
{BA4EE654-7C68-4f21-AB45-228ABCB91E26}
The MeasurementValue that is controlled.
DiscreteValue
{DF0C3745-2D94-4daa-8AA0-20AE415D601B}.ClientEnd
The ValueAliasSet used for translation of a Control value to a name.
ValueAliasSet
{E47F1C07-76A3-4828-BB41-624EB0C9DAE0}.SupplierEnd
Commitments
{215A722F-0E10-4556-A345-B31B11229B80}.SupplierEnd
CommitmentClearing
{215A722F-0E10-4556-A345-B31B11229B80}.ClientEnd
RegisteredResource
{61A71384-CC3E-4247-AE63-5AD07C4A3E89}.ClientEnd
the type of UC status self commitment ISO commitment or SCUC commitment
commitmentType
{527FACAD-30AC-4dff-A647-F8F697938812}
Indicator of either a StartUp or a ShutDown.
instructionType
{B626E793-2768-4fab-B947-47EF25913E8A}
updateType
{9EA85907-611E-4875-A259-19906297D428}
CommodityPrice
{C7E98892-55E0-49fe-9B35-CF765FDE3A10}.ClientEnd
MarketProduct
{2CE15336-9D65-42db-A3CA-4D3E955778DF}.SupplierEnd
Pnode
{F9E2DDE2-0FFA-44c6-9186-CCF290EFA2ED}.SupplierEnd
RTO
{9C7DB57F-73C7-4d73-B17D-1CE635F85AF4}.ClientEnd
The currency in which the Commodity is traded using the standard conventions associated with the Currency enumeration.
commodityCurrency
{28E7466A-68B8-43e9-A152-41C283962539}
The unit of measure in which the Commodity is traded using the standard conventions associated with the UnitSymbol enumeration.
commodityUnit
{FA02E9BA-2CAF-4929-96E6-891A21ECF764}
The unit multiplier e.g. k to convert the unit Wh to kWh using the standard conventions associated with the UnitMultiplier enumeration.
commodityUnitMultiplier
{B18933B5-D585-4df7-BD75-56AAB6407D67}
CommodityDefinition
{C7E98892-55E0-49fe-9B35-CF765FDE3A10}.SupplierEnd
PnodeClearing
{B037CDCC-4EA4-4d2d-8CF4-27BBEFA157FC}.ClientEnd
PriceDescriptor
{0E804F54-A29B-4452-B7D6-078FE7D84D1F}.SupplierEnd
The time interval over which the CommodityPrice is valid using the standard conventions associated with the DateTimeInterval class.
timeIntervalPeriod
{DC2CF275-2E96-4e98-B34D-CF509B532E2C}
ICCP data provider or consumer using communication addressing for a Bilateral table.
BilateralExchangeActor
{F8B558CB-826C-44f6-8B37-E168629E4395}.SupplierEnd
RTUs may be attached to communication links.
RemoteUnits
{E4ED6E40-6C5C-406f-B61F-EFE533D3AE61}.SupplierEnd
CUAllowableAction
{7E14ED1F-0F2B-406f-8316-5676CAE2C27A}.ClientEnd
CUContractorItems
{53544586-E3BD-4bd3-9885-4857731939B8}.ClientEnd
CUGroup
{8FAE377F-EEE5-44eb-962C-214341F7F3FE}.SupplierEnd
CULaborItems
{289D7D61-564F-42e9-B83D-CB11520403E4}.ClientEnd
CUMaterialItems
{7B6A93BA-1EDF-4a37-AE20-76A155009833}.ClientEnd
CUWorkEquipmentItems
{05F15D8B-35FF-4170-9657-52306B692CE3}.ClientEnd
CostType
{01AD8352-4238-4d6f-96FF-7F8AD75B6EF6}.ClientEnd
DesignLocationCUs
{B11E2CCC-4BD2-4bb3-AC4A-FC61ADF42FD2}.SupplierEnd
GenericAssetModel
{29224EFF-E858-46a4-AF56-8007409442DC}.SupplierEnd
Procedures
{A0D146CA-A291-4aa2-8C93-C33AFCBB974E}.SupplierEnd
PropertyUnit
{730C905B-BBFC-44aa-A988-5BCE91C46E12}.ClientEnd
Estimated total cost for perfoming CU.
estCost
{27A8E557-A144-4928-A41D-C08570FF0657}
AssemblyManifest
{ABA7248F-7487-4c32-811C-B708158136CB}.ClientEnd
ModelPartVersion
{C390164D-CBC2-47e2-8EAE-2EC7A1187A16}.ClientEnd
Switches contained in this Composite switch.
Switches
{E6CD744D-0D2A-4e23-9C5E-B2A3778D7618}.SupplierEnd
Breaking capacity or short circuit rating is the maximum rated current which the device can safely interrupt at the rated voltage.
interruptingRating
{9525C8A5-E385-4b62-8111-4C698501E6AC}
Kind of composite switch.
kind
{5F9E9576-360F-431d-8D96-0599C1C8FA37}
Phases carried if applicable.
phaseCode
{50FFA036-5C76-4651-9D2E-BBCCF8DC0206}
Rated voltage.
ratedVoltage
{6C338611-59D7-4ae5-98D7-4DB6AD3E73F2}
Diameter over the concentric neutral strands.
diameterOverNeutral
{0F237A9F-3062-4eba-A9DE-51F5E9E66097}
Geometric mean radius of the neutral strand.
neutralStrandGmr
{50EDC85A-4806-45cf-B338-BE66FBF5B1FE}
DC resistance per unit length of the neutral strand at 20 C.
neutralStrandRDC20
{220DD0D7-8C30-4053-8ABD-78E61B85486B}
Outside radius of the neutral strand.
neutralStrandRadius
{1FAB34BD-4EB6-4b0d-AEF2-50FF7BF26AA2}
DesignLocationCUs
{A2A64DC1-F71D-4a0f-9604-744445395515}.ClientEnd
DesignLocations
{01106373-66A2-47e6-BE11-C6EB50A8EA95}.ClientEnd
Designs
{B55CE47A-87D3-4069-AE0A-CD19D6B6247B}.ClientEnd
Kind of this condition factor.
kind
{DE2809D1-058B-49cc-BA37-2278C6051689}
status
{CB453424-AEE0-4743-B871-6F83590D4D8C}
multiplier
{EDFA4FD2-D5E9-4dc7-AC28-EE6658BED80A}
unit
{19818A5D-D769-4eb2-B84D-616C971F1004}
multiplier
{0B66B808-85A1-479a-8EDA-29D16B739CE2}
unit
{D7DE7981-D0AB-452a-8C9F-E3CF24B3083A}
Base voltage of this conducting equipment. Use only when there is no voltage level container used and only one base voltage applies. For example not used for transformers.
BaseVoltage
{B21687D9-2B46-4880-B016-06CCFA215EC3}.ClientEnd
Action involving grounding operation on this conducting equipment.
GroundingAction
{E49D8003-4EDF-4e58-A61C-0A5F1C6165E1}.ClientEnd
Jumper action involving jumping operation on this conducting equipment.
JumpingAction
{4D35C940-C8A8-4a53-846A-929278E1DB57}.ClientEnd
Outage
{EEA2935F-26F1-463e-890E-676B5DDA189A}.ClientEnd
Protection equipment used to protect specific conducting equipment.
ProtectionEquipments
{1A223051-2D2E-4ca4-8FF1-9C8D1BDE000B}.ClientEnd
The operating condition to the Conducting Equipment is changed when protective action adjustment is activated. For ShuntCompensator or other conducting equipment that operates on discrete values integer the values given in float will be rounded.
ProtectiveActionAdjustment
{44AD5B78-D603-43d9-A73C-68DCFE8B9C09}.SupplierEnd
The status state variable associated with this conducting equipment.
SvStatus
{A1BADE18-494C-4d12-B7E2-2C9AF7F526ED}.ClientEnd
Conducting equipment have terminals that may be connected to other conducting equipment terminals via connectivity nodes or topological nodes.
Terminals
{5FEF5186-7804-4dad-8E18-8C5DB7FCE6B2}.ClientEnd
Segment length for calculating line section capabilities.
length
{3F232A26-A1CA-4477-ADA1-92AC37BFAF1D}
Asset whose change resulted in this configuration event.
ChangedAsset
{71EA796A-141A-445d-9B0E-EF0075BFAFD2}.ClientEnd
Document whose change resulted in this configuration event.
ChangedDocument
{E33CE794-1D36-4889-BDFB-F26AF8508188}.ClientEnd
Location whose change resulted in this configuration event.
ChangedLocation
{5A4A6C15-ADB0-446d-8CFE-0DE670D4800F}.ClientEnd
Organisation role whose change resulted in this configuration event.
ChangedOrganisationRole
{83D1A41E-45C6-49ba-883F-D9E6B3E0643C}.ClientEnd
Person role whose change resulted in this configuration event.
ChangedPersonRole
{472A820F-DB21-4935-A460-E5C9B71BB861}.ClientEnd
Service category whose change resulted in this configuration event.
ChangedServiceCategory
{460BA6C7-2417-41f6-8AC0-A21EE240B5BC}.ClientEnd
Usage point whose change resulted in this configuration event.
ChangedUsagePoint
{BA6788B9-B467-4d11-81A1-9DFE88730490}.ClientEnd
FaultCauseType
{B79138C2-DB7B-43a8-A72B-77D615EB381B}.SupplierEnd
PowerSystemResource
{26DFEBF9-D038-4c7e-96A1-F4832AC44307}.ClientEnd
Group of this ConformLoad.
LoadGroup
{0EFAEF28-CDEB-4076-9D2D-5AE94985E8CF}.ClientEnd
The ConformLoadSchedules in the ConformLoadGroup.
ConformLoadSchedules
{D3B829DB-A9B9-471b-BBAC-A4FE537AA726}.SupplierEnd
Conform loads assigned to this ConformLoadGroup.
EnergyConsumers
{0EFAEF28-CDEB-4076-9D2D-5AE94985E8CF}.SupplierEnd
The ConformLoadGroup where the ConformLoadSchedule belongs.
ConformLoadGroup
{D3B829DB-A9B9-471b-BBAC-A4FE537AA726}.ClientEnd
IndividualPnode
{6DB2691B-152F-462d-B727-DE871F8AAB7A}.SupplierEnd
CRRMarket
{A6EF647F-83D1-46c2-83BA-498C5AC0EE5D}.SupplierEnd
CRROrgRole
{80E51726-F69E-4014-ACD6-C80A45B842AE}.ClientEnd
CRRSegment
{02556F1B-1A48-4bb0-A787-9F04C918321D}.SupplierEnd
Flowgate
{C6E4CA42-E336-4a8a-828E-6AF9E8F25458}.SupplierEnd
CRR category represents PTP for a pointtopoint CRR or NSR for a Network Service Right. If CRR category is PTP both Source ID and Sink ID fields are required. If CRR category is NSR only one field either Source ID or Sink ID shall be not null and the other shall be null. However the NSR category will include at least three records.
cRRcategory
{4C520D47-2ED3-4ab0-B9D3-803FFD498DFC}
Type of the CRR from the possible type definitions in the CRR System e.g. LSE ETC.
cRRtype
{82F8F5AE-05DF-450f-91C3-309A7F0BDF51}
Hedge type Obligation or Option. An obligation type requires the holder to receive or pay the congestion rent. An option type gives the holder the option of receiving or paying the congestion rent.
hedgeType
{84FCF73B-EB28-4295-95EC-A9573BBD87A6}
Time of Use flag of the CRR Peak ON Offpeak OFF or all 24 hours 24HR.
timeOfUse
{4A64E75A-59EB-4a3f-9D95-75200134BC8B}
Switches
{ABF72E73-E9B7-40a5-8FC4-D1B196EC3845}.SupplierEnd
Information on remote connect disconnect switch.
rcdInfo
{6CA585CC-501E-48a4-A4CD-E442EB31B110}
Container of this connectivity node.
ConnectivityNodeContainer
{08EEABA6-269C-44a7-8F82-7BBEFE71ADD6}.SupplierEnd
Terminals interconnected with zero impedance at a this connectivity node.
Terminals
{C7E01609-F4E6-4a6e-8ACF-BDD413E62DE3}.ClientEnd
The topological node to which this connectivity node is assigned. May depend on the current state of switches in the network.
TopologicalNode
{ACD76E10-125A-4f7a-A20A-475AC4334414}.SupplierEnd
Connectivity nodes which belong to this connectivity node container.
ConnectivityNodes
{08EEABA6-269C-44a7-8F82-7BBEFE71ADD6}.ClientEnd
The topological nodes which belong to this connectivity node container.
TopologicalNode
{88BD0C47-4CB3-44db-9A6B-20C783A24478}.ClientEnd
ConstraintResults
{540BF2B6-C997-4421-B8A4-58AC92F6A5E8}.SupplierEnd
TimeSeries
{07DEE107-FB99-4586-A9B9-7F52BB893EAE}.SupplierEnd
ConstraintClearing
{540BF2B6-C997-4421-B8A4-58AC92F6A5E8}.ClientEnd
Flowgate
{18E34024-C496-433d-B129-256CA4377357}.ClientEnd
MktContingency
{01D4A0B2-81CC-4497-A052-25EA792CEC6E}.SupplierEnd
Noncompetitive path constraint FlagYN indicating whether the shadow price on a noncompetitive path was nonzero.
competitivePathConstraint
{7DD8B0A9-DE8C-4152-8CB1-EB980354318A}
Type of constraint.
constraintType
{E6B0EE46-D092-495d-BB25-B26643C0BD64}
Limit flag Maximum Minimum.
limitFlag
{F81636F1-0A15-488d-84ED-25BA5A2A1B62}
Included in optimization YN.
optimizationFlag
{BDCA0BAE-8A04-49e4-ABED-626194094737}
MQS change type.
updateType
{6178EE0C-504C-47b2-81D7-9D517390EBAE}
SecurityConstraintSum
{BB8340BB-8D35-4db5-B3EA-6A408762BF83}.ClientEnd
All charges used to define this consumption tariff interval.
Charges
{3C4455D4-C34E-4001-A555-8912924EE287}.SupplierEnd
Reading type for startValue.
ReadingType
{2C44369F-3DF4-4dcd-9036-EDC39B37AB3D}.SupplierEnd
All tariff profiles defined by this consumption tariff interval.
TariffProfiles
{7F5C8247-4764-43ce-8B24-F568152BB763}.ClientEnd
All time of use tariff intervals influenced by this consumption tariff interval.
TouTariffIntervals
{8AA39685-1453-4631-B85A-DA04510557D0}.SupplierEnd
MWLimitSchedules
{B2755079-F601-4879-9341-AAF0FDCD8B1B}.SupplierEnd
MktContingency
{0906BEF7-3804-4598-9F39-8339F2B0B443}.SupplierEnd
SecurityConstraintSum
{BF65240F-A284-4af5-8E7D-B230D8362719}.SupplierEnd
The single piece of equipment to which to apply the contingency.
Equipment
{90FE687B-C58C-4b05-856E-6D576F7CADBE}.SupplierEnd
The status for the associated equipment when in the contingency state. This status is independent of the case to which the contingency is originally applied but defines the equipment status when the contingency is applied.
contingentStatus
{AD281283-F48F-4f62-AA91-7039DDA80DCF}
Flowgate
{3A09997D-D60D-46df-B010-018CC9A81D1B}.ClientEnd
RegisteredResource
{B2C73AF1-CB11-4c78-BE4B-750739E77C5F}.ClientEnd
TransmissionContractRight
{719073AE-6982-4fac-ACA7-C131AF4340BF}.ClientEnd
This value will be set to YES if the referenced Cnode is defined as the sink point in the contract.
sinkFlag
{46CEAB7B-6927-40b4-BC86-2217335A385A}
This value will be set to YES if the referenced Cnode is defined as the source point in the contract.
sourceFlag
{5B875BAA-510D-462a-88D8-408D7CC444BD}
BidSelfSched
{C020B2A4-890F-455d-8C69-8B0612C789BB}.SupplierEnd
Chain_TransmissionRightChain
{1D17EEA8-4DC7-4648-B0A4-3D0516BC89C2}.ClientEnd
ContractDistributionFactor
{719073AE-6982-4fac-ACA7-C131AF4340BF}.SupplierEnd
Ind_TransmissionRightChain
{2A59E041-E065-428d-9918-A42D868C16C6}.ClientEnd
RTO
{A3A25A93-B38D-4be8-AFA8-1F472DA6E232}.ClientEnd
SchedulingCoordinator
{9344B7EF-5714-48c0-9CD5-ABBE8A690C30}.ClientEnd
SubstitutionResourceList
{869976B9-DCEB-44ff-8BDB-956B7D44DFE7}.SupplierEnd
TREntitlement
{646BBA57-9F62-43b1-9636-2CBBCFAC508B}.SupplierEnd
Transmission Right type is this an individual contract right or a chain contract right. Types CHAIN or INDIVIDUAL
TRType
{EFAE446B-7050-4c0e-AAC4-113E462553AD}
TransmissionInterfaceEntitlement
{BD4EDF28-A98E-4529-8A20-3113450CEBF4}.ClientEnd
Financial value of the contract
contractPrice
{67E2DD6E-E113-424a-8696-73DC4212B49D}
type of the contract. Possible values are but not limited byETC TOR or RMR and RMT self schedules
contractType
{50EFBAEA-CB69-495f-8F28-B2D273379DCD}
Indicator if the location associated with this contract is financial e.g. pricing nodes or physical e.g. connectivity nodes.
financialLocation
{A5B1AFFB-D593-409d-BFFA-66D28B68342C}
Flag to indicate this contract provides financial rights in the DA Market
financialRightsDAM
{7CB8D5C0-F0D4-4f9a-BB9E-18FB22D3F56F}
Flag to indicate this contract provides financial rights in the RT Market
financialRightsRTM
{A8038C1B-BED1-438c-AC6B-AD38473015F4}
This indicates the latest schedule market type a contract can be applied to. This is used in conjunction with the latestSchedMinutes attribute to determine the latest time this contract can be called in. The possible values for this attribute are DAM RTM or it can be omitted. If omitted the latestSchedMinutes attribute defines the value.
latestSchedMktType
{02C369CF-D893-446f-B2C7-1B2FBF65C72A}
Flag to indicate this contract provides physical rights in the DA Market
physicalRightsDAM
{A2C97CC3-4D0F-4852-A317-92969709F57C}
Flag to indicate this contract provides physical rights in the RT Market
physicalRightsRTM
{CF9EC11A-1A0D-4ef3-8694-D84E0072300F}
ErpPayables
{C73FA4A3-2380-4d97-8F28-0D805D815283}.SupplierEnd
WorkCostDetail
{96CD6C4B-B625-48f2-823B-F52CD16FCC1F}.ClientEnd
WorkTask
{3123F76B-B55F-4f42-AEB4-96AA9F5254CA}.ClientEnd
The amount that a given contractor will charge for performing this unit of work.
bidAmount
{55892BA8-8746-490a-8608-B73E9554F70D}
The total amount charged.
cost
{6541723D-E2B5-4670-9994-B50549B996D0}
status
{F41D579D-4E88-4f9e-A557-D9ED371EF8B5}
ControlAction
{55F3693A-6960-486a-AEB0-EEBB67B10D9A}.ClientEnd
Regulating device governed by this control output.
PowerSystemResource
{A1BE05F6-8AA3-4c36-B00D-9A3BC3D8B4D3}.ClientEnd
The remote point controlling the physical actuator.
RemoteControl
{D8E2547F-5EE8-425a-88B2-6878C15AFEF6}.ClientEnd
The unit multiplier of the controlled quantity.
unitMultiplier
{12032CC3-C242-4966-9865-799B40A03B62}
The unit of measure of the controlled quantity.
unitSymbol
{704DC262-1071-4a4d-AC47-83098723EFE6}
Control
{55F3693A-6960-486a-AEB0-EEBB67B10D9A}.SupplierEnd
The energy area that is forecast from this control area specification.
EnergyArea
{91910331-E0D0-4b32-9E25-EC5310A60B71}.SupplierEnd
EnergyGroup
{EC0B638A-E0FD-42c8-B84C-47AA469B8629}.ClientEnd
The specified positive net interchange into the control area i.e. positive sign means flow into the area.
netInterchange
{B02AFBB9-BD7F-45e4-B361-D0EDD5F7CB79}
Active power net interchange tolerance. The attribute shall be a positive value or zero.
pTolerance
{1384C2B5-6BFF-49b9-A768-AE4D26733146}
The primary type of control area definition used to determine if this is used for automatic generation control for planning interchange control or other purposes. A control area specified with primary type of automatic generation control could still be forecast and used as an interchange area in power flow analysis.
type
{66C3EA41-8A06-4176-8AE5-F3970BB794FF}
RegisteredResource
{E2FACF8B-8529-4118-B66B-ABACB5D4B6A4}.SupplierEnd
SubControlArea
{ABACF27C-565A-45bd-B69C-0A1A99CECFC2}.SupplierEnd
Attained.
attained
{B2E2A3D0-6B24-40cf-A4B5-E514512313D7}
Native.
native
{27CBF0DC-4AFA-453e-A245-FF9C8C6D6639}
The generating unit specified for this control area. Note that a control area should include a GeneratingUnit only once.
GeneratingUnit
{682C859C-B9CD-4dde-A959-EB89678BBBD6}.SupplierEnd
A ControlAreaOperator has a collection of tie points that ring the ControlArea called a TieLine.
CAChildOf
{1FE3925A-54B7-4008-8CC6-93CD443CC3C0}.SupplierEnd
A ControlAreaCompany controls a ControlArea.
ControlledBy
{1AFC6FC5-1F2B-45c1-92ED-34FE03FF7500}.ClientEnd
MktControlArea
{72466897-1E7B-4232-8415-B1CF11A7D241}.SupplierEnd
Reconditionings
{87E64861-9690-46b3-ADD5-CF931CEA7994}.SupplierEnd
Kind of cooling system.
coolingKind
{1738008D-77A8-490f-BE53-1F63E4ED27D3}
The power rating associated with type of cooling specified for this stage.
powerRating
{63162C86-80AD-41c4-8AC9-962B359EDA98}
All locations described with position points in this coordinate system.
Locations
{D9DB79D8-27F1-4071-9C79-F0F1F62B4F18}.ClientEnd
multiplier
{58C8EF99-A30B-46a8-B471-3960E5B17784}
unit
{62781DDF-86F3-4cfb-93D8-B79FCCA44427}
multiplier
{0ED554FC-EDA3-475c-BD91-CFCF254D87AE}
unit
{A892F793-EFD8-4d0a-816F-C62F14DDC794}
multiplier
{A4686C05-46C7-4987-AD4B-F37C39B59D69}
unit
{8EB82F99-A67A-4ee9-9BC8-FB807B99CCB9}
multiplier
{683ECF7A-C52C-4696-8E3A-3871F72395A3}
unit
{B39B1C54-D199-470c-9AF4-0053A2144F5F}
ChildCostTypes
{967B42DB-FFF7-48d8-AC58-99DF4BDC3FF3}.SupplierEnd
CompatibleUnits
{01AD8352-4238-4d6f-96FF-7F8AD75B6EF6}.SupplierEnd
ErpJournalEntries
{416479A3-0381-44f8-B625-D715F8C424E6}.SupplierEnd
ParentCostType
{967B42DB-FFF7-48d8-AC58-99DF4BDC3FF3}.ClientEnd
WorkCostDetails
{5446E847-F2C9-4006-ABE5-5682B880301D}.SupplierEnd
status
{6C2713BB-0D7C-409f-BF66-3948CB53290E}
Capabilities
{921FF0C0-21D9-4312-8288-1512B1E7B653}.ClientEnd
ErpPersons
{19D1AD6D-1BA3-400f-BACA-BF16BDB31A48}.SupplierEnd
Skills
{F6C636B7-1341-45e9-9F57-F9DAF8AA60FC}.ClientEnd
status
{9F648612-EFEE-42e2-9402-531F257170E8}
All members of this crew.
CrewMembers
{9C3593D0-040D-4b39-831A-6E1E5BA063DA}.SupplierEnd
Type of this crew.
CrewType
{5A1DA3D9-8576-4f56-BED5-2A869AA8BA84}.SupplierEnd
FieldDispatchHistory
{2F2C04F1-3A57-404e-87F0-356183FF8B57}.ClientEnd
Location
{5396B10B-F4AB-46c8-B558-A0D64090E603}.ClientEnd
Outage
{D0947F3D-A8D0-4b21-9924-B957AF56DC82}.ClientEnd
SwitchingAction
{A7E0FAFD-8B4F-45b4-B614-D821AB007EF9}.ClientEnd
All work assets used by this crew.
WorkAssets
{762660F7-4910-42bc-8748-C7841507E17A}.ClientEnd
All work tasks this crew participates in.
WorkTasks
{D3920004-AE6C-439a-9CED-543CFED22657}.ClientEnd
Status of this crew.
status
{299A7357-1875-4dc2-ACFB-84F3D7F2368B}
Crew to which this crew member belongs.
Crew
{9C3593D0-040D-4b39-831A-6E1E5BA063DA}.ClientEnd
All crews of this type.
Crews
{5A1DA3D9-8576-4f56-BED5-2A869AA8BA84}.ClientEnd
Highpressure synchronous machine with which this crosscompound turbine governor is associated.
HighPressureSynchronousMachineDynamics
{4EEEDF69-9BB6-4d02-B662-A156239AF9B8}.SupplierEnd
Lowpressure synchronous machine with which this crosscompound turbine governor is associated.
LowPressureSynchronousMachineDynamics
{9C225B93-4040-4753-80B9-1A3D0F2B6D81}.SupplierEnd
Current source converter dynamics model used to describe dynamic behaviour of this converter.
CSCDynamics
{923E9B98-7F14-449a-BFFF-B62D5A7D53DF}.ClientEnd
Firing angle that determines the dc voltage at the converter dc terminal. Typical value between 10 degrees and 18 degrees for a rectifier. It is converters state variable result from power flow. The attribute shall be a positive value.
alpha
{9D272F46-EABD-436f-9B05-3AB954FEB505}
Extinction angle. It is used to limit the dc voltage at the inverter if needed. Typical value between 17 degrees and 20 degrees for an inverter. It is converters state variable result from power flow. The attribute shall be a positive value.
gamma
{B9AD7780-6511-4795-8FF2-0797C537AF64}
Maximum firing angle. It is converters configuration data used in power flow. The attribute shall be a positive value.
maxAlpha
{35DA4A07-8966-4207-B9EA-CFA2F8C5556C}
Maximum extinction angle. It is converters configuration data used in power flow. The attribute shall be a positive value.
maxGamma
{CAAD51DE-696B-4678-8DEA-868AFA1529B4}
The maximum direct current Id on the DC side at which the converter should operate. It is converters configuration data use in power flow. The attribute shall be a positive value.
maxIdc
{6C080741-A57E-4534-A156-2380B3E712ED}
Minimum firing angle. It is converters configuration data used in power flow. The attribute shall be a positive value.
minAlpha
{ADAF6A15-8626-4955-BD2A-A3EE3D700C84}
Minimum extinction angle. It is converters configuration data used in power flow. The attribute shall be a positive value.
minGamma
{601E21E7-7AFC-4631-9752-EE3F81D1BEF5}
The minimum direct current Id on the DC side at which the converter should operate. It is converters configuration data used in power flow. The attribute shall be a positive value.
minIdc
{27F20192-3FDA-4372-8F7C-B0D934DD9B2C}
Indicates whether the DC pole is operating as an inverter or as a rectifier. It is converters control variable used in power flow.
operatingMode
{3717F511-42E5-4920-8B73-5AB13798BCF4}
Kind of active power control.
pPccControl
{A4B32267-105D-4bc1-9A46-A87AB1DEB8CC}
Rated converter DC current also called IdN. The attribute shall be a positive value. It is converters configuration data used in power flow.
ratedIdc
{F988CC98-3A7A-401b-B41F-1A8A47BFFE99}
Target firing angle. It is converters control variable used in power flow. It is only applicable for rectifier if continuous tap changer control is used. Allowed values are within the range minAlphalttargetAlphaltmaxAlpha. The attribute shall be a positive value.
targetAlpha
{C7DDA4DF-A9D8-4ed1-888D-EE60728AD998}
Target extinction angle. It is converters control variable used in power flow. It is only applicable for inverter if continuous tap changer control is used. Allowed values are within the range minGammalttargetGammaltmaxGamma. The attribute shall be a positive value.
targetGamma
{7EE02461-D04E-4c41-93DC-0D92F02D10EF}
DC current target value. It is converters control variable used in power flow. The attribute shall be a positive value.
targetIdc
{994D8715-A3DE-4d81-A09A-F3B95325691F}
InternalControlArea
{BEFB4486-B77B-4cd6-A9AD-9D7F2906C32F}.SupplierEnd
multiplier
{86741909-5F72-4d38-8B1F-69C7C7308BE8}
unit
{58C58CD1-5C85-4073-ACF8-9D9F1331364E}
The normal value for limit on current flow. The attribute shall be a positive value or zero.
normalValue
{29A541C2-CB70-432e-98FE-A50695CB2033}
Limit on current flow. The attribute shall be a positive value or zero.
value
{22BAF153-4E49-4e43-9C3D-69D542FF6E89}
Current limit number one 1 for inverse time pickup.
currentLimit1
{B5A966CE-FCE6-48de-A584-63AAE323DD91}
Current limit number 2 for inverse time pickup.
currentLimit2
{F4B8CF9B-D578-4b92-8D43-44FC0962BDAA}
Current limit number 3 for inverse time pickup.
currentLimit3
{BC7E3234-BD9B-4f81-904E-3976DCB72F4D}
Inverse time delay number 1 for current limit number 1.
timeDelay1
{0D844B6D-81B4-4ad0-B752-47B94E9057AF}
Inverse time delay number 2 for current limit number 2.
timeDelay2
{DD8BCFB0-F0D9-482e-B5E3-8B4AF3BF5DD2}
Inverse time delay number 3 for current limit number 3.
timeDelay3
{06BCCEF9-EB0D-4f1c-887B-85AA267314A2}
InternalControlArea
{25FE6285-FBFC-4387-9CFA-5A909EABEF8D}.SupplierEnd
NetworkModelProjectComponent2
{955D5BF8-C371-455c-9915-2EDD3CA75C50}.ClientEnd
Percent of rated current for which the CT remains accurate within specified limits.
accuracyLimit
{A48B5A36-5966-4d5b-ACA8-C62A0DEA5B16}
Power burden of the CT core.
coreBurden
{B15D192E-418B-49ff-B092-C2079C5B0101}
Accuracy limit.
accuracyLimit
{70CE0EFC-E64D-4f4d-BF47-4D2D4DF02706}
Maximum primary current where the CT still displays linear characteristicts.
kneePointCurrent
{C12DD083-946E-443f-88F2-7CA158081D4C}
Maximum voltage across the secondary terminals where the CT still displays linear characteristicts.
kneePointVoltage
{9747ECD5-584E-4929-9755-E8B68A506B51}
Maximum ratio between the primary and secondary current.
maxRatio
{9B3D2F96-C728-482a-B71B-BF73C441E450}
Nominal ratio between the primary and secondary current i.e. 1005.
nominalRatio
{2FC73107-AD91-4352-B046-9A267227228D}
Full load secondary FLS rating for primary winding.
primaryFlsRating
{31268FB9-255D-4dcc-A13E-E86A7873B171}
Ratio for the primary winding tap changer.
primaryRatio
{4FC8F4FB-6FF3-4d94-9153-183ABEB5A97C}
Rated current on the primary side.
ratedCurrent
{1FA61311-E265-4ea0-AE6C-88067C0F6947}
Full load secondary FLS rating for secondary winding.
secondaryFlsRating
{2319B496-2A19-43cd-B842-8DE58971D34A}
Ratio for the secondary winding tap changer.
secondaryRatio
{C17E99E7-988F-446f-84AB-8D8C69656B2C}
Full load secondary FLS rating for tertiary winding.
tertiaryFlsRating
{A8B48EF1-9741-4532-8232-C2CF385CEC80}
Ratio for the tertiary winding tap changer.
tertiaryRatio
{02842A65-0424-4997-9D90-27727F9A2FFC}
An EnergyTransaction may be curtailed by any of the participating entities.
EnergyTransaction
{64C49984-0ED1-438b-9C5C-CE6E9784CFF1}.SupplierEnd
The point data values that define this curve.
CurveDatas
{21D1EA17-DE1A-4a12-BCB8-293A9781EFC4}.ClientEnd
The style or shape of the curve.
curveStyle
{34413CFC-AEF0-475f-BF0A-29A7A851625C}
Multiplier for Xaxis.
xMultiplier
{12D6268F-205E-4580-B694-E0947E6C8EA5}
The Xaxis units of measure.
xUnit
{A977BAEA-28F3-4642-9A6B-1C4181E494B7}
Multiplier for Y1axis.
y1Multiplier
{3CAA546E-E6BD-4dec-830F-24D3F61F0791}
The Y1axis units of measure.
y1Unit
{3D2E7681-5029-4fd3-AD9B-DD04C563A315}
Multiplier for Y2axis.
y2Multiplier
{7C8CB635-5F61-43f2-9D80-B8C8A3D2A273}
The Y2axis units of measure.
y2Unit
{C017B50F-488D-48e5-9511-6968A85AF219}
Multiplier for Y3axis.
y3Multiplier
{AD5383B4-6D5A-4317-89E4-2D5982488252}
The Y3axis units of measure.
y3Unit
{4194FDA4-3971-48c5-9B3F-BAE5112BF33B}
The curve of this curve data point.
Curve
{21D1EA17-DE1A-4a12-BCB8-293A9781EFC4}.SupplierEnd
Customer
{B478C760-01BA-48e3-9819-23C45144AA2E}.ClientEnd
{B478C760-01BA-48e3-9819-23C45144AA2E}.SupplierEnd
All accounts of this customer.
CustomerAccounts
{793C2F8E-D6A8-4991-80CA-22D47E9F6FA8}.SupplierEnd
All agreements of this customer.
CustomerAgreements
{12619422-3644-40fc-AA40-CC129C2C199A}.SupplierEnd
All notifications required by this customer.
CustomerNotifications
{9979122D-C134-46ef-ACBB-9812051756B2}.ClientEnd
All end devices of this customer.
EndDevices
{CAC11EF6-DAA4-4489-BC90-BFEC70C14E61}.SupplierEnd
ErpPersons
{08C6C8AA-21F3-4f0e-91C1-B7765CD6D7FA}.SupplierEnd
The outage plan that identifies the customers that are affected.
OutagePlan
{2B68C98E-D3F5-4de1-9693-2F2E3F99F1BC}.SupplierEnd
PlannedOutageNotification
{C3BE4896-4663-4669-84A9-B881796117E5}.ClientEnd
All trouble tickets for this customer.
TroubleTickets
{DB18A09B-52CE-46d9-98B1-DA9F32529CC5}.ClientEnd
All the works performed for this customer.
Works
{07E56F99-F27D-4363-90E9-D912F7C8DEC7}.SupplierEnd
Kind of customer.
kind
{59942DEA-7ECE-45f3-8D06-B1BFA2460799}
Priority of the customer.
priority
{943442D7-3358-4531-9E76-773D1165CDB1}
Status of this customer.
status
{895DF1D3-73C0-4a14-9BEE-7044014F0D00}
AccountNotification
{FC0059FF-913A-472a-9717-BA43E0EC7EA1}.SupplierEnd
Customer owning this account.
Customer
{793C2F8E-D6A8-4991-80CA-22D47E9F6FA8}.ClientEnd
All agreements for this customer account.
CustomerAgreements
{200971C2-908E-46ed-BAA2-C95ECA8EC1A5}.SupplierEnd
CustomerBillingInfos
{118BDA78-3371-442b-B86A-BDFA164F9F37}.ClientEnd
ErpInvoicees
{F954FA38-DDCE-4eeb-8C01-FA8B0D72A603}.SupplierEnd
All payment transactions for this customer account.
PaymentTransactions
{0B5E9E95-37C0-4b1a-8C38-C1995B9D1EC8}.SupplierEnd
WorkBillingInfos
{86A9BD70-A4A7-4530-B205-5F62F9C1C7DB}.SupplierEnd
The last amount that will be billed to the customer prior to shut off of the account.
lastBillAmount
{3F686220-8A43-454d-B824-A399124EF9E0}
All nonservice related auxiliary agreements that refer to this customer agreement.
AuxiliaryAgreements
{4B0AFE27-A288-4e9f-A8F4-CA0675EB971D}.SupplierEnd
Customer for this agreement.
Customer
{12619422-3644-40fc-AA40-CC129C2C199A}.ClientEnd
Customer account owning this agreement.
CustomerAccount
{200971C2-908E-46ed-BAA2-C95ECA8EC1A5}.ClientEnd
All demand response programs the customer is enrolled in through this customer agreement.
DemandResponsePrograms
{C5454F40-D260-4575-8095-135824469D69}.ClientEnd
could be deprecated in the future All meter readings for this customer agreement.
MeterReadings
{A14F100A-AE6C-49c4-AD0C-FC8D5004074A}.ClientEnd
All pricing structures applicable to this customer agreement.
PricingStructures
{2EF6BAD9-95F9-48bf-9408-24054A043C0F}.SupplierEnd
Service category for this agreement.
ServiceCategory
{1CD25DA9-4F95-43aa-A7CF-B41C352C30AA}.SupplierEnd
All service locations regulated by this customer agreement.
ServiceLocations
{C20149AA-BEFF-43c5-B26A-F75F414F345B}.SupplierEnd
Service supplier for this customer agreement.
ServiceSupplier
{47FE73EC-DD27-4731-8091-E3020EACA869}.ClientEnd
StandardIndustryCode
{6081B3B7-6BE2-4dff-BD8D-9BAF5855DE67}.SupplierEnd
All service delivery points regulated by this customer agreement.
UsagePoints
{0FEA25EE-6DB0-45d0-99F9-D5895A91A455}.SupplierEnd
CustomerAccount
{118BDA78-3371-442b-B86A-BDFA164F9F37}.SupplierEnd
ErpInvoiceLineItems
{E8BD9E1E-C04F-4135-8CAA-39D78433DF77}.SupplierEnd
Kind of bill customer receives.
kind
{4360F5EC-725D-4a31-B84B-35841E1477B7}
Amount of the last payment received from the customer. It is retained in the Customer Billing system although the details of each payment are tracked in the ERP system.
lastPaymentAmt
{CCF88D83-996B-46ef-BA0C-B6B669B1F9E8}
Outstanding balance on the CustomerAccount as of the statement date.
outBalance
{EFA8E507-5E0B-45a4-BE4F-7CE222722533}
Monthly amortized amount due during each billing cycle for the CustomerAccount balance for which the Payment Plan is setup.
pymtPlanAmt
{59600E88-1E1B-4d3f-A4F0-CC5D7C03069D}
A ControlAreaOperator or CustomerConsumer may ring their perimeter with metering which can create a unique SubControlArea at the collection of metering points called a TieLine.
CustChildOf
{BE10D423-5810-4e4c-A856-4B2A6F2C2D59}.SupplierEnd
Customer requiring this notification.
Customer
{9979122D-C134-46ef-ACBB-9812051756B2}.SupplierEnd
Incident as a subject of this customer notification.
Incident
{F292A647-3328-43e1-AA6F-08A42730AF41}.ClientEnd
All trouble tickets with this notification.
TroubleTickets
{2E2B0349-61DB-4eeb-9A2F-465DC303A460}.SupplierEnd
Trigger for this notification.
trigger
{040F4A28-FA7C-4127-A0F0-71E7C8D0B9A5}
The line segment to which the cut is applied.
ACLineSegment
{62963E89-E891-4b03-8000-C14788BD8E57}.SupplierEnd
Action taken with this cut.
CutAction
{8E5D12B6-674B-468d-A0AE-F4ACDB34EC17}.ClientEnd
The length to the place where the cut is located starting from side one of the cut line segment i.e. the line segment Terminal with sequenceNumber equal to 1.
lengthFromTerminal1
{93B76002-D48E-4065-9B8E-AA48F771EB48}
Cut on which this action is taken.
Cut
{8E5D12B6-674B-468d-A0AE-F4ACDB34EC17}.SupplierEnd
Switching action to perform.
kind
{8366996C-5983-4e04-8B43-87E7D73E49A5}
The central pressure of the cyclone during the time interval.
centralPressure
{C0BAACEB-84BC-436d-88C3-624E6F28D878}
The maximum surface wind speed of the cyclone during the time interval.
maxSurfaceWindSpeed
{C2239DA2-1CD2-4e55-937C-C21039DF94B9}
The DC connectivity node to which this DC base terminal connects with zero impedance.
DCNode
{B31A4B2D-8B03-4d82-8839-92F521AB47E1}.ClientEnd
See association end Terminal.TopologicalNode.
DCTopologicalNode
{B7808724-9A0B-430d-9271-410BC33226AB}.SupplierEnd
A DC conducting equipment has DC terminals.
DCTerminals
{12776A02-A0D8-4518-8CE7-D41CD6A5EE8F}.SupplierEnd
ProtectiveActionAdjustment
{83F32DD1-007E-48c2-AD47-79FF388FCEDF}.ClientEnd
Rated DC device voltage. The attribute shall be a positive value. It is configuration data used in power flow.
ratedUdc
{3DC64F40-8B27-46c7-8B18-4E165322F0B7}
The operating mode of an HVDC bipole bipolar monopolar metallic return etc.
operationMode
{9774066F-3156-4132-BBB8-9EA03D8C73E4}
The DC nodes contained in the DC equipment container.
DCNodes
{DD79D292-6A01-48eb-B78A-90F96CB960FC}.ClientEnd
The topological nodes which belong to this connectivity node container.
DCTopologicalNode
{B4C9C4A3-7B73-42b4-866B-ABC9504B8B53}.SupplierEnd
Inductance to ground.
inductance
{B1E83180-0ADD-4e36-A3B8-4374782D1553}
Resistance to ground.
r
{27D61E96-12D6-4bd6-B6D6-179A54519C27}
The SubGeographicalRegion containing the DC line.
Region
{87933AA2-5F6F-4768-BCDE-772A53C5248C}.SupplierEnd
Set of perlength parameters for this line segment.
PerLengthParameter
{2DD2B43E-76CD-494b-A33F-018342B6A5C3}.ClientEnd
Capacitance of the DC line segment. Significant for cables only.
capacitance
{F098A35D-75A4-48ec-8152-0A986069D191}
Inductance of the DC line segment. Negligible compared with DCSeriesDevice used for smoothing.
inductance
{BB86CC21-0C27-4f86-A8BB-F72A9048AD67}
Segment length for calculating line section capabilities.
length
{741D3874-1585-4232-A908-CD3483A68831}
Resistance of the DC line segment.
resistance
{D60EBC0B-45F9-4862-BAB6-2CD98EA1F720}
The DC container for the DC nodes.
DCEquipmentContainer
{DD79D292-6A01-48eb-B78A-90F96CB960FC}.SupplierEnd
DC base terminals interconnected with zero impedance at a this DC connectivity node.
DCTerminals
{B31A4B2D-8B03-4d82-8839-92F521AB47E1}.SupplierEnd
The DC topological node to which this DC connectivity node is assigned. May depend on the current state of switches in the network.
DCTopologicalNode
{5A20F31D-14D7-4c51-B74F-DDC1C56849F3}.SupplierEnd
Inductance of the device.
inductance
{42517B02-5553-4694-B74C-5398419DA9A0}
Resistance of the DC device.
resistance
{8C0DE916-4760-4bff-AE06-9D8E367B5AE0}
Capacitance of the DC shunt.
capacitance
{63CFE75D-E6D2-49b0-855D-E852132DCB54}
Resistance of the DC device.
resistance
{58BABAEC-212C-4629-880D-4A098B094402}
An DC terminal belong to a DC conducting equipment.
DCConductingEquipment
{12776A02-A0D8-4518-8CE7-D41CD6A5EE8F}.ClientEnd
The connectivity node container to which the topological node belongs.
DCEquipmentContainer
{B4C9C4A3-7B73-42b4-866B-ABC9504B8B53}.ClientEnd
The DC connectivity nodes combined together to form this DC topological node. May depend on the current state of switches in the network.
DCNodes
{5A20F31D-14D7-4c51-B74F-DDC1C56849F3}.ClientEnd
See association end TopologicalNode.Terminal.
DCTerminals
{B7808724-9A0B-430d-9271-410BC33226AB}.ClientEnd
Delay
{8B9A7786-D683-4dac-9D0C-983AB413A565}.ClientEnd
VSCtype1
{86E86FC3-61BD-4a5f-A4F1-6BDFD8ADE591}.ClientEnd
Integral gain of the DC voltage regulator Kivdc.
kivdc
{23B47403-8625-4597-AE2F-A552BEE21969}
Proportional gain of the DC voltage regulator Kpvdc.
kpvdc
{83302C91-E18C-45a5-835E-70A0CE8E3B07}
Maximum DC voltage Vdcmax.
vdcmax
{20287260-E42A-4c17-A8D0-134C089205D6}
Minimum DC voltage Vdcmin.
vdcmin
{509AD866-3153-40e6-91FF-5A0BA8EFD7B1}
DERMonitorableParameter
{101FBB2C-C8C9-46ef-9BE3-3EEABF000AEE}.SupplierEnd
DispatchSchedule
{3FA9A03E-1846-4bc5-A641-F8A630355CC2}.SupplierEnd
EndDeviceGroup
{AAA6DC66-3D4C-449d-8DAC-947317B28177}.SupplierEnd
From the metering package this is a grouping mechanism that allows actions to be performed upon multiple EndDevices with a single command
EndDeviceGroup
{4611E517-A1DA-440c-BD29-668CF1F495E2}.ClientEnd
From the metering package this is a grouping mechanism that allows actions to be performed upon multiple EndDevices with a single command
EndDeviceGroup
{F0840A17-1419-47f0-BF59-87D100492401}.SupplierEnd
DERCurveData
{101FBB2C-C8C9-46ef-9BE3-3EEABF000AEE}.ClientEnd
DERParameter
{DA256577-6C27-43ab-9A61-3AC4E0530913}
DispatchSchedule
{EF7AB537-05B9-4c9e-BAFA-5C4082E903B4}.ClientEnd
EndDeviceGroup
{56EE9BE9-6817-4022-967A-0AA909D120DE}.ClientEnd
flowDirection
{EA88826F-8EAD-4952-BC21-D29A1608F891}
yMultiplier
{422B07AD-2E28-4892-884F-66E0450D8DFE}
yUnit
{5426775D-93E1-4ab5-856E-A8E294E0FA42}
Edition of DIN standard.
standardEdition
{B5112550-F76B-43b2-87A6-61C2FC48A8C5}
DIN standard number.
standardNumber
{03FBE6F3-BCA6-4451-BDB6-5FD9511C24AF}
multiplier
{A51E3352-5194-435d-B70E-FCDB750E37D6}
unit
{C38A362A-6559-47ab-8747-99A10D4B404F}
The alternate model using the data.
AlternateModel
{CF5D1E33-0F2F-40d6-B260-30258F4FBA0D}.ClientEnd
ModelPartVersion
{2494ED30-254C-4f13-8F87-6FBEE03C2A4F}.ClientEnd
The profiles that describe the contents of the data set and the rules governing the contents of the data set.
Profile
{A554D44F-37A9-44b7-878F-CDC356BA0B3A}.SupplierEnd
Dataset referenced by this argument of a model operation..
Dataset
{5B31BEB7-2629-4c5a-B015-4D2B871D04D9}.SupplierEnd
The type of role for this dataset role. Should only reference role types that belong to the operation type of the associated operation.
OperationDatasetArgDescription
{235FF3E6-E90D-4131-B4D7-7709E41BBA9D}.SupplierEnd
The operation dataset roles conforming to this role type.
OperationDatasetArg
{235FF3E6-E90D-4131-B4D7-7709E41BBA9D}.ClientEnd
MarketDocument
{F49F44BE-047D-4792-8B5B-A3AA670AA0A1}.SupplierEnd
TimeSeries
{492E4897-E2BA-43e1-ABB0-94017A298B9D}.ClientEnd
Schedules that use this DayType.
SeasonDayTypeSchedules
{9B2613ED-CF92-429b-B26F-0EB80C658169}.SupplierEnd
Currency of this quantity.
currency
{B5002FB6-77FB-4f79-AF52-8498BED27EFB}
Unit multiplier of this quantity.
multiplier
{EE76FF5C-81AF-4694-80E3-5FCA5BB2FE75}
Unit of this quantity.
unit
{C93A29DD-02C6-49fd-90CF-3F0E40EAAEB1}
DefaultBidCurve
{310A11B7-605C-46ea-BD24-2F81FE8AE402}.SupplierEnd
RegisteredResource
{F24F3D0F-AE1B-4418-B515-B72D77505E5F}.SupplierEnd
Default bid type such as Default Energy Bid Default Minimum Load Bid and Default Startup Bid
bidType
{5E7AEF07-C92E-43d6-9ABF-72137169F171}
Minimum load cost in hr
minLoadCost
{FCED7648-1A1F-4a02-9ED5-04260C8348B8}
onpeak offpeak or all
peakFlag
{2052DBBD-E4CC-4e04-97A7-F02329FB5B0F}
DefaultBid
{310A11B7-605C-46ea-BD24-2F81FE8AE402}.ClientEnd
Default energy bid adder flag
debAdderFlag
{9EDCAA98-3D30-4975-B6AF-7FB6187048DF}
Type of calculation basis used to define the default bid segment curve.
bidSegmentCalcType
{5250E18B-4E0C-445a-B3E5-E037B8196B7B}
SecurityConstraintSum
{59C7A4B0-0AB0-47cf-B08A-D99F0E01C0D2}.SupplierEnd
BlockingFunction
{5B3BF302-273E-40f1-A888-A5FFEDE8F08F}.SupplierEnd
CCAinverter
{CBF65696-C189-4ab1-A0C3-34B7539B34A1}.SupplierEnd
CCArectifierControl
{AF4309DA-72A5-4b21-80EC-9653AF6D0620}.SupplierEnd
DCvoltageControl
{8B9A7786-D683-4dac-9D0C-983AB413A565}.SupplierEnd
IdcInverterControl
{F80046F2-833E-473c-81F7-F2217DD56589}.SupplierEnd
PFmode
{0A11698D-6954-4f58-B75E-3CBA73047718}.SupplierEnd
Pcontrol
{BB5EF20F-F668-4cd3-A8C9-5EAA0AD5F5CF}.SupplierEnd
Qlimiter
{784225EE-19A9-4cf5-9299-DAD1950C5181}.SupplierEnd
Qmode
{2303C7D4-EE85-47ba-A595-6180D607EEBD}.SupplierEnd
Qregulator
{B244C310-A752-4f97-8CF9-0D6D0C1AB836}.SupplierEnd
Umode
{84D84ECC-705D-4a61-8B63-60A505B5791B}.SupplierEnd
VDCOL
{DA56FBC7-3797-4264-AE29-61FEBA3C58F7}.SupplierEnd
Time constant.
tm
{046E0C92-C223-47e6-83D3-E54551B2504C}
All customer agreements through which the customer is enrolled in this demand response program.
CustomerAgreements
{C5454F40-D260-4575-8095-135824469D69}.SupplierEnd
All groups of end devices enrolled in this demand response program.
EndDeviceGroups
{2533FBD9-FD86-4734-8759-F972A0C201D4}.SupplierEnd
All usage point groups enrolled in this demand response program.
UsagePointGroups
{36AB849B-4EDC-45e7-98B2-FCA2BC154E2B}.SupplierEnd
Interval within which the program is valid.
validityInterval
{CDF96F9D-AB07-4564-B27E-B2EDAD457112}
ConditionFactors
{B55CE47A-87D3-4069-AE0A-CD19D6B6247B}.SupplierEnd
DesignLocations
{8A82D1F1-DAB4-4972-8F4B-4009DDB5610B}.ClientEnd
DesignLocationsCUs
{49C94F22-F928-4d51-B2E1-CB0EDE52918C}.ClientEnd
ErpBOMs
{385BF030-903C-4fb9-9B45-AE7199B9E2C6}.SupplierEnd
ErpQuoteLineItem
{F494C91F-54E1-42e7-88D5-BEAED03ACDBB}.ClientEnd
Work
{B42E2297-AE8B-42e0-A3FF-529C6B2C87D8}.SupplierEnd
WorkCostDetails
{80D53051-C6F7-4c80-B186-FF6AFCC33A66}.SupplierEnd
WorkTasks
{83CD7FF8-6559-45a7-AB79-BA79FC3B1C82}.SupplierEnd
Estimated cost not price of design.
costEstimate
{AFE4F920-721B-4e16-913B-FF7548C42ECF}
Kind of this design.
kind
{FE9AA4C0-2353-4590-96BB-0766CB6691D1}
Price to customer for implementing design.
price
{1A85DFF8-DE4A-4eac-9FF6-73FE8C10902B}
ConditionFactors
{01106373-66A2-47e6-BE11-C6EB50A8EA95}.SupplierEnd
DesignLocationCUs
{95DC38C2-5D26-4c4a-8D5D-D38F24B0646F}.SupplierEnd
Designs
{8A82D1F1-DAB4-4972-8F4B-4009DDB5610B}.SupplierEnd
ErpBomItemDatas
{4962575B-8FF3-4dfb-8A66-0E1F572C4D90}.ClientEnd
MiscCostItems
{ECAD85F3-E7E4-48d0-B3DF-81B8B5795C03}.SupplierEnd
WorkLocations
{A50D6CAA-AFDC-4c79-A4FF-B15AE7381D4F}.SupplierEnd
The legth of the span from the previous pole to this pole.
spanLength
{1A3D5C61-B5B2-4913-A207-14016F7AF0DB}
status
{C604F7EE-496E-4aae-A5DC-01CFB6F8B7C3}
CUGroups
{324E1A81-07DF-4842-8F2C-ED32F058D0AD}.SupplierEnd
CompatibleUnits
{B11E2CCC-4BD2-4bb3-AC4A-FC61ADF42FD2}.ClientEnd
ConditionFactors
{A2A64DC1-F71D-4a0f-9604-744445395515}.SupplierEnd
DesignLocation
{95DC38C2-5D26-4c4a-8D5D-D38F24B0646F}.ClientEnd
Designs
{49C94F22-F928-4d51-B2E1-CB0EDE52918C}.SupplierEnd
WorkTasks
{FCF781BC-040D-407f-A030-D5BB3656B390}.SupplierEnd
A code that instructs the crew what action to perform.
cuAction
{CBE9C761-A1AF-48a9-BB99-1C592FC57F82}
The quantity of the CU being assigned to this location.
cuQuantity
{B27707D1-10B7-457c-A090-4DF5771F82CC}
status
{FF5E175C-2EBB-4f0c-865A-C052F3A0C7CC}
Phases diagnosed.
phaseCode
{937BAB01-A522-47f4-B440-699DD97A335D}
A diagram is made up of multiple diagram objects.
DiagramElements
{5C4A600A-6EA7-4ac1-A144-9E7C309F375B}.ClientEnd
A Diagram may have a DiagramStyle.
DiagramStyle
{442E3273-18B9-4a81-A9E5-42B612D453BC}.ClientEnd
Coordinate system orientation of the diagram. A positive orientation gives standard righthand orientation with negative orientation indicating a lefthand orientation. For 2D diagrams a positive orientation will result in X values increasing from left to right and Y values increasing from bottom to top. A negative orientation gives the lefthand orientation favoured by computer graphics displays with X values increasing from left to right and Y values increasing from top to bottom.
orientation
{E434F373-9059-4d4e-8D77-8532E6D6E20A}
A diagram object is part of a diagram.
Diagram
{5C4A600A-6EA7-4ac1-A144-9E7C309F375B}.SupplierEnd
A diagram object can have 0 or more points to reflect its layout position routing for polylines or boundary for polygons.
DiagramObjectPoints
{4DFBB74F-9127-43ee-A7AA-04329802814F}.SupplierEnd
A diagram object has a style associated that provides a reference for the style used in the originating system.
DiagramObjectStyle
{2D17C38C-27D8-402d-9B7B-687AC6753212}.SupplierEnd
The domain object to which this diagram object is associated.
IdentifiedObject
{03423B70-34E0-4313-B19B-5FAFFD1F143B}.ClientEnd
A diagram object can be part of multiple visibility layers.
VisibilityLayers
{86380B03-52EA-473d-9BFA-DCDAAE9D1275}.SupplierEnd
Sets the angle of rotation of the diagram object. Zero degrees is pointing to the top of the diagram. Rotation is clockwise. DiagramObject.rotation0 has the following meaning The connection point of an element which has one terminal is pointing to the top side of the diagram. The connection point From side of an element which has more than one terminal is pointing to the top side of the diagram.DiagramObject.rotation90 has the following meaning The connection point of an element which has one terminal is pointing to the right hand side of the diagram. The connection point From side of an element which has more than one terminal is pointing to the right hand side of the diagram.
rotation
{57D901DD-45DA-42f6-8A86-9C0EDBB27214}
A diagram object glue point is associated with 2 or more object points that are considered to be glued together.
DiagramObjectPoints
{1C8A6E42-935B-4a26-88C0-9F9E2AB80D36}.ClientEnd
The diagram object with which the points are associated.
DiagramObject
{4DFBB74F-9127-43ee-A7AA-04329802814F}.ClientEnd
The glue point to which this point is associated.
DiagramObjectGluePoint
{1C8A6E42-935B-4a26-88C0-9F9E2AB80D36}.SupplierEnd
A style can be assigned to multiple diagram objects.
StyledObjects
{2D17C38C-27D8-402d-9B7B-687AC6753212}.ClientEnd
A DiagramStyle can be used by many Diagrams.
Diagram
{442E3273-18B9-4a81-A9E5-42B612D453BC}.SupplierEnd
Specifications
{5070DD0D-A85D-4e3a-8E88-6373ED2A15DE}.SupplierEnd
Depth measurement.
sizeDepth
{8CA22E0C-AE30-4e4b-A78F-CC7B0DEA1E13}
Diameter measurement.
sizeDiameter
{77974126-F80A-4c77-A2BC-48E0FAD3DF66}
Length measurement.
sizeLength
{9F24975A-B14C-464a-8A28-F46A5E7C8639}
Width measurement.
sizeWidth
{1BECEC72-9FD0-479a-8909-0DA023E7C4CB}
Speed change reference iEiisubSCsubi. Typical value 00015.
esc
{172C9946-71BF-4ce9-827C-06C056BD6AD5}
Discontinuous controller gain iKiisubANsubi. Typical value 400.
kan
{88CC3392-903C-43de-A1EE-BE2D080B870A}
Terminal voltage limiter gain iKiisubETLsubi. Typical value 47.
ketl
{83F2BC2C-2EC5-428c-98C0-FC6222093505}
Discontinuous controller time constant iTiisubANsubi gt 0. Typical value 008.
tan
{7227B496-A2E3-4045-85FE-A26F3D5C9C5E}
Time constant iTiisubDsubi gt 0. Typical value 003.
td
{970BD9AF-B8EA-4e22-BA31-C7078F7F3133}
Time constant iTiisubLsubisub1sub gt 0. Typical value 0025.
tl1
{F4408EC1-D7EE-4f4b-973E-B4070BA55DA0}
Time constant iTiisubLsubisub2sub gt 0. Typical value 125.
tl2
{506691B3-18F2-4c8e-92A9-0C3154858E2B}
DEC washout time constant iTiisubWsubisub5sub gt 0. Typical value 5.
tw5
{1B492332-80E5-422c-A56D-54FFD9FAB3CF}
Regulator voltage reference iViisubALsubi. Typical value 55.
val
{EC9A7984-C6A5-4319-AD4D-D46AC9790C97}
Limiter for Van iViisubANMAXsubi.
vanmax
{CE193B01-E2AE-45c6-98CD-C890EE03B4C1}
Limiter iViisubOMAXsubi gt DiscExcContIEEEDEC1A.vomin. Typical value 03.
vomax
{EECCE353-99A8-4bfc-A7D1-AECB07E9EAD0}
Limiter iViisubOMINsubi lt DiscExcContIEEEDEC1A.vomax. Typical value 01.
vomin
{810E9315-9BA9-4a34-B7BC-3631ECE82DE5}
Limiter iViisubSMAXsubigt DiscExcContIEEEDEC1A.vsmin. Typical value 02.
vsmax
{2FD546AC-AFF6-4fcf-823B-0C142FD5FBA1}
Limiter iViisubSMINsubi lt DiscExcContIEEEDEC1A.vsmax. Typical value 0066.
vsmin
{9C0ACCC9-B247-401e-B997-D81A9A60BE64}
Terminal voltage level reference iViisubTCsubi. Typical value 095.
vtc
{B3DE8330-7230-49c7-83C8-2551D44B2303}
Voltage reference iViisubTLMTsubi. Typical value 11.
vtlmt
{A202F3AA-46AC-4521-9CE3-0CA09A4C6DA5}
Voltage limits iViisubTMsubi. Typical value 113.
vtm
{DD958E61-3B62-40e8-A4F6-6D0D505AB8D1}
Voltage limits iViisubTNsubi. Typical value 112.
vtn
{ACE1B286-58AE-4e24-BAD1-16E644F811CC}
Discontinuous controller time constant iTiisubD1subi gt 0.
td1
{E20100A4-74B6-4ec3-9A0E-7813996D9C38}
Discontinuous controller washout time constant iTiisubD2subi gt 0.
td2
{8D004634-40A6-4121-A3BA-BC846E2E4DED}
Limiter iViisubDMAXsubi gt DiscExcContIEEEDEC2A.vdmin.
vdmax
{57AB7FA7-2F12-41ee-83B3-197DFFA2DCB5}
Limiter iViisubDMINsubi lt DiscExcContIEEEDEC2A.vdmax.
vdmin
{A7F4989B-D46C-4d29-BCA0-F3B227599743}
Discontinuous controller input reference iViisubKsubi.
vk
{28170B37-E740-436e-80D2-7A4ED20E26D9}
Reset time delay iTiisubDRsubi gt 0.
tdr
{4077841F-B769-4643-BA0D-C0BB0509F5F1}
Terminal undervoltage comparison level iViisubTMINsubi.
vtmin
{689FCDEC-CF19-43df-ADCC-4C388B8D9571}
Excitation system model with which this discontinuous excitation control model is associated.
ExcitationSystemDynamics
{A3CB1790-95C9-404f-AA0A-91B8334A0AD4}.SupplierEnd
Remote input signal used by this discontinuous excitation control system model.
RemoteInputSignal
{912E18D5-6BA7-4363-935C-5AAF4DB0471F}.SupplierEnd
Parameter of this proprietary userdefined model.
ProprietaryParameterDynamics
{2215F246-53D4-4620-8772-22C2E52230A8}.ClientEnd
The values connected to this measurement.
DiscreteValues
{41BE70FA-EA78-443a-B335-3469A779A71B}.SupplierEnd
The ValueAliasSet used for translation of a MeasurementValue.value to a name.
ValueAliasSet
{27083F43-08EC-487a-A912-C969A351E021}.ClientEnd
The Control variable associated with the MeasurementValue.
Command
{DF0C3745-2D94-4daa-8AA0-20AE415D601B}.SupplierEnd
Measurement to which this value is connected.
Discrete
{41BE70FA-EA78-443a-B335-3469A779A71B}.ClientEnd
RegisteredResource
{E391D3A8-763C-4236-AF13-BC42EC2166B1}.ClientEnd
The accepted mw amount by the responder. aka response mw.
acceptMW
{3216C94B-7EE7-4e42-A9EE-C18A0CA630DB}
The accept status submitted by the responder. enumeration type needs to be defined
acceptStatus
{967EE71B-9B30-4bdf-903F-9EB7F81C2393}
MW amount associated with instruction. For 5 minute binding dispatches this is the Goto MW or DOT
clearedMW
{7FF96547-69BC-4168-8928-DB954D863201}
The type of run for the market clearing.
passIndicator
{EC31AE13-EC8F-40be-9F3D-6A6DCDCC3217}
DERCurveData
{3FA9A03E-1846-4bc5-A641-F8A630355CC2}.ClientEnd
DERMonitorableParameter
{EF7AB537-05B9-4c9e-BAFA-5C4082E903B4}.SupplierEnd
confidence
{2B8421FD-D0D9-4d20-AA11-2760FB9F126F}
Used to specify whether the values over an interval are constant constantYValue or linearly interpolated straightLineYValues
curveStyleKind
{643CD3F7-65EB-4070-8242-B44BF0061219}
The unit of measure for the time axis of the dispatch schedule.
timeIntervalUnit
{B00E0FE8-D5BC-4ebf-BF39-9EACD6568503}
The generic class to support all field end devices such as meters or smart inverters
EndDevice
{2FF7FB6F-CDF4-4bd3-A5ED-857FF363E2B0}.ClientEnd
EndDeviceGroup is used in metering to group end devices this same class is used to group DER
EndDeviceGroup
{EE555BAA-0173-4a8c-ACAF-EB8D9421DF51}.ClientEnd
The current level of active power for a DER group
currentActivePower
{90D71C31-4AD1-4d8e-B733-122B6FEAC8BF}
The current level of apparent power for a DER group
currentApparentPower
{87595782-F158-4046-9575-2070F7060333}
The current level of reactive power for a DER group
currentReactivePower
{4279B3B8-5ECE-4255-A60B-0E237E624B6D}
The maximum level of active power to which a DER group can be set
maxActivePower
{C07156AE-21BC-42f1-8C27-5B599FDCA0A6}
The maximum level of apparent power to which a DER group can be set
maxApparentPower
{94265724-8C55-419b-B959-97A6393A6B05}
The maximum level of reactive power to which a DER group can be set
maxReactivePower
{4CCC87E4-9FE9-45cc-8F4F-6D6D5EF4E47C}
The minimum level of active power to which a DER group can be set
minActivePower
{7F04A927-F0CB-4631-906A-8D91E64EB691}
The minimum level of apparent power to which a DER group can be set
minApparentPower
{9C6402A0-FCD1-46fa-9CF0-9F5AE893B5D9}
The minimum level of reactive power to which a DER group can be set
minReactivePower
{1F575DA3-88DC-493c-AC9B-A1DD4D766484}
multiplier
{7F29E08D-5FC0-46b1-93BB-874F7BB2F23A}
unit
{A747743C-3DB2-4e12-984B-0857DF0555A8}
ActualDemandResponseEvents may exist that are not part of a coordinated MarketActualEvent associated to a Market. These ActualDemandResponseEvents can have many InstructionClearing Instructions for specified RegisteredResources or DemandResponse AggregateNodes.
InstructionClearing
{7B14AF42-A7C8-4839-AEBA-18F104ABE94C}.SupplierEnd
InstructionClearingDOT
{01022165-D079-41fa-B9C3-342CFFA5E537}.SupplierEnd
ResourcePerformanceEvaluations
{568AA2F2-D906-4139-AA0D-393E92602084}.SupplierEnd
Total active power adjustment e.g. load reduction requested for this demand response event.
totalPowerAdjustment
{0A67C2F5-36BF-43f3-9C8D-06A954CD73C3}
GenDistributionFactor
{A0057A86-6FBB-46b3-A9AE-B72D9CDACC6F}.SupplierEnd
LoadDistributionFactor
{49BDACA6-0568-4346-BD7A-07BB3DE08C0C}.SupplierEnd
SysLoadDistribuFactor
{5262F3D5-E6F1-466a-998C-AE0F2E35DBDF}.SupplierEnd
Market type.
marketType
{A61C37F5-C559-4b7c-8809-58FF3C271C76}
Edition of Doble standard.
standardEdition
{ECE4670E-DE75-4f2b-8352-31666F287CD6}
Doble standard number.
standardNumber
{ABD1A107-EF81-4d64-A8A6-54AF3A42CB3F}
Approver of this document.
Approver
{E773805D-E6AC-4d17-9B2A-5E6338923314}.ClientEnd
Author of this document.
Author
{335F0BDA-9420-40ee-B636-5FAD6485F1BB}.ClientEnd
All configuration events created for this document.
ConfigurationEvents
{E33CE794-1D36-4889-BDFB-F26AF8508188}.SupplierEnd
Editor of this document.
Editor
{9F6834C3-98EF-4108-BAB4-479EA61806B9}.ClientEnd
Issuer of this document.
Issuer
{D3F6B3FF-697C-4b9b-845F-66D92692128D}.ClientEnd
Status of this document. For status of subject matter this document represents e.g. Agreement Work use status attribute.Example values for docStatus.status are draft approved cancelled etc.
docStatus
{1898F2ED-210C-46df-AAB7-8A37EE47FB1C}
Electronic address.
electronicAddress
{CD388106-E7BD-4660-9E52-2BDD15EA7E07}
Status of subject matter e.g. Agreement Work this document represents. For status of the document itself use docStatus attribute.
status
{6F277455-3C17-4593-9FB7-F7059BD2EAB6}
MarketDocument
{65A175B6-9924-45f6-8876-8254B2486786}.ClientEnd
Price
{58FBC0F0-40DD-4dbd-A8BE-9C241403F4DB}.ClientEnd
Quantity
{3C6AC9D3-B254-422b-83E0-AD878F50E02C}.ClientEnd
RegisteredResource
{2883C3D9-C348-4a3e-A321-5E35C932E66E}.SupplierEnd
TimeSeries
{35183B72-4EB4-4c7d-BDCB-158AC35D6ACC}.ClientEnd
InstructionClearingDOP
{21EAE1E5-554D-4e8e-BE91-8FB6E528D842}.ClientEnd
RegisteredResouce
{0A0711E7-CD6A-49ca-AFBB-0BB1AE61425F}.ClientEnd
Dispatched Operating Point MW
mwDOP
{10EE6A86-5A50-4b91-91AD-C287F12EEC14}
Indication of DOP validity. Shows the DOP is calculated from the latest run YES. A NO indicator shows that the DOP is copied from a previous execution.Up to 2 intervals can be missed.
runIndicatorDOP
{0BF77B7A-C011-47d0-8F36-EB1FC2218A10}
updateType
{3A01D202-092F-48c4-A98E-CE9001DD10B4}
InstructionClearingDOT
{CEC60D6E-B919-43a0-9B3B-92AE42278138}.ClientEnd
RegisteredResource
{090DD6C1-3007-4b20-A995-9A43659E6687}.SupplierEnd
Flag indicating whether or not the resource was in compliance with the instruction plusminus 10.Directs if a unit is allowed to set the price expost pricing.
compliantIndicator
{5C2DDA7A-E4FE-4fb1-AE1C-58F1B89F8027}
Regulation Status YesNo.
regulationStatus
{5857EC73-37BB-4e8f-BFAC-79D78E2B1A97}
WireSpacingInfos
{18C29DE2-77AC-4a90-9E3D-065A8BC002CE}.ClientEnd
Part of current that constitutes the arrears portion.
arrears
{0910CAA8-10E1-4c33-B334-41D83198EC03}
Part of current that constitutes the charge portion charges Charge.fixedPortion Charge.variablePortion.
charges
{5CE62A2B-0CD9-43ed-95A6-51E11BF0ABFF}
Current total amount now due current principle arrears interest charges. Typically the rule for settlement priority is interest dues then arrears dues then current dues then charge dues.
current
{D16FCD2A-FB4F-4b0b-9A6F-BC591ABE0C6C}
Part of current that constitutes the interest portion.
interest
{76933F35-C90B-44ad-84D5-7ABEB79796A0}
Part of current that constitutes the portion of the principle amount currently due.
principle
{E4EBB98D-4B22-46ba-9415-B8DBF47C1D07}
MktMeasurement
{10B4C6E2-CE00-43d6-91C5-CA7BF16D48A2}.SupplierEnd
A control area can receive dynamic schedules from other control areas
Receive_SubControlArea
{83DC5357-DC69-4c13-B260-5026E5DFD942}.SupplierEnd
A control area can send dynamic schedules to other control areas
Send_SubControlArea
{CB9AAC47-376D-4a7e-9E56-D14A4F86E63E}.SupplierEnd
Edition of EPA standard.
standardEdition
{C09A42E0-AD45-42c7-9898-09A86B390774}
EPA standard number.
standardNumber
{D44EBFAB-2963-4cf3-A66D-EEC8D0FD66CD}
Nominal resistance of device.
r
{6063FBE9-5BE7-424a-AC8F-116EF8F9A799}
The depth below the earths surface of the earthquakes focal point.
focalDepth
{223FD0E0-7F8D-4779-A758-05F04C5101B9}
All documents for this editor.
Documents
{9F6834C3-98EF-4108-BAB4-479EA61806B9}.SupplierEnd
multiplier
{10B02EE7-C719-4b76-AF42-2DB6CDACF235}
unit
{7F887802-EF0E-4dc3-9D85-EED40B85E697}
A thermal generating unit may have one or more emission allowance accounts.
ThermalGeneratingUnit
{0EFC6C1E-3654-4ea3-8239-30E44E8AE7C6}.SupplierEnd
The type of emission for example sulfur dioxide SO2. The y1AxisUnits of the curve contains the unit of measure e.g. kg and the emissionType is the type of emission e.g. sulfur dioxide.
emissionType
{8E04793A-9D24-4870-AD87-04672F8E25D4}
The source of the emission value.
emissionValueSource
{16976F7B-25CE-4278-B31F-FB77890C44B1}
A thermal generating unit may have one or more emission curves.
ThermalGeneratingUnit
{754BD49F-EE90-408a-AEBF-B56AA6C8DA69}.SupplierEnd
The emission content per quantity of fuel burned.
emissionContent
{2D3A1FFE-0A0D-4611-AB59-A8FFA7C779BD}
The type of emission which also gives the production rate measurement unit. The y1AxisUnits of the curve contains the unit of measure e.g. kg and the emissionType is the type of emission e.g. sulfur dioxide.
emissionType
{BD126748-C143-460f-B135-9839304819C6}
Customer owning this end device.
Customer
{CAC11EF6-DAA4-4489-BC90-BFEC70C14E61}.ClientEnd
DispatchablePowerCapability
{2FF7FB6F-CDF4-4bd3-A5ED-857FF363E2B0}.SupplierEnd
All end device controls sending commands to this end device.
EndDeviceControls
{5BFE769E-C4DE-4ab2-9C07-508135C7CD60}.ClientEnd
All events reported by this end device.
EndDeviceEvents
{180BCB9D-1019-4de2-A8A5-3E3FFC3F9022}.ClientEnd
All end device functions this end device performs.
EndDeviceFunctions
{2D6571AD-1092-4ed8-985C-487191687354}.SupplierEnd
All end device groups referring to this end device.
EndDeviceGroups
{ECC0A3D0-FE2F-4df0-B5E6-AB34DDF3162B}.ClientEnd
End device data.
EndDeviceInfo
{2131605C-1AA8-4b31-8DC3-70BFAB2B02BE}.SupplierEnd
Service location whose service delivery is measured by this end device.
ServiceLocation
{E1374558-A400-46da-9FB2-5F7497097A3D}.ClientEnd
Usage point to which this end device belongs.
UsagePoint
{6B05F0D3-B04B-4b78-AF42-4AC3046EF869}.ClientEnd
Time zone offset relative to GMT for the location of this end device.
timeZoneOffset
{7C36F17C-4DDF-4f83-A483-664F1357B439}
End device control issuing this end device action.
EndDeviceControl
{0BF8F40B-72F8-4982-ACED-E7FDF669BA66}.ClientEnd
Amount of time the action of this control is to remain active.
duration
{67B2260C-8823-4042-A63F-C5DDC04678C2}
End device action issued by this end device control.
EndDeviceAction
{0BF8F40B-72F8-4982-ACED-E7FDF669BA66}.SupplierEnd
Type of this end device control.
EndDeviceControlType
{FC153ACC-DBB0-4502-A82D-045850FF2C2F}.SupplierEnd
All end device groups receiving commands from this end device control.
EndDeviceGroups
{47178028-E658-4042-AB65-A6F4DDD8ABF6}.ClientEnd
All end devices receiving commands from this end device control.
EndDevices
{5BFE769E-C4DE-4ab2-9C07-508135C7CD60}.SupplierEnd
All usage point groups receiving commands from this end device control.
UsagePointGroups
{DD9C2BA9-EDBB-4e7b-852C-9AD603C00339}.SupplierEnd
All usage points receiving commands from this end device control.
UsagePoints
{86BE91D2-4532-408d-85BE-C4192311A77E}.SupplierEnd
if applicable Price signal used as parameter for this end device control.
priceSignal
{B374E41E-03C8-4bf8-B26E-23AD77EAC544}
Timing for the control actions performed on the device identified in the end device control.
primaryDeviceTiming
{1E749747-5E54-49cf-AEF9-F9DE873855A6}
if control has scheduled duration Date and time interval the control has been scheduled to execute within.
scheduledInterval
{96304D21-4C37-4450-A079-7EF1740F370E}
Timing for the control actions performed by devices that are responding to event related information sent to the primary device indicated in the end device control. For example load control actions performed by a PAN device in response to demand response event information sent to a PAN gateway server.
secondaryDeviceTiming
{EAA38A87-29EC-4853-AB61-4971ED15A45E}
All end device controls of this type.
EndDeviceControls
{FC153ACC-DBB0-4502-A82D-045850FF2C2F}.ClientEnd
End device that reported this end device event.
EndDevice
{180BCB9D-1019-4de2-A8A5-3E3FFC3F9022}.SupplierEnd
All details of this end device event.
EndDeviceEventDetails
{4154C6F2-6B3E-4dd6-812B-AF5BE1AD1C57}.SupplierEnd
Type of this end device event.
EndDeviceEventType
{7D8504D4-36F9-40b3-B1FF-D401222F3166}.SupplierEnd
Set of measured values to which this event applies.
MeterReading
{DF4C0081-227B-4d2d-A692-33F732385A32}.ClientEnd
Usage point for which this end device event is reported.
UsagePoint
{8DB1B043-3C92-412a-967D-F037C7FA8E36}.SupplierEnd
End device owning this detail.
EndDeviceEvent
{4154C6F2-6B3E-4dd6-812B-AF5BE1AD1C57}.ClientEnd
Value including unit information.
value
{299CCA34-1297-4caf-996D-2178AC151F8E}
All end device events of this type.
EndDeviceEvents
{7D8504D4-36F9-40b3-B1FF-D401222F3166}.ClientEnd
End device that performs this function.
EndDevice
{2D6571AD-1092-4ed8-985C-487191687354}.ClientEnd
All registers for quantities metered by this end device function.
Registers
{EFFC4614-770D-4c79-9E7C-AD272DF81815}.ClientEnd
DERFunction
{AAA6DC66-3D4C-449d-8DAC-947317B28177}.ClientEnd
DERGroupDispatch
{4611E517-A1DA-440c-BD29-668CF1F495E2}.SupplierEnd
DERGroupForecast
{F0840A17-1419-47f0-BF59-87D100492401}.ClientEnd
DERMonitorableParameter
{56EE9BE9-6817-4022-967A-0AA909D120DE}.SupplierEnd
All demand response programs this group of end devices is enrolled in.
DemandResponsePrograms
{2533FBD9-FD86-4734-8759-F972A0C201D4}.ClientEnd
DispatchablePowerCapability
{EE555BAA-0173-4a8c-ACAF-EB8D9421DF51}.SupplierEnd
All end device controls sending commands to this end device group.
EndDeviceControls
{47178028-E658-4042-AB65-A6F4DDD8ABF6}.SupplierEnd
All end devices this end device group refers to.
EndDevices
{ECC0A3D0-FE2F-4df0-B5E6-AB34DDF3162B}.SupplierEnd
status
{19594095-DC78-4d0c-99AE-1F2CA363D2C9}
version
{CC16E974-92E2-4713-A63A-597B5CC46631}
All end devices described with this data.
EndDevices
{2131605C-1AA8-4b31-8DC3-70BFAB2B02BE}.ClientEnd
Inherent capabilities of the device i.e. the functions it supports.
capability
{3C69187E-19A8-4011-B110-F17BD943C14F}
Rated current.
ratedCurrent
{A902CC64-04CD-4f25-B6F0-71B08A465357}
Rated voltage.
ratedVoltage
{08DB4030-817C-45a6-833E-CC55FC5DFC02}
Duration of the end device control action or the business event that is the subject of the end device control.
duration
{3F7A241F-6ED7-4f3f-B536-249808517061}
Start and end time of an interval during which end device control actions are to be executed.
interval
{201051B2-B1EF-4f25-A09B-621B198E73D2}
Kind of randomisation to be applied to the end device control actions to be executed.
randomisation
{38C0C045-CAA0-4943-A7B8-51C9D1BC8637}
The control area specification that is used for the load forecast.
ControlArea
{91910331-E0D0-4b32-9E25-EC5310A60B71}.ClientEnd
EnergyConnection
{B5880CAA-2E1F-4e7e-8CBF-6E8FE1C9519B}.ClientEnd
EnergyGroup
{58AE497B-672B-4bcb-AABC-468888BDB9A9}.SupplierEnd
EnergyComponent
{B5880CAA-2E1F-4e7e-8CBF-6E8FE1C9519B}.SupplierEnd
EnergyConsumerAction
{FED8229A-5B6E-4728-A961-4E85004FEA54}.SupplierEnd
The individual phase models for this energy consumer.
EnergyConsumerPhase
{FE0DC706-B203-4f07-87D5-6218B836646E}.SupplierEnd
Load dynamics model used to describe dynamic behaviour of this energy consumer.
LoadDynamics
{4F34241A-F054-4f5c-8638-560DED3C98B4}.ClientEnd
The load response characteristic of this load. If missing this load is assumed to be constant power.
LoadResponse
{ABB1EF4C-2A3F-4c47-8D73-B51ADA827E97}.SupplierEnd
The energy consumer is assigned to this power cut zone.
PowerCutZone
{10EFC7AF-BD27-4bf9-A05B-BA2A5970F59A}.ClientEnd
Active power of the load. Load sign convention is used i.e. positive sign means flow out from a node.For voltage dependent loads the value is at rated voltage.Starting value for a steady state solution.
p
{5F072D7C-989F-4221-92F2-238C409B4AC2}
Active power of the load that is a fixed quantity and does not vary as load group value varies. Load sign convention is used i.e. positive sign means flow out from a node.
pfixed
{1B9A4235-96FD-4754-9AE5-58493961AAA7}
Fixed active power as a percentage of load group fixed active power. Used to represent the timevarying components. Load sign convention is used i.e. positive sign means flow out from a node.
pfixedPct
{BC15E69E-B780-4792-A3BD-227A4984C490}
The type of phase connection such as wye or delta.
phaseConnection
{7B4A86FE-9F52-4fcc-BAB3-328AC0CECA82}
Reactive power of the load. Load sign convention is used i.e. positive sign means flow out from a node.For voltage dependent loads the value is at rated voltage.Starting value for a steady state solution.
q
{3F213833-3540-4d30-9F05-5A94C9AA1B79}
Reactive power of the load that is a fixed quantity and does not vary as load group value varies. Load sign convention is used i.e. positive sign means flow out from a node.
qfixed
{156252BF-EDEF-4053-A545-045260EE2C8B}
Fixed reactive power as a percentage of load group fixed reactive power. Used to represent the timevarying components. Load sign convention is used i.e. positive sign means flow out from a node.
qfixedPct
{A4B42063-2491-41f9-AAF0-08CF42E84FF5}
EnergyConsumer
{FED8229A-5B6E-4728-A961-4E85004FEA54}.ClientEnd
Switching action to perform
kind
{5BEC25F0-DFF3-4618-AEF2-952866483784}
The energy consumer to which this phase belongs.
EnergyConsumer
{FE0DC706-B203-4f07-87D5-6218B836646E}.ClientEnd
Active power of the load. Load sign convention is used i.e. positive sign means flow out from a node.For voltage dependent loads the value is at rated voltage.Starting value for a steady state solution.
p
{E2356BA8-AADE-4948-A4C5-84D19C9BE6E0}
Active power of the load that is a fixed quantity. Load sign convention is used i.e. positive sign means flow out from a node.
pfixed
{2934D006-53E8-45e9-BC88-AFB3914CF82C}
Fixed active power as per cent of load group fixed active power. Load sign convention is used i.e. positive sign means flow out from a node.
pfixedPct
{8A9A40B2-4F06-4307-B603-2ECFE0E1732B}
Phase of this energy consumer component. If the energy consumer is wye connected the connection is from the indicated phase to the central ground or neutral point. If the energy consumer is delta connected the phase indicates an energy consumer connected from the indicated phase to the next logical nonneutral phase.
phase
{58399B74-5465-48b8-9E03-F04C4DBC4462}
Reactive power of the load. Load sign convention is used i.e. positive sign means flow out from a node.For voltage dependent loads the value is at rated voltage.Starting value for a steady state solution.
q
{E4F2B21F-8B60-4e52-875C-A9F4C40C84DA}
Reactive power of the load that is a fixed quantity. Load sign convention is used i.e. positive sign means flow out from a node.
qfixed
{9F37746E-4202-4b8f-9D11-D8ABC32FF9CD}
Fixed reactive power as per cent of load group fixed reactive power. Load sign convention is used i.e. positive sign means flow out from a node.
qfixedPct
{D0DF196B-DFA2-4115-9104-3460409B3DF4}
BlockDispatchInstruction
{3BC3FBEE-55AB-447d-A7C2-53E7591E1DC1}.ClientEnd
ControlArea
{EC0B638A-E0FD-42c8-B84C-47AA469B8629}.SupplierEnd
EnergyComponent
{58AE497B-672B-4bcb-AABC-468888BDB9A9}.ClientEnd
EnergyTypeReference
{1B0AA3EB-EBFC-4e11-A7A4-13206AA305E0}.SupplierEnd
SvPowerFlow
{9E145EE8-2544-4933-9DE4-FB008FF09419}.ClientEnd
p
{47D83F72-648B-45a6-9177-ADB63ABC3401}
Bids
{728667DC-DD4E-4059-AE1B-FBA6AD106FDB}.ClientEnd
MarketResults
{1BCDE256-7739-44fd-A327-E54563BBB888}.SupplierEnd
RTO
{7B226990-9273-4097-A3EE-975B7273F323}.SupplierEnd
RegisteredResources
{27C8750F-C833-4de8-B407-CF325D392A50}.SupplierEnd
Settlements
{53E470E2-1BB8-49d7-B69A-D59030A5D75A}.SupplierEnd
EnergyTransactions
{7865A63E-2D94-453e-A45B-329DA7F65903}.ClientEnd
FTRs
{38EA7E7F-BA90-431d-816C-66C5286F4757}.SupplierEnd
RegisteredGenerator
{984F3E09-1CA2-412e-9D3B-1138442A36D1}.SupplierEnd
EPI type such as wholesale or retail
energyPriceIndexType
{5D711A0C-F970-4134-A790-959969FF112A}
Valid period for which the energy price index is valid.
validPeriod
{7E58A026-A6F3-4690-9DF2-801317CCB4FF}
The Source for an EnergyTransaction is an EnergyProduct which is injected into a ControlArea. Typically this is a ServicePoint.
EnergyTransactions
{729CC4C8-25A1-41af-8A6B-09D7625F32E2}.ClientEnd
GenerationProvider
{824933A0-9111-4506-81AD-C90C98EB9B66}.SupplierEnd
A Marketer may resell an EnergyProduct.
ResoldBy_Marketer
{FFB388F3-6858-48ca-82BF-9BB8CF25DE4B}.SupplierEnd
A Marketer holds title to an EnergyProduct.
TitleHeldBy_Marketer
{45B2E11F-1F87-46d0-BEDA-714E73AB2B7B}.SupplierEnd
An EnergyTransaction shall have at least one EnergyProfile.
EnergyTransaction
{C129CB64-7DC6-41aa-94F3-0DC8A2B978D7}.SupplierEnd
TransactionBid
{E51D8A6A-35CA-4b26-B4D3-9E33C8AF5D95}.SupplierEnd
Energy Source of a particular Energy Scheduling Type.
EnergySource
{9E393194-24E9-4f6c-9801-8D38633121C9}.ClientEnd
Energy Scheduling Type of an Energy Source.
EnergySchedulingType
{9E393194-24E9-4f6c-9801-8D38633121C9}.SupplierEnd
Action taken with this energy source.
EnergySourceAction
{15E4933B-E1C8-4343-A4C1-6F00DC252FE6}.ClientEnd
The individual phase information of the energy source.
EnergySourcePhase
{774C7E8B-ABB6-4d42-9F1A-8C31613909B9}.ClientEnd
High voltage source active injection. Load sign convention is used i.e. positive sign means flow out from a node.Starting value for steady state solutions.
activePower
{5924942C-E957-4adf-B544-6038926E70E8}
Phasetophase nominal voltage.
nominalVoltage
{AC811957-8FE6-4c92-A301-20AE9D3BFA24}
This is the maximum active power that can be produced by the source. Load sign convention is used i.e. positive sign means flow out from a TopologicalNode bus into the conducting equipment.
pMax
{00037DC7-8613-4877-928B-BA846313A376}
This is the minimum active power that can be produced by the source. Load sign convention is used i.e. positive sign means flow out from a TopologicalNode bus into the conducting equipment.
pMin
{244B567C-A52D-4a89-9432-42EF3E26CD0C}
Positive sequence Thevenin resistance.
r
{EF264738-8B04-4eea-A024-F7D5E2DAA0F3}
Zero sequence Thevenin resistance.
r0
{864DC9B8-D243-400b-AF81-9495FD47BA0B}
High voltage source reactive injection. Load sign convention is used i.e. positive sign means flow out from a node.Starting value for steady state solutions.
reactivePower
{28125ED6-484D-4da2-A713-555556D025B4}
Negative sequence Thevenin resistance.
rn
{A36F03C0-ADF9-46ed-8051-6A031F820282}
Phase angle of aphase open circuit used when voltage characteristics need to be imposed at the node associated with the terminal of the energy source such as when voltages and angles from the transmission level are used as input to the distribution network. The attribute shall be a positive value or zero.
voltageAngle
{445142BE-097F-4954-9E89-325CE9D4D70E}
Phasetophase open circuit voltage magnitude used when voltage characteristics need to be imposed at the node associated with the terminal of the energy source such as when voltages and angles from the transmission level are used as input to the distribution network. The attribute shall be a positive value or zero.
voltageMagnitude
{A7B0DCB7-7ADA-4e63-A635-CEDCC43343BE}
Positive sequence Thevenin reactance.
x
{511C3E9E-75F0-42fd-8E16-A972A3C23E6D}
Zero sequence Thevenin reactance.
x0
{60183FA3-68AD-4510-B89D-3F5F9A1D1F77}
Negative sequence Thevenin reactance.
xn
{2BCE8602-2CB1-48b8-97AE-9163CC618BC7}
Energy source on which this action is taken.
EnergySource
{15E4933B-E1C8-4343-A4C1-6F00DC252FE6}.SupplierEnd
Switching action to perform.
kind
{53675AFA-3C31-4e93-BE1C-7A40BDA35158}
The energy sourceto which the phase belongs.
EnergySource
{774C7E8B-ABB6-4d42-9F1A-8C31613909B9}.SupplierEnd
Phase of this energy source component. If the energy source wye connected the connection is from the indicated phase to the central ground or neutral point. If the energy source is delta connected the phase indicates an energy source connected from the indicated phase to the next logical nonneutral phase.
phase
{0F8C51FC-C6FB-41e8-9023-EE4C8AA358E6}
An EnergyTransaction may be curtailed by any of the participating entities.
CurtailmentProfiles
{64C49984-0ED1-438b-9C5C-CE6E9784CFF1}.ClientEnd
EnergyPriceCurves
{7865A63E-2D94-453e-A45B-329DA7F65903}.SupplierEnd
The Source for an EnergyTransaction is an EnergyProduct which is injected into a ControlArea. Typically this is a ServicePoint.
EnergyProduct
{729CC4C8-25A1-41af-8A6B-09D7625F32E2}.SupplierEnd
An EnergyTransaction shall have at least one EnergyProfile.
EnergyProfiles
{C129CB64-7DC6-41aa-94F3-0DC8A2B978D7}.ClientEnd
Energy is transferred between interchange areas
Export_SubControlArea
{FE5AFCF1-5AF3-41b8-A9F4-38F6BDF94098}.ClientEnd
Energy is transferred between interchange areas
Import_SubControlArea
{2143F763-800E-436a-B8FB-44CEB5B9E1EB}.ClientEnd
An EnergyTransaction may have a LossProfile.
LossProfiles
{0E272DF7-73BF-495c-AEAE-1F184C3A0031}.ClientEnd
A dynamic energy transaction can act as a pseudo tie line.
TieLines
{F598C617-D4AC-4af6-8714-13A45A6CFB71}.SupplierEnd
TransmissionReservation
{AC1E24EF-9143-4c28-B275-913E3666B245}.ClientEnd
Maximum congestion charges in monetary units.
congestChargeMax
{D060A9B8-A278-439d-8A10-BC9DAD0F37E4}
Delivery point active power.
deliveryPointP
{F6874DA3-064D-4792-9469-1B66229ADBE9}
Transaction minimum active power if dispatchable.
energyMin
{1D2E5BB6-B89B-4547-B9A6-4277624C3DCE}
Receipt point active power.
receiptPointP
{A3DFB79A-E8BA-4741-A303-5BA2833A0682}
Approve Deny Study
state
{D5E3908F-E2A8-44f9-AE49-5B600C31942F}
EnergyGroup
{1B0AA3EB-EBFC-4e11-A7A4-13206AA305E0}.ClientEnd
kind
{F480474F-E711-4470-92B8-B4ECAEB83994}
The list of alert types from which the type of this alert is drawn.
AlertTypeList
{47BAF174-F27B-42ab-8162-CA6C1C444323}.SupplierEnd
Environmental data provider for this alert.
EnvironmentalDataProvider
{ACFE0532-D3AF-4f98-950B-B9B06426E751}.SupplierEnd
Type of location to which this environmental alert applies.
EnvironmentalLocationKind
{36C399B4-711A-4109-91F3-44F367B8F1B3}.SupplierEnd
The interval for which this weather alert is in effect.
inEffect
{BEC3F7C0-9592-4780-85CE-57AB1E77AFF6}
Classification condition which this analog helps define.
ClassificationCondition
{8B13B03E-D662-45ec-9CC3-71515B9D13CA}.SupplierEnd
Observation or forecast with which this environmental analog measurement is associated.
EnvironmentalInformation
{6901EAB0-A9FB-4874-AC91-147B47110113}.SupplierEnd
Monitoring station which provides this environmental analog measurement.
EnvironmentalMonitoringStation
{C0F501A7-2245-4a22-A8A6-E8BC3E6BBBB9}.SupplierEnd
The reporting capability this environmental value set helps define.
ReportingCapability
{33EE49E4-C5C2-447f-B5D2-DA0AF83C0024}.SupplierEnd
Code representing the coverage of the weather condition.
coverageKind
{8ACD984F-A238-4e25-A7C9-957F72060D0C}
Code representing the intensity of the weather condition.
intensityKind
{5CCD093C-5C15-448f-84C8-71DF39536243}
Probability of weather condition occurring during the time interval expressed as a percentage. Applicable only when weather condition is related to a forecast not an observation.
probabilityPercent
{80B9FACF-F5A0-439f-BE98-3FFC9B761B19}
Code representing the type of weather condition.
weatherKind
{E804C8CA-6BBB-4d4a-BB1C-BF2E36C21A55}
A specific version of a list of alerts published by this environmental data authority.
AlertTypeList
{2A299E0C-C0CE-4200-AE97-FBD32E1BCFE0}.ClientEnd
Phenomenon classification defined by this environmental data authority.
PhenomenonClassification
{A0D7C120-ECE6-4c9b-B9F6-B37F0029DA01}.ClientEnd
Alert issued by this environmental data provider.
EnvironmentalAlert
{ACFE0532-D3AF-4f98-950B-B9B06426E751}.ClientEnd
Environmental information provided by this environmental data provider.
EnvironmentalInformation
{FF5E2F77-FC5C-40cd-AA83-A72FE1FC7C06}.ClientEnd
Observation or forecast with which this environmental discrete integer is associated.
EnvironmentalInformation
{BC06D77F-CD71-4f36-9D8A-7E8192355052}.SupplierEnd
Kind of environmental discrete integer.
kind
{DF3B1AE2-0DCD-4d35-97ED-5C30CE23F31C}
Forecast or observation related to this environmental event.
EnvironmentalInformation
{7DDC866E-3A61-461b-8E5F-92509F7E781D}.SupplierEnd
Environmental analog associated with this observation or forecast.
EnvironmentalAnalog
{6901EAB0-A9FB-4874-AC91-147B47110113}.ClientEnd
Environmental data provider supplying this environmental information.
EnvironmentalDataProvider
{FF5E2F77-FC5C-40cd-AA83-A72FE1FC7C06}.SupplierEnd
Environmental discrete integer associated with this observation or forecast.
EnvironmentalDiscrete
{BC06D77F-CD71-4f36-9D8A-7E8192355052}.ClientEnd
Environmental event to which this forecast or observation relates.
EnvironmentalEvent
{7DDC866E-3A61-461b-8E5F-92509F7E781D}.ClientEnd
EnvironmentalPhenomenon
{F4F99E9D-5DA9-4ea5-B1C7-69F676562B14}.ClientEnd
Environmental string measurement associated with this forecast or observation.
EnvironmentalStringMeasurement
{4492BBDD-51E1-414b-8D40-F554831AB71A}.ClientEnd
Environmental alert applying to location of this type.
EnvironmentalAlert
{36C399B4-711A-4109-91F3-44F367B8F1B3}.ClientEnd
Environmental phenomenon for which this location is of relevance.
EnvironmentalPhenomenon
{230EC626-6F7A-420a-849C-C0C8A1FD4A45}.ClientEnd
Location of this instance of ths kind of environmental location.
Location
{153D33F0-C3EC-4cda-8188-6776F6BD789B}.SupplierEnd
The kind of location. Typical values might be center extent primary secondary etc.
kind
{1CB2D9F7-AF43-42f0-BCC6-6AF5A8756332}
Environmental analog measurement provided by this monitoring station.
EnvironmentalAnalog
{C0F501A7-2245-4a22-A8A6-E8BC3E6BBBB9}.ClientEnd
Location of this monitoring station.
Location
{17713B5C-F047-400e-ADE7-5B55F485CA85}.SupplierEnd
One of the reporting capabilities of this monitoring station.
ReportingCapability
{6335EFF8-1839-4f0f-A97C-CC890F5D5411}.ClientEnd
TimeSeries
{6E714075-8668-4e58-A652-65C0CBEF02BF}.ClientEnd
UsagePoint
{11F52D5E-EFC9-4c29-A3F6-7C2E9E192F0C}.SupplierEnd
The time offset from UTC a.k.a. GMT configured in the station clock not necessarily the time zone in which the station is physically located.This attribute exists to support management of utility monitoring stations and has no direct relationship to the manner in which time is expressed in EnvironmentalValueSet.
timeZoneOffset
{34BCB6AC-3B39-43ea-A37A-C5FBFB3924C9}
The forecast or observation of which this phenomenon description is a part.
EnvironmentalInformation
{F4F99E9D-5DA9-4ea5-B1C7-69F676562B14}.SupplierEnd
Location of relevance to this environmental phenomenon.
EnvironmentalLocationKind
{230EC626-6F7A-420a-849C-C0C8A1FD4A45}.SupplierEnd
The classification of this phenomenon.
PhenomenonClassification
{CEAA1D59-2A12-4a25-A69D-ACC8789B4E11}.SupplierEnd
The timestamp of the phenomenon as a single point or time interval.
timeInterval
{B2C5E855-5376-4537-8E1A-C847A2AB3600}
Classification condition which this string measurement helps define.
ClassificationCondition
{71F9989B-6173-4d71-B9F1-2184FCC3CEF5}.SupplierEnd
Observation or forecast with which this environmental string is associated.
EnvironmentalInformation
{4492BBDD-51E1-414b-8D40-F554831AB71A}.SupplierEnd
Additional equipment container beyond the primary equipment container. The equipment is contained in another equipment container but also grouped with this equipment container.
AdditionalEquipmentContainer
{43EA076F-F51B-4617-BC39-6D3939D5CEFD}.ClientEnd
The contingency equipments in which this equipment participates.
ContingencyEquipment
{90FE687B-C58C-4b05-856E-6D576F7CADBE}.ClientEnd
Equipment limit series calculation component to which this equipment contributes.
EqiupmentLimitSeriesComponent
{CEFBFF28-402F-45fe-88FA-EF5E6D724964}.ClientEnd
Container of this equipment.
EquipmentContainer
{68BA73EF-8533-48ba-964A-DE0F722292D2}.ClientEnd
EquipmentUnavailabilitySchedule
{D5BE88A6-8696-43ec-A291-81AFED41113B}.ClientEnd
All faults on this equipment.
Faults
{6B3EA616-0934-425c-A898-1D84DADF5261}.ClientEnd
Limit dependencymodels organized under this equipment as a means for organizing the model in a tree view.
LimitDependencyModel
{CEF63A20-BB9F-4d20-85B7-C4EF0AB5624F}.ClientEnd
The operational limit sets associated with this equipment.
OperationalLimitSet
{AEB22FF5-0EEF-4e3a-BE8C-07931F2FAE92}.ClientEnd
All operational restrictions for this equipment.
OperationalRestrictions
{A11D842D-BDDB-42a4-B8FB-43C199D5E3BA}.ClientEnd
All outages in which this equipment is involved.
Outages
{7CB5F824-2EAC-4c6e-B3CE-B2B245253D31}.ClientEnd
PinEquipment
{83B2D8C8-5F34-4fbe-A13F-090F6823061D}.ClientEnd
Protective action is controlling equipment. This can be direct signals from the control center or emulation of action done by protection equipment.
ProtectiveActionEquipment
{C2B4064B-C361-4230-9F19-21614F4EFABE}.ClientEnd
All usage points connected to the electrical grid through this equipment.
UsagePoints
{3E4B9C55-FCC6-42ec-B364-27C62004847F}.ClientEnd
WeatherStation
{C35B9B9D-C271-4005-801D-B7B44FF8D8C7}.SupplierEnd
The additonal contained equipment. The equipment belong to the equipment container. The equipment is contained in another equipment container but also grouped with this equipment container. Examples include when a switch contained in a substation is also desired to be grouped with a line contianer or when a switch is included in a secondary substation and also grouped in a feeder.
AdditionalGroupedEquipment
{43EA076F-F51B-4617-BC39-6D3939D5CEFD}.SupplierEnd
Contained equipment.
Equipments
{68BA73EF-8533-48ba-964A-DE0F722292D2}.SupplierEnd
The terminal connecting to the bus to which the fault is applied.
Terminal
{2CF11C93-156B-4725-864D-F54BFFEBEEB6}.SupplierEnd
Equipment contributing toward the series limit. The reference here is to Equipment rather than a specific limit on the equipment so the grouiping can be reused for multiple limits of different types on the same instance of equipment.
Equipment
{CEFBFF28-402F-45fe-88FA-EF5E6D724964}.SupplierEnd
Equipment
{D5BE88A6-8696-43ec-A291-81AFED41113B}.SupplierEnd
UnavailabilitySwitchAction
{A621ED73-8721-4170-8819-24FA003C3372}.ClientEnd
UnavailablitySchedule
{E688F5A4-D2F9-4a84-85F2-980B6307E7AB}.SupplierEnd
Negative sequence series resistance from terminal sequence 1 to terminal sequence 2. Used for short circuit data exchange according to IEC 60909.EquivalentBranch is a result of network reduction prior to the data exchange.
negativeR12
{B1A62182-45DA-4986-9AD7-77E0AA97A1B9}
Negative sequence series resistance from terminal sequence 2 to terminal sequence 1. Used for short circuit data exchange according to IEC 60909.EquivalentBranch is a result of network reduction prior to the data exchange.
negativeR21
{20639149-2242-4312-872C-16CD27A6283C}
Negative sequence series reactance from terminal sequence 1 to terminal sequence 2. Used for short circuit data exchange according to IEC 60909.Usage EquivalentBranch is a result of network reduction prior to the data exchange.
negativeX12
{CD82466D-D982-4513-8CAA-27FB73559F16}
Negative sequence series reactance from terminal sequence 2 to terminal sequence 1. Used for short circuit data exchange according to IEC 60909.Usage EquivalentBranch is a result of network reduction prior to the data exchange.
negativeX21
{EEF7F824-5B80-4eb2-AA46-C3AB841CA150}
Positive sequence series resistance from terminal sequence 1 to terminal sequence 2 . Used for short circuit data exchange according to IEC 60909. EquivalentBranch is a result of network reduction prior to the data exchange.
positiveR12
{B2DB32FB-D03F-4e20-A232-010D8CBEA16D}
Positive sequence series resistance from terminal sequence 2 to terminal sequence 1. Used for short circuit data exchange according to IEC 60909.EquivalentBranch is a result of network reduction prior to the data exchange.
positiveR21
{8BB8921A-0D66-4f17-9E3F-D86911D7AB83}
Positive sequence series reactance from terminal sequence 1 to terminal sequence 2. Used for short circuit data exchange according to IEC 60909.Usage EquivalentBranch is a result of network reduction prior to the data exchange.
positiveX12
{334AD4DB-EC20-4576-BB4A-A0F37E316CA7}
Positive sequence series reactance from terminal sequence 2 to terminal sequence 1. Used for short circuit data exchange according to IEC 60909.Usage EquivalentBranch is a result of network reduction prior to the data exchange.
positiveX21
{F95AFB29-D445-4d86-A53E-D91AEB6534D7}
Positive sequence series resistance of the reduced branch.
r
{1F492DF7-2255-4d8e-A86F-7B7DD78A06E7}
Resistance from terminal sequence 2 to terminal sequence 1 .Used for steady state power flow. This attribute is optional and represent unbalanced network such as offnominal phase shifter. If only EquivalentBranch.r is given then EquivalentBranch.r21 is assumed equal to EquivalentBranch.r.Usage rule EquivalentBranch is a result of network reduction prior to the data exchange.
r21
{0D332096-38C6-43f9-BC78-C72F55A7C7C7}
Positive sequence series reactance of the reduced branch.
x
{AEAF2B71-B7BD-41c0-9844-C69DBC580F24}
Reactance from terminal sequence 2 to terminal sequence 1. Used for steady state power flow. This attribute is optional and represents an unbalanced network such as offnominal phase shifter. If only EquivalentBranch.x is given then EquivalentBranch.x21 is assumed equal to EquivalentBranch.x.Usage rule EquivalentBranch is a result of network reduction prior to the data exchange.
x21
{2C83250C-F22A-4f91-AC53-6D8D5FEB8868}
Zero sequence series resistance from terminal sequence 1 to terminal sequence 2. Used for short circuit data exchange according to IEC 60909.EquivalentBranch is a result of network reduction prior to the data exchange.
zeroR12
{68167E61-E4CA-4823-A369-4F220EB91141}
Zero sequence series resistance from terminal sequence 2 to terminal sequence 1. Used for short circuit data exchange according to IEC 60909.Usage EquivalentBranch is a result of network reduction prior to the data exchange.
zeroR21
{D0CD7162-A205-4651-8224-59E6C312851E}
Zero sequence series reactance from terminal sequence 1 to terminal sequence 2. Used for short circuit data exchange according to IEC 60909.Usage EquivalentBranch is a result of network reduction prior to the data exchange.
zeroX12
{A782C660-AD8E-4742-AE66-1A5F14EF6D97}
Zero sequence series reactance from terminal sequence 2 to terminal sequence 1. Used for short circuit data exchange according to IEC 60909.Usage EquivalentBranch is a result of network reduction prior to the data exchange.
zeroX21
{959BBBCF-5B65-41ea-B459-8A0496C293CD}
The equivalent where the reduced model belongs.
EquivalentNetwork
{DFE42640-1DEE-47f2-9A22-0AB6F405CCCD}.SupplierEnd
The reactive capability curve used by this equivalent injection.
ReactiveCapabilityCurve
{FC08DB44-00BE-4bc5-8DE9-3538FD5307B8}.ClientEnd
Maximum active power of the injection.
maxP
{329CBFA1-4D02-4d6a-B33F-FCA214810625}
Maximum reactive power of the injection. Used for modelling of infeed for load flow exchange. Not used for short circuit modelling. If maxQ and minQ are not used ReactiveCapabilityCurve can be used.
maxQ
{D033683B-6C04-4090-94B3-212F9C58C3A6}
Minimum active power of the injection.
minP
{67E14F5B-B16F-40c9-9756-B082E67BF7BF}
Minimum reactive power of the injection. Used for modelling of infeed for load flow exchange. Not used for short circuit modelling. If maxQ and minQ are not used ReactiveCapabilityCurve can be used.
minQ
{D4D5B759-8DC7-41ec-BFEE-EF85D3E20724}
Equivalent active power injection. Load sign convention is used i.e. positive sign means flow out from a node.Starting value for steady state solutions.
p
{794BBD16-A21F-4f57-BFF6-6413DF1DC6D5}
Equivalent reactive power injection. Load sign convention is used i.e. positive sign means flow out from a node.Starting value for steady state solutions.
q
{CFD61B60-96D7-45db-83AD-D2441020B6F6}
Positive sequence resistance. Used to represent ExtendedWard IEC 60909.Usage ExtendedWard is a result of network reduction prior to the data exchange.
r
{35F3E67E-F428-439e-ABE0-284CC8BBBD7C}
Zero sequence resistance. Used to represent ExtendedWard IEC 60909.Usage ExtendedWard is a result of network reduction prior to the data exchange.
r0
{48277F25-31FB-4e9d-9F09-482886F04693}
Negative sequence resistance. Used to represent ExtendedWard IEC 60909.Usage ExtendedWard is a result of network reduction prior to the data exchange.
r2
{17951FC2-83D8-4363-9ED5-EE48ADC75FD6}
The target voltage for voltage regulation. The attribute shall be a positive value.
regulationTarget
{6BE562FD-1C81-4544-8594-DBA144DAB96E}
Positive sequence reactance. Used to represent ExtendedWard IEC 60909.Usage ExtendedWard is a result of network reduction prior to the data exchange.
x
{C2694F5C-8E2F-4a91-941B-06C03D805B37}
Zero sequence reactance. Used to represent ExtendedWard IEC 60909.Usage ExtendedWard is a result of network reduction prior to the data exchange.
x0
{D5B4C735-2A8A-414e-B4DC-34A67427B5BD}
Negative sequence reactance. Used to represent ExtendedWard IEC 60909.Usage ExtendedWard is a result of network reduction prior to the data exchange.
x2
{0FE79852-D304-4aec-9BDA-940C762DA50E}
The associated reduced equivalents.
EquivalentEquipments
{DFE42640-1DEE-47f2-9A22-0AB6F405CCCD}.ClientEnd
Positive sequence shunt susceptance.
b
{013695BA-2127-409a-A827-96AED518B7C9}
Positive sequence shunt conductance.
g
{431696B8-B418-463e-9EC1-39699EED25EC}
Design
{385BF030-903C-4fb9-9B45-AE7199B9E2C6}.ClientEnd
ErpBomItemDatas
{4F7E7578-757A-4e21-A7A7-CA0EA44803ED}.ClientEnd
DesignLocation
{4962575B-8FF3-4dfb-8A66-0E1F572C4D90}.SupplierEnd
ErpBOM
{4F7E7578-757A-4e21-A7A7-CA0EA44803ED}.SupplierEnd
TypeAsset
{3FB0DAAA-9E8C-499f-81CE-3F538433A48D}.ClientEnd
ErpPersons
{A11130EF-055F-4b39-8ED5-B1CB36A71F99}.ClientEnd
Asset
{ED3450A6-CFCF-4eb3-95A3-E3511D9B6178}.ClientEnd
status
{82391F6C-A439-421d-8C71-89BF4089B22E}
status
{71513360-2580-4e69-837A-CA97E3815CF1}
CustomerAccount
{F954FA38-DDCE-4eeb-8C01-FA8B0D72A603}.ClientEnd
ErpInvoiceLineItems
{B388BA85-144F-45a8-B558-748EB75E28A1}.ClientEnd
Total amount due on this invoice based on line items and applicable adjustments.
amount
{91EB3FCD-2691-43d5-9C52-8D724F04F256}
Kind of media by which the CustomerBillingInfo was delivered.
billMediaKind
{38133B40-01E4-4645-9F85-44B3C7034150}
Kind of invoice default is sales.
kind
{62986491-D126-49c7-9BD6-9780E991F505}
ComponentErpInvoiceLineItems
{399C8F34-12B4-4bf2-894A-35EFA1225605}.ClientEnd
ContainerErpInvoiceLineItem
{399C8F34-12B4-4bf2-894A-35EFA1225605}.SupplierEnd
Customer billing for services rendered.
CustomerBillingInfos
{E8BD9E1E-C04F-4135-8CAA-39D78433DF77}.ClientEnd
ErpInvoice
{B388BA85-144F-45a8-B558-748EB75E28A1}.SupplierEnd
ErpJournalEntries
{9EEF3CC8-D539-42f5-A90E-DC8E38D38AD0}.SupplierEnd
ErpPayableLineItem
{092D6131-BA4D-4da5-8BDA-C79D2B6EA3BB}.SupplierEnd
ErpPayments
{0A35D96E-B721-4047-BA35-B36895ECE189}.SupplierEnd
ErpQuoteLineItem
{534AB3AB-C172-46ba-AEC1-987D567FA252}.ClientEnd
ErpRecDelvLineItem
{F490DDDB-7EF8-43cf-807E-6C93CBF5BC47}.ClientEnd
ErpRecLineItem
{319D17D5-7DA7-4431-BB15-F0903631C52D}.SupplierEnd
UserAttributes
{5DECAD82-C8FA-4209-A6DC-EC593C447EE3}.SupplierEnd
WorkBillingInfos
{A0C60390-969D-4a91-B406-83ABE393F0BC}.ClientEnd
Bill period for the line item.
billPeriod
{F6229534-2806-4d96-A1FB-CD156ED733BE}
Kind of line item.
kind
{E5DEB9A7-14F1-4717-9C58-D9D5285FE4A3}
TypeAsset
{AECF6503-964C-41a1-AA24-93AF8EF31369}.SupplierEnd
TypeMaterial
{593B111A-12A5-4f96-B00C-4A37F1AB05D7}.SupplierEnd
status
{60C93890-088A-4659-BBBD-FD5C036601D9}
Asset
{84B973F4-8888-4cf6-920A-BD61CD559A80}.SupplierEnd
status
{E905A8B6-7F8A-46b3-AC26-D15056525BC0}
ErpJournalEntries
{D8FAC8C1-1DD4-4a11-8B49-625E02517947}.SupplierEnd
CostTypes
{416479A3-0381-44f8-B625-D715F8C424E6}.ClientEnd
ErpInvoiceLineItem
{9EEF3CC8-D539-42f5-A90E-DC8E38D38AD0}.ClientEnd
ErpJournal
{D8FAC8C1-1DD4-4a11-8B49-625E02517947}.ClientEnd
ErpLedgerEntry
{36F41E78-922E-43b6-AAA6-EC85D608C6F5}.ClientEnd
ErpPayableLineItems
{D1CD0DEB-E710-4dca-948C-38F25D6DAC7D}.ClientEnd
ErpRecLineItems
{1CA7637E-994E-45af-9C55-1D91D2DCD1E8}.ClientEnd
The amount of the debit or credit for this account.
amount
{9736D74D-F1E7-4c80-95DA-538BACC36BB0}
status
{1E2AE628-B7EE-4112-867D-3B1EC16CD498}
ErpLedBudLineItem
{B82012C3-C8D9-454b-9E72-EB38052CD807}.ClientEnd
ErpLedgerBudget
{EBDB9413-5531-469b-948B-04AACB235A46}.SupplierEnd
status
{A679826B-D6AB-4a81-B6DB-D0897E925E63}
ErpLedgerEntries
{9CAFF317-06A1-42c0-8BCA-0FC5E200D600}.SupplierEnd
ErpLedBudLineItems
{EBDB9413-5531-469b-948B-04AACB235A46}.ClientEnd
ErpJounalEntry
{36F41E78-922E-43b6-AAA6-EC85D608C6F5}.SupplierEnd
ErpLedger
{9CAFF317-06A1-42c0-8BCA-0FC5E200D600}.ClientEnd
ErpLedgerEntry
{B82012C3-C8D9-454b-9E72-EB38052CD807}.SupplierEnd
UserAttributes
{930F2019-2141-4f10-80A0-CECF3D224F2D}.SupplierEnd
Kind of account for this entry.
accountKind
{F51254F9-CD47-419f-A5D8-2445EE118220}
The amount of the debit or credit for this account.
amount
{62744601-C3AC-4809-8132-D2E6DD38F1B8}
status
{73DA6418-6B18-440e-AA6D-EB76413A52FA}
AssetModelCatalogueItem
{6A15A364-6A16-4777-8E7A-E9C7ECF79B32}.ClientEnd
ErpPurchaseOrder
{A3434AAB-534F-47cd-A690-16E9D317A9A8}.SupplierEnd
ErpRecDelLineItem
{2241AA6A-7CB0-468a-87C6-B912D051C941}.ClientEnd
ErpReqLineItem
{4DB55D31-B4E9-4481-AB5D-D170CEB9DC09}.ClientEnd
ContractorItems
{C73FA4A3-2380-4d97-8F28-0D805D815283}.ClientEnd
ErpPayableLineItems
{B6C080EE-E4DB-49ac-AEC6-05879D648A4B}.ClientEnd
ErpInvoiceLineItem
{092D6131-BA4D-4da5-8BDA-C79D2B6EA3BB}.ClientEnd
ErpJournalEntries
{D1CD0DEB-E710-4dca-948C-38F25D6DAC7D}.SupplierEnd
ErpPayable
{B6C080EE-E4DB-49ac-AEC6-05879D648A4B}.SupplierEnd
ErpPayments
{456AB7EF-D680-48fe-979F-CB5BF6BD33AF}.SupplierEnd
status
{C9DE4CA9-2044-4997-9638-D5CC6982CA51}
ErpInvoiceLineItems
{0A35D96E-B721-4047-BA35-B36895ECE189}.ClientEnd
ErpPayableLineItems
{456AB7EF-D680-48fe-979F-CB5BF6BD33AF}.ClientEnd
ErpRecLineItems
{7EE5F395-6702-418f-928E-85FD14AA3B35}.ClientEnd
ErpPersons
{284A2414-6888-411f-82F7-90FAF8CA2419}.ClientEnd
status
{31C4A469-A539-4c14-97B9-F76711E1D6E3}
ErpTimeEntries
{FA05B30D-6288-4ec8-A234-C0AE064BBE4A}.ClientEnd
Projects
{55D017C7-9C0F-40fb-81EF-FC182E6BDAAE}.SupplierEnd
WorkCostDetails
{4005B7A5-5B74-4c65-921E-9254AAD5A266}.ClientEnd
Works
{09AE0E89-9CDA-4e45-9D26-E7A6B10F9B3A}.ClientEnd
ErpPOLineItems
{A3434AAB-534F-47cd-A690-16E9D317A9A8}.ClientEnd
ErpQuoteLineItems
{3DD4AB8B-A4F0-42c7-A8BA-5A675F7A44FB}.ClientEnd
AssetModelCatalogueItem
{CE08E4FC-401D-4b25-B35D-68179BF78BEE}.ClientEnd
Design
{F494C91F-54E1-42e7-88D5-BEAED03ACDBB}.SupplierEnd
Some utilities provide quotes to customer for services where the customer accepts the quote by making a payment. An invoice is required for this to occur.
ErpInvoiceLineItem
{534AB3AB-C172-46ba-AEC1-987D567FA252}.SupplierEnd
ErpQuote
{3DD4AB8B-A4F0-42c7-A8BA-5A675F7A44FB}.SupplierEnd
ErpReqLineItem
{9B596E61-9131-4334-9DFD-E4640D172E40}.SupplierEnd
status
{A0C2ADE4-3221-421c-A1D7-AB1FA4C8C572}
Assets
{69D45AA1-C24F-4329-AABF-24C5B1CC8A51}.ClientEnd
ErpInvoiceLineItem
{F490DDDB-7EF8-43cf-807E-6C93CBF5BC47}.SupplierEnd
ErpPOLineItem
{2241AA6A-7CB0-468a-87C6-B912D051C941}.SupplierEnd
ErpReceiveDelivery
{082173E2-98D3-4ec3-BC53-B4812303F891}.SupplierEnd
status
{D9150A1E-05C1-4693-92ED-E6675A766190}
ErpInvoiceLineItem
{319D17D5-7DA7-4431-BB15-F0903631C52D}.ClientEnd
ErpJournalEntries
{1CA7637E-994E-45af-9C55-1D91D2DCD1E8}.SupplierEnd
ErpPayments
{7EE5F395-6702-418f-928E-85FD14AA3B35}.SupplierEnd
ErpReceivable
{D1F3B831-CBFF-422a-8F15-C485016CFA7B}.SupplierEnd
status
{E303B5E2-9EC3-4450-A37F-E39DE20A38BC}
ErpRecLineItems
{D1F3B831-CBFF-422a-8F15-C485016CFA7B}.ClientEnd
ErpRecDelvLineItems
{082173E2-98D3-4ec3-BC53-B4812303F891}.ClientEnd
ErpPOLineItem
{4DB55D31-B4E9-4481-AB5D-D170CEB9DC09}.SupplierEnd
ErpQuoteLineItem
{9B596E61-9131-4334-9DFD-E4640D172E40}.ClientEnd
ErpRequisition
{109F4694-10BD-4f5d-A24F-10ACB4A0EAE7}.SupplierEnd
TypeAsset
{7F453A7B-93B5-4f12-8984-2FC06DB80EED}.ClientEnd
TypeMaterial
{3878A953-62BF-4865-AD6B-E5B11C7EB681}.ClientEnd
Cost of material.
cost
{49E07097-720E-4ce4-8920-34C58859E416}
status
{D26CD3B5-912A-448d-BCBD-5E6F852CEAF2}
ErpReqLineItems
{109F4694-10BD-4f5d-A24F-10ACB4A0EAE7}.ClientEnd
LandProperty
{86405B23-FBDA-4f53-A547-5BE7134DF39C}.ClientEnd
status
{27F5B1B0-6FD4-41c6-A376-A8417DB1B68C}
ErpProjectAccounting
{FA05B30D-6288-4ec8-A234-C0AE064BBE4A}.SupplierEnd
ErpTimeSheet
{6C8E20D2-28EF-4a77-ACA0-D8B0EAFABC9B}.ClientEnd
status
{B378075A-5792-4b9c-9B91-B0C144CF06D0}
ErpTimeEntries
{6C8E20D2-28EF-4a77-ACA0-D8B0EAFABC9B}.SupplierEnd
Outage
{ABABDC87-C805-4e9a-86E2-7C263386DF76}.SupplierEnd
provides the confidence level that this ERT can be accomplished. This may be changedupdated as needed.
confidenceKind
{0EDCEE1C-781D-4e73-BBAF-7CC348F50C47}
ExPostLossResults
{0AE3C025-1AC4-4c40-A3B6-07906E76D2B3}.ClientEnd
ExPostLoss
{0AE3C025-1AC4-4c40-A3B6-07906E76D2B3}.SupplierEnd
SubControlArea
{82BD4DEF-763E-4739-B4DC-07A529BF1E77}.SupplierEnd
ExPostMarketRegionResults
{201C7552-E3C8-41b0-B33F-E52769ABD221}.ClientEnd
ExPostMarketRegion
{201C7552-E3C8-41b0-B33F-E52769ABD221}.SupplierEnd
MarketRegion
{801B61F8-BE1E-447c-ACAC-D47A715E668A}.SupplierEnd
ExPostResults
{9A951836-7F48-4542-A2E5-8EFAF5543E7F}.ClientEnd
ExPostPricing
{9A951836-7F48-4542-A2E5-8EFAF5543E7F}.SupplierEnd
Pnode
{E05F725E-CEBB-458d-9E58-0F2247135211}.ClientEnd
ExPostResourceResults
{E2D7DF58-9B4D-4496-B6BF-A9375B343F69}.ClientEnd
ExPostResource
{E2D7DF58-9B4D-4496-B6BF-A9375B343F69}.SupplierEnd
RegisteredResource
{A5DD0CDB-1742-4212-BFFE-9A1405F36B62}.SupplierEnd
Status of equipment
status
{F85DC6A0-AA8C-47f6-934B-EBBCAA94539E}
Voltage regulator gain iKai gt 0. Typical value 400.
ka
{E352E9FC-7564-45c2-8A93-27C93EF60D93}
Rectifier loading factor proportional to commutating reactance iKci gt 0. Typical value 02.
kc
{28720421-E00D-427e-BF08-E224BB66AA5B}
Demagnetizing factor a function of exciter alternator reactances iKdi gt 0. Typical value 038.
kd
{EDEC8C87-FD52-4865-B7E1-8946B6895B16}
Exciter constant related to selfexcited field iKei. Typical value 1.
ke
{53375318-0A8D-4402-8650-3F870A51BA29}
Excitation control system stabilizer gains iKfi gt 0. Typical value 003.
kf
{BDFC7910-E81F-41c8-BB56-38C14FFE23EB}
Coefficient to allow different usage of the model iKf1i gt 0. Typical value 0.
kf1
{0BF78AC3-C109-48eb-AA0A-860A3D4B4DC7}
Coefficient to allow different usage of the model iKf2i gt 0. Typical value 1.
kf2
{7BF6D8A5-46CD-4844-A76F-A578365F6F75}
Coefficient to allow different usage of the modelspeed coefficient iKsi gt 0. Typical value 0.
ks
{F0525376-BE7F-4cea-A127-C799F84E4011}
Voltage regulator time constant iTai gt 0. Typical value 002.
ta
{CD0AA950-9C88-4360-A0AD-83B7D3447AD2}
Voltage regulator time constant iTbi gt 0. Typical value 0.
tb
{FADEADE2-2D36-4891-8A12-DA20A15169A6}
Voltage regulator time constant iTiisubcsubi gt 0. Typical value 0.
tc
{5943ABA1-201C-4a92-94CD-B1CAAC02F914}
Exciter time constant integration rate associated with exciter control iTei gt 0. Typical value 08.
te
{789A404B-5DED-4b99-B90F-0BD43DECA5AE}
Excitation control system stabilizer time constant iTfi gt 0. Typical value 1.
tf
{E1AC404B-76EC-489e-B3CC-4B0D12E0159E}
Maximum voltage regulator output iViisubamaxsubi gt 0. Typical value 145.
vamax
{6E8F250A-6DD0-40e4-ABD4-05587BE7A46F}
Minimum voltage regulator output iViisubaminsubi lt 0. Typical value 145.
vamin
{3FCC8597-5A3B-484f-BA9E-195684AED978}
Exciter alternator output voltages back of commutating reactance at which saturation is defined iVe1i gt 0. Typical value 418.
ve1
{5990C173-89BC-42d4-AE0F-594FABBBD315}
Exciter alternator output voltages back of commutating reactance at which saturation is defined iVe2i gt 0. Typical value 314.
ve2
{F4F6A8F1-8291-4a3d-9A0C-7E110072178C}
Maximum voltage regulator outputs iVrmaxi gt 0. Typical value 603.
vrmax
{9871BDC8-9344-4a6a-AD9A-A2D0BFA157D1}
Minimum voltage regulator outputs iVrmini lt 0. Typical value 543.
vrmin
{E5D21BA0-CD87-4204-A896-54B339E7B67D}
Voltage regulator gain iKai gt 0. Typical value 400.
ka
{ACAA089F-1C67-4d5a-9CD3-E880D47094F5}
Second stage regulator gain iKbi gt 0. Exciter field current controller gain. Typical value 25.
kb
{CCDF1CF6-E857-4195-8372-17806EEDB350}
Second stage regulator gain iKb1i. It is exciter field current controller gain used as alternative to iKbi to represent a variant of the ExcAC2A model. Typical value 25.
kb1
{A25DC229-BD9A-4df3-B082-EC3CCF1C53C0}
Rectifier loading factor proportional to commutating reactance iKci gt 0. Typical value 028.
kc
{E1213B0A-871F-47bc-9A99-696C7B92AE7C}
Demagnetizing factor a function of exciter alternator reactances iKdi gt 0. Typical value 035.
kd
{8E6000C6-2817-4a72-BC0F-F59C8DF365C0}
Exciter constant related to selfexcited field iKei. Typical value 1.
ke
{8CE743CF-85C7-48c8-B251-A0391076E970}
Excitation control system stabilizer gains iKfi gt 0. Typical value 003.
kf
{DB07700F-9DDD-4419-985A-E144CDED402F}
Exciter field current feedback gain iKhi gt 0. Typical value 1.
kh
{90E213B6-4E4D-4381-BE7C-1DD75B1363D5}
Exciter field current limiter gain iKli. Typical value 10.
kl
{D91822A3-D99C-4253-93E4-C48CEEF7483D}
Coefficient to allow different usage of the model iKl1i. Typical value 1.
kl1
{70CEE85A-A641-4061-8ED4-D33335C10B80}
Coefficient to allow different usage of the modelspeed coefficient iKsi gt 0. Typical value 0.
ks
{6B0EB6D6-ED98-4bee-BAD6-2BAD76A856F2}
Voltage regulator time constant iTai gt 0. Typical value 002.
ta
{4B59FFDC-F416-4e4c-84B8-31116DE62E64}
Voltage regulator time constant iTbi gt 0. Typical value 0.
tb
{9EC97F7D-9BE0-491a-BC07-C0DC2D1137F7}
Voltage regulator time constant iTci gt 0. Typical value 0.
tc
{824C8D42-0D7A-468d-B5CC-F7877EDD5985}
Exciter time constant integration rate associated with exciter control iTei gt 0. Typical value 06.
te
{7EAD0734-3A90-4e3b-9ED8-ADFD341A0DDC}
Excitation control system stabilizer time constant iTfi gt 0. Typical value 1.
tf
{DA313FF0-4B2C-4774-B932-D9D516B29D14}
Maximum voltage regulator output iVamaxi gt 0. Typical value 8.
vamax
{CA058C3C-9EF2-49df-9615-7DA0A0601159}
Minimum voltage regulator output iVamini lt 0. Typical value 8.
vamin
{B7DD036A-20CD-4ac0-83EA-5360671AF242}
Exciter alternator output voltages back of commutating reactance at which saturation is defined iVeiisub1subi gt 0. Typical value 44.
ve1
{EB54B1DF-C0EB-411d-845D-2254C4B0D239}
Exciter alternator output voltages back of commutating reactance at which saturation is defined iVeiisub2subi gt 0. Typical value 33.
ve2
{7CD070A4-3CD7-473b-97B0-A1FE156287CD}
Exciter field current limit reference iVfemaxi gt 0. Typical value 44.
vfemax
{858136D1-E5FF-438e-97F6-E5490B2F71A6}
Maximum exciter field current iVlri gt 0. Typical value 44.
vlr
{EA7735C2-52B8-4d26-A6A0-739722E2808C}
Maximum voltage regulator outputs iVrmaxi gt 0. Typical value 105.
vrmax
{D0814F1D-6821-4a87-A4FA-E1A26089A315}
Minimum voltage regulator outputs iVrmini lt 0. Typical value 95.
vrmin
{7A23162C-7ABA-44ab-95D9-157109870AAA}
Value of iEfd iat which feedback gain changes iEfdni gt 0. Typical value 236.
efdn
{A3042DF9-602E-45a3-B059-65CEB8D39C96}
Voltage regulator gain iKai gt 0. Typical value 4562.
ka
{E13E7FD0-39A5-4290-A813-00AAF02DEE9A}
Rectifier loading factor proportional to commutating reactance iKci gt 0. Typical value 0104.
kc
{B96EE6F8-2701-4059-8A66-567BD7CBEDD3}
Demagnetizing factor a function of exciter alternator reactances iKdi gt 0. Typical value 0499.
kd
{65649D1D-7116-490e-B2B2-0C7E4430FDE7}
Exciter constant related to selfexcited field iKei. Typical value 1.
ke
{32964DCC-A519-4cf2-B7C9-D01D1B142818}
Excitation control system stabilizer gains iKfi gt 0. Typical value 0143.
kf
{607CA28C-EC63-4b6a-A246-DD5C6D271192}
Coefficient to allow different usage of the model iKf1i. Typical value 1.
kf1
{BF519598-F373-4b71-B724-97178F895E67}
Coefficient to allow different usage of the model iKf2i. Typical value 0.
kf2
{75D53490-5289-481d-BD1A-AEC922BB4EBA}
Gain used in the minimum field voltage limiter loop iKlvi. Typical value 0194.
klv
{3FA58A14-69AE-4f51-BFBF-21ADE948741F}
Excitation control system stabilizer gain iKni gt 0. Typical value 005.
kn
{ED447391-A052-4c9f-8E78-6AA296D9AA00}
Constant associated with regulator and alternator field power supply iKri gt 0. Typical value 377.
kr
{20C6FA20-10EF-4522-AED1-2E69076D2263}
Coefficient to allow different usage of the modelspeed coefficient iKsi. Typical value 0.
ks
{DBB8106E-28AD-403f-9FD5-7DB0E5960F69}
Voltage regulator time constant iTai gt 0. Typical value 0013.
ta
{5E288AC9-EC5F-4231-A134-A17167B76401}
Voltage regulator time constant iTbi gt 0. Typical value 0.
tb
{0ABCE488-9509-47af-80D2-FED3E44EEA64}
Voltage regulator time constant iTci gt 0. Typical value 0.
tc
{FC537C5C-7FF9-4924-929C-500556AC74AF}
Exciter time constant integration rate associated with exciter control iTei gt 0. Typical value 117.
te
{02C1ECB0-024B-4193-A523-A9953DC7D26F}
Excitation control system stabilizer time constant iTfi gt 0. Typical value 1.
tf
{96720F36-9A67-4193-BAF3-D1B54696DB07}
Maximum voltage regulator output iVamaxi gt 0. Typical value 1.
vamax
{2F4A90AA-39CF-43c3-88BA-BD3E984B60B6}
Minimum voltage regulator output iVamini lt 0. Typical value 095.
vamin
{0BE2AFD7-734A-4a7d-ACE5-369A1C600961}
Exciter alternator output voltages back of commutating reactance at which saturation is defined iVeiisub1subi gt 0. Typical value 6.24.
ve1
{D09A6721-BE9B-4f17-9DA9-65A9B3882A26}
Exciter alternator output voltages back of commutating reactance at which saturation is defined iVeiisub2subi gt 0. Typical value 468.
ve2
{85335AC3-6D85-42a8-8AD3-211AE48513EF}
Minimum exciter voltage output iVemini lt 0. Typical value 0.
vemin
{835D4207-DF7E-4b1e-B5A5-8E1B0B9921B1}
Exciter field current limit reference iVfemaxi gt 0. Typical value 16.
vfemax
{0631A423-7215-42bd-9A41-0B2746EF9342}
Field voltage used in the minimum field voltage limiter loop iVlvi. Typical value 079.
vlv
{C87B456E-4EBE-4b52-8AE0-C3E8880DCDEC}
Voltage regulator gain iKai gt 0. Typical value 200.
ka
{ECFBEEA9-2D13-4307-8344-9E923FC6B1BF}
Rectifier loading factor proportional to commutating reactance iKci gt 0. Typical value 0.
kc
{53634C52-E09C-41c2-B5B0-96DAE7202C36}
Voltage regulator time constant iTai gt 0. Typical value 0015.
ta
{C6D9F1B8-61B3-4f70-846D-A046DF98EAED}
Voltage regulator time constant iTbi gt 0. Typical value 10.
tb
{8BAA4F93-ED66-4648-8C7F-907948E2EA89}
Voltage regulator time constant iTci gt 0. Typical value 1.
tc
{EC2AD6AE-7DDA-4388-8BFB-2880B3D2FA96}
Maximum voltage regulator input limit iVimaxi gt 0. Typical value 10.
vimax
{579D6B75-ED06-41c0-8E7E-FEC595A45FDA}
Minimum voltage regulator input limit iVimini lt 0. Typical value 10.
vimin
{B0C8E5EB-A424-4db1-AF01-009893DCC060}
Maximum voltage regulator output iVrmaxi gt 0. Typical value 564.
vrmax
{EA6EE52B-F5DA-46f9-BAD1-BE972B273F75}
Minimum voltage regulator output iVrmini lt 0. Typical value 453.
vrmin
{0860327B-4B57-48a5-9706-74094AFD5A25}
Exciter voltage at which exciter saturation is defined iEfd1i gt 0. Typical value 56.
efd1
{F08F3F8D-8662-45f4-AD1A-BEB7FEE3179D}
Exciter voltage at which exciter saturation is defined iEfd2i gt 0. Typical value 42.
efd2
{41A01F37-F323-4c67-9A92-30CE2FB348DB}
Voltage regulator gain iKai gt 0. Typical value 400.
ka
{03228A76-BE94-4f26-B860-00C9E398C26D}
Exciter constant related to selfexcited field iKei. Typical value 1.
ke
{451BE1C1-5B7C-46bc-9B68-DB5DC0C6D308}
Excitation control system stabilizer gains iKfi gt 0. Typical value 003.
kf
{D2E4943C-0F89-4ec0-ABEA-F49597BA2BAE}
Coefficient to allow different usage of the modelspeed coefficient iKsi. Typical value 0.
ks
{1E0D65A1-456B-4110-90F8-7C3790B29AAC}
Voltage regulator time constant iTai gt 0. Typical value 002.
ta
{6B4E1E5A-E204-4cbf-B022-74BFDDD77626}
Voltage regulator time constant iTbi gt 0. Typical value 0.
tb
{BC626702-7E36-4215-B5C1-1E7286874A62}
Voltage regulator time constant iTci gt 0. Typical value 0.
tc
{D30ADC15-2E4D-4600-8D3E-937640013580}
Exciter time constant integration rate associated with exciter control iTei gt 0. Typical value 08.
te
{045D132D-6B82-41b6-9DEC-6DF3EC8956A8}
Excitation control system stabilizer time constant iTf1i gt 0. Typical value 1.
tf1
{860557C1-701D-4813-AFF8-B185E9BA931E}
Excitation control system stabilizer time constant iTf2i gt 0. Typical value 08.
tf2
{C41E6E85-D3BD-4292-BA31-B7183A786171}
Excitation control system stabilizer time constant iTf3i gt 0. Typical value 0.
tf3
{69E3D450-B233-46a6-9DBC-6A0683AEA478}
Maximum voltage regulator output iVrmaxi gt 0. Typical value 73.
vrmax
{BEE0BE8F-A922-45b7-994D-25B52FF0CC3E}
Minimum voltage regulator output iVrmini lt 0. Typical value 73.
vrmin
{28AF5082-2A16-44c7-B4F8-4FD082A59077}
Voltage regulator gain iKai gt 0. Typical value 536.
ka
{A7731403-E017-4e7c-955F-A41E1A3DD9DC}
Rectifier loading factor proportional to commutating reactance iKci gt 0. Typical value 0173.
kc
{9A9A7358-9DE1-46a2-B9E2-CE6D8469940D}
Demagnetizing factor a function of exciter alternator reactances iKdi gt 0. Typical value 191.
kd
{CAEBEC6D-8FFF-4cee-99F9-1FB3BFC0F2ED}
Exciter constant related to selfexcited field iKei. Typical value 16.
ke
{EB2EEAD0-A0AB-4ae6-9613-5D7E1B006685}
Exciter field current limiter gain iKhi gt 0. Typical value 92.
kh
{FAEBB3F9-B56D-4aa8-B90E-534BE9C83391}
Coefficient to allow different usage of the modelspeed coefficient iKsi. Typical value 0.
ks
{F831AE51-35B5-4a57-B59A-AC24ACE6DD63}
Voltage regulator time constant iTai gt 0. Typical value 0086.
ta
{153515CD-B93B-43e4-BBF8-DCD57F6D4702}
Voltage regulator time constant iTbi gt 0. Typical value 9.
tb
{642A2FDD-AC40-4349-9CC0-9358AAC57F8F}
Voltage regulator time constant iTci gt 0. Typical value 3.
tc
{38A4158E-D871-4820-B539-634A7E974B94}
Exciter time constant integration rate associated with exciter control iTei gt 0. Typical value 1.
te
{8A3583C1-6CB1-4879-B732-36F3D17C8909}
Exciter field current limiter time constant iThi gt 0. Typical value 008.
th
{1B667AFC-445F-44d4-969E-6D4C5D7075EE}
Exciter field current limiter time constant iTji gt 0. Typical value 002.
tj
{7E6F9C8D-FD8A-4a6a-8194-C8421C5918EB}
Voltage regulator time constant iTki gt 0. Typical value 018.
tk
{2779039C-0E11-4e07-A8A3-D52DDD878408}
Maximum voltage regulator output iVamaxi gt 0. Typical value 75.
vamax
{FB7C2669-B608-4714-9AA5-6BEBD07786CB}
Minimum voltage regulator output iVamini lt 0. Typical value 75.
vamin
{5F12009F-878A-461d-9557-7A7A608C3508}
Exciter alternator output voltages back of commutating reactance at which saturation is defined iVeiisub1subi gt 0. Typical value 74.
ve1
{451C3C9E-6587-4302-8BF6-C8EC6458E094}
Exciter alternator output voltages back of commutating reactance at which saturation is defined iVeiisub2subi gt 0. Typical value 555.
ve2
{816B5F46-3C4A-4c92-A43E-AD2F45E0635E}
Exciter field current limit reference iVfelimi gt 0. Typical value 19.
vfelim
{0320EBBC-4157-41d8-B89B-74BE683D46F2}
Maximum field current limiter signal reference iVhmaxi gt 0. Typical value 75.
vhmax
{67852D08-8666-4240-9B4D-80A822A8A507}
Maximum voltage regulator output iVrmaxi gt 0. Typical value 44.
vrmax
{5C6320A9-77D7-44cc-B650-35E630F60C3A}
Minimum voltage regulator output iVrmini lt 0. Typical value 36.
vrmin
{855503CC-0084-43fc-BD7A-BEF5A1700877}
Voltage regulator gain iKai gt 0. Typical value 1.
ka
{AE2ADAD7-7C8D-4f20-AB70-C392F926C227}
Rectifier loading factor proportional to commutating reactance iKci gt 0. Typical value 055.
kc
{10206005-EF47-4c2c-8B62-7C6FD521FFDA}
Demagnetizing factor a function of exciter alternator reactances iKdi gt 0. Typical value 11.
kd
{28762860-6566-4c3a-AFD8-E600DDA0515F}
Voltage regulator derivative gain iKdri gt 0. Typical value 10.
kdr
{900226F4-DE57-4f89-9954-9F2C176AC3BE}
Exciter constant related to selfexcited field iKei. Typical value 1.
ke
{A4BC5E7C-FDF3-4bc1-85C7-9AF892FDC9B1}
Voltage regulator integral gain iKiri gt 0. Typical value 5.
kir
{0FFC2183-22F8-4c58-A2C7-BF153EBB4669}
Voltage regulator proportional gain iKpri gt 0 if ExcAC8B.kir 0. Typical value 80.
kpr
{6FFFB667-93A7-4df4-8AA5-1DB65D798B41}
Coefficient to allow different usage of the modelspeed coefficient iKsi. Typical value 0.
ks
{0A3127D2-0C55-41db-A133-3C5EBF81A664}
Voltage regulator time constant iTai gt 0. Typical value 0.
ta
{E819812F-A5E6-4d95-A17F-29F972239DCE}
Lag time constant iTdri gt 0 if ExcAC8B.kdr gt 0. Typical value 01.
tdr
{5A5ECA69-94C4-4fd3-BF6B-228A68CC1420}
Exciter time constant integration rate associated with exciter control iTei gt 0. Typical value 12.
te
{4D9CF1B6-3B1F-4031-9661-20AD0F34332C}
Exciter alternator output voltages back of commutating reactance at which saturation is defined iVeiisub1subi gt 0. Typical value 65.
ve1
{23243B6C-50EC-4fe6-AD64-A11C8EFE4A71}
Exciter alternator output voltages back of commutating reactance at which saturation is defined iVeiisub2subi gt 0. Typical value 9.
ve2
{433C5A4B-817C-4e41-B123-D3B97C18B144}
Minimum exciter voltage output iVemini lt 0. Typical value 0.
vemin
{8B86C726-9B1C-4878-A257-3F129F2701FC}
Exciter field current limit reference iVfemaxi. Typical value 6.
vfemax
{97731F46-EFBE-4dc9-9143-4D0230C84986}
Input signal maximum iVimaxi gt ExcAC8B.vimin. Typical value 35.
vimax
{F6AC54D3-E713-44ed-8D74-FF89FD84E4E6}
Input signal minimum iVimini lt ExcAC8B.vimax. Typical value 10.
vimin
{5AE9EC54-9B83-4f18-BABA-3EB0C9028A62}
PID maximum controller output iVpidmaxi gt ExcAC8B.vpidmin. Typical value 35.
vpidmax
{4E7A9EE1-57C4-48d7-9ED4-625DFD57413F}
PID minimum controller output iVpidmini lt ExcAC8B.vpidmax. Typical value 10.
vpidmin
{7E28E92B-0369-4b37-9AEE-9CDBD2BC4E0D}
Maximum voltage regulator output iVrmaxi gt 0. Typical value 35.
vrmax
{EE2188FA-EAFF-41c4-AB97-D9495752DE17}
Minimum voltage regulator output iVrmini lt 0. Typical value 0.
vrmin
{69AFAABC-EE92-4e5e-9D45-48B61C9CAFFF}
Minimum exciter current iIiisubFMNsubi. Typical value 52.
ifmn
{B2E05510-728E-47ff-BF08-6A64DBC713EA}
Maximum exciter current iIiisubFMXsubi. Typical value 65.
ifmx
{B6032A3B-F568-4d25-9105-D7E159A835E5}
Time constant iTiisub1subi gt 0. Typical value 20.
t1
{7AE76CEF-0A13-45aa-A7A1-188D27D96E77}
Time constant iTiisub2subi gt 0. Typical value 005.
t2
{6CAFD655-B601-44af-89C1-0D8F1744EB00}
Time constant iTiisub3subi gt 0. Typical value 16.
t3
{27123279-7F75-41c1-BEA4-C6CDB5ED4489}
Exciter time constant iTiisubBsubi gt 0. Typical value 004.
tb
{F8F7A5A5-C4DA-4208-B39F-A21351271BC1}
Minimum AVR output iViisubRMNsubi. Typical value 52.
vrmn
{BCFF5C1E-9657-4715-851E-1978FDE307E0}
Maximum AVR output iViisubRMXsubi. Typical value 65.
vrmx
{88942468-4BC0-4630-AB38-6F422297F6EE}
Field voltage value 1 iEiisub1subi. Typical value 4.18.
e1
{F0968B7A-CDE1-462f-9959-1A54BA4D46D0}
Field voltage value 2 iEiisub2subi. Typical value 314.
e2
{8149A099-621B-46cc-9044-99CA9D4D1D6E}
AVR time constant iTiisubAsubi gt 0. Typical value 02.
ta
{B93768F2-3606-4934-BCDE-1A5B57C16192}
AVR time constant iTiisubBsubi gt 0. Typical value 0.
tb
{224188FF-8FE9-4cc5-8A86-071C5ACBCD83}
Exciter time constant iTiisubEsubi gt 0. Typical value 1.
te
{7CEAE241-2D1A-4508-AED1-F633A7C9F13D}
Rate feedback time constant iTiisubFsubi gt 0. Typical value 1.
tf
{A30411E6-FF3B-4b06-97F9-CB37B7EF4C7D}
Minimum AVR output iViisubRMNsubi. Typical value 6.
vrmn
{A289B08B-EEBD-441a-A78E-A80B872B9153}
Maximum AVR output iViisubRMXsubi. Typical value 7.
vrmx
{E8550DDA-8354-4cf2-BED4-17CE3F1EDDB0}
Field voltage value 1 iEiisub1subi. Typical value 418.
e1
{61336F78-5B7B-4a2c-A542-BCF4FC5492ED}
Field voltage value 2 iEiisub2subi. Typical value 314.
e2
{6B0F93FE-3358-41ad-9C6F-DA6AB6A58362}
AVR time constant iTiisubAsubi gt 0. Typical value 002.
ta
{A9B9C919-3A9F-4195-A822-5A45B9671E31}
AVR time constant iTiisubBsubi gt 0. Typical value 0.
tb
{216DD169-CC2F-42a8-BC06-C39F3688D43B}
Exciter time constant iTiisubEsubi gt 0. Typical value 1.
te
{E0707DDC-80EB-4163-8536-2D54F92D564E}
Rate feedback time constant iTiisubF1subi gt 0. Typical value 1.
tf1
{CD886EFF-83FC-4a14-AF12-1A3CF42EDAA9}
Rate feedback time constant iTiisubF2subi gt 0. Typical value 1.
tf2
{49DAB02A-2869-4e0c-B19F-F028A64D8761}
Minimum AVR output iViisubRMNsubi. Typical value 6.
vrmn
{1FD120B2-9B1C-457a-B006-9B8580615946}
Maximum AVR output iViisubRMXsubi. Typical value 7.
vrmx
{2DA5EE99-2CE5-49c9-BDDB-C032352B024C}
Field voltage value 1 iEiisub1subi. Typical value 418.
e1
{72BC9698-F45C-47b6-92E2-6602DFC95DD7}
Field voltage value 2 iEiisub2subi. Typical value 314.
e2
{9680892C-9DF4-4937-A2AF-931C06E69307}
AVR time constant iTiisub1subi gt 0. Typical value 20.
t1
{651B7916-2965-45c2-A45A-BF18E1031819}
AVR time constant iTiisub2subi gt 0. Typical value 16.
t2
{3FDCEBF6-27FE-46f1-8855-64ED04BDB427}
AVR time constant iTiisub3subi gt 0. Typical value 066.
t3
{7B9DA2EB-E0B6-45ab-A3D7-8C63B53FF519}
AVR time constant iTiisub4subi gt 0. Typical value 007.
t4
{7BD82A7B-8D4B-42eb-BBCF-20BCA49BA2BA}
Exciter time constant iTiisubEsubi gt 0. Typical value 1.
te
{F1DA06DD-ABC7-40b0-BB8A-BF0499ED1911}
Minimum AVR output iViisubRMNsubi. Typical value 75.
vrmn
{45A16AAB-0A9C-4541-BA35-E8842317C814}
Maximum AVR output iViisubRMXsubi. Typical value 75.
vrmx
{A584648E-30C2-4222-8C60-AC89B820024E}
AVR time constant iTiisub1subi gt 0. Typical value 48.
t1
{59DD589B-F9E5-4750-8C5D-E74221CBB10B}
Exciter current feedback time constant iTiisub1IFsubi gt 0. Typical value 60.
t1if
{31F029AD-BDA3-4743-8FEE-51C71B4547B2}
AVR time constant iTiisub2subi gt 0. Typical value 15.
t2
{2B018B3B-E937-4004-96D4-2C7060595CDE}
AVR time constant iTiisub3subi gt 0. Typical value 0.
t3
{38432108-372A-4e4e-993A-8CDD288EDF11}
AVR time constant iTiisub4subi gt 0. Typical value 0.
t4
{D9BBDDD6-1F2D-4a3c-8CAA-9DBDD4435730}
Exciter current feedback time constant iTiisubIFsubi gt 0. Typical value 0.
tif
{90E8F3CA-8502-47c1-8001-AE5CA6D4E7F9}
Minimum exciter output iViisubFMNsubi. Typical value 0.
vfmn
{E9C91C31-1B3B-4901-8CCF-16AE526BD84B}
Maximum exciter output iViisubFMXsubi. Typical value 5.
vfmx
{5671C45F-B1ED-4400-BE00-2BCDF639191F}
Minimum AVR output iViisubRMNsubi. Typical value 0.
vrmn
{8587DF68-50AD-457f-8C8F-0E077E853219}
Maximum AVR output iViisubRMXsubi. Typical value 5.
vrmx
{029D4739-1000-4c40-A7C0-09640211675C}
Gain iKai.
ka
{EBC15845-8713-47f1-AD4E-C17E60958F64}
Effective output resistance iRexi. iRexi represents the effective output resistance seen by the excitation system.
rex
{6AFA7BBE-0963-416c-8F44-D6A207AB1A6C}
Time constant iTai gt 0.
ta
{2C8B57D6-36B8-4c1b-87BD-D24E736A060A}
Lead coefficient iAiisub1subi. Typical value 05.
a1
{196174DD-4376-4150-8F4A-4368B56689D5}
Lag coefficient iAiisub2subi. Typical value 05.
a2
{FA22708D-C3EE-45a2-93D9-91141AF23031}
Lead coefficient iAiisub3subi. Typical value 05.
a3
{2FAC3642-93C6-4413-8398-C079BC90B038}
Lag coefficient iAiisub4subi. Typical value 05.
a4
{AFDAA8C5-E3DC-420d-988E-2EFC6D7D5D36}
Lead coefficient iAiisub5subi. Typical value 05.
a5
{ED5A3254-D62E-4992-BEC9-755DF6A78E12}
Lag coefficient iAiisub6subi. Typical value 05.
a6
{7DC32CE4-9972-4dc5-8DE1-5DE9BA9FE662}
Gain iKiisub1subi. Typical value 1.
k1
{4A6DD00D-64C8-494f-8D5A-5B2F62787C5D}
Gain iKiisub3subi. Typical value 3.
k3
{9CB43529-C4F6-470a-A664-E4FB91AEC080}
Gain iKiisub5subi. Typical value 1.
k5
{9ADE7B33-9FAD-4e9b-A36B-B86449ACCCD0}
Lead time constant iTiisub1subi gt 0. Typical value 005.
t1
{43083702-C3C1-4677-BA7C-CCD6A4BC9EC4}
Lag time constant iTiisub2subi gt 0. Typical value 01.
t2
{3F2C4181-F0B0-468d-ACFA-D9300FDE2E43}
Lead time constant iTiisub3subi gt 0. Typical value 01.
t3
{154137D3-A722-40e2-BFD0-C3E02AD81C79}
Lag time constant iTiisub4subi gt 0. Typical value 01.
t4
{CB67E69D-B186-444a-A354-0A61C78BDABD}
Lead time constant iTiisub5subi gt 0. Typical value 01.
t5
{194D05E2-5C64-4ad4-9D1F-7C3253157A8D}
Lag time constant iTiisub6subi gt 0. Typical value 01.
t6
{527EE729-CEC3-4bd3-9060-9F38689C8939}
Leadlag maximum limit iVmax1i gt ExcAVR7.vmin1. Typical value 5.
vmax1
{D504839B-89AE-4aa9-B9EF-2330E0E8C47E}
Leadlag maximum limit iVmax3i gt ExcAVR7.vmin3. Typical value 5.
vmax3
{6D8971E0-CAC4-42f3-BCC9-21C2D0920B9E}
Leadlag maximum limit iVmax5i gt ExcAVR7.vmin5. Typical value 5.
vmax5
{5D4CF79B-C420-43e6-8169-561C272B92EF}
Leadlag minimum limit iVmin1i lt ExcAVR7.vmax1. Typical value 5.
vmin1
{6590DD33-A1E9-470c-917F-8CE98671D135}
Leadlag minimum limit iVmin3i lt ExcAVR7.vmax3. Typical value 5.
vmin3
{32C653FE-DE5F-43e6-994E-B269E48680AB}
Leadlag minimum limit iVmin5i lt ExcAVR7.vmax5. Typical value 2.
vmin5
{88126C3E-316A-47ae-8695-D6409D993DF5}
Maximum open circuit exciter voltage iEfdmaxi gt ExcBBC.efdmin. Typical value 5.
efdmax
{9F81FD3E-073B-4fc6-B597-D204BFE9CC71}
Minimum open circuit exciter voltage iEfdmini lt ExcBBC.efdmax. Typical value 5.
efdmin
{E4A16661-A353-491e-A262-00817AF8A499}
Steady state gain iKi not 0. Typical value 300.
k
{1F130B2E-C2CA-4758-9072-000D8A972125}
Controller time constant iT1i gt 0. Typical value 6.
t1
{90A1697C-9CF0-47f0-A9F9-AA8CD92588C1}
Controller time constant iT2i gt 0. Typical value 1.
t2
{F85E3E82-9BC6-440f-A427-BFC1CF45A2B3}
Leadlag time constant iT3i gt 0. If 0 block is bypassed. Typical value 005.
t3
{F383DE01-0A73-418d-AC0D-D4EE4C0A121D}
Leadlag time constant iT4i gt 0. If 0 block is bypassed. Typical value 001.
t4
{B43932C1-CF21-4614-B36F-F9A1E216BA16}
Maximum control element output iVrmaxi gt ExcBBC.vrmin. Typical value 5.
vrmax
{50E27DDA-9C9A-4960-AF68-94DF8F274E5F}
Minimum control element output iVrmini lt ExcBBC.vrmax. Typical value 5.
vrmin
{275A0816-F302-42e8-977B-7FF9476BFD66}
Effective excitation transformer reactance iXei gt 0. iXei models the regulation of the transformerrectifier unit. Typical value 005.
xe
{A2A1F16A-DBA5-4ba5-83A7-D4D71E5F5446}
Exciter output maximum limit iEfdmaxi gt ExcCZ.efdmin.
efdmax
{EB41FA00-3E29-4a90-8A05-231D04B744E8}
Exciter output minimum limit iEfdmini lt ExcCZ.efdmax.
efdmin
{CC9F5385-763B-4173-BB1B-FAFE42AC419D}
Regulator gain iKai.
ka
{760C25A4-4A6E-45c8-9BAE-E50DF38FAA9C}
Exciter constant related to selfexcited field iKei.
ke
{9125399D-FB15-4ec6-8871-FD2DC8A83CD2}
Regulator proportional gain iKpi.
kp
{A335F6F8-CD40-4e96-AABB-ED690A6D9EE5}
Regulator time constant iTai gt 0.
ta
{A4F99E86-EA26-45d1-AB2F-244CD5C02053}
Regulator integral time constant iTci gt 0.
tc
{6741D922-B5C3-4886-9F09-4BFAE6B2355E}
Exciter time constant integration rate associated with exciter control iTei gt 0.
te
{42D29AF6-A917-4e00-B021-803E179A99C5}
Voltage regulator maximum limit iVrmaxi gt ExcCZ.vrmin.
vrmax
{BAD659A4-7D75-4f7d-BA8D-01DFE315604E}
Voltage regulator minimum limit iVrmini lt ExcCZ.vrmax.
vrmin
{5E3F9034-9E8F-485e-A498-0049FEEB8803}
Exciter voltage at which exciter saturation is defined iEfdiisub1subi gt 0. Typical value 31.
efd1
{DF840D65-1F12-4b17-B146-9F100B9CD916}
Exciter voltage at which exciter saturation is defined iEfdiisub2subi gt 0. Typical value 23.
efd2
{D83C1CDB-1157-4161-97BE-7742654C8FFD}
Maximum voltage exciter output limiter iEfdmaxi gt ExcDC1A.efdmin. Typical value 99.
efdmax
{61BD7FD2-0EE0-4af8-961A-EA51D0B346E7}
Minimum voltage exciter output limiter iEfdmini lt ExcDC1A.edfmax. Typical value 99.
efdmin
{3DBD90DD-D2A4-4518-AEFF-7548D36B198E}
Voltage regulator gain iKai gt 0. Typical value 46.
ka
{9509127B-2876-4710-9888-EDFD807A70FA}
Exciter constant related to selfexcited field iKei. Typical value 0.
ke
{21EED69E-A3FC-404e-A639-785EED726346}
Excitation control system stabilizer gain iKfi gt 0. Typical value 01.
kf
{A08DC504-8361-4e94-B831-C3E145AEB8E6}
Coefficient to allow different usage of the modelspeed coefficient iKsi. Typical value 0.
ks
{86B5E9E1-9A78-4202-AE38-019AF7A232A9}
Voltage regulator time constant iTai gt 0. Typical value 006.
ta
{9D86E198-2BEA-4bef-AEEF-F76EFF2CA4CB}
Voltage regulator time constant iTbi gt 0. Typical value 0.
tb
{46B6BF64-195E-4273-9366-A6777C7DE37B}
Voltage regulator time constant iTci gt 0. Typical value 0.
tc
{76BBF27B-C3BF-41ce-93CA-8EB2C54040CE}
Exciter time constant integration rate associated with exciter control iTei gt 0. Typical value 046.
te
{68423BE2-5E8E-42dc-BEF8-27AD298DE9E3}
Excitation control system stabilizer time constant iTfi gt 0. Typical value 1.
tf
{77AAB9FA-E624-4014-B29A-4BA3A6B5F3E3}
Maximum voltage regulator output iVrmaxi gt ExcDC1A.vrmin. Typical value 1.
vrmax
{8DB84FA2-3224-4e24-821E-BE3C8CB84A03}
Minimum voltage regulator output iVrmini lt 0 and lt ExcDC1A.vrmax. Typical value 09.
vrmin
{3D7D1F82-F8C9-4f51-88A5-0B966FFC9BF0}
Exciter voltage at which exciter saturation is defined iEfdiisub1subi gt 0. Typical value 305.
efd1
{D54B4BB7-E73F-4b62-BE60-336F6EE389DE}
Exciter voltage at which exciter saturation is defined iEfdiisub2subi gt 0. Typical value 229.
efd2
{4D68505E-8C1F-4605-BC89-62066F53390E}
Voltage regulator gain iKai gt 0. Typical value 300.
ka
{BEC8EA04-832F-496f-BF27-0466E1E49518}
Exciter constant related to selfexcited field iKei. If iKei is entered as zero the model calculates an effective value of iKei such that the initial condition value of iVri is zero. The zero value of iKei is not changed. If iKei is entered as nonzero its value is used directly without change. Typical value 1.
ke
{D9F42883-4AC5-4ed2-9AA0-CF161C164F27}
Excitation control system stabilizer gain iKfi gt 0. Typical value 01.
kf
{3DF80536-8C42-4700-B72C-BCD925C660DD}
Coefficient to allow different usage of the modelspeed coefficient iKsi. Typical value 0.
ks
{DCA9D6C9-32D2-4215-83DE-E3F7A471D29F}
Voltage regulator time constant iTai gt 0. Typical value 001.
ta
{09C25A19-6B41-4bd2-94C9-A1F1F17898E3}
Voltage regulator time constant iTbi gt 0. Typical value 0.
tb
{994D7AE3-3AA2-451d-BBCC-8B20294F55FD}
Voltage regulator time constant iTci gt 0. Typical value 0.
tc
{02CAD757-4456-45b6-BE3C-843FF2395842}
Exciter time constant integration rate associated with exciter control iTei gt 0. Typical value 133.
te
{3944CB75-6F6F-45a9-A739-CA9759F75037}
Excitation control system stabilizer time constant iTfi gt 0. Typical value 0675.
tf
{165C91F7-A642-44bd-BDDF-412C37A532BB}
Excitation control system stabilizer time constant iTf1i gt 0. Typical value 0.
tf1
{8B984ACA-F3A6-4724-A430-5697AB3EA828}
Maximum voltage regulator output iVrmaxi gt ExcDC2A.vrmin. Typical value 495.
vrmax
{B8A724CB-E640-46ee-85E2-EEA809086A32}
Minimum voltage regulator output iVrmini lt 0 and lt ExcDC2A.vrmax. Typical value 49.
vrmin
{15F76A7F-59C8-42c4-9DAB-0D96AEC3936A}
Exciter voltage at which exciter saturation is defined iEfdiisub1subi gt 0. Typical value 26.
efd1
{D5676F58-83D1-4091-B934-854BD2CA3C47}
Exciter voltage at which exciter saturation is defined iEfdiisub2subi gt 0. Typical value 345.
efd2
{6BF4B03E-D9E2-453c-BE5D-4D91960F92C1}
Maximum voltage exciter output limiter iEfdmaxi gt ExcDC3A.efdmin. Typical value 99.
efdmax
{498DB7CD-9032-4008-ADF1-F2574D076BDE}
Minimum voltage exciter output limiter iEfdmini lt ExcDC3A.efdmax. Typical value 99.
efdmin
{DD698FDA-DCEB-43ef-A000-6CCB1F0DF250}
Exciter constant related to selfexcited field iKei. Typical value 1.
ke
{78499E44-C695-45a5-B738-D9A4D8844548}
Deadband iKri. Typical value 0.
kr
{148979D4-0B77-42c4-9BAA-56075D3A2757}
Coefficient to allow different usage of the modelspeed coefficient iKsi. Typical value 0.
ks
{705605E6-1E16-4517-ADD9-80037B2E6620}
Fast raiselower contact setting iKvi gt 0. Typical value 005.
kv
{A653E9A1-AF68-45dc-9E00-458445317A53}
Exciter time constant integration rate associated with exciter control iTei gt 0. Typical value 183.
te
{0DE9A386-04CE-4b52-8BC6-4131FFA31E45}
Rheostat travel time iTrhi gt 0. Typical value 20.
trh
{85AE9738-7E7E-4766-9AF0-660A6684FD26}
Maximum voltage regulator output iVrmaxi gt 0. Typical value 5.
vrmax
{3B33D6E7-C29A-4c80-87D6-C5E98BFE6D73}
Minimum voltage regulator output iVrmini lt 0. Typical value 0.
vrmin
{352E2AD3-83BD-4a71-845F-7098FC11F276}
Voltage regulator gain iKai gt 0. Typical value 300.
ka
{309F4A01-7334-4338-ACBE-FC12385008A4}
Exciter constant related to selfexcited field iKei. Typical value 1.
ke
{62BC2CBD-2354-41f3-A8DA-0FD8FD23B70B}
Excitation control system stabilizer gain iKfi gt 0. Typical value 01.
kf
{80AB00D2-F3AD-447b-8A0A-D3FD94D6789C}
Potential circuit gain coefficient iKii gt 0. Typical value 483.
ki
{BD06810C-D2A1-4606-A0D7-367E1EAD3395}
Potential circuit gain coefficient iKpi gt 0. Typical value 437.
kp
{08D978EC-2BE0-456d-8C3F-97F82853D433}
Voltage regulator time constant iTai gt 0. Typical value 001.
ta
{310CB6C7-79B4-4eaf-A95E-02E5E36401C6}
Exciter time constant integration rate associated with exciter control iTei gt 0. Typical value 183.
te
{AE3B830F-EEF4-4f8e-90AA-8C809F79D2C9}
Excitation control system stabilizer time constant iTfi gt 0. Typical value 0675.
tf
{1F94B88E-18DA-4b08-BB7C-42739AFD0D1C}
Available exciter voltage limiter iVb1maxi gt 0. Typical value 1163.
vb1max
{0C95D484-6CE9-459c-97B8-EA0999B67EA1}
Available exciter voltage limiter iVbmaxi gt 0. Typical value 1163.
vbmax
{0F23089F-5703-4833-B551-F4C107B8C6F0}
Maximum voltage regulator output iVrmaxi gt ExcDC3A1.vrmin. Typical value 5.
vrmax
{3170F84A-9B4D-41e7-9FB3-32046D34168B}
Minimum voltage regulator output iVrmini lt 0 and lt ExcDC3A1.vrmax. Typical value 0.
vrmin
{1CEEED34-DDB2-4274-B861-F379107AC52D}
Controller follow up deadband iDpnfi. Typical value 0.
dpnf
{8DA7F27D-8DC1-499e-A513-DBCFF0890060}
Maximum open circuit excitation voltage iEfmaxi gt ExcELIN1.efmin. Typical value 5.
efmax
{774E92D6-C600-4466-8DD0-49AEF1B7DB6A}
Minimum open circuit excitation voltage iEfmini lt ExcELIN1.efmax. Typical value 5.
efmin
{1473307C-E535-4d62-AE34-BA06F3C297B7}
Stabilizer gain 1 iKs1i. Typical value 0.
ks1
{BABB3E98-9806-4b01-A489-2BAE2F6AD136}
Stabilizer gain 2 iKs2i. Typical value 0.
ks2
{70AAE9B2-0BE6-48f9-8FF5-22AF486BC9FC}
Stabilizer limit output ismaxi. Typical value 01.
smax
{F054A7E6-98D8-43ea-A078-6426905BEB67}
Current transducer time constant iTfii gt 0. Typical value 0.
tfi
{8D350F6E-3F82-40c5-96BD-DD9A6517052E}
Controller reset time constant iTnui gt 0. Typical value 2.
tnu
{794F6994-594A-4bcc-B6F8-4E407A605E31}
Stabilizer phase lag time constant iTs1i gt 0. Typical value 1.
ts1
{82337C41-79CF-41f8-A0D5-D02DDAF9C3DC}
Stabilizer filter time constant iTs2i gt 0. Typical value 1.
ts2
{9CA2D61A-1543-4718-93F8-D28B6117D56F}
Stabilizer parameters iTswi gt 0. Typical value 3.
tsw
{16AEF105-37E0-4336-93B1-38E7440E4E5F}
Current controller gain iVpii. Typical value 1245.
vpi
{8D95EEA3-BA68-4e3f-A24B-70DC4324CF07}
Controller follow up gain iVpnfi. Typical value 2.
vpnf
{6EA8457D-5E55-4721-AF8F-1B8FC6047406}
Voltage controller proportional gain iVpui. Typical value 345.
vpu
{9AE6BCD9-9C64-4d4a-AD0D-B049360639A8}
Excitation transformer effective reactance iXei gt 0. iXei represents the regulation of the transformerrectifier unit. Typical value 006.
xe
{0C969D61-FACF-4955-BF20-6C03123BA122}
Gain iEfdbasi. Typical value 01.
efdbas
{2F21471A-EC42-4867-B11E-875DC711E705}
Limiter iIiisubefmaxsubi gt ExcELIN2.iefmin. Typical value 1.
iefmax
{C87B64FC-4A25-4fdd-BBA7-B83C8B821481}
Minimum open circuit excitation voltage iIiisubefmax2subi. Typical value 5.
iefmax2
{038C1B2D-0FD7-4b5a-97EA-39F850C20DE4}
Limiter iIiisubefminsubi lt ExcELIN2.iefmax. Typical value 1.
iefmin
{3D43519F-E015-4e79-BC8C-878E36821501}
Voltage regulator input gain iK1i. Typical value 0.
k1
{ECBDDE37-48FD-41bf-872E-709BB56CBC09}
Voltage regulator input limit iK1eci. Typical value 2.
k1ec
{17BD4F54-11D1-430c-9D68-CA52FA2DA4AC}
Gain iK2i. Typical value 5.
k2
{0BFB6D4F-FC1F-4162-9F15-50CD38CE72DC}
Gain iK3i. Typical value 01.
k3
{8748E875-F144-4b9d-931D-38B64E2FFFB4}
Gain iK4i. Typical value 0.
k4
{7D76F6E1-2BE5-4248-8761-1D3D8C267986}
Voltage controller derivative gain iKd1i. Typical value 345.
kd1
{584155BF-C74A-46ea-BDFE-E3398CDC9818}
Gain iKe2i. Typical value 01.
ke2
{526BB79F-1051-4df0-8DC5-6A33E71AD86D}
Gain iKetbi. Typical value 006.
ketb
{647255F7-20F2-4285-A5E4-5C8634E54BF5}
Controller follow up gain iPID1maxi. Typical value 2.
pid1max
{F253771A-A2A6-4c43-A365-D29B8E2DA2ED}
Exciter saturation function value at the corresponding exciter voltage iVeiisub1subi back of commutating reactance iSeVeiisub1subiii gt 0. Typical value 0.
seve1
{F6296057-FE7D-4eee-9300-D6AA66715CE1}
Exciter saturation function value at the corresponding exciter voltage iVeiisub2subi back of commutating reactance iSeVeiisub2subiii gt 0. Typical value 1.
seve2
{FCBCE510-E759-4711-B2AA-D6C9395CFDA1}
Voltage controller derivative washout time constant iTb1i gt 0. Typical value 1245.
tb1
{F89AE461-A01B-4b91-A917-D2444D85FD6B}
Time constant iTei gt 0. Typical value 0.
te
{53643157-4D99-4d0b-9F16-A89D1E9F33B5}
Time Constant iTiisube2subi gt 0. Typical value 1.
te2
{5E827928-1848-40fc-B725-3A9E6C4A43BD}
Controller follow up deadband iTi1i. Typical value 0.
ti1
{066AB817-A741-41f7-89D9-144CAC48D20F}
Time constant iTiisubi3subi gt 0. Typical value 3.
ti3
{A165BDBA-BD55-4db1-8F0C-FDD0F9CF7C8F}
Time constant iTiisubi4subi gt 0. Typical value 0.
ti4
{D7156E6A-F2BA-441d-A15F-A78EE075DCA5}
Time constant iTiisubr4subi gt 0. Typical value 1.
tr4
{913CA1E6-2AD9-4592-BCC0-96215D96A04C}
Limiter iUpmaxi gt ExcELIN2.upmin. Typical value 3.
upmax
{E5BC43CE-77C2-4e89-86B6-259830DB9D6F}
Limiter iUpmini lt ExcELIN2.upmax. Typical value 0.
upmin
{D9F15DCB-3132-48b6-AE14-7C826FDCDAE4}
Exciter alternator output voltages back of commutating reactance at which saturation is defined iVeiisub1subi gt 0. Typical value 3.
ve1
{E7512511-C071-4cdf-805F-8675785FFC3C}
Exciter alternator output voltages back of commutating reactance at which saturation is defined iVeiisub2subi gt 0. Typical value 0.
ve2
{98DE2F91-766B-4439-8A12-CA3C607B68D7}
Excitation transformer effective reactance iXpi. Typical value 1.
xp
{3109B1D6-F6C5-41f8-B850-AE86524F08EE}
Major loop PI tag gain factor iAei. Typical value 3.
ae
{BC83E18F-8696-46ab-AD0D-214C5408CCC5}
Minor loop PI tag gain factor iAii. Typical value 22.
ai
{7331960F-40B3-4b07-BD38-822DFBB4D615}
AVR constant iAtri. Typical value 219.
atr
{5AB2421B-3BB8-4329-B61B-DB8BCDE50A84}
Field voltage control signal upper limit on AVR base iEmaxi gt ExcHU.emin. Typical value 0996.
emax
{BF3D01CF-6DF9-48a5-B394-0E929BC0AB3C}
Field voltage control signal lower limit on AVR base iEmini lt ExcHU.emax. Typical value 0866.
emin
{E82E172A-9B05-4b7b-AF24-63B5827AD210}
Major loop PI tag output signal upper limit iImaxi gt ExcHU.imin. Typical value 219.
imax
{50EB6DCF-C9CD-4914-A094-EE436B4CF66E}
Major loop PI tag output signal lower limit iImini lt ExcHU.imax. Typical value 01.
imin
{F1D01FB7-E392-4e38-8C36-5AB486BAA2CD}
Major loop PI tag integration time constant iTei gt 0. Typical value 0154.
te
{C920CCDB-C188-488f-8790-E4BCAFB35086}
Minor loop PI control tag integration time constant iTii gt 0. Typical value 001333.
ti
{2DB6BEBD-74C9-4c4a-A69A-D749D23E2F64}
Filter time constant iTri gt 0. If a voltage compensator is used in conjunction with this excitation system model iTr ishould be set to 0. Typical value 001.
tr
{F6185168-7343-4599-9604-74DCA438EC8D}
Voltage regulator gain iKiisubAsubi gt 0. Typical value 400.
ka
{422F3744-4BB7-4279-9813-238F008AA6B6}
Rectifier loading factor proportional to commutating reactance iKiisubCsubi gt 0. Typical value 02.
kc
{ADF175C9-0B78-4198-AC11-A61527C32D8C}
Demagnetizing factor a function of exciter alternator reactances iKiisubDsubi gt 0. Typical value 038.
kd
{89A199F4-1563-4311-A0C0-2225481E572B}
Exciter constant related to selfexcited field iKiisubEsubi. Typical value 1.
ke
{801AA38F-5121-4451-874B-85921A47CCBC}
Excitation control system stabilizer gains iKiisubFsubi gt 0. Typical value 003.
kf
{9F683D12-4F2E-49c1-8338-75CB67113480}
Voltage regulator time constant iTiisubAsubi gt 0. Typical value 002.
ta
{6CA20ECC-DDAA-44e5-B577-51A9EEAF8658}
Voltage regulator time constant iTiisubBsubi gt 0. Typical value 0.
tb
{E2F44D64-E0D0-4a72-9F18-D0115CA2BDE8}
Voltage regulator time constant iTiisubCsubi gt 0. Typical value 0.
tc
{10EDA76F-18B2-493e-9D48-76AFF514CFAF}
Exciter time constant integration rate associated with exciter control iTiisubEsubi gt 0. Typical value 08.
te
{DBC3C0BE-5012-414f-9B64-C20DB7056D86}
Excitation control system stabilizer time constant iTiisubFsubi gt 0. Typical value 1.
tf
{1857FDC3-641A-40e5-867F-919BEF7F32DE}
Maximum voltage regulator output iViisubAMAXsubi gt 0. Typical value 145.
vamax
{F835D8D9-3026-4b74-85A3-4D729D719D55}
Minimum voltage regulator output iViisubAMINsubi lt 0. Typical value 145.
vamin
{2991ABA6-E532-436e-BA2E-14C4CC17F9E3}
Exciter alternator output voltages back of commutating reactance at which saturation is defined iViisubE1subi gt 0. Typical value 418.
ve1
{967C0B25-6A55-4e27-B4D4-6405847CC680}
Exciter alternator output voltages back of commutating reactance at which saturation is defined iViisubE2subi gt 0. Typical value 314.
ve2
{AAB76517-7499-4e01-9B51-F6E9D57FCD56}
Maximum voltage regulator outputs iViisubRMAXsubi gt 0. Typical value 603.
vrmax
{13EF1600-1749-4605-9945-F3D79DBAA0F2}
Minimum voltage regulator outputs iViisubRMINsubi lt 0. Typical value 543.
vrmin
{A1499EF8-A8C9-4e5e-BB4C-60CF118920A0}
Voltage regulator gain iKiisubAsubi gt 0. Typical value 400.
ka
{2EDB427D-57E7-4e1e-9048-7B1B536E481F}
Second stage regulator gain iKiisubBsubi gt 0. Typical value 25.
kb
{4C73167B-A51B-4864-873E-E4C706F2B2FD}
Rectifier loading factor proportional to commutating reactance iKiisubCsubi gt 0. Typical value 028.
kc
{E68C1671-C804-402d-9E2C-E346CA7A5378}
Demagnetizing factor a function of exciter alternator reactances iKiisubDsubi gt 0. Typical value 035.
kd
{4A2F459F-D1C5-4bb9-BED3-5E6D15CD4FAC}
Exciter constant related to selfexcited field iKiisubEsubi gt 0. Typical value 1.
ke
{D154DC6A-6969-46ba-BE29-1579BDADF866}
Excitation control system stabilizer gains iKiisubFsubi gt 0. Typical value 003.
kf
{DE92DC78-8990-41bb-9D7B-6A1FA9704D0A}
Exciter field current feedback gain iKiisubHsubi gt 0. Typical value 1.
kh
{40883B6C-96C0-4f3a-89CD-26548BB301AA}
Voltage regulator time constant iTiisubAsubi gt 0. Typical value 002.
ta
{F077885D-32E4-4480-AADC-E11F8CE0286E}
Voltage regulator time constant iTiisubBsubi gt 0. Typical value 0.
tb
{BF33A5C3-7CD8-444e-B506-E0BA1070FEA1}
Voltage regulator time constant iTiisubCsubi gt 0. Typical value 0.
tc
{9F098821-F066-48dc-AF8D-8EEAD3D5090D}
Exciter time constant integration rate associated with exciter control iTiisubEsubi gt 0. Typical value 06.
te
{154F04ED-1246-45f3-B0F7-D36125F3E2E6}
Excitation control system stabilizer time constant iTiisubFsubi gt 0. Typical value 1.
tf
{DE67A466-8AED-4b4d-928A-20113D538548}
Maximum voltage regulator output iViisubAMAXsubi gt 0. Typical value 8.
vamax
{99E14896-6F9F-4518-B9A4-D204AE39A15F}
Minimum voltage regulator output iViisubAMINsubi lt 0. Typical value 8.
vamin
{237F427A-6BF9-485b-81A1-2780DF676B7D}
Exciter alternator output voltages back of commutating reactance at which saturation is defined iViisubE1subi gt 0. Typical value 44.
ve1
{9DA21252-EF9B-419c-9FC1-AA90CA08684C}
Exciter alternator output voltages back of commutating reactance at which saturation is defined iViisubE2subi gt 0. Typical value 33.
ve2
{EF09F7B9-7772-4b96-B62E-3502B3D78ABD}
Exciter field current limit reference iViisubFEMAXsubi gt 0. Typical value 44.
vfemax
{3C860302-3698-49d3-AD1F-5EDF16F5EA76}
Maximum voltage regulator outputs iViisubRMAXsubi gt 0. Typical value 105.
vrmax
{8C6974E9-342B-49e9-ABE8-0859D97E9F79}
Minimum voltage regulator outputs iViisubRMINsubi lt 0. Typical value 95.
vrmin
{53B974C7-AF78-4cee-9923-FBCB8DEC8B4E}
Value of iEfd iat which feedback gain changes iEiisubFDNsubi gt 0. Typical value 236.
efdn
{864D9154-B21E-4a25-803D-D3C0B11CA22E}
Voltage regulator gain iKiisubAsubi gt 0. Typical value 4562.
ka
{0F09588A-2B6D-42d2-8F74-3D9C9F9E2DFB}
Rectifier loading factor proportional to commutating reactance iKiisubCsubi gt 0. Typical value 0104.
kc
{C777575A-38BB-4bf3-8D57-6E1E19605F63}
Demagnetizing factor a function of exciter alternator reactances iKiisubDsubi gt 0. Typical value 0499.
kd
{69F8D527-E190-4d33-BC11-3F0F32E5800B}
Exciter constant related to selfexcited field iKiisubEsubi. Typical value 1.
ke
{904780F8-4B44-4280-81FE-D2F06366238B}
Excitation control system stabilizer gains iKiisubFsubi gt 0. Typical value 0143.
kf
{BE0A49FE-F1FB-4f4c-9DB7-9EF4F4BFDD68}
Excitation control system stabilizer gain iKiisubNsubi gt 0. Typical value 005.
kn
{E62B02A0-3D26-4d31-B014-52CF8A6AA801}
Constant associated with regulator and alternator field power supply iKiisubRsubi gt 0. Typical value 377.
kr
{294108EE-3FE8-4422-B067-0C0632E9CA2C}
Voltage regulator time constant iTiisubAsubi gt 0. Typical value 0013.
ta
{6C44479B-D961-480d-9BA3-B72474A3F504}
Voltage regulator time constant iTiisubBsubi gt 0. Typical value 0.
tb
{F92DF8C8-73FC-4805-8FD3-85887C40BD73}
Voltage regulator time constant iTiisubCsubi gt 0. Typical value 0.
tc
{360E7C25-8D5A-4ea6-BE04-A8716C84D971}
Exciter time constant integration rate associated with exciter control iTiisubEsubi gt 0. Typical value 117.
te
{868CB845-BE97-44c6-9FDD-1E82BBAF6D59}
Excitation control system stabilizer time constant iTiisubFsubi gt 0. Typical value 1.
tf
{C5699D2E-1512-435f-A9B4-CFF2FB1E331F}
Maximum voltage regulator output iViisubAMAXsubi gt 0. Typical value 1.
vamax
{1632BA35-0E9A-4981-9472-459D6A8B8820}
Minimum voltage regulator output iViisubAMINsubi lt 0. Typical value 095.
vamin
{336961B2-4063-49fd-B0C9-0A1A85FB59F0}
Exciter alternator output voltages back of commutating reactance at which saturation is defined iViisubE1subi gt 0. Typical value 624.
ve1
{AB093CA9-F86B-407c-8185-8F189C3F59C1}
Exciter alternator output voltages back of commutating reactance at which saturation is defined iViisubE2subi gt 0. Typical value 468.
ve2
{94842F29-3DE3-4757-B4CA-F80C66CBD78F}
Minimum exciter voltage output iViisubEMINsubi lt 0. Typical value 0.
vemin
{41BD01F0-65F5-4941-B475-B57816110BB9}
Exciter field current limit reference iViisubFEMAXsubi gt 0. Typical value 16.
vfemax
{26E18DDB-ECC8-4144-B75A-6FEFB5EDF5DA}
Voltage regulator gain iKiisubAsubi gt 0. Typical value 200.
ka
{9AB26A1E-52C8-4393-9C86-13451850938A}
Rectifier loading factor proportional to commutating reactance iKiisubCsubi gt 0. Typical value 0.
kc
{72677163-64C6-4fc7-BC4E-79BD50DBCBE4}
Voltage regulator time constant iTiisubAsubi gt 0. Typical value 0015.
ta
{4E53AB2E-DD96-47f5-A69A-ABB80AB323FA}
Voltage regulator time constant iTiisubBsubi gt 0. Typical value 10.
tb
{B22D2038-5472-4e5a-9B48-8A1E9AB9E001}
Voltage regulator time constant iTiisubCsubi gt 0. Typical value 1.
tc
{973A6F6F-D83F-4bc6-A26C-82FC4AB05503}
Maximum voltage regulator input limit iViisubIMAXsubi gt 0. Typical value 10.
vimax
{36DB172A-A77F-47b8-958E-F265EA56732F}
Minimum voltage regulator input limit iViisubIMINsubi lt 0. Typical value 10.
vimin
{C61F0260-BDDC-4693-B6AF-6E1D3690A9D4}
Maximum voltage regulator output iViisubRMAXsubi gt 0. Typical value 564.
vrmax
{AB4B512D-CAE1-48f3-A269-72829A73F949}
Minimum voltage regulator output iViisubRMINsubi lt 0. Typical value 453.
vrmin
{3EE0C72D-BEDA-4af9-9894-592D01C4ECF7}
Exciter voltage at which exciter saturation is defined iEiisubFD1subi gt 0. Typical value 56.
efd1
{2B4A383D-8271-4e5b-A24E-05637698A45C}
Exciter voltage at which exciter saturation is defined iEiisubFD2subi gt 0. Typical value 42.
efd2
{ADCA5CA8-3A6E-4238-B289-A06FF1C821B2}
Voltage regulator gain iKiisubAsubi gt 0. Typical value 400.
ka
{A8961E8E-AAE9-42db-93BB-EEE2CD983C50}
Exciter constant related to selfexcited field iKiisubEsubi. Typical value 1.
ke
{9F699065-33E5-4a5f-90EC-87CF4F628A78}
Excitation control system stabilizer gains iKiisubFsubi gt 0. Typical value 003.
kf
{DC2E9E76-F2A4-442e-A667-19CAB1E030F9}
Voltage regulator time constant iTiisubAsubi gt 0. Typical value 002.
ta
{A943B68C-2020-44ea-9C86-6EA70F69DC34}
Exciter time constant integration rate associated with exciter control iTiisubEsubi gt 0. Typical value 08.
te
{AA064651-8A19-4434-A193-164E7D345A93}
Excitation control system stabilizer time constant iTiisubF1subi gt 0. Typical value 1.
tf1
{76CD8473-50F8-4338-B03A-480300BAAEF5}
Excitation control system stabilizer time constant iTiisubF2subi gt 0. Typical value 1.
tf2
{C7A1A86E-E15A-4a00-B8E9-1A9313042784}
Excitation control system stabilizer time constant iTiisubF3subi gt 0. Typical value 1.
tf3
{552065B1-F131-4549-91D4-7D76958389BA}
Maximum voltage regulator output iViisubRMAXsubi gt 0. Typical value 73.
vrmax
{B1D2A1BF-6D2A-4fe7-ABEE-F26033355816}
Minimum voltage regulator output iViisubRMINsubi lt 0. Typical value 73.
vrmin
{60DCF610-2D43-415c-ADF3-E1AA1CA569F1}
Voltage regulator gain iKiisubAsubi gt 0. Typical value 536.
ka
{FE78FC51-23B9-4df8-8614-512B1299EE6D}
Rectifier loading factor proportional to commutating reactance iKiisubCsubi gt 0. Typical value 0173.
kc
{23EDD8E0-2455-47cb-B36C-7EB67F2E4635}
Demagnetizing factor a function of exciter alternator reactances iKiisubDsubi gt 0. Typical value 191.
kd
{333DF1C4-8EB3-45fd-956A-70A076B099B5}
Exciter constant related to selfexcited field iKiisubEsubi. Typical value 16.
ke
{C1D1EF1C-F937-4798-83CE-B483F50EB76E}
Exciter field current limiter gain iKiisubHsubi gt 0. Typical value 92.
kh
{C7875C48-1FBE-4d83-8A62-C5FDE342DBD7}
Voltage regulator time constant iTiisubAsubi gt 0. Typical value 0086.
ta
{8B90697C-75D8-453e-A971-67A14487F2F3}
Voltage regulator time constant iTiisubBsubi gt 0. Typical value 9.
tb
{5CCA364B-1C85-498c-90A2-58472E7CA12E}
Voltage regulator time constant iTiisubCsubi gt 0. Typical value 3.
tc
{EAD3C0C3-CEDC-4c23-AE4F-A00F5868D0E1}
Exciter time constant integration rate associated with exciter control iTiisubEsubi gt 0. Typical value 1.
te
{F555AF9A-CB0E-41e7-8430-DFCDCA58A072}
Exciter field current limiter time constant iTiisubHsubi gt 0. Typical value 008.
th
{AC33F7B8-4102-4722-A49B-4CD3CFE944C3}
Exciter field current limiter time constant iTiisubJsubi gt 0. Typical value 002.
tj
{75B5A038-7801-4e7d-B08E-EF9DCD7E916D}
Voltage regulator time constant iTiisubKsubi gt 0. Typical value 018.
tk
{6678A090-4326-4e44-950E-FEEDBCABF49B}
Maximum voltage regulator output iViisubAMAXsubi gt 0. Typical value 75.
vamax
{25C89DD8-4CDF-42a3-8419-F4AC2927A4B0}
Minimum voltage regulator output VsubAMINsub lt 0. Typical value 75.
vamin
{8F2B92CA-C682-451c-82A9-BA1DF142FB0C}
Exciter alternator output voltages back of commutating reactance at which saturation is defined iViisubE1subi gt 0. Typical value 74.
ve1
{814FF27D-8BEF-45d7-984E-769F1E947C4D}
Exciter alternator output voltages back of commutating reactance at which saturation is defined iViisubE2subi gt 0. Typical value 555.
ve2
{054376B1-9EEF-4042-BB73-0570FBC4FA41}
Exciter field current limit reference iViisubFELIMsubi gt 0. Typical value 19.
vfelim
{7D0D4187-3818-4640-A983-82B292E7DF6C}
Maximum field current limiter signal reference iViisubHMAXsubi gt 0. Typical value 75.
vhmax
{FEB707E7-3359-4e2b-9F80-D6F3F15DBF34}
Maximum voltage regulator output iViisubRMAXsubi gt 0. Typical value 44.
vrmax
{E277A280-2EB7-4dcd-9964-E26FD79A88C2}
Minimum voltage regulator output iViisubRMINsubi lt 0. Typical value 36.
vrmin
{732F3742-A6D2-4184-89E3-3FC6A3F522D2}
Rectifier loading factor proportional to commutating reactance iKiisubCsubi gt 0. Typical value 018.
kc
{5C544B08-73B4-4cac-894C-8B4D7A9387EF}
Demagnetizing factor a function of exciter alternator reactances iKiisubDsubi gt 0. Typical value 002.
kd
{73BB310A-BA6B-48b9-AD58-F34CD179C2D0}
Voltage regulator derivative gain iKiisubDRsubi gt 0. Typical value 0.
kdr
{85A8C730-0B18-4e36-9ADC-BE178F6EB83E}
Exciter constant related to selfexcited field iKiisubEsubi. Typical value 1.
ke
{F170FAA1-4646-40b5-AD48-62822291B736}
Excitation control system stabilizer gain iKiisubF1subi gt 0. Typical value 0212.
kf1
{682E62AD-F51A-4d03-8F0E-5BC8B6A5208E}
Excitation control system stabilizer gain iKiisubF2subi gt 0. Typical value 0.
kf2
{78BC81DB-2697-49ff-B38C-173D84A7B0C2}
Excitation control system stabilizer gain iKiisubF3subi gt 0. Typical value 0.
kf3
{7034D99F-AF65-4408-9C18-9E45CC4D639E}
Voltage regulator integral gain iKiisubIAsubi gt 0. Typical value 5969.
kia
{9C2C1ECC-C260-4f76-88C6-12CE3F5B054E}
Voltage regulator integral gain iKiisubIRsubi gt 0. Typical value 424.
kir
{3154DF6C-2586-4a39-B2DB-E28C520ED324}
Exciter field voltage lower limit parameter iKiisubLsubi. Typical value 10.
kl
{A63F07A4-63CD-44da-B7FD-64875FCFCE74}
Potential circuit gain coefficient iKiisubPsubi gt 0. Typical value 496.
kp
{A42C8F39-693F-4bb2-969A-04B22C025FE2}
Voltage regulator proportional gain iKiisubPAsubi gt 0 if ExcIEEEAC7B.kia 0. Typical value 6536.
kpa
{4C8A8C7D-BAE1-493d-82D9-44A8FC4A1492}
Voltage regulator proportional gain iKiisubPRsubi gt 0 if ExcIEEEAC7B.kir 0. Typical value 424.
kpr
{E79A01EC-5419-46ec-9881-C1733E6E24BE}
Lag time constant iTiisubDRsubi gt 0. Typical value 0.
tdr
{7B5029EB-1E46-4449-BD86-112D074A39AA}
Exciter time constant integration rate associated with exciter control iTiisubEsubi gt 0. Typical value 11.
te
{4B420A48-2C4F-43bc-AA94-797FE88CC673}
Excitation control system stabilizer time constant iTiisubFsubi gt 0. Typical value 1.
tf
{90BB088D-FB10-4d1d-B05F-2065D9935B70}
Maximum voltage regulator output iViisubAMAXsubi gt 0. Typical value 1.
vamax
{CC77DD4A-7097-445c-9933-42244ACC4D90}
Minimum voltage regulator output iViisubAMINsubi lt 0. Typical value 095.
vamin
{1936CDCD-FDC8-4303-BDB8-3D328307EF0F}
Exciter alternator output voltages back of commutating reactance at which saturation is defined iViisubE1subi gt 0. Typical value 63.
ve1
{ADF31389-E063-43e4-9BD3-E0D8CF274971}
Exciter alternator output voltages back of commutating reactance at which saturation is defined iViisubE2subi gt 0. Typical value 302.
ve2
{C053EDA8-2777-499d-80D3-45B86B9017B7}
Minimum exciter voltage output iViisubEMINsubi lt 0. Typical value 0.
vemin
{79FD3ACF-8E38-40a7-A649-037ED7C43F4D}
Exciter field current limit reference iViisubFEMAXsubi. Typical value 69.
vfemax
{55C20CD3-AEF6-4e48-AEC4-66767BFC3616}
Maximum voltage regulator output iViisubRMAXsubi gt 0. Typical value 579.
vrmax
{1A99906E-05B7-4737-90DC-F03DD11C6596}
Minimum voltage regulator output iViisubRMINsubi lt 0. Typical value 579.
vrmin
{8153D7D2-77A0-4bb4-96C9-8E02AFA8F568}
Voltage regulator gain iKiisubAsubi gt 0. Typical value 1.
ka
{CAA94157-6749-427e-B6AF-B57A6D332CF5}
Rectifier loading factor proportional to commutating reactance iKiisubCsubi gt 0. Typical value 055.
kc
{3749DD3D-805A-411c-B79B-77EFB1B4ACCD}
Demagnetizing factor a function of exciter alternator reactances iKiisubDsubi gt 0. Typical value 11.
kd
{A4A2918E-C37B-4145-8E30-BC6B7A15C4B3}
Voltage regulator derivative gain iKiisubDRsubi gt 0. Typical value 10.
kdr
{6A82A570-1589-4b3a-A5A2-8567B3DE0E94}
Exciter constant related to selfexcited field iKiisubEsubi. Typical value 1.
ke
{D4ADF936-A070-43ff-BEF6-2282664134B2}
Voltage regulator integral gain iKiisubIRsubi gt 0. Typical value 5.
kir
{A61FB404-CC01-4438-BA0E-9BE20F5321A2}
Voltage regulator proportional gain iKiisubPRsubi gt 0 if ExcIEEEAC8B.kir 0. Typical value 80.
kpr
{0DBFB2BE-9C8B-4bea-B1C5-5AD06E7388DF}
Voltage regulator time constant iTiisubAsubi gt 0. Typical value 0.
ta
{6D74D921-B4E8-4006-99F5-FEB3C8EDAB2C}
Lag time constant iTiisubDRsubi gt 0. Typical value 01.
tdr
{D90ACBA1-D501-4dcd-A475-50BF19B60C27}
Exciter time constant integration rate associated with exciter control iTiisubEsubi gt 0. Typical value 12.
te
{EF6D73D3-92EC-4a03-A027-490136D2846E}
Exciter alternator output voltages back of commutating reactance at which saturation is defined iViisubE1subi gt 0. Typical value 65.
ve1
{02542131-1EF9-4bf9-B481-13FA5C609353}
Exciter alternator output voltages back of commutating reactance at which saturation is defined iViisubE2subi gt 0. Typical value 9.
ve2
{47C123B5-0DD0-4fe8-8289-31BFFA7C643A}
Minimum exciter voltage output iViisubEMINsubi lt 0. Typical value 0.
vemin
{DA1381CA-D93E-448d-8698-152232181C07}
Exciter field current limit reference iViisubFEMAXsubi. Typical value 6.
vfemax
{FA742534-A49C-4dfa-BF6E-587200C494FD}
Maximum voltage regulator output iViisubRMAXsubi gt 0. Typical value 35.
vrmax
{57AD8D66-84EF-4602-8927-8C1124C6F4AF}
Minimum voltage regulator output iViisubRMINsubi lt 0. Typical value 0.
vrmin
{77018ED0-3248-4015-88E5-2A30B0A75C80}
Exciter voltage at which exciter saturation is defined iEiisubFD1subi gt 0. Typical value 31.
efd1
{5C21A9EA-0EE0-49fc-9C22-929904EC936A}
Exciter voltage at which exciter saturation is defined iEiisubFD2subi gt 0. Typical value 23.
efd2
{2FEBAD6C-6AFC-44a6-8E3D-A73589953659}
Voltage regulator gain iKiisubAsubi gt 0. Typical value 46.
ka
{C5CA11EE-15C2-43e3-B786-95FE21086610}
Exciter constant related to selfexcited field iKiisubEsubi. Typical value 0.
ke
{8624D37D-27AE-402d-BC38-C33617C1B4C4}
Excitation control system stabilizer gain iKiisubFsubi gt 0. Typical value 0.1.
kf
{B70D69E2-D568-4b3a-B746-DC1E0445548B}
Voltage regulator time constant iTiisubAsubi gt 0. Typical value 006.
ta
{AF3D37DD-DF2D-486a-8824-AD01FCEDC421}
Voltage regulator time constant iTiisubBsubi gt 0. Typical value 0.
tb
{A2723F9D-DDD9-4d2d-B677-2BEB27AB84CD}
Voltage regulator time constant iTiisubCsubi gt 0. Typical value 0.
tc
{ADEE2D2A-A2AA-4464-BBC3-AB84DC679B64}
Exciter time constant integration rate associated with exciter control iTiisubEsubi gt 0. Typical value 046.
te
{52CFCC80-DB47-4de3-A488-FF52B72B8C26}
Excitation control system stabilizer time constant iTiisubFsubi gt 0. Typical value 1.
tf
{0A4924CE-5629-414b-A863-64657774F76A}
Maximum voltage regulator output iViisubRMAXsubi gt ExcIEEEDC1A.vrmin. Typical value 1.
vrmax
{CF546840-AC64-4f68-9F57-B1F230694524}
Minimum voltage regulator output iViisubRMINsubi lt 0 and lt ExcIEEEDC1A.vrmax. Typical value 09.
vrmin
{9AD95853-3063-4a47-9339-8E1D98ED4854}
Exciter voltage at which exciter saturation is defined iEiisubFD1subi gt 0. Typical value 305.
efd1
{50EF9DEB-5DAC-420d-B896-C8BEBFB06A33}
Exciter voltage at which exciter saturation is defined iEiisubFD2subi gt 0. Typical value 229.
efd2
{BD4B9F65-626E-4182-BC47-8854AE5F86EE}
iexclimi. IEEE standard is ambiguous about lower limit on exciter output. Typical value 999 which means that there is no limit applied.
exclim
{AE32601D-3E52-4ba7-ADCA-D05656320C2B}
Voltage regulator gain iKiisubAsubi gt 0. Typical value 300.
ka
{8B0DBBB2-9EE6-490f-8C42-D63F09AD84E9}
Exciter constant related to selfexcited field iKiisubEsubi. Typical value 1.
ke
{460167B8-C685-4891-8865-77F49AC62D96}
Excitation control system stabilizer gain iKiisubFsubi gt 0. Typical value 01.
kf
{CDF296C2-84C5-41f9-85F6-23316E1DA0A4}
Voltage regulator time constant iTiisubAsubi gt 0. Typical value 001.
ta
{1A461A8D-FE30-49ce-A520-4796C0D30A72}
Voltage regulator time constant iTiisubBsubi gt 0. Typical value 0.
tb
{42E6440E-A6CE-46df-90EF-F30E3406CCAB}
Voltage regulator time constant iTiisubCsubi gt 0. Typical value 0.
tc
{AE5D5AC2-C1F7-431b-96B0-108A679BE624}
Exciter time constant integration rate associated with exciter control iTiisubEsubi gt 0. Typical value 133.
te
{B917F45C-1C6C-4b66-BB8D-A5BD6DE06511}
Excitation control system stabilizer time constant iTiisubFsubi gt 0. Typical value 0675.
tf
{398ABC46-2153-49c3-8A05-F8DC393FBD4D}
Maximum voltage regulator output iViisubRMAXsubigt ExcIEEEDC2A.vrmin. Typical value 495.
vrmax
{49E39611-DF26-4038-809C-A7D73182E5BD}
Minimum voltage regulator output iViisubRMINsubi lt 0 and lt ExcIEEEDC2A.vrmax. Typical value 49.
vrmin
{D6B734BF-53A0-48c3-BEAE-FE61528C3047}
Exciter voltage at which exciter saturation is defined iEiisubFD1subi gt 0. Typical value 3375.
efd1
{A477E4ED-AFDB-404d-A7B7-1B3246698C9A}
Exciter voltage at which exciter saturation is defined iEiisubFD2subi gt 0. Typical value 315.
efd2
{DEE62C44-4D77-4723-B494-C38F2859115B}
Exciter constant related to selfexcited field iKiisubEsubi. Typical value 005.
ke
{F33B7DB6-45EC-498c-93E3-055904655711}
Fast raiselower contact setting iKiisubVsubi gt 0. Typical value 005.
kv
{36D76F22-8191-4d6e-8482-739E31FC97FB}
Exciter time constant integration rate associated with exciter control iTiisubEsubi gt 0. Typical value 05.
te
{E4F92E42-7A71-426f-AB1B-742E1E204EC7}
Rheostat travel time iTiisubRHsubi gt 0. Typical value 20.
trh
{2157905F-0029-4ab8-9E2B-1DF1FC803588}
Maximum voltage regulator output iViisubRMAXsubi gt 0. Typical value 1.
vrmax
{9156F438-7F70-485e-8946-562C988C5E48}
Minimum voltage regulator output iViisubRMINsubi lt 0. Typical value 0.
vrmin
{6E620177-604E-4cc3-A3E1-4BC724583146}
Exciter voltage at which exciter saturation is defined iEiisubFD1subi gt 0. Typical value 175.
efd1
{5DBC11EF-4BDC-4908-80E2-9DB2EA524F5B}
Exciter voltage at which exciter saturation is defined iEiisubFD2subi gt 0. Typical value 233.
efd2
{255AFE50-BEA0-4c6f-AA93-E5F174CEB6F2}
Voltage regulator gain iKiisubAsubi gt 0. Typical value 1.
ka
{C0D0F453-7CD0-440d-B1BF-CFEAE1E09F0B}
Regulator derivative gain iKiisubDsubi gt 0. Typical value 20.
kd
{5BBC5653-C9A0-4ffb-836E-DCE63C56096E}
Exciter constant related to selfexcited field iKiisubEsubi. Typical value 1.
ke
{C5A9E8D6-0397-4986-9A42-0901C42B34B3}
Excitation control system stabilizer gain iKiisubFsubi gt 0. Typical value 0.
kf
{E2C3F1D4-ED5E-459c-A884-51C354FD925B}
Regulator integral gain iKiisubIsubi gt 0. Typical value 20.
ki
{017F2994-D707-4e44-BC0F-3D967EBD47B9}
Regulator proportional gain iKiisubPsubi gt 0. Typical value 20.
kp
{47916C6F-0313-4568-AF12-1E8C20DA022B}
Voltage regulator time constant iTiisubAsubi gt 0. Typical value 02.
ta
{785CE06A-EAC9-4192-9BFA-C0C65986E070}
Regulator derivative filter time constant iTiisubDsubi gt 0 if ExcIEEEDC4B.kd gt 0. Typical value 001.
td
{C6E2EB88-5D76-4e65-A674-254292E91122}
Exciter time constant integration rate associated with exciter control iTiisubEsubi gt 0. Typical value 08.
te
{A3A70E4F-FCCC-404a-B4F7-CE62E226AFBA}
Excitation control system stabilizer time constant iTiisubFsubi gt 0. Typical value 1.
tf
{7BEFB382-83B9-4b72-8AEB-2447E9F5E309}
Minimum exciter voltage output iViisubEMINsubi lt 0. Typical value 0.
vemin
{30D3D922-B230-41c9-BB55-090BE2E6C946}
Maximum voltage regulator output iViisubRMAXsubi gt ExcIEEEDC4B.vrmin. Typical value 27.
vrmax
{B880B106-22CE-450f-B15D-714FA99A7CA3}
Minimum voltage regulator output iViisubRMINsubi lt 0 and lt ExcIEEEDC4B.vrmax. Typical value 09.
vrmin
{5B5EE845-5C6E-438b-A6EE-05AF93F777C5}
Exciter output current limit reference iIiisubLRsubiii. Typical value 0.
ilr
{8C61C4E8-65B7-4dfc-A824-01DE7F42C371}
Voltage regulator gain iKiisubAsubi gt 0. Typical value 190.
ka
{C3392C55-2E2B-46c7-A5A7-5216DEFD6882}
Rectifier loading factor proportional to commutating reactance iKiisubCsubi gt 0. Typical value 008.
kc
{6A214F26-0A35-4e0b-B848-C7EE521DE0DD}
Excitation control system stabilizer gains iKiisubFsubi gt 0. Typical value 0.
kf
{79BE416F-6BF1-4a12-9DAC-B64E820E6D73}
Exciter output current limiter gain iKiisubLRsubi. Typical value 0.
klr
{79702DB8-84F0-447b-AB4E-72DE9A3DCFCE}
Voltage regulator time constant iTiisubAsubi gt 0. Typical value 0.
ta
{9E1D4656-32FB-4950-8A23-98D22367A2A3}
Voltage regulator time constant iTiisubBsubi gt 0. Typical value 10.
tb
{8ACCD110-4BDF-44dc-BEB8-3E3FF740CAF2}
Voltage regulator time constant iTiisubB1subi gt 0. Typical value 0.
tb1
{6E628FDE-3E25-4d8a-ADB9-FEA799D5AEE8}
Voltage regulator time constant iTiisubCsubi gt 0. Typical value 1.
tc
{4FFB39D6-E51A-41cc-A5CB-F534187934F8}
Voltage regulator time constant iTiisubC1subi gt 0. Typical value 0.
tc1
{93C55100-BD33-4560-9072-BBC9C6FB94FB}
Excitation control system stabilizer time constant iTiisubFsubi gt 0. Typical value 1.
tf
{D5D96655-D2D2-4384-A011-96E4EF572612}
Selector of the connection of the UEL input iUELini. Typical value ignoreUELsignal.
uelin
{F343504B-E6F3-427f-A565-30F740733A98}
Maximum voltage regulator output iViisubAMAXsubi gt 0. Typical value 145.
vamax
{F7E74221-6201-4f6c-9EC1-FBD2971F9B03}
Minimum voltage regulator output iViisubAMINsubi lt 0. Typical value 145.
vamin
{1662A19F-3E32-4bcd-B130-C6241BEF9DA0}
Maximum voltage regulator input limit iViisubIMAXsubi gt 0. Typical value 999.
vimax
{7776AE1D-072D-4644-8CB9-E391B7A69C42}
Minimum voltage regulator input limit iViisubIMINsubi lt 0. Typical value 999.
vimin
{68B11135-8D65-4741-8E64-F8AC034E3781}
Maximum voltage regulator outputs iViisubRMAXsubi gt 0. Typical value 78.
vrmax
{C0EF2A02-0DE1-43d6-AF16-59F60666CFE3}
Minimum voltage regulator outputs iViisubRMINsubi lt 0. Typical value 67.
vrmin
{C4C188F6-DC6F-4719-8F19-30CA3FC6DDC2}
Maximum field voltage iEiisubFDMaxsubi gt 0. Typical value 99.
efdmax
{92ED82AD-8685-4b6f-A1CC-8A2C7C3471CA}
Voltage regulator gain iKiisubAsubi gt 0. Typical value 120.
ka
{ABFC48CB-23E8-4029-8AD1-515533A1D1E8}
Rectifier loading factor proportional to commutating reactance iKiisubCsubi gt 0. Typical value 182.
kc
{7DBA1AD4-9659-4feb-A527-2BEC12676699}
Exciter constant related to selfexcited field iKiisubEsubi. Typical value 1.
ke
{F1E795D2-5F05-4ca4-9A1F-953D5697A3B1}
Excitation control system stabilizer gains iKiisubFsubi gt 0. Typical value 005.
kf
{44290411-EAD7-41d2-87F3-2BB40B82AAD0}
Potential circuit gain coefficient iKiisubIsubi gt 0. Typical value 8.
ki
{7AD803D3-A15F-480d-A313-E836B79F6054}
Potential circuit gain coefficient iKiisubPsubi gt 0. Typical value 488.
kp
{88C78104-4F94-4ace-A434-5E802E783FCD}
Voltage regulator time constant iTiisubAsubi gt 0. Typical value 015.
ta
{26B29524-EA7B-498e-89D3-1DE17E911015}
Exciter time constant integration rate associated with exciter control iTiisubEsubi gt 0. Typical value 05.
te
{B7CDFA17-4298-4fa8-9576-86AE3418C639}
Excitation control system stabilizer time constant iTiisubFsubi gt 0. Typical value 1.
tf
{80FC0FA1-DE57-45f4-A9F5-7DC411CE8D97}
Maximum voltage regulator outputs iViisubRMAXsubi gt 0. Typical value 1.
vrmax
{48B7A69B-E09C-4226-B011-8BA4BACD7B7E}
Minimum voltage regulator outputs iViisubRMINsubi lt 0. Typical value 0.
vrmin
{F970BD16-8974-47d8-B89C-74F29C233410}
Voltage regulator gain iKiisubAsubi gt 0. This is parameter iKi in the IEEE standard. Typical value 200.
ka
{A3C087B1-791E-4d06-B035-FFFD372C4D25}
Rectifier loading factor proportional to commutating reactance iKiisubCsubi gt 0. Typical value 02.
kc
{320366EC-3C73-4ac2-85A4-455C018D0453}
Feedback gain constant of the inner loop field regulator iKiisubGsubi gt 0. Typical value 1.
kg
{28145DB2-8F90-4bee-8902-988E21F0103F}
Potential circuit gain coefficient iKiisubIsubi gt 0. Typical value 0.
ki
{B5053791-953F-4710-8D97-38ED9D8765AA}
Forward gain constant of the inner loop field regulator iKiisubMsubi gt 0. Typical value 793.
km
{55344280-D8F0-44a8-912E-8D78BBDBAC7B}
Potential circuit gain coefficient iKiisubPsubi gt 0. Typical value 615.
kp
{8C83DCAE-8746-482b-B978-061BD95E4F2E}
Voltage regulator time constant iTiisubAsubi gt 0. Typical value 0.
ta
{82922C99-28EF-4cb8-9A27-1483A2642ADA}
Voltage regulator time constant iTiisubBsubi gt 0. Typical value 10.
tb
{B5C43A75-77B8-4ef9-A794-1609C29378CC}
Voltage regulator time constant iTiisubCsubi gt 0. Typical value 1.
tc
{9F574F64-792F-412b-ACD9-1A5C2212B8C8}
Potential circuit phase angle ithetapi. Typical value 0.
thetap
{DD50E55D-558D-4ff8-8DC4-943484691AE6}
Forward time constant of inner loop field regulator iTiisubMsubi gt 0. Typical value 04.
tm
{E0507F84-1A36-45b5-ABD2-BBFF182F9478}
Maximum excitation voltage iViisubBMaxsubi gt 0. Typical value 69.
vbmax
{C383680D-D827-4db4-8EDC-0A7E355748A6}
Maximum inner loop feedback voltage iViisubGMaxsubi gt 0. Typical value 58.
vgmax
{45E564F9-292B-423d-A7FF-5CC9A276B442}
Maximum voltage regulator input limit iViisubIMAXsubi gt 0. Typical value 02.
vimax
{C23B5DA8-299C-4ef6-956A-2C0BD0FF1445}
Minimum voltage regulator input limit iViisubIMINsubi lt 0. Typical value 02.
vimin
{FEC4346A-EB5C-4efc-9249-9B33B8E7947C}
Maximum inner loop output iViisubMMaxsubi gt 0. Typical value 1.
vmmax
{6799E6BA-C4A9-44bf-AFFE-8417D6147187}
Minimum inner loop output iViisubMMinsubi lt 0. Typical value 0.
vmmin
{CF18AAEE-1A4A-4951-89BC-DC6F3367331E}
Maximum voltage regulator output iViisubRMAXsubi gt 0. Typical value 10.
vrmax
{29B99855-2D0C-42ce-8074-34940F19C1B5}
Minimum voltage regulator output iViisubRMINsubi lt 0. Typical value 10.
vrmin
{FD78D994-92A4-469f-851F-03C6EBA26A34}
Reactance associated with potential source iXiisubLsubi gt 0. Typical value 0081.
xl
{E331EB82-1416-40a6-931A-A0A18E21F60C}
Rectifier loading factor proportional to commutating reactance iKiisubCsubi gt 0. Typical value 0113.
kc
{CC02EDA1-161E-4915-AFD7-13CFD389C679}
Feedback gain constant of the inner loop field regulator iKiisubGsubi gt 0. Typical value 0.
kg
{174459A8-2467-4d69-8883-AEC34E57F92E}
Potential circuit gain coefficient iKiisubIsubi gt 0. Typical value 0.
ki
{6F4228CF-9DE4-41a5-B8F1-EE416D5E9831}
Voltage regulator integral gain output iKiisubIMsubi. Typical value 0.
kim
{575C835A-8951-432e-8961-C9EE226548F9}
Voltage regulator integral gain iKiisubIRsubi. Typical value 1075.
kir
{05D5287A-45EE-43a3-9AEB-2BE05891A6B1}
Potential circuit gain coefficient iKiisubPsubi gt 0. Typical value 93.
kp
{06CE480A-82FC-4335-B729-C82049B536EC}
Voltage regulator proportional gain output iKiisubPMsubi. Typical value 1.
kpm
{EF32C59F-C1C0-414f-B8A7-1C3F668BC770}
Voltage regulator proportional gain iKiisubPRsubi. Typical value 1075.
kpr
{207D6C86-7591-4ec8-BD8D-8945B8F6A969}
Voltage regulator time constant iTiisubAsubi gt 0. Typical value 002.
ta
{181FE944-E90A-481d-9E6B-07DBCE3BAA12}
Potential circuit phase angle ithetapi. Typical value 0.
thetap
{2E44DFF3-234F-4674-9605-1950FEFBD8B0}
Maximum excitation voltage iViisubBMaxsubi gt 0. Typical value 1163.
vbmax
{FD530BF0-5D2C-4b6b-B433-05157E17E634}
Maximum inner loop output iViisubMMaxsubi gt ExcIEEEST4B.vmmin. Typical value 99.
vmmax
{F537585B-51A8-4bb1-AB3A-3E86C3EE0E56}
Minimum inner loop output iViisubMMinsubi lt ExcIEEEST4B.vmmax. Typical value 99.
vmmin
{47D7013B-638E-479c-B0A8-5D4DE1A8931E}
Maximum voltage regulator output iViisubRMAXsubi gt 0. Typical value 1.
vrmax
{D7A47E4E-5196-422e-8C89-0303D0C3F075}
Minimum voltage regulator output iViisubRMINsubi lt 0. Typical value 087.
vrmin
{F2C0F2D2-96FF-493d-AC5C-17B203C5FE4A}
Reactance associated with potential source iXiisubLsubi gt 0. Typical value 0124.
xl
{B97E568B-A3AE-4d5e-BC45-80FC583F4FBF}
Rectifier regulation factor iKiisubCsubi gt 0. Typical value 0004.
kc
{509279AB-F531-483d-B285-2580410FC297}
Regulator gain iKiisubRsubi gt 0. Typical value 200.
kr
{AFB5267A-5A05-4151-B5A6-B4EB1B90D72D}
Firing circuit time constant iT1i gt 0. Typical value 0004.
t1
{A64D6107-BE0F-4ecc-B143-4FD95D614B6A}
Regulator lag time constant iTiisubB1subi gt 0. Typical value 6.
tb1
{7A70B43C-E1BB-43d3-B604-8A2DF5A2291E}
Regulator lag time constant iTiisubB2subi gt 0. Typical value 001.
tb2
{8C2E0609-F8F1-4008-A312-68C7B77E791D}
Regulator lead time constant iTiisubC1subi gt 0. Typical value 08.
tc1
{C40EF6B0-E52C-4c38-8340-EA19FCA30B98}
Regulator lead time constant iTiisubC2subi gt 0. Typical value 008.
tc2
{CB2BECE7-0213-4f75-84F3-F2E7B5EE4CAE}
OEL lag time constant iTiisubOB1subi gt 0. Typical value 2.
tob1
{270A1478-6631-464f-8035-9FCC45F0C0F1}
OEL lag time constant iTiisubOB2subi gt 0. Typical value 008.
tob2
{AF0A05D8-3FC4-4368-B511-9FC33C358486}
OEL lead time constant iTiisubOC1subi gt 0. Typical value 01.
toc1
{E6FE7F29-6533-4d44-8358-083D8044311A}
OEL lead time constant iTiisubOC2subi gt 0. Typical value 008.
toc2
{F37C04C6-9EBE-4704-B1C3-78A832B9CA3A}
UEL lag time constant iTiisubUB1subi gt 0. Typical value 10.
tub1
{62EC4650-349E-45a2-B6A2-A30853DF5D2B}
UEL lag time constant iTiisubUB2subi gt 0. Typical value 005.
tub2
{1BFC4B8E-A1D8-40dc-8C91-AAC19E758D3E}
UEL lead time constant iTiisubUC1subi gt 0. Typical value 2.
tuc1
{67A12FB3-AFB7-4410-926F-FA9ABA8818E2}
UEL lead time constant iTiisubUC2subi gt 0. Typical value 01.
tuc2
{7C14C219-3BB5-473c-8EB6-D9F785FEA035}
Maximum voltage regulator output iViisubRMAXsubi gt 0. Typical value 5.
vrmax
{BCCEC06F-77FB-404f-ADAC-C7CD0044F084}
Minimum voltage regulator output iViisubRMINsubi lt 0. Typical value 4.
vrmin
{FE8E96AC-F9F7-4439-A2F7-EB1E9ACCE574}
Exciter output current limit reference iIiisubLRsubi gt 0. Typical value 4164.
ilr
{6DD69C6A-D8BC-4408-B8FF-0A69C7C5515D}
Exciter output current limit adjustment iKiisubCIsubi gt 0. Typical value 10577.
kci
{82513056-D3D9-40f9-AE07-BA004F6275B8}
Precontrol gain constant of the inner loop field regulator iKiisubFFsubi. Typical value 1.
kff
{2C19E93F-AE86-490f-9E16-09D964499864}
Feedback gain constant of the inner loop field regulator iKiisubGsubi gt 0. Typical value 1.
kg
{69084BCC-F707-42bf-9056-C152A46F75A5}
Voltage regulator integral gain iKiisubIAsubi gt 0. Typical value 45094.
kia
{B1759B97-C455-4ea6-8074-53A2D7045A1C}
Exciter output current limiter gain iKiisubLRsubi gt 0. Typical value 1733.
klr
{AF352265-457A-413e-B8B7-2127DB0D3943}
Forward gain constant of the inner loop field regulator iKiisubMsubi. Typical value 1.
km
{5068F9C7-5A5F-4d46-94CB-FA4D282B1030}
Voltage regulator proportional gain uKuusubPAsubu gt 0. Typical value 18038.
kpa
{BB5DEF62-10B9-4372-AA2B-E147FF68EDF9}
OEL input selector iOELini. Typical value noOELinput.
oelin
{14735B3B-98B1-4b26-BA49-F6CDF3AAB896}
Feedback time constant of inner loop field voltage regulator iTiisubGsubi gt 0. Typical value 002.
tg
{2DD24D01-74E4-408b-B0FE-05DE3F1700F0}
Maximum voltage regulator output VisubAMAXsubi gt 0. Typical value 481.
vamax
{641AF6B9-0C4E-4c43-89FF-74110288F4A6}
Minimum voltage regulator output iViisubAMINsubi lt 0. Typical value 385.
vamin
{41484B28-927C-4003-A2AF-D7C2CA792F01}
Maximum voltage regulator output iViisubRMAXsubi gt 0. Typical value 481.
vrmax
{35F4955E-5EAE-4da8-B6CA-8781F6256766}
Minimum voltage regulator output iViisubRMINsubi lt 0. Typical value 385.
vrmin
{ABF693C2-6818-4101-B15B-EC0E95E0DC6E}
Highvalue gate feedback gain iKiisubHsubi gt 0. Typical value 1.
kh
{43BBB77E-26A1-4e2d-AEAE-B2F01F28ED3A}
Voltage regulator integral gain iKiisubIAsubi gt 0. Typical value 1.
kia
{ACF9C97C-5D50-4b81-8B26-CF1DD7AA99B6}
Lowvalue gate feedback gain iKiisubLsubi gt 0. Typical value 1.
kl
{F00C0507-801C-4346-BC88-E47C43486F13}
Voltage regulator proportional gain iKiisubPAsubi gt 0. Typical value 40.
kpa
{6BE8FA89-08B1-4fc5-8D60-D33ED957D03C}
OEL input selector iOELini. Typical value noOELinput.
oelin
{90AE62BA-B286-4c1d-BD88-B61080B16E79}
Regulator lag time constant iTiisubBsubi gt 0. Typical value 1.
tb
{6CE3CCDC-54EC-4524-A0B8-AA531D2B17ED}
Regulator lead time constant iTiisubCsubi gt 0. Typical value 1.
tc
{9605D374-AD1C-4e16-86B0-931F43978343}
Excitation control system stabilizer time constant iTiisubFsubi gt 0. Typical value 1.
tf
{A4BCD34E-FEAD-4b60-978C-F63BB4B10A72}
Feedback time constant of inner loop field voltage regulator iTiisubGsubi gt 0. Typical value 1.
tg
{55F1E500-AC63-4eeb-A40B-38836513342F}
Feedback time constant iTiisubIAsubi gt 0. Typical value 3.
tia
{609916C6-3026-44c1-ADBC-0E9D6DDDE3AC}
UEL input selector iUELini. Typical value noUELinput.
uelin
{C3050131-90A7-4129-A13A-D7FBC7AA02A7}
Maximum voltage reference signal iViisubMAXsubi gt 0 and gt ExcIEEEST7B.vmin. Typical value 11.
vmax
{5FDFEECE-FE0F-483f-9383-72FA6A71199F}
Minimum voltage reference signal iViisubMINsubi gt 0 and lt ExcIEEEST7B.vmax. Typical value 09.
vmin
{9C0D10A0-3BBC-4214-9C3E-4887B91D0B7C}
Maximum voltage regulator output iViisubRMAXsubi gt 0. Typical value 5.
vrmax
{C995909E-5AB0-4bec-9C39-F326A5BCDB72}
Minimum voltage regulator output iViisubRMINsubi lt 0. Typical value 45.
vrmin
{6E245220-20CD-4fec-ADF3-93653A6BFCCD}
Voltage regulator gain iKai gt 0. Typical value 210.
ka
{8F0BB6FD-7F47-4352-A2E3-F9D7D94004B5}
Excitation control system stabilizer gain iKfi gt 0. Typical value 001.
kf
{1D74BC2F-93B0-45c9-BEFE-BC2FB6BDBD48}
irci irfdi iRi gt 0. 0 means exciter has negative current capabilitygt 0 means exciter does not have negative current capability. Typical value 5.
r
{F337910E-26D5-4a91-8B95-BF3FB984C9CD}
Voltage regulator time constant iTai gt 0. Typical value 002.
ta
{2E0C4647-5E1A-4c08-AA8B-32E7E2579014}
Excitation control system stabilizer time constant iTf1i gt 0. Typical value 10.
tf1
{298EB9FE-88B8-44d7-B574-1972B587A48B}
Excitation control system stabilizer time constant iTf2i gt 0. Typical value 01.
tf2
{1CA15C51-4950-475d-B24B-CB2AC313CEDF}
Time constant iTri gt 0. Typical value 002.
tr
{4BC6768A-77FC-4409-AB50-00E475D61073}
Maximum voltage regulator ouput iVrmaxi gt ExcNI.vrmin. Typical value 50.
vrmax
{4DEDBBDE-77D5-47c8-9E4A-2864E98248E7}
Minimum voltage regulator ouput iVrmini lt ExcNI.vrmax. Typical value 20.
vrmin
{1508A7D6-CFE0-491f-85DB-4C882088968A}
Saturation parameter iEiisub1subi.
e1
{E942AFAA-EE17-4eb7-A454-2F62F7B5A64D}
Saturation parameter iEiisub2subi.
e2
{2F5E5EBF-4370-4b2d-9DCE-8700FF72D24F}
Gain iKiisubAsubi.
ka
{B9515878-C715-40f4-8904-9EDC3B2389ED}
Gain iKiisubCsubi.
kc
{19B9D3FC-3C8B-42f6-8D56-75943C6851CB}
Gain iKiisubDsubi.
kd
{4733AE75-F9E7-491e-BB20-11B783CBBDAC}
Gain iKiisubEsubi.
ke
{637244DC-2AF8-43fc-804A-7FD020011C58}
Gain iKiisubFsubi.
kf
{3639B35D-63E8-4e68-B0BD-74C8CCA72BA3}
Saturation parameter iSiisubEsubiiEiisub1subiii.
see1
{4021D622-E204-4acb-B0EB-4D7F1B64C62C}
Saturation parameter iSiisubEsubiiEiisub2subiii.
see2
{793E79BE-3ABE-4fff-B270-B401C9F0F5BE}
Time constant iTiisub1subi gt 0.
t1
{6D595B12-BC8E-4395-A927-ACBE45D03353}
Time constant iTiisub2subi gt 0.
t2
{72861C34-AE7A-48f6-AF56-A92AE34FA2D6}
Time constant iTiisub3subi gt 0.
t3
{F36BFBBF-AFE7-44b8-B224-D3FB5AB1B72A}
Time constant iTiisub4subi gt 0.
t4
{7087D1E9-1C15-426b-A575-4C5175032E7D}
Time constant iTiisub5subi gt 0.
t5
{55A9101D-331B-4f60-AF95-8F368C15D9F2}
Time constant iTiisub6subi gt 0.
t6
{D904B8D3-5CEC-436a-AF9B-3E411DBA3DE8}
Time constant iTiisubEsubi gt 0.
te
{CE14CA81-717C-4f49-B370-B5AFFC4BE8A2}
Time constant iTiisubFsubi gt 0.
tf
{AB6022D7-C2E2-409e-BAC3-B713D1AE1D1E}
Limiter iViisubRMAXsubi gt ExcOEX3T.vrmin.
vrmax
{7BD6BE27-E10A-46e3-9011-447DEBF3D4BE}
Limiter iViisubRMINsubi lt ExcOEX3T.vrmax.
vrmin
{F50045B9-586F-4c1b-9608-4081B886208F}
Field voltage value 1 iEiisub1subi. Typical value 0.
e1
{EEBE48FA-7B93-48c7-8735-F9025B42D5F5}
Field voltage value 2 iEiisub2subi. Typical value 0.
e2
{75A8D86C-649D-4786-BC27-0C32CF71AB14}
Exciter maximum limit iEiisubfdmaxsubi gt ExcPIC.efdmin. Typical value 8.
efdmax
{391DD3B5-FBF9-4e8a-8280-396D524557E9}
Exciter minimum limit iEiisubfdminsubi lt ExcPIC.efdmax. Typical value 087.
efdmin
{74EFB20A-4C9C-4c01-93A7-55AF0CD86421}
PI controller gain iKiisubasubi. Typical value 315.
ka
{5BCA2DE1-420A-4899-A08B-91EEB6CB10AD}
Exciter regulation factor iKiisubcsubi. Typical value 008.
kc
{28B3377C-BB8F-42e5-8EB2-7CF4EA397DBE}
Exciter constant iKiisubesubi. Typical value 0.
ke
{902997F3-CF1A-4ad7-8DEE-81FBAB289096}
Rate feedback gain iKiisubfsubi. Typical value 0.
kf
{5AD2CCEE-FFBB-4980-BEAE-79B39C438B58}
Current source gain iKiisubisubi. Typical value 0.
ki
{B552DBF0-7962-4d25-A542-F2F625204F01}
Potential source gain iKiisubpsubi. Typical value 65.
kp
{60EB104E-1D4E-4ecf-8C9B-FC77F7FDBBE6}
Saturation factor at iEiisub1subi iSeiisub1subi. Typical value 0.
se1
{A25CA093-89FD-441d-9E20-8C6B30D1F130}
Saturation factor at iEiisub2subi iSeiisub2subi. Typical value 0.
se2
{BDED94F4-7FD6-4c4d-83E7-004EC29D35E9}
PI controller time constant iTiisuba1subi gt 0. Typical value 1.
ta1
{E9E8CF95-70E3-4d1e-9A9F-8F59BAB44A01}
Voltage regulator time constant iTiisuba2subi gt 0. Typical value 001.
ta2
{E949BFE4-381D-431b-A551-93403A1CEA5A}
Lead time constant iTiisuba3subi gt 0. Typical value 0.
ta3
{DDDC8D0A-13F1-4635-A7D2-FE6C5FD0E7C8}
Lag time constant iTiisuba4subi gt 0. Typical value 0.
ta4
{5ABF11DE-2E44-4e27-9C3B-A55D44C5FDC1}
Exciter time constant iTiisubesubi gt 0. Typical value 0.
te
{2B9F001B-0151-4325-AFAA-26A5423ABBD4}
Rate feedback time constant iTiisubf1subi gt 0. Typical value 0.
tf1
{7B375F84-7678-4c63-B71D-6C887C7EF0A1}
Rate feedback lag time constant iTiisubf2subi gt 0. Typical value 0.
tf2
{F0267C4F-9C65-4307-951B-14F2A9655B2D}
PI maximum limit iViisubr1subi. Typical value 1.
vr1
{AF3CC231-831C-4486-A7D6-4D4CDBB7A6D1}
PI minimum limit iViisubr2subi. Typical value 087.
vr2
{6713D0C3-F0EE-43e5-8DE7-35054F6274E4}
Voltage regulator maximum limit iViisubrmaxsubi gt ExcPIC.vrmin. Typical value 1.
vrmax
{C4D26504-6125-47f1-98EF-1A40D7B21A72}
Voltage regulator minimum limit iViisubrminsubi lt ExcPIC.vrmax. Typical value 087.
vrmin
{B7C19D24-A986-497f-B51A-D77109151D11}
Field voltage value 1 iEiisub1subi. Typical value 3.
e1
{164FF977-2FF6-41c6-AE1F-88734F72D57B}
Field voltage value 2 iEiisub2subi. Typical value 4.
e2
{AE085DFD-AD00-4a0f-9551-537093FB3EE3}
Rate feedback signal flag ifbfi. Typical value fieldCurrent.
fbf
{DFED37F0-9874-4241-8F51-0802853DB747}
Limit type flag iFlimfi. Typical value 0.
flimf
{A0A350C6-93E9-4a81-8410-C769F3920346}
Rectifier regulation factor iKci. Typical value 005.
kc
{38A6941F-0125-4738-B058-C90C350BA0D5}
Exciter regulation factor iKdi. Typical value 2.
kd
{EE04C4BB-5D20-437d-8846-95E2C3E49D12}
Exciter field proportional constant iKei. Typical value 1.
ke
{A6B53E41-5B64-4438-ADE0-54F2BFE82011}
Field voltage feedback gain iKefdi. Typical value 0.
kefd
{BAA1CA90-5E07-49e8-BD09-0DD6DFA58648}
Rate feedback gain iKfi gt 0. Typical value 005.
kf
{21FF995A-7948-43e1-9791-213E20697284}
Field voltage controller feedback gain iKhi. Typical value 0.
kh
{8C0B2D0A-6B2E-438a-9C63-158D4928DBCD}
Field current regulator integral gain iKiii. Typical value 0.
kii
{1128DAA8-399E-47d3-89C3-DEE9BE045E85}
Field current regulator proportional gain iKipi. Typical value 1.
kip
{5C6427A7-6EBA-45e6-A728-B61462497777}
Coefficient to allow different usage of the modelspeed coefficient iKsi. Typical value 0.
ks
{3B54A7AA-444D-4633-AA33-8B2B32D74C9B}
Voltage regulator integral gain iKvii. Typical value 0.
kvi
{5E62EC4C-EF68-4f28-9087-2C2CAEA2472F}
Voltage regulator proportional gain iKvpi. Typical value 2800.
kvp
{13D6632B-6C89-430d-8827-EB2B6E555D3C}
VHz limiter gain iKvphzi. Typical value 0.
kvphz
{FE9FAAE0-6E2B-495c-89A9-E2BA75036112}
Pickup speed of VHz limiter iNvphzi. Typical value 0.
nvphz
{59F067BD-FABE-4f37-8F09-AF177DFB6D1A}
Saturation factor at iEiisub1subii iiSeiisub1subi. Typical value 00001.
se1
{C6DF5A98-35BC-475d-BF75-14EAA742BEFA}
Saturation factor at iEiisub2subi iSeiisub2subi. Typical value 0001.
se2
{AB4E5708-8F13-492c-98D0-ECD404A26A5B}
Voltage regulator time constant iTai gt 0. If 0 block is bypassed. Typical value 001.
ta
{1823BC8A-E677-4e6f-A2DD-E1D6AB82BC6D}
Lag time constant iTb1i gt 0. If 0 block is bypassed. Typical value 0.
tb1
{0D2DC130-91E3-4862-AB8A-0B65AFF5879D}
Lag time constant iTb2i gt 0. If 0 block is bypassed. Typical value 0.
tb2
{3CBCFBD6-90F5-459a-AC76-54D3AC35B22A}
Lead time constant iTc1i gt 0. Typical value 0.
tc1
{E2E39AA3-28B6-4e85-B8BD-B9B671508B85}
Lead time constant iTc2i gt 0. Typical value 0.
tc2
{BE1EB996-C2DE-49c4-AC97-9C58C1BE917A}
Exciter field time constant iTei gt 0. Typical value 12.
te
{3F2A693A-EA97-4152-8DE8-5C65813DD02B}
Rate feedback time constant iTfi gt 0. If 0 the feedback path is not used. Typical value 1.
tf
{A1A80139-7398-453a-8285-88B57F0022AD}
Feedback lead time constant iTf1i gt 0. Typical value 0.
tf1
{8CC07373-DC27-4753-BFF5-497DB67CEC25}
Feedback lag time constant iTf2i gt 0. If 0 block is bypassed. Typical value 0.
tf2
{F9FD5508-79C1-46e1-98B0-61F677DE1764}
Field current bridge time constant iTpi gt 0. Typical value 0.
tp
{521F84AC-7F9F-406d-BBD9-7232D826D809}
Maximum compounding voltage iVcmaxi. Typical value 0.
vcmax
{337CB21C-BCBA-4a33-A646-D85C88358ACA}
Maximum exciter field current iVfmaxi gt ExcREXS.vfmin. Typical value 47.
vfmax
{7247F5BE-EC4E-4c8e-9479-49FA0613BE8D}
Minimum exciter field current iVfmini lt ExcREXS.vfmax. Typical value 20.
vfmin
{E7686DA5-5AE6-4d15-AC40-D5409F72AAB9}
Voltage regulator input limit iVimaxi. Typical value 01.
vimax
{B83961F7-E22F-4aa2-A454-42F7445F7ECF}
Maximum controller output Virmaxi gt ExcREXS.vrmin. Typical value 47.
vrmax
{837348BB-9823-4a46-930D-12039A3F019C}
Minimum controller output iVrmini lt ExcREXS.vrmax. Typical value 20.
vrmin
{33A42831-C76D-45c5-BAD5-C1DE3EBEF120}
Exciter compounding reactance iXci. Typical value 0.
xc
{A79AD54D-A5C2-4903-A5B6-72D42C039209}
Integrator limiter iLSATi. Typical value 573.
lsat
{FC2ED949-867C-4492-A30C-E22DE3F3159F}
Setpoint iLUSi. Typical value 012.
lus
{12DFCF3E-BF50-4476-88E8-DEAF0B00DD9F}
Voltage input time constant iMESUi gt 0. Typical value 002.
mesu
{D228BCF3-F8F4-4771-9D6F-9D8AE6093515}
Input time constant iT4Mi gt 0. Typical value 5.
t4m
{356724A3-E0AA-4491-B323-416289AD1D4F}
Lead lag time constant iTCi gt 0. Typical value 002.
tc
{FCC25BEF-45D5-4172-97CE-45B8979B9F09}
Lead lag time constant iTEi gt 0. Typical value 022.
te
{FA18CA67-BB00-4454-BA75-FC50E96C5C2A}
Exciter time constant iTFi gt 0. Typical value 001.
tf
{028B3D45-810E-48ff-BB3E-BAAF81AD4FE3}
Maximum voltage reference limit iUCMAXi gt ExcRQB.ucmin. Typical value 11.
ucmax
{2527D779-DC89-465d-BAD8-711D4643F64B}
Minimum voltage reference limit iUCMINi lt ExcRQB.ucmax. Typical value 09.
ucmin
{C5E3235C-8A06-4837-8625-6FEE9A8946E2}
Maximum field voltage output iEmaxi gt ExcSCRX.emin. Typical value 5.
emax
{BA58E757-E10E-426a-B0FE-337EF03939CA}
Minimum field voltage output iEmini lt ExcSCRX.emax. Typical value 0.
emin
{6498CE49-AF8F-4aa1-8256-5B79825B452C}
Gain iKi gt 0. Typical value 200.
k
{8AC0E9A7-A057-464e-A78C-6C7983DB937B}
Denominator time constant of laglead block iTbi gt 0. Typical value 10.
tb
{41A5AFD5-E1ED-4f9e-B941-EFB7298F69A8}
Time constant of gain block iTei gt 0. Typical value 002.
te
{719F3A53-D2A7-4c1c-8BC4-38D6579D9D79}
Field voltage clipping maximum limit iEfdmaxi gt ExcSEXS.efdmin. Typical value 5.
efdmax
{F0C86E0F-FC43-4f59-867B-86B521DA22F6}
Field voltage clipping minimum limit iEfdmini lt ExcSEXS.efdmax. Typical value 5.
efdmin
{5E05184B-B1A2-4f70-BF11-66A183E695EB}
Maximum field voltage output iEmaxi gt ExcSEXS.emin. Typical value 5.
emax
{F051BD88-056E-4f60-97EB-872E15E43C53}
Minimum field voltage output iEmini lt ExcSEXS.emax. Typical value 5.
emin
{DBAD3D75-804B-45f8-A507-EA534D2CACD5}
Gain iKi gt 0. Typical value 100.
k
{4F0E6B81-FF7D-4b6b-92FA-52250C6BF3E7}
PI controller gain iKci gt 0 if ExcSEXS.tc gt 0. Typical value 008.
kc
{E3473C5E-7B22-4574-B4F2-853C914A509E}
Denominator time constant of laglead block iTbi gt 0. Typical value 10.
tb
{C5064A87-9B38-4a3c-BFF2-B13AB2109838}
PI controller phase lead time constant iTci gt 0. Typical value 0.
tc
{261F868D-1638-4d43-BFA0-EA83D3E486C0}
Time constant of gain block iTei gt 0. Typical value 005.
te
{FE66CAC3-FB7E-4687-AAD1-479896B7D6ED}
Field voltage clipping upper level limit iEfdmaxi gt ExcSK.efdmin.
efdmax
{0FD6F6E4-E898-412c-A4F6-EE30DF924E8B}
Field voltage clipping lower level limit iEfdmini lt ExcSK.efdmax.
efdmin
{2D429937-73F6-4628-9C56-21D506052E14}
Maximum field voltage output iEmaxi gt ExcSK.emin. Typical value 20.
emax
{B0EEAFBE-2487-4a16-98BB-6A3C34D76506}
Minimum field voltage output iEmini lt ExcSK.emax. Typical value 20.
emin
{8D70C21C-B2B5-4f1b-B601-57CEC3318BE0}
Gain iKi. Typical value 1.
k
{BD843955-8E54-47a7-938A-65CF5F0CB4FC}
Parameter of underexcitation limit iK1i. Typical value 01364.
k1
{68FD4614-5741-4551-A64F-3668F8C7E3AC}
Parameter of underexcitation limit iK2i. Typical value 03861.
k2
{BE8C96ED-F4CA-4ea2-B895-17463F9F87AC}
PI controller gain iKci. Typical value 70.
kc
{561EBBD2-7150-4b48-BAA0-FD28EF893735}
Rectifier regulation factor iKcei. Typical value 0.
kce
{3284DFD6-7744-420e-86A1-9DB5C7852572}
Exciter internal reactance iKdi. Typical value 0.
kd
{5962CD3D-E872-421e-B352-559B29A58F33}
P controller gain iKgobi. Typical value 10.
kgob
{3C6EB743-962C-45ab-BAF1-CA0CAB78F7BC}
PI controller gain iKpi. Typical value 1.
kp
{73AA33B0-E129-40de-8030-ED22FBCBAA92}
PI controller gain of integral component iKqii. Typical value 0.
kqi
{711A9A2D-86D4-46ed-8E07-D20B84FE7DB1}
Rate of rise of the reactive power iKqobi.
kqob
{FCB1D27A-E4A2-47ff-85F5-C23C414DA3E1}
PI controller gain iKqpi. Typical value 0.
kqp
{7D3732D4-96CE-40d2-95EF-6DB819CDB0BE}
Deadband of reactive power inqi. Determines the range of sensitivity. Typical value 0001.
nq
{AD6C219A-305A-4b1b-9879-A8860E0E21BD}
Desired value setpoint of reactive power manual setting iQzi.
qz
{B38B207C-40F5-4827-9F32-3C70C7E8C6E6}
Apparent power of the unit iSbasei gt 0. Unit MVA. Typical value 259.
sbase
{D15ECA3E-3FD1-4584-B2CC-B70884FCDA83}
PI controller phase lead time constant iTci gt 0. Typical value 8.
tc
{690E4CEE-5ADB-4f44-AAC6-56E6811094C2}
Time constant of gain block iTei gt 0. Typical value 01.
te
{7AA1CAD6-AB5F-4943-B253-8024981A7108}
PI controller phase lead time constant iTii gt 0. Typical value 2.
ti
{55A63105-579E-4e85-B7E4-B1E0857B256D}
Time constant iTpi gt 0. Typical value 01.
tp
{1EAE01E6-7A2C-479a-9C23-DA86213629EF}
Voltage transducer time constant iTri gt 0. Typical value 001.
tr
{DB62C59D-8F81-40e1-B20E-E831D5349336}
Maximum error iUImaxi gt ExcSK.uimin. Typical value 10.
uimax
{DE76216E-210B-4730-B70B-451037833DEB}
Minimum error iUImini lt ExcSK.uimax. Typical value 10.
uimin
{AB4D34F7-5072-473b-8E5B-3E36BA53D1C8}
Maximum controller output iURmaxi gt ExcSK.urmin. Typical value 10.
urmax
{31276876-9B91-42c6-B212-5E1B6BE41BCA}
Minimum controller output iURmini lt ExcSK.urmax. Typical value 10.
urmin
{B1B5F001-6874-4d63-89AC-19327190DA78}
Maximum terminal voltage input iVtmaxi gt ExcSK.vtmin. Determines the range of voltage deadband. Typical value 105.
vtmax
{831EC9A6-2EB2-4887-9213-E1F4F75E4C6C}
Minimum terminal voltage input iVtmini lt ExcSK.vtmax. Determines the range of voltage deadband. Typical value 095.
vtmin
{54C4FD15-0EBB-44d3-8231-5C175B2AADBA}
Maximum output iYpi. Typical value 1.
yp
{4CC00DA4-48FD-41c1-832E-DC6C5B06DF4A}
Exciter output current limit reference iIlri. Typical value 0.
ilr
{299F6CC8-4242-415a-8A66-833D42D155D2}
Voltage regulator gain iKai gt 0. Typical value 190.
ka
{5FA43B7E-B066-4055-A993-22EA69BAA575}
Rectifier loading factor proportional to commutating reactance iKci gt 0. Typical value 005.
kc
{C1147AE5-D510-4a61-83E7-12E213058FDA}
Excitation control system stabilizer gains iKfi gt 0. Typical value 0.
kf
{1B2022B8-C962-4d71-9DDF-84813986A02D}
Exciter output current limiter gain iKlri. Typical value 0.
klr
{55D4825C-335E-41bb-8319-724D8040D2D9}
Voltage regulator time constant iTai gt 0. Typical value 002.
ta
{0B71598C-A8A9-49c0-9070-F94B972FA257}
Voltage regulator time constant iTbi gt 0. Typical value 10.
tb
{A91EB8DD-E9B2-49bb-BC30-5C731961AFEC}
Voltage regulator time constant iTb1i gt 0. Typical value 0.
tb1
{D35EF4E2-771E-495c-892C-E7EF82F9E810}
Voltage regulator time constant iTci gt 0. Typical value 1.
tc
{F95F8649-9727-4216-B449-8B1C806A00A9}
Voltage regulator time constant iTc1i gt 0. Typical value 0.
tc1
{644B50E3-A954-43c3-8DCC-CFBD85C3C4E2}
Excitation control system stabilizer time constant iTfi gt 0. Typical value 1.
tf
{297716A1-9281-428e-9DC6-339BB15B7164}
Maximum voltage regulator output iVamaxi gt 0. Typical value 999.
vamax
{9694EE51-19FE-4718-84F8-C80AE21B80D7}
Minimum voltage regulator output iVamini lt 0. Typical value 999.
vamin
{9FBA70E4-BCC1-453e-A3AC-0C35CF7BB9A7}
Maximum voltage regulator input limit iVimaxi gt 0. Typical value 999.
vimax
{BE5AA2C9-CA37-41d1-8BEF-2FC80DAE61FC}
Minimum voltage regulator input limit iVimini lt 0. Typical value 999.
vimin
{06AEEF13-B378-4774-8E8C-A93AB84A6811}
Maximum voltage regulator outputs iVrmaxi gt 0 . Typical value 78.
vrmax
{90BD86F1-4D12-4603-AF05-AEAA91C05F0E}
Minimum voltage regulator outputs iVrmini lt 0. Typical value 67.
vrmin
{E850252E-D5F4-4ab1-A704-7BC626749A0B}
Excitation xfmr effective reactance iXei. Typical value 004.
xe
{C4CA66BD-BB69-42f0-AE49-98B713DB04C0}
Maximum field voltage iEfdmaxi gt 0. Typical value 99.
efdmax
{04FB7F7D-E5C2-4732-B7D7-000573F50691}
Voltage regulator gain iKai gt 0. Typical value 120.
ka
{99A6327C-145D-4aa4-B3CB-18DD357B99D0}
Rectifier loading factor proportional to commutating reactance iKci gt 0. Typical value 182.
kc
{7D5095FE-5B08-4c42-BD59-C0AE5265A315}
Exciter constant related to selfexcited field iKei. Typical value 1.
ke
{334F712E-05EF-4919-A6C1-5558E80D59BD}
Excitation control system stabilizer gains ikfi gt 0. Typical value 005.
kf
{40CB6E18-9774-49bc-B1AA-A3F7A585155E}
Potential circuit gain coefficient iKiisubisubi gt 0. Typical value 8.
ki
{F5EBC6C9-F6EB-4bcf-B60F-5CAA5BD5FA0A}
Potential circuit gain coefficient iKiisubpsubi gt 0. Typical value 488.
kp
{438AA8E0-EC2A-4335-A741-8F099D607516}
Voltage regulator time constant iTai gt 0. Typical value 015.
ta
{E4574F75-ABB8-46e5-BA32-AFB2A0EF8AEC}
Voltage regulator time constant iTbi gt 0. Typical value 0.
tb
{F083AE64-1099-4367-9F63-17026ACEC1C9}
Voltage regulator time constant iTci gt 0. Typical value 0.
tc
{7E2421E3-C609-4fcf-B228-BCE66EC6F370}
Exciter time constant integration rate associated with exciter control iTei gt 0. Typical value 05.
te
{2FF502DB-FC0D-4fac-B790-C8B2743FE5E7}
Excitation control system stabilizer time constant iTfi gt 0. Typical value 07.
tf
{394F4FFC-7825-4681-B651-3326632EEF09}
Maximum voltage regulator outputs iVrmaxi gt 0. Typical value 1.
vrmax
{10DE218B-1E0C-43bb-8834-4E1153698116}
Minimum voltage regulator outputs iVrmini lt 0. Typical value 1.
vrmin
{7B1AEA0E-E3D0-4f18-8F81-DFF7DF4CFBA9}
Maximum AVR output iEfdmaxi gt 0. Typical value 69.
efdmax
{B49CC0D1-FF73-4ede-BA5D-2DD5DDEC017E}
Rectifier loading factor proportional to commutating reactance iKci gt 0. Typical value 11.
kc
{759F8FC1-9C06-4000-B69C-92FEFA3DDD62}
Feedback gain constant of the inner loop field regulator iKgi gt 0. Typical value 1.
kg
{C962B310-42A4-4dee-B320-59C167AFEB20}
Potential circuit gain coefficient iKiisubisubi gt 0. Typical value 483.
ki
{EB7FD237-72F1-4807-BCFB-94A3A09D05B7}
AVR gain iKji gt 0. Typical value 200.
kj
{2E8AD6FA-9042-47c9-B00D-325156CD6AE1}
Forward gain constant of the inner loop field regulator iKmi gt 0. Typical value 704.
km
{0D6CDDEA-0034-4de5-AD0B-F4B58970262D}
Potential source gain iKiisubpsubi gt 0. Typical value 437.
kp
{31D10031-B358-47c1-96D0-9D4D7C67AD71}
Coefficient to allow different usage of the modelspeed coefficient iKsi. Typical value 0.
ks
{112D9E88-EF72-4d1c-85B1-A544F84CAF93}
Coefficient to allow different usage of the modelspeed coefficient iKs1i. Typical value 0.
ks1
{C4A5C191-9F4A-4535-9579-04D479582852}
Voltage regulator time constant iTbi gt 0. Typical value 667.
tb
{3A50E6F6-3D29-4201-B6DB-C63623D018BB}
Voltage regulator time constant iTci gt 0. Typical value 1.
tc
{0E068C63-6C9B-41a1-AF39-BB489330DC3D}
Potential circuit phase angle ithetaiisubpsubi. Typical value 20.
thetap
{95EDEBF4-177D-410e-9BAD-297391272654}
Forward time constant of inner loop field regulator iTmi gt 0. Typical value 1.
tm
{F207B687-878E-4557-85DF-8254522CB6EB}
Maximum excitation voltage iVbmaxi gt 0. Typical value 863.
vbmax
{806CEC8A-3D3B-4db2-B231-FF5CB5460B43}
Maximum inner loop feedback voltage iVgmaxi gt 0. Typical value 653.
vgmax
{C7F51423-E9FB-4dc2-875D-A6EBCEE837FE}
Maximum voltage regulator input limit iVimaxi gt 0. Typical value 02.
vimax
{0B040704-DE08-4fd0-82B0-F6581783A2BD}
Minimum voltage regulator input limit iVimini lt 0. Typical value 02.
vimin
{9BC9955E-E99F-4553-9757-085DE4195D79}
Maximum voltage regulator output iVrmaxi gt 0. Typical value 1.
vrmax
{6F1CDD75-B4DE-499f-A087-2068F39F2797}
Minimum voltage regulator output iVrmini lt 0. Typical value 1.
vrmin
{0A385D67-19AA-4727-8F12-2C0943FB5733}
Reactance associated with potential source iXli gt 0. Typical value 009.
xl
{A84048A2-51DD-4bf5-8FF0-41F0BBA7ECF3}
Rectifier loading factor proportional to commutating reactance iKci gt 0. Typical value 0113.
kc
{6EDEFCBA-079E-4290-854D-CDF8DB25FE4C}
Feedback gain constant of the inner loop field regulator iKgi gt 0. Typical value 0.
kg
{14A18922-E6B8-409f-861B-F794FB4A98AD}
Potential circuit gain coefficient iKii gt 0. Typical value 0.
ki
{D2007931-E17A-4553-A7FD-CAC7E75A0014}
Voltage regulator integral gain output iKimi. Typical value 0.
kim
{4A7B2A9D-6E61-45f0-84C3-99F7E6328846}
Voltage regulator integral gain iKiri. Typical value 1075.
kir
{E0AD83C8-3786-431a-A705-2E9653CA6CB9}
Potential circuit gain coefficient iKpi gt 0. Typical value 93.
kp
{7B352853-2448-486c-9924-E37B59371786}
Voltage regulator proportional gain output iKpmi. Typical value 1.
kpm
{13AAB946-F17E-4fbf-9A11-CD1811931F25}
Voltage regulator proportional gain iKpri. Typical value 1075.
kpr
{E7B37141-1F44-4f27-803C-812CFD52473E}
Voltage regulator time constant iTai gt 0. Typical value 002.
ta
{4EBCE4F0-94D6-4f08-B2E7-F6369BFDC94F}
Potential circuit phase angle ithetaiisubpsubi. Typical value 0.
thetap
{7FD0BF6C-F14E-431c-ADC2-05A61971660F}
Maximum excitation voltage iVbmaxi gt 0. Typical value 1163.
vbmax
{4E09E42B-F894-4f5d-BE2D-D6E1AB8D3AE7}
Maximum inner loop feedback voltage iVgmaxi gt 0. Typical value 58.
vgmax
{FB46EB5E-7D7F-451d-B5B6-22A5554D225E}
Maximum inner loop output iVmmaxi gt ExcST4B.vmmin. Typical value 99.
vmmax
{E94E8EBE-D461-4f60-9238-A0EAA59D8AE3}
Minimum inner loop output iVmmini lt ExcST4B.vmmax. Typical value 99.
vmmin
{D145E2BF-D2C8-4ca7-BF37-F3D3F297A10E}
Maximum voltage regulator output iVrmaxi gt 0. Typical value 1.
vrmax
{E7742CB5-2678-4bc7-82C4-B2E91C3E65A5}
Minimum voltage regulator output iVrmini lt 0. Typical value 087.
vrmin
{00E16C89-365B-4353-B025-D9C196BFC28D}
Reactance associated with potential source iXli gt 0. Typical value 0124.
xl
{47EC3F39-C11A-44c7-A2BF-FC7A201AC00D}
Exciter output current limit reference iIlri gt 0. Typical value 4164.
ilr
{FCA8A10C-DBAD-4049-B59E-F187762F1A65}
Exciter output current limit adjustment iKcli gt 0. Typical value 10577.
kcl
{3A03D787-8FC6-4517-8C9E-3F88D4BA4916}
Precontrol gain constant of the inner loop field regulator iKffi. Typical value 1.
kff
{3A3B956C-CA37-4a16-B43C-D4DCCE5098AB}
Feedback gain constant of the inner loop field regulator iKgi gt 0. Typical value 1.
kg
{E5BA9747-D3A5-480e-8B33-2537D34D3BB3}
Voltage regulator integral gain iKiai gt 0. Typical value 45094.
kia
{478B94F9-DE07-4bd3-922D-AF36B9CEEBF3}
Exciter output current limit adjustment iKcli gt 0. Typical value 1733.
klr
{8C470550-6C26-4c95-887D-97C43A96F782}
Forward gain constant of the inner loop field regulator iKmi. Typical value 1.
km
{C253D207-1AB9-4e5b-A328-470BCC10BE64}
Voltage regulator proportional gain iKpai gt 0. Typical value 18038.
kpa
{604F5148-D7EE-4b63-9F25-EC486268D709}
Voltage regulator derivative gain iKvdi. Typical value 0.
kvd
{A44EC6DA-DCAD-492c-ADF9-BBBAF462B5CF}
OEL input selector iOELini. Typical value noOELinput corresponds to iOELini 0 on diagram.
oelin
{BC9CF815-45CE-47c3-B93E-60A221E7347B}
Feedback time constant of inner loop field voltage regulator iTgi gt 0. Typical value 002.
tg
{EDC9DD41-AAB5-44ad-9270-B02302733648}
Rectifier firing time constant iTsi gt 0. Typical value 0.
ts
{D5C32325-C614-45c1-9CEA-BEA8BD26A1F8}
Voltage regulator derivative gain iTvdi gt 0. Typical value 0.
tvd
{A4BF77C2-C3E0-4953-882B-C195B6215241}
Maximum voltage regulator output iVamaxi gt 0. Typical value 481.
vamax
{C1C060E9-F615-404e-8C90-3839006F23D1}
Minimum voltage regulator output iVamini lt 0. Typical value 385.
vamin
{D8D69CA0-4560-454c-86AD-186598946A99}
Maximum voltage regulator input limit iVimaxi gt ExcST6B.vimin. Typical value 10.
vimax
{9911F24C-D092-46c4-916A-BB94D6C159DB}
Minimum voltage regulator input limit iVimini lt ExcST6B.vimax. Typical value 10.
vimin
{E76D3012-490C-4cf4-8ACB-30708748B417}
Maximum voltage regulator output iVrmaxi gt 0. Typical value 481.
vrmax
{264FE55C-A470-450e-830D-409B9D222CFC}
Minimum voltage regulator output iVrmini lt 0. Typical value 385.
vrmin
{9D2C0854-E7FD-4a26-AEF6-F2F9EDBEA19E}
Excitation source reactance iXci. Typical value 005.
xc
{CFE95EFB-D6A9-4460-A7BB-9F16B7A60E8D}
Highvalue gate feedback gain iKhi gt 0. Typical value 1.
kh
{70132C02-89DD-4f18-9B11-50094001F527}
Voltage regulator integral gain iKiai gt 0. Typical value 1.
kia
{2632802D-0AC4-4221-858A-B3521F14A671}
Lowvalue gate feedback gain iKli gt 0. Typical value 1.
kl
{4440B121-48D5-4f2a-91B3-720A655A30D4}
Voltage regulator proportional gain iKpai gt 0. Typical value 40.
kpa
{C26A669A-D7BA-4113-A91F-37634F96916D}
OEL input selector iOELini. Typical value noOELinput.
oelin
{55897842-91B8-4c4a-A38E-A88FB78B11FF}
Regulator lag time constant iTbi gt 0. Typical value 1.
tb
{8BB6C432-DA6F-4daa-B7F3-678A02D9506D}
Regulator lead time constant iTci gt 0. Typical value 1.
tc
{E341A921-3731-4bad-9E4C-022AB18CE5AA}
Excitation control system stabilizer time constant iTfi gt 0. Typical value 1.
tf
{265813C0-D043-40be-9342-679FAB10BB01}
Feedback time constant of inner loop field voltage regulator iTgi gt 0. Typical value 1.
tg
{DB87FE62-391C-4c72-82F6-446933866664}
Feedback time constant iTiai gt 0. Typical value 3.
tia
{FB558E6B-74F6-4bb2-9DF0-8A453A4D24C2}
Rectifier firing time constant iTsi gt 0. Typical value 0.
ts
{95E5DCB2-CE79-470f-AAA6-871EA7220C07}
UEL input selector iUELini. Typical value noUELinput.
uelin
{CC627920-D4D5-4fd6-A639-11C670C7E6F2}
Maximum voltage reference signal iVmaxi gt 0 and gt ExcST7B.vmin. Typical value 11.
vmax
{21F6CF25-E060-48c9-99F8-04D529E13492}
Minimum voltage reference signal iVmini gt 0 and lt ExcST7B.vmax. Typical value 09.
vmin
{FB2ADFC3-91ED-49cd-97B3-CB0F47BCC7FE}
Maximum voltage regulator output iVrmaxi gt 0. Typical value 5.
vrmax
{EE9E1285-0A4B-4d4d-B499-BDAB8948BA20}
Minimum voltage regulator output iVrmini lt 0. Typical value 45.
vrmin
{E3868033-D2EC-4050-BA79-4C0614B10136}
Discontinuous excitation control model associated with this excitation system model.
DiscontinuousExcitationControlDynamics
{A3CB1790-95C9-404f-AA0A-91B8334A0AD4}.ClientEnd
Overexcitation limiter model associated with this excitation system model.
OverexcitationLimiterDynamics
{A6EC8E29-6996-4dba-B736-0ACEAFBAD928}.ClientEnd
Power factor or VAr controller type 1 model associated with this excitation system model.
PFVArControllerType1Dynamics
{A9638A5A-FA55-428d-8A6E-7CD1F44F4703}.ClientEnd
Power factor or VAr controller type 2 model associated with this excitation system model.
PFVArControllerType2Dynamics
{5FBF52C8-0201-4d22-996D-1457516FB808}.ClientEnd
Power system stabilizer model associated with this excitation system model.
PowerSystemStabilizerDynamics
{EC18A533-5643-4fe6-87AE-2182DD4C9F1F}.ClientEnd
Synchronous machine model with which this excitation system model is associated.
SynchronousMachineDynamics
{C7679E92-5BAF-4548-868A-CE939B02A5E8}.SupplierEnd
Undrexcitation limiter model associated with this excitation system model.
UnderexcitationLimiterDynamics
{280D64B5-2696-4d89-8390-C68A8F827258}.ClientEnd
Voltage compensator model associated with this excitation system model.
VoltageCompensatorDynamics
{261F59A6-26BA-4cfc-9309-36D92F002250}.ClientEnd
Parameter of this proprietary userdefined model.
ProprietaryParameterDynamics
{5206A5D1-9E7E-4283-B6EF-7F3C51885F61}.ClientEnd
ExpectedEnergyValues
{1952C58A-4A15-483e-A741-9C389499CAAB}.SupplierEnd
ExpectedEnergy
{1952C58A-4A15-483e-A741-9C389499CAAB}.ClientEnd
RegisteredResource
{29590DFD-E80A-489e-9558-7515799A9C17}.ClientEnd
extensionsItem
{F3F93A94-3B64-40c9-8285-0A1EE26EADEF}
Power Frequency Bias. This is the change in power injection divided by the change in frequency and negated. A positive value of the power frequency bias provides additional power injection upon a drop in frequency.
governorSCD
{01E4CD87-A49A-4ae9-BFB1-C80033BBD38C}
Maximum initial symmetrical shortcircuit currents Ik max in A Ik SkSQRT3 Un. Used for short circuit data exchange according to IEC 60909.
maxInitialSymShCCurrent
{A9F4F42E-246F-4da4-AE34-14AE148CF3BF}
Maximum active power of the injection.
maxP
{C915FB34-81C2-4752-9F7A-23941C7E985F}
Maximum reactive power limit. It is used for modelling of infeed for load flow exchange and not for short circuit modelling.
maxQ
{7AE475FE-0F78-42e3-81B1-8C8744B9062F}
Minimum initial symmetrical shortcircuit currents Ik min in A Ik SkSQRT3 Un. Used for short circuit data exchange according to IEC 60909.
minInitialSymShCCurrent
{CEA5D0C1-40FF-4bc9-9887-7E2C67B4A121}
Minimum active power of the injection.
minP
{EC098689-7996-4822-A83C-ED6ADCE4CF9B}
Minimum reactive power limit. It is used for modelling of infeed for load flow exchange and not for short circuit modelling.
minQ
{B2CF8876-6398-4362-B2B8-7BC11A81F53E}
Active power injection. Load sign convention is used i.e. positive sign means flow out from a node.Starting value for steady state solutions.
p
{AA86E221-E69B-41af-BB7C-A899574AC007}
Reactive power injection. Load sign convention is used i.e. positive sign means flow out from a node.Starting value for steady state solutions.
q
{747953B0-23CB-4f85-B09F-C9828637BB1C}
Voltage factor in pu which was used to calculate shortcircuit current Ik and power Sk. Used only if short circuit calculations are done according to superposition method.
voltageFactor
{F0AAD163-7313-4376-9CED-46F863F38E66}
Kind of FACTS device.
kind
{C566FB1F-C93C-4dc5-A309-8A9528B43B55}
EnergyPriceCurve
{38EA7E7F-BA90-431d-816C-66C5286F4757}.ClientEnd
Flowgate
{DFEE65EA-08ED-41f3-910F-446DC7C3B26D}.ClientEnd
Pnodes
{A43D8B73-D014-475b-8461-B03EC8169BB8}.SupplierEnd
Quantity typically MWs Seller owns all rights being offered MWs over time on same Point of Receipt Point of Delivery or Resource.
baseEnergy
{0637C1BB-0D22-4afa-8210-FD0ECB0ABCCA}
Reason for breaker failure.
breakerFailureReason
{C4A89781-F158-49af-A637-8B7841514B3E}
Classification of failure.
failureClassification
{01072E4A-F4DF-4aac-ADE1-0C655E70D4F5}
How the asset failure was isolated from the system.
failureIsolationMethod
{F7A2DC7A-E078-4763-B73A-8ABF2A1527C5}
What asset failed to be able to do.
failureMode
{BB740CCA-3762-4f42-AB1A-8F9CBD6C51A9}
Reason for transformer failure.
transformerFailureReason
{F9271E6F-C0A5-4d64-A94F-5E282FB75976}
All types of fault cause.
FaultCauseTypes
{76F2310A-9AC3-4fb7-87A4-E24B2A669076}.SupplierEnd
Equipment carrying this fault.
FaultyEquipment
{6B3EA616-0934-425c-A898-1D84DADF5261}.SupplierEnd
Location
{7F84E357-68DD-4257-BD11-EE226FADA1E6}.SupplierEnd
Outage associated with this fault.
Outage
{B23C14B3-6E9C-4b0c-82C5-781ED12E4406}.ClientEnd
Fault impedance. Its usage is described by kind.
impedance
{4DFBDAF9-B528-44d1-A3D3-8CBABD131499}
The kind of phase fault.
kind
{D4AF3A43-0D83-418f-997A-3957B4A762CC}
The phases participating in the fault. The fault connections into these phases are further specified by the type of fault.
phases
{18AAE005-424C-4b89-941E-5D72E4C2075B}
ConfigurationEvent
{B79138C2-DB7B-43a8-A72B-77D615EB381B}.ClientEnd
All faults with this cause type.
Faults
{76F2310A-9AC3-4fb7-87A4-E24B2A669076}.ClientEnd
The resistance of the fault between phases and ground.
rGround
{DA3016FC-3A48-4d38-B3B3-A21BBF1832FE}
The resistance of the fault between phases.
rLineToLine
{463CA558-541A-42b2-88C0-8E6C80D5471B}
The reactance of the fault between phases and ground.
xGround
{6AC55EA4-E390-491d-AC2A-EF69D162C48A}
The reactance of the fault between phases.
xLineToLine
{36EA383A-71DE-4ead-B46C-66F973DDC08B}
Kind of reset mechanisim of this fault indicator.
resetKind
{E6FE4887-07EB-4b13-97EF-02A0BE271014}
The secondary substations that are normally energized from the feeder. Used for naming purposes. Should be consistent with the other associations for energizing terminal specification and the feeder energization specification.
NamingSecondarySubstation
{D06442E1-D688-4393-8B71-E08E4CA4685F}.SupplierEnd
The substations that are normally energized by the feeder.
NormalEnergizedSubstation
{11C09449-0F39-4372-A153-258CD2A57196}.SupplierEnd
The substation that nominally energizes the feeder. Also used for naming purposes.
NormalEnergizingSubstation
{D83ED2BA-7B91-4a91-81C0-A7CF3669C450}.SupplierEnd
The normal head terminal or terminals of the feeder.
NormalHeadTerminal
{C1A181B0-A25E-4eca-9A0E-394B6E20BB6C}.SupplierEnd
Crew
{2F2C04F1-3A57-404e-87F0-356183FF8B57}.SupplierEnd
FieldDispatchStep
{2B5021A8-7C38-4df1-ABED-A71EC82BC277}.SupplierEnd
PlannedOutage
{37072B50-0229-4a00-A050-8976613B5259}.SupplierEnd
UnplannedOutage
{D82C3366-0534-4013-898A-7202071B4EF5}.SupplierEnd
FieldDispatchHistory
{2B5021A8-7C38-4df1-ABED-A71EC82BC277}.ClientEnd
The status of one or more crews dispatched to perform field work at one or more work sites
dispatchStatus
{AE292504-F155-4d8c-8F8E-371BDFDF9A65}
All safety documents issued to this supervisor.
IssuedSafetyDocuments
{9928D926-C37A-4b01-9B70-087C54DA13DA}.SupplierEnd
All safety documents released by this supervisor.
ReleasedSafetyDocuments
{D76F467F-64BC-408a-BE7C-AEA257C59F88}.SupplierEnd
The asset to which this financial information relates.
Asset
{1B0E0E88-6371-4ed9-AD31-7E0799CB9AD6}.SupplierEnd
The actual purchase cost of this particular asset.
actualPurchaseCost
{04BD44E7-FD1C-4292-A8F8-8DADE6AAA622}
Value of asset as of valueDateTime.
financialValue
{D7044F6F-4037-4595-9910-1C2923148DDB}
The quantity of the asset if per unit length for example conductor.
quantity
{BDFF234B-770A-449a-A2C3-4ACD1948F296}
AuxillaryValues
{6B36C00F-62F3-49c3-998C-F5EDD88A0CA8}.SupplierEnd
Unit multiplier of this quantity.
multiplier
{9A517FCA-1C10-4df0-B2B5-EEC4F2BC2611}
Unit of this quantity.
unit
{99793087-EF72-4fe3-834B-7C2F56A6E5C2}
Point
{DA5D6A56-1992-4d38-994D-E118A3CDC921}.SupplierEnd
TimeSeries
{090E7580-E214-4627-9E02-CE3051F6B408}.ClientEnd
CongestionRevenueRight
{C6E4CA42-E336-4a8a-828E-6AF9E8F25458}.ClientEnd
ConstraintResults
{18E34024-C496-433d-B129-256CA4377357}.SupplierEnd
ContractDistributionFactor
{3A09997D-D60D-46df-B010-018CC9A81D1B}.SupplierEnd
FTRs
{DFEE65EA-08ED-41f3-910F-446DC7C3B26D}.SupplierEnd
FlowgateRelief
{FAA03841-9BD5-44ff-94D8-81234341632C}.SupplierEnd
FlowgateValue
{3482FAE4-117E-4132-A682-1E1D2291A577}.SupplierEnd
From_SubControlArea
{1041B4DE-551C-4099-85BD-E8EBC12523E1}.SupplierEnd
GeneratingUnitDynamicValues
{88A0B4C3-D5DA-43c8-AF9F-4CD15D7E9B66}.ClientEnd
GenericConstraints
{DE1D7657-F706-42fa-AB0A-26D34549C4A7}.ClientEnd
HostControlArea
{AF155808-E637-4950-B9F3-2EAB07EDB824}.ClientEnd
InterTie
{001E125A-BECE-4e28-A128-A8ADBBEFE8D0}.SupplierEnd
InterTieResults
{E8AB91AD-788A-4426-BCAB-5F8132B26BE5}.SupplierEnd
MktLine
{8B57B818-A6B3-4836-BC0E-617E9ABEB67D}.SupplierEnd
MktPowerTransformer
{E865ED1B-5944-445e-BD28-D928C5FF6389}.SupplierEnd
MktTerminal
{E72576E6-C983-42fd-AED5-7EBD0160B933}.ClientEnd
RegisteredInterTie
{B4B4DF5E-5FDD-4ed9-B4E9-ADE4754D4D34}.SupplierEnd
SecurityConstraints
{D96B3C19-134E-4b97-96C3-34675C1BB168}.SupplierEnd
To_SubControlArea
{84D89B72-DEA9-4433-B8A9-4EEC604AA936}.SupplierEnd
TranmissionRightEntitlement
{4577596A-E96F-49da-9220-E1987860787A}.SupplierEnd
TransmissionCapacity
{8921D733-BE8B-4a9f-BB12-03E6AB71B1AB}.SupplierEnd
ViolationLimits
{60BE8E0E-9F8A-4813-93AA-E5DC48BEF7A5}.ClientEnd
The direction of the flowgate export or import
direction
{CBEB429F-27C3-4d36-9CED-C02CF4B44D95}
Export MW rating
exportMWRating
{DA6511CE-1D9A-4fcb-A9EB-6315CF80812D}
Import MW rating
importMWRating
{F6392594-E1B4-4aad-90D6-F3EBA308A3AB}
FlowgateValue
{D6A42AC2-2960-4436-89AF-97FB2C39460D}.SupplierEnd
Flowgate
{FAA03841-9BD5-44ff-94D8-81234341632C}.ClientEnd
Flowgate
{3482FAE4-117E-4132-A682-1E1D2291A577}.ClientEnd
FlowgatePartner
{D6A42AC2-2960-4436-89AF-97FB2C39460D}.ClientEnd
Specifies the direction of energy flow in the flowgate
flowDirectionFlag
{FF6FE5B4-EE2D-4ad7-90F6-4021A1747035}
RegisteredResource
{F7D2A98A-9DDF-4461-8515-85812EF2DDD4}.ClientEnd
The interval for which the forecast is valid. For example a forecast issued now for tomorrow might be valid for the next 2 hours.
validFor
{A058F840-FDF7-42d9-A803-B4EFD6E20F40}
RegisteredResource
{6E79A630-6C5D-4ba3-86D5-0BE5A92B7A38}.ClientEnd
A fuel allocation schedule shall have a fossil fuel.
FuelAllocationSchedules
{C8620C74-1F29-40d6-AB8F-9050A6FB2AE7}.SupplierEnd
A thermal generating unit may have one or more fossil fuels.
ThermalGeneratingUnit
{2839ECA7-4BCD-4b58-8243-16046DF6DFBA}.SupplierEnd
The type of fossil fuel such as coal oil or gas.
fossilFuelType
{072D15FA-975B-445a-BEB8-8BA657B0814B}
The cost in terms of heat value for the given type of fuel.
fuelCost
{60B46C0B-BC3D-4dca-8D2A-90266147C1AA}
The cost of fuel used for economic dispatching which includes fuel cost transportation cost and incremental maintenance cost.
fuelDispatchCost
{E40606FD-C5CF-4d3c-A354-048090DAB96C}
The efficiency factor for the fuel per unit in terms of the effective energy absorbed.
fuelEffFactor
{D86EC3C3-5700-4eef-B610-F18175761B7D}
Handling and processing cost associated with this fuel.
fuelHandlingCost
{3E6E4D4B-58BB-4e20-A1BC-20009FE4767D}
Relative amount of the given type of fuel when multiple fuels are being consumed.
fuelMixture
{BF007CFE-6AB1-4639-8D2F-929145E6AA51}
The fuels fraction of pollution credit per unit of heat content.
fuelSulfur
{1DAFF39E-7664-4ddf-85DA-D342BA88A14B}
The active power output level of the unit at which the given type of fuel is switched on. This fuel e.g. oil is sometimes used to supplement the base fuel e.g. coal at high active power output levels.
highBreakpointP
{8B2493B1-E76B-42ef-BE9D-BB05890FBC30}
The active power output level of the unit at which the given type of fuel is switched off. This fuel e.g. oil is sometimes used to stabilize the base fuel e.g. coal at low active power output levels.
lowBreakpointP
{629EC404-D9B1-4bbc-8619-DEF90D6C21F9}
Off nominal frequency effect on auxiliary real power. Per unit active power variation versus per unit frequency variation.
auxPowerVersusFrequency
{5AA8792F-D4FE-49c5-8FC4-173BC334C94B}
Off nominal voltage effect on auxiliary real power. Per unit active power variation versus per unit voltage variation.
auxPowerVersusVoltage
{F61BB20D-2F93-444f-8DFB-8233EB9C8F5B}
The control mode of the boiler.
boilerControlMode
{8E2CCCAF-2DF1-4f2e-8AD3-FB3995E3EA5F}
Pressure error deadband.
controlPED
{8E342210-75CA-46d2-B4A9-5D3007C44D0D}
Feedwater time constant ratio.
feedWaterTC
{217477B3-505F-43c0-8BE9-835027B1587D}
Fuel demand limit.
fuelDemandLimit
{033739E2-3B1F-4077-AD9B-8F1E06ED4EC9}
Fuel delay.
fuelSupplyDelay
{87C42A46-7134-48f1-BCBE-2D802A25AF59}
Fuel supply time constant.
fuelSupplyTC
{0D256B64-7FC9-42aa-B744-00B089C176A1}
Mechanical power sensor lag.
mechPowerSensorLag
{EC99F758-1FC3-480d-8B5C-302FCDA76A36}
Throttle pressure setpoint.
throttlePressureSP
{0128B0B3-F0DD-4cde-8ADD-03C5CE48298D}
Frame
{EDD89720-4773-45ee-9FB3-8DFFCD2B09AA}.ClientEnd
Model frame type of the model frame.
ModelFrameType
{48C2079D-ACDD-4f43-B91E-201B0B6EEBFB}.SupplierEnd
multiplier
{72725AEC-C5F4-458b-9558-EF3378A97B34}
unit
{1400EF48-1ADD-4118-B82C-00E133BEEDD5}
Frequency on the AC side.
frequency
{051B7664-65BB-43d9-8CE0-21A90A2FB4BB}
The maximum active power on the DC side at which the frequency converter should operate.
maxP
{48B1699E-00F5-49b0-BF5D-E2ECD93C664E}
The maximum voltage on the DC side at which the frequency converter should operate.
maxU
{CA02BD7C-C525-4cef-A3FC-AC647F7ABF8B}
The minimum active power on the DC side at which the frequency converter should operate.
minP
{C6727346-BC0E-41f0-9159-C5BC431A4C8A}
The minimum voltage on the DC side at which the frequency converter should operate.
minU
{2E9BA9EF-2B21-46e0-8620-E44A01575A0D}
A fuel allocation schedule shall have a fossil fuel.
FossilFuel
{C8620C74-1F29-40d6-AB8F-9050A6FB2AE7}.ClientEnd
A thermal generating unit may have one or more fuel allocation schedules.
ThermalGeneratingUnit
{B6363E4A-4FC1-40b5-AE09-A51CCFB2B37E}.SupplierEnd
The type of fuel which also indicates the corresponding measurement unit.
fuelType
{A6B03E09-B052-4539-A181-DD2D8A8CC0DD}
RegisteredGenerator
{D73658B4-E454-4c33-84E3-F4704B76D7FD}.SupplierEnd
GasPrice
{0E1E2A5F-A268-439c-AD0C-58D72BC2233F}.ClientEnd
OilPrice
{4309159F-3756-4294-B5A1-E8863F5CEA5B}.ClientEnd
RTO
{D369B12F-39AD-45d8-B6C9-CDD43DE3458A}.ClientEnd
RegisteredGenerator
{2A9F12A2-E1BC-468f-B9A6-8FD550AE1D66}.SupplierEnd
FuelRegion
{0E1E2A5F-A268-439c-AD0C-58D72BC2233F}.SupplierEnd
Input to the gate.
GateInputPin
{0D3AAA53-9731-464c-8DA3-7F929B5C355E}.ClientEnd
PinGate
{71584FA4-43BB-4d8b-84DF-B578C3B8580C}.SupplierEnd
For the ProtectiveAction to be activated the condition for communication needs to be met true.
ProtectiveActionCom
{D34B99BA-6D10-4f96-88B9-7AD3024A8166}.ClientEnd
ProtectiveActionEnabled
{1A878962-D12D-4598-ADE4-4D8B2DDE6CA7}.ClientEnd
RemedialActionScheme
{F4AEF34E-199A-4f15-B975-FF0B28FD8751}.SupplierEnd
StageTrigger
{5AED1733-5EAF-4438-9A42-E9656E4508DA}.ClientEnd
StageTriggerArmed
{EB996EFA-4676-43b1-8D6E-DCBC54112791}.ClientEnd
StageTriggerCom
{5CBC56EA-4603-4ba3-93A1-162E6A7AC535}.ClientEnd
TriggerCondition
{1E9CF642-F79D-453e-840A-CCAA1AB4A74D}.ClientEnd
The logical operation of the gate.
kind
{9B264C0E-5D19-425e-B695-360A5EF8601D}
Gate
{0D3AAA53-9731-464c-8DA3-7F929B5C355E}.SupplierEnd
The compare operation.
aDLogicKind
{D0BB4BF2-E3B8-4a44-B804-B04F666C8E16}
The duration the compare condition need to be present before given a true. Default is 0 seconds.
duration
{5B4C1B5B-24C8-4e5f-87C8-15D5CE202B18}
The threshold percentage that should be used for compare with the percentage change between input value and threshold value.
thresholdPercentage
{8DD81831-4791-4f0e-A5EA-42C8D98D4045}
AggregatedPnode
{909A546B-EA82-4f60-8B44-1E47722DB03E}.ClientEnd
DistributionFactorSet
{A0057A86-6FBB-46b3-A9AE-B72D9CDACC6F}.ClientEnd
IndividualPnode
{1A518B75-8859-4a3f-AB51-3C3CD3B54E95}.ClientEnd
Standard synchronous machine out of which current flow is being compensated for.
SynchronousMachineDynamics
{E86FBA0E-B146-4508-95E0-F005CB0E4DF5}.SupplierEnd
The standard IEEE type 2 voltage compensator of this compensation.
VcompIEEEType2
{85A30109-1473-4ba8-A00B-DA4D28CE2463}.SupplierEnd
font color0f0f0fResistive component of compensation of generator associated with this IEEE type 2 voltage compensator for current flow out of another generator iRciji.font
rcij
{CED75700-A90E-4ca0-A51D-C6E70B233738}
font color0f0f0fReactive component of compensation of generator associated with this IEEE type 2 voltage compensator for current flow out of another generator iXciji.font
xcij
{65AD49AF-DB66-4f21-B2B1-0A8FC21708D6}
A generating unit may have one or more cost curves depending upon fuel mixture and fuel cost.
GeneratingUnit
{7B33215F-75EA-4926-9F28-841CBF3A0F5E}.SupplierEnd
A generating unit may have an operating schedule indicating the planned operation of the unit.
GeneratingUnit
{F1D837F0-09B0-4009-810F-62E6AF45ECC4}.SupplierEnd
GeneralClearingResults
{839D164D-CDF7-48fd-9700-7D80076D1DB7}.SupplierEnd
GeneralClearing
{839D164D-CDF7-48fd-9700-7D80076D1DB7}.ClientEnd
SubControlArea
{52EA9C29-FB61-4524-A03E-85E09C194BB4}.ClientEnd
Load PredictionForecast MW by Time Period 5 10 15
loadForecast
{D8FD0335-8760-41c8-8192-7F4D379C4FDD}
BidSet
{DBBF1D0E-B376-4e47-A369-EB0EB0F211C5}.SupplierEnd
NotificationTimeCurve
{9A5F74CD-56FF-45e1-8BC8-5AD82D6C11B0}.SupplierEnd
RampRateCurve
{B75E5730-E5F1-4d60-BAEF-5B89FAB09454}.SupplierEnd
RegisteredGenerator
{C4BA4125-803E-42c1-9C0B-2D5179DA8B57}.ClientEnd
SecurityConstraints
{EF812433-5985-4f7f-AEE9-C31F08021E9B}.SupplierEnd
StartUpCostCurve
{2C224C9B-54C9-40f5-8796-E455294849C7}.ClientEnd
StartUpTimeCurve
{70D9DB41-202E-44ce-B18A-F7269093B950}.ClientEnd
Maximum Dn ramp rate in MWmin
lowerRampRate
{33B8C18F-EB58-4bc5-9C5A-5EE230B92A4B}
Power rating available for unit under emergency conditions greater than or equal to maximum economic limit.
maxEmergencyMW
{3A9CB9D6-B603-436f-B3E5-4935F3E6BDCB}
Minimum power rating for unit under emergency conditions which is less than or equal to the economic minimum.
minEmergencyMW
{0D1E4459-4AB5-4836-B2F4-53B46E31E631}
Maximum Up ramp rate in MWmin
raiseRampRate
{47C13D89-9469-4f29-8FCD-12BBFFE627D8}
Resource startup ramp rate MWminute
startUpRampRate
{8ED10432-6C3F-48f0-B07B-3221E606FB01}
ControlArea specifications for this generating unit.
ControlAreaGeneratingUnit
{682C859C-B9CD-4dde-A959-EB89678BBBD6}.ClientEnd
A generating unit may have one or more cost curves depending upon fuel mixture and fuel cost.
GenUnitOpCostCurves
{7B33215F-75EA-4926-9F28-841CBF3A0F5E}.ClientEnd
A generating unit may have an operating schedule indicating the planned operation of the unit.
GenUnitOpSchedule
{F1D837F0-09B0-4009-810F-62E6AF45ECC4}.ClientEnd
A generating unit may have a gross active power to net active power curve describing the losses and auxiliary power requirements of the unit.
GrossToNetActivePowerCurves
{5A8B2A9D-6CA6-40c5-A362-38519E574F17}.ClientEnd
A synchronous machine may operate as a generator and as such becomes a member of a generating unit.
RotatingMachine
{075455B4-8BAD-4ff0-BF82-B9A27A62A8D2}.SupplierEnd
The planned unused capacity spinning reserve which can be used to support emergency load.
allocSpinResP
{1F5D4B4A-6801-4fc6-8936-04DBB4998742}
The planned unused capacity which can be used to support automatic control overruns.
autoCntrlMarginP
{6718295E-BD0D-4e85-BEB1-3E29975096DE}
For dispatchable units this value represents the economic active power basepoint for units that are not dispatchable this value represents the fixed generation value. The value shall be between the operating low and high limits.
baseP
{61BED29F-6FAD-4dd3-8E38-670E386E9752}
Unit control error deadband. When a units desired active power change is less than this deadband then no control pulses will be sent to the unit.
controlDeadband
{EEBA5F2E-D53D-4d7d-A31C-89958F27B90D}
Pulse high limit which is the largest control pulse that the unit can respond to.
controlPulseHigh
{59777C02-3FD3-4e8b-994C-9ECE05887964}
Pulse low limit which is the smallest control pulse that the unit can respond to.
controlPulseLow
{4F598483-A0C2-4430-8772-3B7E2CE57351}
Unit response rate which specifies the active power change for a control pulse of one second in the most responsive loading level of the unit.
controlResponseRate
{D33CB2D7-6634-43b7-98E0-BC00E9C47873}
The efficiency of the unit in converting mechanical energy from the prime mover into electrical energy.
efficiency
{9C05FAE6-5DC5-4e7f-AC3E-BF89EC1E5D26}
The unit control mode.
genControlMode
{26EC8389-AA1E-4af2-86B8-A5180CC6994B}
The source of controls for a generating unit. Defines the control status of the generating unit.
genControlSource
{7D2A94D5-4ACC-412f-818C-FEA312773FEC}
Governor motor position limit.
governorMPL
{B27D599B-17FC-49b9-8E5B-9C3362843FAF}
Governor Speed Changer Droop. This is the change in generator power output divided by the change in frequency normalized by the nominal power of the generator and the nominal frequency and expressed in percent and negated. A positive value of speed change droop provides additional generator output upon a drop in frequency.
governorSCD
{96994FFA-E19B-4945-A813-0EFF4E608B65}
High limit for secondary AGC control.
highControlLimit
{5170760A-4045-4543-92EC-D055F8D9F82B}
Default initial active power which is used to store a powerflow result for the initial active power for this unit in this network configuration.
initialP
{CC9FC613-AC81-4626-87D4-F4AF0ED17767}
Low limit for secondary AGC control.
lowControlLimit
{3E6466C6-E3A6-4e4d-8355-A07F9B742A65}
The normal maximum rate the generating unit active power output can be lowered by control actions.
lowerRampRate
{DF0E3A44-4CA4-46b6-AC47-5336E7F98FE4}
Maximum high economic active power limit that should not exceed the maximum operating active power limit.
maxEconomicP
{62CC5B01-6098-4901-B00D-F5455C940661}
This is the maximum operating active power limit the dispatcher can enter for this unit.
maxOperatingP
{90C37DAB-392D-4ee6-9648-9B77F316F1BD}
Maximum allowable spinning reserve. Spinning reserve will never be considered greater than this value regardless of the current operating point.
maximumAllowableSpinningReserve
{2D6E3559-8BC0-4d16-94DF-2A84AAEA3170}
Low economic active power limit that shall be greater than or equal to the minimum operating active power limit.
minEconomicP
{E2AA7DB8-B51C-4a60-87DF-84BF0CA0E294}
This is the minimum operating active power limit the dispatcher can enter for this unit.
minOperatingP
{5F668F34-E61A-467a-893F-E7E46A3BCE82}
Minimum time interval between unit shutdown and startup.
minimumOffTime
{3A5AB7E8-8785-4df2-905B-0EC62CDB55BC}
Detail level of the generator model data.
modelDetail
{181DA738-39E3-49f5-8AEB-2EF181A9CBFA}
The nominal power of the generating unit. Used to give precise meaning to percentage based attributes such as the governor speed change droop governorSCD attribute.The attribute shall be a positive value equal to or less than RotatingMachine.ratedS.
nominalP
{B11EF073-DEE6-49eb-BFCB-F354BD7764CA}
The normal maximum rate the generating unit active power output can be raised by control actions.
raiseRampRate
{74265370-26DF-4cc7-924A-E7F236BA6259}
The units gross rated maximum capacity book value.The attribute shall be a positive value.
ratedGrossMaxP
{0778CB94-7024-438a-A36A-4B8890E49C72}
The gross rated minimum generation level which the unit can safely operate at while delivering power to the transmission grid.The attribute shall be a positive value.
ratedGrossMinP
{2CB7C074-A213-4539-8C0C-954E59FD158D}
The net rated maximum capacity determined by subtracting the auxiliary power used to operate the internal plant machinery from the rated gross maximum capacity.The attribute shall be a positive value.
ratedNetMaxP
{08CAD54F-B098-4615-968F-A42A0DB56AC5}
The initial startup cost incurred for each start of the GeneratingUnit.
startupCost
{59C81DCB-E449-4f74-9832-7314FC2842A9}
Time it takes to get the unit online from the time that the prime mover mechanical power is applied.
startupTime
{7B3E6342-0BE6-47f5-BE64-25B61DFA8B3A}
The efficiency of the unit in converting the fuel into electrical energy.
totalEfficiency
{086F12C2-E050-4c15-B92A-9003226BCD9E}
The variable cost component of production per unit of ActivePower.
variableCost
{48530DFC-135F-41ec-AB43-9A8B74E49F2B}
Flowgate
{88A0B4C3-D5DA-43c8-AF9F-4CD15D7E9B66}.SupplierEnd
MktGeneratingUnit
{068663E7-88C7-413e-9ACC-BB0E7776514E}.SupplierEnd
ProvidedBy
{824933A0-9111-4506-81AD-C90C98EB9B66}.ClientEnd
Maximum real power limit.
maxP
{CEDE215E-3C0F-4ab4-A78E-B22F0D13026F}
Maximum reactive power limit.
maxQ
{0991B405-A98B-4f18-8367-998F2378C290}
Minimum real power generated.
minP
{17EA8B2A-24D3-4fff-BB41-78B155E40156}
Minimum reactive power generated.
minQ
{1AA72317-0104-4dd5-9A00-677D98C78088}
Directaxis subtransient resistance.
rDirectSubtrans
{C067DDB7-FED9-4a24-9A24-3544A27A32B6}
Directaxis synchronous resistance.
rDirectSync
{216CBBD8-2C5E-4443-B086-EF40563E4AE7}
Directaxis transient resistance.
rDirectTrans
{E0EE9B44-CAD8-4239-9309-1BF0945DB3E4}
Quadratureaxis subtransient resistance.
rQuadSubtrans
{D69BF9DD-80AC-49e6-BC8F-817DD0ADB25D}
Quadratureaxis synchronous resistance.
rQuadSync
{EA6C67B1-9E4E-4c32-B179-F88495B5D53D}
Quadratureaxis transient resistance.
rQuadTrans
{5C38980E-CFE1-4599-8B78-9AE138F14741}
Directaxis subtransient reactance.
xDirectSubtrans
{C885051F-1AC6-42be-9B19-56E9D719BC66}
Directaxis synchronous reactance.
xDirectSync
{A1006CC7-77E9-40b2-9DE5-7E242D3B92CD}
Directaxis transient reactance.
xDirectTrans
{4FE0A5E4-9832-40b3-B337-1008BF42E0F9}
Quadratureaxis subtransient reactance.
xQuadSubtrans
{2664207C-EA94-4c0f-B473-078B65D601A8}
Quadratureaxis synchronous reactance.
xQuadSync
{FCD2ED71-FFA4-4af7-A023-829D28D479FA}
Quadratureaxis transient reactance.
xQuadTrans
{6B7F7A1E-C890-4792-8E16-1763DB18707A}
PowerSystemResource
{7F56BF7C-C7AA-432b-8454-59AE37E0C7F8}.SupplierEnd
Flowgate
{DE1D7657-F706-42fa-AB0A-26D34549C4A7}.SupplierEnd
TransmissionCapacity
{384C3E51-C664-4bf5-A75C-E0697CE38B7D}.SupplierEnd
All subgeographical regions within this geographical region.
Regions
{023E20DF-DF02-4ffb-A047-E5BBDB18AB59}.SupplierEnd
Kind of geospheric analog.
kind
{E8705F4C-3A5E-47fa-85D3-E7AB9C469376}
Speed governor deadband in PU speed idbi. In the majority of applications it is recommended that this value be set to zero. Typical value 0.
db
{1F2F9638-E2C0-4ad9-A56E-17407C762BD7}
Speed sensitivity coefficient iDmi. iDmi can represent either the variation of the engine power with the shaft speed or the variation of maximum power capability with shaft speed. If it is positive it describes the falling slope of the engine speed verses power characteristic as speed increases. A slightly falling characteristic is typical for reciprocating engines and some aeroderivative turbines. If it is negative the engine power is assumed to be unaffected by the shaft speed but the maximum permissible fuel flow is taken to fall with falling shaft speed. This is characteristic of singleshaft industrial turbines due to exhaust temperature limits. Typical value 0.
dm
{71820DA6-2706-4458-88A0-20F956E13AD4}
Acceleration limiter gain iKai. Typical value 10.
ka
{DCA687A7-C276-4bc6-A92B-9480E9B0D82E}
Governor derivative gain iKdgovi. Typical value 0.
kdgov
{C0C8A3D9-B473-4e5a-894C-A4C3E33B42B9}
Governor integral gain iKigovi. Typical value 2.
kigov
{24B5987E-823E-4bd2-804A-719E059BD939}
Load limiter integral gain for PI controller iKiloadi. Typical value 067.
kiload
{975F88A9-80D8-4bc0-B275-1F4A2DAE0729}
Power controller reset gain iKimwi. The default value of 001 corresponds to a reset time of 100 s. A value of 0001 corresponds to a relatively slowacting load controller. Typical value 001.
kimw
{E5A95F4A-2C34-44de-A1AC-2B6C76EAC3B6}
Governor proportional gain iKpgovi. Typical value 10.
kpgov
{95AFE270-83FE-4893-9E66-BB171BD64952}
Load limiter proportional gain for PI controller iKploadi. Typical value 2.
kpload
{BFFC2751-105D-40b9-9516-1F5D84ED58B2}
Turbine gain iKturbi gt 0. Typical value 15.
kturb
{3001C9F9-9263-4059-9722-1CAEE3EE5598}
Load limiter reference value iLdrefi. Typical value 1.
ldref
{F71C2E67-F670-4459-903B-FC4C7A83A994}
Maximum value for speed error signal imaxerri gt GovCT1.minerr. Typical value 005.
maxerr
{19F506B9-F125-412e-9BE4-83C600F0BE1E}
Minimum value for speed error signal iminerri lt GovCT1.maxerr. Typical value 005.
minerr
{435E2931-1B95-4476-A660-E0AC517EEDDE}
Base for power values iMWbasei gt 0. Unit MW.
mwbase
{11C3B1FC-99D3-4f1f-9091-93732BDF5621}
Permanent droop iRi. Typical value 004.
r
{2A8FF93B-DBE4-4a02-983E-3957E8132B9A}
Maximum rate of load limit decrease iRdowni. Typical value 99.
rdown
{ADD1DE1E-D3B6-4e09-8459-37AEBEE092BC}
Feedback signal for droop iRselecti. Typical value electricalPower.
rselect
{62A176EF-DA19-41ee-B7DC-02C52FE22B0E}
Maximum rate of load limit increase iRupi. Typical value 99.
rup
{988EB45B-4BD2-4eca-83F5-79F3E645CAF8}
Acceleration limiter time constant iTai gt 0. Typical value 01.
ta
{EFBE3FF7-A860-41f4-8C1D-FC066E8D3ED1}
Actuator time constant iTacti gt 0. Typical value 05.
tact
{B65C3493-923E-4ac2-9811-98079D855150}
Turbine lag time constant iTbi gt 0. Typical value 05.
tb
{F56DAE19-35E3-4d26-8F54-E57BDCF213E2}
Turbine lead time constant iTci gt 0. Typical value 0.
tc
{273F4064-EFB4-4dc9-BB32-F6C316B76A4A}
Governor derivative controller time constant iTdgovi gt 0. Typical value 1.
tdgov
{AADB6002-51D6-440a-926B-8958FD04F9DC}
Transport time delay for diesel engine used in representing diesel engines where there is a small but measurable transport delay between a change in fuel flow setting and the development of torque iTengi gt 0. iTengi should be zero in all but special cases where this transport delay is of particular concern. Typical value 0.
teng
{3C48B77E-EEC9-4bb5-AE7C-8FBF40B2EA42}
Loadlimiter time constant iTfloadi gt 0. Typical value 3.
tfload
{8DDF6345-31C1-4309-AEC1-A6349D16E0CF}
Electrical power transducer time constant iTpeleci gt 0. Typical value 1.
tpelec
{D145F158-DBD0-4961-BAAF-095E1E36EAD1}
Temperature detection lead time constant iTsai gt 0. Typical value 4.
tsa
{C9A3081E-ED67-4df3-9999-64AC59151732}
Temperature detection lag time constant iTsbi gt 0. Typical value 5.
tsb
{D435F302-D53E-4833-AE46-88ABDD6A8DA0}
Maximum valve position limit iVmaxi gt GovCT1.vmin. Typical value 1.
vmax
{08DAC325-81F5-41c4-AFCE-6CBA6F705FE0}
Minimum valve position limit iVmini lt GovCT1.vmax. Typical value 015.
vmin
{053C5410-E2C4-4708-B724-23E65A8D8496}
No load fuel flow iWfnli. Typical value 02.
wfnl
{8741996D-7CF1-49f7-B0B5-D351F23F98AB}
Speed governor deadband in PU speed idbi. In the majority of applications it is recommended that this value be set to zero. Typical value 0.
db
{B1E307A2-31D8-41e5-A45C-113ACC08CCDB}
Speed sensitivity coefficient iDmi. iDmi can represent either the variation of the engine power with the shaft speed or the variation of maximum power capability with shaft speed. If it is positive it describes the falling slope of the engine speed verses power characteristic as speed increases. A slightly falling characteristic is typical for reciprocating engines and some aeroderivative turbines. If it is negative the engine power is assumed to be unaffected by the shaft speed but the maximum permissible fuel flow is taken to fall with falling shaft speed. This is characteristic of singleshaft industrial turbines due to exhaust temperature limits. Typical value 0.
dm
{6B4551A2-A769-42e7-8766-248F419EEF70}
Frequency threshold 1 iFlim1i. Unit Hz. Typical value 59.
flim1
{9EC8978A-2C3D-47c8-A2C8-690593D0CD70}
Frequency threshold 10 iFlim10i. Unit Hz. Typical value 0.
flim10
{DAB43067-9223-4ff1-BE29-D9D70D0B0597}
Frequency threshold 2 iFlim2i. Unit Hz. Typical value 0.
flim2
{E1FEB400-CC03-416e-A834-AAB59A889F5F}
Frequency threshold 3 iFlim3i. Unit Hz. Typical value 0.
flim3
{01592279-2A42-4153-9EBC-44913C81AC67}
Frequency threshold 4 iFlim4i. Unit Hz. Typical value 0.
flim4
{1D53C016-BB44-4c49-8FAD-AA936A09A713}
Frequency threshold 5 iFlim5i. Unit Hz. Typical value 0.
flim5
{7492E59F-5841-428e-B9FB-A459E80AF91A}
Frequency threshold 6 iFlim6i. Unit Hz. Typical value 0.
flim6
{80D49807-0A34-4232-9738-F1EFEBA5CE97}
Frequency threshold 7 iFlim7i. Unit Hz. Typical value 0.
flim7
{B314EA22-F268-4a9f-9EF8-47C80C4ED7EC}
Frequency threshold 8 iFlim8i. Unit Hz. Typical value 0.
flim8
{6DFBEDFF-068D-4578-82A1-57BE09AED551}
Frequency threshold 9 iFlim9i. Unit Hz. Typical value 0.
flim9
{0122E53A-E52D-499c-8C61-9977CA711C4F}
Acceleration limiter gain iKai. Typical value 10.
ka
{AD9A5421-FF79-4fa3-9955-AF2114F8D3FB}
Governor derivative gain iKdgovi. Typical value 0.
kdgov
{7D85D163-296C-4d4d-A5BF-59795E29B47D}
Governor integral gain iKigovi. Typical value 045.
kigov
{E72CBF33-4107-4ec5-8BFA-2EB4DF0F8BE8}
Load limiter integral gain for PI controller iKiloadi. Typical value 1.
kiload
{8357AAD1-E716-4487-BB97-3FDC2A770121}
Power controller reset gain iKimwi. The default value of 001 corresponds to a reset time of 100 seconds. A value of 0001 corresponds to a relatively slowacting load controller. Typical value 0.
kimw
{1536B628-C3F8-494d-970C-BA2B7741EF1F}
Governor proportional gain iKpgovi. Typical value 4.
kpgov
{4767D01C-B187-4245-A8B3-FCBDB01AB18F}
Load limiter proportional gain for PI controller iKploadi. Typical value 1.
kpload
{BC9B5A0B-9BDE-4c57-9A65-0AA92ED678E5}
Turbine gain iKturbi. Typical value 19168.
kturb
{4C092125-5E94-4d92-9ED4-62921AE1C83C}
Load limiter reference value iLdrefi. Typical value 1.
ldref
{0F8DF7C4-E603-49d7-8229-B05D5565184D}
Maximum value for speed error signal iMaxerri gt GovCT2.minerr. Typical value 1.
maxerr
{4C434ABB-DBA9-4114-B0FC-9627D66F066A}
Minimum value for speed error signal iMinerri lt GovCT2.maxerr. Typical value 1.
minerr
{BD083295-6042-4340-A3AF-04C25ED8F176}
Base for power values iMWbasei gt 0. Unit MW.
mwbase
{F051FF75-F04D-480d-9B65-AD23AE499091}
Power limit 1 iPlim1i. Typical value 08325.
plim1
{A38E7D08-E899-48f2-A79E-D25E4AB2131B}
Power limit 10 iPlim10i. Typical value 0.
plim10
{35DA60BF-1F6B-403c-BD5E-B63A9B59A3DA}
Power limit 2 Plim2. Typical value 0.
plim2
{E992D293-2BA9-455e-9A47-69DDFF4458A2}
Power limit 3 iPlim3i. Typical value 0.
plim3
{35AD4466-34EC-4571-95F6-A679262412A3}
Power limit 4 iPlim4i. Typical value 0.
plim4
{5B430703-A5E1-4e68-BE21-C3B2F40D006D}
Power limit 5 iPlim5i. Typical value 0.
plim5
{334820BF-B1E4-45af-82BC-9D1C40EB29A5}
Power limit 6 iPlim6i. Typical value 0.
plim6
{1E611B2E-9A22-4ee0-A606-CA0DE642CDF2}
Power limit 7 iPlim7i. Typical value 0.
plim7
{31352583-9FAD-40ef-BCE4-0646396BCFC6}
Power limit 8 iPlim8i. Typical value 0.
plim8
{96E8FA08-BFF0-462e-85F3-6D6AC902A505}
Power Limit 9 iPlim9i. Typical value 0.
plim9
{0031888A-ADA3-4f90-9FA3-69804C4A86F9}
Ramp rate for frequencydependent power limit iPratei. Typical value 0017.
prate
{5DD4D166-0F8C-48d2-A66E-2A1263822872}
Permanent droop iRi. Typical value 005.
r
{09C63393-129B-4dd2-984E-94D4FF8B563A}
Maximum rate of load limit decrease iRdowni. Typical value 99.
rdown
{AB9EBE18-2954-4f49-ABD2-11D68B74A973}
Feedback signal for droop iRselecti. Typical value electricalPower.
rselect
{D519C9BE-855D-4d33-892C-183D266FDA05}
Maximum rate of load limit increase iRupi. Typical value 99.
rup
{C734EE8E-AE90-404a-BC6E-B5275CE82B36}
Acceleration limiter time constant iTai gt 0. Typical value 1.
ta
{74C0E921-4534-45b6-98EF-AAE5B53E5FF3}
Actuator time constant iTacti gt 0. Typical value 04.
tact
{9AF4BDC5-93F2-455f-99F4-F9CDDC6C136C}
Turbine lag time constant iTbi gt 0. Typical value 01.
tb
{5B057734-D6FD-4698-A1C5-F969BD02EFB0}
Turbine lead time constant iTci gt 0. Typical value 0.
tc
{E5507C19-4FF6-410c-A640-19BA6441CBFF}
Governor derivative controller time constant iTdgovi gt 0. Typical value 1.
tdgov
{4267DFD1-9F8A-4dba-A530-06EDA7DC791D}
Transport time delay for diesel engine used in representing diesel engines where there is a small but measurable transport delay between a change in fuel flow setting and the development of torque iTengi gt 0. iTengi should be zero in all but special cases where this transport delay is of particular concern. Typical value 0.
teng
{25FB30F3-44F4-40e0-BBCC-AF73DADE2832}
Load limiter time constant iTfloadi gt 0. Typical value 3.
tfload
{2B6E9280-2A13-407f-9D93-4B1E045DECF5}
Electrical power transducer time constant iTpeleci gt 0. Typical value 25.
tpelec
{CAEFFCE4-FF92-4948-9850-E11E1B785BFF}
Temperature detection lead time constant iTsai gt 0. Typical value 0.
tsa
{979B4DCF-410D-45a2-B976-BC216F73B2C2}
Temperature detection lag time constant iTsbi gt 0. Typical value 50.
tsb
{1B8F3848-D518-4507-91CF-441A19EC5554}
Maximum valve position limit iVmaxi gt GovCT2.vmin. Typical value 1.
vmax
{E8441676-D766-49e6-818B-763B8DD05D90}
Minimum valve position limit iVmini lt GovCT2.vmax. Typical value 0175.
vmin
{A3779824-E52A-4a57-84DA-4B2DF5C17799}
No load fuel flow iWfnli. Typical value 0187.
wfnl
{153EDD62-68F3-4993-A1C6-88813E54B88D}
Ambient temperature load limit iLoad Limiti. Typical value 1.
at
{56FAD993-8736-4e20-B890-058FB038BC31}
Turbine damping factor iDturbi. Typical value 018.
dturb
{3EA5895C-9257-4379-8A3D-B6F997A85810}
Temperature limiter gain iKti. Typical value 3.
kt
{769624AF-9464-4126-9445-7B9E64F56A10}
Base for power values iMWbasei gt 0. Unit MW.
mwbase
{1CA3D859-BBFE-45e8-B9F8-E8DB4FA52E78}
Permanent droop iRi gt0. Typical value 004.
r
{71F37AE5-473B-4e4c-BEB6-DADE188F583F}
Governor mechanism time constant iT1i gt 0. iT1i represents the natural valve positioning time constant of the governor for small disturbances as seen when rate limiting is not in effect. Typical value 05.
t1
{AC4D3D92-6624-4861-8751-0D6C798BD44C}
Turbine power time constant iT2i gt 0. iT2i represents delay due to internal energy storage of the gas turbine engine. iT2i can be used to give a rough approximation to the delay associated with acceleration of the compressor spool of a multishaft engine or with the compressibility of gas in the plenum of a free power turbine of an aeroderivative unit for example. Typical value 05.
t2
{2828896F-6D2F-4873-8C74-0D69399F0552}
Turbine exhaust temperature time constant iT3i gt 0. Typical value 3.
t3
{2C012AF8-935F-4628-8EF8-40CA7763E8E9}
Maximum turbine power PU of MWbase iVmaxi gt GovGAST.vmin. Typical value 1.
vmax
{EFD4A194-6B9C-413a-A97E-1D4524BBB93F}
Minimum turbine power PU of MWbase iVmini lt GovGAST.vmax. Typical value 0.
vmin
{2EAF6D4A-826E-4fee-9BA1-08A0044DEB3B}
Intentional deadband width idb1i. Unit Hz. Typical value 0.
db1
{3DE6895A-EEE5-4b31-B9F8-B46965B026C7}
Unintentional deadband idb2i. Unit MW. Typical value 0.
db2
{C35915F9-E1F0-46b0-BF58-5A2A4D38D7F7}
Intentional db hysteresis iepsi. Unit Hz. Typical value 0.
eps
{DCBCC604-699C-44b9-AA14-A480603898D9}
Fuel flow at zero power output iFidlei. Typical value 018.
fidle
{71DDABC1-4D62-4087-B6B1-5E50CE4AC2A5}
Nonlinear gain point 1 PU gv iGv1i. Typical value 0.
gv1
{E06CDA93-A254-422c-8E84-E1D24AE53C96}
Nonlinear gain point 2PU gv iGv2i. Typical value 0.
gv2
{AAF2388C-B687-4e0f-943C-ED61922177EC}
Nonlinear gain point 3 PU gv iGv3i. Typical value 0.
gv3
{691F02EA-F4D5-43b1-8E52-7CB56FDF1441}
Nonlinear gain point 4 PU gv iGv4i. Typical value 0.
gv4
{9F9110FD-A2B4-4f84-9492-949875A9C7C1}
Nonlinear gain point 5 PU gv iGv5i. Typical value 0.
gv5
{F004ADAA-B76F-43c8-B1C7-3623192556DE}
Nonlinear gain point 6 PU gv iGv6i. Typical value 0.
gv6
{6123327F-ACBA-42da-A65A-86BE9A7F0B26}
Governor gain iKai. Typical value 0.
ka
{AE7517F8-0BA9-451f-B3E9-CFE01BF8785E}
Temperature limiter gain iKti. Typical value 3.
kt
{39606C19-0167-4bd5-9B4C-4AF7D94AED9C}
Ambient temperature load limit iLmaxi. iLmaxi is the turbine power output corresponding to the limiting exhaust gas temperature. Typical value 1.
lmax
{09EB2B8F-9D85-4d12-A12A-F34F85663093}
Valve position change allowed at fast rate iLoadinci. Typical value 005.
loadinc
{84B7E018-DCEE-4b68-8160-C26A1BBBD881}
Base for power values iMWbasei gt 0. Unit MW.
mwbase
{9119B06D-2FDA-475a-A446-027940C1C607}
Nonlinear gain point 1 PU power iPgv1i. Typical value 0.
pgv1
{A3ABADB7-436B-41ec-A468-B3B2D73954F3}
Nonlinear gain point 2 PU power iPgv2i. Typical value 0.
pgv2
{BA10A591-0F3A-4154-A413-D0301879FD1F}
Nonlinear gain point 3 PU power iPgv3i. Typical value 0.
pgv3
{0265C2FC-4392-4c68-9950-EEB13F703BA5}
Nonlinear gain point 4 PU power iPgv4i. Typical value 0.
pgv4
{CC11422C-C01E-4b25-A8A1-C4636539773B}
Nonlinear gain point 5 PU power iPgv5i. Typical value 0.
pgv5
{A0433ABD-6C39-4614-A77C-9C2E45DD6988}
Nonlinear gain point 6 PU power iPgv6i. Typical value 0.
pgv6
{B6886018-FC42-497a-937C-88410225FD97}
Permanent droop iRi gt0. Typical value 004.
r
{7B4E7DBF-073F-4b72-A864-77E23AAE6FF5}
Governor mechanism time constant iT1i gt 0. iT1i represents the natural valve positioning time constant of the governor for small disturbances as seen when rate limiting is not in effect. Typical value 05.
t1
{E9696364-A2B8-4f03-959D-75A993C64A5A}
Turbine power time constant iT2i gt 0. iT2i represents delay due to internal energy storage of the gas turbine engine. iT2i can be used to give a rough approximation to the delay associated with acceleration of the compressor spool of a multishaft engine or with the compressibility of gas in the plenum of the free power turbine of an aeroderivative unit for example. Typical value 05.
t2
{64540ACB-5451-44bf-8CDD-F596C4BEAC1F}
Turbine exhaust temperature time constant iT3i gt 0. iT3i represents delay in the exhaust temperature and load limiting system. Typical value 3.
t3
{5EABA132-95FD-4b43-8826-63E65FAF762D}
Governor lead time constant iT4i gt 0. Typical value 0.
t4
{D81791D7-28ED-46ce-8021-A3BA70519221}
Governor lag time constant iT5i gt 0. If 0 entire gain and leadlag block is bypassed. Typical value 0.
t5
{27AAE52A-2F86-4769-834E-813B6C64DBDB}
Valve position averaging time constant iTltri gt 0. Typical value 10.
tltr
{4ED80D64-8C8B-447f-ADA1-6F7CF120C18D}
Maximum turbine power PU of MWbase iVmaxi gt GovGAST1.vmin. Typical value 1.
vmax
{14CA128C-AC3C-4bc1-93BD-8DEA1CA13AAB}
Minimum turbine power PU of MWbase iVmini lt GovGAST1.vmax. Typical value 0.
vmin
{9A64CA9D-3112-449b-B6B4-CAFE72E1AD4D}
Exhaust temperature parameter iAf1i. Unit PU temperature. Based on temperature in degrees C.
af1
{45D1CDB3-9790-4435-B51F-958417705B7D}
Coefficient equal to 051speed iAf2i.
af2
{FE4D3144-88D8-4b0d-974C-D8A40367AAB6}
iBf1i. iBf1i iEi1 iWi where iEi speed sensitivity coefficient is 055 to 065 x iTri. Unit PU temperature. Based on temperature in degrees C.
bf1
{B92A787E-BD67-4e86-9481-88322F441A90}
Turbine torque coefficient Ksubhhvsub depends on heating value of fuel stream in combustion chamber iBf2i.
bf2
{5A58EC44-4260-407d-8A0A-65062F325410}
Coefficient defining fuel flow where power output is 0 iCf2i. Synchronous but no output. Typically 023 x Ksubhhvsub 23 fuel flow.
cf2
{189FE130-752A-47d1-A143-C0AEA8CBEC8A}
Combustion reaction time delay iEcri gt 0.
ecr
{C8CC2888-0234-4a6b-9454-E718EC9C5FCE}
Turbine and exhaust delay iEtdi gt 0.
etd
{C6549C57-903E-42a4-A5EC-AA10F1F22E5B}
Ratio of fuel adjustment iK3i.
k3
{DD0B6D8A-ECB4-42af-8B4A-26F0E6FDCB4E}
Gain of radiation shield iK4i.
k4
{B184C87E-486E-4431-95EC-A02F85A6A247}
Gain of radiation shield iK5i.
k5
{442B9151-C66C-42ba-BDE0-7078CAC6074F}
Minimum fuel flow iK6i.
k6
{9AED82B1-77AF-48cf-A9AA-46A5A7BF2AF7}
Fuel system feedback iKfi.
kf
{57CA2EAB-F0AC-4bd2-8E3C-F519267628E1}
Base for power values iMWbasei gt 0. Unit MW.
mwbase
{D51C0958-8DCB-4518-AD30-9E18CCBF805F}
Fuel control time constant iTi gt 0.
t
{7CA936B5-234A-4a03-B4A6-F6D9E40DDED4}
Radiation shield time constant iT3i gt 0.
t3
{00AE3E90-B57E-4915-8CC8-257830299FDF}
Thermocouple time constant iT4i gt 0.
t4
{F93BA02B-3C3D-430f-BF9A-B44884D13DD2}
Temperature control time constant iT5i gt 0.
t5
{69EDC641-2E10-4217-9A74-F0246EC3C354}
Temperature control iTci. Unit F or C depending on parameters iAf1i and iBf1i.
tc
{E918F440-CD04-4df9-959F-0C4280F74BA7}
Compressor discharge time constant iTcdi gt 0.
tcd
{58B8978E-E048-426d-8403-1A9CDC382868}
Fuel system time constant iTfi gt 0.
tf
{AB8C99F1-2336-4458-B1C9-9C72699E64EB}
Maximum turbine limit iTmaxi gt GovGAST2.tmin.
tmax
{457E7CFE-99B1-4f6d-A785-3592667767FA}
Minimum turbine limit iTmini lt GovGAST2.tmax.
tmin
{580E6981-A7F4-470d-8CA5-BDE825F2F07F}
Rated temperature iTri. Unit C depending on parametersi Af1 iand iBf1i.
tr
{F60CE303-14F5-466e-BB64-CDEA1639D7D7}
Turbine rating iTratei. Unit MW.
trate
{8E5D6A8E-160A-4cc9-B1D3-8AC674C631ED}
Temperature controller integration rate iTti gt 0.
tt
{90C62C8B-D05E-483e-B262-A2F00497D446}
Governor gain 1droop on turbine rating iWi.
w
{2D07300D-F950-4cf0-9119-B374421AD84E}
Governor lead time constant iXi gt 0.
x
{73139190-89B3-49a6-B40C-9B3E882BF9B5}
Governor lag time constant iYi gt 0.
y
{27A89971-0780-4400-A3FC-C3328DCD458A}
Droop ibpi. Typical value 005.
bp
{32C8F38B-3ED4-49dc-BD87-BDCF5996A1A7}
Exhaust temperature variation due to fuel flow increasing from 0 to 1 PU ideltaTci. Typical value 390.
dtc
{FF0EDAE8-A645-44a6-AF77-D1AB52E65AC6}
Minimum fuel flow iKai. Typical value 023.
ka
{01270F02-562D-43e6-A95F-89F75BF99E7B}
Fuel flow maximum negative error value iMNefi. Typical value 005.
mnef
{41DFFB06-4845-4516-B054-7CFBEAC51ACE}
Fuel flow maximum positive error value iMXefi. Typical value 005.
mxef
{A44E5F29-F284-4a40-A9D6-DCB26261646B}
Minimum fuel flow iRCMNi. Typical value 01.
rcmn
{5ABD4AC2-83A6-4521-96D2-C4564EF32AE3}
Maximum fuel flow iRCMXi. Typical value 1.
rcmx
{071DA61F-581D-4533-9AD4-DD252C7D3657}
Fuel control time constant iTaci gt 0. Typical value 01.
tac
{8E9E716B-22A1-4c7d-90B1-406E16125BF8}
Compressor discharge volume time constant iTci gt 0. Typical value 02.
tc
{EA039A7D-EA1A-4234-8C5E-C1A95873945C}
Temperature controller derivative gain iTdi gt 0. Typical value 33.
td
{306776E9-EBA0-4639-9116-DF141F89D537}
Turbine rated exhaust temperature correspondent to Pm1 PU iTfeni. Typical value 540.
tfen
{436A97FD-C667-4c3e-AFB4-58E04364EACF}
Time constant of speed governor iTgi gt 0. Typical value 005.
tg
{903247BF-FA07-4c14-8C39-8CCBBAF12668}
Time constant of radiation shield iTsii gt 0. Typical value 15.
tsi
{974011B1-12BB-41b7-86D2-0AD1CEC5A4B5}
Temperature controller integration rate iTti. Typical value 250.
tt
{DE04646B-0149-4ef5-BABC-5C6345F61444}
Time constant of thermocouple iTtci gt 0. Typical value 25.
ttc
{C9E318B6-94C6-41b6-8BA0-91C5C0FE7FB2}
Time constant of fuel valve positioner iTyi gt 0. Typical value 02.
ty
{74EE6FF5-3F88-4a6c-8A8A-347833CA98C0}
Droop ibiisubpsubi. Typical value 005.
bp
{B0042327-D84B-4f77-84C5-92D654C95F99}
Compressor gain iKtmi. Typical value 0.
ktm
{BCE95750-8510-4e52-870B-1526020B0C69}
Fuel flow maximum negative error value iMNefi. Typical value 005.
mnef
{2E39EE3B-6FF8-41e7-B5FB-4B90351E9AAF}
Fuel flow maximum positive error value iMXefi. Typical value 005.
mxef
{AF76CEFE-2152-403c-A7F0-64AB057B5575}
Minimum valve opening iRYMNi. Typical value 0.
rymn
{8346DE86-66A8-4655-970D-191A4BA7E31D}
Maximum valve opening iRYMXi. Typical value 11.
rymx
{F6F33950-4461-4023-9632-DF5F22447CD3}
Maximum gate opening velocity iTAi gt 0. Typical value 3.
ta
{08B45EBF-58BE-4521-8D83-E0B0575B901E}
Maximum gate closing velocity iTCi gt 0. Typical value 05.
tc
{E413FBF9-2B72-4503-A885-99D375AA93F0}
Fuel control time constant iTcmi gt 0. Typical value 01.
tcm
{36547794-00BE-489d-AAFA-82D56B82E48B}
Compressor discharge volume time constant iTmi gt 0. Typical value 02.
tm
{97E46F38-5DB0-4d7d-B70F-89DF57E3889F}
Time constant of fuel valve positioner iTyi gt 0. Typical value 01.
ty
{EA8EB802-82AA-4181-980B-5AB56A4A7D36}
Exhaust temperature parameter iAf1i.
af1
{BAD3FD6B-543F-439f-9916-B601A0F797C7}
Coefficient equal to 051speed iAf2i.
af2
{8F604F6A-68EC-440f-91F8-1903348F2EED}
iBf1i. iBf1i iEi1iwi where iEi speed sensitivity coefficient is 055 to 065 x iTri.
bf1
{0DE33289-2AED-4ef1-A029-0FF07549AE7B}
Turbine torque coefficient Ksubhhvsub depends on heating value of fuel stream in combustion chamber iBf2i.
bf2
{90C76F60-AA06-47bf-A995-F69246EA0A22}
Coefficient defining fuel flow where power output is 0 iCf2i. Synchronous but no output. Typically 023 x Ksubhhv sub23 fuel flow.
cf2
{9938F6C5-6F70-4a1b-8FF1-783310424DEC}
Combustion reaction time delay iEcri gt 0.
ecr
{E2649AC7-0447-4721-9286-0CD92F82CCDA}
Turbine and exhaust delay iEtdi gt 0.
etd
{2F025F5E-0E6E-46d0-993B-12FD2DAB66E5}
Ratio of fuel adjustment iK3i.
k3
{1BF22E14-F29C-4c06-BA62-F729E97EC481}
Gain of radiation shield iK4i.
k4
{062F1807-AE26-43a1-A4EB-CA47829BD673}
Gain of radiation shield iK5i.
k5
{65F461A9-A23A-45d1-AF07-6636C1A51130}
Minimum fuel flow iK6i.
k6
{25B6A870-C68F-4285-9372-FF25F758DCAE}
Drop governor gain iKdi.
kd
{3CD8EA5C-A3F3-464d-8F75-C955E8B5D411}
iKdroopi gt 0.
kdroop
{53BE233F-E597-435e-9EE8-32762D5769E2}
Fuel system feedback iKfi.
kf
{18034879-9FB3-4d8d-B4AC-B70FF2FB3DC7}
Isochronous Governor Gain iKii.
ki
{06B18E6E-3F42-45f8-B5AC-CFA014647CB1}
PID proportional gain iKpi.
kp
{DF1A90F2-14A2-4959-BD6B-91F3FDF6721C}
Base for power values iMWbasei gt 0. Unit MW.
mwbase
{AD1058DB-3580-425e-B7B4-E620AF7591E9}
Fuel control time constant iTi gt 0.
t
{4496FC4C-2076-4835-B622-0B5A8D831F1B}
Radiation shield time constant iT3i gt 0.
t3
{4F3EC56D-F128-4311-9955-FC1FD2B3109A}
Thermocouple time constant iT4i gt 0.
t4
{BF2AFDA2-E1A3-4d2a-BD38-29DE53C2B114}
Temperature control time constant iT5i gt 0.
t5
{65E05FB4-5E10-4954-AB84-0D5158770FC3}
Temperature control iTci.
tc
{8989E83E-350D-412e-ABFF-98F4620A653A}
Compressor discharge time constant iTcdi gt 0.
tcd
{7AD2404F-9868-475e-AABD-B43E58786C38}
Power transducer time constant iTdi gt 0.
td
{1794CD83-3D07-4080-8914-B555130719A7}
Fuel system time constant iTfi gt 0.
tf
{68DE0768-EB04-4763-AC7A-F51498FE937D}
Maximum Turbine limit iTmaxi gt GovGASTWD.tmin.
tmax
{A2026E04-2E46-4d23-80A9-26CB247809C0}
Minimum turbine limit iTmini lt GovGASTWD.tmax.
tmin
{A222E8D5-F51E-4667-947A-E3692AF0E7E7}
Rated temperature iTri.
tr
{B2CC37AB-1ED9-4fb3-82E1-13EB499510E7}
Turbine rating iTratei. Unit MW.
trate
{775688D9-771C-42f5-ADFB-94FBF83CC532}
Temperature controller integration rate iTti gt 0.
tt
{F80ED7EC-E304-4138-962C-26E978B77294}
Turbine gain iAti gt 0. Typical value 12.
at
{B7667ACF-A3F2-46b5-9D3E-063C9B9449E8}
Turbine damping factor iDturbi gt 0. Typical value 05.
dturb
{755F807F-32CC-441a-BC36-9ED655CCED76}
Maximum gate opening iGmaxi gt 0 and gt GovHydro.gmin. Typical value 1.
gmax
{9446DBF8-C9AF-401c-B824-104D8ABBCBD7}
Minimum gate opening iGmini gt 0 and lt GovHydro1.gmax. Typical value 0.
gmin
{10A3351A-C604-4fba-8CC0-969F1AED05FB}
Turbine nominal head ihdami. Typical value 1.
hdam
{F36E6359-6BDC-4bf8-9AE2-FFA83D3305DD}
Base for power values iMWbasei gt 0. Unit MW.
mwbase
{53C775F6-5EDB-47f7-B289-3D4CDA27036F}
Noload flow at nominal head iqnli gt 0. Typical value 008.
qnl
{E92E8ECF-2FB1-4bb7-A8FC-E72000068EFE}
Permanent droop iRi gt 0. Typical value 004.
rperm
{9BE9B3D7-3418-4731-92B2-F7C837C1D5D6}
Temporary droop iri gt GovHydro1.rperm. Typical value 03.
rtemp
{6AC646D5-1AA8-4094-82A5-8C3E51C76DC1}
Filter time constant iTfi gt 0. Typical value 005.
tf
{34CD9FC9-5BEC-4716-8C51-42A2248E4AB1}
Gate servo time constant iTgi gt 0. Typical value 05.
tg
{C2E7046C-F87E-463c-B8DC-0A1659464824}
Washout time constant iTri gt 0. Typical value 5.
tr
{8ED7DB99-BFE1-4f4d-A514-A485B51FF796}
Water inertia time constant iTwi gt 0. Typical value 1.
tw
{29D38CF8-2E1A-4871-893C-5EA177EA05B5}
Turbine numerator multiplier iAturbi. Typical value 1.
aturb
{62ED2FCB-050A-4e79-8966-FB7F2EF07CE4}
Turbine denominator multiplier iBturbi gt 0. Typical value 05.
bturb
{E3809028-3CEF-4107-B272-07CC7A261105}
Intentional deadband width idb1i. Unit Hz. Typical value 0.
db1
{97534C85-AB6A-478a-A705-11AA3D60F5DB}
Unintentional deadband idb2i. Unit MW. Typical value 0.
db2
{D73EA3B4-D639-4809-A28A-735E1C1A0A4B}
Intentional db hysteresis iepsi. Unit Hz. Typical value 0.
eps
{08085396-4033-40fd-B33E-F796827E2E4B}
Nonlinear gain point 1 PU gv iGv1i. Typical value 0.
gv1
{D3C8856D-381E-43b3-9B97-941BFB32FAD1}
Nonlinear gain point 2 PU gv iGv2i. Typical value 0.
gv2
{FEE091BA-B020-44ba-92CE-A314506CDCA2}
Nonlinear gain point 3 PU gv iGv3i. Typical value 0.
gv3
{75B8E10D-9DD0-4383-A0B5-300A0F5A3A07}
Nonlinear gain point 4 PU gv iGv4i. Typical value 0.
gv4
{31549E35-2F8C-4b9c-BFE0-1DFEE682032B}
Nonlinear gain point 5 PU gv iGv5i. Typical value 0.
gv5
{0024B25D-7AC0-46b4-B23A-4DC1FB04BE4C}
Nonlinear gain point 6 PU gv iGv6i. Typical value 0.
gv6
{A0DB7792-3596-494a-80E2-1EFAAB7FD568}
Turbine gain iKturbi. Typical value 1.
kturb
{3330DA77-7708-4432-9A6F-5EC54310927F}
Base for power values iMWbasei gt 0. Unit MW.
mwbase
{48698C3C-1FA7-460c-A379-CF2EB7D917D0}
Nonlinear gain point 1 PU power iPgv1i. Typical value 0.
pgv1
{2BAF50B1-0FA4-4674-B69A-D86F14281837}
Nonlinear gain point 2 PU power iPgv2i. Typical value 0.
pgv2
{CF48DDB5-A67F-4177-8C17-ED362029D415}
Nonlinear gain point 3 PU power iPgv3i. Typical value 0.
pgv3
{01657288-FA03-41ed-844A-83823B0E3C49}
Nonlinear gain point 4 PU power Pigv4i. Typical value 0.
pgv4
{ED6B6B42-6E64-4e26-9DC2-22EE254F24EF}
Nonlinear gain point 5 PU power iPgv5i. Typical value 0.
pgv5
{D683E5C6-B0C7-4c8c-9C06-C47A0CE0DB00}
Nonlinear gain point 6 PU power iPgv6i. Typical value 0.
pgv6
{02D61038-D9FF-4c91-BFC2-B8755C2B721D}
Maximum gate opening iPmaxi gt GovHydro2.pmin. Typical value 1.
pmax
{6666A8BF-FB6A-4bfc-B1DF-123C568D7716}
Minimum gate opening iPmini lt GovHydro2.pmax. Typical value 0.
pmin
{3D67CB36-E987-433a-AF14-4F1E28F4A135}
Permanent droop iRpermi. Typical value 005.
rperm
{83E10A7C-DA3B-4977-96C3-640BCE7FACA1}
Temporary droop iRtempi. Typical value 05.
rtemp
{39355991-8503-4302-B260-7A55BA48EA7D}
Gate servo time constant iTgi gt 0. Typical value 05.
tg
{5F198946-1F0F-4528-B747-673816A2E56B}
Pilot servo valve time constant iTpi gt 0. Typical value 003.
tp
{A2425B1F-6D60-4ed1-A7ED-9E3691D1CEC5}
Dashpot time constant iTri gt 0. Typical value 12.
tr
{C58AF2A0-34CB-455d-8B59-82DEE72271AF}
Water inertia time constant iTwi gt 0. Typical value 2.
tw
{525B78BC-5FA6-4c31-B85D-40CB3C3B620D}
Turbine gain iAti gt0. Typical value 12.
at
{078ABE56-A03D-4bf1-BC79-934A31C45EB1}
Intentional deadband width idb1i. Unit Hz. Typical value 0.
db1
{98032353-4C78-4352-BB64-03EA33BA297A}
Unintentional deadband idb2i. Unit MW. Typical value 0.
db2
{2484B0A2-1159-486e-98BC-C0BC6871B967}
Turbine damping factor iDturbi. Typical value 02.
dturb
{263A9D47-66FC-4559-A0B3-BE630F7109B4}
Intentional db hysteresis iepsi. Unit Hz. Typical value 0.
eps
{CF04C226-EE15-493b-B870-68E05326BC62}
Nonlinear gain point 1 PU gv iGv1i. Typical value 0.
gv1
{BB8E4881-00EC-4c53-91F3-8F22C088347B}
Nonlinear gain point 2 PU gv iGv2i. Typical value 0.
gv2
{48F3A651-16FB-470b-ACF8-4312FEBFC83A}
Nonlinear gain point 3 PU gv iGv3i. Typical value 0.
gv3
{E438F419-E218-4113-9DE5-5F5FC9EB950F}
Nonlinear gain point 4 PU gv iGv4i. Typical value 0.
gv4
{55A2ACE0-CBD5-4523-AEC1-95078DBC1BC7}
Nonlinear gain point 5 PU gv iGv5i. Typical value 0.
gv5
{F5FCBBB1-7B15-4a04-AB56-78F31CF394ED}
Nonlinear gain point 6 PU gv iGv6i. Typical value 0.
gv6
{99EE7DB4-67C3-4b6f-A430-D99A4F2C5B7D}
Turbine nominal head iH0i. Typical value 1.
h0
{34DB767C-6620-4e95-94E3-C3AB43E47C5E}
Derivative gain iK1i. Typical value 001.
k1
{4DAB5BC2-FE3A-495c-B64B-810989A16C14}
Double derivative gain if iCflagi 1 iK2i. Typical value 25.
k2
{6086AE56-2AC4-409a-ABF2-09DE9CFAC17C}
Gate servo gain iKgi. Typical value 2.
kg
{E8D446BB-3ECF-467c-AF0F-3F22114FB419}
Integral gain iKii. Typical value 05.
ki
{0EE19D78-66C0-432c-9A25-30591A2F9311}
Base for power values iMWbasei gt 0. Unit MW.
mwbase
{F34A20D8-56F8-45fb-9DF9-5E4D8A5AB5ED}
Nonlinear gain point 1 PU power iPgv1i. Typical value 0.
pgv1
{4CD72DD2-E947-4873-BD51-648B82313081}
Nonlinear gain point 2 PU power iPgv2i. Typical value 0.
pgv2
{26FC0D05-52EA-43b0-953C-4D9F92AA8B1B}
Nonlinear gain point 3 PU power iPgv3i. Typical value 0.
pgv3
{A6A541E5-FAE5-49d3-9473-AA62A8611DB6}
Nonlinear gain point 4 PU power iPgv4i. Typical value 0.
pgv4
{020EB4AF-98C1-4f85-B532-D243A377023A}
Nonlinear gain point 5 PU power iPgv5i. Typical value 0.
pgv5
{25B07835-84A0-4b04-8364-6DE54BA04A20}
Nonlinear gain point 6 PU power iPgv6i. Typical value 0.
pgv6
{6EAC63C1-275C-4286-90FC-7DB7C2C329CD}
Maximum gate opening PU of MWbase iPmaxi gt GovHydro3.pmin. Typical value 1.
pmax
{2A4A956F-07C7-4ab3-B635-F2EDC06CB2F0}
Minimum gate opening PU of iMWbasei iPmini lt GovHydro3.pmax. Typical value 0.
pmin
{90539CF5-62A2-45d0-B41D-CA226600D555}
Noload turbine flow at nominal head iQnli. Typical value 008.
qnl
{14A2DBDF-10AD-4295-ACB5-0151A8C82C68}
Steadystate droop PU for electrical power feedback iReleci. Typical value 005.
relec
{C1D58766-8E27-4e1d-8E7E-AE92D0E48A0E}
Steadystate droop PU for governor output feedback iRgatei. Typical value 0.
rgate
{9C264F67-E29E-42cf-A965-73C7069703C3}
Input filter time constant iTdi gt 0. Typical value 005.
td
{593E6877-BBCB-4a33-BADC-A012025A0AB6}
Washout time constant iTfi gt 0. Typical value 01.
tf
{C7DEAEDA-0761-4eb9-BEE0-45386C066B5F}
Gate servo time constant iTpi gt 0. Typical value 005.
tp
{4D992F59-3F30-4ab2-B5D7-8AD276C00A48}
Power feedback time constant iTti gt 0. Typical value 02.
tt
{C3E77CF6-BE70-4f5f-868F-3E1047EC8A63}
Water inertia time constant iTwi gt 0. If 0 block is bypassed. Typical value 1.
tw
{0ACC8A01-70B3-4b20-ADD9-64C961799471}
Turbine gain iAti. Typical value 12.
at
{8507C6F2-29F7-4a95-972A-012FA0064FF5}
Kaplan blade servo point 0 iBgv0i 0 for simple 0 for FrancisPelton. Typical value for Kaplan 0.
bgv0
{B470D9B7-3FB0-4b9a-9B85-B241C58FC596}
Kaplan blade servo point 1 iBgv1i 0 for simple 0 for FrancisPelton. Typical value for Kaplan 0.
bgv1
{F067D149-09D0-4516-B7C4-2E28C86BDA40}
Kaplan blade servo point 2 iBgv2i 0 for simple 0 for FrancisPelton. Typical value for Kaplan 01.
bgv2
{3A8C5ACC-5FC7-4448-902C-F919B366B72E}
Kaplan blade servo point 3 iBgv3i 0 for simple 0 for FrancisPelton. Typical value for Kaplan 0667.
bgv3
{1FDD0FE4-F933-4ba3-8E7D-8DDDD11152AA}
Kaplan blade servo point 4 iBgv4i 0 for simple 0 for FrancisPelton. Typical value for Kaplan 09.
bgv4
{F0301C42-6FC0-4ad2-B2E1-DCDC77E8240A}
Kaplan blade servo point 5 iBgv5i 0 for simple 0 for FrancisPelton. Typical value for Kaplan 1.
bgv5
{1593114D-AFB3-40fc-BD32-78C98035B012}
Intentional deadband width idb1i. Unit Hz. Typical value 0.
db1
{7F3A2379-5A30-4ba2-A417-57684A69C36C}
Unintentional deadband idb2i. Unit MW. Typical value 0.
db2
{E567E7BB-3D9F-4031-B786-3C6A84196ECC}
Turbine damping factor iDturbi. Unit delta P PU of iMWbasei delta speed PU. Typical value for simple 05 FrancisPelton 11 Kaplan 11.
dturb
{03E6CE59-FDB0-4ba0-A1EE-E529D6FF39E8}
Intentional db hysteresis iepsi. Unit Hz. Typical value 0.
eps
{621898DB-B575-4abf-B834-D6E1321429D0}
Maximum gate opening PU of iMWbasei iGmaxi gt GovHydro4.gmin. Typical value 1.
gmax
{80817639-2699-4b57-9E44-52E2307DE031}
Minimum gate opening PU of iMWbasei iGmini lt GovHydro4.gmax. Typical value 0.
gmin
{4E09A8F5-7A95-4acd-AA1D-21E898CACFBB}
Nonlinear gain point 0 PU gv iGv0i 0 for simple. Typical for FrancisPelton 01 Kaplan 01.
gv0
{5D8E826B-D20B-4243-9C33-891B2EA5B257}
Nonlinear gain point 1 PU gv iGv1i 0 for simple gt GovHydro4.gv0 for FrancisPelton and Kaplan. Typical value for FrancisPelton 04 Kaplan 04.
gv1
{438C9730-67B5-4d3b-BC2A-D321B66DA1B2}
Nonlinear gain point 2 PU gv iGv2i 0 for simple gt GovHydro4.gv1 for FrancisPelton and Kaplan. Typical value for FrancisPelton 05 Kaplan 05.
gv2
{730712FE-0761-486e-8533-86816BBEE72D}
Nonlinear gain point 3 PU gv iGv3i 0 for simple gt GovHydro4.gv2 for FrancisPelton and Kaplan. Typical value for FrancisPelton 07 Kaplan 07.
gv3
{AE20C7D2-84EA-4cb3-87DB-99DCDE0CF5B7}
Nonlinear gain point 4 PU gv iGv4i 0 for simple gt GovHydro4.gv3 for FrancisPelton and Kaplan. Typical value for FrancisPelton 08 Kaplan 08.
gv4
{A4D2BE8E-5554-416e-B948-00F0D78B8342}
Nonlinear gain point 5 PU gv iGv5i 0 for simple lt 1 and gt GovHydro4.gv4 for FrancisPelton and Kaplan. Typical value for FrancisPelton 09 Kaplan 09.
gv5
{EAA3C490-A3FE-4e4d-A0EA-ADE1F55B7176}
Head available at dam ihdami. Typical value 1.
hdam
{127AC479-9F31-484f-9AE7-09EE022A5210}
The kind of model being represented simple FrancisPelton or Kaplan.
model
{D17882F1-3D71-45a3-A849-0F01A91FB22E}
Base for power values iMWbasei gt 0. Unit MW.
mwbase
{F78B90E0-1062-472d-96B4-5B3A1C3A3468}
Nonlinear gain point 0 PU power iPgv0i 0 for simple. Typical value 0.
pgv0
{DF7D151D-7EB8-4050-B696-73224C1233FE}
Nonlinear gain point 1 PU power iPgv1i 0 for simple.Typical value for FrancisPelton 042 Kaplan 035.
pgv1
{6F7596D9-D3E7-4059-9FCA-8193421EA31D}
Nonlinear gain point 2 PU power iPgv2i 0 for simple.Typical value for FrancisPelton 056 Kaplan 0468.
pgv2
{0FAF88E7-45D0-4482-8DE9-81C41F115D5C}
Nonlinear gain point 3 PU power iPgv3i 0 for simple.Typical value for FrancisPelton 08 Kaplan 0796.
pgv3
{DB67820C-2709-4d28-B825-2448ED18C208}
Nonlinear gain point 4 PU power iPgv4i 0 for simple.Typical value for FrancisPelton 09 Kaplan 0917.
pgv4
{1B925978-241D-481b-8E59-161244D6FE9C}
Nonlinear gain point 5 PU power iPgv5i 0 for simple. Typical value for FrancisPelton 097 Kaplan 099.
pgv5
{1575ED37-1AA6-4a7b-A2C6-101C347450E6}
Noload flow at nominal head iQnli.Typical value for simple 008 FrancisPelton 0 Kaplan 0.
qnl
{34949B92-60D3-4fe8-AC41-CF66479AA56E}
Permanent droop iRpermi gt 0. Typical value 005.
rperm
{A173BC61-79B9-4ad0-A9C4-06183A399010}
Temporary droop iRtempi gt 0. Typical value 03.
rtemp
{17BCD83F-00A5-4731-B99F-0CD1B03A7E7F}
Blade servo time constant iTbladei gt 0. Typical value 100.
tblade
{EA5F20AA-C5FB-429a-A3CA-3EEA464D5209}
Gate servo time constant iTgi gt 0. Typical value 05.
tg
{1C5BA69C-215E-4fd2-B1C3-EB0789E70050}
Pilot servo time constant iTpi gt 0. Typical value 01.
tp
{315FE273-0A7A-4189-9DE9-750E50777BD9}
Dashpot time constant iTri gt 0. Typical value 5.
tr
{FD6AF508-00EB-4a96-8B38-93E0E89B3BF9}
Water inertia time constant iTwi gt 0. Typical value 1.
tw
{71259C52-1385-4cac-9CB4-070A6AF0EAB5}
Turbine numerator multiplier iAturbi see parameter detail 3. Typical value 1.
aturb
{742DF58E-5CEF-457f-8D8A-B691DA3E7CAB}
Turbine denominator multiplier iBturbi see parameter detail 3. Typical value 05.
bturb
{46357550-189B-4010-A68B-D8952C5CA389}
Intentional deadband width idb1i. Unit Hz. Typical value 0.
db1
{F26F2059-7050-4dc1-A947-15B1C7FDEEBD}
Unintentional deadband idb2i. Unit MW. Typical value 0.
db2
{33BAB8AB-301D-43ab-9671-69EA9B323DF9}
Intentional db hysteresis iepsi. Unit Hz. Typical value 0.
eps
{0DDABA81-FF0A-4fb0-AC55-8C7A3FCBDAB8}
Maximum gate opening iGmaxi gt GovHydroDD.gmin. Typical value 0.
gmax
{8D3A60C8-C643-4c01-A4EF-138885E431CE}
Minimum gate opening iGmini lt GovHydroDD.gmax. Typical value 0.
gmin
{0B5537D8-F08B-45d4-81B3-B07B47A897CB}
Nonlinear gain point 1 PU gv iGv1i. Typical value 0.
gv1
{A77EFA00-5ECA-4ecf-9BEE-8B1B18AB6D66}
Nonlinear gain point 2 PU gv iGv2i. Typical value 0.
gv2
{94304CDB-20CC-4eeb-BD9F-00964B4D6440}
Nonlinear gain point 3 PU gv iGv3i. Typical value 0.
gv3
{DD52A994-2B69-4d26-B80A-8F911DECB125}
Nonlinear gain point 4 PU gv iGv4i. Typical value 0.
gv4
{21CA9AC2-A119-4922-9D8C-E5CE77C8B9FF}
Nonlinear gain point 5 PU gv iGv5i. Typical value 0.
gv5
{B278D8BE-6696-4d77-948D-A967B79EFBE0}
Nonlinear gain point 6 PU gv iGv6i. Typical value 0.
gv6
{18868044-EF4E-409f-81F5-AC745D4C22EB}
Single derivative gain iK1i. Typical value 36.
k1
{E90A046D-F554-41ab-988B-09312E35C984}
Double derivative gain iK2i. Typical value 02.
k2
{A25A162A-B728-4973-9735-F60DD78BE066}
Gate servo gain iKgi. Typical value 3.
kg
{A717271A-3A89-48c6-9AD1-FB8F0783FDE1}
Integral gain iKii. Typical value 1.
ki
{3F379118-5D8F-409b-B107-F0C1AA48405E}
Base for power values iMWbasei gt0. Unit MW.
mwbase
{7E84DB32-5477-4292-9EF5-D79F373AD29E}
Nonlinear gain point 1 PU power iPgv1i. Typical value 0.
pgv1
{FA1D0554-6159-46b2-9A1E-4E93F30FA875}
Nonlinear gain point 2 PU power iPgv2i. Typical value 0.
pgv2
{3E4BC076-FED6-4724-B7F1-423DC0E8DB19}
Nonlinear gain point 3 PU power iPgv3i. Typical value 0.
pgv3
{B304A009-0CBF-473d-B841-B32FAD1BFAB3}
Nonlinear gain point 4 PU power iPgv4i. Typical value 0.
pgv4
{F3C92CFE-570F-4f77-9DE9-F1DBEB5E7591}
Nonlinear gain point 5 PU power iPgv5i. Typical value 0.
pgv5
{F14B6E86-74F3-4a76-8AD1-DF22F5D180BD}
Nonlinear gain point 6 PU power iPgv6i. Typical value 0.
pgv6
{16FC5B3B-E320-4595-BD7F-AD1B13A10912}
Maximum gate opening PU of iMWbasei iPmaxi gt GovHydroDD.pmin. Typical value 1.
pmax
{28C0FE72-4D95-43b5-96A5-54E4F950542A}
Minimum gate opening PU of iMWbasei iPmini gt GovHydroDD.pmax. Typical value 0.
pmin
{21E787D0-EE26-4c1e-A519-45645C9BD889}
Steady state droop iRi. Typical value 005.
r
{53DB3212-BC20-4539-95BB-092E8C6F7C2B}
Input filter time constant iTdi gt 0. If 0 block is bypassed. Typical value 0.
td
{6931EDFA-1F35-40c3-8B19-CBEA6B8691EF}
Washout time constant iTfi gt 0. Typical value 01.
tf
{39290CE3-6480-4280-9FDF-F64C23288B3E}
Gate servo time constant iTpi gt 0. If 0 block is bypassed. Typical value 035.
tp
{2F0EF951-62E3-46c3-99CA-7925DB7307ED}
Power feedback time constant iTti gt 0. If 0 block is bypassed. Typical value 002.
tt
{4438E251-2C80-4882-BABC-4EBB5E12EF6D}
Turbine time constant iTturbi gt 0. See parameter detail 3. Typical value 08.
tturb
{6181F368-C827-45bf-8116-53E23B813EBA}
Opening section iSiisubEFFsubi at the maximum efficiency iAmi. Typical value 07.
am
{CDD58297-5216-4d32-8F40-434C6C439295}
Area of the surge tank iAiisubV0subi. Unit msup2sup. Typical value 30.
av0
{A33B7E93-CC68-4ffe-830D-AD91C896CFFA}
Area of the compensation tank iAiisubV1subi. Unit msup2sup. Typical value 700.
av1
{63098FB2-5381-4f82-A5B0-81F4E75AABE9}
Droop iBpi. Typical value 005.
bp
{6C2F9039-A507-40f6-9F93-6B4CB4A9433D}
Intentional deadband width iDB1i. Unit Hz. Typical value 0.
db1
{67AF015D-266C-4842-8997-B56495A6C12D}
Maximum efficiency iEtaMaxi. Typical value 105.
etamax
{8C502ADB-F1C2-4f24-832A-16000AE62DF4}
Governor control flag iCflagi. Typical value mechanicHydrolicTachoAccelerator.
governorControl
{82B8D404-5ADD-480e-B503-D4243F4A57BB}
Head of compensation chamber water level with respect to the level of penstock iHiisub1subi. Unit km. Typical value 0004.
h1
{5BCFE1A1-41AD-47ca-A0C0-B0805A74F7D0}
Head of surge tank water level with respect to the level of penstock iHiisub2subi. Unit km. Typical value 0040.
h2
{36C26250-BA01-4bf6-BF80-3A4A7A4EADAE}
Rated hydraulic head iHiisubnsubi. Unit km. Typical value 0250.
hn
{A44E4508-5DD9-4c7a-B30E-E4890B44DEE5}
Penstock loss coefficient due to friction iKci. Typical value 0025.
kc
{B0194F3B-D136-41e8-B56A-B489613A4E01}
Water tunnel and surge chamber loss coefficient due to friction iKgi. Typical value 0025.
kg
{1CA60ACA-C1ED-4da4-A3CB-D985FC2FFE74}
Washout gain iKti. Typical value 025.
kt
{7EBD2E09-1B36-40f1-AD52-6B315E477B7D}
Noload turbine flow at nominal head iQc0i. Typical value 01.
qc0
{FF1F840D-A377-461b-89EE-B4E0A17A8B03}
Rated flow iQiisubnsubi. Unit msup3sups. Typical value 250.
qn
{9160A05A-A4F0-45ef-B8B0-877061CD1AE9}
Derivative gain iTai gt 0. Typical value 3.
ta
{2BE28249-109B-4376-A07D-48989E4EA2FD}
Washout time constant iTdi gt 0. Typical value 6.
td
{2DD22B3C-E4D8-456a-B433-D56A697F5CB3}
Gate servo time constant iTsi gt 0. Typical value 05.
ts
{BC545CFB-AE7F-4330-A4A0-65C804071946}
Water inertia time constant iTwnci gt 0. Typical value 1.
twnc
{AC7A1124-2F84-458f-B6FC-F6A1B68E550F}
Water tunnel and surge chamber inertia time constant iTwngi gt 0. Typical value 3.
twng
{14A49FBB-F163-4e82-8659-29483CCA0670}
Derivative feedback gain iTxi gt 0. Typical value 1.
tx
{54E7ABD7-762E-4fcf-AF24-D70C1CD37C2F}
Maximum gate opening iValvMaxi gt GovHydroFrancis.valvmin. Typical value 11.
valvmax
{AC4668F4-C3F4-4894-B6FD-49833BBB1E64}
Minimum gate opening iValvMini lt GovHydroFrancis.valvmax. Typical value 0.
valvmin
{7CF42B23-33C4-4b7b-AACA-D4E41B4EBC3B}
Head of upper water level with respect to the level of penstock iZsfci. Unit km. Typical value 0025.
zsfc
{F6047EA4-365D-4b6d-A4B1-DFA864AAA713}
Governor gain iKi.
k
{0C98F22E-4C87-4e9d-A331-D9CECC2076D8}
Base for power values iMWbasei gt 0. Unit MW.
mwbase
{EABE1337-3C6D-4bda-AE52-4BE263C548F0}
Gate maximum iPmaxi gt GovHydroIEEE0.pmin.
pmax
{BDD1A88C-93DB-4e7f-A4E0-8A19338333B9}
Gate minimum iPmini lt GovHydroIEEE.pmax.
pmin
{B67D4FAF-C46E-4fb6-B956-F1348378BD1C}
Governor lag time constant iT1i gt 0. Typical value 025.
t1
{C2EE48B3-FE0E-4677-9F12-728C2CCEB38A}
Governor lead time constant iT2i gt 0. Typical value 0.
t2
{521A3E0D-2616-4433-BE64-913378974122}
Gate actuator time constant iT3i gt 0. Typical value 01.
t3
{64474B0C-A6DC-458d-B808-2E08FE207EF7}
Water starting time iT4i gt 0.
t4
{ECAE8F95-0A47-4454-BECF-D6E41D67E305}
Turbine numerator multiplier iAturbi. Typical value 1.
aturb
{16160504-A508-40d7-BCCE-CE33FC6E2B56}
Turbine denominator multiplier iBturbi gt 0. Typical value 05.
bturb
{D752432F-BBE9-4780-B0A2-A995EFFEB72D}
Nonlinear gain point 1 PU gv iGv1i. Typical value 0.
gv1
{F63CD920-C121-496e-88BA-CA5AC02192B4}
Nonlinear gain point 2 PU gv iGv2i. Typical value 0.
gv2
{4FBEA10C-88E1-4c59-97A5-9BADCC30B096}
Nonlinear gain point 3 PU gv iGv3i. Typical value 0.
gv3
{1866D0CA-87CE-48af-ACAD-3CA491A175C3}
Nonlinear gain point 4 PU gv iGv4i. Typical value 0.
gv4
{61F3F8D7-3C7C-4a3d-8458-6C6011EDFF2C}
Nonlinear gain point 5 PU gv iGv5i. Typical value 0.
gv5
{2390C7A9-A7D2-476f-9C9F-0AD28541B21C}
Nonlinear gain point 6 PU gv iGv6i. Typical value 0.
gv6
{D4FF4666-5B17-439c-954E-EDDD294CDA46}
Turbine gain iKturbi. Typical value 1.
kturb
{77B93020-3F48-4c9e-A774-D6BFE6AFCCAC}
Base for power values iMWbasei gt 0. Unit MW.
mwbase
{44C5C73C-0AB4-40f1-9F7A-FE5302C723C2}
Nonlinear gain point 1 PU power iPgv1i. Typical value 0.
pgv1
{E7E87A7F-DC7E-4f38-B8F3-3375D35257FC}
Nonlinear gain point 2 PU power iPgv2i. Typical value 0.
pgv2
{17C6FF41-FFA8-407b-8814-9E5CDCB3E1BE}
Nonlinear gain point 3 PU power iPgv3i. Typical value 0.
pgv3
{91B3B43A-1177-408a-9D6C-C634DEF5EAF6}
Nonlinear gain point 4 PU power iPgv4i. Typical value 0.
pgv4
{882EC2DD-001A-420e-8391-8367277AC3F8}
Nonlinear gain point 5 PU power iPgv5i. Typical value 0.
pgv5
{639267D9-A5BA-472c-A36D-3EF97AAC2613}
Nonlinear gain point 6 PU power iPgv6i. Typical value 0.
pgv6
{D5A833C3-F4B9-4573-9381-DC03E502FBD4}
Maximum gate opening iPmaxi gt GovHydroIEEE2.pmin. Typical value 1.
pmax
{D1CAFBCA-9330-4839-91DF-AFDB88017678}
Minimum gate opening iPmini ltGovHydroIEEE2.pmax. Typical value 0.
pmin
{E25A4956-E306-410f-BA73-6F15ADECB877}
Permanent droop iRpermi. Typical value 005.
rperm
{81F58BDC-9674-48ae-B0FE-E350F658E7DB}
Temporary droop iRtempi. Typical value 05.
rtemp
{2D6BBE42-78AB-421d-A47B-C57247CEC49C}
Gate servo time constant iTgi gt 0. Typical value 05.
tg
{14DED583-6BF8-4ee5-862E-A9A487DC2DBB}
Pilot servo valve time constant iTpi gt 0. Typical value 003.
tp
{60E17F40-2444-4aca-B5B2-AF400E1FE8D6}
Dashpot time constant iTri gt 0. Typical value 12.
tr
{9131D573-1974-476e-A568-3A7B10BD5282}
Water inertia time constant iTwi gt 0. Typical value 2.
tw
{BAACA66F-EFFE-4fcf-A4D7-17B12CC36D36}
Turbine numerator multiplier iAturbi see parameter detail 3. Typical value 1.
aturb
{A615AF4E-FEC4-4a58-BEB9-367C21380B9C}
Turbine denominator multiplier iBturbi see parameter detail 3. Typical value 05.
bturb
{305E0037-79D2-4072-8B33-417B7A9AE85F}
Intentional deadband width idb1i. Unit Hz. Typical value 0.
db1
{F5D3F30B-B09A-42df-ACD9-FA51C40401CB}
Unintentional deadband idb2i. Unit MW. Typical value 0.
db2
{1E661077-4598-47c6-95F1-F4F51E2A9BEC}
Intentional db hysteresis iepsi. Unit Hz. Typical value 0.
eps
{394D8886-5129-4cc2-BCBB-BED57E4A46E4}
Nonlinear gain point 1 PU gv iGv1i. Typical value 0.
gv1
{48F144E3-D53C-4900-9D4D-8E8386AFEC20}
Nonlinear gain point 2 PU gv iGv2i. Typical value 0.
gv2
{64D7C701-4121-44e8-BF5D-7A8A3ADD56E8}
Nonlinear gain point 3 PU gv iGv3i. Typical value 0.
gv3
{488E2C53-75C6-485a-AE23-3BABD359FF75}
Nonlinear gain point 4 PU gv iGv4i. Typical value 0.
gv4
{DCD778C1-9395-43da-BD58-6AC7248F844D}
Nonlinear gain point 5 PU gv iGv5i. Typical value 0.
gv5
{46E280BF-A3F2-44db-8266-004297A7DC73}
Nonlinear gain point 6 PU gv iGv6i. Typical value 0.
gv6
{B7C4539F-EEC2-4d51-BF1D-DD5B70F3D3BE}
Derivative gain iKdi. Typical value 111.
kd
{0AC54FA8-2D92-4c63-8C5B-B6A836772EB1}
Gate servo gain iKgi. Typical value 25.
kg
{B8ACA60C-1A2E-4641-A01B-24B3071DE0CE}
Integral gain iKii. Typical value 036.
ki
{35EA3654-61F8-4201-93CD-BBE3BEBE91B2}
Proportional gain iKpi. Typical value 01.
kp
{41C75A1B-D28D-47eb-8ED1-6C43683F7DAD}
Base for power values iMWbasei gt 0. Unit MW.
mwbase
{2BDA3F51-E500-4d92-8B9A-748E56A96008}
Nonlinear gain point 1 PU power iPgv1i. Typical value 0.
pgv1
{F591C394-5348-44d8-9E9D-B3B104849B33}
Nonlinear gain point 2 PU power iPgv2i. Typical value 0.
pgv2
{C0270DB3-14BF-4e8c-A100-4086CDBA6A83}
Nonlinear gain point 3 PU power iPgv3i. Typical value 0.
pgv3
{7D9B3CAA-B416-4707-856C-8DD047D57B0B}
Nonlinear gain point 4 PU power iPgv4i. Typical value 0.
pgv4
{28FC71C1-927E-49d4-B408-2100A121BF9A}
Nonlinear gain point 5 PU power iPgv5i. Typical value 0.
pgv5
{5B0277C1-F92A-46f9-9CAD-90CBF4D1E2F8}
Nonlinear gain point 6 PU power iPgv6i. Typical value 0.
pgv6
{A2B3EAAE-FFBB-4144-B9C6-64EBC1342BBE}
Maximum gate opening PU of MWbase iPmaxi gt GovHydroPID.pmin. Typical value 1.
pmax
{602962F1-A2C4-40fa-9C42-F99638B56C35}
Minimum gate opening PU of MWbase iPmini lt GovHydroPID.pmax. Typical value 0.
pmin
{0900038F-AFCE-4fb5-9370-D2E3976C9658}
Steady state droop iRi. Typical value 005.
r
{FCDC9A31-F6F3-4656-BD40-07900815888B}
Input filter time constant iTdi gt 0. If 0 block is bypassed. Typical value 0.
td
{33B4696B-D0BA-4288-B534-368A8602E155}
Washout time constant iTfi gt 0. Typical value 01.
tf
{0F5FFB1C-F808-436f-868D-C93C0AFAC4BB}
Gate servo time constant iTpi gt 0. If 0 block is bypassed. Typical value 035.
tp
{6734CBC0-118E-40b9-8173-6C1BD5293EE2}
Power feedback time constant iTti gt 0. If 0 block is bypassed. Typical value 002.
tt
{F5150390-6D98-442e-A271-A9E9EDA3D44F}
Turbine time constant iTturbi gt 0. See Parameter detail 3. Typical value 08.
tturb
{902C49B0-A17E-4a16-983B-8F50B2ED7E71}
Factor multiplying iTwi iAtwi. Typical value 0.
atw
{E85C5E35-5F88-47cd-B421-D55156046A44}
Turbine damping factor iDi. Unit delta P delta speed. Typical value 0.
d
{8F5B12F0-DEC8-4710-9C4A-CF32A668224D}
Gate opening at speed no load iG0i. Typical value 0.
g0
{DFA88B53-923A-4701-ABA6-98DE8AFFA96E}
Intermediate gate opening iG1i. Typical value 0.
g1
{C74498BC-04F0-4a98-B178-D5C3316816F6}
Intermediate gate opening iG2i. Typical value 0.
g2
{9D4C505D-0E6A-4417-8896-80C6AC6DE8E6}
Maximum gate opening iGmaxi gt GovHydroPID2.gmin. Typical value 0.
gmax
{25FCEB84-D6FA-4e50-8F78-3E4C087DA2CE}
Minimum gate opening iGmini gt GovHydroPID2.gmax. Typical value 0.
gmin
{C638F1C1-57F1-498a-91CE-56CAA8F479A9}
Derivative gain iKdi. Typical value 0.
kd
{EDDDE006-3AD1-47e5-B855-4E8D842C79B7}
Proportional gain iKpi. Typical value 0.
kp
{A5C16343-07B0-41eb-A707-D9A504DF8D12}
Base for power values iMWbasei gt0. Unit MW.
mwbase
{FE7F559C-B2D0-465d-BFD6-769F3E0211C3}
Power at gate opening iG1i iP1i. Typical value 0.
p1
{042F3249-6DDD-45ef-AE9E-980A4491DB56}
Power at gate opening G2 iP2i. Typical value 0.
p2
{96879763-74D4-4de8-813A-78255403DD56}
Power at full opened gate iP3i. Typical value 0.
p3
{959FD35A-DCDD-41d6-885C-5EAC52C46A62}
Permanent drop iRpermi. Typical value 0.
rperm
{EBE6A524-8A1B-41cd-863B-BC88F43CBFBE}
Controller time constant iTai gt 0. Typical value 0.
ta
{61632889-472A-4ef6-B2FA-D8EE7244B7BB}
Gate servo time constant iTbi gt 0.
tb
{096EFB3F-52B3-4058-B977-C9219A5853E7}
Speed detector time constant iTregi gt 0. Typical value 0.
treg
{9FEF6BAE-D400-4cce-898B-DDDF520CC671}
Water inertia time constant iTwi gt 0. Typical value 0.
tw
{956D8A87-4895-4242-BB57-ABAB839FBAC7}
Area of the surge tank iAiisubV0subi. Unit msup2sup. Typical value 30.
av0
{2F20AFE2-FBC0-44ce-BF77-D998719D17A2}
Area of the compensation tank iAiisubV1subi. Unit msup2sup. Typical value 700.
av1
{2D371EC1-51E6-404c-BEC1-77A780F72510}
Droop ibpi. Typical value 005.
bp
{DD70C425-193B-4f92-B028-A12AFB7DB27C}
Intentional deadband width iDB1i. Unit Hz. Typical value 0.
db1
{B7E183DE-8BDE-45d4-8A25-8494AAE0A455}
Intentional deadband width of valve opening error iDB2i. Unit Hz. Typical value 001.
db2
{B66E1AF1-69FC-40a0-88E2-74688EE03FB8}
Head of compensation chamber water level with respect to the level of penstock iHiisub1subi. Unit km. Typical value 0004.
h1
{A377687D-8B26-4763-8A47-711E82F90682}
Head of surge tank water level with respect to the level of penstock iHiisub2subi. Unit km. Typical value 0040.
h2
{1627FCC3-0850-498b-B4AC-CF9964A6E502}
Rated hydraulic head iHiisubnsubi. Unit km. Typical value 0250.
hn
{4498B638-C25C-4ec1-9DD9-2CBBB5018AEB}
Penstock loss coefficient due to friction iKci. Typical value 0025.
kc
{77E94867-E358-4e63-A3D6-579D12956FF4}
Water tunnel and surge chamber loss coefficient due to friction iKgi. Typical value 0025.
kg
{87732474-836A-4593-845F-A57C2C4634F9}
Noload turbine flow at nominal head iQc0i. Typical value 005.
qc0
{1C546174-B511-4831-A680-3BE4BA42D308}
Rated flow iQiisubnsubi. Unit msup3sups. Typical value 250.
qn
{DF90C1F5-CD28-44f8-B2D6-6FBD043F2D52}
Derivative gain accelerometer time constant iTai gt 0. Typical value 3.
ta
{970E95EF-72A9-4773-8802-184E8FD45A6C}
Gate servo time constant iTsi gt 0. Typical value 015.
ts
{7A57AC08-D35A-4875-8430-185F56385CB1}
Servomotor integrator time constant iTvi gt 0. Typical value 03.
tv
{F9C3A679-8AE8-4b2b-9152-0D884937D745}
Water inertia time constant iTwnci gt 0. Typical value 1.
twnc
{728E5D63-2341-43e2-A646-CDB5BF1A2A3A}
Water tunnel and surge chamber inertia time constant iTwngi gt 0. Typical value 3.
twng
{878D05D6-AB48-440c-AEB6-6975519E07B6}
Electronic integrator time constant iTxi gt 0. Typical value 05.
tx
{99714F28-2A9D-425f-B569-9FB01313B3EC}
Maximum gate opening iValvMaxi gt GovHydroPelton.valvmin. Typical value 11.
valvmax
{A481FBBF-800B-425e-A3BA-39A68696209D}
Minimum gate opening iValvMini lt GovHydroPelton.valvmax. Typical value 0.
valvmin
{1DBDEB21-7152-40fe-A850-1A7498C1C310}
Maximum servomotor valve opening velocity iVavi. Typical value 01.
vav
{CE8C0735-87A8-49f1-A5BF-9E6AE80E68D0}
Maximum servomotor valve closing velocity iVcvi. Typical value 01.
vcv
{B923AB16-1662-49b2-BB20-155B839F7470}
Head of upper water level with respect to the level of penstock iZsfci. Unit km. Typical value 0025.
zsfc
{1B29880E-20FC-4d30-A1D0-92C67AC5A6F1}
Turbine gain iAti. Typical value 12.
at
{0E9985D1-534B-448c-9C1B-228630BF4E38}
Intentional deadband width idb1i. Unit Hz. Typical value 0.
db1
{5FB28864-B480-4761-AC5C-FC9105551A8B}
Unintentional deadband idb2i. Unit MW. Typical value 0.
db2
{EB1E0DD7-BE69-4319-BAB7-ED823A27FBB9}
Turbine damping factor iDturbi. Typical value 02.
dturb
{8266D47E-6B2C-44e2-826E-32FFFC21F734}
Intentional db hysteresis iepsi. Unit Hz. Typical value 0.
eps
{37046D34-6DEB-465a-B139-1F3E1D076C03}
Maximum governor output iGmaxi gt GovHydroR.gmin. Typical value 105.
gmax
{8A41CBC0-AB0D-4961-8EB4-6AEDEA80A556}
Minimum governor output iGmini lt GovHydroR.gmax. Typical value 005.
gmin
{E4D1B26B-5928-4058-BC8C-8199EECEB47C}
Nonlinear gain point 1 PU gv iGv1i. Typical value 0.
gv1
{4E2CE730-28E8-4b84-925D-0EAA28888ABA}
Nonlinear gain point 2 PU gv iGv2i. Typical value 0.
gv2
{F8D4C82E-C4C2-4c69-B4D7-88ED67A1A0C8}
Nonlinear gain point 3 PU gv iGv3i. Typical value 0.
gv3
{1E2A1AB1-0794-4334-85D5-925352C72E8D}
Nonlinear gain point 4 PU gv iGv4i. Typical value 0.
gv4
{CEDE59C7-AE9A-4cae-9138-B949B9785CC1}
Nonlinear gain point 5 PU gv iGv5i. Typical value 0.
gv5
{B5576BF4-D9F9-43ef-85A7-F34F76DFDAE5}
Nonlinear gain point 6 PU gv iGv6i. Typical value 0.
gv6
{75DD60CD-B8BC-419d-9FE1-994C381FB28D}
Turbine nominal head iH0i. Typical value 1.
h0
{4F45C6E9-616B-4743-9B0C-6876D1E9F82D}
Gate servo gain iKgi. Typical value 2.
kg
{580CB40B-63C6-4887-AA8C-C85CF002C194}
Integral gain iKii. Typical value 05.
ki
{162371C6-8C21-42a3-845E-FD4A170CDBC5}
Base for power values iMWbasei gt 0. Unit MW.
mwbase
{0A892D73-D119-44a0-A803-A2698869527F}
Nonlinear gain point 1 PU power iPgv1i. Typical value 0.
pgv1
{E0545B0A-0FFD-4453-AED2-F64A92ECD272}
Nonlinear gain point 2 PU power iPgv2i. Typical value 0.
pgv2
{E00557F7-4AB0-42fb-8B50-C8E017DA8B46}
Nonlinear gain point 3 PU power iPgv3i. Typical value 0.
pgv3
{1CAFBC3B-07BB-4a4f-B9E4-8926A95DBC6D}
Nonlinear gain point 4 PU power iPgv4i. Typical value 0.
pgv4
{FDCC0FA8-54CB-4924-AA3F-179BFEF59DD8}
Nonlinear gain point 5 PU power iPgv5i. Typical value 0.
pgv5
{66504A0A-EA8F-4324-96E1-1F2C12D9C010}
Nonlinear gain point 6 PU power iPgv6i. Typical value 0.
pgv6
{B90932E3-AFF8-493f-991E-F1843C925C02}
Maximum gate opening PU of iMWbasei iPmaxi gt GovHydroR.pmin. Typical value 1.
pmax
{8EC63699-2FE3-4266-B523-56C94559CE05}
Minimum gate opening PU of iMWbasei iPmini lt GovHydroR.pmax. Typical value 0.
pmin
{9617CE68-08F4-4c9e-8FE8-9B3A5AA4CE1E}
Noload turbine flow at nominal head iQnli. Typical value 008.
qnl
{0272C6F1-EC6B-416a-BF08-319565D9844A}
Steadystate droop iRi. Typical value 005.
r
{B5F21912-8537-4442-9EA7-C45B72A466ED}
Lead time constant 1 iT1i gt 0. Typical value 15.
t1
{9E7F522B-AD1A-49e8-AF96-7B6CDEB6E3E4}
Lag time constant 1 iT2i gt 0. Typical value 01.
t2
{38922249-DA0A-473a-BA63-60D8D49B580B}
Lead time constant 2 iT3i gt 0. Typical value 15.
t3
{0AC56C2D-5D7C-40b3-A6AB-18A3E91F63A0}
Lag time constant 2 iT4i gt 0. Typical value 01.
t4
{5077F2AE-4AFE-4ec7-B463-3C14542202C6}
Lead time constant 3 iT5i gt 0. Typical value 0.
t5
{F1288D02-630F-4075-BB67-2A353A304804}
Lag time constant 3 iT6i gt 0. Typical value 005.
t6
{6C4CC16E-11B3-499c-9504-26A87FB0B215}
Lead time constant 4 iT7i gt 0. Typical value 0.
t7
{15E0C07D-885D-4f51-BC05-46726D2D381E}
Lag time constant 4 iT8i gt 0. Typical value 005.
t8
{7E2B8BB3-7911-4d47-BB71-AF4739C2C031}
Input filter time constant iTdi gt 0. Typical value 005.
td
{9E4B88B2-2284-4cc5-8CBD-9B5C54C29FD9}
Gate servo time constant iTpi gt 0. Typical value 005.
tp
{C55C485A-F0CA-4d21-AE5A-13C6F3FB8B43}
Power feedback time constant iTti gt 0. Typical value 0.
tt
{5631C3CD-114F-4950-99F2-131BD87E6268}
Water inertia time constant iTwi gt 0. Typical value 1.
tw
{363D660D-331E-4ba8-9E6F-7D8D3D809F3E}
Speed deadband idbi.
db
{849E983B-D5DE-4f0b-A7F5-DC3C8B94A1FE}
Value to allow the integral controller to advance beyond the gate limits iDicni.
dicn
{AE31A0FF-07F7-4afd-ACDA-0F43B55FCF4F}
Value to allow the pilot valve controller to advance beyond the gate limits iDpvi.
dpv
{45C9B199-CD8D-4406-9EBE-BAF277E4A5BD}
Turbine damping factor iDturbi. Unit delta P PU of iMWbasei delta speed PU.
dturb
{3D1FD0CB-274D-4ac7-8C02-74871B687668}
Flowgate 1 iFl1i. Flow value for gate position point 1 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
fl1
{9BDB8DCC-58BC-4c29-BF70-AF981D0B0F8A}
Flowgate 2 iFl2i. Flow value for gate position point 2 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
fl2
{C992A913-F55B-4dc0-BEE9-53A854BFB9B2}
Flowgate 3 iFl3i. Flow value for gate position point 3 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
fl3
{109E4766-868D-45bd-AD37-6AF5D1EBA46C}
Flowgate 4 iFl4i. Flow value for gate position point 4 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
fl4
{7EBDECEA-6D5F-4a64-9066-3B1FA5665F3E}
Flowgate 5 iFl5i. Flow value for gate position point 5 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
fl5
{5760844D-73C0-4a88-8CA1-00E51F83F368}
Flow P1 iFp1i. Turbine flow value for point 1 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
fp1
{1916E846-ED5F-4813-BA63-8C3EFDFE76B5}
Flow P10 iFp10i. Turbine flow value for point 10 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
fp10
{4EA2E0CD-8F91-4aac-BECF-170592984B28}
Flow P2 iFp2i. Turbine flow value for point 2 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
fp2
{7E25342F-C381-4549-8E29-7298D378987F}
Flow P3 iFp3i. Turbine flow value for point 3 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
fp3
{78D35C8A-4CE5-4c92-A35D-AB0CFB535856}
Flow P4 iFp4i. Turbine flow value for point 4 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
fp4
{21066FBB-3F5E-492c-86D7-A9046294A620}
Flow P5 iFp5i. Turbine flow value for point 5 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
fp5
{7DED80F8-F034-49c5-8687-FC3838D5885E}
Flow P6 iFp6i. Turbine flow value for point 6 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
fp6
{344C9FCA-23FE-4e7f-A035-07A5CD93B8DA}
Flow P7 iFp7i. Turbine flow value for point 7 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
fp7
{B99854AF-E5A3-41a0-91F0-1EDE86523725}
Flow P8 iFp8i. Turbine flow value for point 8 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
fp8
{2B40A8AB-32F3-41b5-A657-FDBDAB8A14E3}
Flow P9 iFp9i. Turbine flow value for point 9 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
fp9
{BD244D13-5805-4f39-A0D4-6AB400B42DFA}
Maximum gate position iGmaxi gt GovHydroWEH.gmin.
gmax
{46B0E2D5-707A-4605-B164-F105314D5F1B}
Minimum gate position iGmini lt GovHydroWEH.gmax.
gmin
{24665CC3-493E-48aa-9214-6ACA9765CD9B}
Maximum gate closing rate iGtmxcli.
gtmxcl
{34423799-3E6A-447d-ACCA-A5AC39DF6432}
Maximum gate opening rate iGtmxopi.
gtmxop
{1EEDF8E6-3068-4887-9EC8-C2EA214B87E0}
Gate 1 iGv1i. Gate Position value for point 1 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
gv1
{A9C5A0A5-4720-4d99-A7A7-2D26F00D79E0}
Gate 2 iGv2i. Gate Position value for point 2 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
gv2
{EEC48490-894C-4250-B1C4-72F856BE5A36}
Gate 3 iGv3i. Gate Position value for point 3 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
gv3
{0CB4F774-A53F-4eb4-88FA-A50756044440}
Gate 4 iGv4i. Gate Position value for point 4 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
gv4
{E5EE3181-0144-42de-9355-F5431928AE8C}
Gate 5 iGv5i. Gate Position value for point 5 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
gv5
{F04970BE-5332-4023-9D01-3CF0F2A64EEE}
Derivative controller derivative gain iKdi.
kd
{437820AA-EB84-43e3-9F14-CD29F17E5357}
Derivative controller Integral gain iKii.
ki
{186CD31C-11C2-4600-9C52-C73868C11E8C}
Derivative control gain iKpi.
kp
{6C38D8F7-4D15-4269-88C5-8BB7D8B7B534}
Base for power values iMWbasei gt 0. Unit MW.
mwbase
{E9D4FB05-AC60-4ec0-97F7-D0F12CD79F7C}
Pmss flow P1 iPmss1i. Mechanical power output for turbine flow point 1 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
pmss1
{7D878D2D-2290-494e-ABE1-2E30138DBADA}
Pmss flow P10 iPmss10i. Mechanical power output for turbine flow point 10 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
pmss10
{D1502FC1-74AE-4abe-9D8B-3A91C9B34B75}
Pmss flow P2 iPmss2i. Mechanical power output for turbine flow point 2 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
pmss2
{93ADB708-1FCF-46a7-A1FE-84B92459F065}
Pmss flow P3 iPmss3i. Mechanical power output for turbine flow point 3 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
pmss3
{CEC08DD4-FC8C-4e17-9617-C88CF79F807C}
Pmss flow P4 iPmss4i. Mechanical power output for turbine flow point 4 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
pmss4
{375B46F3-DFA0-48be-8747-B26DED2033EB}
Pmss flow P5 iPmss5i. Mechanical power output for turbine flow point 5 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
pmss5
{569E9FF0-4F73-4459-BC27-4C496AD9EA29}
Pmss flow P6 iPmss6i. Mechanical power output for turbine flow point 6 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
pmss6
{7515B1CA-A07C-4ee5-8977-871CAAF88680}
Pmss flow P7 iPmss7i. Mechanical power output for turbine flow point 7 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
pmss7
{C7FE804F-AB3E-41fd-B89C-259FED97771C}
Pmss flow P8 iPmss8i. Mechanical power output for turbine flow point 8 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
pmss8
{0021E92F-92DC-4c3b-8AF2-459A6CD9859C}
Pmss flow P9 iPmss9i. Mechanical power output for turbine flow point 9 for lookup table representing PU mechanical power on machine MVA rating as a function of turbine flow.
pmss9
{9F0CD115-B416-4c42-AC39-07560AE20E0D}
Derivative controller time constant iTdi gt 0. Limits the derivative characteristic beyond a breakdown frequency to avoid amplification of highfrequency noise.
td
{CA60CB57-5545-44b2-A97E-B31C19C35908}
Distributive valve time lag time constant iTdvi gt 0.
tdv
{163C915E-AF38-4e64-9D52-5BF5424C6118}
Value to allow the distribution valve controller to advance beyond the gate movement rate limit iTgi gt 0.
tg
{E9402819-AB88-4baa-BD6E-2B688C06C3BE}
Pilot valve time lag time constant iTpi gt 0.
tp
{36419228-318B-4c64-AB00-A75F021B45EF}
Electrical power droop time constant iTpei gt 0.
tpe
{F37EFAD1-2A67-4c5f-B7CC-7658CC10C1E2}
Water inertia time constant iTwi gt 0.
tw
{60C51DC4-0C85-4c88-B9FB-8535481239A0}
Turbine damping factor iDi. Unit delta P delta speed.
d
{1CDFD103-979A-45f2-AC53-B6EBABF1658E}
Gate opening limit maximum iGatmaxi gt GovHydroWPID.gatmin.
gatmax
{CBC8CAC7-BBD5-46ea-AA63-9BBA95339CA9}
Gate opening limit minimum iGatmini lt GovHydroWPID.gatmax.
gatmin
{59E5BEF5-54B4-4300-948D-E434DDC29D67}
Gate position 1 iGv1i.
gv1
{54D1F02F-B3AE-4c97-92AC-E3ECB097EE4E}
Gate position 2 iGv2i.
gv2
{4BF85918-D50B-4ded-A4A7-7D751F42AF41}
Gate position 3 iGv3i 10.
gv3
{088C7FD4-A64F-4679-9308-F019240AB520}
Derivative gain iKdi. Typical value 111.
kd
{7DD3DF14-A636-486c-93BF-2CDE421C351A}
Reset gain iKii. Typical value 036.
ki
{80A87F57-E0A0-4355-8369-5F25F473B715}
Proportional gain iKpi. Typical value 01.
kp
{DC7ECAB0-32B9-4f6b-96CD-21A7737B8AE3}
Base for power values iMWbasei gt 0. Unit MW.
mwbase
{F0BFC978-6685-4754-8C7B-33DAC29144ED}
Output at iGv1i PU of iMWbasei iPgv1i.
pgv1
{6499A090-412B-4d38-B39E-65354DA61FFC}
Output at iGv2i PU of iMWbasei iPgv2i.
pgv2
{B5555EA0-F1DA-4444-91EF-A708739B01BB}
Output at iGv3i PU of iMWbasei iPgv3i.
pgv3
{C1C12E4E-54B8-4819-9EA7-3700A2F6D4F4}
Maximum power output iPmaxi gt GovHydroWPID.pmin.
pmax
{C5161F34-C44E-4101-B7C7-AC4EC8AF73D4}
Minimum power output iPmini lt GovHydroWPID.pmax.
pmin
{C0683772-32A1-48e0-831F-580D802FA100}
Permanent drop iRegi.
reg
{943CF738-EE1C-47da-A25F-0C2EEC63695D}
Controller time constant iTai gt 0. Typical value 0.
ta
{4B54F2C1-ACDC-4a1b-BD6B-44F3B1BE10C6}
Gate servo time constant iTbi gt 0. Typical value 0.
tb
{0F0841FD-29F4-4349-ABE3-4371D74439DB}
Speed detector time constant iTregi gt 0.
treg
{2FE7836B-00FF-46e9-BF83-1AD62994F770}
Water inertia time constant iTwi gt 0. Typical value 0.
tw
{61278E8C-3A6F-4b21-A728-6920DD784BCD}
Maximum gate opening velocity iVelmaxi gt GovHydroWPID.velmin. Unit PU s. Typical value 0.
velmax
{8099C25E-58FC-47d6-A4E5-9B275BAA8990}
Maximum gate closing velocity iVelmini lt GovHydroWPID.velmax. Unit PU s. Typical value 0.
velmin
{966F8F0A-F65F-483f-B4A6-0DD4E3D4B61B}
Turbine damping coefficient iDti. Unit delta P delta speed. Typical value 0.
dt
{2E52C3FD-AFC7-45df-979E-816627C3BD3B}
Base for power values iMWbasei gt 0. Unit MW.
mwbase
{2DEDF38C-4F35-4a09-A72B-1E682C971FEF}
Permanent droop iRi. Typical value 005.
r
{DEF748BA-6B2D-41bf-B4AB-684779F9E07C}
Steam bowl time constant iT1i gt 0. Typical value 05.
t1
{4A1A56EA-CC0F-45de-A8C0-5B84F599EBBF}
Numerator time constant of iT2iiT3i block iT2i gt 0. Typical value 3.
t2
{70493A6B-C94A-4b89-9561-AC0392054D36}
Reheater time constant iT3i gt 0. Typical value 10.
t3
{343FBD73-1436-4911-9FDA-B150560357FD}
Maximum valve position PU of imwcapi iVmaxi gt GovSteam0.vmin. Typical value 1.
vmax
{6699F1C1-E261-4ac0-AA90-240DCE9EDDB5}
Minimum valve position PU of imwcapi iVmini lt GovSteam0.vmax. Typical value 0.
vmin
{DC8803D9-2717-41cc-B675-7CDBDF480BF3}
Intentional deadband width idb1i. Unit Hz. Typical value 0.
db1
{A77CBD3D-9EF5-4960-983F-4BF3E49C5B9A}
Unintentional deadband idb2i. Unit MW. Typical value 0.
db2
{585062E0-7AF5-49a4-9109-11EA6036AB5F}
Intentional db hysteresis iepsi. Unit Hz. Typical value 0.
eps
{11565F1A-7262-4d99-9D36-85008D67B2E2}
Nonlinear gain valve position point 1 iGV1i. Typical value 0.
gv1
{D31498E8-812A-4616-BF02-E62F0267A6E7}
Nonlinear gain valve position point 2 iGV2i. Typical value 04.
gv2
{9911B00A-D603-484a-BDE5-543F20B0A5A8}
Nonlinear gain valve position point 3 iGV3i. Typical value 05.
gv3
{FAC8C6BF-EAF3-4b9c-AF63-EC0441E6994A}
Nonlinear gain valve position point 4 iGV4i. Typical value 06.
gv4
{6AC94045-31C6-4865-BF63-B9A9ACD16490}
Nonlinear gain valve position point 5 iGV5i. Typical value 1.
gv5
{3B50B532-5A5C-4889-AB87-B31155DB184F}
Nonlinear gain valve position point 6 iGV6i. Typical value 0.
gv6
{2F114B0F-A915-4b0b-97B3-D9EAB684BDF3}
Governor gain reciprocal of droop iKi gt 0. Typical value 25.
k
{EB46DBE2-3AED-40c4-A6A6-975580FB1882}
Base for power values iMWbasei gt 0. Unit MW.
mwbase
{11EA8F80-CAD5-44e3-8893-3FBF11D33D5F}
Nonlinear gain power value point 1 iPgv1i. Typical value 0.
pgv1
{188F2130-8802-45f5-91AA-2A9514AC388D}
Nonlinear gain power value point 2 iPgv2i. Typical value 075.
pgv2
{7D77B573-07F0-47f7-BFFF-4F13EE82DA25}
Nonlinear gain power value point 3 iPgv3i. Typical value 091.
pgv3
{DDF38B36-369E-4d46-9D55-C9F87C94F24C}
Nonlinear gain power value point 4 iPgv4i. Typical value 098.
pgv4
{3EF3FE5E-3655-4c03-9F17-38BB5B02D04A}
Nonlinear gain power value point 5 iPgv5i. Typical value 1.
pgv5
{7D9CEFCA-A8B6-4bce-BD69-F7CAA3B08F5E}
Nonlinear gain power value point 6 iPgv6i. Typical value 0.
pgv6
{3D47DC91-D57C-4556-A31F-96B696DE66F1}
Maximum valve opening iPmaxi gt GovSteam1.pmin. Typical value 1.
pmax
{7C1F64A8-147F-4e18-95F0-3F0BABF82895}
Minimum valve opening iPmini gt 0 and lt GovSteam1.pmax. Typical value 0.
pmin
{C43C4789-9603-48d4-8BCB-72AE473AB8A1}
Governor lag time constant iT1i gt 0. Typical value 0.
t1
{84219FED-6A24-4520-ADEA-42E38B6E5465}
Governor lead time constant iT2i gt 0. Typical value 0.
t2
{CB1CBB4D-B666-4352-A131-5FA0663EACEF}
Valve positioner time constant iT3 igt 0. Typical value 01.
t3
{B05D1EC4-887A-4d17-9F0D-AF50BCA30EE5}
Inlet pipingsteam bowl time constant iT4i gt 0. Typical value 03.
t4
{06C29E01-3EBE-4768-AFB8-EAD717A5BE02}
Time constant of second boiler pass iT5i gt 0. Typical value 5.
t5
{E5405C9F-90A0-4002-8DF6-994A5AB4678F}
Time constant of third boiler pass iT6i gt 0. Typical value 05.
t6
{0B28BBC7-8677-4352-871C-C629D45FA46D}
Time constant of fourth boiler pass iT7i gt 0. Typical value 0.
t7
{79D2E4BF-C691-4c14-9039-653FC5A12749}
Frequency deadband iDBFi. Typical value 0.
dbf
{4ECCC0CA-82AA-4b5c-836B-0E47BE551C38}
Fuel flow maximum negative error value iMNiisubEFsubi. Typical value 1.
mnef
{AFD2584D-F92C-42a8-947A-428E8CE2E897}
Fuel flow maximum positive error value iMXiisubEFsubi. Typical value 1.
mxef
{4E4A36B6-988F-4c44-A020-6165A778B92A}
Maximum fuel flow iPiisubMAXsubi gt GovSteam2.pmin. Typical value 1.
pmax
{285C7FC5-344F-4625-AE73-9DB41F052ECD}
Minimum fuel flow iPiisubMINsubi lt GovSteam2.pmax. Typical value 0.
pmin
{881CB33A-F1B3-4373-8E54-DDABCBF500E6}
Governor lag time constant iTiisub1subi gt 0. Typical value 045.
t1
{35B345F9-6E69-4ad2-8F13-6A1029B16261}
Governor lead time constant iTiisub2subi gt 0. Typical value 0.
t2
{5B194B27-05BF-4e75-8DD3-2D801159E3A5}
Frequency deadband ifiisubcutsubi gt 0. Typical value 0002.
fcut
{0E18FB6D-C7CF-4b3d-8979-F10B6ED20238}
Gain iK2i. Typical value 075.
k2
{D6246395-FC43-4751-A620-E9AFCE848947}
Gain iK3i. Typical value 05.
k3
{752C1268-60AE-4c49-9D23-775FFFEA156B}
Gain iKdi. Typical value 10.
kd
{5251AB39-0329-46a3-AFF1-A029EFF6CF94}
Gain iKgi. Typical value 10.
kg
{A43E1339-FEE8-4462-8DF2-9D3D49165DB5}
Gain iKlsi gt 0. Typical value 01.
kls
{30DFF15C-37AA-4700-A237-29BF65295E8B}
Gain iKpi. Typical value 10.
kp
{2B8EBC64-4CC4-43ad-9A0F-B96F89FB39CA}
Gain iKsi. Typical value 210.
ks
{A7302803-04A9-4430-8E57-97AB9A240F03}
High power limit iPmaxi gt GovSteamBB.pmin. Typical value 10.
pmax
{F7EBD23C-4A5A-4941-8D0D-AF35EEBE3AB9}
Low power limit iPmini lt GovSteamBB.pmax. Typical value 0.
pmin
{92C0B557-9F74-41cb-819A-EAD19DD6BDFE}
Time constant iT1i. Typical value 005.
t1
{06D55A71-AF1B-46ac-BF85-3C64F21A808A}
Time constant iT4i. Typical value 015.
t4
{23F09386-B96A-4807-9E42-35EBCD7355B5}
Time constant iT5i. Typical value 120.
t5
{D1164155-DB71-4d65-B3ED-B9DED1577924}
Time constant iT6i. Typical value 075.
t6
{1E8F11DC-A2F0-4144-915D-408A7F982624}
Time constant iTdi gt 0. Typical value 10.
td
{0E0D3B71-1315-4fcb-8B30-B3CF976B8AFD}
Time constant iTni gt 0. Typical value 10.
tn
{4212F57B-6F71-4352-8793-EE325DFC21B4}
HP damping factor iDhpi. Typical value 0.
dhp
{CAA4CE58-A372-4921-B2C8-4A02D2858FC2}
LP damping factor iDlpi. Typical value 0.
dlp
{F2553540-1BBF-4ba2-9BAB-5A46146D77C8}
Fraction of HP power ahead of reheater iFhpi. Typical value 03.
fhp
{F243C240-3FE8-4c29-BB34-B8741BF6D940}
Fraction of LP power ahead of reheater iFlpi. Typical value 07.
flp
{2D0CC21A-3B88-4712-A698-A93DE78DCCC9}
Base for power values iMWbasei gt 0. Unit MW.
mwbase
{7D26F55F-866C-4dc1-9929-4475EF721953}
Maximum HP value position iPmaxhpi. Typical value 1.
pmaxhp
{0215266A-9E00-4294-B267-67FB9D77D6FD}
Maximum LP value position iPmaxlpi. Typical value 1.
pmaxlp
{5C39A692-9C54-4c8c-8E60-A0953782C737}
HP governor droop iRhpi gt 0. Typical value 005.
rhp
{A1DB6375-5D37-4daa-877D-E25951792479}
LP governor droop iRlpi gt 0. Typical value 005.
rlp
{E93DE78A-2C59-418d-9776-509B889795D6}
HP governor time constant iT1hpi gt 0. Typical value 01.
t1hp
{3D952D69-270E-4d49-88FD-8FA58FA272ED}
LP governor time constant iT1lpi gt 0. Typical value 01.
t1lp
{C89637BB-AA65-403b-A87E-9EFEFB6FB8EE}
HP turbine time constant iT3hpi gt 0. Typical value 01.
t3hp
{B189CEEA-2CA7-4e67-8F67-0B367BDDCD7D}
LP turbine time constant iT3lpi gt 0. Typical value 01.
t3lp
{08AA57C2-525A-4c3b-99FE-F6DECFBF63A2}
HP turbine time constant iT4hpi gt 0. Typical value 01.
t4hp
{7C37A7BF-EBA3-471b-928B-2239F4485D94}
LP turbine time constant iT4lpi gt 0. Typical value 01.
t4lp
{20C82B5A-F5C2-4019-8669-321C7A5F1B5E}
HP reheater time constant iT5hpi gt 0. Typical value 10.
t5hp
{B1789202-591E-47af-8790-F6E94CB23471}
LP reheater time constant iT5lpi gt 0. Typical value 10.
t5lp
{BDC9972B-0E8D-40ef-AD59-E2FC50B8CA3F}
Intercept valves rate closing limit iCici. Typical value 22.
cic
{1CE2C5C6-F833-4b5f-B445-84FBCFD7361D}
Intercept valves rate opening limit iCioi. Typical value 0123.
cio
{568A9507-36A3-421b-9640-2A9CA7E27E5D}
Deadband of the frequency corrector idb1i. Typical value 0.
db1
{3C28927B-00E6-4258-B92E-D97480764999}
Deadband of the speed governor idb2i. Typical value 00004.
db2
{E4E274A4-6302-48b5-9E76-FFE916C9B1A2}
Maximum control valve position iHhpmaxi. Typical value 1.
hhpmax
{A1183CB7-248E-49b3-9CBE-174DAA2AA360}
Gain of the power controller iKei. Typical value 065.
ke
{9C484EA6-BDD5-4168-8BF8-316D4B3BB6D1}
Gain of the frequency corrector iKfcori. Typical value 20.
kfcor
{F44827D7-5A62-4e6a-B51B-889200EE9BAC}
Fraction of total turbine output generated by HP part iKhpi. Typical value 0277.
khp
{DCD58561-BCFA-4811-AB0A-696EC2C80130}
Fraction of total turbine output generated by HP part iKlpi. Typical value 0723.
klp
{90CB447C-DD10-4264-A94F-7295BFD6BAC6}
Gain of the speed governor iKwcori. Typical value 20.
komegacor
{DFA76021-D5A7-4ef8-99C2-57EE96E5C8B1}
Base for power values iMWbasei gt 0. Unit MW.
mwbase
{F36677CC-53A8-4a82-8071-5D477609BFCD}
Maximal active power of the turbine iPmaxi. Typical value 1.
pmax
{141D9FB3-AE5A-453b-90FC-7666AEFB9923}
Maximum low pressure limit iPrhmaxi. Typical value 14.
prhmax
{E4A8F98D-D571-48be-86EA-AA4DA473C260}
Intercept valves transfer limit iSimxi. Typical value 0425.
simx
{110F9C82-647B-433d-A6D0-F20BE969A8FD}
Boiler time constant iTbi gt 0. Typical value 100.
tb
{6939BF5E-1A7B-49c3-BCAE-B256D5305802}
Derivative time constant of the power controller iTdpi gt 0. Typical value 0.
tdp
{81B7D62E-D2DB-41c9-A79E-163FB2210FF4}
Electro hydraulic transducer iTeni gt 0. Typical value 01.
ten
{19813DEF-9416-4ffa-804B-D47E5FF2C4CC}
Frequency transducer time constant iTfi gt 0. Typical value 0.
tf
{CDDB592D-5B31-49d5-BA52-5374D479B1BE}
Time constant of the power controller iTfpi gt 0. Typical value 0.
tfp
{B5F3AA62-2076-4637-8306-B36724D11885}
High pressure HP time constant of the turbine iThpi gt 0. Typical value 031.
thp
{57975343-40A0-46bb-A43C-13E600304884}
Integral time constant of the power controller iTipi gt 0. Typical value 2.
tip
{0F8A085F-B368-436d-9D92-343E88AF2219}
Low pressure LP time constant of the turbine iTlpi gt 0. Typical value 045.
tlp
{29B893EA-A77B-43ea-8A20-6D6320408868}
Power transducer time constant iTpi gt 0. Typical value 007.
tp
{BCC75C87-06BE-4533-AA66-7FFC57721184}
Reheater time constant of the turbine iTrhi gt 0. Typical value 8.
trh
{35B57951-2DF1-4ebe-9382-5BEAACC7C1A4}
Control valves servo time constant iTvhpi gt 0. Typical value 01.
tvhp
{C4AD7C67-5135-4472-B036-22EB2964F783}
Intercept valves servo time constant iTvipi gt 0. Typical value 015.
tvip
{E0C2F944-FE5B-48af-A4C2-FEC518B2AB55}
Speed transducer time constant iTwi gt 0. Typical value 002.
tw
{7899000C-51A1-4038-8E92-908FEB0D86C0}
Upper limit for frequency correction iWfmaxi gt GovSteamEU.wfmin. Typical value 005.
wfmax
{5E5EA0F9-E4E3-4c29-915D-D2D38D6D0424}
Lower limit for frequency correction iWfmini lt GovSteamEU.wfmax. Typical value 005.
wfmin
{4206D95B-5A8C-42ee-B955-02C4C77EFD69}
Emergency speed control lower limit iwmax1i. Typical value 1025.
wmax1
{451E7E3F-6990-43b5-AF43-78CFC5A711B6}
Emergency speed control upper limit iwmax2i. Typical value 105.
wmax2
{A329D28C-1432-4fbe-A428-E947CC5F4448}
Upper limit for the speed governor iWwmaxi gt GovSteamEU.wwmin. Typical value 01.
wwmax
{2BDA9EEB-A0A5-42a0-A6E3-132EFA209F17}
Lower limit for the speed governor frequency correction iWwmini lt GovSteamEU.wwmax. Typical value 1.
wwmin
{FDD5FF45-AB58-4636-814A-F587E30F1EA8}
iDti.
dt
{1078B67F-81D7-43e3-AC0C-095EB6FE9E0D}
Fraction of the turbine power developed by turbine sections not involved in fast valving iKi.
k
{5D8BF3BB-513A-425b-99E1-296E80E4BB77}
Alternate base used instead of machine base in equipment model if necessary iMWbasei gt 0. Unit MW.
mwbase
{775BD8D4-7E30-4e5c-83C8-37E6EC02069C}
iRi.
r
{FE49FC81-A61A-49f5-B89B-7B3DC35958E8}
Governor time constant iT1i gt 0.
t1
{E72B25DB-96F9-4ce4-9A5A-478DD9F8CF48}
Reheater time constant iT3i gt 0.
t3
{CFF9C104-AF8A-4a1b-9235-8498396F3C58}
Time after initial time for valve to close iTai gt 0.
ta
{CA28640A-98C2-45f5-9FB4-3CA075811C95}
Time after initial time for valve to begin opening iTbi gt 0.
tb
{A4905A52-147D-425f-8D70-0BD93B908647}
Time after initial time for valve to become fully open iTci gt 0.
tc
{03ED1261-377F-4cdf-BF52-3C02546B2E7B}
Time constant with which power falls off after intercept valve closure iTti gt 0.
tt
{C31BA8DF-B822-49a7-BBE7-3317B0A9A159}
iVmaxi gt GovSteamFV2.vmin.
vmax
{CF82BE67-DCDF-421e-BC3B-0B97CD064051}
iVmini lt GovSteamFV2.vmax.
vmin
{FA92EA93-7BE4-427e-98A4-CFDDF7128C54}
Nonlinear gain valve position point 1 iGV1i. Typical value 0.
gv1
{E874B1DF-E7F2-4dd2-84F9-13E25FCE9FE1}
Nonlinear gain valve position point 2 iGV2i. Typical value 04.
gv2
{D6ACEA3F-7510-495a-89B0-D9EC37898E57}
Nonlinear gain valve position point 3 iGV3i. Typical value 05.
gv3
{72054D4A-B578-4339-BF19-A0D87AC68CC6}
Nonlinear gain valve position point 4 iGV4i. Typical value 06.
gv4
{429CB562-E8AB-434d-9F06-0531A5FB8EC2}
Nonlinear gain valve position point 5 iGV5i. Typical value 1.
gv5
{CADA4FA7-24F0-4006-8FCA-C0DFA7B528AF}
Nonlinear gain valve position point 6 iGV6i. Typical value 0.
gv6
{EB422568-E0EB-46e3-A82E-CE28ED9AA6D5}
Governor gain reciprocal of droop iKi. Typical value 20.
k
{D812C52D-7AB5-4275-AA2B-72BFBEC2935C}
Fraction of turbine power developed after first boiler pass iK1i. Typical value 02.
k1
{50077BE8-96B4-4ace-996C-F03786379A92}
Fraction of turbine power developed after second boiler pass iK2i. Typical value 02.
k2
{A7687637-D622-492f-A7FE-78F185BB94F3}
Fraction of hp turbine power developed after crossover or third boiler pass iK3i. Typical value 06.
k3
{82C3CBE7-853A-4dbb-9BCF-8B6FC6DDE68C}
Base for power values iMWbasei gt 0. Unit MW.
mwbase
{5D07D037-9E57-48ec-B14E-EA6B6DB4B0D9}
Nonlinear gain power value point 1 iPgv1i. Typical value 0.
pgv1
{4B6A30E2-D5EB-4364-9D05-5985E67AD5EF}
Nonlinear gain power value point 2 iPgv2i. Typical value 075.
pgv2
{39CE6A04-677D-46ce-A4B3-46A3CC5B3703}
Nonlinear gain power value point 3 iPgv3i. Typical value 091.
pgv3
{169C7971-2422-4a63-95B9-861B6395671B}
Nonlinear gain power value point 4 iPgv4i. Typical value 098.
pgv4
{A48F5B0F-293F-443b-84F9-3808641B4A47}
Nonlinear gain power value point 5 iPgv5i. Typical value 1.
pgv5
{B63726CA-1E67-412f-A0C2-CCB460851FD6}
Nonlinear gain power value point 6 iPgv6i. Typical value 0.
pgv6
{F9940DA2-49DB-4808-9791-1E3354DE3B0C}
Maximum valve opening PU of iMWbasei iPmaxi gt GovSteamFV3.pmin. Typical value 1.
pmax
{83CDC484-448A-41e9-9B76-1387BA086210}
Minimum valve opening PU of iMWbasei iPmini lt GovSteamFV3.pmax. Typical value 0.
pmin
{5067B69C-1F2E-4ae7-B34D-82E10D593270}
Max. pressure in reheater iPrmaxi. Typical value 1.
prmax
{08A80961-533E-4c2d-9922-B957DC12B461}
Governor lead time constant iT1i gt 0. Typical value 0.
t1
{96858B4F-3184-49fe-A309-14C0C5292B1A}
Governor lag time constant iT2i gt 0. Typical value 0.
t2
{69C796D4-A0AF-4327-B185-59635C60C453}
Valve positioner time constant iT3i gt 0. Typical value 0.
t3
{E218667B-0751-41ab-B15A-793C48132DC1}
Inlet pipingsteam bowl time constant iT4i gt 0. Typical value 02.
t4
{20359039-EB27-41fc-A1C6-00DF036CFE3A}
Time constant of second boiler pass i.e. reheater iT5i gt 0 if fast valving is used otherwise gt 0. Typical value 05.
t5
{FEEC774C-00BF-47c5-BB64-66AA92CB02DA}
Time constant of crossover or third boiler pass iT6i gt 0. Typical value 10.
t6
{0C07F8A3-EC87-44e3-802B-E29F6E7A0CF4}
Time to close intercept valve IV iTai gt 0. Typical value 097.
ta
{19FF9DAA-9677-4971-BD65-451BFDC95350}
Time until IV starts to reopen iTbi gt 0. Typical value 098.
tb
{31CD944F-4727-4535-889B-8ED2187C1D7F}
Time until IV is fully open iTci gt 0. Typical value 099.
tc
{65A3FED2-6AFD-45ec-822F-07E55F257F30}
Minimum value of pressure regulator output iCpsmni. Typical value 1.
cpsmn
{E9DBD13F-85FF-4f9d-9CC2-CBF8D30537F2}
Maximum value of pressure regulator output iCpsmxi. Typical value 1.
cpsmx
{E2C0F331-1B3D-411a-B83C-A907C3286AFA}
Minimum value of regulator setpoint iCrmni. Typical value 0.
crmn
{34ECA262-63E9-4632-8FFB-FA2D44612B6D}
Maximum value of regulator setpoint iCrmxi. Typical value 12.
crmx
{49ED4396-A7C2-45f0-A3DE-4E1BCF2F36AF}
Derivative gain of pressure regulator iKdci. Typical value 1.
kdc
{C946421B-13FD-4d63-BE11-411FAA7A1488}
Frequency bias reciprocal of droop iKf1i. Typical value 20.
kf1
{508C2858-C010-49b6-A75C-AFC7AA3BBAE8}
Frequency control reciprocal of droop iKf3i. Typical value 20.
kf3
{B1997DED-9F95-41ac-9AC5-820C23706CC0}
Fraction of total turbine output generated by HP part iKhpi. Typical value 035.
khp
{850AE4D1-F8FE-4d1c-B2E7-214EB3E7D533}
Integral gain of pressure regulator iKici. Typical value 00033.
kic
{11BEE5A6-7EC1-475b-B096-71A00DD5B0DC}
Integral gain of pressure feedback regulator iKipi. Typical value 05.
kip
{5638FE78-5181-4a8a-8C8B-44EEE90EE355}
Integral gain of electrohydraulic regulator iKiti. Typical value 004.
kit
{36D398CE-4730-4956-88E2-D1EAAD1DCE48}
First gain coefficient of intercept valves characteristic iKmp1i. Typical value 05.
kmp1
{A3F3162A-036E-421b-AD4D-A8B7A1629142}
Second gain coefficient of intercept valves characteristic iKmp2i. Typical value 35.
kmp2
{4B7EF22B-BF12-460b-9661-4F05ABC35877}
Proportional gain of pressure regulator iKpci. Typical value 05.
kpc
{F60F8893-378A-47da-8EA0-EAF3FAD00195}
Proportional gain of pressure feedback regulator iKppi. Typical value 1.
kpp
{D7AA6144-3E0C-4292-8213-0C08C3620A12}
Proportional gain of electrohydraulic regulator iKpti. Typical value 03.
kpt
{1E78FDA6-6D86-46a7-A6F8-88B14D05EDAC}
Maximum variation of fuel flow iKrci. Typical value 005.
krc
{AB7B7099-8460-428e-AFCB-CA16A9874F0B}
Pressure loss due to flow friction in the boiler tubes iKshi. Typical value 008.
ksh
{7544C5BC-B364-4ea0-A283-32E3560EEA64}
Maximum negative power error iLpii. Typical value 015.
lpi
{BD96AA9C-4159-4c5e-BB47-AD342BFDD719}
Maximum positive power error iLpsi. Typical value 003.
lps
{3C8A33C3-274B-4d1d-8D5D-AAB04C4DB84A}
Lower limit for frequency correction iMNiisubEFsubi. Typical value 005.
mnef
{285955C5-D035-42a8-966C-3AFD99799AA8}
Upper limit for frequency correction iMXiisubEFsubi. Typical value 005.
mxef
{801A2891-39DA-433a-B3F3-A06D2E96A234}
First value of pressure set point static characteristic iPr1i. Typical value 02.
pr1
{CD5E7783-3DE0-4520-88AE-C2610005E1BA}
Second value of pressure set point static characteristic corresponding to iPs0i 10 PU iPr2i. Typical value 075.
pr2
{0A7E701E-3922-4e2a-8C1F-C74A2FE11E13}
Minimum value of pressure set point static characteristic iPsmni. Typical value 1.
psmn
{A7DF91CF-A30F-43d6-8B79-565A2F75D427}
Minimum value of integral regulator iRsmimni. Typical value 0.
rsmimn
{8B05B27E-532F-414c-B2F8-60AEF76DC6E5}
Maximum value of integral regulator iRsmimxi. Typical value 11.
rsmimx
{86384E60-6DED-4a13-B081-87A85572597D}
Minimum value of integral regulator iRvgmni. Typical value 0.
rvgmn
{CFFE55BB-0A0C-423a-BFD8-68A65FBCAA5D}
Maximum value of integral regulator iRvgmxi. Typical value 12.
rvgmx
{026BE588-F74B-4015-8F31-646BE73272A8}
Minimum valve opening iSrmni. Typical value 0.
srmn
{BDD9B27C-E19C-40a2-B9A3-40C178F96C3A}
Maximum valve opening iSrmxi. Typical value 11.
srmx
{6A4B6465-FFFC-4cc9-9A19-0D739D468207}
Intercept valves characteristic discontinuity point iSrsmpi. Typical value 043.
srsmp
{6DA38905-8256-404b-A444-04C9EE89644E}
Control valves rate opening time iTai gt 0. Typical value 08.
ta
{5E168E27-CF72-411e-BEE5-E17364F8E223}
Intercept valves rate opening time iTami gt 0. Typical value 08.
tam
{B7BEFDB3-EC75-4c1d-A5CD-5ABF52976BE3}
Control valves rate closing time iTci gt 0. Typical value 05.
tc
{21F03085-6C79-4dad-9C3F-E8F964F79C7D}
Intercept valves rate closing time iTcmi gt 0. Typical value 05.
tcm
{D34C3D25-D4CC-42c6-8F48-4812BA6C67E2}
Derivative time constant of pressure regulator iTdci gt 0. Typical value 90.
tdc
{92244DA9-318A-408b-AE5C-433CBE35824A}
Time constant of fuel regulation iTf1i gt 0. Typical value 10.
tf1
{DD5F9B1D-032F-4d31-A0DF-437758280B81}
Time constant of steam chest iTf2i gt 0. Typical value 10.
tf2
{4F79E063-4AA6-4983-9E6E-295EF7A60FB1}
High pressure HP time constant of the turbine iThpi gt 0. Typical value 015.
thp
{10FD21BA-CD02-446b-8E93-593B94D77B67}
Low pressure LP time constant of the turbine iTmpi gt 0. Typical value 04.
tmp
{396BC671-A807-4b26-B7A3-91C37689C5AE}
Reheater time constant of the turbine iTrhi gt 0. Typical value 10.
trh
{21F92AA8-3819-4808-8972-F78A329F7A44}
Boiler time constant iTvi gt 0. Typical value 60.
tv
{5BB2D156-1D6A-4a63-A31D-C707296AAC5A}
Control valves servo time constant iTyi gt 0. Typical value 01.
ty
{16218B62-D2B3-45a6-9FC1-B0BED9126075}
Coefficient of linearized equations of turbine Stodola formulation iYi. Typical value 013.
y
{2ADF361B-A0F5-46d4-B6BA-A90C2B2B965F}
Minimum control valve position iYhpmni. Typical value 0.
yhpmn
{8925B517-7D03-4a5f-A11C-6AEE121FD1C4}
Maximum control valve position iYhpmxi. Typical value 11.
yhpmx
{AD266096-6044-474c-9B43-B09B41FDB5C2}
Minimum intercept valve position iYmpmni. Typical value 0.
ympmn
{8F8B125A-EA23-4807-8A7F-571B0D75E79B}
Maximum intercept valve position iYmpmxi. Typical value 11.
ympmx
{8F18ED11-7811-4dc3-BA55-B3519E8F6FBD}
Governor gain reciprocal of droop iKi gt 0. Typical value 25.
k
{3B0BA29C-E505-4c31-AC6D-22153D6A2344}
Base for power values iMWbasei gt 0i. iUnit MW.
mwbase
{D7E35874-9E7E-401b-8C00-EFF8CE6D581B}
Maximum valve opening iPmaxi gt GovSteamIEEE1.pmin. Typical value 1.
pmax
{C0A21ABD-B86F-4be6-843A-6418DBDFBA74}
Minimum valve opening iPmini gt 0 and lt GovSteamIEEE1.pmax. Typical value 0.
pmin
{E07CF9E0-312E-4170-B843-E218030E028A}
Governor lag time constant iT1i gt 0. Typical value 0.
t1
{A43E3910-A206-47ce-90EF-4EDDCEAD2B97}
Governor lead time constant iT2i gt 0. Typical value 0.
t2
{7B8DF74C-AF7D-4355-BC96-3E03C80DC2C2}
Valve positioner time constant iT3i gt 0. Typical value 01.
t3
{528BF1FA-2DE1-49af-9EFE-992F44D064BA}
Inlet pipingsteam bowl time constant iT4i gt 0. Typical value 03.
t4
{D42E87AF-7FB9-4f45-8951-C2672F43892A}
Time constant of second boiler pass iT5i gt 0. Typical value 5.
t5
{C87552A6-806A-4e71-8690-82F8580A2D8D}
Time constant of third boiler pass iT6i gt 0. Typical value 05.
t6
{B6FEADDA-2652-401b-BCAC-3EC97560751D}
Time constant of fourth boiler pass iT7i gt 0. Typical value 0.
t7
{034804D5-AB66-4855-9002-4CDF1ACC780C}
One PU regulation iK1i.
k1
{03926971-3F21-4914-927A-AF05CD061C02}
Fraction iK2i.
k2
{9FD36089-0DEA-4e95-BCFD-634C00DA8598}
Fraction iK3i.
k3
{67B9B9D6-D9DC-48d6-90F5-045C8CBDF2BC}
Base for power values iMWbasei gt 0. Unit MW.
mwbase
{C613BB7A-3323-4635-B664-C4E30D182893}
Upper power limit iPmaxi gt GovSteamSGO.pmin.
pmax
{43756471-2CE6-410b-B4B7-A4711385608C}
Lower power limit iPmini gt 0 and lt GovSteamSGO.pmax.
pmin
{4C92810B-55D6-4f56-B1FD-381DF7F8F6E7}
Controller lag iT1i gt 0.
t1
{9DD652EA-4807-4313-8A33-F94BA5596DF0}
Controller lead compensation iT2i gt 0.
t2
{C1793777-CC94-4269-98CF-7D2904A63C2A}
Governor lag iT3i gt 0.
t3
{0D4E6BB8-A356-4073-9D8C-2B6164ECEC24}
Delay due to steam inlet volumes associated with steam chest and inlet piping iT4i gt 0.
t4
{5C4F8354-CA49-4224-AB28-1A759E350DC7}
Reheater delay including hot and cold leads iT5i gt 0.
t5
{F33128D7-055F-4bbd-A4A3-9116F3C417D0}
Delay due to IPLP turbine crossover pipes and LP end hoods iT6i gt 0.
t6
{CA8EC5EB-322E-418b-BB3B-B256740CD309}
A generating unit may have a gross active power to net active power curve describing the losses and auxiliary power requirements of the unit.
GeneratingUnit
{5A8B2A9D-6CA6-40c5-A362-38519E574F17}.SupplierEnd
Action taken with this ground.
GroundAction
{66B211AA-2CA9-43e6-9304-6C6E078FC904}.ClientEnd
The line segment that this ground action will affect. This is the only way to access relationship to clamp in case the ground needs to be placed along the line segment.
AlongACLineSegment
{1E3F8223-0B92-4d7f-B4A8-4D976F915A99}.SupplierEnd
Ground on which this action is taken.
Ground
{66B211AA-2CA9-43e6-9304-6C6E078FC904}.SupplierEnd
Equipment being grounded with this operation. In case of placing a ground anywhere along a line segment you must use the clamp to get the distance from one terminal so use the explicit relation with line segment. In all other cases including placing the ground at a line segment terminal reference to one or more conducting equipment is sufficient.
GroundedEquipment
{E49D8003-4EDF-4e58-A61C-0A5F1C6165E1}.SupplierEnd
Switching action to perform.
kind
{66457754-0A36-4354-B043-81FCC23B4478}
Reactance of device.
x
{EAF81570-74C7-49bb-B7CD-DDC0F14E9A27}
Qregulator
{7AC340E9-74FE-45f9-8424-0F67D74E0B6A}.SupplierEnd
VDCOL
{14C2B235-371D-4ebf-BFF8-1E462660C3D0}.SupplierEnd
functionKind
{3F937634-1749-4f11-A2D1-B3D391549380}
Status of this hazard.
status
{FCC8BE04-7ADD-48f6-8612-BA3EA0E20610}
Risk score with which this health score is associated.
AssetRiskScore
{35D3A10F-8986-4cb3-84BA-68730CC19A28}.SupplierEnd
A thermal generating unit may have a heat input curve.
ThermalGeneratingUnit
{0F7AF31F-7DEC-4822-9117-8C921A5EADD4}.SupplierEnd
Power output auxiliary power multiplier adjustment factor.
auxPowerMult
{C363F167-DCA3-444f-A356-B2EC5EC6BFE3}
Power output auxiliary power offset adjustment factor.
auxPowerOffset
{EBDBFAC3-F5B4-417e-9DCE-FD4332A94039}
Heat input efficiency multiplier adjustment factor.
heatInputEff
{A9882A3A-810D-44e6-BC69-3AD2A316B429}
Heat input offset adjustment factor.
heatInputOffset
{93844E51-F4F7-47ab-91CA-B268630921DA}
multiplier
{5DEF0F44-4B0F-4c43-8A24-A09D1CF5FFD6}
unit
{F95A9930-5D29-48ea-B9E4-F822F6F83BE4}
A thermal generating unit may have a heat rate curve.
ThermalGeneratingUnit
{E732F28C-0BF4-4edf-8CAB-14E807036F6F}.SupplierEnd
A combustion turbine may have a heat recovery boiler for making steam.
CombustionTurbines
{C08435B8-5EEA-4a1c-84DE-0253F3F7AC68}.SupplierEnd
AdjacentCASet
{8E4B9C0F-0498-44a7-BFE9-8CB6884935B0}.SupplierEnd
BidSelfSched
{A54AFE0A-D986-4114-B72E-9243C90ABC98}.SupplierEnd
CnodeDistributionFactor
{334067AA-47A1-45ec-86D0-469477F304C9}.SupplierEnd
A ControlAreaCompany controls a ControlArea.
Controls
{1AFC6FC5-1F2B-45c1-92ED-34FE03FF7500}.SupplierEnd
Flowgate
{AF155808-E637-4950-B9F3-2EAB07EDB824}.SupplierEnd
LossClearingResults
{AD728487-11BF-4cf9-8208-EB973AA30251}.SupplierEnd
RTO
{61BC778B-58EC-4247-B85A-DA7F2D069EB9}.ClientEnd
RegisteredResource
{4F7E336A-F935-41ea-B46D-CA4A8FBC907C}.SupplierEnd
The interchange area may operate as a control area
SubControlAreas
{FBEF4124-D3C2-4585-A504-3D5551015F14}.SupplierEnd
SysLoadDistribuFactor
{451D980C-3785-4de0-AC06-5515EF2C589B}.SupplierEnd
TransferInterface
{916AF086-1537-4361-A735-CFC6D28337F9}.SupplierEnd
The areas present control mode CF constant frequency or CTL constant tieline or TLB tieline bias or OFF off control
areaControlMode
{98508A61-49E6-4434-A8AA-2EE605E1E720}
The present power system frequency set point for automatic generation control
freqSetPoint
{680B241E-AF4C-450e-817A-01CF7FEFDFFE}
multiplier
{D6A39BEF-98E8-41ea-B1C7-A5A740DB7F72}
unit
{2E277D44-14DA-4343-85AC-FFBF01D847F8}
A hydro generating unit has an efficiency curve.
HydroGeneratingUnit
{8EFF4A51-FC21-4aa8-936F-C5CD96AED3B5}.SupplierEnd
A hydro generating unit has an efficiency curve.
HydroGeneratingEfficiencyCurves
{8EFF4A51-FC21-4aa8-936F-C5CD96AED3B5}.ClientEnd
The hydro generating unit belongs to a hydro power plant.
HydroPowerPlant
{DF7B4AA7-A2FE-443d-80DA-3E081B767D96}.ClientEnd
A hydro generating unit has a penstock loss curve.
PenstockLossCurve
{7ACC0340-79B7-4e30-B609-66235FA04D5D}.ClientEnd
A hydro generating unit has a tailbay loss curve.
TailbayLossCurve
{F9B9CD62-2EEB-4f1a-969B-6EE451A47D3F}.ClientEnd
The height water drops from the reservoir midpoint to the turbine.
dropHeight
{B502B280-7E7E-4b6b-891B-61CB4DD59A36}
Energy conversion capability for generating.
energyConversionCapability
{FD24D707-A27D-4ff0-AD05-342786B12544}
The equivalent cost of water that drives the hydro turbine.
hydroUnitWaterCost
{8EA91FB4-19DF-4575-8188-A14EA84B2E96}
Type of turbine.
turbineType
{5C107CE1-BFC7-49b0-877E-A3F16C08008B}
Generators are supplied water from or pumps discharge water to an upstream reservoir.
GenSourcePumpDischargeReservoir
{00B2E13E-C0A8-4011-8062-D47DDF498C70}.SupplierEnd
The hydro generating unit belongs to a hydro power plant.
HydroGeneratingUnits
{DF7B4AA7-A2FE-443d-80DA-3E081B767D96}.SupplierEnd
The hydro pump may be a member of a pumped storage plant or a pump for distributing water.
HydroPumps
{97B133E1-465B-463d-A8D6-CD977E575F10}.SupplierEnd
Generators discharge water to or pumps are supplied water from a downstream reservoir.
Reservoir
{2C3E96AE-B573-4669-98A0-A1B15E5B69A2}.SupplierEnd
Water travel delay from tailbay to next downstream hydro power station.
dischargeTravelDelay
{7E41C303-46EA-49e5-811F-391B6D32DB9C}
The hydro plants generating rating active power for rated head conditions.The attribute shall be a positive value.
genRatedP
{28D52CE4-E00F-48b9-B17D-8C2589281C71}
The type of hydro power plant water storage.
hydroPlantStorageType
{19631246-ED56-44ae-A636-6C1B4DACDDF0}
Total plant discharge capacity.
plantDischargeCapacity
{7BCFA6C6-1EA0-4c6a-9FC4-5E4DF0B64AFF}
The plants rated gross head.The attribute shall be a positive value.
plantRatedHead
{656435AA-37ED-4a01-970D-4292DAABEDD4}
The hydro plants pumping rating active power for rated head conditions.The attribute shall be a positive value.
pumpRatedP
{7C1B9181-2FEF-4d65-9411-DFDD7CEFD2C5}
The level at which the surge tank spills.
surgeTankCrestLevel
{2AE16ADA-2ECF-4899-ACBB-FCF6C9807C2C}
The hydro pump may be a member of a pumped storage plant or a pump for distributing water.
HydroPowerPlant
{97B133E1-465B-463d-A8D6-CD977E575F10}.ClientEnd
The hydro pump has a pumping schedule over time indicating when pumping is to occur.
HydroPumpOpSchedule
{FBD22BD2-FDFF-4973-A3EF-F30E7E51A36C}.ClientEnd
The synchronous machine drives the turbine which moves the water from a low elevation to a higher elevation. The direction of machine rotation for pumping may or may not be the same as for generating.
RotatingMachine
{B7907DA2-3474-44e7-8BA4-9B2DB3D1D425}.ClientEnd
The pumping discharge under maximum head conditions usually at full gate.
pumpDischAtMaxHead
{9D90170B-3F8F-40a9-B12F-1096B584C7C6}
The pumping discharge under minimum head conditions usually at full gate.
pumpDischAtMinHead
{18BF0612-CF16-449c-B10E-E37CDEAF6D5E}
The pumping power under maximum head conditions usually at full gate.
pumpPowerAtMaxHead
{D1FB01DB-20BE-4ba6-BB53-397352A73FE1}
The pumping power under minimum head conditions usually at full gate.
pumpPowerAtMinHead
{A663A382-B65C-4b74-999D-234661878F20}
The hydro pump has a pumping schedule over time indicating when pumping is to occur.
HydroPump
{FBD22BD2-FDFF-4973-A3EF-F30E7E51A36C}.SupplierEnd
Gate upper limit.
gateUpperLimit
{F8DFE559-ADA7-4947-8207-604FEEF7807A}
Maximum efficiency active power at maximum head conditions.
maxHeadMaxP
{9DDEDD01-FED7-4702-8C77-2F953107A7FD}
Maximum efficiency active power at minimum head conditions.
minHeadMaxP
{E761D565-2AAC-41f6-9D30-3DFFFF11EBEA}
Rated speed in number of revolutions. The attribute shall be a positive value.
speedRating
{A1F6B52E-13C8-4422-B314-31C7450BC0FB}
Speed regulation.
speedRegulation
{D59C0A8B-F4E3-432b-9809-157934B00C0F}
Transient droop time constant.
transientDroopTime
{B57DCA5C-64B9-43ba-94AB-E03D5848E150}
Transient regulation.
transientRegulation
{36E50ED7-D493-41e7-83F7-944A9FCC05A7}
Rated turbine active power. The attribute shall be a positive value.
turbineRating
{A3FA8BFD-6022-45e5-8FED-09082CF033FC}
Type of turbine.
turbineType
{F57E682E-9BC6-41ce-8566-C0CC08E30A48}
Water starting time.
waterStartingTime
{A405790B-074F-441d-B7CD-AE5818D76533}
Kind of hydrospheric analog.
kind
{01D4ACA7-1A34-4942-A956-09C303B9DF9E}
Bilateral table agreement that includes the informational message.
TASE2BilateralTable
{D286EEBB-4C7C-449f-8621-C35CE7904696}.SupplierEnd
Indicates if the Point is global scoped e.g. VCC or accessible only to the Bilateral table peer e.g. ICC.
scope
{8ED16BF5-7CC8-4e3b-8FE1-11C8455AF042}
Provides information regarding the access privileges allowed to the ICCP Point.
accessPriviledge
{F0A85B7D-074A-412d-8E63-4FDB313F5FA9}
Specifies the type of ICCP quality that will be conveyed as part of the ICCP Point.
pointQuality
{82B1178E-ED69-4116-8D6B-8FEAD66C9BC2}
Indicates the ICCP Point type that is to be conveyed.A CIM AccumlatorValue shall be mapped to an ICCP real.A CIM AnalogValue shall be mapped to an ICCP real.A CIM DiscreteValue shall be mapped to either an ICCP real state stateSupplemental or either protection event type.A CIM StringMeasurementValue does not have a standardized mapping.
pointType
{F2BADF24-7697-4aa5-866E-C58D0F4CD4E7}
Indicates if the Point is global scoped e.g. VCC or accessible only to the Bilateral table peer e.g. ICC.
scope
{C5080713-CF50-4d85-9B8B-8BB69C33C65F}
Specifies the expected security mechanism per IEC 623514 to be utilized.
applicationSecurityRequirement
{637A7E23-1FF3-410b-A39B-5F676EDDE97B}
Edition of IEC standard.
standardEdition
{585CC50D-21F9-440d-ABE6-2D3D0704FBC4}
IEC standard number.
standardNumber
{0C85B647-C34F-470e-B7D6-25AEA75D63E6}
Edition of IEEE standard.
standardEdition
{FD546E83-49E5-4d47-B13D-08A13B74DB6E}
IEEE standard number.
standardNumber
{72D3AE93-F639-43e0-B530-A65D534C57D9}
Bilateral ICCP point for the measurement or control.
BilateralToIOPoint
{D2E53A93-0C08-4243-8A32-01EF61C12DBB}.SupplierEnd
Local merasurement value source for an ICCP point.
IOPointSource
{F40144F0-7CF5-4813-9870-55D84B003374}.ClientEnd
ICCP point for a local measurement value source.
IOPoint
{F40144F0-7CF5-4813-9870-55D84B003374}.SupplierEnd
IP address type.
addressType
{83E31300-ECA0-4c28-8A25-D0B0C19F6ED6}
Edition of ISO standard.
standardEdition
{C2FB345E-2A1C-4b48-9EA2-BEF5D3C70E7A}
ISO standard number.
standardNumber
{3EF36699-DC51-44c9-81A1-09C19A488257}
Certificate to be bound for use for Application layer mutual authentication.
UpperLayerPublicX509Certificate
{5562C131-015C-4469-BB74-1B33BA1A81D9}.ClientEnd
CSCtype1
{339D9BE1-B6FE-4ebd-B884-707C77DA6C91}.SupplierEnd
Delay
{F80046F2-833E-473c-81F7-F2217DD56589}.ClientEnd
VDCOL
{D9D8D23C-3E4B-4af0-B456-954687DFA9E6}.ClientEnd
The diagram objects that are associated with the domain object.
DiagramObjects
{03423B70-34E0-4313-B19B-5FAFFD1F143B}.SupplierEnd
Dataset containing the data objects.
InstanceSet
{8740E742-45B5-4b82-8058-EFA19A56A689}.SupplierEnd
All names of this identified object.
Names
{203C47E2-30FB-4c8f-ABEA-1661621CC0A7}.ClientEnd
The single CIM data object in the appropriate dataset context.
PropertiesCIMDataObject
{F527D24E-59B1-4748-B31A-660841060493}.ClientEnd
Data objects registered.
TargetingCIMDataObject
{950EB9DD-F3F6-405e-81C4-3D00B3ABD338}.ClientEnd
CSCtype1
{2F9E4B3A-A9A7-43b4-8FAD-55865942D1B6}.SupplierEnd
multiplier
{92990EDC-2F54-42c3-8F99-B78E953C4A09}
unit
{B16F7D93-D30C-49a4-8E27-369431523B0A}
A control area can have one or more net inadvertent interchange accounts
SubControlArea
{3CB78F17-FFCF-48bc-835B-C78BF0FB4994}.SupplierEnd
All notifications for a customer related to the status change of this incident.
CustomerNotifications
{F292A647-3328-43e1-AA6F-08A42730AF41}.SupplierEnd
All hazards associated with this incident.
IncidentHazard
{68AE0E00-0724-4e70-981A-2F27766EAF3E}.SupplierEnd
Location of this incident.
Location
{92317947-BF8F-4e74-A2A0-4C97EDA82DD0}.SupplierEnd
Outage for this incident.
Outage
{91D33A1C-B14C-40a2-8C56-19764D00E571}.SupplierEnd
Operator who owns this incident.
Owner
{C2056AB7-C6BB-48a9-9AC4-CC384465DB27}.SupplierEnd
TroubleOrder
{3D79F2D5-BE8F-4d59-A6FE-14060E81D5FA}.ClientEnd
All trouble tickets reporting this incident.
TroubleTickets
{604AF98C-C65C-46ec-828D-96FE5F906C35}.ClientEnd
UnplannedOutage
{F41F931E-15E0-43ea-9BBE-8F6DB650B1D9}.SupplierEnd
All works addressing this incident.
Works
{49B9A841-26C8-423d-94AD-33ADD3293D00}.SupplierEnd
Incident associated with this hazard.
Incident
{68AE0E00-0724-4e70-981A-2F27766EAF3E}.ClientEnd
Trouble ticket associated with this hazard.
TroubleTicket
{F1DCAE08-2CD6-4c12-9B22-D06B9E9DAA02}.ClientEnd
IncrementalDataset
{4727D339-3136-4719-B7FF-3F8D5D00B334}.SupplierEnd
IncrementalDatasetArgDescription
{343EFB4F-6622-4258-9EC1-BCB257B0ECB8}.SupplierEnd
The incremental dataset used for this argument instance.
IncrementalDatasetArg
{343EFB4F-6622-4258-9EC1-BCB257B0ECB8}.ClientEnd
A thermal generating unit may have an incremental heat rate curve.
ThermalGeneratingUnit
{44777851-6FBC-4f50-AF92-1EA11CE04CA8}.SupplierEnd
CongestionArea
{6DB2691B-152F-462d-B727-DE871F8AAB7A}.ClientEnd
GenDistributionFactor
{1A518B75-8859-4a3f-AB51-3C3CD3B54E95}.SupplierEnd
LoadDistributionFactor
{3F23D218-E902-4629-B47B-6E2F216E85DF}.SupplierEnd
MktConnectivityNode
{2B0FBC3E-406E-4d8b-A02A-36C41F9A1D0E}.SupplierEnd
PnodeDistributionFactor
{24E9F23C-430E-4596-B763-07DB8054801D}.SupplierEnd
multiplier
{DF6B0AAC-52CD-4c60-8800-409FE83F07D1}
unit
{7668DEE2-8EA2-47c3-9C02-E4B53F39569C}
multiplier
{F05ABE27-834D-45c9-AD64-4B7F0EC4DC73}
unit
{AD33BEF6-443E-4d2c-A32A-9152AEB8D250}
A reservoir may have a natural inflow forecast.
Reservoir
{390FA231-DEA9-4f7c-9E58-9EA15F9F2F0C}.SupplierEnd
Kind of analog representing inspection result.
kind
{223CD58E-7581-423f-9A39-FAC7937B528C}
AccordingToSchedules
{37ACB8AF-5C2E-4faa-8C9D-87E718507CBD}.ClientEnd
Kind of discrete representing inspection result.
kind
{F24FF102-2B32-41ed-97BD-90FFF1EE7382}
The role of a dataset in the context of an operation.
DatasetArg
{5B31BEB7-2629-4c5a-B015-4D2B871D04D9}.ClientEnd
Data objects contained in the dataset.
InstanceSetMember
{8740E742-45B5-4b82-8058-EFA19A56A689}.ClientEnd
ActualDemandResponseEvents may exist that are not part of a cordinated MarketActualEvent associated to a Market. These ActualDemandResponseEvents can have many InstructionClearing Instructions for specified RegisteredResources or Distributed Energy Resource type of AggregateNodes.
ActualDemandResponseEvent
{7B14AF42-A7C8-4839-AEBA-18F104ABE94C}.ClientEnd
Instructions
{B51C2A99-4E92-4961-A6C0-F5BB918A2A32}.ClientEnd
ResourceDeploymentStatus
{23E96A97-D54D-4d70-8585-71267B61B888}.SupplierEnd
DopInstruction
{21EAE1E5-554D-4e8e-BE91-8FB6E528D842}.SupplierEnd
DemandResponseActualEvent
{01022165-D079-41fa-B9C3-342CFFA5E537}.ClientEnd
DotInstruction
{CEC60D6E-B919-43a0-9B3B-92AE42278138}.SupplierEnd
Indication that the system is currently operating in a contingency mode.
contingencyActive
{053E4E87-A262-4b01-85C2-561E03435F2B}
dispatchMode
{16F39C62-17F5-4ecb-9626-F74D211EDBD1}
AggregateNode
{917AB6A6-8808-4d28-B5EB-217844E5D8B1}.SupplierEnd
InstructionClearing
{B51C2A99-4E92-4961-A6C0-F5BB918A2A32}.SupplierEnd
RegisteredResource
{7B076588-700D-4bbc-80C9-CA48511DE042}.SupplierEnd
bindingInstruction
{92EF9110-493F-45e2-9DAD-96940A666F62}
instruction source for market quality results INS ACT
instructionSource
{840886A3-DD5B-4c03-A1D3-044812FB88A9}
Indicator of either a StartUp or a ShutDown.
instructionType
{44F83183-5D66-47d1-9ADC-5A120C320B6F}
Manually Blocked Indicator YesNo. The instruction has been blocked by an Operator.
manuallyBlocked
{384324F4-53D6-4332-93F2-EBB059193AFF}
updateType
{56B266F3-BF55-4817-BF75-EF207B49D688}
Unit multiplier of this quantity.
multiplier
{286F4EA7-EFD2-4fdc-B949-CA5DBE502F0A}
Unit of this quantity.
unit
{FA3EBEDD-32A3-4c7e-AA72-8F6A20C0DE4A}
RampRateCurve
{1BDCCD9A-FE44-4136-9A38-58893BFCA0AA}.SupplierEnd
RegisteredInterTie
{E8B2FD01-4BC1-4e68-B739-26E746DDB71F}.SupplierEnd
InterTieResults
{CD0BFC1C-1DAF-4569-BDDF-9FD9518B3A7E}.SupplierEnd
RegisteredInterTie
{C1ECE446-41CB-4935-9DD9-BB8E3EA8F832}.ClientEnd
The accept status submitted by the responder. Valid values are NONRESPONSE ACCEPT DECLINE PARTIAL.
acceptStatus
{E9B4D769-DED5-4bbd-8842-9907CFD756F8}
Part of the Composite key that downstream app uses to match the instruction
passIndicator
{1D66B497-93F3-4b21-A024-44DA0D6F6F62}
Flowgate
{E8AB91AD-788A-4426-BCAB-5F8132B26BE5}.ClientEnd
InterTieClearing
{CD0BFC1C-1DAF-4569-BDDF-9FD9518B3A7E}.ClientEnd
InterchangeSchedule
{C18B28C7-505A-47a1-861A-9B8EC4C4FAA8}.ClientEnd
InterTie
{F470E1A6-33AE-4803-A2CA-A8627C7D6956}.SupplierEnd
InterchangeETCData
{C18B28C7-505A-47a1-861A-9B8EC4C4FAA8}.SupplierEnd
RegisteredInterTie
{EB89CB04-1946-4823-B7D2-6E517A703273}.SupplierEnd
To indicate a check out type such as adjusted capacity or dispatch capacity.
checkOutType
{0DE58477-5040-4bfa-9EDB-F556A29E971C}
Import or export.
directionType
{9CA5B0A9-5F61-465f-9507-78F104392696}
Energy product type.
energyType
{3B444EC5-D5A8-466d-BECB-A8679D350E3C}
Market type.
marketType
{5A41A1C6-CA1B-4a6d-81FF-87C5D3CC2AAD}
Schedule type.
scheduleType
{2062604B-81D8-4b65-9021-C65259115BDE}
RegisteredResource
{6E8D1E08-8516-4936-BA3D-566DD94BE286}.ClientEnd
CurrentEmergencySI
{BEFB4486-B77B-4cd6-A9AD-9D7F2906C32F}.ClientEnd
CurrentScheduledInterchange
{25FE6285-FBFC-4387-9CFA-5A909EABEF8D}.ClientEnd
Bushings to which the fixed contacts of this interrupter isare attached. Some interrupters have one fixed and one moving contact some have 2 fixed contacts some 2 moving contacts. An interrupter will have relationships with 2 bushings and those relationships may be any combination of the FixedContact and MovingContact associations.
Bushings to which the moving contacts of this interrupter isare attached. Some interrupters have one fixed and one moving contact some have 2 fixed contacts some 2 moving contacts. An interrupter will have relationships with 2 bushings and those relationships may be any combination of the FixedContact and MovingContact associations.
Bushing
{04E4A3E7-BA8B-450c-A235-995CEAB16935}.SupplierEnd
{C2A54CC4-02E6-4205-BF7A-A8BAE99CDBAA}.SupplierEnd
Breaker mechanism controlling this interrupter.
OperatingMechanism
{DA02B460-9B93-4dff-AF33-7056DC71BA82}.ClientEnd
Interrupting medium.
interruptingMedium
{203BEC08-AB3F-4e25-8BE4-6B14B92E7006}
Interval reading contained in this block.
IntervalReadings
{0DE6A2FC-3A1D-4025-9791-0BDC1FE70873}.SupplierEnd
Meter reading containing this interval block.
MeterReading
{15942C2F-68E7-46d2-88D4-0C74530EE8E5}.SupplierEnd
Pending calculation to apply to interval reading values contained by this block after which the resulting reading type is different than the original because it reflects the conversion result.
PendingCalculation
{6805BD0C-43D7-4b31-81D9-807FDA537C71}.SupplierEnd
Type information for interval reading values contained in this block.
ReadingType
{5E2DE546-E491-4480-879B-2607C691B257}.SupplierEnd
All blocks containing this interval reading.
IntervalBlocks
{0DE6A2FC-3A1D-4025-9791-0BDC1FE70873}.ClientEnd
The point data values that define a curve.
TimePoints
{73F6489D-7DA0-44ef-8CC9-D8AF413DAC53}.SupplierEnd
An IrregularTimePoint belongs to an IrregularIntervalSchedule.
IntervalSchedule
{73F6489D-7DA0-44ef-8CC9-D8AF413DAC53}.ClientEnd
The time is relative to the schedule starting time.
time
{7F344F9D-2DFC-4f89-9CA5-0AB59385A201}
All documents for this issuer.
Documents
{D3F6B3FF-697C-4b9b-845F-66D92692128D}.SupplierEnd
Configuration of joint.
configurationKind
{D84F2B73-EA32-4eaf-8105-5A5C411E3AB0}
Material used to fill the joint.
fillKind
{75D4C599-4E0E-4ae6-8322-7F99A1D12C96}
Action taken with this jumper.
JumperAction
{A665FDB4-D392-4791-8A37-99C6494742D4}.ClientEnd
The line segment that this jumper action will affect. This is the only way to access relationship to clamp in case the jumper needs to connect along the line segment.
ACLineSegments
{9581D491-DFD1-477b-A1F8-56207CB6A28F}.SupplierEnd
Clamp
{74BBE709-CFEF-40a9-A120-33F704608576}.ClientEnd
Conducting equipment is affected when the jumper action connects one or both ends of a jumper to the conducting equipment. If the jumper action involves placing one or both ends of a jumper anywhere along a line segment you must use the clamp to get the distance from one terminal using the explicit relation with clamp. In the case of placing one or both ends of the jumper at a line segment terminal reference to one or more line segments is sufficient.
JumpedEquipments
{4D35C940-C8A8-4a53-846A-929278E1DB57}.SupplierEnd
Jumper on which this action is taken.
Jumper
{A665FDB4-D392-4791-8A37-99C6494742D4}.SupplierEnd
Switching action to perform.
kind
{5C8EEC22-6AC5-4ca3-8117-FE471700B406}
multiplier
{633D88B5-13E1-4dd6-8CBF-61A5DE5E46FE}
unit
{7150BC2B-A31A-4c34-8BB8-C5FAEC099C84}
Test lab which produced this set of lab test results.
AssetTestLab
{2E1C1072-F34D-447f-A661-8FC9A06E3F6D}.SupplierEnd
Specimen on which lab testing done in determining results.
Specimen
{C2DD4DA1-4B26-4df0-8A58-EA8BE7DC80D4}.SupplierEnd
Reason for performing test.
reasonForTest
{8FB67C6B-F023-4b3d-B021-843DE4BB093E}
ErpPersons
{A04894E3-14E3-4cfe-B0D3-57701085ACBE}.ClientEnd
WorkCostDetail
{955B011F-CCEE-4126-A607-513F05388ADE}.SupplierEnd
WorkTask
{FDB3A56B-46C4-4591-A0EA-AA7F58E3236A}.ClientEnd
Total cost for labor. Note that this may not be able to be derived from labor rate and time charged.
cost
{3873F482-0558-4407-A2DF-271244BE21E9}
Time required to perform work.
laborDuration
{CDC2AF11-6EE9-411c-8A3C-01413EFB0DFF}
The labor rate applied for work.
laborRate
{D8E44A34-BF06-49cf-ADAF-6B45466D31C6}
status
{E6AEDA33-EC3C-4a08-B05F-54600691B920}
Edition of Laborelec standard.
standardEdition
{F1099835-5A56-449d-B391-E45364A57BF2}
Laborelec standard number.
standardNumber
{D18A07C1-E5F8-4d97-953E-4B0847C37367}
AssetContainers
{658256E1-9CC7-4618-861D-E2D5F2458763}.SupplierEnd
ErpOrganisationRoles
{125BFBC7-E66A-4486-A898-CE2D1087BB13}.SupplierEnd
ErpPersonRoles
{E882A219-E4D5-4259-AD38-2754C0D502A2}.SupplierEnd
ErpSiteLevelDatas
{86405B23-FBDA-4f53-A547-5BE7134DF39C}.SupplierEnd
All location grants this land property has.
LocationGrants
{C759CAEB-F5C3-465e-97E7-310578A2EE42}.SupplierEnd
The spatail description of a piece of property.
Locations
{ACFA3E19-34F0-4388-A1A3-CF9E27854574}.SupplierEnd
All rights of way this land property has.
RightOfWays
{EB5019C4-5ACE-4ae3-BA94-0695131D9A29}.ClientEnd
Demographics around the site.
demographicKind
{6CE69ADE-D00D-4c72-A88D-B83ACFE99914}
Kind of land property categorised according to its main functional use from the utilitys perspective.
kind
{19EC9B8D-AEEA-4f46-BE1B-240FD53D9781}
status
{527490A6-7D55-44b3-8B46-A187C91F0209}
multiplier
{7E3DD904-59E9-4a23-8877-756089992413}
unit
{3D6E3075-6B8A-44df-9D89-B4713FE7BDAC}
A reservoir may have a level versus volume relationship.
Reservoir
{1CA34C6F-D018-451a-B9BA-91A089FCA0F8}.SupplierEnd
Likelihood that strike fell within errorEllipse.
errorEllipseConfidence
{612A2FC7-6BED-4589-9006-6F974398B2FF}
Length of major semiaxis longest radius of the error ellipse.
errorEllipseMajorSemiAxis
{B21AA3B7-F1CE-4b83-BDA0-79AF0B9B9466}
Length of minor semiaxis shortest radius of the error ellipse.
errorEllipseMinorSemiAxis
{B51075A5-F832-4ae4-A64F-D284B630B623}
The orientation of the major semi axis in degrees from True North.
errorEllipseOrientation
{C59923E9-97B3-4034-9115-48EE9BF34DBC}
Peak current of strike.
peakAmplitude
{CCD211E7-E954-44fa-80E2-37C50425C968}
Procedures
{B58288B5-634A-4da2-AF81-FC8EE0EB0F45}.ClientEnd
The equipment for which this limit dependency model is organized under.
Equipment
{CEF63A20-BB9F-4d20-85B7-C4EF0AB5624F}.SupplierEnd
The operational limits to which this limit dependency model applies.
OperationalLimit
{930C423F-F107-4857-A500-C7D5C97E88CB}.ClientEnd
SourceOperationalLimit
{312BBC54-9F5A-4000-8A02-754DB702EB90}.SupplierEnd
The associated source limit is scaled by this value to compute the limit of the dependency model.
limitScalingPercent
{A5FE7CA4-6641-485d-A9C6-8E5BE591EA3B}
The subgeographical region of the line.
Region
{BAB73169-D3BE-43c3-A58B-F1B87EAA1239}.ClientEnd
Amount for this line item.
amount
{70BAF500-3C22-48cc-98F0-4ED38C0A4B3E}
Totalised monetary value of all errors due to process rounding or truncating that is not reflected in amount.
rounding
{174ABABE-C74F-4683-BDC3-BF78EAFFC3B4}
The line segment of this line fault.
ACLineSegment
{BBA661BB-92B7-4934-988B-DF65931690EE}.SupplierEnd
The length to the place where the fault is located starting from terminal with sequence number 1 of the faulted line segment.
lengthFromTerminal1
{39244DFF-5709-4fd8-AE0A-F5BA2C171329}
Zero sequence shunt charging susceptance per section.
b0PerSection
{18D033B2-4A27-4254-8F20-5442D0E163E7}
Positive sequence shunt charging susceptance per section.
bPerSection
{295441F9-63A5-4222-894E-F64C29A24C5E}
Zero sequence shunt charging conductance per section.
g0PerSection
{2D5E2E4F-C07A-4000-BD54-C5FBF7B99D7A}
Positive sequence shunt charging conductance per section.
gPerSection
{DAB7E864-95F0-4325-B595-3997057DD82F}
Susceptance per section of the phase if shunt compensator is wye connected. Susceptance per section phase to phase if shunt compensator is delta connected.
bPerSection
{5E420ADA-58AC-48a1-BE11-10AC64D4F407}
Conductance per section for this phase if shunt compensator is wye connected. Conductance per section phase to phase if shunt compensator is delta connected.
gPerSection
{5FE8AC9E-7752-476f-9F1E-FE43FAA0B288}
Aggregate motor dynamic load associated with this aggregate load.
LoadMotor
{4492B845-85C0-4825-8D06-D03F4BBCDF4A}.ClientEnd
Aggregate static load associated with this aggregate load.
LoadStatic
{4C437CDA-D82C-4512-ADA6-9B94A96DF087}.ClientEnd
The SubLoadAreas in the LoadArea.
SubLoadAreas
{985B4F6F-A487-4691-9470-6EE3C9636DC8}.SupplierEnd
AreaLoadBid
{66BF4185-41CD-43e2-8659-871C1A781082}.ClientEnd
LoadReductionPriceCurve
{6CFF5725-EC18-4ea2-A12C-2D2ECE52DD51}.SupplierEnd
RampRateCurve
{AD8B5072-D22F-4473-AF99-5A6CD5C52809}.SupplierEnd
RegisteredLoad
{4D1C0118-19FE-4b30-B956-5BEF77F618EE}.ClientEnd
Maximum rate that load can be reduced MWminute
dropRampRate
{F02D2AE9-01E5-4aaf-8514-2AFD109C8F16}
load reduction initiation cost
loadRedInitiationCost
{DFF2667B-6568-4423-9DAF-6A1B088E5353}
Minimum MW load below which it may not be reduced.
minLoad
{3BD81119-B627-46f3-9DD3-AEA9CFD0FAEC}
Minimum MW for a load reduction e.g. MW rating of a discrete pump.
minLoadReduction
{9B453547-9F05-454c-B3BE-E076741D4999}
Cost in at the minimum reduced load
minLoadReductionCost
{6895F631-C303-48ab-B972-323D15EE7B32}
Maximum rate load may be restored MWminute
pickUpRampRate
{6D8F4BDB-469D-44d3-A900-74DB99BC8097}
The fixed cost associated with committing a load reduction.
shutdownCost
{30A20BCC-4547-4ec1-BFE0-27CF0FE3D562}
Inertia constant iHi gt 0. Typical value 25.
h
{51D2BF52-33B6-40d5-99E3-8BA27720D977}
AggregatedPnode
{1E748A16-16A1-4251-B7F2-5AB41F4B8AB1}.ClientEnd
DistributionFactorSet
{49BDACA6-0568-4346-BD7A-07BB3DE08C0C}.ClientEnd
IndividualPnode
{3F23D218-E902-4629-B47B-6E2F216E85DF}.ClientEnd
Energy consumer to which this dynamics load model applies.
EnergyConsumer
{4F34241A-F054-4f5c-8638-560DED3C98B4}.SupplierEnd
RegisteredResource
{3C97A30C-33B1-4e87-8AAE-BC2568E2F4BD}.ClientEnd
RegisteredResource
{D80F6DFF-96C2-4687-ABA8-88B11C00DF6E}.SupplierEnd
updateType
{4319F9CF-E227-4ef7-BF28-34D73D33C75C}
Type of generic nonlinear load model.
genericNonLinearLoadModelType
{0EC63AF7-FC07-4c14-A043-DBB66B7A86FA}
Time constant of lag function of active power iTiisubPsubi gt 0.
tp
{63971A4F-C775-4c11-BD27-ECA0D8DA093E}
Time constant of lag function of reactive power iTiisubQsubi gt 0.
tq
{9B0A9261-37AA-4035-BA52-310ABC78830C}
The SubLoadArea where the Loadgroup belongs.
SubLoadArea
{6910F2B1-E481-496a-91B7-7AAA14F6D47E}.ClientEnd
Aggregate load to which this aggregate motor dynamic load belongs.
LoadAggregate
{4492B845-85C0-4825-8D06-D03F4BBCDF4A}.SupplierEnd
Inertia constant iHi gt 0. Typical value 04.
h
{F0FD1C52-0775-434a-9500-FB4301BC7E34}
Transient reactance iLpi. Typical value 015.
lp
{CFCCAC01-5A98-46bd-8114-530A5D13C6B1}
Subtransient reactance iLppi. Typical value 015.
lpp
{B75DCE7C-EE1B-4f60-909D-64CD5F999CFD}
Synchronous reactance iLsi. Typical value 32.
ls
{A7D4FF09-5F6C-4cf3-8D09-A1ECC0B90A8B}
Stator resistance iRai. Typical value 0.
ra
{2EBF719B-7221-43f6-89D0-2262283F223F}
Circuit breaker operating time iTbkri gt 0. Typical value 008.
tbkr
{F3B08BB9-8193-4eb0-B62C-DFBB9AC72F0E}
Transient rotor time constant iTpoi gt 0. Typical value 1.
tpo
{31ACC981-C4AC-45bd-8CA1-01B3F8B3B1BA}
Subtransient rotor time constant iTppoi gt 0. Typical value 002.
tppo
{FFCCD719-96F8-4d29-88AE-7AC5107217C7}
Voltage trip pickup time iTvi gt 0. Typical value 01.
tv
{8D2E6339-44AA-470f-9644-7978BEDD30BD}
Voltage threshold for tripping iVti. Typical value 07.
vt
{8DB2CEC8-F4C3-486a-82BD-040623B3666F}
SchedulingCoordinator
{1F7B041F-E74A-417c-95DE-6C226FA9485B}.SupplierEnd
Share in percentage of total Market load for the selected time interval.
share
{3EBCC71D-EDAE-430f-99F2-C938741EC06A}
LoadBid
{6CFF5725-EC18-4ea2-A12C-2D2ECE52DD51}.ClientEnd
The set of loads that have the response characteristics.
EnergyConsumer
{ABB1EF4C-2A3F-4c47-8D73-B51ADA827E97}.ClientEnd
Aggregate load to which this aggregate static load belongs.
LoadAggregate
{4C437CDA-D82C-4512-ADA6-9B94A96DF087}.SupplierEnd
Type of static load model. Typical value constantZ.
staticLoadModelType
{F78BA2E0-BA77-4658-BF2D-6EE1BEA7A2F1}
Parameter of this proprietary userdefined model.
ProprietaryParameterDynamics
{42F5637B-59FE-4442-AC86-EC1605637C40}.ClientEnd
RTO
{E6D2764A-B166-47aa-85A1-8B82794864DB}.ClientEnd
RegisteredGenerator
{2AFCD919-E0B4-402b-9374-D1683A531031}.SupplierEnd
All assets at this location.
Assets
{1547DDC4-B4CB-4406-B642-4E0337FC4594}.ClientEnd
All configuration events created for this location.
ConfigurationEvents
{5A4A6C15-ADB0-446d-8CFE-0DE670D4800F}.SupplierEnd
Coordinate system used to describe position points of this location.
CoordinateSystem
{D9DB79D8-27F1-4071-9C79-F0F1F62B4F18}.SupplierEnd
Crew
{5396B10B-F4AB-46c8-B558-A0D64090E603}.SupplierEnd
Crews
{9F98B054-8439-4bd9-8F2E-43422494EFE5}.ClientEnd
Kind of environmental location which this location is.
EnvironmentalLocationKind
{153D33F0-C3EC-4cda-8188-6776F6BD789B}.ClientEnd
Monitoring station located at this location.
EnvironmentalMonitoringStation
{17713B5C-F047-400e-ADE7-5B55F485CA85}.ClientEnd
Fault
{7F84E357-68DD-4257-BD11-EE226FADA1E6}.ClientEnd
All asset hazards at this location.
Hazards
{A7C698DB-6096-423a-918E-5D26CD309E44}.ClientEnd
Incident at this location.
Incident
{92317947-BF8F-4e74-A2A0-4C97EDA82DD0}.ClientEnd
LandProperties
{ACFA3E19-34F0-4388-A1A3-CF9E27854574}.ClientEnd
Measurements
{F582AAC6-446D-49be-9380-09E21CAA0CCF}.SupplierEnd
OutageOrder
{5D0E1B69-67C1-469c-B013-AE8901A8B015}.ClientEnd
Sequence of position points describing this location expressed in coordinate system Location.CoordinateSystem.
PositionPoints
{DBF35456-ABE1-4deb-A885-2E48B3D6F8F6}.SupplierEnd
All power system resources at this location.
PowerSystemResources
{9F4B30FA-0A66-4ce4-9A00-413B0DB058C7}.SupplierEnd
Routes
{BD8B4DA4-D676-478b-B855-5DB85DFFDB26}.ClientEnd
SwitchingOrder
{4909DE0B-FF1E-4cd5-8339-71D4430BBEF1}.SupplierEnd
TroubleOrder
{2BE0988C-AEEE-43e6-9FB2-B3C811465CE1}.ClientEnd
Electronic address.
electronicAddress
{27DF32EF-8F8F-437d-8C52-A9AEF3D04CE9}
Main address of the location.
mainAddress
{44CF2281-A210-4c5a-A26A-D802302AA58D}
Phone number.
phone1
{35C3E445-F094-4720-8C8E-FC83D922CD89}
Additional phone number.
phone2
{B2B17DA4-F097-4a16-B416-353F451C0A78}
Secondary address of the location. For example PO Box address may have different ZIP code than that in the mainAddress.
secondaryAddress
{A1C7D128-217A-4d61-90BF-7ACFB4216F92}
Status of this location.
status
{716A4DAA-ED9F-42f4-8AD2-C1B6DBB88896}
Land property this location grant applies to.
LandProperty
{C759CAEB-F5C3-465e-97E7-310578A2EE42}.ClientEnd
LossClearingResults
{9EC3534E-B7AC-4cc1-B1A2-D7CAD11E98DD}.SupplierEnd
HostControlArea
{AD728487-11BF-4cf9-8208-EB973AA30251}.ClientEnd
LossClearing
{9EC3534E-B7AC-4cc1-B1A2-D7CAD11E98DD}.ClientEnd
RUCZone
{28810405-AFDC-42b6-889E-E5634F47D761}.ClientEnd
SubControlArea
{609C0491-3062-444d-9F49-61791CBD647B}.SupplierEnd
An EnergyTransaction may have a LossProfile.
EnergyTransaction
{0E272DF7-73BF-495c-AEAE-1F184C3A0031}.SupplierEnd
Part of the LossProfile for an EnergyTransaction may be a loss for a TransmissionProvider. If so the TransmissionProvider must be one of the participating entities in the EnergyTransaction.
HasLoss_
{A0E07F75-BF34-4a53-91DA-8AC7F9199E13}.SupplierEnd
MktConnectivityNode
{BAB096FD-2D2E-4088-887E-124132BB99A0}.SupplierEnd
LMPMFinalFlag
{12C50657-2A30-4f30-91A7-F81207258D35}
MPMTestResults
{8F96A178-A65F-4a2f-9906-0E01C5028264}.SupplierEnd
SMPMFinalFlag
{C34F8682-0D24-49a2-B6B4-115AC644A903}
mitigationOccuredFlag
{F4B0EB6A-3B29-4e91-8A3C-6B2FE008D142}
MPMTestCategory
{F2AACF8A-1162-4769-8B44-79E4491F3254}.ClientEnd
MitigatedBidClearing
{E48948D6-38C5-4c7b-8933-F5947320697F}.ClientEnd
RegisteredResource
{606C8F33-4FFF-4ea5-A5B5-CEB460B07A57}.ClientEnd
MPMResourceStatus
{F2AACF8A-1162-4769-8B44-79E4491F3254}.SupplierEnd
MPMTestResults
{BE5BB481-4AB2-4a4b-8C64-B3875DA5546C}.SupplierEnd
MPMTestThreshold
{5D041FF2-6CFE-4b89-B8AC-DF1E41386754}.SupplierEnd
Nature of threshold dataM Mitigation thresholdR Reporting threshold
purposeFlag
{AD384B1A-B6ED-4880-9AE2-B3217FBD9A64}
1 Global Price Test2 Global Conduct Test3 Global Impact Test4 Local Price Test5 Local Conduct Test6 Local Impact Test
testIdentifier
{EFE3B0F6-6342-4694-A875-850D9384E4C0}
The method of performing the market power monitoring. Examples are Normal default thresholds or Alternate thresholds.
testMethod
{02EFC8E3-3783-4f65-834F-863DB41EBDD5}
AggregatedPnode
{C0382101-491D-471a-B6BD-412F2E2BEFE1}.ClientEnd
MPMClearing
{8F96A178-A65F-4a2f-9906-0E01C5028264}.ClientEnd
MPMTestCategory
{BE5BB481-4AB2-4a4b-8C64-B3875DA5546C}.ClientEnd
Used to show the Margin result of the Impact test
marginPercent
{CB16FFD1-D63F-4ccc-85CB-A24610675CDE}
The results of the test. For the Price Impact and Conduct tests typical values are NA Pass Fail Disable or Skip.
outcome
{9B184A03-B407-4be3-A732-7A3FEBAFB186}
AggregatedPnode
{3A9890C7-0792-48c5-BE74-53A2FA81C59A}.SupplierEnd
MPMTestCategory
{5D041FF2-6CFE-4b89-B8AC-DF1E41386754}.ClientEnd
RegisteredResource
{BEDAF373-FFF3-488c-94D4-242E91A60CFB}.SupplierEnd
Market Type DAM RTM
marketType
{DB981E2A-6A80-485c-A814-D14A1B513C40}
Price Threshold in
percent
{0750D9AA-DBCC-4749-ABE7-1D613A27DF3B}
Price Threshold in MW
price
{A6610301-EBD1-40c1-8FAF-82505741C767}
MeteredSubSystem
{A5BC78A9-02B6-4693-833B-5988046C9A07}.SupplierEnd
RTO
{42061DAA-FC2A-4510-A0B6-81F8DDD07587}.SupplierEnd
Charge for Emission Costs Start Up Costs or Minimum Load Costs.
costRecovery
{9A176D4F-6DFB-416f-97B3-80B920630ECC}
MSS Load Following may select Net vs. Gross settlement. Net Settlement requires the net Demand settled at the MSS LAP and Net Supply needs to settle at the equivalent to the weighted average price of the MSS generation. Gross load will be settled at the System LAP and the Gross supply will be settled at the LMP. MSS Aggregation that elects gross settlement shall have to identify if its resources are Load Following or not.
grossSettlement
{8D3502CE-C109-4679-A24D-EEF5A8C262C2}
Provides an indication if losses are to be ignored for this zone. Also refered to as Exclude Marginal Losses.
ignoreLosses
{DB2547D7-7FA4-485d-B341-F560E31635E0}
Provides an indication if marginal losses are to be ignored for this zone.
ignoreMarginalLosses
{E4B1E2B6-C61C-4233-82B4-19C63EE950D3}
Indication that this particular MSSA participates in the Load Following function.
loadFollowing
{C5E15E5D-E3DC-4f5b-BAE9-9195BDEF79A0}
Indicates that RUC will be procured by the ISO or self provided.
rucProcurement
{5BDF1B45-574F-4bfd-ABF8-C870D2C7DE2A}
MeteredSubSystem
{92A84479-AD05-4df5-BE48-E000CB70D4B3}.ClientEnd
Provides an indication if losses are to be ignored for this metered subsystem zone.
ignoreLosses
{6DC4E554-BE3F-4d2d-8336-B1E48773AC3B}
Metered SubSystem MSS Load Following may select Net vs. Gross settlement. Net Settlement requires the net Demand settled at the Metered SubSustem MSS Load Aggregation Point LAP and Net Supply needs to settle at the equivalent to the weighted average price of the MSS generation. Gross load will be settled at the System LAP and the Gross supply will be settled at the LMP. MSS Aggregation that elects gross settlement shall have to identify if its resources are Load Following or not.
rucGrossSettlement
{CC1E3B2B-0887-4b24-B5EC-A75900C98C3A}
SecurityConstraintLimit
{B2755079-F601-4879-9341-AAF0FDCD8B1B}.ClientEnd
multiplier
{0E5F2BFD-8703-49fc-B826-41CE003DBC98}
unit
{5C9C7A55-729A-4981-8F1D-AD83C2E569B2}
Change in the disturbance storm time Dst index. The size of a geomagnetic storm is classified as moderate 50 nT gtminimum of Dst gt 100 nT intense 100 nT gt minimum Dst gt 250 nT or superstorm minimum of Dst lt 250 nT.
changeDst
{38E67047-21E7-4d3b-9B27-BC2E8D3E02BC}
Kind of breaker maintenance performed by this maintenance work task.
breakerMaintenanceKind
{DE40F27B-05CC-40c6-85DF-50C0C31BF814}
Kind of transformer maintenance performed by this maintenance work task.
transformerMaintenanceKind
{8189DD2E-E93E-43c1-A39E-22D4FE9E3759}
A MajorChargeGroup can have 0n ChargeType. A ChargeType can associate to 0n MajorChargeGroup.
ChargeType
{90202EBC-584B-4461-94E0-1F697B9901DA}.SupplierEnd
MarketInvoice
{BE562C52-127A-4564-95DF-779C969CA8C0}.ClientEnd
MktScheduledEvent
{890B707F-43E2-4bb0-BE45-1359D597DA95}.SupplierEnd
Settlement
{66C30E2D-CB35-48aa-A9C2-A0E325DA6FD5}.SupplierEnd
All asset models by this manufacturer.
ProductAssetModels
{4B21049D-BA80-4bd7-A107-BD54730986AA}.ClientEnd
MarketFactors
{DC280149-D350-4b9a-9EB9-28F20E183E1D}.ClientEnd
MarketProducts
{8A7E15E4-F0D3-453a-9ECB-CC6F62725DA9}.ClientEnd
MarketRun
{622410B9-A129-42a5-B23C-DD8F7914108C}.ClientEnd
Market run triggered by this actual event. For example the DA market run is triggered by the actual open bid submission event and terminated by the actual execution and completion of the DA market run captured by the runState of the MarketRun.
MarketRun
{930F69B6-9BC4-4791-8097-015E9B6F277C}.SupplierEnd
Planned event executed by this actual event.
PlannedMarketEvent
{6F2C5CBA-31FA-4fbf-93FC-0732720881FC}.SupplierEnd
Event status e.g. active canceled expired etc.
eventStatus
{3D1A1CBE-18BB-4913-8A8C-7491E7340418}
MarketProductClearing
{193E6A14-52CA-4269-A05F-CC3FCD23A162}.ClientEnd
AceTariffType
{17256E85-4394-4e3a-95AC-8ECE9214CA71}.ClientEnd
AttributeInstanceComponent
{56078672-F984-4496-A0EE-E53993207A8C}.SupplierEnd
DateAndOrTime
{F49F44BE-047D-4792-8B5B-A3AA670AA0A1}.ClientEnd
Domain
{65A175B6-9924-45f6-8876-8254B2486786}.SupplierEnd
MarketDocument
{6E6D96F5-F1A5-4401-9DDB-9AA7004318AC}.ClientEnd
MarketParticipant
{15329A77-AC86-4d04-9E5A-63C6BAA901A8}.ClientEnd
Period
{07DDBEDE-D21C-439d-AAF4-F347D1B02B1E}.SupplierEnd
Process
{02A672D8-0CED-4250-99DC-0E425C62E548}.ClientEnd
Reason
{B1D45B36-F3A6-4f96-A2D1-0E8AD7CFBBF6}.ClientEnd
SelfMarketDocument
{6E6D96F5-F1A5-4401-9DDB-9AA7004318AC}.SupplierEnd
TimeSeries
{8685CC5C-5A4F-4b05-AC0B-AE70B37260A5}.ClientEnd
TimeSeries
{D819A727-1DB3-424c-9D73-1E1D3668972A}.ClientEnd
Market
{DC280149-D350-4b9a-9EB9-28F20E183E1D}.SupplierEnd
MktActivityRecord
{3B634A0B-A62D-4bc1-906D-A2B67BA6B989}.SupplierEnd
MajorChargeGroup
{BE562C52-127A-4564-95DF-779C969CA8C0}.SupplierEnd
MarketInvoiceLineItems
{2EDD1DEF-974C-4208-BC3A-F7F232F27A8F}.ClientEnd
Total amount due on this invoice based on line items and applicable adjustments.
amount
{99DA6952-B9CB-41b8-B784-71C34EDD61D3}
Kind of media by which the CustomerBillingInfo was delivered.
billMediaKind
{46E55177-239C-4c51-B01D-E87ECE8D107D}
Kind of invoice default is sales.
kind
{05167FF5-1A6F-4a9f-9E90-E0EDD5DB4275}
ComponentMarketInvoiceLineItems
{AF978BE6-BF2F-453f-B08B-F421B78F3243}.ClientEnd
ContainerMarketInvoiceLineItem
{AF978BE6-BF2F-453f-B08B-F421B78F3243}.SupplierEnd
MarketInvoice
{2EDD1DEF-974C-4208-BC3A-F7F232F27A8F}.SupplierEnd
Settlement
{C0177491-5DB7-458c-8967-3D68B4E446EA}.SupplierEnd
Bill period for the line item.
billPeriod
{175EE50A-E411-479d-8D1E-4D9DA9C05A0A}
Kind of line item.
kind
{A1EAFC5B-AAA3-4196-B064-C04CC86BB340}
MarketLedgerEntries
{FAE450BD-F214-4f34-BF8C-489DA9D4DC4D}.SupplierEnd
MarketLedger
{FAE450BD-F214-4f34-BF8C-489DA9D4DC4D}.ClientEnd
Settlement
{DE87169A-1AAE-49ed-BD84-5D34B06D5FC7}.SupplierEnd
Kind of account for this entry.
accountKind
{016366EB-4F3E-47f9-9F2C-24F421349F52}
The amount of the debit or credit for this account.
amount
{FB60A19F-D7A2-47f7-872A-2C93035A44AB}
Status of ledger entry.
status
{BB1F100D-4CC3-4b1c-889C-4DAD6FF96E08}
RegisteredResource
{E489A51C-813C-4dd4-B929-320AFC501DEA}.SupplierEnd
TimeSeries
{DFA9145B-F296-4711-93A0-08DAEC6641D6}.SupplierEnd
Bid
{4483FC15-4087-4afd-8766-1D708647568D}.ClientEnd
MarketDocument
{15329A77-AC86-4d04-9E5A-63C6BAA901A8}.SupplierEnd
MarketPerson
{DB33BF98-91AD-4809-B83F-315F5A277246}.SupplierEnd
MarketRole
{24379B20-BB0D-49b6-B4BD-3ECE8DE8C8B5}.ClientEnd
RegisteredResource
{7EC28792-B0B8-4baa-9CE0-B5896FAAB9BA}.ClientEnd
SchedulingCoordinator
{B7A4F593-994A-4de3-804C-823ABC09CB5B}.ClientEnd
TimeSeries
{1ACE2F82-31E4-482b-B2EF-A568B3991A86}.ClientEnd
MarketParticipant
{DB33BF98-91AD-4809-B83F-315F5A277246}.ClientEnd
MarketSkills
{79C287DE-B210-4dca-BF3B-74038B8B585E}.SupplierEnd
Alternate Electronic address.
electronicAddressAlternate
{2F95FC92-1F17-4a4f-A828-84B683869325}
Primary Electronic address.
electronicAddressPrimary
{3D19FB72-8B61-4b47-B44F-7A715A83EA88}
Landline phone number.
landlinePhone
{A5FCC193-5CD7-4cf8-9C5B-7AAD808AF5A4}
Mobile phone number.
mobilePhone
{9DAA0C00-8AB6-4239-9DAC-5DC8AAEDDDE9}
status
{160B9787-B5FD-4a17-99FA-828717A6D7BE}
A market plan has a number of markets DA HA RT.
PlannedMarket
{9939F0DA-F147-4cab-A25A-C40C674AF836}.SupplierEnd
BidError
{9E7BFD17-29EA-44f9-8314-8B82238242CC}.SupplierEnd
BidPriceCap
{82238162-E851-4fa8-8103-3D73229CE310}.SupplierEnd
CommodityDefinition
{2CE15336-9D65-42db-A3CA-4D3E955778DF}.ClientEnd
Market
{8A7E15E4-F0D3-453a-9ECB-CC6F62725DA9}.SupplierEnd
MarketRegionResults
{473EB75C-4F19-4d7e-8585-2A0AE52F3F22}.SupplierEnd
ProductBids
{E7348A42-CD3B-49ba-B555-9BE41638E702}.SupplierEnd
Market product associated with reserve requirement must be a reserve or regulation product.
ReserveReqs
{B135E6CF-CF03-4e34-8A2A-CAB47CB13C0C}.ClientEnd
ResourceAwardInstruction
{DCAE610D-01F2-4d9d-84E5-FC64B8C205A5}.SupplierEnd
Market product type examplesEN EnergyRU Regulation UpRD Regulation DnSR Spinning ReserveNR NonSpinning ReserveRC RUC
marketProductType
{E612BB3D-5CE6-4f3c-9BD3-914F8447DD06}
MarketSkills
{7B119A79-FBC3-4255-8D6C-04F192205945}.ClientEnd
ExPostMarketRegionResults
{801B61F8-BE1E-447c-ACAC-D47A715E668A}.ClientEnd
MarketRegionResults
{08BD1B28-8AA8-4bc1-859C-C7296DDF32CF}.SupplierEnd
ReserveDemandCurve
{C2EA5FDF-AB5A-4353-86E1-3AC96CCCA3CC}.SupplierEnd
AncillaryServiceClearing
{F1B3EB5C-675E-4790-95CC-79C38272C39C}.ClientEnd
MarketProduct
{473EB75C-4F19-4d7e-8585-2A0AE52F3F22}.ClientEnd
MarketRegion
{08BD1B28-8AA8-4bc1-859C-C7296DDF32CF}.ClientEnd
Locational AS Flags indicating whether the Upper or Lower Bound limit of the AS regional procurment is binding
limitFlag
{7B959257-3ED0-42b4-8F4F-35DF3356AD5F}
The Lumpy FlagYN indicates whether the resource that sets the price is a lumpy generator by hour over the time horizon.Only applicable for the Day Ahead Market
lumpyIndicator
{4C2E7A9A-AF6D-4f74-BF17-C5BC9DC2EB90}
EnergyMarket
{1BCDE256-7739-44fd-A327-E54563BBB888}.ClientEnd
Global Contingent Operating Reserve Availability Indicator YesNo
contingentOperatingResAvail
{887AE29E-13A3-4159-A15F-3F50E55B7742}
MarketParticipant
{24379B20-BB0D-49b6-B4BD-3ECE8DE8C8B5}.SupplierEnd
Market
{622410B9-A129-42a5-B23C-DD8F7914108C}.SupplierEnd
All actual events that trigger this market run.
MarketActualEvent
{930F69B6-9BC4-4791-8097-015E9B6F277C}.ClientEnd
A planned market could have multiple market runs for the reason that a planned market could have a rerun.
PlannedMarket
{E537509E-3F2D-41ba-881E-85BABB782FC0}.ClientEnd
The execution type Day Ahead Intra Day Real Time PreDispatch Real Time Dispatch
executionType
{3E3E16C8-55F7-460f-A830-E11D697AFED4}
The market type Day Ahead Market or Real Time Market.
marketType
{04726F39-C49C-487c-9D25-12FCC83BB8FD}
MajorChargeGroup
{890B707F-43E2-4bb0-BE45-1359D597DA95}.ClientEnd
Duration of the scheduled event for example the time to ramp between values.
duration
{4559B6DA-2560-4c14-92EE-29BD1AE23788}
status
{996FB657-A475-4c2e-A80C-7562396B1AE0}
MarketPerson
{79C287DE-B210-4dca-BF3B-74038B8B585E}.ClientEnd
MarketQualificationRequirements
{7B119A79-FBC3-4255-8D6C-04F192205945}.SupplierEnd
Interval between the certification and its expiry.
certificationPeriod
{9C2E6F5E-18DD-4b73-822E-099F7BDE1744}
MarketStatementLineItem
{E7BE2BCE-CD84-4967-861E-5AFCA116CB56}.ClientEnd
ComponentMarketStatementLineItem
{00ADC084-731A-4011-BD96-3B38CDF055F7}.ClientEnd
ContainerMarketStatementLineItem
{00ADC084-731A-4011-BD96-3B38CDF055F7}.SupplierEnd
MarketStatement
{E7BE2BCE-CD84-4967-861E-5AFCA116CB56}.SupplierEnd
MktUserAttribute
{EA6E81CB-9BBB-4a78-A1D6-B66BC9D9B2B7}.SupplierEnd
PassThroughBill
{C9289981-55CD-40d3-9FB2-9C66EC3AEB17}.ClientEnd
A Marketer holds title to an EnergyProduct.
HoldsTitleTo_EnergyProducts
{45B2E11F-1F87-46d0-BEDA-714E73AB2B7B}.ClientEnd
A Marketer may resell an EnergyProduct.
Resells_EnergyProduct
{FFB388F3-6858-48ca-82BF-9BB8CF25DE4B}.ClientEnd
multiplier
{D40AF86B-C0F4-411f-91D2-A75099897751}
unit
{6CF35055-FDC7-44dc-B75D-BD9B6175FE11}
TypeMaterial
{1D24C169-2407-4dc7-9946-2E7695DD3662}.ClientEnd
WorkTask
{BFEEB8FC-4560-4027-829D-304562ADB795}.ClientEnd
Quantity of material used.
quantity
{6CC6AB98-8734-4afc-9C5B-3C7C4B3DC2A4}
Asset
{016DD996-A1EA-4bb6-8349-AF38EEDFF7AD}.ClientEnd
Calculation method hierarchy which applies to this analog.
CalculationMethodHierarchy
{F91A2D8A-DA8C-4273-9073-224DE84F0F21}.SupplierEnd
Locations
{F582AAC6-446D-49be-9380-09E21CAA0CCF}.ClientEnd
MeasurementAction
{0566ECD1-879E-43fc-AFB0-A8B79BFC4DEE}.ClientEnd
MeasurementCalculatorInput
{05661ED0-AD2E-4ee0-A3E5-9A25623C86D6}.ClientEnd
PinMeasurement
{D94A460B-0ABB-4872-900D-CDEEB9374DB3}.ClientEnd
The power system resource that contains the measurement.
PowerSystemResource
{78186A65-461E-4479-9917-94B5C4F2F9F6}.ClientEnd
Measurements are specified in types of documents such as procedures.
Procedures
{FEA58AE6-6428-4541-9097-FEFB35D64AD7}.ClientEnd
ProtectiveActionAdjustment
{9685ABB8-FD59-47dc-891C-CFC7E0CC0A6F}.SupplierEnd
One or more measurements may be associated with a terminal in the network.
Terminal
{9C2962C4-F1BE-4c1a-9577-DB6E59B8FB49}.SupplierEnd
Indicates to which phases the measurement applies and avoids the need to use measurementType to also encode phase information which would explode the types. The phase information in Measurement along with measurementType and phases uniquely defines a Measurement for a device based on normal network phase. Their meaning will not change when the computed energizing phasing is changed due to jumpers or other reasons.If the attribute is missing three phases ABC shall be assumed.
phases
{752AF06E-692D-4889-820C-2CBDA746E822}
The unit multiplier of the measured quantity.
unitMultiplier
{E6B15F9B-D6F8-412c-B662-FC9D1902C7ED}
The unit of measure of the measured quantity.
unitSymbol
{257F4465-5F67-4dca-91CB-2D2F6F040283}
Measurement
{0566ECD1-879E-43fc-AFB0-A8B79BFC4DEE}.SupplierEnd
Used in the calculation.
MeasurementCalculatorInput
{F24A2F91-9867-44ee-A6E6-31185DC84FC5}.ClientEnd
PinMeasurement
{CFBABACD-D1FC-46de-8BA7-DA6F2F4B3CC9}.SupplierEnd
Calculation operation executed on the operants.
kind
{8EC69B84-0006-4d3b-B402-721E72411644}
Measurement used as input to a calculation.
Measurement
{05661ED0-AD2E-4ee0-A3E5-9A25623C86D6}.SupplierEnd
MeasurementCalculator
{F24A2F91-9867-44ee-A6E6-31185DC84FC5}.SupplierEnd
CalculationMethodHierarchy
{54A8E767-B481-4e4a-947E-047AC60B5490}.ClientEnd
ErpPerson
{E047391D-9AD5-4022-964F-3C6152531AE3}.ClientEnd
A MeasurementValue has a MeasurementValueQuality associated with it.
MeasurementValueQuality
{BF14C261-4E21-4d59-89B0-1CAC365A66A1}.ClientEnd
A reference to the type of source that updates the MeasurementValue e.g. SCADA CCLink manual etc. User conventions for the names of sources are contained in the introduction to IEC 61970301.
MeasurementValueSource
{A71FD16F-0766-4c32-AFBC-626DE7028412}.ClientEnd
ProcedureDataSet
{A0C93754-F2B4-4597-96C0-BDCA60E5BC09}.ClientEnd
Link to the physical telemetered point associated with this measurement.
RemoteSource
{A7C88F72-6063-4225-8BCA-A830CE33CAC0}.SupplierEnd
The limit expressed as a percentage of the sensor maximum that errors will not exceed when the sensor is used under reference conditions.
sensorAccuracy
{6473AC26-9C48-4a1c-9FE5-BA7CE555F4DD}
A MeasurementValue has a MeasurementValueQuality associated with it.
MeasurementValue
{BF14C261-4E21-4d59-89B0-1CAC365A66A1}.SupplierEnd
The MeasurementValues updated by the source.
MeasurementValues
{A71FD16F-0766-4c32-AFBC-626DE7028412}.SupplierEnd
Asynchronous machine model with which this mechanical load model is associated. MechanicalLoadDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics.
AsynchronousMachineDynamics
{2E5B6ACA-CE14-4ff7-A95C-1961DD872622}.SupplierEnd
Synchronous machine model with which this mechanical load model is associated. MechanicalLoadDynamics shall have either an association to SynchronousMachineDynamics or AsynchronousMachineDyanmics.
SynchronousMachineDynamics
{2298CEEA-3BC8-4a46-9C31-9B6C0CDB1324}.SupplierEnd
Parameter of this proprietary userdefined model.
ProprietaryParameterDynamics
{16E261AB-0A61-4015-A4AF-C0D1E3AADE99}.ClientEnd
Medium with which this asset is filled.
Asset
{C899B2C5-BB4D-4ce8-A659-85956A304887}.SupplierEnd
Specification
{E64B800B-A4D4-4190-B7C3-AC53BAA0C1DD}.ClientEnd
Kind of this medium.
kind
{2E93E180-7FA6-4cc1-9D7C-A8A0671D04BF}
The volume of the medium specified for this application. Note that the actual volume is a type of measurement associated witht the asset.
volumeSpec
{C5525725-B4B4-40f5-8001-F5941F5C58D4}
Merchant agreement that instantiated this merchant account.
MerchantAgreement
{6385AC88-456C-4b10-A868-F0F70A08912C}.ClientEnd
All transactors this merchant account is registered with.
Transactors
{4E9EC9E2-B298-41e8-9F52-493E9BBBDAC4}.SupplierEnd
All vendor shifts that operate on this merchant account.
VendorShifts
{28C890D5-DD6C-419b-AC03-0323BBD41D10}.SupplierEnd
The current operating balance of this account.
currentBalance
{7BA81B69-B5F3-493d-A61B-5EB3355C674B}
The balance of this account after taking into account any pending debits from VendorShift.merchantDebitAmount and pending credits from BankStatement.merchantCreditAmount or credits see also BankStatement attributes and VendorShift attributes.
provisionalBalance
{5ACC1A8F-DC23-4e45-98FE-2348EE41DA53}
All merchant accounts instantiated as a result of this merchant agreement.
MerchantAccounts
{6385AC88-456C-4b10-A868-F0F70A08912C}.SupplierEnd
All multipliers applied at this meter.
MeterMultipliers
{7310B281-4A19-4049-8E9E-774367FEA689}.SupplierEnd
All meter readings provided by this meter.
MeterReadings
{AFE4FF06-8B2A-466e-8CA5-C0C940A18F23}.SupplierEnd
All work tasks on replacement of this old meter.
MeterReplacementWorkTasks
{1617E573-158B-4042-8A7B-4A88A56E774C}.ClientEnd
All nonreplacement work tasks on this meter.
MeterServiceWorkTask
{B91474A2-AF62-4326-B24C-CA6F2959ABD1}.ClientEnd
All vending transactions on this meter.
VendingTransactions
{95682AE1-DDB3-4fa2-AC18-655296065A72}.ClientEnd
Meter applying this multiplier.
Meter
{7310B281-4A19-4049-8E9E-774367FEA689}.ClientEnd
Kind of multiplier.
kind
{3952B5E5-304C-4a15-8267-F2C328C765D7}
could be deprecated in the future Customer agreement for this meter reading.
CustomerAgreement
{A14F100A-AE6C-49c4-AD0C-FC8D5004074A}.SupplierEnd
All end device events associated with this set of measured values.
EndDeviceEvents
{DF4C0081-227B-4d2d-A692-33F732385A32}.SupplierEnd
All interval blocks contained in this meter reading.
IntervalBlocks
{15942C2F-68E7-46d2-88D4-0C74530EE8E5}.ClientEnd
Meter providing this reading.
Meter
{AFE4FF06-8B2A-466e-8CA5-C0C940A18F23}.ClientEnd
All reading values contained within this meter reading.
Readings
{50ABD845-4A69-4a91-A0FE-99656D135A6F}.ClientEnd
Usage point from which this meter reading set of values has been obtained.
UsagePoint
{EB5C430A-F69D-402a-9806-69357BFC879C}.SupplierEnd
Date and time interval of the data items contained within this meter reading.
valuesInterval
{9146DBC3-DC7A-4ec3-AFF9-F20F5635E8D8}
Meter on which this nonreplacement work task is performed.
Meter
{B91474A2-AF62-4326-B24C-CA6F2959ABD1}.SupplierEnd
Old meter replaced by this work task.
OldMeter
{1617E573-158B-4042-8A7B-4A88A56E774C}.SupplierEnd
Usage point to which this meter service work task applies.
UsagePoint
{30B864E4-AFB6-47b2-BF72-C36AA03A3F68}.SupplierEnd
MSSAggregation
{A5BC78A9-02B6-4693-833B-5988046C9A07}.ClientEnd
MSSZone
{92A84479-AD05-4df5-BE48-E000CB70D4B3}.SupplierEnd
All reading types required to be collected by this metrology requirement.
ReadingTypes
{B5CE221C-AAE6-4ae6-A720-B4E199752DF9}.SupplierEnd
All usage points having this metrology requirement.
UsagePoints
{28F71A07-2CD9-466b-BB76-3CAC30AEEC8F}.SupplierEnd
Reason for this metrology requirement being specified.
reason
{DBB69BD4-7DF4-4382-BCBE-77DCC2FEAF19}
multiplier
{1ACF207C-AF79-4e5e-B536-DF1C7EDFB417}
unit
{45CF91A2-F79F-4606-B73D-F3E2D818F46E}
DesignLocation
{ECAD85F3-E7E4-48d0-B3DF-81B8B5795C03}.ClientEnd
WorkCostDetail
{D3D92A8C-C7B5-4a95-B1BF-113EA20D2A57}.SupplierEnd
WorkTask
{AB707969-391C-4b7b-9824-9E98B7029488}.ClientEnd
The cost per unit for this misc. item.
costPerUnit
{35E1E964-0BDA-4d41-9100-16B05FC51411}
The quantity of the misc. item being assigned to this location.
quantity
{E34551CA-BF53-4af9-B734-83F525452144}
status
{034A2A27-DC0C-4cea-BB44-7316C8AF712D}
Bid
{41CDA34B-D1DA-4d10-BD9C-9ACD84F95C4F}.SupplierEnd
MitigatedBidClearing
{CC434B38-6DC2-46e9-A8FF-4CC3583B4114}.SupplierEnd
MPMResourceStatus
{E48948D6-38C5-4c7b-8933-F5947320697F}.SupplierEnd
MitigatedBid
{CC434B38-6DC2-46e9-A8FF-4CC3583B4114}.ClientEnd
RMRDetermination
{5A2FDC45-69C0-48d6-B301-3B257BF71F43}.ClientEnd
Bid
{BB5D09A6-5901-41e0-9C70-FEA07F4C897A}.ClientEnd
EndAFlow
{C683E41C-A3EC-4316-BD46-D25F17ED532B}.ClientEnd
EndBFlow
{977B9C6C-1464-4035-A670-FC92869C7E0B}.ClientEnd
MarketFactors
{3B634A0B-A62D-4bc1-906D-A2B67BA6B989}.ClientEnd
The type of limit the value representsBranch Limit TypesShort TermMedium TermLong TermVoltage LimitsHighLow
limitType
{9EA49FA7-07EC-4189-A4DD-9BA4C569D8CE}
AggregatedPnode
{667EE2EC-BAF5-4e35-9AEA-070E69E9AACF}.SupplierEnd
CombinedCycleLogicalConfiguration
{E85573FF-D877-4da8-AD0E-F1D7EBBB5773}.ClientEnd
CnodeDistributionFactor
{2E462F8F-23E2-41eb-8C60-ECC38D2C21A2}.ClientEnd
IndividualPnode
{2B0FBC3E-406E-4d8b-A02A-36C41F9A1D0E}.ClientEnd
LossPenaltyFactor
{BAB096FD-2D2E-4088-887E-124132BB99A0}.ClientEnd
NodeConstraintTerm
{E32D476E-22A4-4002-A185-3CB6C77E4005}.ClientEnd
RTO
{E1B1E7AA-80C6-41cb-8B19-3F793E0E7B53}.ClientEnd
RegisteredResource
{102246E9-40F9-404f-A841-A49127DDD797}.ClientEnd
SysLoadDistribuFactor
{C9774777-9F95-427f-B6A2-3AD33980CE68}.ClientEnd
ConstraintResults
{01D4A0B2-81CC-4497-A052-25EA792CEC6E}.ClientEnd
ContingencyConstraintLimit
{0906BEF7-3804-4598-9F39-8339F2B0B443}.ClientEnd
TransferInterfaceSolutionA
{C3F0F2CA-4331-417e-BB6F-AC8830FC9ABF}.ClientEnd
TransferInterfaceSolutionB
{A997CE1E-D37D-451f-AAE5-0DEBC8D07E52}.ClientEnd
ControlAreaSolutionData
{72466897-1E7B-4232-8415-B1CF11A7D241}.ClientEnd
GeneratingUnitDynamicValues
{068663E7-88C7-413e-9ACC-BB0E7776514E}.ClientEnd
RegisteredGenerator
{1BFB226F-6654-4314-8030-31CF5E037B03}.ClientEnd
ResourceVerifiableCosts
{19E8F4BC-BA0C-4a8b-8AFC-83E8D5EE0E8D}.ClientEnd
Flowgate
{8B57B818-A6B3-4836-BC0E-617E9ABEB67D}.ClientEnd
TransmissionRightOfWay
{30BB45B0-2DB4-4d68-BC65-DFE2DF74D8D1}.SupplierEnd
A measurement is made on the B side of a tie point
ByTiePoint
{405D53E3-14AD-4d07-9D1F-3F3285139237}.ClientEnd
DynamicSchedule
{10B4C6E2-CE00-43d6-91C5-CA7BF16D48A2}.ClientEnd
A measurement is made on the A side of a tie point
ForTiePoint
{BE3DB3DE-E7FF-4f27-8DC0-5606F98986E5}.ClientEnd
Allows Pnode an association to aggregated resources external DC ties or psuedo tie measurements.
Pnode
{72AD4107-7210-4172-B722-F58EA3179E3E}.ClientEnd
ViolationLimit
{7B62C3C6-7398-40f5-BDE5-CBD6C32FC0EF}.ClientEnd
TimeSeries
{CBE02ED5-1004-4fe7-8827-53E8B4BDDE03}.SupplierEnd
EndAFlow
{6B82670E-C342-4f85-A215-9BB510562254}.ClientEnd
EndBFlow
{D9B28EF9-4971-4bb7-B90B-5D0EF7D92756}.ClientEnd
Flowgate
{E865ED1B-5944-445e-BD28-D928C5FF6389}.ClientEnd
EndAFlow
{5C0AAF99-2DB3-4ce7-8154-9C37E518CB30}.ClientEnd
EndBFlow
{A6C6B3F9-7B48-423b-99F5-774083959E01}.ClientEnd
ShuntCompensatorDynamicData
{4C898DD2-7D9D-4138-A8D0-B271310AE638}.ClientEnd
SwitchStatus
{F865D7AC-3978-4a82-A41D-4131DB7D21B2}.ClientEnd
TapChangerDynamicData
{FD943330-575B-40e5-BD88-67AED345044F}.ClientEnd
Flowgate
{E72576E6-C983-42fd-AED5-7EBD0160B933}.SupplierEnd
TerminalConstraintTerm
{B8192AA1-3321-4d5a-9823-446CC79C90D7}.ClientEnd
CombinedCycleConfigurationMember
{DF15B386-08F6-4c78-95AD-B7B10FCC1AB9}.ClientEnd
AttributeProperty
{3FB05567-9270-4fcb-8976-9ADA1813AE21}.ClientEnd
BillDeterminant
{3D3E108F-27E6-46ff-B50B-1A3A9365B887}.ClientEnd
ChargeGroup
{7E99E40A-D085-4ca0-9CA9-3E9E0C539B2A}.ClientEnd
ChargeType
{FA4D0F9A-CFBA-4b39-8AF5-D8EDA0559E55}.ClientEnd
MarketStatementLineItem
{EA6E81CB-9BBB-4a78-A1D6-B66BC9D9B2B7}.ClientEnd
PassThroughBill
{8190276C-7601-4378-973C-AE9F4C42620E}.ClientEnd
Modeling Authority Sets supplied and maintained by this Modeling Authority.
ModelingAuthoritySets
{DD1413D0-73ED-4d90-8ADB-E87B483F7D14}.ClientEnd
Models of the model frame.
ModelSpecification
{F71435FC-A6DA-4cce-BB6F-AAE8A1166194}.ClientEnd
Modeling Authority suppliying and maintaining the data for the objects in this Modeling Authority Set.
ModelingAuthority
{DD1413D0-73ED-4d90-8ADB-E87B483F7D14}.SupplierEnd
Model frames of the model frame type.
ModelFrame
{48C2079D-ACDD-4f43-B91E-201B0B6EEBFB}.ClientEnd
Arguments of the operation.
ModelOperationArg
{8FC83F05-9979-46fe-AC90-E3B729F03BDB}.ClientEnd
The type of the model operation.
ModelOperationDescription
{784F27D9-2196-49a7-BAA9-5C220EDE1B7E}.SupplierEnd
OperationSequence
{625A7E9A-0BA8-4b99-8F27-F85B489D5E7E}.ClientEnd
The opeation for the operation argument.
ModelOperation
{8FC83F05-9979-46fe-AC90-E3B729F03BDB}.SupplierEnd
The type of operation for this type of dataset role. Operations referencing the dataset role type should only belong to operations that reference the operation type.
ModelOperationDefinition
{351BA520-733C-4ff8-89F0-7F56FA528900}.SupplierEnd
The instances of operations that conform to this operation type.
ModelOperation
{784F27D9-2196-49a7-BAA9-5C220EDE1B7E}.ClientEnd
The type of dataset roles that can be used for a type of general model operation.
OperationDatasetArgDescription
{351BA520-733C-4ff8-89F0-7F56FA528900}.ClientEnd
ModelOperation
{625A7E9A-0BA8-4b99-8F27-F85B489D5E7E}.SupplierEnd
The assembly description into which model parts should be included.
AssemblyDescription
{63DD40D8-8901-4fa0-B3DA-04BEDB15C589}.ClientEnd
Model frame of the model part.
FrameworkPart
{F71435FC-A6DA-4cce-BB6F-AAE8A1166194}.SupplierEnd
Modle parts conforming to the model part specification.
Model
{F5F3F26B-ED67-4cc0-AFDD-6BAB5F794D13}.ClientEnd
AssemblyManifest
{181112F7-C48F-44b9-B4D1-249851E26CBA}.ClientEnd
CompleteModelToBeDeleted
{C390164D-CBC2-47e2-8EAE-2EC7A1187A16}.SupplierEnd
DataSet
{2494ED30-254C-4f13-8F87-6FBEE03C2A4F}.SupplierEnd
Model specification of the modelt.
ModelSpecification
{F5F3F26B-ED67-4cc0-AFDD-6BAB5F794D13}.SupplierEnd
multiplier
{86CC9B3D-6DFC-4a34-9152-1BD808FBDD41}
unit
{FA0E49C2-B5F3-4084-948C-2A553D874695}
The starting terminal for the calculation of distances along the first branch of the mutual coupling. Normally MutualCoupling would only be used for terminals of AC line segments. The first and second terminals of a mutual coupling should point to different AC line segments.
First_Terminal
{E0778435-CE76-4d56-9FCA-FF9F04ED4FCA}.SupplierEnd
The starting terminal for the calculation of distances along the second branch of the mutual coupling.
Second_Terminal
{3849B779-18E4-46d5-B987-8359D8A98A12}.SupplierEnd
Zero sequence mutual coupling shunt charging susceptance uniformly distributed of the entire line section.
b0ch
{AC6F5010-FE14-46d4-8356-FAC00C72C23E}
Distance to the start of the coupled region from the first lines terminal having sequence number equal to 1.
distance11
{24F204CC-E384-4dfe-98B9-D0075DF1DA65}
Distance to the end of the coupled region from the first lines terminal with sequence number equal to 1.
distance12
{7275F327-1ABD-4a11-B170-904B24B53BDD}
Distance to the start of coupled region from the second lines terminal with sequence number equal to 1.
distance21
{5BB2F943-1CE7-4997-9E13-BAD43BA321F6}
Distance to the end of coupled region from the second lines terminal with sequence number equal to 1.
distance22
{40540F6D-3306-4d14-B600-53F9A1392F82}
Zero sequence mutual coupling shunt charging conductance uniformly distributed of the entire line section.
g0ch
{5AC0AF5A-CD75-4dc9-9A70-DE9012477272}
Zero sequence branchtobranch mutual impedance coupling resistance.
r0
{4F35A9CE-4DB1-4270-BC6C-2E4415752E41}
Zero sequence branchtobranch mutual impedance coupling reactance.
x0
{D4B922E9-B25A-4821-A84E-AEDFA549F466}
Identified object that this name designates.
IdentifiedObject
{203C47E2-30FB-4c8f-ABEA-1661621CC0A7}.SupplierEnd
Type of this name.
NameType
{2DF559F1-C2F0-43ff-B7E0-654C3E738FDE}.SupplierEnd
Authority responsible for managing names of this type.
NameTypeAuthority
{19684F95-02B1-4b64-B345-ADF4DDB40433}.SupplierEnd
All names of this type.
Names
{2DF559F1-C2F0-43ff-B7E0-654C3E738FDE}.ClientEnd
All name types managed by this authority.
NameTypes
{19684F95-02B1-4b64-B345-ADF4DDB40433}.ClientEnd
NetworkFrame
{695E7BFC-35D6-4d1d-AAA2-D5F42AA026BB}.SupplierEnd
{CA21CE47-5254-4798-BFEE-38C0883A3CC1}.SupplierEnd
FrameworkPart
{EDD89720-4773-45ee-9FB3-8DFFCD2B09AA}.SupplierEnd
NetworkBoundary
{695E7BFC-35D6-4d1d-AAA2-D5F42AA026BB}.ClientEnd
{CA21CE47-5254-4798-BFEE-38C0883A3CC1}.ClientEnd
Operation
{33808218-A5AF-495e-8ACC-888EF93D696E}.SupplierEnd
Projects that are included in this parent project.
ContainedProject
{11B9FF97-2A88-467b-A14A-1843624A76BF}.ClientEnd
Child
{2A18274D-D3FD-4344-8344-B2FDC6DDCA5D}.ClientEnd
A specific version of the network model project change.
NetworkModelProjectChangeVersion
{E749C3AE-A14B-4d74-905B-0BDDBE3992F3}.ClientEnd
The details of model changes for this project. The change set should have a new identifier if it changes.
ChangeSet
{D0FD1813-3105-4ab3-AA49-9C2E1C71624E}.SupplierEnd
The persistent network model project change to which this version applies.
NetworkModelProjectChange
{E749C3AE-A14B-4d74-905B-0BDDBE3992F3}.SupplierEnd
The state of this network model project version.
NetworkModelProjectState
{79467043-AB52-45dc-900F-3947F6B07CC0}.SupplierEnd
The project version that will supercede this project version.
SupercededBy
{84532593-82B1-4531-9C9A-EE2D56ED988A}.SupplierEnd
Project version that is being superceded.
Supercedes
{84532593-82B1-4531-9C9A-EE2D56ED988A}.ClientEnd
The parent project of this project.
ContainingProject
{11B9FF97-2A88-467b-A14A-1843624A76BF}.SupplierEnd
NetworkModelProjectDocument
{0203E575-3F55-4f26-BFAF-8F659C7E7E80}.SupplierEnd
ProjectARelationships
{186C7F99-9FCA-41de-8436-41E563322984}.ClientEnd
ProjectBRelationships
{49452EA4-5410-4415-B1E8-99AC0B96119F}.ClientEnd
CurrentState
{955D5BF8-C371-455c-9915-2EDD3CA75C50}.SupplierEnd
Parent
{2A18274D-D3FD-4344-8344-B2FDC6DDCA5D}.SupplierEnd
NetworkModelProjectComponent
{0203E575-3F55-4f26-BFAF-8F659C7E7E80}.ClientEnd
ProjectA
{186C7F99-9FCA-41de-8436-41E563322984}.SupplierEnd
ProjectB
{49452EA4-5410-4415-B1E8-99AC0B96119F}.SupplierEnd
ChangeSets
{5C7D89EE-E6F6-4bc7-9B55-013A14F63C05}.SupplierEnd
DenpendecyDependingStage
{66BEEFB3-CC6F-4eb4-B3FF-8D386E2F2D98}.ClientEnd
DependencyDependentOnStage
{DA34DBEB-9B66-47df-B464-9D7E5EC7EA99}.ClientEnd
The change versions that are at this state.
NetworkModelProjectChangeVersion
{79467043-AB52-45dc-900F-3947F6B07CC0}.ClientEnd
Transformer end that current is applied to in this noload test.
EnergisedEnd
{F3E7A0B0-A48C-4358-8A44-11C4C94ABFB4}.SupplierEnd
Voltage applied to the winding end during test.
energisedEndVoltage
{20FBD71A-ECFC-4665-BC2C-38A1996F3CE7}
Exciting current measured from a positivesequence or singlephase excitation test.
excitingCurrent
{483E5C02-946E-4159-938B-4B1774667A52}
Exciting current measured from a zerosequence opencircuit excitation test.
excitingCurrentZero
{FD31067C-C048-4f4f-923E-EC9F02E7E694}
Losses measured from a positivesequence or singlephase excitation test.
loss
{BC40329E-347C-4bcb-ACF4-879701BBE06A}
Losses measured from a zerosequence excitation test.
lossZero
{613CA323-1A7C-442f-B8DF-39AF71F7A4E1}
MktConnectivityNode
{E32D476E-22A4-4002-A185-3CB6C77E4005}.SupplierEnd
Group of this ConformLoad.
LoadGroup
{3CAF0C58-293B-4fcd-945A-945312494BFB}.ClientEnd
Conform loads assigned to this ConformLoadGroup.
EnergyConsumers
{3CAF0C58-293B-4fcd-945A-945312494BFB}.SupplierEnd
The NonConformLoadSchedules in the NonConformLoadGroup.
NonConformLoadSchedules
{30607CC5-5FB9-4bd4-8F9D-BD718F651B4E}.SupplierEnd
The NonConformLoadGroup where the NonConformLoadSchedule belongs.
NonConformLoadGroup
{30607CC5-5FB9-4bd4-8F9D-BD718F651B4E}.ClientEnd
The projected cost for this item.
amount
{BC547B43-1F66-4933-AAB5-BD3B7E548B0D}
Positive sequence shunt charging susceptance per section.
b
{2444AD6A-5AE8-4468-ACEB-73E8D4613927}
Positive sequence shunt charging conductance per section.
g
{191632B6-2840-477e-B57D-AB48DC16ADB8}
Positive sequence shunt charging susceptance per section.
b
{6F759E68-6762-48f7-83F8-A68CCBF75008}
Zero sequence shunt charging susceptance per section.
b0
{5BC99084-351E-4a1d-AEEA-41C16FBE6AA8}
Positive sequence shunt charging conductance per section.
g
{60A2BA6A-2613-4fd4-99D4-72E10BF34045}
Zero sequence shunt charging conductance per section.
g0
{E58C51D2-C678-4903-ADFB-59CA9EC22209}
GeneratingBids
{9A5F74CD-56FF-45e1-8BC8-5AD82D6C11B0}.ClientEnd
The data object holding preconditions of updates.
ObjectReverseModification
{22E96F65-7EFC-4331-BA60-BA9C5D984E2E}.ClientEnd
The associated data object representing the update. Normally the associaiton is specifed but in the case of a proxy object where the association is removed we might not reference any data object as it would only reference a proxy data object with no associations.
ObjectModification
{22E96F65-7EFC-4331-BA60-BA9C5D984E2E}.SupplierEnd
Kind of analog representing oil fluid test analysis result.
kind
{F30FD808-456D-4ef1-93B0-DF58F603E429}
Kind of discrete representing oil fluid test analysis result.
kind
{4E3257AD-BED3-4db4-9C0F-E63C7BC8A135}
Kind of analog representing oil dissolved gases analysis result.
kind
{5D615ACB-C887-465a-B339-FB3D202411CB}
Kind of analog representing oil metals elements analysis result.
kind
{DE0264E7-5366-4fbc-A51A-4EFFE5F26CD1}
Kind of analog representing oil moisture analysis result.
kind
{A5E40132-9CBD-4838-B58E-0694B1841409}
Kind of analog representing oil PCB analysis result.
kind
{1038D4BB-1176-4e34-82DB-6628D7ADC79A}
Kind of discrete representing oil PCB test analysis result.
kind
{FCA1D905-CCB3-4c74-BC12-1F2885A376B4}
Kind of analog representing oil paper degradation analysis result.
kind
{4F15F807-15FA-4fdd-B36C-4BB7FC7938D4}
Kind of analog representing oil particulate analysis result.
kind
{31A17357-0261-4295-8328-2E201A2C2FD0}
Kind of discrete representing oil particulate analysis result.
kind
{63B47147-116B-4cc3-99D3-80E3F77FD60E}
FuelRegion
{4309159F-3756-4294-B5A1-E8863F5CEA5B}.SupplierEnd
Location from which oil sample taken.
oilSampleTakenFrom
{4035942E-3822-481e-9B7A-E717A379390C}
Oil sample temperature.
oilSampleTemperature
{5ED27F1C-8473-406a-8CC5-A014A849FC2C}
Source of oil temperature.
oilTemperatureSource
{63B3B095-DD70-4ec7-849D-424121278112}
Type of sample container.
sampleContainer
{9ECB0B31-A44C-4d90-B30E-068B7789B6C2}
All Assignments for this Crew.
Assignments
{B597E5EE-DEFD-46c2-9B5C-1B4B22EA8086}.SupplierEnd
Capabilities
{A3C41283-0A33-4ee9-A5AA-105826F2A3B8}.ClientEnd
Locations
{9F98B054-8439-4bd9-8F2E-43422494EFE5}.SupplierEnd
Route
{E3EA714F-98DF-4908-8D66-9D4D2D2ECDBE}.SupplierEnd
ShiftPatterns
{764EE186-E180-4d38-9772-53A73AAE0278}.SupplierEnd
Crafts
{19D1AD6D-1BA3-400f-BACA-BF16BDB31A48}.ClientEnd
CustomerData
{08C6C8AA-21F3-4f0e-91C1-B7765CD6D7FA}.ClientEnd
ErpCompetency
{A11130EF-055F-4b39-8ED5-B1CB36A71F99}.SupplierEnd
ErpPersonnel
{284A2414-6888-411f-82F7-90FAF8CA2419}.SupplierEnd
LaborItems
{A04894E3-14E3-4cfe-B0D3-57701085ACBE}.SupplierEnd
LandPropertyRoles
{ABB493E7-418A-4fe4-B85B-23905A057C94}.SupplierEnd
MeasurementValues
{E047391D-9AD5-4022-964F-3C6152531AE3}.SupplierEnd
OrganisationRoles
{694B40C4-6F8C-41a2-9D1E-27B7A4572BBE}.SupplierEnd
Skills
{9D792EF4-F8E0-42ce-A1BF-B84E9BA01D5F}.SupplierEnd
status
{85D1041F-EF9D-4161-A285-EEB8EAEDA342}
The maximum rms voltage that may be applied across an open contact without breaking down the dielectric properties of the switch in the open position.
dielectricStrength
{07BB73CC-6FAB-4867-8927-69AAC0C36694}
The highest value of current the switch can make at the rated voltage under specified operating conditions without suffering significant deterioration of its performance.
makingCapacity
{BEB67DB0-4C7F-4415-AE1D-4FE26FE0BD47}
The lowest value of current that the switch can make carry and break in uninterrupted duty at the rated voltage under specified operating conditions without suffering significant deterioration of its performance.
minimumCurrent
{2CF18E57-21C4-4787-8165-7FCE2E42E726}
The highest value of current the switch can carry in the closed position at the rated voltage under specified operating conditions without suffering significant deterioration of its performance.
withstandCurrent
{903743F6-97BC-4bfe-A957-B4CCAD2196FA}
Overload rating for 24 hours.
dayOverLoadRating
{45CAF1A7-AA19-440b-96F6-FFF7F2A8E241}
Overload rating for 1 hour.
hourOverLoadRating
{99C410E9-8AA7-4654-BFF9-5E5983FE1E44}
Weight of solid insultation in transformer.
solidInsulationWeight
{17A5040D-2047-4a64-8D7B-14FE792ADB70}
Type of insultation used for transformer windings.
windingInsulationKind
{DC10AE0D-7691-4b41-AA73-93D4D55D2812}
Kind of construction for this transformer.
constructionKind
{F31C5B99-BA3D-4c01-A540-618EF7A9A998}
Weight of core and coils in transformer.
coreCoilsWeight
{31200834-25CB-4cac-BAC7-CE5BF875DAD8}
Core kind of this transformer product.
coreKind
{8C022234-AB4E-4f1d-B592-448A1F9C484A}
Function of this transformer.
function
{E1D99D79-255D-4598-AB65-61A021740C26}
Basic insulation level of neutral.
neutralBIL
{586E9509-F1A5-4c20-B445-C2A0C378E8DB}
Kind of oil preservation system.
oilPreservationKind
{E6B251F6-B06E-4078-B823-F9DC9F97BEBD}
Capabilities
{99651776-E1FC-4685-A904-70049BEA9646}.ClientEnd
ContractorItems
{3123F76B-B55F-4f42-AEB4-96AA9F5254CA}.SupplierEnd
Design
{83CD7FF8-6559-45a7-AB79-BA79FC3B1C82}.ClientEnd
DesignLocationCUs
{FCF781BC-040D-407f-A030-D5BB3656B390}.ClientEnd
LaborItems
{FDB3A56B-46C4-4591-A0EA-AA7F58E3236A}.SupplierEnd
MiscCostItems
{AB707969-391C-4b7b-9824-9E98B7029488}.SupplierEnd
OverheadCost
{B41A8F8E-876B-48ea-B6D2-DE732BA34F6E}.SupplierEnd
QualificationRequirements
{B3426602-AFB3-44a7-9BCB-107ADC91CCAB}.SupplierEnd
Usages
{AADBFD79-5E2A-47b4-A108-F25824E68687}.SupplierEnd
WorkCostDetails
{7F10B6C7-082B-4d2d-B95B-E5DF634041D3}.ClientEnd
WorkFlowStep
{C76E630D-24B2-45f0-8B97-801F51060C44}.ClientEnd
WorkLocations
{ECA7D24D-E18E-412d-BD83-31B1B68A4448}.ClientEnd
Transformer end that current is applied to in this opencircuit test.
EnergisedEnd
{71BB3848-4B63-4fd1-9254-66CEBBF18C94}.SupplierEnd
Transformer end measured for induced voltage and angle in this opencircuit test.
OpenEnd
{AC00E333-4A04-486e-AA1A-D3D83FB22682}.SupplierEnd
Voltage applied to the winding end during test.
energisedEndVoltage
{61C79A42-CF37-45d8-BD20-3C3E9DFF5F5A}
Voltage measured at the opencircuited end with the energised end set to rated voltage and all other ends open.
openEndVoltage
{7B8EF14F-49BF-482d-8D73-A2C345AE7693}
Phase shift measured at the open end with the energised end set to rated voltage and all other ends open.
phaseShift
{950DE312-6E35-45e0-B7A6-16CABB15AE0D}
Interrupter controlled by this mechanism.
InterrupterUnit
{DA02B460-9B93-4dff-AF33-7056DC71BA82}.SupplierEnd
Close current nominal.
closeAmps
{D85DBA0C-1D24-4ed4-9DE9-F12A9EA6D7DE}
Close voltage in volts DC.
closeVoltage
{3A230AB7-1714-40e6-94C2-C7CB4B860F51}
Kind of breaker operating mechanism.
mechanismKind
{E2DDF690-CBC3-44e3-91E3-B1C6CAD899FE}
Rated motor run current in amps.
motorRunCurrent
{998D6F29-FB81-4424-97B5-CC05634FC07A}
Rated motor start current in amps.
motorStartCurrent
{97BFB3F3-C987-43b4-8A38-6729D54038C7}
Nominal motor voltage in volts DC.
motorVoltage
{AE0A2159-D904-4884-AEDE-17CDB6B8FB8C}
Trip current nominal.
tripAmps
{0762F532-1818-4a10-BB84-F74D30629D0F}
Trip voltage in volts DC.
tripVoltage
{EA3B14F8-6C27-4377-99B3-5AA95E5B14D8}
The operating shares of this operating participant. An operating participant can be resused for any number of power system resources.
OperatingShare
{C8C2BA26-2410-41d8-9E77-EC3873BDCE5B}.ClientEnd
The operating participant having this share with the associated power system resource.
OperatingParticipant
{C8C2BA26-2410-41d8-9E77-EC3873BDCE5B}.SupplierEnd
The power system resource to which the share applies.
PowerSystemResource
{343B3487-FA8E-4906-A8F1-4D6E3B27F4AF}.SupplierEnd
Percentage operational ownership between the pair power system resource and operating participant associated with this share. The total percentage ownership for a power system resource should add to 100.
percentage
{91E1E9AB-B240-4b98-9917-82000F0A4CFB}
NetworkModelCaseDefinition
{33808218-A5AF-495e-8ACC-888EF93D696E}.ClientEnd
The limit dependency models which are used to calculate this limit. If no limit dependencies are specified then the native limit value is used.
LimitDependencyModel
{930C423F-F107-4857-A500-C7D5C97E88CB}.SupplierEnd
LimitScalingLimit
{312BBC54-9F5A-4000-8A02-754DB702EB90}.ClientEnd
The limit type associated with this limit.
OperationalLimitType
{E3D73666-E647-4b0a-B020-0700E4FCDECC}.SupplierEnd
The equipment to which the limit set applies.
Equipment
{AEB22FF5-0EEF-4e3a-BE8C-07931F2FAE92}.SupplierEnd
The terminal where the operational limit set apply.
Terminal
{E741C3E3-646B-4238-BE21-DFE9B0A603C1}.SupplierEnd
The operational limits associated with this type of limit.
OperationalLimit
{E3D73666-E647-4b0a-B020-0700E4FCDECC}.ClientEnd
SourceOperationalLimitTypeScaling
{B089AC15-CDFC-4c0d-9765-7F449337E6AB}.ClientEnd
TargetOperationalLimitmTypeScaling
{870033E1-C96D-4c7f-BC97-DB2B6D26C20F}.ClientEnd
The nominal acceptable duration of the limit. Limits are commonly expressed in terms of the time limit for which the limit is normally acceptable. The actual acceptable duration of a specific limit may depend on other local factors such as temperature or wind speed. The attribute has meaning only if the flag isInfiniteDuration is set to false hence it shall not be exchanged when isInfiniteDuration is set to true.
acceptableDuration
{4596C956-5F6F-4af5-9726-AA67E22FD030}
The direction of the limit.
direction
{247D5C99-6296-4916-93DB-C4DA1CFF667F}
All equipments to which this restriction applies.
Equipments
{A11D842D-BDDB-42a4-B8FB-43C199D5E3BA}.SupplierEnd
Asset model to which this restriction applies.
ProductAssetModel
{52B7FEC7-526D-4b4e-8839-1C5E1DE7D0A4}.SupplierEnd
Interval during which this restriction is applied.
activePeriod
{9403F5A8-AF55-43eb-B08A-29A04BD09050}
Restricted new value includes unit of measure and potentially multiplier.
restrictedValue
{E7974231-35DC-4526-BC91-D229A5682DF4}
Asset on which this tag has been placed.
Asset
{6C60E3EC-3A0D-400d-BFBB-48BE5355B286}.SupplierEnd
Power system resource on which this tag has been placed.
PowerSystemResource
{AB49BFBC-0F00-4bf2-95B2-BCBAD3CA1BA5}.SupplierEnd
Tag action associated with this tag.
TagAction
{987DD03E-CEAD-487e-B8AA-EDF24171399B}.ClientEnd
Planned equipment outage with this updated rating.
PlannedOutage
{C5F3A5B0-064B-4cc4-AA34-0296D8D7919A}.SupplierEnd
All safety documents issued by this supervisor.
IssuedSafetyDocuments
{019E9E3C-C2CC-4a76-9DB0-DEC77795FB72}.SupplierEnd
All safety documents released to this supervisor.
ReleasedSafetyDocuments
{9101B352-8544-44a4-9F4A-B24425BA24E4}.SupplierEnd
SourceOperationalLimitType
{B089AC15-CDFC-4c0d-9765-7F449337E6AB}.SupplierEnd
TargetOperationalLimit
{870033E1-C96D-4c7f-BC97-DB2B6D26C20F}.SupplierEnd
The percentage scaling of the source limit to compute the target limit. Applys to operational limits within an operaitonal limit set when both source and target operational limit types exist.
scalingPercent
{F075EE22-BD60-410a-BD34-DB3EC0782816}
All incidents owned by this operator.
Incidents
{C2056AB7-C6BB-48a9-9AC4-CC384465DB27}.ClientEnd
All switching steps this operator is responsible for.
SwitchingSteps
{4CE8C00C-90B0-4798-B63D-CD522B565717}.ClientEnd
Pnode
{94E0B2E3-2515-46e5-ACE3-EE9FFB04B4EA}.SupplierEnd
Maximum MW for the SourceSink for the Allocation
maxMWAllocation
{E4946B4E-E169-4321-B2ED-317D8034E5D2}
RegisteredResource
{AB61B549-CFB6-4874-A737-21DD7CC11D7A}.ClientEnd
association type for the association between Organisation and Resource
asscType
{57004E7F-B083-4ef7-AF68-8908ED46D738}
Flag to indicate that the SC representing the Resource is the Master SC.
masterSchedulingCoordinatorFlag
{EE0A5D17-AD01-473e-9608-EAB24A2125D6}
ownership percentage for each resource
ownershipPercent
{355B6F0A-5E7A-48d9-A4A8-C5937075C606}
Parent organisation of this organisation.
ParentOrganisation
{859EDB59-64A7-41fc-8B17-1A318CDA46C9}.SupplierEnd
All roles of this organisation.
Roles
{69EAE008-4E1D-4248-A3AB-1554BEBAB5B8}.ClientEnd
SwitchingPlanRequest
{9F41E5C9-778C-4e68-B6F3-EE634A0DD569}.ClientEnd
Electronic address.
electronicAddress
{420B480C-5DE3-4687-811D-95091C63FC97}
Phone number.
phone1
{C6A9116C-C752-4c65-B59B-9A77B6149795}
Additional phone number.
phone2
{1857252F-D8A8-45d0-AD06-817CBCA55A73}
Postal address potentially different than streetAddress e.g. another city.
postalAddress
{F59336DC-7E1F-4ef6-8534-6BDF3F957952}
Street address.
streetAddress
{6EDF9FBB-9D0C-4b28-96A8-6E023DBAFD26}
All configuration events created for this organisation role.
ConfigurationEvents
{83D1A41E-45C6-49ba-883F-D9E6B3E0643C}.SupplierEnd
Organisation having this role.
Organisation
{69EAE008-4E1D-4248-A3AB-1554BEBAB5B8}.SupplierEnd
Crew
{D0947F3D-A8D0-4b21-9924-B957AF56DC82}.SupplierEnd
all deenergized useage points associated with the outage.
DeEnergizedUsagePoint
{97DDAF6C-65B2-463f-8202-046CC1702F4C}.SupplierEnd
All energized usage points associated with this outage.
EnergizedUsagePoint
{13D27FCF-5727-416e-9B7E-FCE3388F7C11}.SupplierEnd
All equipments associated with this outage.
Equipments
{7CB5F824-2EAC-4c6e-B3CE-B2B245253D31}.SupplierEnd
EstimatedRestorationTime
{ABABDC87-C805-4e9a-86E2-7C263386DF76}.ClientEnd
All faults involved in this outage.
Faults
{B23C14B3-6E9C-4b0c-82C5-781ED12E4406}.SupplierEnd
Incident reported in trouble call that results in this outage.
Incident
{91D33A1C-B14C-40a2-8C56-19764D00E571}.ClientEnd
OutageArea
{FA533EAF-39C8-41ca-8599-A37602141D77}.ClientEnd
OutageIsolationEquipment
{EEA2935F-26F1-463e-890E-676B5DDA189A}.SupplierEnd
All switch actions to apply within the scope of this planned outage. Each such action groups switches to which the action is to apply in order to produce the desired network state considered as outage.
PlannedSwitchActions
{7DAECB14-3133-4fec-91BB-CBC4E6C8147D}.SupplierEnd
All switching plans that lead to supply restoration due to this outage. Only one will be retained for execution.
SwitchingPlans
{D2D106C9-7B45-4172-8201-66E3FAC64E75}.ClientEnd
Actual outage period end of the period corresponds to the actual restoration time.
actualPeriod
{0AD368D5-C6D0-47a8-B938-051F2AC57B2C}
Estimated outage period for a planned outage. The start of the period is the start of the planned outage and the end of the period corresponds to the end of the planned outage.
estimatedPeriod
{8C9C1A9F-3138-4ade-A916-15CC7860C66E}
Defines if the outage has been verified or is only estimated
outageKind
{4EEF77FC-63B4-44f5-9831-FB5BBDD0FD98}
defines the status of the crew as in dispatched or arrived etc.
statusKind
{CEB45334-9B67-4ff2-AC41-C15BAC571F12}
Summary counts of service points customers affected by this outage.
summary
{092BCE4E-C750-42c7-8623-55B144F00805}
Outage
{FA533EAF-39C8-41ca-8599-A37602141D77}.SupplierEnd
defines the type of area that has the outage county state zipcode etc.
outageAreaKind
{84A9A4DF-C2DA-44d1-880E-B2535B286214}
Location
{5D0E1B69-67C1-469c-B013-AE8901A8B015}.SupplierEnd
OutagePlan
{CC6A368B-E2F3-4765-8252-5F09775C61A8}.ClientEnd
The customers that are affected by this planned outage.
Customer
{2B68C98E-D3F5-4de1-9693-2F2E3F99F1BC}.ClientEnd
OutageOrder
{CC6A368B-E2F3-4765-8252-5F09775C61A8}.SupplierEnd
The outage resulting from the execution of the outage plan.
PlannedOutage
{D5052A16-C1AA-4cfa-B0E4-1C79BE08873C}.SupplierEnd
The swiching plan that is associated with the outage plan.
SwitchingPlan
{205E346A-7AC3-4f63-9926-D90B3687F39B}.ClientEnd
planned start and end time of the planned outage.
plannedPeriod
{5FA03C41-4627-4d3a-B71B-75B8A5497E8E}
Limit value of rated field current iIiisubFDLIMsubi. Typical value 105.
ifdlim
{66957AD8-4FCD-4213-90F5-FB82CD9E5D86}
Gain Over excitation limiter iKiisubOIsubi. Typical value 01.
koi
{B0ACAB27-BDEE-4a04-A31A-6EA6EAAEFD2F}
Maximum error signal iViisubOIMAXsubi gt OverexcLim2.voimin. Typical value 0.
voimax
{3B23EBC7-34DE-4930-B0C7-C48EF5B11E0C}
Minimum error signal iViisubOIMINsubi lt OverexcLim2.voimax. Typical value 9999.
voimin
{115E6DFC-68FC-4812-8490-EB8F660FF379}
OEL pickupdropout hysteresis iHYSTi. Typical value 003.
hyst
{6775D95B-4AD1-4381-81F2-3AD4F9BCE7D5}
OEL timed field current limit iIiisubFDLIMsubi. Typical value 105.
ifdlim
{F9830F3B-CA71-4dbd-B07D-C8B89AB17045}
OEL instantaneous field current limit iIiisubFDMAXsubi. Typical value 15.
ifdmax
{E26BD0DE-A3DF-44d1-B28A-72D67687AB1D}
OEL timed field current limiter pickup level iIiisubTFPUsubi. Typical value 105.
itfpu
{683231C5-5A6A-4b2c-ADEF-07DC80EA390A}
OEL cooldown gain iKiisubCDsubi. Typical value 1.
kcd
{A06197E1-D459-4d9f-B272-50F1E02B0B62}
Low voltage point on the inverse time characteristic iEFDiisub1subi. Typical value 11.
efd1
{6E93D0F1-706F-4a97-BD16-CA06018C721A}
Mid voltage point on the inverse time characteristic iEFDiisub2subi. Typical value 12.
efd2
{C0FA5CFE-B194-40cb-9A5B-4CA852B9CF6F}
High voltage point on the inverse time characteristic iEFDiisub3subi. Typical value 15.
efd3
{D2E6E305-DDE8-4145-8A00-E4CF232BF980}
Desired field voltage iEFDiisubDESsubi. Typical value 09.
efddes
{5EBC6BC9-3478-486d-85C2-959082B3CFEE}
Rated field voltage iEFDiisubRATEDsubi. Typical value 105.
efdrated
{DE1555D8-E82B-4a71-B5F0-F7F81738792E}
Gain iKiisubMXsubi. Typical value 001.
kmx
{F522FB66-52E2-4e73-A046-67AB96645898}
Time to trip the exciter at the low voltage point on the inverse time characteristic iTIMEiisub1subi gt 0. Typical value 120.
t1
{5A860B82-5646-45df-B2AE-F0DF75FC21BD}
Time to trip the exciter at the mid voltage point on the inverse time characteristic iTIMEiisub2subi gt 0. Typical value 40.
t2
{8D730482-987C-4cfa-A383-2512A411A957}
Time to trip the exciter at the high voltage point on the inverse time characteristic iTIMEiisub3subi gt 0. Typical value 15.
t3
{7D221F50-39E9-4fdf-AA40-9A4A701E2B6F}
Low voltage limit iViisubLOWsubi gt 0.
vlow
{A978FFFC-55EA-4ed3-939F-E99DECBAD1E3}
Low voltage or current point on the inverse time characteristic iEFDiisub1subi. Typical value 11.
efd1
{80810BAD-6ADD-4804-8F1E-90CD58477DB0}
Mid voltage or current point on the inverse time characteristic iEFDiisub2subi. Typical value 12.
efd2
{5BC46827-7294-48b7-9FC2-A50165561794}
High voltage or current point on the inverse time characteristic iEFDiisub3subi. Typical value 15.
efd3
{A666F92C-2DE4-4692-A0A5-EA163E033A7A}
Desired field voltage if imi false or desired field current if im i true iEFDiisubDESsubi. Typical value 1.
efddes
{DA111266-23DB-4016-9E0B-3018AFE61789}
Rated field voltage if m false or rated field current if m true iEFDiisubRATEDsubi. Typical value 105.
efdrated
{3C1D582F-A381-492d-816D-78728741AE89}
Gain iKiisubMXsubi. Typical value 0002.
kmx
{CE7DB459-ADDE-4c49-9048-BD054F2A038E}
Time to trip the exciter at the low voltage or current point on the inverse time characteristic iTIMEiisub1subi gt 0. Typical value 120.
t1
{BEDF4730-E0B9-4e21-9A52-E169A0F6E360}
Time to trip the exciter at the mid voltage or current point on the inverse time characteristic iTIMEiisub2subi gt 0. Typical value 40.
t2
{566048CD-4F3D-4c43-A8FA-115FAC3A4DF2}
Time to trip the exciter at the high voltage or current point on the inverse time characteristic iTIMEiisub3subi gt 0. Typical value 15.
t3
{43D2DB67-39E9-496a-971C-FA7680F2EEA7}
Low voltage limit iViisubLOWsubi gt 0.
vlow
{7880978D-4726-4959-AF94-9218A6379989}
Excitation system model with which this overexcitation limiter model is associated.
ExcitationSystemDynamics
{A6EC8E29-6996-4dba-B736-0ACEAFBAD928}.SupplierEnd
Parameter of this proprietary userdefined model.
ProprietaryParameterDynamics
{8154CFB5-D525-420f-B290-005306255D1B}.ClientEnd
WorkCostDetails
{C5ADCDD4-2638-408f-9377-13A155EB81D7}.SupplierEnd
WorkTasks
{B41A8F8E-876B-48ea-B6D2-DE732BA34F6E}.ClientEnd
The overhead cost to be applied.
cost
{E32E78A7-3219-47cf-9C1C-AE27EA7630A7}
status
{F7C9CC16-861A-4d8d-8574-52EFB5A9CDA3}
Asset that is object of this ownership.
Asset
{7323F8B4-3F0F-40c7-8BCA-72BFFF4394A9}.SupplierEnd
Asset owner that is subject in this ownership.
AssetOwner
{4276D5C7-95E8-44db-84E8-C01DA2834B6C}.SupplierEnd
Share of this ownership.
share
{D0968FCF-20A0-4260-8B4A-87C53082B98D}
Excitation system model with which this power actor or VAr controller type 1 model is associated.
ExcitationSystemDynamics
{A9638A5A-FA55-428d-8A6E-7CD1F44F4703}.SupplierEnd
Remote input signal used by this power factor or VAr controller type 1 model.
RemoteInputSignal
{08E5127F-7B16-4f73-A4EF-20E79A544461}.SupplierEnd
Voltage adjuster model associated with this power factor or VAr controller type 1 model.
VoltageAdjusterDynamics
{7A74A658-111A-4af6-B1B7-CAA3F6F7BA11}.ClientEnd
Parameter of this proprietary userdefined model.
ProprietaryParameterDynamics
{836BD709-E07C-4f9e-A2CD-CD5C69C06B2A}.ClientEnd
Excitation system model with which this power factor or VAr controller type 2 is associated.
ExcitationSystemDynamics
{5FBF52C8-0201-4d22-996D-1457516FB808}.SupplierEnd
Parameter of this proprietary userdefined model.
ProprietaryParameterDynamics
{1FD4D65B-F0C9-4390-8928-11A647913605}.ClientEnd
PF controller time delay iTiisubPFCsubi gt 0. Typical value 5.
tpfc
{BF35DF2A-BB20-44b5-9A29-D379F8CF2949}
Minimum machine terminal current needed to enable pfvar controller iViisubITMINsubi.
vitmin
{AA4EDA55-39C8-4770-A4F2-5A260F4FE82F}
Synchronous machine power factor iViisubPFsubi.
vpf
{5C6C7E59-9AC8-4cbd-9DCC-362FDB1A209A}
PF controller reference iViisubPFREFsubi.
vpfref
{9D3C22AD-4A21-45b7-8F5F-02207FA2020E}
Maximum machine terminal voltage needed for pfvar controller to be enabled iViisubVTMAXsubi gt PFVArType1IEEEPFController.vvtmin.
vvtmax
{895E640F-E9DD-4763-B6D9-8E3B8C9E4A51}
Minimum machine terminal voltage needed to enable pfvar controller iViisubVTMINsubi lt PFVArType1IEEEPFController.vvtmax.
vvtmin
{23D4E471-0C6F-42a6-9546-8FB0A3B5BE14}
Var controller time delay iTiisubVARCsubi gt 0. Typical value 5.
tvarc
{949BDAB4-CC6F-4a23-B3D4-52075E7BDC09}
Synchronous machine power factor iViisubVARsubi.
vvar
{1D63915C-5CDA-4d19-84CA-BE19B7275C97}
Var controller reference iViisubVARREFsubi.
vvarref
{A1324C55-CF8C-4767-A8E5-524A379F8C81}
Maximum machine terminal voltage needed for pfVAr controller to be enabled iViisubVTMAXsubi gt PVFArType1IEEEVArController.vvtmin.
vvtmax
{48B2E327-00AB-4caf-82C3-49A30B4DC865}
Minimum machine terminal voltage needed to enable pfvar controller iViisubVTMINsubi lt PVFArType1IEEEVArController.vvtmax.
vvtmin
{A2A74F95-ADFD-49b4-AB46-50E851F92A73}
Reset gain iKii.
ki
{53F1EC69-C547-42db-B42C-D2AAED592E24}
Proportional gain iKpi.
kp
{571AF56B-26D3-4a5e-9C78-FEF6A5799D29}
Output limit imaxi.
max
{FA2E3192-8365-4020-92E1-76CC4DEFE0F9}
Reference value of reactive power or power factor iRefi.The reference value is initialised by this model. This initialisation can override the value exchanged by this attribute to represent a plant operators change of the reference setting.
ref
{3F4F381E-3DE4-4ef0-AB78-89550E557272}
Integral gain of the pf controller iKiisubIsubi. Typical value 1.
ki
{D712B5A8-89FE-4344-BB00-62DD4AC67CFE}
Proportional gain of the pf controller iKiisubPsubi. Typical value 1.
kp
{0944DB7C-E782-431a-AC24-8396563AB454}
Power factor reference iPiisubFREFsubi.
pfref
{BD8E49CB-E735-48c8-9638-2823E1AB8E84}
Maximum output of the pf controller iViisubCLMTsubi. Typical value 01.
vclmt
{AA81F228-F401-43d6-A216-B5038249011E}
Voltage regulator reference iViisubREFsubi.
vref
{8418DF35-E9F9-426a-B701-7B6C66A2A62F}
Integral gain of the pf controller iKiisubIsubi.
ki
{909D4B6B-EC0A-46f2-81E6-162163E00AF1}
Proportional gain of the pf controller iKiisubPsubi.
kp
{F998AC26-3547-4dfe-8BAE-9F779A2BC157}
Reactive power reference iQiisubREFsubi.
qref
{89323CED-C9D0-40bf-9C18-E8ADFAE7F49B}
Maximum output of the pf controller iViisubCLMTsubi.
vclmt
{0E592614-4AF3-4bef-8E8E-4924F3D0B073}
Voltage regulator reference iViisubREFsubi.
vref
{EA57344E-35F0-4549-99AA-3428C83A2157}
Delay
{0A11698D-6954-4f58-B75E-3CBA73047718}.ClientEnd
VSCtype1
{E76FDA89-DE78-4412-88D5-5554DBCA51D8}.SupplierEnd
Power system resource that generated this event.
PowerSystemResource
{8A1816B8-B53E-4ace-9651-A32675F78437}.SupplierEnd
Kind of event.
kind
{A5054EAE-D869-4ceb-BCDB-5062E267179B}
Power system resources classified with this power system resource type.
PowerSystemResources
{739158B5-6CE8-473f-87FF-1CDA17078612}.ClientEnd
multiplier
{39670F5A-8684-4c87-A5BD-DDCDAE008F27}
unit
{D54E5F22-5150-4af7-AFB8-57E4C7ACD22E}
Cold leg feedback lag time constant.
coldLegFBLagTC
{537FBCC6-8E5E-4b3f-993B-CC6782D90488}
Cold leg feedback lead time constant.
coldLegFBLeadTC1
{BF0CAE76-4807-4ef4-A45D-6616C49B5164}
Cold leg feedback lead time constant.
coldLegFBLeadTC2
{DC1ACE90-F79F-4afa-93C6-105B67E9D5FA}
Cold leg feedback gain 1.
coldLegFG1
{A457C8C2-0F4B-4b58-9C75-37B5F1DD314B}
Cold leg feedback gain 2.
coldLegFG2
{6EFAFC52-D699-4ba0-AA4B-A577D5AB1402}
Cold leg lag time constant.
coldLegLagTC
{6F87418C-03EF-41e6-B6D3-8AF359594DB9}
Core heat transfer lag time constant.
coreHTLagTC1
{3D313F7F-D2B2-4b52-A841-85512A06655E}
Core heat transfer lag time constant.
coreHTLagTC2
{BFF946CF-FCBC-488a-B8CD-6C058DEF6527}
Core neutronics effective time constant.
coreNeutronicsEffTC
{2D1AF5A9-4D0D-4dfc-83B4-7FE73678BAB3}
Core neutronics and heat transfer.
coreNeutronicsHT
{F57DEBE5-909E-439f-8B91-0B5C93A1A064}
Feedback factor.
feedbackFactor
{4BD8579F-0FAF-42cd-B648-D416F38B32C6}
Hot leg lag time constant.
hotLegLagTC
{12D5B892-82E2-434c-B4F0-5F3E959D68B0}
Hot leg steam gain.
hotLegSteamGain
{A5BD787B-5C20-45e6-9393-EBC04734313A}
Hot leg to cold leg gain.
hotLegToColdLegGain
{6B67E4DD-756E-4f40-BEF5-31F78CF13704}
Pressure control gain.
pressureCG
{567AC90A-B9D1-41a8-A60F-5F3DCF47773F}
Steam flow feedback gain.
steamFlowFG
{2BE21F18-A2C3-4243-B7E5-C38F1BE91577}
Steam pressure drop lag time constant.
steamPressureDropLagTC
{64695027-4AD8-4826-9CA1-ADBDE27C4037}
Steam pressure feedback gain.
steamPressureFG
{E20F458A-A1C2-4a28-A22E-400E8C96228A}
Throttle pressure factor.
throttlePressureFactor
{736545C0-A272-4846-8F52-5094C2E4AB83}
Throttle pressure setpoint.
throttlePressureSP
{C79842D4-4106-4adb-B8B2-CE38462B6A7B}
Appliance being controlled.
appliance
{78E102A7-2078-4ba0-A5C9-D473517F8D89}
Used to define a maximum energy usage limit as a percentage of the client implementations specific average energy usage. The load adjustment percentage is added to 100 creating a percentage limit applied to the client implementations specific average energy usage. A 10 load adjustment percentage will establish an energy usage limit equal to 90 of the client implementations specific average energy usage. Each load adjustment percentage is referenced to the client implementations specific average energy usage. There are no cumulative effects.The range of this field is 100 to 100 with a resolution of 1. A 100 value equals a total load shed. A 100 value will limit the energy usage to the client implementations specific average energy usage.
avgLoadAdjustment
{05241FB8-A11C-473e-B34C-6431697AFC5C}
Requested offset to apply to the normal cooling setpoint at the time of the start of the event. It represents a temperature change that will be applied to the associated cooling set point. The temperature offsets will be calculated per the local temperature in the thermostat. The calculated temperature will be interpreted as the number of degrees to be added to the cooling set point. Sequential demand response events are not cumulative. The offset shall be applied to the normal setpoint.
coolingOffset
{D6D19B3C-F964-42f2-9304-215DDA9C0F83}
Requested cooling set point. Temperature set point is typically defined and calculated based on local temperature.
coolingSetpoint
{3394913E-3EC6-431e-8336-216F2807CFA8}
Maximum on state duty cycle as a percentage of time. For example if the value is 80 the device would be in an on state for 80 of the time for the duration of the action.
dutyCycle
{6AE1150A-D257-4cfa-BB78-EBEDF16983AF}
Requested offset to apply to the normal heating setpoint at the time of the start of the event. It represents a temperature change that will be applied to the associated heating set point. The temperature offsets will be calculated per the local temperature in the thermostat. The calculated temperature will be interpreted as the number of degrees to be subtracted from the heating set point. Sequential demand response events are not cumulative. The offset shall be applied to the normal setpoint.
heatingOffset
{D228B3BC-35C6-47f1-AF49-7D90DDC366B5}
Requested heating set point. Temperature set point is typically defined and calculated based on local temperature.
heatingSetpoint
{0DEB60D7-E61F-42de-88A1-6368D55F2444}
Transmission mode to be used for this PAN display control.
transmissionMode
{74849BCC-313E-4805-BB77-7927149BFCA8}
All pricing details issued by this PAN pricing commandaction.
PanPricingDetails
{BAEC4D70-D943-4d13-ADC2-66BB67EDAF4E}.SupplierEnd
PAN pricing commandaction issuing this price detail.
PanPricing
{BAEC4D70-D943-4d13-ADC2-66BB67EDAF4E}.ClientEnd
Price of the commodity measured in base unit of currency per unitOfMeasure.
generationPrice
{D4641443-D044-4c9d-B689-A04D75E28388}
Price of the commodity measured in base unit of currency per unitOfMeasure.
price
{B2954B45-91D3-47cb-8D37-8008B91E5C36}
Organisation that is part of this parent organisation.
Organisation
{859EDB59-64A7-41fc-8B17-1A318CDA46C9}.ClientEnd
multiplier
{2DE44EFF-C5E7-4f44-8A44-C6476EBE3F62}
unit
{04DAA147-D0FD-43d2-A1CB-9FF94062683E}
ChargeProfiles
{7A4358BC-7C4E-4235-A405-C2C839499AA8}.ClientEnd
MarketStatementLineItem
{C9289981-55CD-40d3-9FB2-9C66EC3AEB17}.SupplierEnd
MktUserAttribute
{8190276C-7601-4378-973C-AE9F4C42620E}.SupplierEnd
adjustedAmount
{33178D57-6760-42a0-BC4F-DAC34BADC14C}
The charge amount of the productservice.
amount
{AD6A886A-F200-43ad-ACB2-951FACCCB62D}
The price of productservice.
price
{E508A505-F3C1-4431-BD6A-D9E1BEC893AC}
The product quantity.
quantity
{3124D4DB-BB67-4995-9F52-9068696AC6FB}
The tax on services taken.
taxAmount
{6AA26030-6540-4907-B8DE-4352D10D1009}
Delay
{BB5EF20F-F668-4cd3-A8C9-5EAA0AD5F5CF}.ClientEnd
VSCtype1
{3E4C2CFA-1298-41b3-9038-5F139DAC76C3}.SupplierEnd
All blocks of interval reading values to which this pending conversion applies.
IntervalBlocks
{6805BD0C-43D7-4b31-81D9-807FDA537C71}.ClientEnd
Reading type resulting from this pending conversion.
ReadingType
{498A2163-CE45-41ed-9E07-BE86679D0941}.SupplierEnd
A hydro generating unit has a penstock loss curve.
HydroGeneratingUnit
{7ACC0340-79B7-4e30-B609-66235FA04D5D}.SupplierEnd
multiplier
{A2810EB7-9B4B-4386-9EE5-CAE5AB1E6E2C}
unit
{A1336F58-9A3A-462d-A932-4C80CE9A24AB}
All line segments described by this set of perlength parameters.
DCLineSegments
{2DD2B43E-76CD-494b-A33F-018342B6A5C3}.SupplierEnd
Capacitance per unit of length of the DC line segment significant for cables only.
capacitance
{15E50782-BFC5-4868-AB01-397A205F429A}
Inductance per unit of length of the DC line segment.
inductance
{5F8F991E-DBD5-439c-B634-1CBA1A6C8CC2}
Resistance per length of the DC line segment.
resistance
{B64B75B7-7A9B-4a51-A817-628DCF8272BA}
All line segments described by this perlength impedance.
ACLineSegments
{741AE432-C721-4a8d-92F4-C8B96FA98A3A}.SupplierEnd
WireAssemblyInfo
{07F81D46-A7D6-403d-9687-5A39ABF063FB}.ClientEnd
All data that belong to this conductor phase impedance.
PhaseImpedanceData
{5506602F-6D0E-417e-A8EF-92CE8761DBB1}.SupplierEnd
Zero sequence shunt charging susceptance per unit of length.
b0ch
{19485899-99EC-4153-8DF2-A8D9401CD14D}
Positive sequence shunt charging susceptance per unit of length.
bch
{6BFECEA8-BE4E-401b-9E77-C2DF6A5B8688}
Zero sequence shunt charging conductance per unit of length.
g0ch
{2F22AD1F-E6BD-48ab-AF0C-6FECA9347A61}
Positive sequence shunt charging conductance per unit of length.
gch
{F7751ED0-0F91-48b8-BAE7-23EC99566689}
Positive sequence series resistance per unit of length.
r
{7E44D42E-7317-458c-96BB-A3B855A661EE}
Zero sequence series resistance per unit of length.
r0
{8D5D71FD-6C26-4fc4-A1EB-A33694E47A0C}
Positive sequence series reactance per unit of length.
x
{46EE2153-4161-4d60-93F1-342C0040A4D4}
Zero sequence series reactance per unit of length.
x0
{EE0F97E0-7903-463f-B5C2-61B2ACBB2AB5}
MarketDocument
{07DDBEDE-D21C-439d-AAF4-F347D1B02B1E}.ClientEnd
Point
{3D8A83E0-5619-4336-8E5E-7157CFB6ACD9}.ClientEnd
Reason
{E9655504-21F4-4c54-B6E8-8735610776CE}.SupplierEnd
TimeSeries
{2FF42F79-5F9B-4d18-9FE4-F2D14B85ADD8}.ClientEnd
The start and end date and time for a given interval.
timeInterval
{DD1D6EC4-DA3E-4dc9-B849-543C06A8AA95}
Unit in which calculation interval is defined.
calculationIntervalUnit
{D4D54AA8-3192-4eb7-AB62-BB65E7E0E451}
All roles of this person.
Roles
{0E663BCA-51EE-49c8-AC1A-B4DDD37EBF8D}.SupplierEnd
Electronic address.
electronicAddress
{B6E5566E-3885-474b-ADD7-3AA95C15EA3C}
Landline phone number.
landlinePhone
{68F341A5-D6D0-4324-AEFF-6F52998EB8AD}
Mobile phone number.
mobilePhone
{269C84CE-90F7-41ff-AA62-BCF12E049BA2}
ErpPerson
{694B40C4-6F8C-41a2-9D1E-27B7A4572BBE}.ClientEnd
LandProperty
{E882A219-E4D5-4259-AD38-2754C0D502A2}.ClientEnd
Person
{ABB493E7-418A-4fe4-B85B-23905A057C94}.ClientEnd
All appointments for this person.
Appointments
{C9DF52B7-89D3-4d66-8D7F-13A02C9F8C6A}.SupplierEnd
All configuration events created for this person role.
ConfigurationEvents
{472A820F-DB21-4935-A460-E5C9B71BB861}.SupplierEnd
Person having this role.
Person
{0E663BCA-51EE-49c8-AC1A-B4DDD37EBF8D}.ClientEnd
The mode of operation of the Petersen coil.
mode
{9E0AA2E1-5653-4ebc-B5B4-49027065D01D}
The nominal voltage for which the coil is designed.
nominalU
{E1BE229C-3743-423e-8437-A7F7AEC0C9DD}
The offset current that the Petersen coil controller is operating from the resonant point. This is normally a fixed amount for which the controller is configured and could be positive or negative. Typically 0 to 60 A depending on voltage and resonance conditions.
offsetCurrent
{B1508A24-D2C6-4199-A0A8-03BAED4649F6}
The control current used to control the Petersen coil also known as the position current. Typically in the range of 20 mA to 200 mA.
positionCurrent
{C965BDE0-0426-46b5-A0C2-54956F9AD7EE}
The maximum reactance.
xGroundMax
{1FB3F4FB-2915-4aed-92F5-58D3CD2ECDF5}
The minimum reactance.
xGroundMin
{897F6E69-DAE7-4bd0-96F4-CBD61ED7257F}
The nominal reactance. This is the operating point normally over compensation that is defined based on the resonance point in the healthy network condition. The impedance is calculated based on nominal voltage divided by position current.
xGroundNominal
{84902AD5-0FA1-4993-9BDD-9B736E29961E}
Conductor phase impedance to which this data belongs.
PhaseImpedance
{5506602F-6D0E-417e-A8EF-92CE8761DBB1}.ClientEnd
Susceptance matrix element value per length of unit.
b
{1DEC16E8-BB4B-4129-8426-571BE51A06DF}
Refer to the class description.
fromPhase
{FE4138E8-9EA4-444c-8E8A-FE869BA285E5}
Conductance matrix element value per length of unit.
g
{ABCF69F3-3654-4c50-B79A-732107602E40}
Resistance matrix element value per length of unit.
r
{D98F796A-C101-40df-88AA-716D4B1ADDC6}
Refer to the class description.
toPhase
{4F1C3521-EEBF-4308-BD6A-3FE4E034A175}
Reactance matrix element value per length of unit.
x
{662B9C37-BBE3-4d7f-A8A8-1A351B492DD4}
Transformer end to which this phase tap changer belongs.
TransformerEnd
{1CC9941E-7C40-434a-98D6-B767348B392C}.ClientEnd
The phase angle between the inphase winding and the outof phase winding used for creating phase shift. The outofphase winding produces what is known as the difference voltage. Setting this angle to 90 degrees is not the same as a symmetrical transformer. The attribute can only be multiples of 30 degrees. The allowed range is 150 degrees to 150 degrees excluding 0.
windingConnectionAngle
{73F12408-9962-4614-8F76-9276D859E042}
Phase shift per step position. A positive value indicates a positive angle variation from the Terminal at the PowerTransformerEnd where the TapChanger is located into the transformer.The actual phase shift increment might be more accurately computed from the symmetrical or asymmetrical models or a tap step table lookup if those are available.
stepPhaseShiftIncrement
{0A0AF042-84CF-4e48-996A-60122C60C8C7}
The reactance depends on the tap position according to a u shaped curve. The maximum reactance xMax appears at the low and high tap positions. Depending on the u curve the attribute can be either higher or lower than PowerTransformerEnd.x.
xMax
{03CCD0FC-F097-4b6c-B818-30E1C538B4CC}
The reactance depends on the tap position according to a u shaped curve. The minimum reactance xMin appears at the mid tap position. PowerTransformerEnd.x shall be consistent with PhaseTapChangerLinear.xMin and PhaseTapChangerNonLinear.xMin. In case of inconsistency PowerTransformerEnd.x shall be used.
xMin
{E65A4D9F-3409-4701-BCFA-927E64603CC6}
The voltage step increment on the out of phase winding the PowerTransformerEnd where the TapChanger is located specified in percent of rated voltage of the PowerTransformerEnd. A positive value means a positive voltage variation from the Terminal at the PowerTransformerEnd where the TapChanger is located into the transformer.When the increment is negative the voltage decreases when the tap step increases.
voltageStepIncrement
{5CB8CF11-E238-4e2b-A64C-4D6F353E8BD7}
The reactance depends on the tap position according to a u shaped curve. The maximum reactance xMax appears at the low and high tap positions. Depending on the u curve the attribute can be either higher or lower than PowerTransformerEnd.x.
xMax
{85F2E96A-037E-49cb-A502-52D5D496ECBF}
The reactance depend on the tap position according to a u shaped curve. The minimum reactance xMin appear at the mid tap position. PowerTransformerEnd.x shall be consistent with PhaseTapChangerLinear.xMin and PhaseTapChangerNonLinear.xMin. In case of inconsistency PowerTransformerEnd.x shall be used.
xMin
{0E3B5325-2A89-476d-9A79-CD4ACD14C5FE}
The points of this table.
PhaseTapChangerTablePoint
{8FA5B368-A444-46c0-8ABF-395C08B18AEA}.ClientEnd
The phase tap changers to which this phase tap table applies.
PhaseTapChangerTabular
{C44C5EDF-9A90-4699-8F22-C6DB647DA10B}.SupplierEnd
The table of this point.
PhaseTapChangerTable
{8FA5B368-A444-46c0-8ABF-395C08B18AEA}.SupplierEnd
The angle difference in degrees. A positive value indicates a positive angle variation from the Terminal at the PowerTransformerEnd where the TapChanger is located into the transformer.
angle
{7D40B9B7-F9FC-45a0-A7CE-28D3DC182E4D}
The phase tap changer table for this phase tap changer.
PhaseTapChangerTable
{C44C5EDF-9A90-4699-8F22-C6DB647DA10B}.ClientEnd
Condition contributing to the classification of this phenomenon.
ClassificationCondition
{0E97F0E1-C420-4b89-983A-670FE0F14582}.ClientEnd
Authority defining this environmental phenomenon.
EnvironmentalDataAuthority
{A0D7C120-ECE6-4c9b-B9F6-B37F0029DA01}.SupplierEnd
EnvironmentalPhenomenon
{CEAA1D59-2A12-4a25-A69D-ACC8789B4E11}.ClientEnd
The branch group that should be used in compare.
BranchGroup
{CB739CC6-8BA5-4ceb-BD00-62D8654B263A}.SupplierEnd
The compare operation done on the branch group.
kind
{E23F693A-5C82-4520-8600-24F5D9399438}
The Equipment that should be used in compare.
Equipment
{83B2D8C8-5F34-4fbe-A13F-090F6823061D}.SupplierEnd
The compare operation done on the equipment.
kind
{BE6A78EC-8295-48c4-8956-E03F158C1853}
GateOutput
{71584FA4-43BB-4d8b-84DF-B578C3B8580C}.ClientEnd
The Measurement that should be used in compare.
Measurement
{D94A460B-0ABB-4872-900D-CDEEB9374DB3}.SupplierEnd
Result of the calculation used as input to a gate.
MeasurementCalculator
{CFBABACD-D1FC-46de-8BA7-DA6F2F4B3CC9}.ClientEnd
The Terminal that should be used in compare.
Terminal
{70327476-E811-4a87-97E1-35C5519C96DC}.SupplierEnd
The compare operation done on the terminal.
kind
{EFEF51B4-E261-43f7-AE5A-4C78383F9CC9}
A market plan has a number of markets DA HA RT.
MarketPlan
{9939F0DA-F147-4cab-A25A-C40C674AF836}.ClientEnd
A planned market could have multiple market runs for the reason that a planned market could have a rerun.
MarketRun
{E537509E-3F2D-41ba-881E-85BABB782FC0}.SupplierEnd
A planned market shall have a set of planned events
PlannedMarketEvent
{05AB4FB1-EAD5-41a2-A114-2A1E55AD4E0B}.SupplierEnd
Market type.
marketType
{A36284FB-32CA-4120-9EEA-30D4848E0F2D}
All actual events that execute this planned event.
MarketActualEvent
{6F2C5CBA-31FA-4fbf-93FC-0732720881FC}.ClientEnd
A planned market shall have a set of planned events
PlannedMarket
{05AB4FB1-EAD5-41a2-A114-2A1E55AD4E0B}.ClientEnd
FieldDispatchHistory
{37072B50-0229-4a00-A050-8976613B5259}.ClientEnd
Outage plan for executing a planned outage.
OutagePlan
{D5052A16-C1AA-4cfa-B0E4-1C79BE08873C}.ClientEnd
All updated ratings for this planned equipment outage.
UpdatedRatings
{C5F3A5B0-064B-4cc4-AA34-0296D8D7919A}.ClientEnd
Customer
{C3BE4896-4663-4669-84A9-B881796117E5}.SupplierEnd
SwitchingPlan
{D86059AA-B4DC-4561-AA64-9EF56A447F18}.SupplierEnd
AggregateNode
{CAB06BAC-94AA-411c-9272-D4C6EB676F32}.ClientEnd
CommodityDefinition
{F9E2DDE2-0FFA-44c6-9186-CCF290EFA2ED}.ClientEnd
DeliveryTransactionBids
{34A3B7CA-5000-4f2c-85C0-4A822CE31BA9}.SupplierEnd
ExPostResults
{E05F725E-CEBB-458d-9E58-0F2247135211}.SupplierEnd
FTRs
{A43D8B73-D014-475b-8461-B03EC8169BB8}.ClientEnd
Allows Measurements to be associated to Pnodes.
MktMeasurement
{72AD4107-7210-4172-B722-F58EA3179E3E}.SupplierEnd
OrgPnodeAllocation
{94E0B2E3-2515-46e5-ACE3-EE9FFB04B4EA}.ClientEnd
PnodeResults
{2F4D2395-38CC-4e92-B4E4-A65606A9903C}.SupplierEnd
RTO
{226E4117-5AE6-4526-BD59-AE3741B82CD9}.ClientEnd
ReceiptTransactionBids
{ACB6DCFB-9B97-4ab9-AE5A-A643C314A45D}.SupplierEnd
A registered resource injects power at one or more connectivity nodes related to a pnode
RegisteredResources
{6A346D84-A25C-41c8-8AFD-BB63272C9F39}.SupplierEnd
SinkCRRSegment
{6840ECDE-F677-428f-9118-D01BDF989AE0}.SupplierEnd
SourceCRRSegment
{C97DA9A4-D136-4894-A6A2-CA207A447300}.SupplierEnd
SubControlArea
{EE82157A-8E48-4af6-9DC9-7A0098943EE0}.SupplierEnd
Trade
{D878BD22-6A72-4e0c-8DFA-7844C9BCA884}.SupplierEnd
CommodityPrice
{B037CDCC-4EA4-4d2d-8CF4-27BBEFA157FC}.SupplierEnd
PnodeResults
{BD964F65-1835-43f0-9378-E63CB1D35575}.SupplierEnd
AggregatedPnode
{C455B6B7-BDE8-4036-B32B-EFD8413FD6B7}.ClientEnd
BidDistributionFactor
{92BD0FDA-3BFA-4ea4-9233-9C19F31CCB39}.ClientEnd
IndividualPnode
{24E9F23C-430E-4596-B763-07DB8054801D}.ClientEnd
Indication that this distribution factor is to apply during off peak.
offPeak
{403623AD-6F2D-4f82-8618-65C566EBCB23}
Indication that this factor is to apply during Peak periods.
onPeak
{3264FF8A-5DA4-4a33-85F7-0AD012EAC3A3}
Pnode
{2F4D2395-38CC-4e92-B4E4-A65606A9903C}.ClientEnd
PnodeClearing
{BD964F65-1835-43f0-9378-E63CB1D35575}.ClientEnd
updateType
{78192DBC-041C-47f1-97CA-8C6FF75ECFF6}
AceTariffType
{BABB4FDB-5AA4-4c38-80B1-35F9E79D3BAE}.SupplierEnd
FlowDirection
{DA5D6A56-1992-4d38-994D-E118A3CDC921}.ClientEnd
Period
{3D8A83E0-5619-4336-8E5E-7157CFB6ACD9}.SupplierEnd
Price
{F4D10473-017B-4e8a-95D0-6C83335A55CB}.ClientEnd
Quantity
{70A03E37-CDFC-438e-BB13-DBBD82A9288E}.ClientEnd
Reason
{5937F13C-6809-4fd4-9A5E-CC24BE6B8CA7}.ClientEnd
TimeSeries
{E778FB34-70AF-4315-A61A-98894C17384B}.SupplierEnd
All shifts this point of sale operated in.
CashierShifts
{5F23BDB7-8C52-4be9-BDFD-61927D2EA76C}.ClientEnd
All streetlights attached to this pole.
Streetlights
{7CD98E1E-DB38-4f5f-B4AB-606B687CE71D}.SupplierEnd
Kind of base for this pole.
baseKind
{624A4E48-10A0-4ab3-A7B4-8E81D1533FD0}
Diameter of the pole.
diameter
{D98F5A13-BF6D-4ad0-A7D0-C58D478FC2CE}
Length of the pole inclusive of any section of the pole that may be underground postinstallation.
length
{07335125-0D59-4779-9824-D767C3E0FDD4}
Kind of preservative for this pole.
preservativeKind
{BEB20D48-1F28-4073-8A40-B0CF0E81670B}
Kind of treatment for this pole.
treatmentKind
{11E35D3E-7280-4641-9746-9F283AFE6964}
Location described by this position point.
Location
{DBF35456-ABE1-4deb-A885-2E48B3D6F8F6}.ClientEnd
Potential transformer construction type.
type
{EBA48103-D1D0-40ca-A26E-1192BB845D6B}
nominalRatio
{DE855743-0E60-46a8-BF3B-DF1F23D95114}
Ratio for the primary winding tap changer.
primaryRatio
{A5150EE5-BFDD-4a2e-BB70-C2E92F558421}
Rated voltage on the primary side.
ratedVoltage
{F7E6C2CB-1DFE-4249-9440-837196C8F912}
Ratio for the secondary winding tap changer.
secondaryRatio
{BE6A3168-8DD7-48ef-80AE-0C2C8E680535}
Ratio for the tertiary winding tap changer.
tertiaryRatio
{00C30FD6-1010-4aad-9D11-E2DE46FCD426}
Energy consumer is assigned to the power cut zone.
EnergyConsumers
{10EFC7AF-BD27-4bf9-A05B-BA2A5970F59A}.SupplierEnd
First level amount of load to cut as a percentage of total zone load.
cutLevel1
{DB7E760E-68D5-47b3-B342-CA51A4134645}
Second level amount of load to cut as a percentage of total zone load.
cutLevel2
{84DC2C8B-8922-4736-A581-3989CB5D79FB}
The individual phases models for the power electronics connection.
PowerElectronicsConnectionPhase
{99A71DC5-9620-460a-B0F1-AE69019A3DB9}.SupplierEnd
An AC network connection may have several power electronics units connecting through it.
PowerElectronicsUnit
{8AC914EE-116B-477b-A122-C5E4A57DECDE}.SupplierEnd
The wind turbine type 3 or type 4 dynamics model associated with this power electronics connection.
WindTurbineType3or4Dynamics
{55DFB003-A30A-4242-A110-1251E461ED28}.ClientEnd
Maximum fault current this device will contribute in perunit of rated current before the converter protection will trip or bypass.
maxIFault
{9E9630BE-7754-4d85-A4A9-D48ED99DB232}
Maximum reactive power limit. This is the maximum nameplate limit for the unit.
maxQ
{923BD813-8AFE-4d59-89ED-D9E09A386346}
Minimum reactive power limit for the unit. This is the minimum nameplate limit for the unit.
minQ
{50765898-4B48-40ad-8D81-0544B670F0CA}
Active power injection. Load sign convention is used i.e. positive sign means flow out from a node.Starting value for a steady state solution.
p
{E50A8D52-31FA-46ce-A1A7-1A680426BCE0}
Reactive power injection. Load sign convention is used i.e. positive sign means flow out from a node.Starting value for a steady state solution.
q
{653A93F9-690F-4825-8C09-B75BC246100B}
Equivalent resistance RG of generator. RG is considered for the calculation of all currents except for the calculation of the peak current ip. Used for short circuit data exchange according to IEC 60909.
r
{981CA1B3-83EF-46c2-BAC5-BF1A66770D46}
Zero sequence resistance of the synchronous machine.
r0
{C264E3E0-424B-4042-B6BB-B8D2E54E29BC}
Nameplate apparent power rating for the unit.The attribute shall have a positive value.
ratedS
{AF84AC1B-4955-464e-BCC2-F4DAE8E96958}
Rated voltage nameplate data Ur in IEC 609090. It is primarily used for short circuit data exchange according to IEC 60909.The attribute shall be a positive value.
ratedU
{07C8D926-E1AA-4271-8FED-BE90CAB30360}
Negative sequence Thevenin resistance.
rn
{A4C54A90-737E-467e-8AE4-F86A7E30E637}
Positive sequence Thevenin reactance.
x
{F091C7E2-D681-44f0-B0E1-7F74529A9B93}
Zero sequence Thevenin reactance.
x0
{B70E3ED7-0B60-44f4-A893-9E40B93AD501}
Negative sequence Thevenin reactance.
xn
{D46879D7-923F-4270-94B0-53E739144605}
Power electronics connection of this power electronics connection phase.
PowerElectronicsConnection
{99A71DC5-9620-460a-B0F1-AE69019A3DB9}.ClientEnd
Active power injection. Load sign convention is used i.e. positive sign means flow into the equipment from the network.
p
{3C2706EB-9824-4f51-BC9E-568AE958790F}
Phase of this energy producer component. If the energy producer is wye connected the connection is from the indicated phase to the central ground or neutral point. If the energy producer is delta connected the phase indicates an energy producer connected from the indicated phase to the next logical nonneutral phase.
phase
{FE3E371D-D600-4c25-83DF-6FAC560B4C5C}
Reactive power injection. Load sign convention is used i.e. positive sign means flow into the equipment from the network.
q
{73316C88-88F9-4b33-84AE-4D9A2A3F8B5A}
A power electronics unit has a connection to the AC network.
PowerElectronicsConnection
{8AC914EE-116B-477b-A122-C5E4A57DECDE}.ClientEnd
Maximum active power limit. This is the maximum nameplate limit for the unit.
maxP
{7E4ECD94-7AF7-4272-B3A0-9D43EB43396B}
Minimum active power limit. This is the minimum nameplate limit for the unit.
minP
{A00BE308-7FF6-494b-AC6D-4F0EF01F6D84}
Emergency high voltage limit.
emergencyHighVoltLimit
{53493219-2615-4730-B13F-FD3B8110A474}
Emergency low voltage limit.
emergencyLowVoltLimit
{3C73A8F4-962D-4adc-B790-2AE44E40DC45}
Normal high voltage limit.
normalHighVoltLimit
{3121953F-E24E-4330-BF3F-C6855B0B9658}
Normal low voltage limit.
normalLowVoltLimit
{733F6E47-0C19-4434-938B-6C3F220A8ECA}
Value of uninterrupted service Cost per energy.
valueUninterruptedServiceEnergy
{48C24858-8B1B-48e0-933E-AF52E7748427}
Datasheet information for this power system resource.
AssetDatasheet
{009BA3E8-B2DD-4bef-B118-F700692FC9EA}.ClientEnd
All assets represented by this power system resource. For example multiple conductor assets are electrically modelled as a single AC line segment.
Assets
{9709C87C-3A85-4ce4-BA02-CEBB104E7DB5}.ClientEnd
All clearances applicable to this power system resource.
Clearances
{65134A4B-0FD0-4c17-A353-8696C19D36F6}.ClientEnd
ConfigurationEvent
{26DFEBF9-D038-4c7e-96A1-F4832AC44307}.SupplierEnd
The controller outputs used to actually govern a regulating device e.g. the magnetization of a synchronous machine or capacitor bank breaker actuator.
Controls
{A1BE05F6-8AA3-4c36-B00D-9A3BC3D8B4D3}.SupplierEnd
GenericAction
{7F56BF7C-C7AA-432b-8454-59AE37E0C7F8}.ClientEnd
Location of this power system resource.
Location
{9F4B30FA-0A66-4ce4-9A00-413B0DB058C7}.ClientEnd
The measurements associated with this power system resource.
Measurements
{78186A65-461E-4479-9917-94B5C4F2F9F6}.SupplierEnd
The operating shares of this power system resource.
OperatingShare
{343B3487-FA8E-4906-A8F1-4D6E3B27F4AF}.ClientEnd
All operational tags placed on this power system resource.
OperationalTags
{AB49BFBC-0F00-4bf2-95B2-BCBAD3CA1BA5}.ClientEnd
All events associated with this power system resource.
PSREvents
{8A1816B8-B53E-4ace-9651-A32675F78437}.ClientEnd
Custom classification for this power system resource.
PSRType
{739158B5-6CE8-473f-87FF-1CDA17078612}.SupplierEnd
Reporting groups to which this power system resource belongs.
ReportingGroup
{62E3FEEC-F7FE-4ee8-88DC-231AEF7F6DE3}.ClientEnd
VerificationAction
{4F85BB5D-133B-4060-B422-86E5B9320EE2}.ClientEnd
Excitation system model with which this power system stabilizer model is associated.
ExcitationSystemDynamics
{EC18A533-5643-4fe6-87AE-2182DD4C9F1F}.SupplierEnd
Remote input signal used by this power system stabilizer model.
RemoteInputSignal
{57187DF7-A206-4e9a-BEB5-C8CEE8478241}.SupplierEnd
Parameter of this proprietary userdefined model.
ProprietaryParameterDynamics
{7EC302C9-2A4C-4779-A3DB-B8F2587D9C33}.ClientEnd
The ends of this power transformer.
PowerTransformerEnd
{AAC9230B-982D-4588-BD28-882E60820FEA}.SupplierEnd
All transformers that belong to this bank.
TransformerTanks
{732D3510-8B59-4b75-8EBD-5E7EFC0BD19D}.ClientEnd
The highest operating current Ib in IEC 609090 before short circuit depends on network configuration and relevant reliability philosophy. It is used for calculation of the impedance correction factor KT defined in IEC 609090.
beforeShCircuitHighestOperatingCurrent
{AE4EA8D2-F7DE-4b53-BB69-AC364144A1CF}
The highest operating voltage Ub in IEC 609090 before short circuit. It is used for calculation of the impedance correction factor KT defined in IEC 609090. This is worst case voltage on the low side winding 3.7.1 of IEC 609092001. Used to define operating conditions.
beforeShCircuitHighestOperatingVoltage
{4E3E92DC-A260-4f23-87CC-E569FF4567A7}
The angle of power factor before short circuit phib in IEC 609090. It is used for calculation of the impedance correction factor KT defined in IEC 609090. This is the worst case power factor. Used to define operating conditions.
beforeShortCircuitAnglePf
{041C6D4A-4D33-416b-869F-3546D7B28527}
The minimum operating voltage uQmin in IEC 609090 at the high voltage side Q side of the unit transformer of the power station unit. A value well established from longterm operating experience of the system. It is used for calculation of the impedance correction factor KG defined in IEC 609090.
highSideMinOperatingU
{B621D953-1CCB-4d6e-AE7D-6231CCE96831}
The power transformer of this power transformer end.
PowerTransformer
{AAC9230B-982D-4588-BD28-882E60820FEA}.ClientEnd
Magnetizing branch susceptance B mag. The value can be positive or negative.
b
{049B7FAE-6F21-4fa4-9BDC-744C262C99AB}
Zero sequence magnetizing branch susceptance.
b0
{9F90313E-3782-459e-A4BC-66938E5A52F5}
Kind of connection.
connectionKind
{BC71F2C6-F76B-459a-A7AF-04800FBD1AE6}
Magnetizing branch conductance.
g
{1DB7A689-A778-4f98-821B-549122D33482}
Zero sequence magnetizing branch conductance starmodel.
g0
{40582586-E7A8-4d85-9328-02F6B38300A1}
Resistance starmodel of the transformer end.The attribute shall be equal to or greater than zero for nonequivalent transformers.
r
{7B85D922-082E-482e-A2FB-D2164647BE6E}
Zero sequence series resistance starmodel of the transformer end.
r0
{ED74BF4C-8DAC-425b-9352-4051C611F9BC}
Normal apparent power rating.The attribute shall be a positive value. For a twowinding transformer the values for the high and low voltage sides shall be identical.
ratedS
{03C41DCA-8576-4294-B1A4-64D6289BC413}
Rated voltage phasephase for threephase windings and either phasephase or phaseneutral for singlephase windings.A high voltage side as given by TransformerEnd.endNumber shall have a ratedU that is greater than or equal to ratedU for the lower voltage sides.The attribute shall be a positive value.
ratedU
{38795744-6A3E-4a62-A8D9-E3FCF020A456}
Positive sequence series reactance starmodel of the transformer end.
x
{0DDEF3C0-D3D0-475e-8C6F-D7363D0E5AF4}
Zero sequence series reactance of the transformer end.
x0
{9F61AC19-7526-4234-AB78-F7FC96E9833F}
Data for all the tanks described by this power transformer data.
TransformerTankInfos
{C20239B0-27AB-4040-9B55-35834EB98EDC}.ClientEnd
multiplier
{AD8A8750-8E4A-4e85-87DF-E1E986A67FBA}
unit
{6D35CBFE-ECA6-4cdd-B823-9E7AC7B978D6}
Domain
{58FBC0F0-40DD-4dbd-A8BE-9C241403F4DB}.SupplierEnd
Point
{F4D10473-017B-4e8a-95D0-6C83335A55CB}.SupplierEnd
TimeSeries
{76FC513C-3CAE-45e6-9CD8-53B33147F936}.SupplierEnd
CommodityPrice
{0E804F54-A29B-4452-B7D6-078FE7D84D1F}.ClientEnd
The time frame for the price using the standard conventions associated with the MarketType enumeration.
marketType
{4E6648A6-B0B8-4314-A3BA-B5BC6FA737AC}
The kind of price being described. In general the priceType will either be total to signify that the price is the price paid to buy or sell the commodity sometimes referred to as an allin price or one of potentially many components.
priceType
{5FDB37AC-5F5B-4580-A8EA-D994C2E04281}
All customer agreements with this pricing structure.
CustomerAgreements
{2EF6BAD9-95F9-48bf-9408-24054A043C0F}.ClientEnd
Service category to which this pricing structure applies.
ServiceCategory
{4940002E-34B8-4d2b-96A5-2E4EC7A20FF2}.ClientEnd
All tariffs used by this pricing structure.
Tariffs
{680631D0-BB57-456d-A598-1F9D4D60D510}.SupplierEnd
All transactions applying this pricing structure.
Transactions
{25EA2CE6-048D-4220-8F20-CA27D99F9BAE}.SupplierEnd
All service delivery points with prepayment meter running as a standalone device with no CustomerAgreement or Customer to which this pricing structure applies.
UsagePoints
{E0F674C9-204B-4aa1-9887-8B17137752E6}.SupplierEnd
accounting Kind of revenue often used to determine the grace period allowed before collection actions are taken on a customer grace periods vary between revenue classes.
revenueKind
{9C08315F-A074-429a-A117-3870EAACDD77}
Synchronous machines this Prime mover drives.
SynchronousMachines
{9C153102-5D80-4895-9BF2-7371CA48A80D}.SupplierEnd
All assets to which this procedure applies.
Assets
{3458C266-F6A0-4e72-8A55-BFFF83421DE2}.SupplierEnd
CompatibleUnits
{A0D146CA-A291-4aa2-8C93-C33AFCBB974E}.ClientEnd
Limits
{B58288B5-634A-4da2-AF81-FC8EE0EB0F45}.SupplierEnd
Document containing this measurement.
Measurements
{FEA58AE6-6428-4541-9097-FEFB35D64AD7}.SupplierEnd
All data sets captured by this procedure.
ProcedureDataSets
{BBF99755-5B8E-4ec2-9DBC-F1E8BD1714ED}.SupplierEnd
Kind of procedure.
kind
{622F03BF-37D4-4cc6-A997-5D10A488B99F}
Asset to which this procedure data set applies.
Asset
{F1E16F01-CC4F-4170-9610-3C1C6E17A43F}.SupplierEnd
MeasurementValue
{A0C93754-F2B4-4597-96C0-BDCA60E5BC09}.SupplierEnd
Procedure capturing this data set.
Procedure
{BBF99755-5B8E-4ec2-9DBC-F1E8BD1714ED}.ClientEnd
UserAttributes used to specify further properties of this procedure data set. Use name to specify what kind of property it is and value.value attribute for the actual value.
Properties
{779BA9D1-950E-4184-B4C5-D887B32ECEDB}.ClientEnd
TransformerObservations
{8D7EAE31-2FA3-4a2f-84AC-416327FD5679}.SupplierEnd
Work task that created this procedure data set.
WorkTask
{78EB6E9E-9B0C-466e-B813-E041B622EF3D}.SupplierEnd
MarketDocument
{02A672D8-0CED-4250-99DC-0E425C62E548}.SupplierEnd
An asset of this model.
Asset
{24E0529D-66B4-4bd0-BE95-E9F7A501079C}.ClientEnd
Asset information nameplate for this product asset model.
AssetInfo
{C53749B6-0642-4045-81C7-6DC6CDBC280D}.SupplierEnd
AssetModelCatalogueItems
{4AAC30DE-2757-4a42-BD3F-E6C4713581FA}.SupplierEnd
Catalog asset type to which this product asset model conforms.
CatalogAssetType
{2558E36F-4A9B-4eab-B70C-B1D8802138AE}.SupplierEnd
Manufacturer of this asset model.
Manufacturer
{4B21049D-BA80-4bd7-A107-BD54730986AA}.SupplierEnd
All operational restrictions applying to this asset model.
OperationalRestrictions
{52B7FEC7-526D-4b4e-8839-1C5E1DE7D0A4}.ClientEnd
Kind of corporate standard for this asset model.
corporateStandardKind
{BB1C84F5-BD18-4030-A6BF-76BDB18B182F}
Overall length of this asset model.
overallLength
{1D1B7E6D-C796-4ea3-BE5C-E190FD99677F}
Intended usage for this asset model.
usageKind
{D588FE49-9E84-416d-A061-0F2C2A66CEBD}
Total manufactured weight of asset.
weightTotal
{5BA8CFE6-3E0B-4d77-8910-62D0B57A2537}
A bid comprises one or more product bids of market products
Bid
{BCC6B1A9-977E-41f0-9C3A-DDB18F4AA27F}.SupplierEnd
BidDistributionFactor
{566D5A4B-E23C-4c3e-81A6-C484F10859CC}.SupplierEnd
BidHourlyProductSchedule
{ED4A9CB4-F670-45e4-B569-BC258596026F}.ClientEnd
BidSchedule
{E6A900FF-246B-49e3-8F19-A2DBF2BB4BB5}.SupplierEnd
BidSelfSched
{62141B29-E60E-480d-B668-C305C09264D7}.SupplierEnd
MarketProduct
{E7348A42-CD3B-49ba-B555-9BE41638E702}.ClientEnd
The data sets that make use of the profile.
DataSet
{A554D44F-37A9-44b7-878F-CDC356BA0B3A}.ClientEnd
A profile has profile data associated with it.
ProfileDatas
{4E6C16FA-9BCA-473a-841B-EB80A9400115}.ClientEnd
A profile has profile data associated with it.
Profile
{4E6C16FA-9BCA-473a-841B-EB80A9400115}.SupplierEnd
Capacity level for the profile in MW.
capacityLevel
{4C847B36-679A-4036-9C3B-B42AD11BAB02}
Energy level for the profile in MWH.
energyLevel
{E6477DF2-D56C-4bb1-A721-AAF48E6C609E}
BusinessCase
{3E0CE628-2617-4405-B164-788B1A9E8408}.ClientEnd
ErpProjectAccounting
{55D017C7-9C0F-40fb-81EF-FC182E6BDAAE}.ClientEnd
ParentProject
{21F63393-A2CF-4d44-A733-C5191FBFB5E1}.ClientEnd
SubProjects
{21F63393-A2CF-4d44-A733-C5191FBFB5E1}.SupplierEnd
Works
{FD74BD30-960D-447e-B2BA-F87F95FF9001}.ClientEnd
Overall project budget.
budget
{92E4D4E2-B3DF-4940-9EAA-EA899D2D51DD}
LandProperty
{125BFBC7-E66A-4486-A898-CE2D1087BB13}.ClientEnd
CUMaterialItems
{EBAAAA49-96BE-4f07-8F12-EAF5BDD82A20}.SupplierEnd
CompatibleUnits
{730C905B-BBFC-44aa-A988-5BCE91C46E12}.SupplierEnd
WorkCostDetails
{A4CC1ED7-99AE-40a3-8386-8274E4C431D9}.ClientEnd
Activity code identifies a specific and distinguishable work action.
activityCode
{2974AAA7-F19D-4001-8DE1-65656B62A853}
status
{F4B6353B-20EA-4317-938E-796D5052841C}
distributionFactor
{0BF94D9F-91D4-4536-B51C-E765D72885A2}
Proprietary userdefined model with which this parameter is associated.
AsynchronousMachineUserDefined
{D22E87BF-F1D2-49ef-B02C-1F3F666251B8}.SupplierEnd
Proprietary userdefined model with which this parameter is associated.
CSCUserDefined
{BDBA0EFE-6EA8-41c4-B3E1-5DE008753AF0}.ClientEnd
Proprietary userdefined model with which this parameter is associated.
DiscontinuousExcitationControlUserDefined
{2215F246-53D4-4620-8772-22C2E52230A8}.SupplierEnd
Proprietary userdefined model with which this parameter is associated.
ExcitationSystemUserDefined
{5206A5D1-9E7E-4283-B6EF-7F3C51885F61}.SupplierEnd
Proprietary userdefined model with which this parameter is associated.
LoadUserDefined
{42F5637B-59FE-4442-AC86-EC1605637C40}.SupplierEnd
Proprietary userdefined model with which this parameter is associated.
MechanicalLoadUserDefined
{16E261AB-0A61-4015-A4AF-C0D1E3AADE99}.SupplierEnd
Proprietary userdefined model with which this parameter is associated.
OverexcitationLimiterUserDefined
{8154CFB5-D525-420f-B290-005306255D1B}.SupplierEnd
Proprietary userdefined model with which this parameter is associated.
PFVArControllerType1UserDefined
{836BD709-E07C-4f9e-A2CD-CD5C69C06B2A}.SupplierEnd
Proprietary userdefined model with which this parameter is associated.
PFVArControllerType2UserDefined
{1FD4D65B-F0C9-4390-8928-11A647913605}.SupplierEnd
Proprietary userdefined model with which this parameter is associated.
PowerSystemStabilizerUserDefined
{7EC302C9-2A4C-4779-A3DB-B8F2587D9C33}.SupplierEnd
Proprietary userdefined model with which this parameter is associated.
SVCUserDefined
{16A60C5C-8F8E-4e74-BF69-62A6C79FF350}.ClientEnd
Proprietary userdefined model with which this parameter is associated.
SynchronousMachineUserDefined
{996B609E-F446-4d2f-89B1-0A3771AD65C2}.SupplierEnd
Proprietary userdefined model with which this parameter is associated.
TurbineGovernorUserDefined
{E9CE179B-FE93-40fa-AF55-290AFD448CA7}.SupplierEnd
Proprietary userdefined model with which this parameter is associated.
TurbineLoadControllerUserDefined
{B43C2066-FB4C-497e-9C4F-E259EF67913D}.SupplierEnd
Proprietary userdefined model with which this parameter is associated.
UnderexcitationLimiterUserDefined
{B7D39B4A-5132-4f2d-8450-A510C4F0B92A}.SupplierEnd
Proprietary userdefined model with which this parameter is associated.
VSCUserDefined
{AB07F11F-12BF-40f7-A3A5-86F42927D688}.ClientEnd
Proprietary userdefined model with which this parameter is associated.
VoltageAdjusterUserDefined
{DF4D0AAC-C129-47a1-ADAF-DB0071F13178}.SupplierEnd
Proprietary userdefined model with which this parameter is associated.
VoltageCompensatorUserDefined
{8A60B7E2-A760-4eba-9D83-DDFC09AE0C14}.SupplierEnd
Proprietary userdefined model with which this parameter is associated.
WindPlantUserDefined
{92B518F0-1BFC-4f7d-A5E3-B076C3298208}.ClientEnd
Proprietary userdefined model with which this parameter is associated.
WindType1or2UserDefined
{88DDF410-39C9-46c0-AC56-EC92DA7D9E97}.ClientEnd
Proprietary userdefined model with which this parameter is associated.
WindType3or4UserDefined
{7F96DE9C-5421-45cc-A5C5-B8C03C2B4B23}.ClientEnd
Protection equipments that operate this ProtectedSwitch.
OperatedByProtectionEquipment
{AEDB116C-6830-4d8b-96FA-C4ADA5EFF5CB}.ClientEnd
A breaker may have zero or more automatic reclosures after a trip occurs.
RecloseSequences
{6447ED06-EC4F-4efc-88F3-7FB21521C7FC}.ClientEnd
The maximum fault current a breaking device can break safely under prescribed conditions of use.
breakingCapacity
{52EB29C5-1F53-46e6-84EC-400C4B5AF75F}
Protection equipment may be used to protect specific conducting equipment.
ConductingEquipments
{1A223051-2D2E-4ca4-8FF1-9C8D1BDE000B}.SupplierEnd
Protected switches operated by this ProtectionEquipment.
ProtectedSwitches
{AEDB116C-6830-4d8b-96FA-C4ADA5EFF5CB}.SupplierEnd
Protective action can emulate the action done by one or more protection equipment. In a node breaker model were protective equipment is model this association will be used.
ProtectiveAction
{F800024C-67E3-43ed-8940-DC3AA37C7171}.SupplierEnd
The time delay from detection of abnormal conditions to relay operation.
relayDelayTime
{5C71AC12-B479-4721-892B-CED42C5F9CA9}
The unit multiplier of the value.
unitMultiplier
{ED1638AD-1A5B-45ec-B4B3-FE9F63AF652D}
The unit of measure of the value.
unitSymbol
{23D1C552-3A55-4563-A003-1120FEE90AAE}
Actual ground trip for this type of relay if applicable.
groundTrip
{B9914730-5FE2-4932-8C55-5A129880D5DB}
Actual phase trip for this type of relay if applicable.
phaseTrip
{12416897-F0DB-44d8-99DF-038EA4B370F5}
GateComCondition
{D34B99BA-6D10-4f96-88B9-7AD3024A8166}.SupplierEnd
Association to a Gate that through a gate logic and input pin defines enabling of the ProtectiveAction.
GateEnabledCondition
{1A878962-D12D-4598-ADE4-4D8B2DDE6CA7}.SupplierEnd
ProtectionEquipment
{F800024C-67E3-43ed-8940-DC3AA37C7171}.ClientEnd
ProtectiveActionCollection
{010F7F0E-C9F9-4f9e-A4BA-61BCFAFC99D7}.ClientEnd
ConductingEquipment whose operating condition is changed when this protective action adjustment gets activated.
ConductingEquipment
{44AD5B78-D603-43d9-A73C-68DCFE8B9C09}.ClientEnd
The operating condition to the Conducting Equipment is changed when protective action adjustment is activated.
DCConductingEquipment
{83F32DD1-007E-48c2-AD47-79FF388FCEDF}.SupplierEnd
The measurement is used to control the operation of an equipment.
Measurement
{9685ABB8-FD59-47dc-891C-CFC7E0CC0A6F}.ClientEnd
The adjustment is given in percent of the active value.
byPercentage
{78CF5B22-20FA-4227-938B-B92D200F57E1}
Defines the kind of adjustment that should be done. With this value the correct attribute containing the value needs to be used.
kind
{89F17D7E-BFBA-406e-91C8-14A649F3F8CA}
Set of ProtectiveAction belonging to a ProtectiveActionCollection.
ProtectiveAction
{010F7F0E-C9F9-4f9e-A4BA-61BCFAFC99D7}.SupplierEnd
When condition to the StageTrigger is met the actions in the ProtectiveActionCollection are activatedtriggered.
StageTrigger
{E36506E6-0D19-4846-93FA-EA04CBD6AC84}.SupplierEnd
Equipment
{C2B4064B-C361-4230-9F19-21614F4EFABE}.SupplierEnd
RegulatingControl
{2FDA9413-8CFA-434f-8187-40289D0A95BA}.SupplierEnd
Remote peer that will receive ICCP information in a Bilateral table.
BilateralExchangeActor
{D71D178C-4ECF-4cf5-A2F9-02324DC52065}.SupplierEnd
Measurement or control for the bilateral ICCP point.
IOPoint
{D2E53A93-0C08-4243-8A32-01EF61C12DBB}.ClientEnd
Minimum power PSS enabling iPmini. Typical value 025.
pmin
{D1BC7E22-C311-46c5-BCD1-7D0E17C75813}
Leadlag time constant iTiisub10subi gt 0. Typical value 0.
t10
{70693E88-D22B-4f77-915D-E4B7E7FFA527}
Washout iTiisub5subi gt 0. Typical value 35.
t5
{89FC20AE-5F4D-49ab-9B9A-EE5CDAEDC377}
Filter time constant iTiisub6subi gt 0. Typical value 0.
t6
{CB40BBB5-10C1-48f4-8D0D-DB0DC8132F65}
Leadlag time constant iTiisub7subi gt 0. If 0 both blocks are bypassed. Typical value 0.
t7
{B1ACDEAB-EC5D-4fe8-BAC6-4E44A25DC539}
Leadlag time constant iTiisub8subi gt 0. Typical value 0.
t8
{A4B89A31-6631-4501-9E0F-7615193D55CE}
Leadlag time constant iTiisub9subi gt 0. If 0 both blocks are bypassed. Typical value 0.
t9
{37C2987F-6FEA-4f8e-9B13-8633B1B4BEC6}
Electric power filter time constant iTiisubPEsubi gt 0. Typical value 005.
tpe
{207ED9A0-EE7A-4337-8985-86693BB79299}
Stabilizer output maximum limit iViisubSMNsubi. Typical value 006.
vsmn
{9B53532B-528A-48f9-AD6A-2C79864D8156}
Stabilizer output minimum limit iViisubSMXsubi. Typical value 006.
vsmx
{DE083CFE-9A2E-44f2-9A9C-BC746A6B14FE}
Notch filter parameter iAiisub1subi.
a1
{18432371-9711-49b6-B1E3-36801F34C756}
Notch filter parameter iAiisub2subi.
a2
{BD0FBD73-A34E-4b53-B8ED-1E2D32B0C557}
Notch filter parameter iAiisub3subi.
a3
{DD1DAC48-A59F-4da9-A350-B7F6B3A57338}
Notch filter parameter iAiisub4subi.
a4
{2A824CFC-A7F1-4ebe-A191-4D2E2D51FC7C}
Notch filter parameter iAiisub5subi.
a5
{E02771C6-A44B-4b21-9E02-4013371C576C}
Notch filter parameter iAiisub6subi.
a6
{50A21182-7D54-468a-A17A-4C53486D1664}
Notch filter parameter iAiisub7subi.
a7
{ED6658F9-1EC8-4b9e-9676-DC40AF1CCCE7}
Notch filter parameter iAiisub8subi.
a8
{C4CBC178-352C-4ed5-B79E-E6DDBFBC475C}
Type of input signal rotorAngularFrequencyDeviation busFrequencyDeviation generatorElectricalPower generatorAcceleratingPower busVoltage or busVoltageDerivative.
inputSignalType
{2858FCD2-D037-4074-82B5-AD33CEF04C1B}
Stabilizer gain iKiisubssubi.
ks
{4303A89C-5AA6-43a7-A286-35AF5508C5EF}
Leadlag time constant iTiisub1subi gt 0.
t1
{7BDE7BA3-0B4A-492c-B859-D322F71B8A36}
Leadlag time constant iTiisub2subi gt 0.
t2
{6CE2A59E-2589-4c97-9EE7-43A2B58DBC54}
Leadlag time constant iTiisub3subi gt 0.
t3
{E6A8B5CE-3598-49e9-AE4F-B74E409461E7}
Leadlag time constant iTiisub4subi gt 0.
t4
{6B32F9E5-47E4-42aa-8CDC-C9C979D70DFF}
Washout time constant iTiisub5subi gt 0.
t5
{40876337-80B0-4c33-BF46-B10E1CA977CF}
Transducer time constant iTiisub6subi gt 0.
t6
{0BFB60DD-4358-4513-BF1D-1EC4EC342DF5}
Time constant iTdelayi gt 0.
tdelay
{771EE399-66B7-4e17-B1C1-5DF41E2C6DFD}
Stabilizer input cutoff threshold iVcli.
vcl
{88C5C11B-4CA3-4132-9E77-9A607D4917D8}
Stabilizer input cutoff threshold iVcui.
vcu
{DE33EFF0-939C-4369-AA15-97A5446F26C3}
Maximum stabilizer output iVrmaxi gt Pss1A.vrmin.
vrmax
{99706091-CA51-4943-A518-326FC76D3803}
Minimum stabilizer output iVrmini lt Pss1A.vrmax.
vrmin
{1261CBB1-5D73-4fff-84C5-215FE3F49A22}
Stabilizer gain iKs1i. Typical value 12.
ks1
{F98828C5-A1C2-44fc-B0AF-D784EF3EF827}
Gain on signal 2 iKs2i. Typical value 02.
ks2
{302E91AA-0C44-428b-A559-CD0A7452186A}
Gain on signal 2 input before ramptracking filter iKs3i. Typical value 1.
ks3
{20CB34FA-0659-436b-AB1D-D48095CFDF54}
Gain on signal 2 input after ramptracking filter iKs4i. Typical value 1.
ks4
{93B590B5-CCE0-49d4-BDCD-758A565F72A8}
Leadlag time constant iTiisub1subi gt 0. Typical value 012.
t1
{0EAEED4C-C880-469d-82DB-8F8E28942DFB}
Leadlag time constant iTiisub10subi gt 0. Typical value 0.
t10
{2FED642A-038A-4837-85EE-46CB44438329}
Leadlag time constant iTiisub11subi gt 0. Typical value 0.
t11
{55181E61-DB6D-420e-9CC4-E247603D68B0}
Leadlag time constant iTiisub2subi gt 0. Typical value 002.
t2
{49972815-84C7-40d5-8DC9-01E40B9FF4AC}
Leadlag time constant iTiisub3subi gt 0. Typical value 03.
t3
{E9EAA9DB-B818-4790-A7C4-0E0AAB404386}
Leadlag time constant iTiisub4subi gt 0. Typical value 002.
t4
{AC479311-251E-4322-8F5D-284C676E4FC4}
Time constant on signal 1 iTiisub6subi gt 0. Typical value 0.
t6
{B5CE0BE2-50B8-4faf-86A9-91FDB13CABE5}
Time constant on signal 2 iTiisub7subi gt 0. Typical value 2.
t7
{720E50D0-1801-4675-A681-272A90DE0FEE}
Lead of ramp tracking filter iTiisub8subi gt 0. Typical value 02.
t8
{46D0A834-18CD-4d07-9B9F-4FD29F1D4C02}
Lag of ramp tracking filter iTiisub9subi gt 0. Typical value 01.
t9
{26216F3D-DDF0-4a35-9681-9341D9EFB636}
Lead constant iTiisubasubi gt 0. Typical value 0.
ta
{DCA88921-CAF2-4e0a-B7BB-A36F5C258E67}
Lag time constant iTiisubbsubi gt 0. Typical value 0.
tb
{D3E4EA3B-1104-4ecf-8872-6D281C46C378}
First washout on signal 1 iTiisubw1subi gt 0. Typical value 2.
tw1
{34DD18BA-660C-4ad6-9994-FE8ECDDFA178}
Second washout on signal 1 iTiisubw2subi gt 0. Typical value 2.
tw2
{910C3354-DA65-4a67-B00F-F5C0FAD0F174}
First washout on signal 2 iTiisubw3subi gt 0. Typical value 2.
tw3
{A25D5A7F-D5AE-467a-A191-9B4F3890739D}
Second washout on signal 2 iTiisubw4subi gt 0. Typical value 0.
tw4
{09FCB5F3-76DC-49c8-929F-34328D10BE70}
Input signal 1 maximum limit iVsi1maxi gt Pss2B.vsi1min. Typical value 2.
vsi1max
{C47E9535-5CE2-456a-9641-DF992F63E0BA}
Input signal 1 minimum limit iVsi1mini lt Pss2B.vsi1max. Typical value 2.
vsi1min
{7D098878-DFC5-44d2-940A-CFC474E045C4}
Input signal 2 maximum limit iVsi2maxi gt Pss2B.vsi2min. Typical value 2.
vsi2max
{D6867E7D-B7E9-49ae-9136-CFDAD504D56A}
Input signal 2 minimum limit iVsi2mini lt Pss2B.vsi2max. Typical value 2.
vsi2min
{83753CE1-73AF-48ac-B037-06258ECBBEEB}
Stabilizer output maximum limit iVstmaxi gt Pss2B.vstmin. Typical value 01.
vstmax
{395AE089-D808-4724-948A-3EB7D04F80E2}
Stabilizer output minimum limit iVstmini lt Pss2B.vstmax. Typical value 01.
vstmin
{84433A80-593D-467e-8144-1308967CFB3D}
Type of input signal 1 rotorAngularFrequencyDeviation busFrequencyDeviation generatorElectricalPower generatorAcceleratingPower busVoltage or busVoltageDerivative shall be different than Pss2ST.inputSignal2Type. Typical value rotorAngularFrequencyDeviation.
inputSignal1Type
{CFF0885B-F7BC-487a-9AC2-719DC9E9A863}
Type of input signal 2 rotorAngularFrequencyDeviation busFrequencyDeviation generatorElectricalPower generatorAcceleratingPower busVoltage or busVoltageDerivative shall be different than Pss2ST.inputSignal1Type. Typical value busVoltageDerivative.
inputSignal2Type
{DA8C256C-E543-4cfd-A25C-E46B4B4ABFD2}
Gain iKiisub1subi.
k1
{388BFF8E-5BAC-40b1-BCE7-711F32CE9069}
Gain iKiisub2subi.
k2
{09EAE50B-660F-431b-A3DF-60FE1B6D0362}
Limiter iLiisubSMAXsubi gt Pss2ST.lsmin.
lsmax
{36ED1D9F-45B0-469b-AB1B-43DAB35DFC06}
Limiter iLiisubSMINsubi lt Pss2ST.lsmax.
lsmin
{A152649C-2F91-4c19-AF69-A4BDA7C603D7}
Time constant iTiisub1subi gt 0.
t1
{4C8A06A4-7FF2-42d7-A7D9-BDA8DE0CC6EA}
Time constant iTiisub10subi gt 0.
t10
{9703E541-D28A-45c6-89FA-3912BE731C39}
Time constant iTiisub2subi gt 0.
t2
{00A324FA-3866-4999-8A2C-268B8C4CD76E}
Time constant iTiisub3subi gt 0.
t3
{2E4DA1B4-E5DB-4823-98B8-5A29EE892DB9}
Time constant iTiisub4subi gt 0.
t4
{1EED62C2-46E1-4b27-907D-246EA1CE8E16}
Time constant iTiisub5subi gt 0.
t5
{8618BBA0-9FB2-426e-975B-6D84FD5BCB43}
Time constant iTiisub6subi gt 0.
t6
{43E5A382-DFD7-4a5a-8281-2896BB4E833E}
Time constant iTiisub7subi gt 0.
t7
{6B8331C1-9313-4da9-B130-6654B279D498}
Time constant iTiisub8subi gt 0.
t8
{327B8744-12B6-4c93-8E7F-0BF0FD0AB3B0}
Time constant iTiisub9subi gt 0.
t9
{E4E354AD-D199-4111-BEEB-1618A4783C8F}
Cutoff limiter iViisubCLsubi.
vcl
{E9B81925-DEB1-4d91-926B-F0A5EA1EF9C7}
Cutoff limiter iViisubCUsubi.
vcu
{B1729CBD-2156-46b0-9718-2927AEA5825B}
Stabilizer output deadband iDEADBANDi. Typical value 0.
deadband
{09829B27-F382-4cfd-9877-D0F8D6F45D86}
Minimum power PSS enabling iPmini. Typical value 025.
pmin
{2716F17A-F333-4229-8B2D-7F0B19389A8F}
Leadlag time constant iTiisubL1subi gt 0. Typical value 0.
tl1
{972149E2-7329-49d7-B143-C91CE1D0D0CF}
Leadlag time constant iTiisubL2subi gt 0. If 0 both blocks are bypassed. Typical value 0.
tl2
{43397194-BE33-40b2-8EF4-A94168040611}
Leadlag time constant iTiisubL3subi gt 0. Typical value 0.
tl3
{08F21632-907E-4d2e-BBB9-5730DC0C6B52}
Leadlag time constant TsubL4sub gt 0. If 0 both blocks are bypassed. Typical value 0.
tl4
{9E52C1D5-4573-4968-BD27-F6B3016C6677}
Electric power filter time constant iTiisubPEsubi gt 0. Typical value 005.
tpe
{FF15A722-A340-44d3-B1A1-C8472C183AB7}
First washout iTiisubW1subi gt 0. Typical value 35.
tw1
{6117E3AD-8E40-45b0-B2CA-EF18017F7BD2}
Second washout iTiisubW2subi gt 0. Typical value 0.
tw2
{340AD2DB-7807-49b1-BBCA-07A89716F3A2}
Stabilizer output maximum limit iViisubSMNsubi. Typical value 01.
vsmn
{9B6B07F2-A39E-445e-8CB5-34A6B595996D}
Stabilizer output minimum limit iViisubSMXsubi. Typical value 01.
vsmx
{7C25E501-C92A-47b9-931B-4C55DDF1DA2B}
Coefficient iaPSSi. Typical value 01.
apss
{C4097C61-41F7-42c7-A518-DEBC279A5A1A}
Gain iKs1i. Typical value 1.
ks1
{4FC53F60-7C4B-408d-BC41-874A5EDDB13F}
Gain iKs2i. Typical value 01.
ks2
{9207B864-DFE6-4ca4-85C6-9D73FEF61911}
Coefficient ipPSSi gt 0 and lt 4. Typical value 01.
ppss
{5386C61F-F104-48b5-B5D9-F072A7E193D6}
PSS limiter ipsslimi. Typical value 01.
psslim
{C591CA0E-9828-4264-BF06-AC81A5C08487}
Time constant iTs1i gt 0. Typical value 0.
ts1
{28F9E71C-64F9-4a8e-BC68-1F237AF91080}
Time constant iTs2i gt 0. Typical value 1.
ts2
{1EA22630-7B09-4870-83F9-D2951596D853}
Time constant iTs3i gt 0. Typical value 1.
ts3
{4EF98AD2-1049-4221-B1FC-1C1879FB8FD3}
Time constant iTs4i gt 0. Typical value 01.
ts4
{5AA64434-E7B2-446f-B0A8-5EB187CF40F1}
Time constant iTs5i gt 0. Typical value 0.
ts5
{1FEB7B31-979D-47e7-B552-C15A9EDC24EB}
Time constant iTs6i gt 0. Typical value 1.
ts6
{9EC34595-ECC6-4286-8D0A-466908BBD3A1}
PSS signal conditioning frequency filter constant iA1i. Typical value 0061.
a1
{3A42ABB9-11F1-4a35-8886-7F6BC8AF4B92}
PSS signal conditioning frequency filter constant iA2i. Typical value 00017.
a2
{60DFB355-6080-49e2-B574-9CD273250A1A}
Type of input signal rotorAngularFrequencyDeviation generatorElectricalPower or busFrequencyDeviation. Typical value rotorAngularFrequencyDeviation.
inputSignalType
{9BEB25F6-CC27-40a7-BF6A-30E9CB472F5C}
Stabilizer gain iKsi. Typical value 5.
ks
{1EA8B903-0881-4864-9106-6484CEE4899F}
Leadlag time constant iT1i gt 0. Typical value 03.
t1
{DF29EFDC-0824-4420-B49B-300F1D1D3BAA}
Leadlag time constant iT2i gt 0. Typical value 003.
t2
{9F627C73-4C0E-4a88-A74E-B8077F9B2B01}
Leadlag time constant iT3i gt 0. Typical value 03.
t3
{7A92A9D3-93F2-43f2-9A88-028EC34903A0}
Leadlag time constant iT4i gt 0. Typical value 003.
t4
{0C4DEB3F-D76E-4961-8AC3-BCA446EBE55A}
Washout time constant iT5i gt 0. Typical value 10.
t5
{B3A436DD-788F-466d-A6A8-6FEC93704172}
Transducer time constant iT6i gt 0. Typical value 001.
t6
{118961FB-9D75-4866-8DC8-534F6906C308}
Maximum stabilizer output iVrmaxi gt PssIEEE1A.vrmin. Typical value 005.
vrmax
{620CE161-D66D-4ff4-B914-653AF376B883}
Minimum stabilizer output iVrmini lt PssIEEE1A.vrmax. Typical value 005.
vrmin
{43B4D9BC-6CE5-4948-A360-DA5CA9D4F64B}
Type of input signal 1 rotorAngularFrequencyDeviation busFrequencyDeviation. Typical value rotorAngularFrequencyDeviation.
inputSignal1Type
{5422DA40-A15B-477d-BEBA-D0F93E671F10}
Type of input signal 2 generatorElectricalPower. Typical value generatorElectricalPower.
inputSignal2Type
{D51693EB-EDE4-45d7-BEBE-4C01EE3CC744}
Stabilizer gain iKs1i. Typical value 12.
ks1
{9EDB2C0C-B5B1-4969-9BB8-15E88D445A74}
Gain on signal 2 iKs2i. Typical value 02.
ks2
{42040DA0-97DA-4d23-B935-02768C9077A4}
Gain on signal 2 input before ramptracking filter iKs3i. Typical value 1.
ks3
{FE1D8234-330D-47f9-9DD6-4CF126F472BC}
Leadlag time constant iT1i gt 0. Typical value 012.
t1
{A29BE3F3-46B5-4700-A3E6-DED949328BA7}
Leadlag time constant iT10i gt 0. Typical value 0.
t10
{CAD1F821-393F-4240-B41E-28A2E6036531}
Leadlag time constant iT11i gt 0. Typical value 0.
t11
{6AA08681-7EEF-43d6-9E3B-F6352C1AFEC0}
Leadlag time constant iT2i gt 0. Typical value 002.
t2
{0325A8EA-E44D-49c1-AC84-A43A5F960594}
Leadlag time constant iT3i gt 0. Typical value 03.
t3
{7578052C-8C82-4061-8FA4-B088AA9E0BF3}
Leadlag time constant iT4i gt 0. Typical value 002.
t4
{E7FCEDB2-B9B7-48a2-B6D9-C7F0A6433893}
Time constant on signal 1 iT6i gt 0. Typical value 0.
t6
{E8160673-0560-4ed3-BAA7-BEE04561C031}
Time constant on signal 2 iT7i gt 0. Typical value 2.
t7
{E62B50F7-069F-4749-ADA5-D1AE91D6AD9B}
Lead of ramp tracking filter iT8i gt 0. Typical value 02.
t8
{8B585680-5B86-4b0d-89A5-7666CB401B30}
Lag of ramp tracking filter iT9i gt 0. Typical value 01.
t9
{88F08006-7320-454c-89C1-B7E0ED841935}
First washout on signal 1 iTw1i gt 0. Typical value 2.
tw1
{247C6F44-DA26-4c69-A790-7D51421F7173}
Second washout on signal 1 iTw2i gt 0. Typical value 2.
tw2
{3657663A-7327-4532-B814-B9932AF6103F}
First washout on signal 2 iTw3i gt 0. Typical value 2.
tw3
{22EF3559-3803-4f96-95B8-1FA1FDCD2B57}
Second washout on signal 2 iTw4i gt 0. Typical value 0.
tw4
{68328808-0B10-4cec-BAF9-366F7E2C5E25}
Input signal 1 maximum limit iVsi1maxi gt PssIEEE2B.vsi1min. Typical value 2.
vsi1max
{E2717352-71CF-495e-8411-037CF6F9ABE1}
Input signal 1 minimum limit iVsi1mini lt PssIEEE2B.vsi1max. Typical value 2.
vsi1min
{4674160B-50EA-4c0d-8EAB-9F0BB26BD044}
Input signal 2 maximum limit iVsi2maxi gt PssIEEE2B.vsi2min. Typical value 2.
vsi2max
{20B9E8F1-9CE9-4dcc-8F8F-DE3D04C7762C}
Input signal 2 minimum limit iVsi2mini lt PssIEEE2B.vsi2max. Typical value 2.
vsi2min
{B1CCB690-974A-4131-A1B9-B69592C85D15}
Stabilizer output maximum limit iVstmaxi gt PssIEEE2B.vstmin. Typical value 01.
vstmax
{740E3F53-BF89-48d6-9D3D-2293D4546513}
Stabilizer output minimum limit iVstmini lt PssIEEE2B.vstmax. Typical value 01.
vstmin
{932B2B40-7B7C-4ecb-A109-9EABEF808831}
Notch filter parameter iA1i. Typical value 0359.
a1
{29C3988D-1FA0-4156-AA65-041AD1E3A91A}
Notch filter parameter iA2i. Typical value 0586.
a2
{3B30B23B-C248-438d-807B-5CEC02C3C3EF}
Notch filter parameter iA3i. Typical value 0429.
a3
{BADBDF74-BBF6-4617-B923-B9DE59B83EFC}
Notch filter parameter iA4i. Typical value 0564.
a4
{E4214356-9AC0-4570-B593-1CB76075CD56}
Notch filter parameter iA5i. Typical value 0001.
a5
{0B37C17C-CD7E-4d90-B766-DAE5E2C6CBA0}
Notch filter parameter iA6i. Typical value 0.
a6
{C8E8DF62-715D-41da-B028-15F5AC5B4586}
Notch filter parameter iA7i. Typical value 0031.
a7
{F8D369DF-90B4-4dd4-9ABC-4C724682D725}
Notch filter parameter iA8i. Typical value 0.
a8
{675C1F36-6FC8-4cff-89C3-9EE8B307B481}
Gain on signal 1 iKs1i. Typical value 0602.
ks1
{A07F2DD1-C835-4d95-AE33-04A03887E4EF}
Gain on signal 2 iKs2i. Typical value 3012.
ks2
{596EDE0C-3D07-43b6-9885-E7B8641AFF8A}
Transducer time constant iT1i gt 0. Typical value 0012.
t1
{EDD30EB8-DCEB-4c45-B5F2-F8EC487167F2}
Transducer time constant iT2i gt 0. Typical value 0012.
t2
{40699E7A-CFE1-4188-B007-37BFB93BCC12}
Washout time constant iTw1i gt 0. Typical value 03.
tw1
{C5598A2E-3817-4a5e-B26C-BF21362A2B64}
Washout time constant iTw2i gt 0. Typical value 03.
tw2
{AE19065C-FB01-4859-9897-361735D064E5}
Washout time constant iTw3i gt 0. Typical value 06.
tw3
{02C64498-6919-4278-9EB2-06CAD82A5785}
Stabilizer output maximum limit iVstmaxi gt PssIEEE3B.vstmin. Typical value 01.
vstmax
{0C55A361-DEDC-41c9-A63F-0EF60120B92E}
Stabilizer output minimum limit iVstmini lt PssIEEE3B.vstmax. Typical value 01.
vstmin
{63B2226D-3BF8-42a7-8E71-B71C132673F6}
High band gain iKiisubHsubi. Typical value 120.
kh
{B330EB08-840E-4ad3-BA3E-2A7C11B7F1C7}
High band differential filter gain iKiisubH1subi. Typical value 66.
kh1
{B946A3C9-006B-44d7-A9F3-74B0B08B3BAF}
High band first leadlag blocks coefficient iKiisubH11subi. Typical value 1.
kh11
{3E829533-0365-408b-A6F3-0D25FE3D5635}
High band first leadlag blocks coefficient iKiisubH17subi. Typical value 1.
kh17
{A1EAC99C-2B7C-4416-9110-B034E435109B}
High band differential filter gain iKiisubH2subi. Typical value 66.
kh2
{B938E916-77C3-485a-B33E-11E55B3DA69D}
Intermediate band gain iKiisubIsubi. Typical value 30.
ki
{CBE44C35-2773-4c37-930A-A846E509729A}
Intermediate band differential filter gain iKiisubI1subi. Typical value 66.
ki1
{228F3175-9E16-4322-B23E-03309CC0F389}
Intermediate band first leadlag blocks coefficient iKiisubI11subi. Typical value 1.
ki11
{42D1403C-7AC8-4a7f-AF3E-5AD19B6576D3}
Intermediate band first leadlag blocks coefficient iKiisubI17subi. Typical value 1.
ki17
{0126F076-9D98-43c5-ADAA-71EF12921BDA}
Intermediate band differential filter gain iKiisubI2subi. Typical value 66.
ki2
{F5D69F7F-2DA9-4fe6-B821-768C06D27F87}
Low band gain iKiisubLsubi. Typical value 7.5.
kl
{F661FCE8-795F-47dc-B4EE-1F4D64A86ED5}
Low band differential filter gain iKiisubL1subi. Typical value 66.
kl1
{A25D9B28-CA02-428b-9B2B-FEB4ABE9B5CA}
Low band first leadlag blocks coefficient iKiisubL11subi. Typical value 1.
kl11
{9E02BB3C-E4C3-4136-A2B6-63AAA85FA572}
Low band first leadlag blocks coefficient iKiisubL17subi. Typical value 1.
kl17
{BAC5CF0A-2A3D-4d59-85D5-2FABE7399189}
Low band differential filter gain iKiisubL2subi. Typical value 66.
kl2
{27FFC2C9-0AD7-416c-BD97-7D5E4DD1C92E}
High band time constant iTiisubH1subi gt 0. Typical value 001513.
th1
{B1565F1D-937E-4f87-8E1B-F78219A1E793}
High band time constant iTiisubH10subi gt 0. Typical value 0.
th10
{3877A778-4B50-4384-AD8B-FD4ECC18A210}
High band time constant iTiisubH11subi gt 0. Typical value 0.
th11
{8E3C18EE-C082-4592-9E11-306A5865649A}
High band time constant iTiisubH12subi gt 0. Typical value 0.
th12
{EFBFA9DF-E84D-4910-8448-2CF72DBC59CA}
High band time constant iTiisubH2subi gt 0. Typical value 001816.
th2
{5126E6D4-989A-44e2-867B-287A3DFF7F71}
High band time constant iTiisubH3subi gt 0. Typical value 0.
th3
{A0FB3FAF-1A5F-401c-8C5F-E8F51A7FD0A0}
High band time constant iTiisubH4subi gt 0. Typical value 0.
th4
{333A2965-C561-42e7-ACE7-657656991630}
High band time constant iTiisubH5subi gt 0. Typical value 0.
th5
{2041028D-058A-442a-9E46-06D0EB098F7E}
High band time constant iTiisubH6subi gt 0. Typical value 0.
th6
{BEFD6842-39A2-411c-AD53-070714A22D7A}
High band time constant iTiisubH7subi gt 0. Typical value 001816.
th7
{C9DF4A27-8A3C-4e85-B1F8-415F5CAAE2A5}
High band time constant iTiisubH8subi gt 0. Typical value 002179.
th8
{3298914E-888F-48a0-AA51-35B2948C0CFB}
High band time constant iTiisubH9subi gt 0. Typical value 0.
th9
{899ED447-3FFE-4b9e-AC1D-325C18B2CD34}
Intermediate band time constant iTiisubI1subi gt 0. Typical value 0173.
ti1
{E9BAB416-CBF7-410f-B5AE-4C925AB37279}
Intermediate band time constant iTiisubI10subi gt 0. Typical value 0.
ti10
{F003E333-8DF9-4451-B83A-10242088D230}
Intermediate band time constant iTiisubI11subi gt 0. Typical value 0.
ti11
{84BC8320-5294-481a-AD82-B582D79C91A9}
Intermediate band time constant iTiisubI12subi gt 0. Typical value 0.
ti12
{ADE80289-4ED6-4df7-BA31-5D956C4A0B8F}
Intermediate band time constant iTiisubI2subi gt 0. Typical value 02075.
ti2
{133C2C29-0856-4fab-90D4-D7230A3A4066}
Intermediate band time constant iTiisubI3subi gt 0. Typical value 0.
ti3
{EC11DE7C-108C-4252-8901-42030560D618}
Intermediate band time constant iTiisubI4subi gt 0. Typical value 0.
ti4
{C57AA21C-4F7E-4650-BBA9-ADD5F1EF8CC5}
Intermediate band time constant iTiisubI5subi gt 0. Typical value 0.
ti5
{70F4E512-41F2-42dd-B791-9D445EF22D3D}
Intermediate band time constant iTiisubI6subi gt 0. Typical value 0.
ti6
{732159B4-C65D-47d9-966E-2DE2529A662A}
Intermediate band time constant iTiisubI7subi gt 0. Typical value 02075.
ti7
{7B8B831A-10FA-4f9b-A9F8-0303199D3098}
Intermediate band time constant iTiisubI8subi gt 0. Typical value 02491.
ti8
{07D34D54-9BD5-47f5-8CA8-D2D4CF1F8A39}
Intermediate band time constant iTiisubI9subi gt 0. Typical value 0.
ti9
{2A291614-DF59-46fc-AC26-BDCBE69E1766}
Low band time constant iTiisubL1subi gt 0. Typical value 173.
tl1
{EED80EC0-0995-44b1-92F4-33290BE3EFF0}
Low band time constant iTiisubL10subi gt 0. Typical value 0.
tl10
{18522492-E1BC-4a45-8BDF-3417466A8C1E}
Low band time constant iTiisubL11subi gt 0. Typical value 0.
tl11
{DB610C67-A0D1-4682-9D68-512F8417FB25}
Low band time constant iTiisubL12subi gt 0. Typical value 0.
tl12
{6E82C1C2-659E-49c2-9C6B-4BBA72FF5443}
Low band time constant iTiisubL2subi gt 0. Typical value 2075.
tl2
{DF838F6A-62DF-48dc-91CB-12C8DBAAD7AD}
Low band time constant iTiisubL3subi gt 0. Typical value 0.
tl3
{B5BE4EEE-8B6D-4bd6-ACF3-5C75E822571D}
Low band time constant iTiisubL4subi gt 0. Typical value 0.
tl4
{63EF51D4-1C99-41e3-80DF-8B8675F16B82}
Low band time constant iTiisubL5subi gt 0. Typical value 0.
tl5
{07D2B4C6-BAE5-439b-A0D5-B11E5C8CC87D}
Low band time constant iTiisubL6subi gt 0. Typical value 0.
tl6
{3A70AAE4-BD26-457b-A33B-BD09E448524F}
Low band time constant iTiisubL7subi gt 0. Typical value 2075.
tl7
{62B2B8D6-9440-4d9a-B3A9-CD373EB778B6}
Low band time constant iTiisubL8subi gt 0. Typical value 2491.
tl8
{AC91BB28-73A8-4eba-9C9B-C779447A714A}
Low band time constant iTiisubL9subi gt 0. Typical value 0.
tl9
{C1F0E4B7-5685-4cfe-80E5-5FBD47436C3B}
High band output maximum limit iViisubHmaxsubi gt PssIEEE4B.vhmin. Typical value 06.
vhmax
{20BC2A7A-8F06-401e-AA8F-189D4FBA1414}
High band output minimum limit iViisubHminsubi lt PssIEEE4V.vhmax. Typical value 06.
vhmin
{B5F36484-8F0C-45c6-B6A3-32361D83E7DE}
Intermediate band output maximum limit iViisubImaxsubi gt PssIEEE4B.vimin. Typical value 06.
vimax
{D271E688-E2F9-4529-A703-A9D0E93006D7}
Intermediate band output minimum limit iViisubIminsubi lt PssIEEE4B.vimax. Typical value 06.
vimin
{068865B9-E763-43f2-9650-B3A896A9CB65}
Low band output maximum limit iViisubLmaxsubi gt PssIEEE4B.vlmin. Typical value 0075.
vlmax
{BDB0C9CE-DF5E-474b-B0B7-2E373C3295CB}
Low band output minimum limit iViisubLminsubi lt PssIEEE4B.vlmax. Typical value 0075.
vlmin
{25C3E71D-B1B9-4fc0-A8FC-2432F05535D2}
PSS output maximum limit iViisubSTmaxsubi gt PssIEEE4B.vstmin. Typical value 015.
vstmax
{331230C2-2EF0-41ce-9D5E-A29389371349}
PSS output minimum limit iViisubSTminsubi lt PssIEEE4B.vstmax. Typical value 015.
vstmin
{73A3A5F1-5D59-4401-9A84-5205FF321148}
Time step related to activation of controls ideltatci gt 0. Typical value 0025.
dtc
{21E26C02-B1FF-4a47-9FC1-31DBB1E94B91}
Time step frequency calculation ideltatfi gt 0. Typical value 0025.
dtf
{9893B9AA-CB01-4bed-81C8-5EF5ADB4A506}
Time step active power calculation ideltatpi gt 0. Typical value 00125.
dtp
{56B7F182-5BF0-4139-A6C9-6E82F5819074}
Gain iKi. Typical value 9.
k
{149BED87-629F-4c78-95E2-39C8CA4C0969}
iMi. iM i 2 x iHi. Typical value 5.
m
{771479EE-58B0-4922-8DB9-AD23C67D35D7}
Time constant iT1i gt 0. Typical value 03.
t1
{B247F970-6B77-4d46-9434-2ED921BE5F6D}
Time constant iT2i gt 0. Typical value 1.
t2
{5F178F5F-4EF0-4c1e-8A69-830923EC6304}
Time constant iT3i gt 0. Typical value 02.
t3
{7BDEEFBA-DDDA-404b-849D-1054B6347898}
Time constant iT4i gt 0. Typical value 005.
t4
{632D559B-A58E-419f-A685-58EAC15E2001}
Time constant iTfi gt 0. Typical value 02.
tf
{C6C6644B-B6FB-4b0f-855F-6A7E0048EAA3}
Time constant iTpi gt 0. Typical value 02.
tp
{751AFEC6-3A92-420b-B3E4-B31B5A11AA01}
Filter coefficient iA0i.
a0
{EA2F4BEA-73DB-4224-AA30-1E511B152E42}
Limiter iAli.
a1
{83D4F571-389C-41d7-B052-BAA01333CEB4}
Filter coefficient iA2i.
a2
{F908870E-691A-44cc-A668-30CE61054777}
Filter coefficient iA3i.
a3
{018F63E9-E39C-4ea8-9A79-2EA75B27DE72}
Filter coefficient iA4i.
a4
{50C3EDB5-3A00-4172-B546-CD483CFBFDBC}
Filter coefficient iA5i.
a5
{59F9C4F2-1DB4-4d8c-BE5E-1E0F2486A367}
Limiter iAli.
al
{332AE08B-9AB0-4034-A703-B61289770C4C}
Threshold value above which output averaging will be bypassed iAthresi. Typical value 0005.
athres
{8134EB59-AD5B-4b49-A78A-294E7D8ADAF3}
Filter coefficient iB0i.
b0
{310F2AFA-65E3-4fe7-969D-6E91C51E5D48}
Filter coefficient iB1i.
b1
{4F1E7567-EC5E-496a-A487-598C0CD4CED1}
Filter coefficient iB2i.
b2
{E038B8D2-EA4C-49f6-A65A-E309D19375BB}
Filter coefficient iB3i.
b3
{A88B6DD5-2A5C-454e-B840-C9834951F533}
Filter coefficient iB4i.
b4
{DDB2917A-448D-4e0c-BACD-ABA820B29208}
Filter coefficient iB5i.
b5
{34670B67-141E-420e-86DC-2B4C8582BD08}
Limiter iDli.
dl
{521BE6A1-4207-47cc-BC15-894EF2CA779B}
Time step related to activation of controls ideltatci gt 0. Typical value 0025 003 for 50 Hz.
dtc
{83D0BFCE-2064-47a5-B67C-70DA771BA68C}
Time step frequency calculation ideltatfi gt 0. Typical value 0025 003 for 50 Hz.
dtf
{F98F6493-C793-4489-8838-54649844C2B8}
Time step active power calculation ideltatpi gt 0. Typical value 00125 0015 for 50 Hz.
dtp
{73C6218C-1AFF-4762-A2BC-47FF4A9B7D3A}
Gain iKi. Typical value 9.
k
{4A7D975B-A0B8-4261-9923-6C5AE0547A5B}
Threshold value iLthresi.
lthres
{9F02270C-CBAB-4897-87B9-003C972E0CBB}
iMi. iMi 2 x iHi. Typical value 5.
m
{7C0027A4-3774-4fce-A4E4-EE1C1C533475}
iPmini.
pmin
{7867934E-3E65-40df-93A9-C827AF840E01}
Time constant iT1i gt 0. Typical value 03.
t1
{CB68C895-9B7A-4fe7-A0F4-8005860B9F47}
Time constant iT2i gt 0. Typical value 1.
t2
{47B8B379-59F0-4247-9B1B-2015B8F90E79}
Time constant iT3i gt 0. Typical value 02.
t3
{AA386BC3-B56E-497a-BAC9-2F0C3D50CA78}
Time constant iT4i gt 0. Typical value 005.
t4
{E423735B-F025-47fd-8D17-D8C34F44C439}
Time constant iT5i gt 0.
t5
{A5681E99-7069-43a4-8B6A-6EABF1D8B04B}
Time constant iT6i gt 0.
t6
{280A56E7-B1BD-4eaf-9EF0-4934AC38094C}
Time constant iTfi gt 0. Typical value 02.
tf
{69438D6C-D640-4920-920E-D0E6D15B65C9}
Time constant iTpi gt 0. Typical value 02.
tp
{A816A7FB-010D-475f-AB77-E5CA7BC6E200}
Speed deadband iSIBVi. Typical value 0006.
sibv
{25A44BAC-70C2-4638-B867-62B3BEA331A2}
Lead lag time constant iT4Fi gt 0. Typical value 0045.
t4f
{F10CB117-1EF4-4c87-941E-BB3779497DCC}
Input time constant iT4Mi gt 0. Typical value 5.
t4m
{1E13B238-C8C7-4192-A70B-6091BA857E76}
Speed time constant iT4MOMi gt 0. Typical value 127.
t4mom
{FEC1EADC-4517-4cb3-999E-0856192ED6D8}
Speed delay iTOMDi gt 0. Typical value 002.
tomd
{47F8A6AC-DDC9-498b-AD23-F7976C685FAD}
Speed time constant iTOMSLi gt 0. Typical value 004.
tomsl
{7B4D2D3F-23E8-4796-B85D-94130D50BCFB}
Gain iKxi. Typical value 27.
kx
{2C28DCEE-9492-4588-AEF3-3FA52C9422B4}
Time constant iTai gt 0. Typical value 037.
ta
{1ECE094C-3893-4314-8E19-1FF74F9BF815}
Time constant iTbi gt 0. Typical value 037.
tb
{F9A9604C-C37F-4999-BDB9-0800579A98D6}
Time constant iTci gt 0. Typical value 0035.
tc
{5A58D4A2-5E2B-4df8-801E-A3E812F55E06}
Time constant iTdi gt 0. Typical value 00.
td
{374EEB43-BAA4-4b99-8C8B-028F0F6981F0}
Time constant iTei gt 0. Typical value 00169.
te
{16F004D8-7B9B-42e3-AEE7-C4C4C30A752B}
Time constant iTti gt 0. Typical value 018.
tt
{90A62BA6-6FF0-4588-AB47-C0F67C379895}
Reset time constant iTx1i gt 0. Typical value 0035.
tx1
{E30E060B-ECD1-4950-8615-3CFF8467F0D9}
Time constant iTx2i gt 0. Typical value 50.
tx2
{403B3C21-B95B-46ae-BE65-3A45D17F2666}
Limiter iVsmaxi gt PssSB4.vsmin. Typical value 0062.
vsmax
{6D83076D-C50C-4308-9B7C-1FE83743D4B5}
Limiter iVsmini lt PssSB4.vsmax. Typical value 0062.
vsmin
{807D80F6-6A45-4882-A0E8-7047DC33222D}
Main gain iKi. Typical value 1.
k
{CF93D41D-54C5-4f36-8145-12FC07043368}
Gain 0 iK0i. Typical value 0012.
k0
{D82A667C-A7DE-45b6-9E7C-FDA163EB7B9C}
Gain 1 iK1i. Typical value 0488.
k1
{9876545C-0A30-4881-B2A6-56247A50A2D8}
Gain 2 iK2i. Typical value 0064.
k2
{9FCD558B-3085-4673-8E88-126F32495200}
Gain 3 iK3i. Typical value 0224.
k3
{F4F74F0D-485C-4579-B087-6220606DA960}
Gain 4 iK4i. Typical value 01.
k4
{8B9E0F2C-828C-418d-B995-198B38BA53E5}
Time constant 1 iT1i gt 0. Typical value 0076.
t1
{6726B2F3-C89C-4ec3-A10D-64D827D61C80}
Time constant 2 iT2i gt 0. Typical value 0086.
t2
{E508BE6D-BFAD-4bd3-9D58-487962567A80}
Time constant 3 iT3i gt 0. Typical value 1068.
t3
{EEDB48FD-466F-479f-8B50-2C9B934A2F55}
Time constant 4 iT4i gt 0. Typical value 1913.
t4
{5407ECA9-0AB4-46b7-8049-E6471B64A41F}
Input time constant iTiisubdsubi gt 0. Typical value 10.
td
{9E863A8C-B2B5-43f2-9EC7-B7E7A208A606}
Output maximum limit iVsmaxi gt PssSH.vsmin. Typical value 01.
vsmax
{1D97C9D0-E3DC-4a64-95F2-2FCAB7CE17A3}
Output minimum limit iVsmini lt PssSH.vsmax. Typical value 01.
vsmin
{8E01C789-3734-4418-844F-8A638A81E0DF}
Gain iPi iKiisub1subi. Typical value 03.
k1
{CA6C05FC-A193-4963-BD3E-A73161D564CF}
Gain ifiisubEsubii iiKiisub2subi. Typical value 015.
k2
{6275FEEA-64E3-4d11-94B3-E85281DC1B0A}
Gain iIiisubfsubii iiKiisub3subi. Typical value 10.
k3
{696EFC91-3E54-42eb-8DB4-9E96E5011EDE}
Denominator time constant iTiisub1subi gt 0005. Typical value 03.
t1
{4EDF8011-93D6-4643-A556-ECC6BA91471E}
Filter time constant iTiisub2subi gt 0005. Typical value 035.
t2
{F3D23C47-4E69-4b24-9A20-9BD3059A78AE}
Denominator time constant iTiisub3subi gt 0005. Typical value 022.
t3
{5DEFCA45-CB72-4a12-BCB4-A207C56A374E}
Filter time constant iTiisub4subi gt 0005. Typical value 002.
t4
{7BE8F1D6-1D4C-4833-BA30-374703D06DE1}
Denominator time constant iTiisub5subi gt 0005. Typical value 002.
t5
{63DBFE0F-46D3-4e43-B9B6-9DDAB865512B}
Filter time constant iTiisub6subi gt 0005. Typical value 002.
t6
{59DB1983-0DAF-464e-947A-ABCEFFF0FD67}
Stabilizer output maximum limit iViisubSMAXsubi gt PssSK.vsmin. Typical value 04.
vsmax
{C4B8BB7A-AF38-467f-86D4-46E08D0BDC50}
Stabilizer output minimum limit iViisubSMINsubi lt PssSK.vsmax. Typical value 0.4.
vsmin
{7EED5614-AE1E-4890-A231-4857FA7C71A2}
Stabilizer output limiter iHiisubLIMsubi. Typical value 05.
hlim
{9AC76FF9-DF83-4397-9F22-C0C4A4F8C561}
Gain iK2i. Typical value 10.
k2
{7239752A-FF81-47c0-A800-B0971A966180}
Gain iK3i. Typical value 025.
k3
{0E4E1CA9-DC9B-4687-8DD4-B668960CD165}
Gain iK4i. Typical value 0075.
k4
{734E1A07-7893-4f0d-8239-79AC28EF5E71}
Gain iK5i. Typical value 25.
k5
{0B0EE36D-7F50-4ab4-BC22-53B7D490FEAD}
Time constant iT2i. Typical value 40.
t2
{30211023-AA7E-4f57-BA0E-81262157838D}
Time constant iT3i. Typical value 20.
t3
{5E59E2BC-46B6-4a17-9692-732FBF0ABCDB}
Time constant iT5i. Typical value 45.
t5
{5874D4E5-3374-41ed-88EA-244E309F7C88}
Type of input signal 1 rotorAngularFrequencyDeviation busFrequencyDeviation generatorElectricalPower generatorAcceleratingPower busVoltage or busVoltageDerivative shall be different than PssWECC.inputSignal2Type. Typical value rotorAngularFrequencyDeviation.
inputSignal1Type
{45AD9318-298A-4e62-A7A7-FC79EDBBCE83}
Type of input signal 2 rotorAngularFrequencyDeviation busFrequencyDeviation generatorElectricalPower generatorAcceleratingPower busVoltage busVoltageDerivative shall be different than PssWECC.inputSignal1Type. Typical value busVoltageDerivative.
inputSignal2Type
{CE7A8469-3DFE-42c6-8303-F1660F8AB428}
Input signal 1 gain iKiisub1subi. Typical value 113.
k1
{4143B66A-209D-4a3b-BCAF-7BDE4AFF2B30}
Input signal 2 gain iKiisub2subi. Typical value 00.
k2
{C7C76093-3F49-42d9-8C89-A4F8E10C2661}
Input signal 1 transducer time constant iTiisub1subi gt 0. Typical value 0037.
t1
{8A8B471E-A930-4965-9C8E-47B351E3F1CB}
Lag time constant iTiisub10subi gt 0. Typical value 0.
t10
{E8999A42-A0F6-4585-AB5C-EB6BF5DA978D}
Input signal 2 transducer time constant iTiisub2subi gt 0. Typical value 00.
t2
{93B8BF85-A20B-4d8b-84A4-2B7FAD0322DB}
Stabilizer washout time constant iTiisub3subi gt 0. Typical value 95.
t3
{E2FE415A-8E6B-47ba-8123-CCE9648D2AF9}
Stabilizer washout time lag constant iTiisub4subi gt 0. Typical value 95.
t4
{93FA4FDB-11B5-4c8f-9261-F0903F324799}
Lead time constant iTiisub5subi gt 0. Typical value 17.
t5
{47CBD07D-EE09-4f33-A3DA-22777057AF60}
Lag time constant iTiisub6subi gt 0. Typical value 15.
t6
{5F729D59-B68C-410c-A948-C02D3D9A882E}
Lead time constant iTiisub7subi gt 0. Typical value 17.
t7
{D80371EC-9902-4d71-B3FC-8E2E03CDF3E4}
Lag time constant iTiisub8subi gt 0. Typical value 15.
t8
{C82F2A60-94E0-4360-AED3-2D2E01C4EE1E}
Lead time constant iTiisub9subi gt 0. Typical value 0.
t9
{7BEC731C-190E-4b0f-9F7E-AFC1E2C7ACC7}
Minimum value for voltage compensator output iViisubCLsubi. Typical value 0.
vcl
{56D21C29-B8C0-4964-AF41-9D085F6B6B2E}
Maximum value for voltage compensator output iViisubCUsubi. Typical value 0.
vcu
{FD20EFD0-D7BB-483a-B49B-92B5BE406B9C}
Maximum output signal iVsmaxi gt PssWECC.vsmin. Typical value 005.
vsmax
{441910D0-BCB8-4114-A1EE-5B50748611C5}
Minimum output signal iVsmini lt PssWECC.vsmax. Typical value 005.
vsmin
{124D95AC-84DB-4a66-81CC-46CBE8C0E32C}
Application layer used with the certificate for mutual authentication.
ISOUpperLayer
{5562C131-015C-4469-BB74-1B33BA1A81D9}.SupplierEnd
The association allows a certificate to be bound for use by TLS.
TCPAccessPoint
{D25EF464-773A-4ecc-AAF8-781EC96B694C}.SupplierEnd
Delay
{784225EE-19A9-4cf5-9299-DAD1950C5181}.ClientEnd
VSCtype1
{28C86EC6-3D7B-4965-99CB-2AB0622D2C24}.SupplierEnd
Delay
{2303C7D4-EE85-47ba-A595-6180D607EEBD}.ClientEnd
VSCtype1
{3EEAA87A-6141-43c6-AE82-9A6DAC9A62E9}.SupplierEnd
Delay
{B244C310-A752-4f97-8CF9-0D6D0C1AB836}.ClientEnd
HVDClookUpTable
{7AC340E9-74FE-45f9-8424-0F67D74E0B6A}.ClientEnd
VSCtype1
{4CCAE11F-2B9B-48f1-B5A0-6357DC443AD7}.SupplierEnd
CULaborItems
{5E0A5A68-F3A6-4607-B782-EC1790EB274A}.ClientEnd
Skills
{E5C4C8B8-F4DA-4f11-BECD-A45EE50E9E7D}.ClientEnd
Specifications
{5119AA22-9D22-4252-BA20-4DF21D5E255F}.SupplierEnd
WorkTasks
{B3426602-AFB3-44a7-9BCB-107ADC91CCAB}.ClientEnd
Source gives information related to the origin of a value. The value may be acquired from the process defaulted or substituted.
source
{E4D6FE8C-2979-4ab1-92C8-705335298653}
Validity of the measurement value.
validity
{C5A711E6-F0C4-47c1-B00E-1FF68CD1B4F8}
Additional information related to the associated quantity.
Detail_Quantity
{E4139F38-C2AF-497b-B916-ECD41EA35023}.ClientEnd
Domain
{3C6AC9D3-B254-422b-83E0-AD878F50E02C}.SupplierEnd
Point
{70A03E37-CDFC-438e-BB13-DBBD82A9288E}.SupplierEnd
TimeSeries
{B7D5F09D-C0DE-43ce-8CC2-0D383279A6BC}.SupplierEnd
Bid
{20A022E9-69A4-4231-A566-82296460EFB1}.SupplierEnd
MitigatedBidClearing
{5A2FDC45-69C0-48d6-B301-3B257BF71F43}.SupplierEnd
RegisteredGenerator
{EE70F7CB-C4DE-4b60-B550-F2637B3FCA48}.ClientEnd
RegisteredResource
{8E2C431E-EC49-4d10-AF9B-073F1BEBDF5F}.ClientEnd
updateType
{F7BC3A42-402E-4ea4-A9AD-F8263B7F94D2}
RegisteredGenerator
{BD442AE6-4D67-494f-9554-BB1CA9309001}.ClientEnd
RegisteredGenerator
{0F128EA3-56EC-44d9-9DCF-6D1D373C70D4}.ClientEnd
RegisteredGenerator
{CEE03ED5-21D8-4bd8-9EC7-78456D6479FB}.ClientEnd
RegisteredGenerator
{47819087-489C-452d-B08E-D0239FC0DFCA}.ClientEnd
AdjacentCASet
{E7E0DD2A-8D53-4ec2-BEE0-BFCCE3D2E252}.SupplierEnd
AggregateNode
{95DFE9B0-18E0-4c05-9AC1-211693BB8524}.SupplierEnd
CommodityDefinition
{9C7DB57F-73C7-4d73-B17D-1CE635F85AF4}.SupplierEnd
EnergyMarkets
{7B226990-9273-4097-A3EE-975B7273F323}.ClientEnd
FuelRegion
{D369B12F-39AD-45d8-B6C9-CDD43DE3458A}.SupplierEnd
HostControlArea
{61BC778B-58EC-4247-B85A-DA7F2D069EB9}.SupplierEnd
LocalReliabilityArea
{E6D2764A-B166-47aa-85A1-8B82794864DB}.SupplierEnd
MSSAggregation
{42061DAA-FC2A-4510-A0B6-81F8DDD07587}.ClientEnd
MktConnectivityNode
{E1B1E7AA-80C6-41cb-8B19-3F793E0E7B53}.SupplierEnd
Pnodes
{226E4117-5AE6-4526-BD59-AE3741B82CD9}.SupplierEnd
ResourceGroupReqs
{1D7D9A91-1BD0-4ef7-80D1-449BA51B49F1}.ClientEnd
SecurityConstraints
{B8D4120C-7577-4aba-A03D-07C4351445C2}.ClientEnd
SecurityConstraintsLinear
{83B2008B-320E-4b16-94B7-804FFDC9588F}.ClientEnd
SubControlArea
{BA94D32D-6765-457a-9130-34C38FCE2CD6}.SupplierEnd
TransmissionContractRight
{A3A25A93-B38D-4be8-AFA8-1F472DA6E232}.SupplierEnd
TransmissionRightChain
{1E012DD2-B528-4079-B377-8386C7DB1523}.SupplierEnd
ClearingResourceAward
{5EDD557D-2252-41e2-AB74-1A856B5BD487}.ClientEnd
RegisteredResource
{54ACC62F-CE0C-41aa-AF9B-3A4F0A5E245D}.ClientEnd
major product type may include the following but not limited toEnergyRegulation UpRegulation DnSpinning ReserveNonSpinning ReserveOperating Reserve
marketProductType
{00C0F0FE-C31B-4f68-BF79-33C01A0AE5BE}
updateType
{9A3DBA39-FBD5-4e16-A824-1D4414287358}
LossClearingResults
{28810405-AFDC-42b6-889E-E5634F47D761}.SupplierEnd
The ValueAliasSet used for translation of a Control value to a name.
ValueAliasSet
{689EAD20-E5B3-46ae-BABC-7A32ADA8F247}.SupplierEnd
GeneratingBid
{B75E5730-E5F1-4d60-BAEF-5B89FAB09454}.ClientEnd
InterTieBid
{1BDCCD9A-FE44-4136-9A38-58893BFCA0AA}.ClientEnd
LoadBid
{AD8B5072-D22F-4473-AF99-5A6CD5C52809}.ClientEnd
RegisteredResource
{B3D5D7A1-24C6-45ae-9EFE-8FCCE619290E}.ClientEnd
condition for the ramp rate
condition
{3D4C9579-34DE-43b7-9C24-B9EFBB67739F}
The condition that identifies whether a Generating Resource should be constrained from Ancillary Service provision if its Schedule or Dispatch change across Trading Hours or Trading Intervals requires more than a specified fraction of the duration of the Trading Hour or Trading Interval. Valid values are FastSlow
constraintRampType
{0A21AF83-027D-464f-B4D2-33421BF5EAAF}
How ramp rate is applied e.g. raise or lower as when applied to a generation resource
rampRateType
{F8927E6D-38BE-4785-9C8D-7F9AD88EE1DE}
The tap ratio table for this ratio tap changer.
RatioTapChangerTable
{9E0B115E-9239-415e-93A5-C5D5CDF33606}.SupplierEnd
Transformer end to which this ratio tap changer belongs.
TransformerEnd
{D8F7848F-543A-4d91-BA97-2A9B3FCFF0C6}.ClientEnd
Tap step increment in per cent of rated voltage of the power transformer end per step position.When the increment is negative the voltage decreases when the tap step increases.
stepVoltageIncrement
{D8CA42B3-3BCB-47df-BE8A-5DD4E3546D52}
Specifies the regulation control mode voltage or reactive of the RatioTapChanger.
tculControlMode
{A7105B45-FAF9-4012-9A98-CCFA67F55C96}
The ratio tap changer of this tap ratio table.
RatioTapChanger
{9E0B115E-9239-415e-93A5-C5D5CDF33606}.ClientEnd
Points of this table.
RatioTapChangerTablePoint
{2D6853F4-72C6-433d-A408-600CB32AF0B0}.ClientEnd
Table of this point.
RatioTapChangerTable
{2D6853F4-72C6-433d-A408-600CB32AF0B0}.SupplierEnd
multiplier
{19537A69-BEDD-487c-BFA7-131495198EB9}
unit
{9D48185D-2672-4a59-B967-AFE697937BD5}
multiplier
{7154DFD0-EE0B-4140-BEA8-7F728CE79C24}
unit
{BCDA3620-EC0B-4840-8EF5-CF87AEA8B0D8}
The equivalent injection using this reactive capability curve.
EquivalentInjection
{FC08DB44-00BE-4bc5-8DE9-3538FD5307B8}.SupplierEnd
Synchronous machines using this curve as default.
InitiallyUsedBySynchronousMachines
{6BEDDBFC-3D03-47f1-A9B8-266425DE28E8}.SupplierEnd
Synchronous machines using this curve.
SynchronousMachines
{3724CB9D-F524-4771-91F7-6BDCEBD04E47}.SupplierEnd
The machines coolant temperature e.g. ambient air or stator circulating water.
coolantTemperature
{2A37F217-BEF3-487c-9FFE-9384C84D555B}
The hydrogen coolant pressure.
hydrogenPressure
{E5956813-39D3-4361-9782-0832C4ACFC99}
multiplier
{3ED78537-D36E-429a-AA73-EB86BF7020FB}
unit
{C4DA5044-2A5B-4504-997D-67F35395A5B0}
All meter readings sets of values containing this reading value.
MeterReadings
{50ABD845-4A69-4a91-A0FE-99656D135A6F}.SupplierEnd
Type information for this reading value.
ReadingType
{F4B9F142-89CC-4df5-93BC-B2C1BD389AE9}.SupplierEnd
Reason for this reading being taken.
reason
{E186EC9F-5F21-4e1d-80AC-76674C2EE96E}
Reading value to which this quality applies.
Reading
{DD6190AA-B446-4216-8E50-3E7421E80344}.SupplierEnd
Type of this reading quality.
ReadingQualityType
{92E5364D-67C4-4eed-850C-DABD16BEC1BB}.SupplierEnd
All reading qualities of this type.
ReadingQualities
{92E5364D-67C4-4eed-850C-DABD16BEC1BB}.ClientEnd
Channel reportingcollecting register values with this type information.
Channel
{D4257F98-65DB-49d2-B38F-C912709EE1BE}.SupplierEnd
All tariff intervals with consumption described by this reading type.
ConsumptionTariffIntervals
{2C44369F-3DF4-4dcd-9036-EDC39B37AB3D}.ClientEnd
All blocks containing interval reading values with this type information.
IntervalBlocks
{5E2DE546-E491-4480-879B-2607C691B257}.ClientEnd
All metrology requirements that require this reading type to be collected.
MetrologyRequirements
{B5CE221C-AAE6-4ae6-A720-B4E199752DF9}.ClientEnd
Pending calculation that produced this reading type.
PendingCalculation
{498A2163-CE45-41ed-9E07-BE86679D0941}.ClientEnd
All reading values with this type information.
Readings
{F4B9F142-89CC-4df5-93BC-B2C1BD389AE9}.ClientEnd
Accumulation behaviour of a reading over time usually measuringPeriod to be used with individual endpoints as opposed to macroPeriod and aggregate that are used to describe aggregations of data from individual endpoints.
accumulation
{64DB8EA4-3709-455f-87D3-D2B76C275464}
Salient attribute of the reading data aggregated from individual endpoints. This is mainly used to define a mathematical operation carried out over macroPeriod but may also be used to describe an attribute of the data when the macroPeriod is not defined.
aggregate
{4BCF265A-A069-46f1-AD91-840831A1CC69}
Argument used to introduce numbers into the unit of measure description where they are needed e.g. 4 where the measure needs an argument such as CEMIn4. Most arguments used in practice however will be integers i.e. denominator1.Value 0 in numerator and denominator means not applicable.
argument
{F9EEB80B-15E0-443a-9A33-175857305C35}
Commodity being measured.
commodity
{041374E8-07D8-4f28-9626-93D5D9DDC974}
Meteringspecific currency.
currency
{EF6C9401-02C7-4b5f-9288-F2A9754845C4}
Flow direction for a reading where the direction of flow of the commodity is important for electricity measurements this includes current energy power and demand.
flowDirection
{79AAA8D8-BCEE-4bd4-B34D-03475F29C42E}
Indication of a harmonic or interharmonic basis for the measurement. Value 0 in numerator and denominator means not applicable.
interharmonic
{785937B7-DD8B-41e6-BF3E-28B1FFD90921}
Time period of interest that reflects how the reading is viewed or captured over a long period of time.
macroPeriod
{41A1F323-E004-4ac6-9704-AB567B0B1E8E}
Identifies what is being measured as refinement of commodity. When combined with unit it provides detail to the unit of measure. For example energy with a unit of measure of kWh indicates to the user that active energy is being measured while with kVAh or kVArh it indicates apparent energy and reactive energy respectively. power can be combined in a similar way with various power units of measure Distortion power distortionVoltAmperes with kVA is different from power with kVA.
measurementKind
{C3E2457C-C85C-458d-AD5A-350493DCA72A}
Time attribute inherent or fundamental to the reading value as opposed to macroPeriod that supplies an adjective to describe aspects of a time period with regard to the measurement. It refers to the way the value was originally measured and not to the frequency at which it is reported or presented. For example an hourly interval of consumption data would have value hourly as an attribute. However in the case of an hourly sampled voltage value the meterReadings schema would carry the hourly interval size information.It is common for meters to report demand in a form that is measured over the course of a portion of an hour while enterprise applications however commonly assume the demand in kW or kVAr normalised to 1 hour. The system that receives readings directly from the meter therefore shall perform this transformation before publishing readings for use by the other enterprise systems. The scalar used is chosen based on the block size not any subinterval size.
measuringPeriod
{7B6C39D5-8341-4d3a-B4D2-72CB83E0400F}
Meteringspecific multiplier.
multiplier
{BDF133DF-E3C4-4310-985C-766D4C7C0DF3}
Meteringspecific phase code.
phases
{AD213E03-86C1-49f8-B2C3-ED6C169D645B}
Meteringspecific unit.
unit
{C718D1BB-0BE8-4fd6-9EA1-96DA5ACD6476}
multiplier
{598000BC-F3E4-4b89-AB35-243CE95ED8C9}
unit
{95DF265F-6A3E-49c4-81DC-D37DD0CE521D}
MarketDocument
{B1D45B36-F3A6-4f96-A2D1-0E8AD7CFBBF6}.SupplierEnd
Period
{E9655504-21F4-4c54-B6E8-8735610776CE}.ClientEnd
Point
{5937F13C-6809-4fd4-9A5E-CC24BE6B8CA7}.SupplierEnd
RegisteredResource
{283FAB08-B9D7-4a6a-88C2-77B410F3C1C8}.ClientEnd
TimeSeries
{F3011AEA-011F-4ef6-A0F7-5ED118EF2480}.ClientEnd
Cashier shift during which this receipt was recorded.
CashierShift
{3CC80665-07B4-4a5d-9D19-56F2B340FE1D}.ClientEnd
All payments received in the form of tenders recorded by this receipt.
Tenders
{61AB1FC1-BB28-47a2-95E4-1FB09BBE1111}.ClientEnd
All transactions recorded for this receipted payment.
Transactions
{436A1D66-C447-4f0e-84DE-DEE861AA01CD}.SupplierEnd
Vendor shift during which this receipt was recorded.
VendorShift
{652E0D7A-D247-45a6-80F2-A0339EFE02D7}.ClientEnd
Receipted amount with rounding date and note.
line
{877D2C12-4368-4021-B365-574E9255A543}
A breaker may have zero or more automatic reclosures after a trip occurs.
ProtectedSwitch
{6447ED06-EC4F-4efc-88F3-7FB21521C7FC}.SupplierEnd
Indicates the time lapse before the reclose step will execute a reclose.
recloseDelay
{A9398E5B-13B6-4991-9082-E30DAEE31044}
Ground trip rating.
groundTripRating
{403CF97E-8E06-4419-AC52-415F19686A46}
Phase trip rating.
phaseTripRating
{23CD3D1C-7840-4e17-915E-62FE5DCCF268}
Asset
{0EDF1A71-1F5E-42e5-9A94-8DFC165669B6}.ClientEnd
PowerRatings
{87E64861-9690-46b3-ADD5-CF931CEA7994}.ClientEnd
TransformerObservations
{8A289EE0-AF52-4d3d-B1DF-2BF047C45F44}.SupplierEnd
status
{9588E218-4A19-4b8d-B948-9777EFC26F0C}
All channels that collectreport values from this register.
Channels
{BDCC2E66-6842-4911-B918-FE7BEF381847}.SupplierEnd
End device function metering quantities displayed by this register.
EndDeviceFunction
{EFFC4614-770D-4c79-9E7C-AD272DF81815}.SupplierEnd
Usage Point
{04237804-35ED-45c5-A932-B74209BBA2C0}.ClientEnd
Clock time interval for register to begingcease accumulating time of usage e.g. start at 800 am stop at 500 pm.
touTier
{21DCD64F-3A2F-4370-B0C5-7A4ED5CDB62D}
Maximum Base Load MW per Participating Load Resource
maxBaseLoad
{E91CFE1F-3AA7-44ca-B919-CF280EC8B3F4}
maximum load reduction
maxLoadReduction
{295B5406-67D1-44ba-BBAE-2EE5883A14F4}
Minimum MW for a load reduction e.g. MW rating of a discrete pump.This attribute may be used also in the LoadBid class. The reason that the attribute is also modeled in this class is that it is resource attribute and needs to be persistently stored.
minLoadReduction
{E553FED0-9DFB-4025-B7FE-96E8499C8386}
minimum load reduction cost. Single number for the load
minLoadReductionCost
{A4DD08BB-BA99-4f9e-B185-D79E98A6AC8A}
ResourcePerformanceRatings
{1449B836-5D46-40fb-ADF8-710E12AD33A4}.ClientEnd
ResponseMethods
{69F7D11C-2F4C-4da3-993F-D604EBFA8F53}.ClientEnd
AuxillaryObject
{B773A97C-0734-453a-BE6C-701847C433D6}.ClientEnd
EnergyPriceIndex
{984F3E09-1CA2-412e-9D3B-1138442A36D1}.ClientEnd
FuelCostCurve
{D73658B4-E454-4c33-84E3-F4704B76D7FD}.ClientEnd
FuelRegion
{2A9F12A2-E1BC-468f-B9A6-8FD550AE1D66}.ClientEnd
GeneratingBids
{C4BA4125-803E-42c1-9C0B-2D5179DA8B57}.SupplierEnd
LocalReliabilityArea
{2AFCD919-E0B4-402b-9374-D1683A531031}.ClientEnd
MktHeatRateCurve
{1BFB226F-6654-4314-8030-31CF5E037B03}.SupplierEnd
Reliability must not run RMNR flag indicated whether the RMR unit is set as an RMNR in the current market
RMNRFlag
{3C38B0C5-574D-4496-8B47-F052EEEF14F9}
Reliability must run RMR flag indicates whether the unit is RMR Indicates whether the unit is RMRN not an RMR unit1 RMR Condition 1 unit2 RMR Condition 2 unit
RMRFlag
{D81E98D7-B8B8-419c-B4D2-F4ECC0E3A8D1}
RMRHeatRateCurve
{EE70F7CB-C4DE-4b60-B550-F2637B3FCA48}.SupplierEnd
Indicates the RMR Manual predetermination status YN
RMRManualIndicator
{7E3BD8DC-18A2-43cd-A600-0E6161E405F5}
RMRStartUpCostCurve
{BD442AE6-4D67-494f-9554-BB1CA9309001}.SupplierEnd
RMRStartUpEnergyCurve
{0F128EA3-56EC-44d9-9DCF-6D1D373C70D4}.SupplierEnd
RMRStartUpFuelCurve
{CEE03ED5-21D8-4bd8-9EC7-78456D6479FB}.SupplierEnd
RMRStartUpTimeCurve
{47819087-489C-452d-B08E-D0239FC0DFCA}.SupplierEnd
Reliability must take RMT flag YesNo indicates whether the unit is RMT
RMTFlag
{4018C7E3-AEA6-4fe1-BDD5-4DED3FBEA373}
RegulatingLimit
{A0FB2AF5-A2A8-4edb-9EE5-789F40B1C427}.SupplierEnd
StartUpCostCurves
{5280EFA9-0801-4e47-AE46-18FA93656505}.ClientEnd
StartUpEnergyCurve
{6F584527-B9F8-4bf0-8BA6-16C6A099CFDF}.SupplierEnd
StartUpFuelCurve
{AA03FF31-0541-46dc-AC61-8F38D2603BD6}.SupplierEnd
StartUpTimeCurve
{70E6AE66-01DD-4461-AE89-C87284489617}.SupplierEnd
Trade
{039D769F-A03A-444a-8786-96815FE89B99}.SupplierEnd
UnitInitialConditions
{F5E62ED0-90DD-4d2f-AAD2-99DD94F92779}.ClientEnd
The ratio of actual energy produced by resource divided by the maximum potential energy if the resource is fully utilized. As an example wind farms.
capacityFactor
{F8F927B4-6F19-4592-A711-4B09F4431850}
Constrained Output Generator COG Indicator YesNo per Generating Resource
constrainedOutputFlag
{C2483159-69F8-4d10-8ADD-BDBF9A609313}
Response rate in MW per minute for ramping energy down.
energyDownRampRate
{ED118D24-B87E-4d60-9410-753DF1C65663}
Response rate in MW per minute for ramping energy up.
energyUpRampRate
{56D40FD5-F57B-4293-AAB0-E9DE80348F27}
Some longstart up time units may need to receive start up instruction before DA market results are available. LongStart resources may be either physical resources within the control with startup times greater than 18 hours or the longstart contractual intertie commitment that shall be completed by 6 am oneday ahead. Therefore there is a need for a process to determine the commitment of such resources before the DA market.
extremeLongStart
{9C7CD5E9-01B8-421f-8AE5-D7E5A998647B}
Values Natural Gas Based Resource Non Natural Gas Based ResourceNG NaturalGasBased Resource a Resource that is powered by Natural GasNNG NonNaturalGasBased Resource a Resouce that is powered by some other fuel than Natural Gas
fuelSource
{B6D6D10F-6B80-4b64-AC0E-CF1166C1B6EB}
High limit for secondary AGC control
highControlLimit
{616ECE19-D953-4d06-B73E-A0C875029250}
Certifies resources for use in MSS Load Following Down
loadFollowingDownMSS
{31674352-5DEF-4033-8B8C-9D24C027C060}
Certifies resources for use in MSS Load Following Up
loadFollowingUpMSS
{A9549DD6-70A9-47ca-B549-A6CCE737A641}
Low limit for secondary AGC control
lowControlLImit
{0D02E7CA-AED9-4c85-9B28-03ACEAAEE1FA}
Maximum Dependable Capacity MNDC. Maximun Net Dependable Capacity is used in association with an RMR contract.
maxDependableCap
{1037A1B4-581D-475c-8340-62EFCFB5A529}
The registered maximum Minimum Load Cost of a Generating Resource registered with a Cost Basis of Bid Cost.
maxMinLoadCost
{F81A7EBB-F994-44fa-B8D5-6FA3A87D53B2}
max pumping level of a hydro pump unit
maxPumpingLevel
{5C768E97-D0E0-4158-BB9C-D572F56C590F}
Maximum allowable spinning reserve. Spinning reserve will never be considered greater than this value regardless of the current operating point.
maximumAllowableSpinningReserve
{6A059B2A-FF73-4a94-8286-E871D9110A7E}
This is the maximum operating MW limit the dispatcher can enter for this unit
maximumOperatingLimit
{F5C35730-CF9E-4344-B01C-E6C75DBF3E15}
minimum load cost. Value is currencyhr
minLoadCost
{0D435EBF-DB38-4e07-8A50-1FBF02893792}
The cost basis for minimum load.
minimumLoadCostBasis
{493F7DCE-BB9C-4b18-A74D-C4487B4AFEAB}
The cost for the fuel required to get a Generating Resource to operate at the minimum load level
minimumLoadFuelCost
{292FA130-17FA-45f9-9C9B-00B20DEE4675}
This is the minimum operating MW limit the dispatcher can enter for this unit.
minimumOperatingLimit
{603B2BE3-B094-4fce-8760-E31F572CC5C3}
Flag to indicate that this unit is a resource adequacy resource and must offer.
mustOfferRA
{F233261E-A5E6-487e-85DE-85B0C99C20BF}
MW value stated on the nameplate of the Generator the value it potentially could provide.
nameplateCapacity
{8DC5C99C-FE18-4300-A4E5-84BE92D36BED}
The portion of the Operating Cost of a Generating Resource that is not related to fuel cost.
operatingMaintenanceCost
{B29BE4AB-51AA-4d93-B667-1AD031995F95}
pumpingCost
{5AC99121-D3D1-4075-87C9-B746A21D658B}
Quick start flag YesNo. Identifies the registered generator as a quick start unit. A quick start unit is a unit that has the ability to be available for load within a 30 minute period.
quickStartFlag
{A8D3D311-0CB4-40cc-B84F-85402703BC59}
Ramp curve type. Identifies the type of curve which may be a fixed static or dynamic.
rampCurveType
{966632EF-831B-4119-B75B-24EA7B803E51}
Regulation down response rate in MW per minute
regulationDownRampRate
{3C864244-2D28-4eab-83A8-5D238415357D}
Specifies if the unit is regulating or not regulating or expected to be regulating but is not.
regulationFlag
{63769B37-4425-437f-AE0D-217CB2427CF3}
Regulation up response rate in MW per minute.
regulationUpRampRate
{38769D89-C10C-4a5e-BE11-AC78944BB1AF}
Response rate in MW per minute for spinning reserve.
spinRampRate
{DAD7E13C-5A29-4bf3-8666-B134A4EDB980}
The cost basis for start up.
startUpCostBasis
{22ABD753-BBCC-45d9-8948-1C316D758F58}
Is the Resource Synchronous Condenser capable Resource?
syncCondCapable
{BB67E8CA-A308-47b2-92F7-815A5623518A}
Generating unit type Combined Cycle Gas Turbine Hydro Turbine Other Photovoltaic Hydro PumpTurbine Reciprocating Engine Steam Turbine Synchronous Condenser Wind Turbine
unitType
{10C48566-74A2-4d03-A82D-19FEF2253140}
Use limit flag indicates if the uselimited resource is fully scheduled or has some slack for realtime dispatch YN
useLimitFlag
{57B50884-A51F-4a19-BBBC-3B5AF04619B5}
Provides an indication that this resource is intending to participate in an intermittent resource program.
variableEnergyResource
{2B5595DF-8888-4cb5-A799-B7F6CAB2DD03}
Flowgate
{B4B4DF5E-5FDD-4ed9-B4E9-ADE4754D4D34}.ClientEnd
InterTieBid
{E8B2FD01-4BC1-4e68-B739-26E746DDB71F}.ClientEnd
InterTieDispatchResponse
{C1ECE446-41CB-4935-9DD9-BB8E3EA8F832}.SupplierEnd
InterchangeSchedule
{EB89CB04-1946-4823-B7D2-6E517A703273}.ClientEnd
WheelingCounterParty
{A446E5B3-C506-49f2-A28E-A19EEAB812A7}.ClientEnd
Indicates the direction exportimport of an InterTie resource.
direction
{001882C9-B9D3-4fb1-84A7-5336BDCBE3FF}
Under each major product type the commodity type can be applied to further specify the type.
energyProductType
{4650C03C-A67C-4583-A83C-5DBC9CB27091}
Flag to indicated whether this Intertie is a DC Tie.
isDCTie
{E292375A-3614-4ed1-AAE2-39E9BDC80DF2}
Specifies whether the intertie resource is registered for the dynamic interchange.
isDynamicInterchange
{4CD99B77-3154-48a7-A2AA-EE764BAD5442}
AuxillaryObject
{E8E1ADFD-2A7D-4748-8265-3F63BD1FED9B}.ClientEnd
LoadBids
{4D1C0118-19FE-4b30-B956-5BEF77F618EE}.SupplierEnd
Indication that this resource is associated with an Adjacent Control Area.
ACAFlag
{60097741-A438-46d9-B8A9-B2E48A18679F}
Indication that the resource participates in the optimization process by default.
ASSPOptimizationFlag
{0A5B9A2D-4F1C-46c1-86B7-820C54B3D615}
AdjacentCASet
{886205D7-4ADB-42fe-A010-F455E9A5B54F}.SupplierEnd
An AggregateNode may be associated with up to many RegisteredResources.
AggregateNode
{E4F5F679-427A-4403-B876-8642E8E03574}.SupplierEnd
AllocationResultValues
{5074A0CF-AF43-4460-BC17-3037761F765B}.SupplierEnd
Commitments
{61A71384-CC3E-4247-AE63-5AD07C4A3E89}.SupplierEnd
ContractDistributionFactor
{B2C73AF1-CB11-4c78-BE4B-750739E77C5F}.SupplierEnd
ControlAreaDesignation
{E2FACF8B-8529-4118-B66B-ABACB5D4B6A4}.ClientEnd
DefaultBid
{F24F3D0F-AE1B-4418-B515-B72D77505E5F}.ClientEnd
DispatchInstReply
{E391D3A8-763C-4236-AF13-BC42EC2166B1}.SupplierEnd
Domain
{2883C3D9-C348-4a3e-A321-5E35C932E66E}.ClientEnd
DopInstruction
{0A0711E7-CD6A-49ca-AFBB-0BB1AE61425F}.SupplierEnd
DotInstruction
{090DD6C1-3007-4b20-A995-9A43659E6687}.ClientEnd
Indication that this resource is associated with an Embedded Control area.
ECAFlag
{D12DD9FD-30B3-45fd-8FFB-2979539DBB2C}
EnergyMarkets
{27C8750F-C833-4de8-B407-CF325D392A50}.ClientEnd
ExPostResourceResults
{A5DD0CDB-1742-4212-BFFE-9A1405F36B62}.ClientEnd
ExpectedEnergyValues
{29590DFD-E80A-489e-9558-7515799A9C17}.SupplierEnd
ForbiddenRegion
{F7D2A98A-9DDF-4461-8515-85812EF2DDD4}.SupplierEnd
FormerReference
{6E79A630-6C5D-4ba3-86D5-0BE5A92B7A38}.SupplierEnd
HostControlArea
{4F7E336A-F935-41ea-B46D-CA4A8FBC907C}.ClientEnd
Instructions
{7B076588-700D-4bbc-80C9-CA48511DE042}.ClientEnd
InterTie
{10599FAD-DB09-4c8e-AB20-91BBA790855D}.SupplierEnd
IntermittentResourceEligibility
{6E8D1E08-8516-4936-BA3D-566DD94BE286}.SupplierEnd
LMPM flag indicates whether the resource is subject to the LMPM test YesNo.
LMPMFlag
{7EB83470-2118-44ae-B5CE-1269BEBD213B}
LoadFollowingInst
{3C97A30C-33B1-4e87-8AAE-BC2568E2F4BD}.SupplierEnd
LoadFollowingOperatorInput
{D80F6DFF-96C2-4687-ABA8-88B11C00DF6E}.ClientEnd
MPMResourceStatus
{606C8F33-4FFF-4ea5-A5B5-CEB460B07A57}.SupplierEnd
MPMTestThreshold
{BEDAF373-FFF3-488c-94D4-242E91A60CFB}.ClientEnd
MarketObjectStatus
{E489A51C-813C-4dd4-B929-320AFC501DEA}.ClientEnd
MarketParticipant
{7EC28792-B0B8-4baa-9CE0-B5896FAAB9BA}.SupplierEnd
MktConnectivityNode
{102246E9-40F9-404f-A841-A49127DDD797}.SupplierEnd
OrgResOwnership
{AB61B549-CFB6-4874-A737-21DD7CC11D7A}.SupplierEnd
A registered resource injects power at one or more connectivity nodes related to a pnode
Pnode
{6A346D84-A25C-41c8-8AFD-BB63272C9F39}.ClientEnd
RMROperatorInput
{8E2C431E-EC49-4d10-AF9B-073F1BEBDF5F}.SupplierEnd
RUCAwardInstruction
{54ACC62F-CE0C-41aa-AF9B-3A4F0A5E245D}.SupplierEnd
RampRateCurve
{B3D5D7A1-24C6-45ae-9EFE-8FCCE619290E}.SupplierEnd
Reason
{283FAB08-B9D7-4a6a-88C2-77B410F3C1C8}.SupplierEnd
RegisteredResources are qualified for resource ancillary service types which include market product types as well as other types such as BlackStart by the association to the class ResourceAncillaryServiceQualification.
ResourceAncillaryServiceQualification
{2E6B6A80-3A52-4eb7-BA69-7EEAF4ED407E}.SupplierEnd
ResourceAwardInstruction
{B6254365-DEB6-483c-875B-4D6152FA2C38}.ClientEnd
ResourceCapacity
{28093C63-595E-4d62-9B92-32DCFA9B4573}.SupplierEnd
ResourceCertification
{198AD87C-C5A0-4f5f-A7C2-F108234D452C}.SupplierEnd
ResourceDispatchResults
{8D71D0FE-0F4C-4878-9AB1-1987773508D8}.SupplierEnd
ResourceGroups
{0E6C97A8-F5B9-4a7e-BDB1-71642B518DC3}.SupplierEnd
ResourceLoadFollowingInst
{3633FC0F-EC33-44ac-AE95-ACFD3E22EDD6}.SupplierEnd
ResourceVerifiableCosts
{F273F12C-B3BA-4688-8600-74598825F110}.ClientEnd
SMPM flag indicates whether the resource is subject to the SMPM test YesNo.
SMPMFlag
{DEAB88BD-73C1-4aae-BEE5-80619CD8544E}
SubControlArea
{8406940A-7751-48cd-BEC8-1C7154E28625}.SupplierEnd
SubstitutionResourceList
{8BD04841-261A-42f1-AF12-1F6BE08DB56A}.SupplierEnd
TimeSeries
{DF9EE60B-C140-4257-AED0-716349B4B59B}.SupplierEnd
Contingent operating reserve availiability YesNo. Resource is availiable to participate with capacity in contingency dispatch.
contingencyAvailFlag
{E34999CD-45F1-4e09-8CA9-59EDDCA45DEA}
Flexible offer flag YN.
flexibleOfferFlag
{91A73064-5EE8-4792-B3ED-D8A64CCB68B7}
Indicates need to dispatch before the start of the operating hour. Only relevant in RealTime Market. Applies to generation intertie and participating load resource. Value YN.
hourlyPredispatch
{5434514C-FBE7-455a-86F9-7262A9031EB2}
A flag to indicate if a resource is an aggregated resource.
isAggregatedRes
{8A330AF7-AAA2-408c-AD75-1EA4F74F70F3}
Market Participation flag indicates whether the resource participate in the market.
marketParticipationFlag
{2B107CA6-4719-4466-B301-3CA1F3793B3B}
Minimum number of consecutive hours a resource shall be dispatched if bid is accepted.
minDispatchTime
{990B339C-1043-4943-B04E-B912FD1BF8A8}
Must offer flag indicates whether the unit is subject to the must offer provisions YN.
mustOfferFlag
{1E22D6A5-86D1-4a93-A894-FF4121AB71B5}
Flag to indicate that the Resource is not participating in the Market Operations.
nonMarket
{B16143F2-E7F9-44c1-90AA-16E6B8E18A22}
Indication that the registered resource is a Point of Delivery YES resource which implies there is a POD Loss Factor.
pointOfDeliveryFlag
{D4363E65-3FF5-432c-A700-91B640849A06}
Price setting flag indicates whether a resource is capable of setting the Market Clearing Price Y for the DA market and if not indicates whether the resource shall submit bids for energy at 0 S or not N.Initially in the RegisteredGenerator class. It was moved to the RegisteredResource class for the participating load dispatch purpose.
priceSetFlagDA
{F2F8884B-1565-4f8c-AA64-B95482046781}
Price setting flag indicates whether a resource is capable of setting the Market Clearing Price Y for the RT market and if not indicates whether the resource shall submit bids for energy at 0 S or not N.Initially in the RegisteredGenerator class. It was moved to the RegisteredResource class for the participating load dispatch purpose.
priceSetFlagRT
{6EE3E81D-1087-470a-9310-2C9690FA5B94}
Registration Status of resource Active Mothballed Planned or Decommissioned.
registrationStatus
{BD6EA656-8A84-41e7-974D-FD9129191247}
Indication that this resource participates in the resource adequacy function.
resourceAdequacyFlag
{D03179F8-B019-4757-B3FC-447742DE5E63}
The regular interval time point data values that define this schedule.
TimePoints
{BC2A40CA-8EF4-4afa-8676-9EA3886E7EE6}.SupplierEnd
The time between each pair of subsequent regular time points in sequence order.
timeStep
{DFAEFBCD-8780-41f2-9D97-388E50F9709D}
Regular interval schedule containing this time point.
IntervalSchedule
{BC2A40CA-8EF4-4afa-8676-9EA3886E7EE6}.ClientEnd
The regulating control scheme in which this equipment participates.
RegulatingControl
{DA01278E-D92F-45c7-8007-F72728FA9797}.SupplierEnd
Enabledisable a regulating control or set new target value.
ProtectiveActionRegulation
{2FDA9413-8CFA-434f-8187-40289D0A95BA}.ClientEnd
The equipment that participates in this regulating control scheme.
RegulatingCondEq
{DA01278E-D92F-45c7-8007-F72728FA9797}.ClientEnd
Schedule for this regulating control.
RegulationSchedule
{C1558282-923D-4767-9EF7-BF4C4E82AE43}.ClientEnd
The terminal associated with this regulating control. The terminal is associated instead of a node since the terminal could connect into either a topological node or a connectivity node. Sometimes it is useful to model regulation at a terminal of a bus bar object.
Terminal
{329F27E5-05A7-4f46-AD18-D92971CC1BF3}.ClientEnd
The regulating control mode presently available. This specification allows for determining the kind of regulation without need for obtaining the units from a schedule.
mode
{0A56ECD7-3F74-4730-9F39-FFCB836BBBDB}
Phase voltage controlling this regulator measured at regulator location.
monitoredPhase
{478DE43F-60E6-4f99-92E2-CB59E264B2B8}
Specify the multiplier for used for the targetValue.
targetValueUnitMultiplier
{31FF79A4-B2A7-4692-A7A9-992283FEEB2E}
RegisteredGenerator
{A0FB2AF5-A2A8-4edb-9EE5-789F40B1C427}.ClientEnd
highLimit
{51D40332-8C3E-4650-9010-6712523EC22B}
lowLimit
{6BBDEA79-983A-4d9a-BA90-D2B1BE029057}
Regulating controls that have this schedule.
RegulatingControl
{C1558282-923D-4767-9EF7-BF4C4E82AE43}.SupplierEnd
A VoltageControlZone may have a voltage regulation schedule.
VoltageControlZones
{56DF2E78-015D-485f-9708-D84FAFD9124C}.SupplierEnd
displacement
{4B7B980C-63C0-4a50-9862-0F4B53612F42}
kind
{51E8894A-C37A-449c-8268-866609668EA0}
Assets
{2FBB4D9A-182E-47c5-8227-76C599CC4086}.SupplierEnd
Specification
{D1E9877C-BF93-4c20-98EC-841633A21B58}.SupplierEnd
Mean time to repair MTTR hours.
mTTR
{0427917F-6CD8-432f-81E7-18C337342A4F}
Momentary failure rate temporary failureskftyear.
momFailureRate
{D663F042-87CB-4a19-ADBE-232D9C32561E}
Gate that through a gate logic and input pin defines arming of the Remedial Action Schemes RAS.
GateArmed
{F4AEF34E-199A-4f15-B975-FF0B28FD8751}.ClientEnd
A Remedial Action Scheme RAS consist of one or more stage that are trigger and execute protection action.
Stage
{8DCB0B7D-45B9-483c-A5E0-6AD156D9B7A1}.ClientEnd
Triggering of the Remedial Action Schemes RAS.
TriggerCondition
{2D5E06E1-6BCA-41a9-9B81-E5FFA56FE6AC}.ClientEnd
Kind of Remedial Action Scheme RAS.
kind
{7BCE4598-196E-40b9-A8B3-D23E10784AF4}
Setting of the timeout elapsed time.
armedTimeout
{8B577ED4-82CE-43a2-9A38-4B30BAC60C04}
Voltage limit on customer side of RCD switch above which the connect should not be made.
customerVoltageLimit
{ABB8657C-24A9-40bd-9D82-83B8C3915231}
Limit of energy before disconnect.
energyLimit
{92297B46-8B9F-4876-9716-BE6F2A3B2D3E}
Warning energy limit used to trigger event code that energy usage is nearing limit.
energyUsageWarning
{345CAAF2-594E-40a3-BECF-FDF5513E3B74}
Load limit above which the connect should either not take place or should cause an immediate disconnect.
powerLimit
{FD1A6CBC-10B3-44cb-9128-DCCC36851BC6}
The Control for the RemoteControl point.
Control
{D8E2547F-5EE8-425a-88B2-6878C15AFEF6}.SupplierEnd
Discontinuous excitation control model using this remote input signal.
DiscontinuousExcitationControlDynamics
{912E18D5-6BA7-4363-935C-5AAF4DB0471F}.ClientEnd
Power factor or VAr controller type 1 model using this remote input signal.
PFVArControllerType1Dynamics
{08E5127F-7B16-4f73-A4EF-20E79A544461}.ClientEnd
Power system stabilizer model using this remote input signal.
PowerSystemStabilizerDynamics
{57187DF7-A206-4e9a-BEB5-C8CEE8478241}.ClientEnd
Remote terminal with which this input signal is associated.
Terminal
{7CA6A357-5876-45c2-9ED0-266641C5D519}.SupplierEnd
Underexcitation limiter model using this remote input signal.
UnderexcitationLimiterDynamics
{926FD0F1-B98A-492d-AD1E-CCA64FBEB605}.ClientEnd
Voltage compensator model using this remote input signal.
VoltageCompensatorDynamics
{F5F154AE-0B1E-4436-BB0A-FB640908FA63}.ClientEnd
The wind plant using the remote signal.
WindPlantDynamics
{A386534A-CECA-4cf5-B0FB-5C4A4D5EA497}.ClientEnd
Wind generator type 1 or type 2 model using this remote input signal.
WindTurbineType1or2Dynamics
{87FA8C90-E6B5-40bb-A4FC-AD947AB5E303}.ClientEnd
Wind turbine type 3 or type 4 models using this remote input signal.
WindTurbineType3or4Dynamics
{6BAC6893-7D0D-407c-903E-4E5F0755C0CE}.ClientEnd
Type of input signal.
remoteSignalType
{72DA94DD-E3E3-4960-8AD3-66CDF0F4B6F8}
Remote unit this point belongs to.
RemoteUnit
{76D05D85-2279-4d21-AFD6-336064DBAF22}.SupplierEnd
Link to the physical telemetered point associated with this measurement.
MeasurementValue
{A7C88F72-6063-4225-8BCA-A830CE33CAC0}.ClientEnd
The time interval between scans.
scanInterval
{27C5E1A2-B3C0-4142-98E3-55D454CF7D61}
RTUs may be attached to communication links.
CommunicationLinks
{E4ED6E40-6C5C-406f-B61F-EFE533D3AE61}.ClientEnd
Remote points this Remote unit contains.
RemotePoints
{76D05D85-2279-4d21-AFD6-336064DBAF22}.ClientEnd
Type of remote unit.
remoteUnitType
{111D4E3D-B96D-4c71-9196-AFD9439B30B7}
Repair work task under which breaker item of this type is repaired.
RepairWorkTask
{C716C74F-2E3C-498a-85C0-DA5BD43AEA95}.SupplierEnd
Breaker component or problem area which is the focus of this maintenance work task for work tasks related to breakers only.
breakerRepairItem
{B3ACED35-1012-4523-ABC2-4F7A28E6C099}
Transformer component or problem area which is the focus of this maintenance work task for work tasks related to transformers only.
transformerRepairItem
{58D810FD-373D-4e8a-A148-A94D2CCB7448}
Type of breaker item to be repaird by this repair work task.
BreakerRepairItem
{C716C74F-2E3C-498a-85C0-DA5BD43AEA95}.ClientEnd
One of the environmental value sets expressing one of the reporting capabilities.
EnvironmentalAnalog
{33EE49E4-C5C2-447f-B5D2-DA0AF83C0024}.ClientEnd
The environmental monitoring station to which this set of reporting capabilities belong.
EnvironmentalMonitoringStation
{6335EFF8-1839-4f0f-A97C-CC890F5D5411}.SupplierEnd
Unit of time in which reporting period is expressed.
reportingIntervalType
{1DD5725E-06D1-4f1a-A7D9-E788F45F453D}
Indicates how the weather station reports observations.
reportingMethod
{291E5936-8313-4a59-805F-73B01DDE076B}
The bus name markers that belong to this reporting group.
BusNameMarker
{37254491-51A1-43fd-8EA9-325A03BB2B8F}.ClientEnd
Power system resources which belong to this reporting group.
PowerSystemResource
{62E3FEEC-F7FE-4ee8-88DC-231AEF7F6DE3}.SupplierEnd
The topological nodes that belong to the reporting group.
TopologicalNode
{1134BB7B-6737-4184-A156-3E1FE506083D}.ClientEnd
ASRequirements
{6B2BD6A2-CC2E-4cf3-BCDE-BB717B4A931B}.ClientEnd
MarketRegion
{C2EA5FDF-AB5A-4353-86E1-3AC96CCCA3CC}.ClientEnd
Reserve requirement type that the max and curve apply to. For example operating reserve regulation and contingency.
reserveRequirementType
{3AD9C24B-EC97-459e-8ABA-5FB7B74E8342}
Market product associated with reserve requirement must be a reserve or regulation product.
MarketProduct
{B135E6CF-CF03-4e34-8A2A-CAB47CB13C0C}.SupplierEnd
ReserveReqCurve
{9181F9BC-7A3E-4c83-87CC-B9FEC9AC20B7}.ClientEnd
SensitivityPriceCurve
{7EED99BC-CD41-443b-94DE-ED7BDA941A80}.SupplierEnd
ReserveReq
{9181F9BC-7A3E-4c83-87CC-B9FEC9AC20B7}.SupplierEnd
Generators discharge water to or pumps are supplied water from a downstream reservoir.
HydroPowerPlants
{2C3E96AE-B573-4669-98A0-A1B15E5B69A2}.ClientEnd
A reservoir may have a natural inflow forecast.
InflowForecasts
{390FA231-DEA9-4f7c-9E58-9EA15F9F2F0C}.ClientEnd
A reservoir may have a level versus volume relationship.
LevelVsVolumeCurves
{1CA34C6F-D018-451a-B9BA-91A089FCA0F8}.ClientEnd
A reservoir may spill into a downstream reservoir.
SpillsFromReservoir
{D6D8406C-3239-432c-8EF7-EA8C64638856}.ClientEnd
A reservoir may spill into a downstream reservoir.
SpillsIntoReservoirs
{D6D8406C-3239-432c-8EF7-EA8C64638856}.SupplierEnd
A reservoir may have a water level target schedule.
TargetLevelSchedule
{B07A132F-C127-483d-A307-B2513535A40A}.ClientEnd
Generators are supplied water from or pumps discharge water to an upstream reservoir.
UpstreamFromHydroPowerPlants
{00B2E13E-C0A8-4011-8062-D47DDF498C70}.ClientEnd
Storage volume between the full supply level and the normal minimum operating level.
activeStorageCapacity
{17391B1F-DFAA-4e5d-8050-B45943CA2AD3}
Full supply level above which water will spill. This can be the spillway crest level or the top of closed gates.
fullSupplyLevel
{90E3C69E-1138-41e8-A4FC-6FDD25360069}
Total capacity of reservoir.
grossCapacity
{F7AA9685-2312-46f5-B54D-BDEEB76A659D}
Normal minimum operating level below which the penstocks will draw air.
normalMinOperateLevel
{FD40FEA9-7B4D-42bb-9403-CBCCD05DF2C7}
The spillway water travel delay to the next downstream reservoir.
spillTravelDelay
{BA136AFA-1D9E-470e-8298-BAD7AC41930C}
The length of the spillway crest.
spillwayCrestLength
{C89E2806-58B3-4c6c-B9E7-112DFF10158F}
Spillway crest level above which water will spill.
spillwayCrestLevel
{C50C7FF9-3DC6-494b-B117-64C94342B7EE}
multiplier
{6256F839-CBEB-4164-926A-0C7D450E1529}
unit
{CDBE0328-0DCE-4f27-A805-49EC479BCAD4}
multiplier
{99CB440E-D654-4929-9D1A-3B22407B5ADC}
unit
{93670290-AE2E-44b4-BF92-B336ACF73EAA}
RUCAwardInstruction
{5EDD557D-2252-41e2-AB74-1A856B5BD487}.SupplierEnd
ResourceAwardInstruction
{CBA2B259-50D6-4c20-9DEA-8E0D4B92E07F}.SupplierEnd
Indication that the system is currently operating in a contingency mode.
contingencyActive
{61E1FBA0-8C2A-493f-BAC8-5961682EE118}
dispatchMode
{416EFBA8-81FC-4e97-B702-A5EE79F9BFF1}
ClearingResourceAward
{CBA2B259-50D6-4c20-9DEA-8E0D4B92E07F}.ClientEnd
MarketProduct
{DCAE610D-01F2-4d9d-84E5-FC64B8C205A5}.ClientEnd
RegisteredResource
{B6254365-DEB6-483c-875B-4D6152FA2C38}.SupplierEnd
SelfScheduleBreakdown
{905CC309-F54E-43fc-BE60-1DD63FC99CAC}.SupplierEnd
Indicates if an award was manually blocked YN. Valid for Spinning and Nonspinning.
manuallyBlocked
{9CE9D015-E1F1-4b71-B5E7-F2704E5E2EE3}
Indicator Yes No that this resource set the price for this dispatch schedule.
marginalResourceIndicator
{0167C2E5-9519-4175-8732-DD9E793AE30F}
updateType
{1B33CF60-DE9D-4e41-919C-79FBC0EB56A6}
BidError
{1733E069-3742-4625-B384-DB2661EDD78B}.SupplierEnd
contingent operating reserve availiability YesNo. Resource is availiable to participate with capacity only in contingency dispatch.
contingencyAvailFlag
{46E5EF0C-D885-430b-B19A-B0B7F059814F}
A Yes indicates that this bid was created by the ISO.
createdISO
{0D9AAAA1-12D7-4853-A7AB-2C06EB523E6C}
RegisteredResource
{28093C63-595E-4d62-9B92-32DCFA9B4573}.ClientEnd
capacity typeThe types are but not limited toRegulation UpRegulation DnSpinning ReserveNonSpinning ReserveFOO capacityMOO capacity
capacityType
{60727D62-1399-49f7-A12D-3AC4831BB915}
Unit selection for the capacity values.
unitSymbol
{385B9EEF-12AF-487d-9907-5E3E872105C5}
RegisteredResources are qualified for resource ancillary service types which include market product types as well as other types such as BlackStart by the association to the class ResourceAncillaryServiceQualification.
RegisteredResource
{198AD87C-C5A0-4f5f-A7C2-F108234D452C}.ClientEnd
{2E6B6A80-3A52-4eb7-BA69-7EEAF4ED407E}.ClientEnd
certifiedDAM
{8E67568B-FBF5-49a6-91E8-583C4B36DF92}
certifiedNonspinDAM
{CE5927C8-C38E-49a2-90F8-AC75F1C4FDB1}
certifiedNonspinRTM
{48D46413-A88D-4d51-A38D-E33613610E72}
certifiedPIRP
{85BA9F07-099E-4179-A007-2F0957C4D9EA}
certifiedRTM
{AB7147FB-5633-4594-906B-9F3431D7BA5D}
certifiedRUC
{DB42263C-314D-47d6-9084-7F4D8D458977}
certifiedRegulation
{90F51713-A6EA-45ef-94ED-1F5D71118BFE}
certifiedReplaceAS
{5EBBA86E-A3B5-4fe7-A9E5-7A979EB74C11}
certifiedSpin
{D661A50C-00DE-4826-A2E6-8A1988ED303C}
market type
market
{385FE5E5-114D-42d0-8180-65B855B33CD0}
Status of the qualification Y Active N Inactive
qualificationFlag
{29A74821-4943-41f1-A65D-9EC9F6AADF60}
Type of service based on ResourceAncillaryServiceType enumeration
type
{6327F78A-BC21-4ef1-BB69-684E4BC85CE8}
ResourceDispatchResults
{1719FC4E-4D25-4f3d-8F87-8A99542BBE51}.SupplierEnd
ResourceLoadFollowingInst
{98A7253A-C806-4b6f-8EF0-E5922B92E7C2}.SupplierEnd
InstructionClearing
{23E96A97-D54D-4d70-8585-71267B61B888}.ClientEnd
RegisteredResource
{8D71D0FE-0F4C-4878-9AB1-1987773508D8}.ClientEnd
ResourceClearing
{1719FC4E-4D25-4f3d-8F87-8A99542BBE51}.ClientEnd
Contingent Operating Reserve Indicator YesNo. Resource participating with AS capacity in contingency dispatch.
contingencyFlag
{608BFBE0-B85E-4b13-BB26-239BACFDE997}
Penalty Dispatch Indicator Yes No indicating an uneconomic adjustment.
penaltyDispatchIndicator
{BFD70DEE-3780-4848-8341-846815E97B37}
updateType
{67D29C7A-92E7-43be-85D2-417C22BECBC0}
RegisteredResources
{0E6C97A8-F5B9-4a7e-BDB1-71642B518DC3}.ClientEnd
ResourceGroupReqs
{2BED8656-05D2-4daf-890F-B14948CB3F57}.SupplierEnd
Status of this group.
status
{684974AF-BC80-4eaf-9717-025040FFA2DD}
RTOs
{1D7D9A91-1BD0-4ef7-80D1-449BA51B49F1}.SupplierEnd
ResourceGroup
{2BED8656-05D2-4daf-890F-B14948CB3F57}.ClientEnd
RegisteredResource
{3633FC0F-EC33-44ac-AE95-ACFD3E22EDD6}.ClientEnd
ResourceClearing
{98A7253A-C806-4b6f-8EF0-E5922B92E7C2}.ClientEnd
ResourceVerifiableCosts
{627F546D-4614-4c83-BC0E-7D5722D3FC8B}.SupplierEnd
Percentage of Fuel Index Price gas for operating above Low Sustained Limit LSL
gasPercentAboveLowSustainedLimit
{9E3D2AEB-6365-4a62-93A3-A6B617216F75}
Percentage of Fuel Oil Price FOP for operating above Low Sustained Limit LSL
oilPercentAboveLowSustainedLimit
{5D681789-53C6-43ad-BAC8-78427A931871}
Percentage of Solid Fuel for operating above Low Sustained Limit LSL
solidfuelPercentAboveLowSustainedLimit
{4639ACA7-0212-461a-8E4E-3FAA4CA6549E}
DemandResponseActualEvent
{568AA2F2-D906-4139-AA0D-393E92602084}.ClientEnd
ResorcePerformanceGlobalFactor
{A5B613FC-5B70-40eb-B760-4948D4892332}.ClientEnd
ResourcePerformanceTimeSeriesFactors
{67DF97CB-CE1E-4576-9B2A-5FB9AD92D4B2}.SupplierEnd
ResourcePerformanceEvaluation
{A5B613FC-5B70-40eb-B760-4948D4892332}.SupplierEnd
RegisteredResource
{1449B836-5D46-40fb-ADF8-710E12AD33A4}.SupplierEnd
ResourcePerformanceEvaluation
{67DF97CB-CE1E-4576-9B2A-5FB9AD92D4B2}.ClientEnd
Percentage of Fuel Index Price gas for cold startup
gasPercentColdStartup
{B1F5F6DC-A7A7-48f5-AF5A-9B0AB262CF92}
Percentage of Fuel Index Price gas for hot startup
gasPercentHotStartup
{C271D4D2-EBEA-4da0-9510-BBEF40C8946F}
Percentage of Fuel Index Price gas for intermediate startup
gasPercentIntermediateStartup
{1C9D49B7-8902-40b4-A3DC-20E2C171E4D9}
Percentage of FIP gas for operating at LSL
gasPercentLowSustainedLimit
{0C7D89B4-1CDC-4e6d-8EDF-A6CE80E536FB}
Percentage of Fuel Oil Price FOP for cold startup
oilPercentColdStartup
{FADF9E8F-646A-4bf6-8546-51CAA5F648B0}
Percentage of Fuel Oil Price FOP for hot startup
oilPercentHotStartup
{BC1CF5BB-B77D-4b3d-80AA-277DB6069B0F}
Percentage of Fuel Oil Price FOP for intermediate startup
oilPercentIntermediateStartup
{BAEFFD3F-902B-4a0d-8AD9-F5C989BD46C9}
Percentage of FOP oil for operating at LSL
oilPercentLowSustainedLimit
{7EED2EC4-B830-43fd-A23E-DBD0EC4C8FB6}
Percentage of Solid Fuel for cold startup
solidfuelPercentColdStartup
{7AC412DF-4E08-4aec-A4C8-53B70C678463}
Percentage of Solid Fuel for hot startup
solidfuelPercentHotStartup
{460A370E-259B-447b-92F0-49E74E78E6C2}
Percentage of Solid Fuel for intermedite startup
solidfuelPercentIntermediateStartup
{A864BE35-4819-4980-ACD3-2E9A153EB3EE}
Percentage of Solid Fuel for operating at LSL
solidfuelPercentLowSustainedLimit
{149C7ED3-9938-4fe5-B965-617196195FB4}
MktHeatRateCurve
{19E8F4BC-BA0C-4a8b-8AFC-83E8D5EE0E8D}.SupplierEnd
RegisteredResource
{F273F12C-B3BA-4688-8600-74598825F110}.SupplierEnd
ResourceOperationMaintenanceCost
{627F546D-4614-4c83-BC0E-7D5722D3FC8B}.ClientEnd
RegisteredResource
{69F7D11C-2F4C-4da3-993F-D604EBFA8F53}.SupplierEnd
All land properties this right of way applies to.
LandProperties
{EB5019C4-5ACE-4ae3-BA94-0695131D9A29}.SupplierEnd
Individual health score associated with this risk score.
AssetHealthScore
{35D3A10F-8986-4cb3-84BA-68730CC19A28}.ClientEnd
The risk kind such as CustomerRisk FinancialRisk SafetyRisk etc.
kind
{4DC2763A-42AD-45aa-AD90-1395DBBEC173}
status
{5A535BCE-5B60-42c0-B302-220654AB6048}
A synchronous machine may operate as a generator and as such becomes a member of a generating unit.
GeneratingUnit
{075455B4-8BAD-4ff0-BF82-B9A27A62A8D2}.ClientEnd
The synchronous machine drives the turbine which moves the water from a low elevation to a higher elevation. The direction of machine rotation for pumping may or may not be the same as for generating.
HydroPump
{B7907DA2-3474-44e7-8BA4-9B2DB3D1D425}.SupplierEnd
Active power injection. Load sign convention is used i.e. positive sign means flow out from a node.Starting value for a steady state solution.
p
{792C720E-AF6B-47ed-84D7-C08A882047CD}
Reactive power injection. Load sign convention is used i.e. positive sign means flow out from a node.Starting value for a steady state solution.
q
{9444CBB2-5BC1-46df-B4EA-356639D6F3F9}
Nameplate apparent power rating for the unit.The attribute shall have a positive value.
ratedS
{5E80BBF0-7614-49da-9D9C-AC059D65E824}
Rated voltage nameplate data Ur in IEC 609090. It is primarily used for short circuit data exchange according to IEC 60909.The attribute shall be a positive value.
ratedU
{5DD8EA89-5A11-4fe2-8700-3F88CB0E5DAC}
Inertia constant of generator or motor and mechanical load iHi gt 0. This is the specification for the stored energy in the rotating mass when operating at rated speed. For a generator this includes the generator plus all other elements turbine exciter on the same shaft and has units of MW x s. For a motor it includes the motor plus its mechanical load. Conventional units are PU on the generator MVA base usually expressed as MW x s MVA or just s. This value is used in the accelerating power reference frame for operator training simulator solutions. Typical value 3.
inertia
{79CEC581-6B20-4d45-AD35-EFE623343AAD}
Stator leakage reactance iXli gt 0. Typical value 015.
statorLeakageReactance
{0AAC33B1-D461-46e7-A2C4-46A5D40E45D9}
Stator armature resistance iRsi gt 0. Typical value 0005.
statorResistance
{E651F525-F913-4b2b-ADFC-236B404DB0DB}
multiplier
{82A7E88E-89CA-46ed-8FAA-1B2E2CFF4928}
unit
{0919D36A-A771-475c-85DA-CEF54827C06D}
Crews
{E3EA714F-98DF-4908-8D66-9D4D2D2ECDBE}.ClientEnd
Locations
{BD8B4DA4-D676-478b-B855-5DB85DFFDB26}.SupplierEnd
status
{2EEF5127-ED4A-4b5c-8A7C-2020591E45C1}
Maximum capacitive reactive power.
capacitiveRating
{210D8469-2544-4d53-BF19-137D5C6A5B6D}
Maximum inductive reactive power.
inductiveRating
{98DDDB20-C1D2-4cfa-BA1E-D6C62545D3C8}
Parameter of this proprietary userdefined model.
ProprietaryParameterDynamics
{16A60C5C-8F8E-4e74-BF69-62A6C79FF350}.SupplierEnd
Supervisor that issued this safety document.
IssuedBySupervisor
{019E9E3C-C2CC-4a76-9DB0-DEC77795FB72}.ClientEnd
Supervisor to whom this safety document is issued.
IssuedToSupervisor
{9928D926-C37A-4b01-9B70-087C54DA13DA}.ClientEnd
Supervisor that released this safety document.
ReleasedBySupervisor
{D76F467F-64BC-408a-BE7C-AEA257C59F88}.ClientEnd
Supervisor to which this safety document is released.
ReleasedToSupervisor
{9101B352-8544-44a4-9F4A-B24425BA24E4}.ClientEnd
Switching plan to which this safety document applies.
SwitchingPlan
{27C9D948-FDCD-4bb2-9FA5-B01A6569D284}.ClientEnd
value
{D97A1BB5-F8C5-4d41-A24D-79D2E425B1E2}
The apparent power limit value for the scheduled time.
value
{7EF6CD0D-2350-4a60-94EC-F4C71CA24433}
The current flow limit value applicable at the scheduled time.
value
{B264B48B-449E-4dec-A0A0-3453274F6B7A}
Assets
{E182BB37-0828-425d-B4E7-9C8FE6B40993}.SupplierEnd
Specification for this scheduled event.
ScheduledEventData
{15E116B8-63BD-4073-A9A6-7D5FDF290740}.ClientEnd
Duration of the scheduled event for example the time to ramp between values.
duration
{D5EAF14A-79D1-4d17-93B0-B9E9C9D6886F}
status
{0A536F7A-8AB5-4b30-8669-79BBC3298B09}
InspectionDataSet
{37ACB8AF-5C2E-4faa-8C9D-87E718507CBD}.SupplierEnd
All scheduled events with this specification.
ScheduledEvents
{15E116B8-63BD-4073-A9A6-7D5FDF290740}.SupplierEnd
Estimated date and time for activity execution with earliest possibility of activity initiation and latest possibility of activity completion.
estimatedWindow
{05F7F71F-1BB8-41f2-A908-6195E76E8179}
Requested date and time interval for activity execution.
requestedWindow
{85E209E1-2D1D-4d3e-920D-1ECC0FBCFA47}
status
{E1112898-C686-40af-A921-5FAC00352F0B}
The season for which the scheduled limits applies. If not specified then applicable ot any season.
Season
{292AF232-83A8-4d6a-9D01-F01B02F5ADF3}.SupplierEnd
The voltage limit value for the scheduled time.
value
{87464AFE-82F5-4627-B0AB-93487057CB13}
FromSCTrade
{6D895553-2440-4f7c-BC33-B46D1B29C9D3}.SupplierEnd
LoadRatio
{1F7B041F-E74A-417c-95DE-6C226FA9485B}.ClientEnd
MarketParticipant
{B7A4F593-994A-4de3-804C-823ABC09CB5B}.SupplierEnd
SubmitFromSCTrade
{5BFC46E8-DD4B-4516-8376-1EFDF9C076C7}.SupplierEnd
SubmitToSCTrade
{AC7FD549-FA5C-45d6-B2D9-4609F963A05C}.SupplierEnd
ToSCTrade
{7714A894-C9FB-420d-B21E-799E489A3AC8}.SupplierEnd
TransmissionContractRight
{9344B7EF-5714-48c0-9CD5-ABBE8A690C30}.SupplierEnd
Flag to indicate creditworthiness Y N
creditFlag
{239B5BB2-0418-485a-8DB4-9509C6634009}
Flowgate
{001E125A-BECE-4e28-A128-A8ADBBEFE8D0}.ClientEnd
InterchangeSchedule
{F470E1A6-33AE-4803-A2CA-A8627C7D6956}.ClientEnd
RegisteredResource
{10599FAD-DB09-4c8e-AB20-91BBA790855D}.ClientEnd
Asset container to which this seal is applied.
AssetContainer
{FDAAA9DF-09C4-4044-B2F9-0C70CD16B243}.ClientEnd
Condition of seal.
condition
{59CDFA31-796A-49c1-891D-CB71C65EE6BF}
Kind of seal.
kind
{242B0C46-91B9-49ad-A49B-FEBAE5DB649C}
The scheduled limits associated with the season.
ScheduledLimits
{292AF232-83A8-4d6a-9D01-F01B02F5ADF3}.ClientEnd
Schedules that use this Season.
SeasonDayTypeSchedules
{D7DD6204-0DD9-4e66-89F5-66E3F0610825}.SupplierEnd
DayType for the Schedule.
DayType
{9B2613ED-CF92-429b-B26F-0EB80C658169}.ClientEnd
Season for the Schedule.
Season
{D7DD6204-0DD9-4e66-89F5-66E3F0610825}.ClientEnd
multiplier
{DF58DF5F-F450-4b71-A1A9-1BBA5C696E5C}
unit
{383E0AEB-B11C-4c02-8C56-5E84FCDA0D3B}
BaseCaseConstraintLimit
{8FF929E3-7DF8-484e-9AE6-E78FD919B4C1}.ClientEnd
ConstraintTerms
{BB8340BB-8D35-4db5-B3EA-6A408762BF83}.SupplierEnd
ContingencyConstraintLimits
{BF65240F-A284-4af5-8E7D-B230D8362719}.ClientEnd
DefaultConstraintLimit
{59C7A4B0-0AB0-47cf-B08A-D99F0E01C0D2}.ClientEnd
RTO
{83B2008B-320E-4b16-94B7-804FFDC9588F}.SupplierEnd
Flowgate
{D96B3C19-134E-4b97-96C3-34675C1BB168}.ClientEnd
GeneratingBid
{EF812433-5985-4f7f-AEE9-C31F08021E9B}.ClientEnd
RTO
{B8D4120C-7577-4aba-A03D-07C4351445C2}.SupplierEnd
Actual branch or group of branches MW flow only for transmission constraints
actualMW
{3F4F5E44-40C3-4fb2-ABF6-6CCD01F0B8B7}
Maximum MW limit
maxMW
{A553DBCE-3908-4d10-8777-D39412F3583C}
Minimum MW limit only for transmission constraints.
minMW
{C452A034-8A7B-41a2-AC43-F11FEFDC2C1F}
Optimal MW flow
mwFlow
{9C18181A-43C1-451f-BAA5-B055EBEB110B}
Binding MW limit.
mwLimit
{EE4C25B6-CA8B-450b-BC29-B761B0C43343}
Security constraint shadow price.
shadowPrice
{0D5172D6-0E6B-4767-BA3D-E70AD5D318D4}
ResourceAwardInstruction
{905CC309-F54E-43fc-BE60-1DD63FC99CAC}.ClientEnd
Self schedule breakdown type.
selfSchedType
{D94DCDEB-89BA-49f1-96AA-1EB2DA733DD9}
ReserveReq
{7EED99BC-CD41-443b-94DE-ED7BDA941A80}.ClientEnd
SelfSeries
{C719B547-0548-4e82-8A7C-4150017941AB}.SupplierEnd
Series
{C719B547-0548-4e82-8A7C-4150017941AB}.ClientEnd
Positive sequence resistance.
r
{0921F3FA-D656-43fd-979B-13401C2AC583}
Zero sequence resistance.
r0
{E37FE89F-D6D7-4728-894D-1797E5FE6B15}
The maximum current the varistor is designed to handle at specified duration. It is used for short circuit calculations and exchanged only if SeriesCompensator.varistorPresent is true.The attribute shall be a positive value.
varistorRatedCurrent
{A64EF97A-B0EC-45de-B90A-1A86F08CA31B}
The dc voltage at which the varistor starts conducting. It is used for short circuit calculations and exchanged only if SeriesCompensator.varistorPresent is true.
varistorVoltageThreshold
{5E30BCEC-E8EB-4b1d-9AE5-E44FF6B0FFDE}
Positive sequence reactance.
x
{F6F38E50-1E7A-4736-9E5E-0A3058E1D256}
Zero sequence reactance.
x0
{B3898136-E885-48bc-BBFB-A9F50D36078B}
All configuration events created for this service category.
ConfigurationEvents
{460BA6C7-2417-41f6-8AC0-A21EE240B5BC}.SupplierEnd
All customer agreements with this service category.
CustomerAgreements
{1CD25DA9-4F95-43aa-A7CF-B41C352C30AA}.ClientEnd
All pricing structures applicable to this service category.
PricingStructures
{4940002E-34B8-4d2b-96A5-2E4EC7A20FF2}.SupplierEnd
All usage points that deliver this category of service.
UsagePoints
{E8ABDA4A-FD10-41db-B40A-285E3E93266A}.ClientEnd
Kind of service.
kind
{2EBA6E82-3221-4395-829D-A3E65904FFC2}
Period in which this service guantee applies.
applicationPeriod
{0BFD8F02-C834-4a59-8DFB-2717DC74C117}
Amount to be paid by the service provider to the customer for each violation of the serviceRequirement.
payAmount
{8D25CF2E-092C-48f3-A976-8DB91767633B}
All customer agreements regulating this service location.
CustomerAgreements
{C20149AA-BEFF-43c5-B26A-F75F414F345B}.ClientEnd
All end devices that measure the service delivered to this service location.
EndDevices
{E1374558-A400-46da-9FB2-5F7497097A3D}.SupplierEnd
TroubleTicket
{61FDCE34-6ACD-4edb-A961-05C33EC48E86}.SupplierEnd
All usage points delivering service of the same type to this service location.
UsagePoints
{9FD59FA1-2361-4259-948C-56433EAAF9B0}.SupplierEnd
Usage point applying this multiplier.
UsagePoint
{79BFF755-2D9F-4654-B2FF-58E647CF5C97}.ClientEnd
Kind of multiplier.
kind
{FD0F696B-C1EF-4d5f-AD59-106A1F4AF45E}
A transmission path has a pointofdelivery service point
PODTransmissionPath
{21CB6E87-75AD-4919-B4ED-4192EC9CC857}.SupplierEnd
A transmission path has a pointofreceipt service point
PORTransmissionPath
{94CD1232-0212-4261-9FE4-36493F16F0E4}.SupplierEnd
SinkReservation
{64CB9D37-23DD-46f9-A4A8-47CF257C8105}.SupplierEnd
SourceReservation
{E205C545-1AF7-4249-9970-5E34913BCC3E}.SupplierEnd
All BackAccounts this ServiceSupplier owns.
BankAccounts
{A4F61027-A9D2-47ab-AAEA-74678D39E4DE}.SupplierEnd
All customer agreements of this service supplier.
CustomerAgreements
{47FE73EC-DD27-4731-8091-E3020EACA869}.SupplierEnd
All usage points this service supplier utilises to deliver a service.
UsagePoints
{543EBBDE-C4D2-433d-AA02-21917EA65375}.SupplierEnd
Kind of supplier.
kind
{97BCE74A-66DA-41c5-B277-E5E426C84E5B}
EnergyMarket
{53E470E2-1BB8-49d7-B69A-D59030A5D75A}.ClientEnd
MajorChargeGroup
{66C30E2D-CB35-48aa-A9C2-A0E325DA6FD5}.ClientEnd
MarketInvoiceLineItem
{C0177491-5DB7-458c-8967-3D68B4E446EA}.ClientEnd
MarketLedgerEntry
{DE87169A-1AAE-49ed-BD84-5D34B06D5FC7}.ClientEnd
Interval for activity of this shift.
activityInterval
{D6FE67F4-3C80-4b32-9818-8D5532DE061F}
Total of amounts receipted during this shift that can be manually banked cash and cheques for example. Values are obtained from Receipt attributessumReceipt.receiptAmount for all Receipt.bankable true.
receiptsGrandTotalBankable
{D5335364-235D-4a48-861B-7AF98AAB8DED}
Total of amounts receipted during this shift that cannot be manually banked card payments for example. Values are obtained from Receipt attributessumReceipt.receiptAmount for all Receipt.bankable false.
receiptsGrandTotalNonBankable
{BC17E248-6477-4d51-B41B-4E4E78CB5829}
Cumulative amount in error due to process rounding not reflected in receiptsGrandTotal. Values are obtained from Receipt attributessumReceipt.receiptRounding.
receiptsGrandTotalRounding
{C3518183-0A41-4389-9A21-109535A6EE06}
Cumulative total of transacted amounts during this shift. Values are obtained from transactionsumTransaction.transactionAmount. It also has to be reconciled against transaction summarysumTransactionSummary.transactionsTotal.
transactionsGrandTotal
{6C451EBA-C13A-4b82-82F8-FBB163AD8BA7}
Cumulative amount in error due to process rounding not reflected in transactionsGandTotal. Values are obtained from Transaction attributessumTransaction.transactionRounding.
transactionsGrandTotalRounding
{8A10D665-72FD-4267-AA34-9A63931D2A21}
Crews
{764EE186-E180-4d38-9772-53A73AAE0278}.ClientEnd
status
{6178AA14-8632-4cdf-90B8-12138E280E35}
Date and time interval for which this shift pattern is valid when it became effective and when it expires.
validityInterval
{5F729D51-43E5-41b8-A854-85A58F6206FB}
Transformer end that voltage is applied to in this shortcircuit test. The test voltage is chosen to induce rated current in the energised end.
EnergisedEnd
{2E74ED8F-7D38-402e-861A-F390B8A642DD}.SupplierEnd
All ends shortcircuited in this shortcircuit test.
GroundedEnds
{B6AF9146-CA85-4239-9212-97F858E8662C}.SupplierEnd
Short circuit current..
current
{1F3F5D90-C113-4284-9E85-BDC58EAA8C76}
Leakage impedance measured from a positivesequence or singlephase shortcircuit test.
leakageImpedance
{C03D7C4E-BB84-4120-AA44-C46A92A28D85}
Leakage impedance measured from a zerosequence shortcircuit test.
leakageImpedanceZero
{BBD1204C-898A-4f87-9751-5E8F3B3D4AE5}
Load losses from a positivesequence or singlephase shortcircuit test.
loss
{225E0C38-4C00-4998-9880-DEF76F478BAA}
Load losses from a zerosequence shortcircuit test.
lossZero
{9FC0751F-4F3E-4419-AF99-6FA178C8DD27}
Short circuit apparent power.
power
{DE0DBBF2-103F-48e0-B037-B395D72EF1C8}
Short circuit voltage..
voltage
{A20E661F-6064-42af-BA8B-CF34F8A2C0F0}
ShuntCompensatorAction
{9AE30218-76B9-40f7-A698-BEA89FA25113}.SupplierEnd
The individual phases models for the shunt compensator.
ShuntCompensatorPhase
{C9E66DE4-0CA6-4e91-A991-5377B910EB14}.SupplierEnd
The state for the number of shunt compensator sections in service.
SvShuntCompensatorSections
{E34ED370-94B3-4e27-B2EC-76FFEED7FAF5}.ClientEnd
An automatic voltage regulation delay AVRDelay which is the time delay from a change in voltage to when the capacitor is allowed to change state. This filters out temporary changes in voltage.
aVRDelay
{41DD5C9D-F00A-412d-B1CA-33CA58C7440E}
The voltage at which the nominal reactive power may be calculated. This should normally be within 10 of the voltage at which the capacitor is connected to the network.
nomU
{FF89F4A3-5F28-4e65-82C7-AE0A0164C161}
The type of phase connection such as wye or delta.
phaseConnection
{53CF7DD7-A76B-40c3-9D46-B8F4B2AD9A24}
Voltage sensitivity required for the device to regulate the bus voltage in voltagereactive power.
voltageSensitivity
{FA12B93F-FE0C-4b5a-9028-226FA7BAE2E9}
ShuntCompensator
{9AE30218-76B9-40f7-A698-BEA89FA25113}.ClientEnd
Switching action to perform
kind
{D61F7ED2-3034-446c-A7E6-A0227DE1FD1C}
ShuntCompensatorInfo
{A5EB9D9A-15FF-4076-9909-2B14A074EA9C}.ClientEnd
The size of the individual units that make up the bank.
cellSize
{ACAEE29C-5B26-4a73-B6AE-12EBEC5331DE}
Kind of control if any.
controlKind
{85BB5EC6-8B89-430a-AA64-7EF587EF3876}
For locally controlled shunt impedances which have a voltage override feature the high voltage override value. If the voltage is above this value the shunt impedance will be turned off regardless of the other local controller settings.
highVoltageOverride
{1B170E34-1AC6-490e-9F3A-798EC6F79CAE}
Kind of local controller.
localControlKind
{86E40043-1E27-47bf-89B1-6A17E0F30CAB}
For locally controlled shunt impedances which have a voltage override feature the low voltage override value. If the voltage is below this value the shunt impedance will be turned on regardless of the other local controller settings.
lowVoltageOverride
{FDEB0357-8EAB-44b8-87E8-DA9A6ED0A801}
For VAR amp or power factor locally controlled shunt impedances Kind of regulation branch.
regBranchKind
{65BCE8A9-0D6F-4265-B4FE-D828403B58D4}
Phases that are measured for controlling the device.
sensingPhaseCode
{B38D809A-2A66-41d6-BE06-2D6FADC5DFC8}
Time interval between consecutive switching operations.
switchOperationCycle
{055BF15E-41F1-4025-B226-79E6A5420387}
MktShuntCompensator
{4C898DD2-7D9D-4138-A8D0-B271310AE638}.SupplierEnd
ShuntCompensatorControl
{A5EB9D9A-15FF-4076-9909-2B14A074EA9C}.SupplierEnd
Maximum allowed apparent power loss.
maxPowerLoss
{54CBED91-48A8-49bb-BEDA-05CFF307441B}
Rated current.
ratedCurrent
{4A99376B-5DC3-4624-A07C-747A7172A8F6}
Rated reactive power.
ratedReactivePower
{4608D242-6EF9-42be-B3FD-9F96542D71C5}
Rated voltage.
ratedVoltage
{BA81D35A-EDC6-4968-8264-56C8F0954E71}
Shunt compensator of this shunt compensator phase.
ShuntCompensator
{C9E66DE4-0CA6-4e91-A991-5377B910EB14}.ClientEnd
Phase of this shunt compensator component. If the shunt compensator is wye connected the connection is from the indicated phase to the central ground or neutral point. If the shunt compensator is delta connected the phase indicates a shunt compensator connected from the indicated phase to the next logical nonneutral phase.
phase
{623751D6-D4B2-463b-8D77-0E4BD5D0A99B}
A thermal generating unit may have a shutdown curve.
ThermalGeneratingUnit
{4D553F1E-EFC5-42c1-92D6-0E421FE8975B}.SupplierEnd
Fixed shutdown cost.
shutdownCost
{09C3B77C-60B5-452a-AB1F-2D43BD4EE800}
Kind of this function.
kind
{3ECD9B17-7937-4d8d-B398-2F9197F585AD}
Crafts
{F6C636B7-1341-45e9-9F57-F9DAF8AA60FC}.SupplierEnd
ErpPerson
{9D792EF4-F8E0-42ce-A1BF-B84E9BA01D5F}.ClientEnd
QualificationRequirements
{E5C4C8B8-F4DA-4f11-BECD-A45EE50E9E7D}.SupplierEnd
Interval between the certification and its expiry.
certificationPeriod
{116B8739-9A90-48b6-B6AD-98F5CA835FB2}
Level of skill for a Craft.
level
{E2D47EC8-BA96-4046-8C2B-27FCEBEB216A}
Kind of space analog.
kind
{5F3FC9AB-6EDA-4390-8E8C-646A41CD6034}
UserAttributes used to specify further properties of the asset covered with this specification. Use name to specify what kind of property it is and value.value attribute for the actual value.
AssetProperites
{77BA456A-7BFE-460d-9B1F-6CFF50541E78}.ClientEnd
AssetPropertyCurves
{54F87E6E-39D6-413c-AF0C-2BC67DD4F008}.SupplierEnd
DimensionsInfos
{5070DD0D-A85D-4e3a-8E88-6373ED2A15DE}.ClientEnd
Mediums
{E64B800B-A4D4-4190-B7C3-AC53BAA0C1DD}.SupplierEnd
QualificationRequirements
{5119AA22-9D22-4252-BA20-4DF21D5E255F}.ClientEnd
UserAttributes used to specify ratings of the asset covered by this specification. Ratings also can be used to set the initial value of operational measurement limits. Use name to specify what kind of rating it is e.g. voltage current and value attribute for the actual value and unit information of the rating.
Ratings
{A095B451-1D6E-48b1-8999-6944FB2D21D0}.ClientEnd
ReliabilityInfos
{D1E9877C-BF93-4c20-98EC-841633A21B58}.ClientEnd
Test sampler taker who gathered this specimen.
AssetTestSampleTaker
{B057FDCC-0EE2-422a-A257-ADAE38F4BB01}.SupplierEnd
Results from lab testing done on specimen.
LabTestDataSet
{C2DD4DA1-4B26-4df0-8A58-EA8BE7DC80D4}.ClientEnd
Operating ambient temperature in C.
ambientTemperatureAtSampling
{0FA4E55E-ED4B-4f68-90CB-6A4CF4CA436B}
Operating ambient humidity in percent.
humidityAtSampling
{71765497-90E9-417c-ABEB-2D69386FB5A3}
multiplier
{FBDA5FCF-A38C-4346-92F6-2DFB2B0D3895}
unit
{74C09094-CAA7-4c9a-95C3-47A5B2404762}
RemedialActionScheme
{8DCB0B7D-45B9-483c-A5E0-6AD156D9B7A1}.SupplierEnd
A Stage consist of one or more StageTrigger.
StageTrigger
{A409C34B-147C-43be-B5D6-51CEB1F7EC3F}.ClientEnd
Association to a Gate that through a gate logic and input pin defines arming of the StageTrigger.
GateArmed
{EB996EFA-4676-43b1-8D6E-DCBC54112791}.SupplierEnd
For the StageTrigger to active the set of protective actions the condition for communication needs to be met true.
GateComCondition
{5CBC56EA-4603-4ba3-93A1-162E6A7AC535}.SupplierEnd
The Gate result that trigger the StageTrigger and thereby executing the a set of protective actions.
GateTrigger
{5AED1733-5EAF-4438-9A42-E9656E4508DA}.SupplierEnd
ProtectiveActionCollection
{E36506E6-0D19-4846-93FA-EA04CBD6AC84}.ClientEnd
Stage
{A409C34B-147C-43be-B5D6-51CEB1F7EC3F}.SupplierEnd
CustomerAgreements
{6081B3B7-6BE2-4dff-BD8D-9BAF5855DE67}.ClientEnd
The units startup model may have a startup ignition fuel curve.
StartupModel
{C38D6633-D0B0-4d21-B763-449DFF5AF2B2}.SupplierEnd
Type of ignition fuel.
ignitionFuelType
{C0AFBB3C-2C3E-4e9e-BFD8-47888F84708B}
The units startup model may have a startup main fuel curve.
StartupModel
{09B7E8E0-2AC8-4a66-AB2A-A93F87445E7D}.SupplierEnd
Type of main fuel.
mainFuelType
{E3D51998-0F3A-45fc-886D-E130B8765796}
The units startup model may have a startup ramp curve.
StartupModel
{4425F095-1419-4c26-8C88-C49B274DA364}.SupplierEnd
The startup ramp rate in gross for a unit that is on hot standby.
hotStandbyRamp
{AF249DD9-1266-4768-8BDD-23C837C7A198}
GeneratingBid
{2C224C9B-54C9-40f5-8796-E455294849C7}.SupplierEnd
RegisteredGenerators
{5280EFA9-0801-4e47-AE46-18FA93656505}.SupplierEnd
RegisteredGenerator
{6F584527-B9F8-4bf0-8BA6-16C6A099CFDF}.ClientEnd
RegisteredGenerator
{AA03FF31-0541-46dc-AC61-8F38D2603BD6}.ClientEnd
GeneratingBid
{70D9DB41-202E-44ce-B18A-F7269093B950}.SupplierEnd
RegisteredGenerator
{70E6AE66-01DD-4461-AE89-C87284489617}.ClientEnd
The units startup model may have a startup ignition fuel curve.
StartIgnFuelCurve
{C38D6633-D0B0-4d21-B763-449DFF5AF2B2}.ClientEnd
The units startup model may have a startup main fuel curve.
StartMainFuelCurve
{09B7E8E0-2AC8-4a66-AB2A-A93F87445E7D}.ClientEnd
The units startup model may have a startup ramp curve.
StartRampCurve
{4425F095-1419-4c26-8C88-C49B274DA364}.ClientEnd
A thermal generating unit may have a startup model.
ThermalGeneratingUnit
{99C4296C-33D5-4c79-A4FB-0A9EC0794967}.SupplierEnd
Fixed maintenance cost.
fixedMaintCost
{760B633F-99EF-4f6d-8CA8-B4B5880A26CE}
The amount of heat input per time unit required for hot standby operation.
hotStandbyHeat
{E71276CD-C2B1-42ce-8481-78CBA4F6394F}
Incremental maintenance cost.
incrementalMaintCost
{DFCA0C86-9A51-43bf-B5A3-BDBEEDE377E4}
The minimum number of hours the unit must be down before restart.
minimumDownTime
{4CD20558-5875-4ac7-86A2-20DA3BD585B9}
The minimum number of hours the unit must be operating before being allowed to shut down.
minimumRunTime
{ECF4E9FF-B38E-4962-BD09-AA1DF2E8D2DC}
The opportunity cost associated with the return in monetary unit. This represents the restarts share of the unit depreciation and risk of an event which would damage the unit.
riskFactorCost
{68F157E6-FEC4-43c4-BDD6-16465BC7913E}
Total miscellaneous start up costs.
startupCost
{09CB2A01-9830-4356-9049-4065388E8C1C}
The units auxiliary active power consumption to maintain standby mode.
stbyAuxP
{4DF7BFED-0C3C-4474-B711-8787C7070917}
Static Var Compensator dynamics model used to describe dynamic behaviour of this Static Var Compensator.
StaticVarCompensatorDynamics
{13F2FB39-01AE-4cc8-8B2D-1E843943E145}.ClientEnd
Capacitive reactance at maximum capacitive reactive power. Shall always be positive.
capacitiveRating
{E35F733F-7F1A-4124-8539-BE6FEE250CCD}
Inductive reactance at maximum inductive reactive power. Shall always be negative.
inductiveRating
{3F4C093D-2CC5-4ee5-A225-31D4B7AFD3AC}
Reactive power injection. Load sign convention is used i.e. positive sign means flow out from a node.Starting value for a steady state solution.
q
{EAA3BC8D-A193-4c4e-BE22-F45A9C2A491C}
SVC control mode.
sVCControlMode
{5D29151B-3D23-4964-BE66-3C58A2D84411}
The characteristics slope of an SVC defines how the reactive power output changes in proportion to the difference between the regulated bus voltage and the voltage setpoint.The attribute shall be a positive value or zero.
slope
{71A799EF-C590-4631-A53A-EC207BFFC113}
The reactive power output of the SVC is proportional to the difference between the voltage at the regulated bus and the voltage setpoint. When the regulated bus voltage is equal to the voltage setpoint the reactive power output is zero.
voltageSetPoint
{170589DF-9B85-487a-BC91-4BC8ECB1D88C}
Static Var Compensator to which Static Var Compensator dynamics model applies.
StaticVarCompensator
{13F2FB39-01AE-4cc8-8B2D-1E843943E145}.SupplierEnd
The order in which this statistical calculation is done.
CalculationMethodOrder
{3472E24D-F0B4-42fa-AC2A-06A47816E2D7}.SupplierEnd
Calculation mode.
calculationMode
{14CDE2CD-4A7E-48e5-BDD0-317BA89E9C8A}
Kind of statistical calculation specifying how the measurement value is calculated.
calculationTechnique
{9D14D95E-1052-43eb-9FD3-BFB300D4F236}
A cogeneration plant has a steam sendout schedule.
CogenerationPlant
{29FFC448-2620-47ba-BE72-7DE2E8858FD0}.SupplierEnd
Steam turbines may have steam supplied by a steam supply.
SteamTurbines
{93AA313B-1303-4624-9368-557ED82DDB59}.SupplierEnd
Steam turbines may have steam supplied by a steam supply.
SteamSupplys
{93AA313B-1303-4624-9368-557ED82DDB59}.ClientEnd
Crossover time constant.
crossoverTC
{BC022F6E-0F59-432b-877C-B9F0BE686B85}
First reheater time constant.
reheater1TC
{F882F483-4C43-4bdc-A2E2-E17CD57AB9B0}
Second reheater time constant.
reheater2TC
{69FADD2A-834A-4af5-9042-6B51AF8B0840}
Steam chest time constant.
steamChestTC
{2AC91EE6-4C0A-47f3-B4E3-746439190A8D}
Status of this address.
status
{32354147-6588-46c6-9B6F-C327E702BCAC}
Street detail.
streetDetail
{080F12A9-718C-4a10-A2BE-878231C3927F}
Town detail.
townDetail
{07E7BC8F-BAA8-4462-BDA1-BA35D58B129D}
Pole to which thiss streetlight is attached.
Pole
{7CD98E1E-DB38-4f5f-B4AB-606B687CE71D}.ClientEnd
Length of arm. Note that a new light may be placed on an existing arm.
armLength
{83A307A1-6E90-47dc-8716-3A1FF0F2CF0C}
Lamp kind.
lampKind
{AE93BE6F-645B-40ce-916E-9D30BEBAA915}
Power rating of light.
lightRating
{369AE287-31F6-48aa-911D-DF8B05944CBB}
The values connected to this measurement.
StringMeasurementValues
{05328E98-5B4F-4f0b-B2C2-BDCB0EF11D35}.ClientEnd
Measurement to which this value is connected.
StringMeasurement
{05328E98-5B4F-4f0b-B2C2-BDCB0EF11D35}.SupplierEnd
Unit multiplier of this quantity.
multiplier
{63AA3365-459E-41b7-B43C-645BEF9F9DAD}
Unit of this quantity.
unit
{175C2CD1-448B-4e14-A8E5-7811DF130C49}
Structure support for this structure.
StructureSupports
{56A18E04-CDA2-4508-BE62-DE15B2FDE7D7}.SupplierEnd
WireSpacingInfos
{7995689F-9BD5-49e1-BAE8-C986A5446310}.ClientEnd
Visible height of structure above ground level for overhead construction e.g. Pole or Tower or below ground level for an underground vault manhole etc. Refer to associated DimensionPropertiesInfo for other types of dimensions.
height
{85F62439-56B8-4ec7-AC19-4C99CD234A67}
Material this structure is made of.
materialKind
{7D3CB05A-3B0D-4075-9C4C-AC060E8857F0}
Maximum rated voltage of the equipment that can be mounted oncontained within the structure.
ratedVoltage
{3EE72D69-2ED8-493f-93CC-7CA89A9619F6}
The secured structure supported by this structure support.
SecuredStructure
{56A18E04-CDA2-4508-BE62-DE15B2FDE7D7}.ClientEnd
if anchor Kind of anchor.
anchorKind
{C4434326-F3F2-4200-9473-F8E26B0B92D0}
if anchor Length of rod used.
anchorRodLength
{40123234-BEBF-48f4-B938-21D72C3D2970}
Direction of this support structure.
direction
{E16D0A41-D1A0-4b09-95AD-1ABA0E5EA383}
Kind of structure support.
kind
{0E185E57-D6CD-4929-8F09-373419661020}
Length of this support structure.
length
{B2008BB0-6908-4871-8FB7-D045954082F6}
AdjacentCASet
{6E3CCC1F-13F4-4f39-8628-7EAC38F18D74}.ClientEnd
AggregateNode
{95FCC4C7-2611-4267-9EF0-B7A30B49ECE8}.ClientEnd
AreaReserveSpecification
{F6EC071D-A9FE-4972-8340-7B298A3F59EF}.ClientEnd
BidSelfSched
{8B909238-F00E-4f58-A22C-21C482041260}.SupplierEnd
CnodeDistributionFactor
{69BC43A4-9AD8-4639-A0FA-43901913DEDB}.ClientEnd
ControlAreaDesignation
{ABACF27C-565A-45bd-B69C-0A1A99CECFC2}.ClientEnd
ExPostLossResults
{82BD4DEF-763E-4739-B4DC-07A529BF1E77}.ClientEnd
Energy is transferred between interchange areas
Export_EnergyTransactions
{FE5AFCF1-5AF3-41b8-A9F4-38F6BDF94098}.SupplierEnd
From_Flowgate
{1041B4DE-551C-4099-85BD-E8EBC12523E1}.ClientEnd
GeneralClearingResults
{52EA9C29-FB61-4524-A03E-85E09C194BB4}.SupplierEnd
The interchange area may operate as a control area
HostControlArea
{FBEF4124-D3C2-4585-A504-3D5551015F14}.ClientEnd
Energy is transferred between interchange areas
Import_EnergyTransactions
{2143F763-800E-436a-B8FB-44CEB5B9E1EB}.SupplierEnd
A control area can have one or more net inadvertent interchange accounts
InadvertentAccount
{3CB78F17-FFCF-48bc-835B-C78BF0FB4994}.ClientEnd
LossClearingResults
{609C0491-3062-444d-9F49-61791CBD647B}.ClientEnd
Pnode
{EE82157A-8E48-4af6-9DC9-7A0098943EE0}.ClientEnd
RTO
{BA94D32D-6765-457a-9130-34C38FCE2CD6}.ClientEnd
A control area can receive dynamic schedules from other control areas
Receive_DynamicSchedules
{83DC5357-DC69-4c13-B260-5026E5DFD942}.ClientEnd
RegisteredResource
{8406940A-7751-48cd-BEC8-1C7154E28625}.ClientEnd
A control area can send dynamic schedules to other control areas
Send_DynamicSchedules
{CB9AAC47-376D-4a7e-9E56-D14A4F86E63E}.ClientEnd
The SubControlArea is on the A side of a collection of metered points which define the SubControlAreas boundary for a ControlAreaOperator or CustomerConsumer.
SideA_TieLines
{A0461DED-D054-4723-9A90-182B86F0177A}.ClientEnd
The SubControlArea is on the B side of a collection of metered points which define the SubControlAreas boundary for a ControlAreaOperator or CustomerConsumer.
SideB_TieLines
{3DBD1F56-AC7D-4daa-BEA3-1F36902AF8D6}.ClientEnd
To_Flowgate
{84D89B72-DEA9-4433-B8A9-4EEC604AA936}.ClientEnd
Used in conjunction with the InternalCA flag. If the InternalCA flag is YES this flag does not apply. If the InternaCA flag is NO this flag provides an indication of AdjacentCA NO or Embedded CA YES.
embeddedControlArea
{AE6DA985-8D93-461a-BA70-C1E1E7B240EC}
A YesNo indication that this control area is contained internal to the system.
internalCA
{C18E7C81-E2C6-44b2-BF64-3ED3C6803CC2}
Indication that this control area is the local control area.
localCA
{8827F780-172A-4aa8-8A9A-0FD8CB344649}
The DC lines in this subgeographical region.
DCLines
{87933AA2-5F6F-4768-BCDE-772A53C5248C}.ClientEnd
The lines within the subgeographical region.
Lines
{BAB73169-D3BE-43c3-A58B-F1B87EAA1239}.SupplierEnd
The geographical region which this subgeographical region is within.
Region
{023E20DF-DF02-4ffb-A047-E5BBDB18AB59}.ClientEnd
The substations in this subgeographical region.
Substations
{66E7D72B-2889-483c-80A2-2E51B283F2B1}.SupplierEnd
The LoadArea where the SubLoadArea belongs.
LoadArea
{985B4F6F-A487-4691-9470-6EE3C9636DC8}.ClientEnd
The Loadgroups in the SubLoadArea.
LoadGroups
{6910F2B1-E481-496a-91B7-7AAA14F6D47E}.SupplierEnd
Bays contained in the substation.
Bays
{51152F4A-1B03-451f-BA84-6A05A6AE1630}.ClientEnd
The primary feeder that normally energizes the secondary substation. Used for naming purposes. Either this association or the substation to subgeographical region should be used for hierarchical containment specification.
NamingFeeder
{D06442E1-D688-4393-8B71-E08E4CA4685F}.ClientEnd
The normal energized feeders of the substation. Also used for naming purposes.
NormalEnergizedFeeder
{D83ED2BA-7B91-4a91-81C0-A7CF3669C450}.ClientEnd
The feeders that potentially energize the downstream substation. Should be consistent with the associations that describe the naming hierarchy.
NormalEnergizingFeeder
{11C09449-0F39-4372-A153-258CD2A57196}.ClientEnd
The SubGeographicalRegion containing the substation.
Region
{66E7D72B-2889-483c-80A2-2E51B283F2B1}.ClientEnd
The voltage levels within this substation.
VoltageLevels
{0E9E9E28-C575-47c5-BF01-7F4EB8B36D16}.SupplierEnd
RegisteredResource
{8BD04841-261A-42f1-AF12-1F6BE08DB56A}.ClientEnd
TransmissionContractRight
{869976B9-DCEB-44ff-8BDB-956B7D44DFE7}.ClientEnd
Maximum continuous power frequency voltage allowed on the surge arrester.
continuousOperatingVoltage
{6CDB06F8-CA6A-4e35-A80A-FC270829F0B5}
Residual voltage during an 8x20 microsecond current impulse at the nominal discharge current level.
lightningImpulseDischargeVoltage
{8BDDADF7-055C-44a7-9962-CD64321A6839}
The lightning discharge current used to classify the arrester. Choices are limited to 1.5 2.5 5 10 and 20 kA by IEC 60099.
nominalDischargeCurrent
{5E1A8FC6-62BA-405e-BB8B-76F9DA205829}
Fault current level at which all parts of the failed arrester lie within a circle prescribed by IEC 60099.
pressureReliefClass
{3953FC64-1B9E-4db3-A163-338F0ECA9143}
The temporary overvoltage TOV level at power frequency that the surge arrester withstands for 10 seconds.
ratedVoltage
{5AEEF44D-CC1A-4514-A087-4E6350EB6ABF}
Residual voltage during a current impulse with front time of 1 microsecond and magnitude equal to the nominal discharge current level.
steepFrontDischargeVoltage
{FA9DB83F-62F9-452c-926D-6F473208F93A}
Residual voltage during a current impulse with front time of at least 30 microseconds and magnitude specified in IEC 60099 for the line discharge class. Does not apply to line discharge class 0.
switchingImpulseDischargeVoltage
{923A09AB-C1E2-4a71-AFB2-63E400F061DA}
multiplier
{E0742F08-9A12-471f-ABF4-DD7CC752C0C9}
unit
{5F029910-FE0C-4726-A5FD-9CBECFF40F29}
multiplier
{4E5C6626-C0DA-457e-9F3B-1CB0C6CFCCCE}
unit
{2F3A3342-2DA4-445c-A69F-E2F935C427FA}
The topological node associated with the flow injection state variable.
TopologicalNode
{65235B7E-6091-4035-BB6C-FD64EA32C24B}.SupplierEnd
The active power mismatch between calculated injection and initial injection. Positive sign means injection into the TopologicalNode bus.
pInjection
{B02C5723-912A-4bd8-BA35-6887EBD8AED0}
The terminal phase at which the connection is applied. If missing the injection is assumed to be balanced among nonneutral phases.
phase
{CD960FEC-49EB-489f-9CC2-069E98BF3109}
The reactive power mismatch between calculated injection and initial injection. Positive sign means injection into the TopologicalNode bus.
qInjection
{3E4BB80E-3418-47b4-AB66-36177D470417}
EnergyGroup
{9E145EE8-2544-4933-9DE4-FB008FF09419}.SupplierEnd
The terminal associated with the power flow state variable.
Terminal
{652607BF-3991-4400-89A1-D3208A9FB60D}.SupplierEnd
The active power flow. Load sign convention is used i.e. positive sign means flow out from a TopologicalNode bus into the conducting equipment.
p
{626A0C29-2FD5-41d3-ADD9-D11D922B2D72}
The individual phase of the flow. If unspecified then assumed to be balanced among phases.
phase
{3A0A5CD8-DB0E-41fc-860F-DC7769CB16F2}
The reactive power flow. Load sign convention is used i.e. positive sign means flow out from a TopologicalNode bus into the conducting equipment.
q
{B7D95D29-FFA8-4bd2-B8CF-621150B9A9CE}
The shunt compensator for which the state applies.
ShuntCompensator
{E34ED370-94B3-4e27-B2EC-76FFEED7FAF5}.SupplierEnd
The terminal phase at which the connection is applied. If missing the injection is assumed to be balanced among nonneutral phases.
phase
{5B5AF88F-78C1-4d6c-97D5-07760B029804}
The conducting equipment associated with the status state variable.
ConductingEquipment
{A1BADE18-494C-4d12-B7E2-2C9AF7F526ED}.SupplierEnd
The individual phase status. If the attribute is unspecified then three phase model is assumed.
phase
{0C299D0C-7EE7-4696-BFAE-7DD091F24B14}
The switch associated with the switch state.
Switch
{F56E3CEE-AA4F-4da4-B8AA-A646C6EC8FBD}.SupplierEnd
The terminal phase at which the connection is applied. If missing the injection is assumed to be balanced among nonneutral phases.
phase
{5501A636-5B85-4d71-8330-E9ED8F51CD46}
The tap changer associated with the tap step state.
TapChanger
{CAAE86A7-3A22-41ff-A8A4-68A4B4723DD2}.SupplierEnd
The topological node associated with the voltage state.
TopologicalNode
{4628B761-2D2E-4428-AB48-91ADDAB6ED29}.SupplierEnd
The voltage angle of the topological node complex voltage with respect to system reference.
angle
{1D320E89-265C-41ec-A654-A0FE668376BD}
If specified the voltage is the line to ground voltage of the individual phase. If unspecified then the voltage is assumed balanced.
phase
{49991EDC-1187-4282-8771-D71CBDDBE7C5}
The voltage magnitude at the topological node. The attribute shall be a positive value.
v
{B4D2EA92-2DE6-41bb-9362-77F68809B646}
Composite switch to which this Switch belongs.
CompositeSwitch
{E6CD744D-0D2A-4e23-9C5E-B2A3778D7618}.ClientEnd
ConnectDisconnectFunctions
{ABF72E73-E9B7-40a5-8FC4-D1B196EC3845}.ClientEnd
The switch state associated with the switch.
SvSwitch
{F56E3CEE-AA4F-4da4-B8AA-A646C6EC8FBD}.ClientEnd
Action changing status of this switch.
SwitchAction
{FE121092-F0C3-453d-81C5-4E473EC5F7A5}.ClientEnd
The individual switch phases for the switch.
SwitchPhase
{ECD7A6EB-ADCC-4463-898C-77400900FFDC}.SupplierEnd
A Switch can be associated with SwitchSchedules.
SwitchSchedules
{440A6BB4-CEFF-4c2b-8512-9008A52371C0}.SupplierEnd
UnavailabilitySwitchAction
{0C9534D4-CB50-4b67-88A1-762995554EA1}.ClientEnd
The maximum continuous current carrying capacity in amps governed by the device material and construction.The attribute shall be a positive value.
ratedCurrent
{486957C7-D5EF-499f-8CE3-7A2E88765D52}
Switch that is the object of this switch action.
OperatedSwitch
{FE121092-F0C3-453d-81C5-4E473EC5F7A5}.SupplierEnd
Planned outage for whose scope this switch action applies.
PlannedOutage
{7DAECB14-3133-4fec-91BB-CBC4E6C8147D}.ClientEnd
Switching action to perform.
kind
{CB209D30-15D7-4525-8F66-9B0E2CF7BCCF}
The maximum fault current a breaking device can break safely under prescribed conditions of use.
breakingCapacity
{D1E70A4D-6D44-451d-95BC-F4CBDA3BF165}
Weight of gas in each tank of SF6 dead tank breaker.
gasWeightPerTank
{FB310EDA-3064-4783-896C-ECE09394DE3F}
Gas or air pressure at or below which a low pressure alarm is generated.
lowPressureAlarm
{1F0BA60A-B64C-41c3-9B46-0B1D3C4B1F45}
Gas or air pressure below which the breaker will not open.
lowPressureLockOut
{4411A396-B4BE-4b4b-AB8A-DFB67AD2A3DD}
Volume of oil in each tank of bulk oil breaker.
oilVolumePerTank
{EF23AC03-FC2D-44db-862D-C7D913D369A6}
Rated current.
ratedCurrent
{4977C6DF-6942-44b1-9737-FFF45E46AF9E}
Frequency for which switch is rated.
ratedFrequency
{39398985-20DE-4183-9AC1-4613C7F54560}
Rated impulse withstand voltage also known as BIL Basic Impulse Level.
ratedImpulseWithstandVoltage
{9427D894-AA4D-4a9d-9F1F-9239B284E984}
Switch rated interrupting time in seconds.
ratedInterruptingTime
{30D9FDC7-4B28-4869-86C2-B9C405EBE65A}
Rated voltage.
ratedVoltage
{BBC6C1D2-BBBE-48a9-B7D8-CE65E2BD9970}
Breaker asset to which this operation information applies.
Breaker
{D39D36F1-D054-4dbc-8E93-564DC921D2DB}.SupplierEnd
The switch of the switch phase.
Switch
{ECD7A6EB-ADCC-4463-898C-77400900FFDC}.ClientEnd
Phase of this SwitchPhase on the side with terminal sequence number equal to 1. Should be a phase contained in that terminals phases attribute.
phaseSide1
{2DA4F4E9-B9A5-443a-9E85-E7AEAB2C7ACD}
Phase of this SwitchPhase on the side with terminal sequence number equal to 2. Should be a phase contained in that terminals Terminal.phases attribute.
phaseSide2
{BFC8496F-8B0D-4303-BD3E-4229B57A7D10}
The maximum continuous current carrying capacity in amps governed by the device material and construction.The attribute shall be a positive value.
ratedCurrent
{96858D1B-7CBC-4335-9D29-760A0394032C}
A SwitchSchedule is associated with a Switch.
Switch
{440A6BB4-CEFF-4c2b-8512-9008A52371C0}.ClientEnd
MktSwitch
{F865D7AC-3978-4a82-A41D-4131DB7D21B2}.SupplierEnd
Circuit Breaker Status closed or open of the circuit breaker from the power flow.
switchStatus
{C01AFC8E-EF1B-4657-8684-10E35AE10CA2}
Crew
{A7E0FAFD-8B4F-45b4-B614-D821AB007EF9}.SupplierEnd
Operator responsible for this switching step.
Operator
{4CE8C00C-90B0-4798-B63D-CD522B565717}.SupplierEnd
SwitchingEvent
{D6B0C16A-D051-4e89-A8B6-F922CDD37B8A}.SupplierEnd
SwitchingPlan
{342466CF-F77D-455b-AE6E-601403A7AC6D}.SupplierEnd
SwitchingStep
{AEB3B57B-446D-4886-89F5-9B26EA823237}.ClientEnd
Phases of the Switching Action
phases
{EF2EBC58-D3DB-4167-95C6-50D1F274E39B}
SwitchingAction
{D6B0C16A-D051-4e89-A8B6-F922CDD37B8A}.ClientEnd
Location
{4909DE0B-FF1E-4cd5-8339-71D4430BBEF1}.ClientEnd
SwitchingPlan
{997A942D-55D5-453f-8757-284E88136668}.SupplierEnd
The planned start and end time for the switching order.
plannedExecutionInterval
{94F12B92-AB9B-428e-9771-3064A2E98519}
Outage that will be activated or eliminated when this switching plan gets executed.
Outage
{D2D106C9-7B45-4172-8201-66E3FAC64E75}.SupplierEnd
The outage plan for which the switching plan is defined.
OutagePlan
{205E346A-7AC3-4f63-9926-D90B3687F39B}.SupplierEnd
PlannedOutageNotification
{D86059AA-B4DC-4561-AA64-9EF56A447F18}.ClientEnd
All safety documents applicable to this swtiching plan.
SafetyDocuments
{27C9D948-FDCD-4bb2-9FA5-B01A6569D284}.SupplierEnd
SwitchingAction
{342466CF-F77D-455b-AE6E-601403A7AC6D}.ClientEnd
SwitchingOrder
{997A942D-55D5-453f-8757-284E88136668}.ClientEnd
SwitchingPlanRequest
{648AFF78-8D22-4600-A50C-89FA5615F248}.ClientEnd
All groups of switching steps within this switching plan.
SwitchingStepGroups
{3BD787CE-70EE-4500-B66D-3B01AA018B58}.SupplierEnd
All work tasks to execute this switching plan.
WorkTasks
{1B1B92E7-633C-4e30-BCDE-9C62496BE1E8}.SupplierEnd
the planned start and end times for the switching plan.
plannedPeriod
{1F964C14-A51B-47aa-9AF9-8840741E6592}
RequestingOrganization
{9F41E5C9-778C-4e68-B6F3-EE634A0DD569}.SupplierEnd
SwitchingPlan
{648AFF78-8D22-4600-A50C-89FA5615F248}.SupplierEnd
forwardSwitchingDateTimeInterval
{6228BA53-09CE-41fd-9CB1-53406E58683A}
The window of time during which one or more customers will be deenergized during execution of the switching plan.
outageDateTimeInterval
{16EB8BE0-A988-4316-9CE8-FC73C73875CC}
reverseSwitchingDateTimeInterval
{A048C3B4-26CB-469e-B1C5-31C960EEA918}
SwitchingAction
{AEB3B57B-446D-4886-89F5-9B26EA823237}.SupplierEnd
SwitchingStepGroup
{9979325A-954B-4a3c-8836-B2C1A866D545}.SupplierEnd
Switching plan to which this group belongs.
SwitchingPlan
{3BD787CE-70EE-4500-B66D-3B01AA018B58}.ClientEnd
SwitchingStep
{9979325A-954B-4a3c-8836-B2C1A866D545}.ClientEnd
The maximum allowable voltage vector phase angle difference across the open device.
maxAngleDiff
{CF9BEE80-A0FD-4099-8E9B-74E0E1F23122}
The maximum allowable frequency difference across the open device.
maxFreqDiff
{79177A3F-6BA1-4c98-ACC8-D4E2859634A7}
The maximum allowable difference voltage across the open device.
maxVoltDiff
{C8AFFA34-11D5-4367-A006-E2A26954F064}
The default reactive capability curve for use by a synchronous machine.
InitialReactiveCapabilityCurve
{6BEDDBFC-3D03-47f1-A9B8-266425DE28E8}.ClientEnd
Prime movers that drive this SynchronousMachine.
PrimeMovers
{9C153102-5D80-4895-9BF2-7371CA48A80D}.ClientEnd
All available reactive capability curves for this synchronous machine.
ReactiveCapabilityCurves
{3724CB9D-F524-4771-91F7-6BDCEBD04E47}.ClientEnd
Synchronous machine dynamics model used to describe dynamic behaviour of this synchronous machine.
SynchronousMachineDynamics
{EAEF3FB4-D1E0-417a-9741-F25D491661F0}.ClientEnd
Time delay required when switching from Automatic Voltage Regulation AVR to Manual for a lagging MVAr violation.
aVRToManualLag
{8E8FAE0F-8AB3-461e-87AE-13D268F13340}
Time delay required when switching from Automatic Voltage Regulation AVR to Manual for a leading MVAr violation.
aVRToManualLead
{EC465023-F164-4b10-8FCB-FACEE28A4D66}
Default base reactive power value. This value represents the initial reactive power that can be used by any application function.
baseQ
{4257F82E-4A8B-4da5-968D-82DBD19AA3EA}
Active power consumed when in condenser mode operation.
condenserP
{0B22702D-FD5C-4b09-93A6-65E19B875E3D}
Method of cooling the machine.
coolantType
{C236899A-1671-494f-8F38-0B8F1F4FBFA3}
Generator star point earthing resistance Re. Used for short circuit data exchange according to IEC 60909.
earthingStarPointR
{91080667-F08F-4376-A5BB-2FF78C475574}
Generator star point earthing reactance Xe. Used for short circuit data exchange according to IEC 60909.
earthingStarPointX
{ED9C53CE-C21E-4d12-B219-BE9E666EF2AA}
Steadystate shortcircuit current in A for the profile of generator with compound excitation during 3phase short circuit. Ikk0 Generator with no compound excitation. Ikkltgt0 Generator with compound excitation.Ikk is used to calculate the minimum steadystate shortcircuit current for generators with compound excitation.4.6.1.2 in IEC 6090902001.Used only for single fed short circuit on a generator. 4.3.4.2. in IEC 6090902001.
ikk
{8A08EE9F-30F4-4ddd-9531-161EAB9B8F7E}
Time delay required when switching from Manual to Automatic Voltage Regulation. This value is used in the accelerating power reference frame for powerflow solutions.
manualToAVR
{70C785D8-FE57-4b1d-ABC1-6F6247089D83}
Maximum reactive power limit. This is the maximum nameplate limit for the unit.
maxQ
{0381E429-3037-4d2d-9AC8-CBED18D6B275}
Maximum voltage limit for the unit.
maxU
{3A71319C-C9FB-449d-AAB9-EAE1C75907FC}
Minimum reactive power limit for the unit.
minQ
{D2AAFB98-B566-478d-A769-6475747B2200}
Minimum voltage limit for the unit.
minU
{60A97F8C-C22B-4d32-8728-24E8EFC7C318}
Current mode of operation.
operatingMode
{AD303DEF-0BE9-4364-91F7-68A8CAA1C408}
Part of the coordinated reactive control that comes from this machine. The attribute is used as a participation factor not necessarily summing up to 100 for the participating devices in the control.
qPercent
{3CBD29B9-1D15-4816-8720-F72FF7CE0C5D}
Equivalent resistance RG of generator. RG is considered for the calculation of all currents except for the calculation of the peak current ip. Used for short circuit data exchange according to IEC 60909.
r
{F5F4EFCA-977E-4231-ACF7-CEDC8A85CD6F}
Zero sequence resistance of the synchronous machine.
r0
{3734B4AC-4BD3-4f19-A04C-3435D7EE6C14}
Negative sequence resistance.
r2
{3D5502B1-D49E-4c17-87D6-44C0850D2D41}
Directaxis subtransient reactance saturated also known as Xdsat.
satDirectSubtransX
{5155AE7B-4DBA-4521-B3B8-B3623D53AF96}
Directaxes saturated synchronous reactance xdsat reciprocal of shortcircuit ration. Used for short circuit data exchange only for single fed short circuit on a generator. 4.3.4.2. in IEC 6090902001.
satDirectSyncX
{FB6AA45C-2D6E-4ce4-92F0-5669E53A8EDF}
Saturated Directaxis transient reactance. The attribute is primarily used for short circuit calculations according to ANSI.
satDirectTransX
{B56C10AE-7F4B-4b90-BE6C-BC1D10973D6F}
Type of rotor used by short circuit applications only for single fed short circuit according to IEC 60909.
shortCircuitRotorType
{B1ED2B65-1FE5-47b0-B3A5-66BABE52A30E}
Modes that this synchronous machine can operate in.
type
{546739CC-1CB9-4986-A713-D882FF155AEA}
Range of generator voltage regulation PG in IEC 609090 used for calculation of the impedance correction factor KG defined in IEC 609090.This attribute is used to describe the operating voltage of the generating unit.
voltageRegulationRange
{EA18FF08-9F66-47bc-BF32-90256C925F9C}
Zero sequence reactance of the synchronous machine.
x0
{B18BF255-A3E4-4cba-B7D0-6E4F825191A9}
Negative sequence reactance.
x2
{BF860696-8442-4a51-A9C4-D369A3154954}
Excitation base system mode. It should be equal to the value of iWLMDVi given by the user. iWLMDVi is the PU ratio between the field voltage and the excitation current iEfdi iWLMDVi x iIfdi. Typical value ifag.
ifdBaseType
{56BE4D5E-9BF0-4130-98D0-08E12BD43448}
The crosscompound turbine governor with which this highpressure synchronous machine is associated.
CrossCompoundTurbineGovernorDyanmics
{4EEEDF69-9BB6-4d02-B662-A156239AF9B8}.ClientEnd
The crosscompound turbine governor with which this lowpressure synchronous machine is associated.
CrossCompoundTurbineGovernorDynamics
{9C225B93-4040-4753-80B9-1A3D0F2B6D81}.ClientEnd
Excitation system model associated with this synchronous machine model.
ExcitationSystemDynamics
{C7679E92-5BAF-4548-868A-CE939B02A5E8}.ClientEnd
Compensation of voltage compensators generator for current flow out of this generator.
GenICompensationForGenJ
{E86FBA0E-B146-4508-95E0-F005CB0E4DF5}.ClientEnd
Mechanical load model associated with this synchronous machine model.
MechanicalLoadDynamics
{2298CEEA-3BC8-4a46-9C31-9B6C0CDB1324}.ClientEnd
Synchronous machine to which synchronous machine dynamics model applies.
SynchronousMachine
{EAEF3FB4-D1E0-417a-9741-F25D491661F0}.SupplierEnd
Turbinegovernor model associated with this synchronous machine model. Multiplicity of greater than one is intended to support hydro units that have multiple turbines on one generator.
TurbineGovernorDynamics
{7E94D7D8-30B5-4d27-A321-7C51BCCE5C42}.SupplierEnd
Directaxis damper 1 winding resistance.
r1d
{9E798A67-DC42-425f-A10D-9610076DCF0F}
Quadratureaxis damper 1 winding resistance.
r1q
{F1213B97-B871-4549-BF5F-5F16B1B0D639}
Quadratureaxis damper 2 winding resistance.
r2q
{849F71C7-D146-45cb-A4BE-753B6726F94F}
Field winding resistance.
rfd
{1B9F3978-4D5C-4980-A1C3-C884DA4885A2}
Directaxis damper 1 winding leakage reactance.
x1d
{C4E53960-70A6-47e5-9311-176463359305}
Quadratureaxis damper 1 winding leakage reactance.
x1q
{CE53BB3B-68BC-4086-9F34-E4A21BF68277}
Quadratureaxis damper 2 winding leakage reactance.
x2q
{D3593FFF-9C2F-4247-84FB-6DAE7962B470}
Directaxis mutual reactance.
xad
{5051FDB0-1D4E-430b-BC09-503C3DA07790}
Quadratureaxis mutual reactance.
xaq
{DE956CD6-ADD5-46cd-9B1C-33B2398D501D}
Differential mutual Canay reactance.
xf1d
{50022E63-E39D-429b-AE4E-975F9006E67A}
Field winding leakage reactance.
xfd
{5AE2A85B-6BEB-47af-8821-E927CF95B709}
Type of synchronous machine model used in dynamic simulation applications.
modelType
{73D6CB74-566F-4841-8A9E-3BAD3C224435}
Type of rotor on physical machine.
rotorType
{231BC777-B2A8-4e3d-B83E-FF8C3710102E}
Damping time constant for Canay reactance gt 0. Typical value 0.
tc
{C1919777-31F2-4644-A6D1-28C6DAA9043C}
Directaxis transient rotor time constant iTdoi gt SynchronousMachineTimeConstantReactance.tppdo. Typical value 5.
tpdo
{8E796ADA-01A1-4ef9-8324-8039862B5514}
Directaxis subtransient rotor time constant iTdoi gt 0. Typical value 003.
tppdo
{BA422BE7-8810-45d5-BF06-7FFAE8DF6AB4}
Quadratureaxis subtransient rotor time constant iTqoi gt 0. Typical value 003.
tppqo
{44000A7F-C655-4c11-BAA8-0B20B5067545}
Quadratureaxis transient rotor time constant iTqoi gt SynchronousMachineTimeConstantReactance.tppqo. Typical value 05.
tpqo
{3CD276B4-CB60-4bdd-9B3E-830D1571FC0C}
Directaxis subtransient reactance unsaturated iXdi gt RotatingMachineDynamics.statorLeakageReactance. Typical value 02.
xDirectSubtrans
{C8601C6E-0A50-4b75-82E5-C945BF86BF82}
Directaxis synchronous reactance iXdi gt SynchronousMachineTimeConstantReactance.xDirectTrans. The quotient of a sustained value of that AC component of armature voltage that is produced by the total directaxis flux due to directaxis armature current and the value of the AC component of this current the machine running at rated speed. Typical value 18.
xDirectSync
{E5E769E3-B497-4bb4-9663-3EA4746454F0}
Directaxis transient reactance unsaturated iXdi gt SynchronousMachineTimeConstantReactance.xDirectSubtrans. Typical value 05.
xDirectTrans
{E3134A5A-B4EC-48e4-86E7-155A1C2AFC7E}
Quadratureaxis subtransient reactance iXqi gt RotatingMachineDynamics.statorLeakageReactance. Typical value 02.
xQuadSubtrans
{0E7D135F-5F3A-46c6-AE4C-B60EC7FBEA1E}
Quadratureaxis synchronous reactance iXqi gt SynchronousMachineTimeConstantReactance.xQuadTrans.The ratio of the component of reactive armature voltage due to the quadratureaxis component of armature current to this component of current under steady state conditions and at rated frequency. Typical value 16.
xQuadSync
{A305C84C-5B1A-4031-B732-D563DB6CF731}
Quadratureaxis transient reactance iXqi gt SynchronousMachineTimeConstantReactance.xQuadSubtrans. Typical value 03.
xQuadTrans
{0DD0CE8E-9CD0-41c7-AE60-A9BC031E2532}
Parameter of this proprietary userdefined model.
ProprietaryParameterDynamics
{996B609E-F446-4d2f-89B1-0A3771AD65C2}.ClientEnd
DistributionFactorSet
{5262F3D5-E6F1-466a-998C-AE0F2E35DBDF}.ClientEnd
HostControlArea
{451D980C-3785-4de0-AC06-5515EF2C589B}.ClientEnd
MktConnectivityNode
{C9774777-9F95-427f-B6A2-3AD33980CE68}.SupplierEnd
AggregatedPnode
{172CCB30-32D5-4d42-90DE-5FC85FCBF6C3}.ClientEnd
AreaLoadCurve
{825890F9-E350-40bd-AAE5-57E92CB28556}.SupplierEnd
Edition of TAPPI standard.
standardEdition
{FC3D0B9B-514A-49e1-A275-B5E4E57FC4FA}
TAPPI standard number.
standardNumber
{178BCCDB-B058-4f73-B130-5B5769DD3406}
Informational message to be included in a Bilateral Table agreement.
ICCPInformationMessage
{D286EEBB-4C7C-449f-8621-C35CE7904696}.ClientEnd
Is the Public Certificate used for mutual authentication between peers.
PublicX509Certificate
{D25EF464-773A-4ecc-AAF8-781EC96B694C}.ClientEnd
TransmissionContractRight
{646BBA57-9F62-43b1-9636-2CBBCFAC508B}.ClientEnd
Tag associated with this tag action.
OperationalTag
{987DD03E-CEAD-487e-B8AA-EDF24171399B}.SupplierEnd
Kind of tag action.
kind
{8ED3BAEC-B5E3-42ee-9454-4335FA916550}
A hydro generating unit has a tailbay loss curve.
HydroGeneratingUnit
{F9B9CD62-2EEB-4f1a-969B-6EE451A47D3F}.SupplierEnd
The tap step state associated with the tap changer.
SvTapStep
{CAAE86A7-3A22-41ff-A8A4-68A4B4723DD2}.ClientEnd
The regulating control scheme in which this tap changer participates.
TapChangerControl
{422A1828-CD78-4432-8BAE-244E4B58419D}.SupplierEnd
A TapChanger can have TapSchedules.
TapSchedules
{277E86F7-F72A-4768-9169-BE7D66F087B6}.ClientEnd
For an LTC the delay for initial tap changer operation first step change.
initialDelay
{0AA6B766-F046-494b-9390-05BD55E7879C}
Voltage at which the winding operates at the neutral tap setting. It is the voltage at the terminal of the PowerTransformerEnd associated with the tap changer when all tap changers on the transformer are at their neutralStep position. Normally neutralU of the tap changer is the same as ratedU of the PowerTransformerEnd but it can differ in special cases such as when the tapping mechanism is separate from the winding more common on lower voltage transformers.This attribute is not relevant for PhaseTapChangerAsymmetrical PhaseTapChangerSymmetrical and PhaseTapChangerLinear.
neutralU
{773D3CD1-ED8D-4b55-9D8B-93CFB1E9F5B3}
For an LTC the delay for subsequent tap changer operation second and later step changes.
subsequentDelay
{4F65DA6B-7334-4903-AA61-23253E9E5FE6}
The tap changers that participates in this regulating tap control scheme.
TapChanger
{422A1828-CD78-4432-8BAE-244E4B58419D}.ClientEnd
Maximum allowed regulated voltage on the PT secondary regardless of line drop compensation. Sometimes referred to as firsthouse protection.
limitVoltage
{261AF2D6-5458-4172-B562-A5B87EF2DE46}
Line drop compensator resistance setting for normal forward power flow.
lineDropR
{CD06DD47-4320-478a-8A92-D221920A8F11}
Line drop compensator reactance setting for normal forward power flow.
lineDropX
{8508D424-8BD1-4091-ACDB-421EBDE54070}
Line drop compensator resistance setting for reverse power flow.
reverseLineDropR
{7E55A13C-2039-4480-94D6-3D5349B78D50}
Line drop compensator reactance setting for reverse power flow.
reverseLineDropX
{26287D63-3073-4251-BB04-A62DA3D4D241}
MktTapChanger
{FD943330-575B-40e5-BD88-67AED345044F}.SupplierEnd
Basic Insulation Level BIL expressed as the impulse crest voltage of a nominal wave typically 1.2 X 50 microsecond. This is a measure of the ability of the insulation to withstand very high voltage surges.
bil
{07C90492-435C-4506-957B-77D770A68C06}
Builtin current transformer primary rating.
ctRating
{7D5BDC10-5874-459c-A4B0-ADEE6521C215}
Frequency at which the ratings apply.
frequency
{D58B8023-ABD8-428e-A20F-003A4E938A57}
Voltage at which the winding operates at the neutral tap setting.
neutralU
{96E8E752-183F-4c03-918E-07D614C09B53}
Rated apparent power.
ratedApparentPower
{499E7222-8003-4284-B65F-2BB2A1938EA7}
Rated current.
ratedCurrent
{786D4754-E158-43cb-A811-1E4F65A2AD49}
Rated voltage.
ratedVoltage
{63094176-6903-4c9e-A5A8-8F80346B7C45}
Phase shift per step position.
stepPhaseIncrement
{DBDEA3D1-F974-4cc5-8CA6-5AD750F4D9E3}
Tap step increment in per cent of rated voltage per step position.
stepVoltageIncrement
{6B881398-B17D-42e8-A4F8-18E054F82BF5}
The magnetizing branch susceptance deviation as a percentage of nominal value. The actual susceptance is calculated as followscalculated magnetizing susceptance bnominal 1 bfrom this class100. The bnominal is defined as the static magnetizing susceptance on the associated power transformer end or ends. This model assumes the star impedance pi model form.
b
{EA68668F-E3EE-4702-978C-26D6BCED0B86}
The magnetizing branch conductance deviation as a percentage of nominal value. The actual conductance is calculated as followscalculated magnetizing conductance gnominal 1 gfrom this class100. The gnominal is defined as the static magnetizing conductance on the associated power transformer end or ends. This model assumes the star impedance pi model form.
g
{F33BB85C-0624-4ff6-BA15-DBDA563BB4FB}
The resistance deviation as a percentage of nominal value. The actual reactance is calculated as followscalculated resistance rnominal 1 rfrom this class100. The rnominal is defined as the static resistance on the associated power transformer end or ends. This model assumes the star impedance pi model form.
r
{81B79598-EB65-43c7-A0E5-B982F1EDF158}
The series reactance deviation as a percentage of nominal value. The actual reactance is calculated as followscalculated reactance xnominal 1 xfrom this class100. The xnominal is defined as the static series reactance on the associated power transformer end or ends. This model assumes the star impedance pi model form.
x
{55B6B5C3-6A91-4136-936A-8AF71058D544}
A TapSchedule is associated with a TapChanger.
TapChanger
{277E86F7-F72A-4768-9169-BE7D66F087B6}.SupplierEnd
Percentage of the tape shield width that overlaps in each wrap typically 10 to 25.
tapeLap
{DA7ECDFF-E1EF-44c0-9DD2-A7EAF89A4681}
Thickness of the tape shield before wrapping.
tapeThickness
{B2318584-1C47-4dee-8AE7-E811DE174D87}
A reservoir may have a water level target schedule.
Reservoir
{B07A132F-C127-483d-A307-B2513535A40A}.SupplierEnd
High target level limit above which the reservoir operation will be penalized.
highLevelLimit
{107C6947-5FB4-499d-BC3D-B968E8D3A5CF}
Low target level limit below which the reservoir operation will be penalized.
lowLevelLimit
{2113498E-1110-4b1e-A32E-2243B5BFB42A}
All pricing structures using this tariff.
PricingStructures
{680631D0-BB57-456d-A598-1F9D4D60D510}.ClientEnd
All tariff profiles using this tariff.
TariffProfiles
{ACE9DED4-6714-43a2-B1E5-D6530EDBACDC}.SupplierEnd
All consumption tariff intervals used to define this tariff profile.
ConsumptionTariffIntervals
{7F5C8247-4764-43ce-8B24-F568152BB763}.SupplierEnd
All tariffs defined by this tariff profile.
Tariffs
{ACE9DED4-6714-43a2-B1E5-D6530EDBACDC}.ClientEnd
All time tariff intervals used to define this tariff profile.
TimeTariffIntervals
{75A8F24D-7EEA-437e-830C-234893BB85F2}.SupplierEnd
multiplier
{28CABC7C-75AF-4bd8-AD42-B3EE3582114F}
unit
{191926AD-DB8F-466a-94B7-D3BA4C4167F6}
The scaling of the operational limit in percent.
limitPercent
{1952BC3C-BA32-48d2-AFB3-CFAAB7AB11C1}
The temperature of the table point.
temperature
{C9440439-DED1-4c1e-B707-94FF631925B3}
AuxillaryData
{FBA403AA-DCD7-404a-9D19-752C36A45A12}.SupplierEnd
Card used to tender payment.
Card
{61A73D4C-E942-43c5-8D12-F351276DE012}.ClientEnd
Cheque used to tender payment.
Cheque
{96162BCD-6CF6-40e7-B42A-5D0EB89F2B16}.ClientEnd
Receipt that recorded this receiving of a payment in the form of tenders.
Receipt
{61AB1FC1-BB28-47a2-95E4-1FB09BBE1111}.SupplierEnd
Amount tendered by customer.
amount
{9C95CEAE-B189-4f6b-A800-24FF7042BDD7}
Difference between amount tendered by customer and the amount charged by point of sale.
change
{E3BE4E86-1F65-4d06-91DD-EFDC0EDE78C0}
Kind of tender from customer.
kind
{C955372D-A862-4ae2-97DC-C11D107DD503}
The auxiliary equipment connected to the terminal.
AuxiliaryEquipment
{43A2A194-FB7E-4b55-8C73-A2E6C7AA2BF4}.ClientEnd
The directed branch group terminals for which this terminal is monitored.
BranchGroupTerminal
{D1FC8C2B-42F2-4d32-95B9-1C5FE76F9BAD}.ClientEnd
Bushing
{1E353A86-0A4E-4184-8B22-CE084F0A6AA8}.ClientEnd
Circuit
{6876E705-D5F6-4c77-9072-D14AF881DA08}.ClientEnd
The conducting equipment of the terminal. Conducting equipment have terminals that may be connected to other conducting equipment terminals via connectivity nodes or topological nodes.
ConductingEquipment
{5FEF5186-7804-4dad-8E18-8C5DB7FCE6B2}.SupplierEnd
The connectivity node to which this terminal connects with zero impedance.
ConnectivityNode
{C7E01609-F4E6-4a6e-8ACF-BDD413E62DE3}.SupplierEnd
All converters DC sides linked to this point of common coupling terminal.
ConverterDCSides
{6880D3F9-475B-4887-8B4A-332FABFC8F47}.ClientEnd
The equipment faults at this terminal.
EquipmentFaults
{2CF11C93-156B-4725-864D-F54BFFEBEEB6}.ClientEnd
Mutual couplings associated with the branch as the first branch.
HasFirstMutualCoupling
{E0778435-CE76-4d56-9FCA-FF9F04ED4FCA}.ClientEnd
Mutual couplings with the branch associated as the first branch.
HasSecondMutualCoupling
{3849B779-18E4-46d5-B987-8359D8A98A12}.ClientEnd
The feeder that this terminal normally feeds. Only specified for the terminals at head of feeders.
NormalHeadFeeder
{C1A181B0-A25E-4eca-9A0E-394B6E20BB6C}.ClientEnd
PinTerminal
{70327476-E811-4a87-97E1-35C5519C96DC}.ClientEnd
The controls regulating this terminal.
RegulatingControl
{329F27E5-05A7-4f46-AD18-D92971CC1BF3}.SupplierEnd
Input signal coming from this terminal.
RemoteInputSignal
{7CA6A357-5876-45c2-9ED0-266641C5D519}.ClientEnd
The power flow state variable associated with the terminal.
SvPowerFlow
{652607BF-3991-4400-89A1-D3208A9FB60D}.ClientEnd
The control area tie flows to which this terminal associates.
TieFlow
{30EE4FA9-5A0A-4d1f-ADEC-2FAEA55B9F47}.ClientEnd
The topological node associated with the terminal. This can be used as an alternative to the connectivity node path to topological node thus making it unnecessary to model connectivity nodes in some cases. Note that the if connectivity nodes are in the model this association would probably not be used as an input specification.
TopologicalNode
{F490BFCA-36A8-4fe2-B28B-66466134B41E}.SupplierEnd
All transformer ends connected at this terminal.
TransformerEnd
{D79E7AD2-9F0B-42d7-8CB3-107B2534515E}.ClientEnd
Represents the normal network phasing condition. If the attribute is missing three phases ABC shall be assumed except for terminals of grounding classes specializations of EarthFaultCompensator GroundDisconnector GroundSwitch and Ground which will be assumed to be N. Therefore phase code ABCN is explicitly declared when needed e.g. for star point grounding equipment.The phase code on terminals connecting same ConnectivityNode or same TopologicalNode as well as for equipment between two terminals shall be consistent.
phases
{8C0E221E-4988-48bf-BFC3-F9FFD7E7E075}
MktTerminal
{B8192AA1-3321-4d5a-9823-446CC79C90D7}.SupplierEnd
An asset health analog related to this lab test standard.
AssetAnalog
{2E6CE9AA-C3EE-4729-8DE4-6CB4B1AC3E42}.ClientEnd
An asset health discrete related to this lab test standard.
AssetDiscrete
{7AF83EF1-4332-45fc-ADCA-D6AC1324070C}.ClientEnd
An asset health string related to this lab test standard.
AssetString
{12941279-B146-4307-A6F4-220520C33D5E}.ClientEnd
Identification of test method used if multiple methods specified by test standard.
testMethod
{CCF095C2-E957-493b-95E1-2DC1C067C6E4}
Which ASTM standard used to determine analog value result. Applies only if ASTM standard used.
testStandardASTM
{2DA20E52-0F06-4464-857F-286769BA95D6}
Which CIGRE standard used to determine analog value result. Applies only if CIGRE standard used.
testStandardCIGRE
{67CCFE80-A44F-4b79-BB61-DA6E0CBA92A6}
Which DIN standard used to determine analog value result. Applies only if DIN standard used.
testStandardDIN
{42389BCD-7E85-4859-96E8-8B60D089FCEE}
Which Doble standard used to determine analog value result. Applies only if Doble standard used.
testStandardDoble
{A082407F-DBA4-4150-81F5-A04247D81A94}
Which EPA standard used to determine analog value result. Applies only if EPA standard used.
testStandardEPA
{34CEA855-A9B8-4a0f-B8DF-A7413C49146F}
Which IEC standard used to determine analog value result. Applies only if IEC standard used.
testStandardIEC
{739D469C-9BCE-4150-91ED-DB84E0C935C3}
Which IEEE standard used to determine analog value result. Applies only if IEEE standard used.
testStandardIEEE
{0CFAE803-7015-456b-9C27-8CAB9FAFCBCD}
Which ISO standard used to determine analog value result. Applies only if ISO standard used.
testStandardISO
{3D9C3CAB-EE77-4ecf-96D7-4DF5F0EECFD8}
Which Laborelec standard used to determine analog value result. Applies only if Laborelec standard used.
testStandardLaborelec
{2B85C983-D5DF-4c0f-81AF-321B44325569}
Which TAPPI standard used to determine analog value result. Applies only if TAPPI standard used.
testStandardTAPPI
{1FB9DCBA-6B38-4652-958C-95EB5B7A54E6}
Which UK Ministry of Defence standard used to determine analog value result. Applies only if UK Ministry of Defence standard used.
testStandardUKMinistryOfDefence
{F1675D39-DE17-41af-9E1D-F115202C8004}
Which WEP standard used to determine analog value result. Applies only if WEP standard used.
testStandardWEP
{25666DF8-FF56-4b54-BFF0-8CC0551BA561}
Identification of variant of test method or standard if one is specified by the standard.
testVariant
{0F15BD3C-ED7D-4f6e-8EDA-DEAD81F2AB9B}
A thermal generating unit may be a member of a compressed air energy storage plant.
CAESPlant
{22CD9D0F-3294-4b03-B8CD-2834FB574022}.ClientEnd
A thermal generating unit may be a member of a cogeneration plant.
CogenerationPlant
{E1908858-346B-40b8-9CAB-D6DDC55C0455}.ClientEnd
A thermal generating unit may be a member of a combined cycle plant.
CombinedCyclePlant
{1A607D5D-0E44-490a-B14D-8A8B2A3D7057}.ClientEnd
A thermal generating unit may have one or more emission curves.
EmissionCurves
{754BD49F-EE90-408a-AEBF-B56AA6C8DA69}.ClientEnd
A thermal generating unit may have one or more emission allowance accounts.
EmmissionAccounts
{0EFC6C1E-3654-4ea3-8239-30E44E8AE7C6}.ClientEnd
A thermal generating unit may have one or more fossil fuels.
FossilFuels
{2839ECA7-4BCD-4b58-8243-16046DF6DFBA}.ClientEnd
A thermal generating unit may have one or more fuel allocation schedules.
FuelAllocationSchedules
{B6363E4A-4FC1-40b5-AE09-A51CCFB2B37E}.ClientEnd
A thermal generating unit may have a heat input curve.
HeatInputCurve
{0F7AF31F-7DEC-4822-9117-8C921A5EADD4}.ClientEnd
A thermal generating unit may have a heat rate curve.
HeatRateCurve
{E732F28C-0BF4-4edf-8CAB-14E807036F6F}.ClientEnd
A thermal generating unit may have an incremental heat rate curve.
IncrementalHeatRateCurve
{44777851-6FBC-4f50-AF92-1EA11CE04CA8}.ClientEnd
A thermal generating unit may have a shutdown curve.
ShutdownCurve
{4D553F1E-EFC5-42c1-92D6-0E421FE8975B}.ClientEnd
A thermal generating unit may have a startup model.
StartupModel
{99C4296C-33D5-4c79-A4FB-0A9EC0794967}.ClientEnd
Operating and maintenance cost for the thermal unit.
oMCost
{9E07717A-8138-4a67-B588-2648A3EDB6C8}
The terminal to which this tie flow belongs.
Terminal
{30EE4FA9-5A0A-4d1f-ADEC-2FAEA55B9F47}.SupplierEnd
A dynamic energy transaction can act as a pseudo tie line.
EnergyTransaction
{F598C617-D4AC-4af6-8714-13A45A6CFB71}.ClientEnd
A ControlAreaOperator has a collection of tie points that ring the ControlArea called a TieLine.
ParentOfA
{1FE3925A-54B7-4008-8CC6-93CD443CC3C0}.ClientEnd
A CustomerConsumer may ring its perimeter with metering which can create a unique SubControlArea at the collection of metering points called a TieLine.
ParentOfB
{BE10D423-5810-4e4c-A856-4B2A6F2C2D59}.ClientEnd
The SubControlArea is on the A side of a collection of metered points which define the SubControlAreas boundary for a ControlAreaOperator or CustomerConsumer.
SideA_SubControlArea
{A0461DED-D054-4723-9A90-182B86F0177A}.SupplierEnd
The SubControlArea is on the B side of a collection of metered points which define the SubControlAreas boundary for a ControlAreaOperator or CustomerConsumer.
SideB_SubControlArea
{3DBD1F56-AC7D-4daa-BEA3-1F36902AF8D6}.SupplierEnd
A measurement is made on the B side of a tie point
ByMktMeasurement
{405D53E3-14AD-4d07-9D1F-3F3285139237}.SupplierEnd
A measurement is made on the A side of a tie point
ForMktMeasurement
{BE3DB3DE-E7FF-4f27-8DC0-5606F98986E5}.SupplierEnd
The MW rating of the tie point.
tiePointMWRating
{0E359BD0-AB1C-4b90-9CD0-5B37239D59FF}
Time schedule owning this time point.
TimeSchedule
{625A1F67-1CDE-402f-98D9-030899992A1B}.ClientEnd
if intervalbased A point in time relative to scheduled start time in TimeSchedule.scheduleInterval.start.
relativeTimeInterval
{4CE7089B-723E-4f30-905D-7660B02A13BE}
Status of this time point.
status
{11905F1C-71EB-4b95-83FC-D104DEDB53B9}
Interval defining the window of time that this time point is valid for example seasonal only on weekends not on weekends only 800 am to 500 pm etc..
window
{8080DB7B-1AE8-4827-AC27-2F17BDCC4BF5}
Sequence of time points belonging to this time schedule.
TimePoints
{625A1F67-1CDE-402f-98D9-030899992A1B}.SupplierEnd
The offset from midnight i.e. 0 h 0 min 0 s for the periodic time points to begin. For example for an interval meter that is set up for five minute intervals recurrencePeriod3005 min setting offset1202 min would result in scheduled events to read the meter executing at 2 min 7 min 12 min 17 min 22 min 27 min 32 min 37 min 42 min 47 min 52 min and 57 min past each hour.
offset
{FE7D56EF-99D8-46f2-8229-2D9285D48E61}
Duration between time points from the beginning of one period to the beginning of the next period. Note that a device like a meter may have multiple interval periods e.g. 1 min 5 min 15 min 30 min or 60 min.
recurrencePeriod
{1108D50A-817E-402a-9227-1AF82F685CD4}
Schedule date and time interval.
scheduleInterval
{5A773436-47DB-4da3-8C1F-F6D8070A63C6}
AttributeInstanceComponent
{12A8F6B9-95CA-4bbd-9E17-5C2026B33D51}.ClientEnd
Auction
{5894E7F6-D7B8-4658-85C7-272AEC744D46}.ClientEnd
ConstraintDuration
{07DEE107-FB99-4586-A9B9-7F52BB893EAE}.ClientEnd
DateAndOrTime
{492E4897-E2BA-43e1-ABB0-94017A298B9D}.SupplierEnd
Domain
{35183B72-4EB4-4c7d-BDCB-158AC35D6ACC}.SupplierEnd
EnvironmentalMonitoringStation
{6E714075-8668-4e58-A652-65C0CBEF02BF}.SupplierEnd
FlowDirection
{090E7580-E214-4627-9E02-CE3051F6B408}.SupplierEnd
MarketDocument
{8685CC5C-5A4F-4b05-AC0B-AE70B37260A5}.SupplierEnd
MarketEvaluationPoint
{D819A727-1DB3-424c-9D73-1E1D3668972A}.SupplierEnd
MarketObjectStatus
{DFA9145B-F296-4711-93A0-08DAEC6641D6}.ClientEnd
MarketParticipant
{1ACE2F82-31E4-482b-B2EF-A568B3991A86}.SupplierEnd
MktPSRType
{CBE02ED5-1004-4fe7-8827-53E8B4BDDE03}.ClientEnd
Period
{2FF42F79-5F9B-4d18-9FE4-F2D14B85ADD8}.SupplierEnd
Point
{E778FB34-70AF-4315-A61A-98894C17384B}.ClientEnd
Price
{76FC513C-3CAE-45e6-9CD8-53B33147F936}.ClientEnd
Quantity
{B7D5F09D-C0DE-43ce-8CC2-0D383279A6BC}.ClientEnd
Reason
{F3011AEA-011F-4ef6-A0F7-5ED118EF2480}.SupplierEnd
RegisteredResource
{DF9EE60B-C140-4257-AED0-716349B4B59B}.ClientEnd
Unit
{2CD55C37-FF3C-4881-B74E-437DAEAFB82E}.ClientEnd
All charges used to define this time tariff interval.
Charges
{0A0C819B-B021-48a1-BE23-8DEE728FFA6C}.SupplierEnd
All consumption tariff intervals that introduce variation in this time of use tariff interval allows to express e.g. peak hour prices that are different with different consumption blocks.
ConsumptionTariffIntervals
{8AA39685-1453-4631-B85A-DA04510557D0}.ClientEnd
All tariff profiles defined by this time tariff interval.
TariffProfiles
{75A8F24D-7EEA-437e-830C-234893BB85F2}.ClientEnd
The angle reference for the island. Normally there is one TopologicalNode that is selected as the angle reference for each island. Other reference schemes exist so the association is typically optional.
AngleRefTopologicalNode
{7537BE85-0F89-40e3-89A0-C8C7F534F430}.SupplierEnd
A topological node belongs to a topological island.
TopologicalNodes
{C890568A-2C06-4a80-B381-F84EBB81CE0A}.ClientEnd
The island for which the node is an angle reference. Normally there is one angle reference node for each island.
AngleRefTopologicalIsland
{7537BE85-0F89-40e3-89A0-C8C7F534F430}.ClientEnd
The base voltage of the topological node.
BaseVoltage
{6F37A2BE-FB37-4a6c-8BB1-CFC6690C1867}.SupplierEnd
BusnameMarkers that may refer to a pre defined TopologicalNode.
BusNameMarker
{33820695-1C8F-47c2-96B4-E770AF9728EF}.ClientEnd
The connectivity node container to which the topological node belongs.
ConnectivityNodeContainer
{88BD0C47-4CB3-44db-9A6B-20C783A24478}.SupplierEnd
The connectivity nodes combine together to form this topological node. May depend on the current state of switches in the network.
ConnectivityNodes
{ACD76E10-125A-4f7a-A20A-475AC4334414}.ClientEnd
The reporting group to which the topological node belongs.
ReportingGroup
{1134BB7B-6737-4184-A156-3E1FE506083D}.SupplierEnd
The injection flows state variables associated with the topological node.
SvInjection
{65235B7E-6091-4035-BB6C-FD64EA32C24B}.ClientEnd
The state voltage associated with the topological node.
SvVoltage
{4628B761-2D2E-4428-AB48-91ADDAB6ED29}.ClientEnd
The terminals associated with the topological node. This can be used as an alternative to the connectivity node path to terminal thus making it unnecessary to model connectivity nodes in some cases. Note that if connectivity nodes are in the model this association would probably not be used as an input specification.
Terminal
{F490BFCA-36A8-4fe2-B28B-66466134B41E}.ClientEnd
A topological node belongs to a topological island.
TopologicalIsland
{C890568A-2C06-4a80-B381-F84EBB81CE0A}.SupplierEnd
The active power injected into the bus at this location in addition to injections from equipment. Positive sign means injection into the TopologicalNode bus.Starting value for a steady state solution.
pInjection
{2C6F17C9-E8CD-4fdb-8029-A612C4EF7C6D}
The reactive power injected into the bus at this location in addition to injections from equipment. Positive sign means injection into the TopologicalNode bus.Starting value for a steady state solution.
qInjection
{1F312481-3DC3-4029-8B50-C8BA23CE0972}
Fujita scale referred to as EFscale starting in 2007 for the tornado.
fScale
{00289016-4A09-43be-AE71-4E4802CE7959}
Width of the tornado during the time interval.
width
{F2E6BD32-E569-48bd-ADB4-4C5C7F51B2AF}
Construction structure on the tower.
constructionKind
{2697D3C3-0A65-4816-BA14-4BCEA757E1A0}
ActionRequest
{54A2C406-8667-40cf-88A9-3A48629020FE}.ClientEnd
From_SC
{6D895553-2440-4f7c-BC33-B46D1B29C9D3}.ClientEnd
Pnode
{D878BD22-6A72-4e0c-8DFA-7844C9BCA884}.ClientEnd
RegisteredGenerator
{039D769F-A03A-444a-8786-96815FE89B99}.ClientEnd
To_SC
{7714A894-C9FB-420d-B21E-799E489A3AC8}.ClientEnd
TradeError
{C4DD2011-EF22-4fc2-A435-9C9F02E742A6}.SupplierEnd
TradeProduct
{9C3C0AFA-2A91-406d-9B41-CCF03BAA1C90}.ClientEnd
marketType
{4684F3F1-E6F3-4981-904D-7FB77AFA4A5C}
submitFromSchedulingCoordinator
{5BFC46E8-DD4B-4516-8376-1EFDF9C076C7}.ClientEnd
submitToSchedulingCoordinator
{AC7FD549-FA5C-45d6-B2D9-4609F963A05C}.ClientEnd
Trade
{C4DD2011-EF22-4fc2-A435-9C9F02E742A6}.ClientEnd
Trade
{9C3C0AFA-2A91-406d-9B41-CCF03BAA1C90}.SupplierEnd
IST InterSC Trade AST Ancilliary Services Trade UCT Unit Commitment Trade
tradeType
{59B065E2-D032-42db-823F-C81F0D0389F9}
TradingHubValues
{E2DFBA75-A026-4167-A09D-D673685B25A5}.SupplierEnd
marketType
{8F4686A6-0AF0-4ae4-830C-8ECA95AC626F}
AggregatedPnode
{28734C41-4653-42fe-A8E1-178A7444F6EC}.SupplierEnd
TradingHubPrice
{E2DFBA75-A026-4167-A09D-D673685B25A5}.ClientEnd
Auxiliary account for this payment transaction.
AuxiliaryAccount
{DF6F03CB-FADB-4f4b-BE70-872C51D6376A}.ClientEnd
Cashier shift during which this transaction was recorded.
CashierShift
{2D10DF39-BE65-4644-A37D-1155967E0230}.ClientEnd
Customer account for this payment transaction.
CustomerAccount
{0B5E9E95-37C0-4b1a-8C38-C1995B9D1EC8}.ClientEnd
Meter for this vending transaction.
Meter
{95682AE1-DDB3-4fa2-AC18-655296065A72}.SupplierEnd
Pricing structure applicable for this transaction.
PricingStructure
{25EA2CE6-048D-4220-8F20-CA27D99F9BAE}.ClientEnd
The receipted payment for which this transaction has been recorded.
Receipt
{436A1D66-C447-4f0e-84DE-DEE861AA01CD}.ClientEnd
All snapshots of meter parameters recorded at the time of this transaction. Use name and value.value attributes to specify name and value of a parameter from meter.
UserAttributes
{2749DDBF-3B2B-40e4-AF4B-40B8874DF1F9}.ClientEnd
Vendor shift during which this transaction was recorded.
VendorShift
{C7BF480F-86A2-4fe5-BB3D-D4EA91B0C386}.ClientEnd
Kind of transaction.
kind
{65B0E136-6632-46ff-ADF7-8701F09AFE7F}
Transaction amount rounding date and note for this transaction line.
line
{6926B3B1-11AF-49c2-B386-83FCFE189E71}
Actual amount of service units that is being paid for.
serviceUnitsEnergy
{0B863D4C-B4D0-4eeb-8165-B9469112080E}
Number of service units not reflected in serviceUnitsEnergy due to process rounding or truncating errors.
serviceUnitsError
{9BB33DE3-8DA4-429c-8120-ACBF3C4C9EA2}
Delivery_Pnode
{34A3B7CA-5000-4f2c-85C0-4A822CE31BA9}.ClientEnd
EnergyProfiles
{E51D8A6A-35CA-4b26-B4D3-9E33C8AF5D95}.ClientEnd
Receipt_Pnode
{ACB6DCFB-9B97-4ab9-AE5A-A643C314A45D}.ClientEnd
TransactionBidResults
{2D2D0010-F20C-446b-A623-73D0BD29F617}.ClientEnd
TransmissionReservation
{B39F413C-7625-4635-8150-E32231965E94}.ClientEnd
TransactionBidResults
{CA24857F-3571-4389-90DB-F93AF9F4E45C}.ClientEnd
TransactionBid
{2D2D0010-F20C-446b-A623-73D0BD29F617}.SupplierEnd
TransactionBidClearing
{CA24857F-3571-4389-90DB-F93AF9F4E45C}.SupplierEnd
All merchant accounts registered with this transactor.
MerchantAccounts
{4E9EC9E2-B298-41e8-9F52-493E9BBBDAC4}.ClientEnd
HostControlArea
{916AF086-1537-4361-A735-CFC6D28337F9}.ClientEnd
TransferInterfaceSolution
{B93FC9AB-985E-49f5-80B0-93755B80C82B}.ClientEnd
MktContingencyA
{C3F0F2CA-4331-417e-BB6F-AC8830FC9ABF}.SupplierEnd
MktContingencyB
{A997CE1E-D37D-451f-AAE5-0DEBC8D07E52}.SupplierEnd
TransferInterface
{B93FC9AB-985E-49f5-80B0-93755B80C82B}.SupplierEnd
All transformer ends having this core admittance.
TransformerEnd
{DE4C9D0B-23BA-4ce9-83D1-BF12F521B593}.SupplierEnd
Transformer end datasheet used to calculate this core admittance.
TransformerEndInfo
{B327563C-A528-49f8-827D-F19F78BD5C59}.ClientEnd
Magnetizing branch susceptance B mag. The value can be positive or negative.
b
{928EB30C-C38B-45ed-BECF-DE3FCC6C9308}
Zero sequence magnetizing branch susceptance.
b0
{AFD9DEEF-8A95-4753-9A43-0F26BF54DE65}
Magnetizing branch conductance G mag.
g
{EAEA9448-77A7-4e23-9496-89BE1A58E225}
Zero sequence magnetizing branch conductance.
g0
{9DE460B2-6CED-4c6f-A389-E54FA2BE13C9}
Base voltage of the transformer end. This is essential for PU calculation.
BaseVoltage
{DEF1E6AE-B7B9-43bf-9A91-E4BFC453DC4D}.SupplierEnd
Core admittance of this transformer end representing magnetising current and core losses. The full values of the transformer should be supplied for one transformer end only.
CoreAdmittance
{DE4C9D0B-23BA-4ce9-83D1-BF12F521B593}.ClientEnd
All mesh impedances between this to and other from transformer ends.
FromMeshImpedance
{0C083589-3190-4ac0-ACA6-6C089CF712A1}.ClientEnd
FromWindingInsulations
{85692DA6-1368-431a-B29A-40C8C1AD42B8}.ClientEnd
Phase tap changer associated with this transformer end.
PhaseTapChanger
{1CC9941E-7C40-434a-98D6-B767348B392C}.SupplierEnd
Ratio tap changer associated with this transformer end.
RatioTapChanger
{D8F7848F-543A-4d91-BA97-2A9B3FCFF0C6}.SupplierEnd
accurate for 2 or 3winding transformers only Pimodel impedances of this transformer end. By convention for a two winding transformer the full values of the transformer should be entered on the high voltage end endNumber1.
StarImpedance
{5078C60A-39BE-4141-9354-41C6894404A6}.SupplierEnd
Terminal of the power transformer to which this transformer end belongs.
Terminal
{D79E7AD2-9F0B-42d7-8CB3-107B2534515E}.SupplierEnd
All mesh impedances between this from and other to transformer ends.
ToMeshImpedance
{E43C771D-3409-4e2c-B0A8-D0643B55F7A5}.ClientEnd
ToWindingInsulations
{F014FE41-F5D2-4748-870B-0A78530405BD}.ClientEnd
Core shunt magnetizing susceptance in the saturation region.
bmagSat
{4950386F-0EBF-4612-B5A1-D6E0BA9ED7E0}
The reference voltage at which the magnetizing saturation measurements were made.
magBaseU
{57D6ABA6-A7AD-4761-A186-972500D1F6E5}
Core magnetizing saturation curve knee flux level.
magSatFlux
{803C147E-320E-4c05-8C2E-1F4CB27D5217}
for Yn and Zn connections Resistance part of neutral impedance where grounded is true.
rground
{EE05F10D-59F9-4a26-84CF-01E7909E179B}
for Yn and Zn connections Reactive part of neutral impedance where grounded is true.
xground
{50CE0265-4A20-4352-B5D6-FCFECC48E995}
Core admittance calculated from this transformer end datasheet representing magnetising current and core losses. The full values of the transformer should be supplied for one transformer end info only.
CoreAdmittance
{B327563C-A528-49f8-827D-F19F78BD5C59}.SupplierEnd
All noload test measurements in which this transformer end was energised.
EnergisedEndNoLoadTests
{F3E7A0B0-A48C-4358-8A44-11C4C94ABFB4}.ClientEnd
All opencircuit test measurements in which this transformer end was excited.
EnergisedEndOpenCircuitTests
{71BB3848-4B63-4fd1-9254-66CEBBF18C94}.ClientEnd
All shortcircuit test measurements in which this transformer end was energised.
EnergisedEndShortCircuitTests
{2E74ED8F-7D38-402e-861A-F390B8A642DD}.ClientEnd
All mesh impedances between this to and other from transformer ends.
FromMeshImpedances
{9F2DA196-8DEB-4c6c-B505-2954675E7A50}.SupplierEnd
All shortcircuit test measurements in which this transformer end was shortcircuited.
GroundedEndShortCircuitTests
{B6AF9146-CA85-4239-9212-97F858E8662C}.ClientEnd
All opencircuit test measurements in which this transformer end was not excited.
OpenEndOpenCircuitTests
{AC00E333-4A04-486e-AA1A-D3D83FB22682}.ClientEnd
All mesh impedances between this from and other to transformer ends.
ToMeshImpedances
{3EAF2DD7-ACE0-4031-970E-D1D4B25FBAEA}.SupplierEnd
Transformer star impedance calculated from this transformer end datasheet.
TransformerStarImpedance
{6B73B4A4-6B37-4a21-88C2-6A840F845023}.SupplierEnd
Transformer tank data that this end description is part of.
TransformerTankInfo
{6324A313-0688-4347-972B-AB0ED0E65531}.ClientEnd
Kind of connection.
connectionKind
{FAC8E176-2837-4a78-80FE-938B199A7579}
Apparent power that the winding can carry under emergency conditions also called longterm emergency power.
emergencyS
{44FBD108-12C1-434b-88BD-A508AE03F156}
Basic insulation level voltage rating.
insulationU
{30C7D2E4-5F41-4a18-A5A0-5B01DC907E85}
DC resistance.
r
{B185B333-46D3-4a80-8449-F5BAAFB5B275}
Normal apparent power rating.
ratedS
{9F419B0D-B321-4881-947A-129B555A0F08}
Rated voltage phasephase for threephase windings and either phasephase or phaseneutral for singlephase windings.
ratedU
{DB2C5D96-5C2F-49ed-B129-F0647D5800BD}
Apparent power that this winding can carry for a short period of time in emergency.
shortTermS
{734AED57-B659-47f4-A0F1-AFD48B66E8EE}
From end this mesh impedance is connected to. It determines the voltage reference.
FromTransformerEnd
{0C083589-3190-4ac0-ACA6-6C089CF712A1}.SupplierEnd
from transformer end datasheet this mesh impedance is calculated from. It determines the voltage reference.
FromTransformerEndInfo
{9F2DA196-8DEB-4c6c-B505-2954675E7A50}.ClientEnd
All transformer ends this mesh impedance is connected to.
ToTransformerEnd
{E43C771D-3409-4e2c-B0A8-D0643B55F7A5}.SupplierEnd
All to transformer end datasheets this mesh impedance for from transformer end is calculated from.
ToTransformerEndInfos
{3EAF2DD7-ACE0-4031-970E-D1D4B25FBAEA}.ClientEnd
Resistance between the from and the to end seen from the from end.
r
{21BB6532-5B66-45eb-8BD7-0DA588282A4A}
Zerosequence resistance between the from and the to end seen from the from end.
r0
{366E684D-52D4-41c2-B293-CC65EA5FBC28}
Reactance between the from and the to end seen from the from end.
x
{1EFF11FE-5520-4c57-90FB-E0EECA189682}
Zerosequence reactance between the from and the to end seen from the from end.
x0
{9444EE0F-D215-47d2-A536-7DADD5FA2D62}
BushingInsultationPFs
{DE9B5DD5-948F-45ee-967F-41C9BA2892AE}.ClientEnd
ProcedureDataSets
{8D7EAE31-2FA3-4a2f-84AC-416327FD5679}.ClientEnd
Reconditioning
{8A289EE0-AF52-4d3d-B1DF-2BF047C45F44}.ClientEnd
Transformer
{472A2705-2D9A-4589-BBE2-8A3AC63A9DE5}.SupplierEnd
WindingInsulationPFs
{97F8FF5D-183D-4b1c-B364-25B5C98E0F5F}.SupplierEnd
Bushing temperature.
bushingTemp
{FE4BCB99-058A-4eac-8129-0A2CFDB02501}
Hotspot oil temperature.
hotSpotTemp
{F83771D3-9987-4930-B423-5ED74B4A649C}
Oil Quality AnalysisDielectric Strength.
oilDielectricStrength
{D69A827D-834A-49e8-B6D9-C927574C6BC9}
status
{6ADE4A75-BDDB-482b-B53B-A179805B1C1F}
Top oil temperature.
topOilTemp
{25E30821-C0D4-4500-911C-0A5D9AE66DEC}
All transformer ends having this star impedance.
TransformerEnd
{5078C60A-39BE-4141-9354-41C6894404A6}.ClientEnd
Transformer end datasheet used to calculate this transformer star impedance.
TransformerEndInfo
{6B73B4A4-6B37-4a21-88C2-6A840F845023}.ClientEnd
Resistance of the transformer end.
r
{5B9D7450-DA41-4af2-BFC7-25FD2258A98C}
Zero sequence series resistance of the transformer end.
r0
{E99F040E-F78C-4483-913E-8C4A35E9A91D}
Positive sequence series reactance of the transformer end.
x
{DF5DFD38-6773-4727-8D72-5B6C82EB0ECB}
Zero sequence series reactance of the transformer end.
x0
{2B4BC0D1-E16A-40c5-8678-D2FBC1A38DD6}
Bank this transformer belongs to.
PowerTransformer
{732D3510-8B59-4b75-8EBD-5E7EFC0BD19D}.SupplierEnd
TransformerObservations
{472A2705-2D9A-4589-BBE2-8A3AC63A9DE5}.ClientEnd
All windings of this transformer.
TransformerTankEnds
{BD3E9F56-CE54-46c2-AD6E-0BF1AF5013B8}.ClientEnd
Transformer this winding belongs to.
TransformerTank
{BD3E9F56-CE54-46c2-AD6E-0BF1AF5013B8}.SupplierEnd
Describes the phases carried by a conducting equipment.
phases
{ECEAD537-8731-44da-A641-EDEF7450C23A}
Power transformer data that this tank description is part of.
PowerTransformerInfo
{C20239B0-27AB-4040-9B55-35834EB98EDC}.SupplierEnd
Data for all the ends described by this transformer tank data.
TransformerEndInfos
{6324A313-0688-4347-972B-AB0ED0E65531}.SupplierEnd
Base power at which the tests are conducted usually equal to the rateds of one of the involved transformer ends.
basePower
{056471A6-B8A8-433c-9FB2-095E6C4C2F8E}
Temperature at which the test is conducted.
temperature
{88CF359F-297E-409b-864E-7DBEFBC169B4}
Flowgate
{8921D733-BE8B-4a9f-BB12-03E6AB71B1AB}.ClientEnd
GenericConstraints
{384C3E51-C664-4bf5-A75C-E0697CE38B7D}.ClientEnd
A TransmissionPath is contained in a TransmissionCorridor.
ContainedIn
{BBFEDE77-77EC-472b-8A6E-AAE200EDE3DB}.ClientEnd
A transmission rightofway is a member of a transmission corridor
TransmissionRightOfWays
{4FBC14D9-C78F-424f-A518-E6A6E2D5C45F}.SupplierEnd
ContractRight
{BD4EDF28-A98E-4529-8A20-3113450CEBF4}.SupplierEnd
Flowgate
{4577596A-E96F-49da-9220-E1987860787A}.ClientEnd
A transmission path has a pointofdelivery service point
DeliveryPoint
{21CB6E87-75AD-4919-B4ED-4192EC9CC857}.ClientEnd
A TransmissionPath is contained in a TransmissionCorridor.
For
{BBFEDE77-77EC-472b-8A6E-AAE200EDE3DB}.SupplierEnd
A transmission product is located on a transmission path.
LocatedOn
{809F7661-A156-4e85-AE91-4F035C749051}.ClientEnd
A transmission path has a pointofreceipt service point
PointOfReceipt
{94CD1232-0212-4261-9FE4-36493F16F0E4}.ClientEnd
TransmissionReservation
{FF809EA0-FAD0-4d14-B083-AD186EADB2CF}.SupplierEnd
The available transmission capability of a transmission path for the reference direction.
availTransferCapability
{435EE2C8-310E-45fb-93AA-5787EC45EB5B}
The total transmission capability of a transmission path in the reference direction.
totalTransferCapability
{EC8178AE-269B-4126-AE61-3F5A0768194E}
A transmission product is located on a transmission path.
LocationFor
{809F7661-A156-4e85-AE91-4F035C749051}.SupplierEnd
A TransmissionProvider offers a TransmissionProduct.
TransmissionProvider
{EC0C3662-DB09-4af3-BA2A-86166CE1C300}.SupplierEnd
Part of the LossProfile for an EnergyTransaction may be a loss for a TransmissionProvider. If so the TransmissionProvider must be one of the participating entities in the EnergyTransaction.
For
{A0E07F75-BF34-4a53-91DA-8AC7F9199E13}.ClientEnd
A TransmissionProvider offers a TransmissionProduct.
TransmissionProducts
{EC0C3662-DB09-4af3-BA2A-86166CE1C300}.ClientEnd
EnergyTransaction
{AC1E24EF-9143-4c28-B275-913E3666B245}.SupplierEnd
Sink
{64CB9D37-23DD-46f9-A4A8-47CF257C8105}.ClientEnd
Source
{E205C545-1AF7-4249-9970-5E34913BCC3E}.ClientEnd
TransactionBid
{B39F413C-7625-4635-8150-E32231965E94}.SupplierEnd
TransmissionPath
{FF809EA0-FAD0-4d14-B083-AD186EADB2CF}.ClientEnd
Chain_ContractRight
{1D17EEA8-4DC7-4648-B0A4-3D0516BC89C2}.SupplierEnd
Ind_ContractRight
{2A59E041-E065-428d-9918-A42D868C16C6}.SupplierEnd
RTO
{1E012DD2-B528-4079-B377-8386C7DB1523}.ClientEnd
MktLine
{30BB45B0-2DB4-4d68-BC65-DFE2DF74D8D1}.ClientEnd
A transmission rightofway is a member of a transmission corridor
TransmissionCorridor
{4FBC14D9-C78F-424f-A518-E6A6E2D5C45F}.ClientEnd
The resulting Gate that is the condition for the Trigger.
GateTrigger
{1E9CF642-F79D-453e-840A-CCAA1AB4A74D}.SupplierEnd
RemedialActionScheme
{2D5E06E1-6BCA-41a9-9B81-E5FFA56FE6AC}.SupplierEnd
Incident
{3D79F2D5-BE8F-4d59-A6FE-14060E81D5FA}.SupplierEnd
Location
{2BE0988C-AEEE-43e6-9FB2-B3C811465CE1}.SupplierEnd
TroubleTicket
{42D4F687-C45E-4afb-8E19-6BD1A3F5E209}.SupplierEnd
UnplannedOutage
{D36FE243-EBDF-427d-841A-BF9DD24E97E4}.ClientEnd
WorkTask
{0C2AE19D-0F46-483f-BA2C-8AFA95A466F6}.ClientEnd
The planned start and end time for the trouble order.
plannedExecutionInterval
{4B5AA04E-6220-4276-BCCB-C781325E39DA}
Customer for whom this trouble ticket is relevant.
Customer
{DB18A09B-52CE-46d9-98B1-DA9F32529CC5}.SupplierEnd
Incident reported in this trouble ticket
Incident
{604AF98C-C65C-46ec-828D-96FE5F906C35}.SupplierEnd
All hazards reported with this trouble ticket.
IncidentHazard
{F1DCAE08-2CD6-4c12-9B22-D06B9E9DAA02}.SupplierEnd
Notification for this trouble ticket.
Notification
{2E2B0349-61DB-4eeb-9A2F-465DC303A460}.ClientEnd
ServiceLocation
{61FDCE34-6ACD-4edb-A961-05C33EC48E86}.ClientEnd
TroubleOrder
{42D4F687-C45E-4afb-8E19-6BD1A3F5E209}.ClientEnd
UnplannedOutage
{76C1C366-6D04-44f8-B3FA-BD123E9196FD}.ClientEnd
Indicates how the customer reported trouble.
reportingKind
{1F8F0207-79BC-48ab-BF72-DE1D9CFDB9F2}
Controller deadband idbi. Typical value 0.
db
{E218CC9F-E5CC-4c05-872F-508374139965}
Maximum control error iEmaxi see parameter detail 4. Typical value 002.
emax
{5293C632-28A0-45d4-9820-4AF63CE2AFC8}
Frequency bias gain iFbi. Typical value 0.
fb
{318CC923-F6AF-4ccc-B364-CF85DE83A1D3}
Maximum turbine speedload reference bias iIrmaxi see parameter detail 3. Typical value 0.
irmax
{594A2700-90F0-4ca2-9FB3-0FAD84B96E2C}
Integral gain iKii. Typical value 0.
ki
{5AA55CDC-9469-4f03-B327-AE36DD877738}
Proportional gain iKpi. Typical value 0.
kp
{85A716AE-3B40-4bdb-A829-B53CDDDC52E0}
Base for power values iMWbasei gt 0. Unit MW.
mwbase
{5DEE3DCC-9C0F-4a44-B20A-A41F1BFA6213}
Power controller setpoint iPmwseti see parameter detail 1. Unit MW. Typical value 0.
pmwset
{80B91A23-4C94-420f-A5B3-38783A465994}
Power transducer time constant iTpeleci gt 0. Typical value 0.
tpelec
{D74FEDF5-5775-47aa-B051-49EF1F447195}
Asynchronous machine model with which this turbinegovernor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics.
AsynchronousMachineDynamics
{6884320E-0E98-4316-859C-B1DF18D6ED2A}.SupplierEnd
Synchronous machine model with which this turbinegovernor model is associated. TurbineGovernorDynamics shall have either an association to SynchronousMachineDynamics or to AsynchronousMachineDynamics.
SynchronousMachineDynamics
{7E94D7D8-30B5-4d27-A321-7C51BCCE5C42}.ClientEnd
Turbine load controller providing input to this turbinegovernor.
TurbineLoadControllerDynamics
{21C6EABE-ECAB-4ae5-BF01-82E439E5696A}.ClientEnd
Parameter of this proprietary userdefined model.
ProprietaryParameterDynamics
{E9CE179B-FE93-40fa-AF55-290AFD448CA7}.ClientEnd
Turbinegovernor controlled by this turbine load controller.
TurbineGovernorDynamics
{21C6EABE-ECAB-4ae5-BF01-82E439E5696A}.SupplierEnd
Parameter of this proprietary userdefined model.
ProprietaryParameterDynamics
{B43C2066-FB4C-497e-9C4F-E259EF67913D}.ClientEnd
TypeAssets
{C03D47F2-A60F-4e08-BAA2-09494FC4FFE5}.ClientEnd
status
{53086566-D1AB-4f97-A080-68924093C387}
CUMaterialItems
{5FD8B251-F630-475d-9DE8-4E62B3FDAF21}.ClientEnd
ErpIssueInventories
{593B111A-12A5-4f96-B00C-4A37F1AB05D7}.ClientEnd
ErpReqLineItems
{3878A953-62BF-4865-AD6B-E5B11C7EB681}.SupplierEnd
MaterialItems
{1D24C169-2407-4dc7-9946-2E7695DD3662}.SupplierEnd
The estimated unit cost of this type of material either for a unit cost or cost per unit length. Cost is for material or asset only and does not include labor to installconstruct or configure it.
estUnitCost
{A2BE6366-D8C6-41fd-8A86-19948B28FE14}
Edition of UK Ministry of Defence standard.
standardEdition
{6C0454BD-DD4E-40a0-BD64-BD476D4EFF35}
UK Ministry of Defence standard number.
standardNumber
{23ABC5E2-8191-4fd3-B23B-85836D537533}
Delay
{84D84ECC-705D-4a61-8B63-60A505B5791B}.ClientEnd
VSCtype1
{ABBAB2B2-1509-4175-A3E8-48DBC8251AFA}.SupplierEnd
UnavailabilityScheduleDependsOn
{90D8D560-4E3D-4b2e-8C5A-1081DB355463}.SupplierEnd
UnavailabilityScheduleImpacts
{08883996-485F-438c-8235-9EABAB0ED9A2}.SupplierEnd
EquipmentUnavailabilitySchedule
{A621ED73-8721-4170-8819-24FA003C3372}.SupplierEnd
Switch
{0C9534D4-CB50-4b67-88A1-762995554EA1}.SupplierEnd
AvailablityPlan
{A2312A8D-C0CB-4b47-98F8-79E9ADD45A56}.SupplierEnd
DependsOn
{08883996-485F-438c-8235-9EABAB0ED9A2}.ClientEnd
EquipmentUnavailabilitySchedule
{E688F5A4-D2F9-4a84-85F2-980B6307E7AB}.ClientEnd
Impacts
{90D8D560-4E3D-4b2e-8C5A-1081DB355463}.ClientEnd
Gain Under excitation limiter iKiisubUIsubi. Typical value 01.
kui
{F1CC5232-22AF-497d-9315-F0CB76173769}
Segment P initial point iPiisub0subi. Typical value 0.
p0
{AA7D77B2-176F-4aea-A4E7-14DBF9A4BB63}
Segment P end point iPiisub1subi. Typical value 1.
p1
{B088E1D0-1D81-4440-9F8B-F953DA64138F}
Segment Q initial point iQiisub0subi. Typical value 031.
q0
{AC6B4982-0E6C-4a30-8E10-C2DA8E3E7783}
Segment Q end point iQiisub1subi. Typical value 01.
q1
{AED2F338-9CC8-4f9f-981C-D1190C9B029E}
Maximum error signal iViisubUIMAXsubi gt UnderexcLim2Simplified.vuimin. Typical value 1.
vuimax
{17B0573A-B105-449a-8086-57A21D6E8A4C}
Minimum error signal iViisubUIMINsubi lt UnderexcLim2Simplified.vuimax. Typical value 0.
vuimin
{AAB703B4-E112-4652-B083-10C983E1FE2D}
UEL centre setting iKiisubUCsubi. Typical value 138.
kuc
{95624309-574B-4a7d-95A8-D7B74A51CC80}
UEL excitation system stabilizer gain iKiisubUFsubi. Typical value 33.
kuf
{A041F713-6AA1-4469-A442-AA6C9F6618B9}
UEL integral gain iKiisubUIsubi. Typical value 0.
kui
{D150083F-440F-4529-A5E4-28A0EE01FCC9}
UEL proportional gain iKiisubULsubi. Typical value 100.
kul
{E0650CD7-D55C-42ae-AF62-9E6973017E11}
UEL radius setting iKiisubURsubi. Typical value 195.
kur
{64920A14-D8E7-4bdc-9BC7-928FAB1DA88D}
UEL lead time constant iTiisubU1subi gt 0. Typical value 0.
tu1
{504D7CFF-F1F2-4e49-9C4C-539CCDBF8A3B}
UEL lag time constant iTiisubU2subi gt 0. Typical value 005.
tu2
{FE82EA04-AD03-49b4-994A-0F5718B96D51}
UEL lead time constant iTiisubU3subi gt 0. Typical value 0.
tu3
{F0EA1404-1DE1-4527-BAD7-FFA84D2FB1F7}
UEL lag time constant iTiisubU4subi gt 0. Typical value 0.
tu4
{909FDF1E-8257-4738-8E77-07C9C514969E}
UEL maximum limit for operating point phasor magnitude iViisubUCMAXsubi. Typical value 58.
vucmax
{28B8D1B7-18FD-4289-85E7-C484ECE27255}
UEL integrator output maximum limit iViisubUIMAXsubi gt UnderexcLimIEEE1.vuimin.
vuimax
{8F78C41F-55AF-41ee-B034-5A24A69371A9}
UEL integrator output minimum limit iViisubUIMINsubi lt UnderexcLimIEEE1.vuimax.
vuimin
{5CB635B8-4B94-4cfc-A7D5-4082AF8ED4BD}
UEL output maximum limit iViisubULMAXsubi gt UnderexcLimIEEE1.vulmin. Typical value 18.
vulmax
{122CC9B8-792D-4c95-B9A8-22E46A576BC6}
UEL output minimum limit iViisubULMINsubi lt UnderexcLimIEEE1.vulmax. Typical value 18.
vulmin
{C3BFB41C-6613-484a-99EB-A479BBCCB746}
UEL maximum limit for radius phasor magnitude iViisubURMAXsubi. Typical value 58.
vurmax
{E5F17609-3CDB-4279-8CBF-7E2EC3AD5995}
Gain associated with optional integrator feedback input signal to UEL iKiisubFBsubi. Typical value 0.
kfb
{386D854B-91F4-4396-8863-AB26E8AE48A7}
UEL excitation system stabilizer gain iKiisubUFsubi. Typical value 0.
kuf
{82AE58AB-5557-4846-A849-07C8CC17EA36}
UEL integral gain iKiisubUIsubi. Typical value 05.
kui
{44808547-9B47-42c8-909C-A179DBE007BF}
UEL proportional gain iKiisubULsubi. Typical value 08.
kul
{106D7EED-180C-4757-92C5-03614E5D3F88}
Real power values for endpoints iPiisub0subi. Typical value 0.
p0
{CAF5C974-04A4-404f-A555-D2F6A0499FDA}
Real power values for endpoints iPiisub1subi. Typical value 03.
p1
{60939239-B9B9-4623-A3AB-DE77A4F9A24D}
Real power values for endpoints iPiisub10subi.
p10
{97F7FF2B-E4A6-4d50-BDB5-ED8C95175B1D}
Real power values for endpoints iPiisub2subi. Typical value 06.
p2
{8666CA72-BB27-4137-A8EA-62D73DD31CC7}
Real power values for endpoints iPiisub3subi. Typical value 09.
p3
{02661186-1F76-4688-AACD-D55B0A04733C}
Real power values for endpoints iPiisub4subi. Typical value 102.
p4
{AE843EBB-828F-4374-A4D4-5BCE03711D71}
Real power values for endpoints iPiisub5subi.
p5
{8284C4A4-A60D-43c8-A25C-5F13D836B7AB}
Real power values for endpoints iPiisub6subi.
p6
{84CE15EF-D9A4-464c-A933-7A6006336790}
Real power values for endpoints iPiisub7subi.
p7
{56191AD7-E237-4246-8A0E-DDF29118C567}
Real power values for endpoints iPiisub8subi.
p8
{A45644B1-5F12-4556-935B-C20EB3C1F707}
Real power values for endpoints iPiisub9subi.
p9
{3EB11732-31A3-4f4a-9E47-1A63A9470CD5}
Reactive power values for endpoints iQiisub0subi. Typical value 031.
q0
{40CDC020-FAB5-4dae-9E02-5D40CCA6D573}
Reactive power values for endpoints iQiisub1subi. Typical value 031.
q1
{156904B0-6A59-4fdd-A79D-2972E0085799}
Reactive power values for endpoints iQiisub10subi.
q10
{075CA9C7-7410-4697-9E03-D02AD24D2C5B}
Reactive power values for endpoints iQiisub2subi. Typical value 028.
q2
{4EEF0485-9E68-448f-B7BA-737FC4EE2513}
Reactive power values for endpoints iQiisub3subi. Typical value 021.
q3
{B363EC37-038F-4f47-8267-789AD3E1E404}
Reactive power values for endpoints iQiisub4subi. Typical value 0.
q4
{F4526DBD-78C5-4fe3-BCA6-36BF889E64D6}
Reactive power values for endpoints iQiisub5subi.
q5
{DF8A8A62-10D3-4e00-81C5-E33FF45525E0}
Reactive power values for endpoints iQiisub6subi.
q6
{58634D5B-228B-4c38-A808-87D2D0084789}
Reactive power values for endpoints iQiisub7subi.
q7
{8935F65A-5B90-4938-B3FC-A81A7EB8F84D}
Reactive power values for endpoints iQiisub8subi.
q8
{45C2DBF5-B4CD-4dd6-AB5E-1BEA1ADAB2D7}
Reactive power values for endpoints iQiisub9subi.
q9
{D603A8C8-C4D0-4979-A5C6-6F8686AB3D84}
UEL lead time constant iTiisubU1subi gt 0. Typical value 0.
tu1
{AC3107E9-DCED-46d6-A6EE-C7A778EB7155}
UEL lag time constant iTiisubU2subi gt 0. Typical value 0.
tu2
{89D6BE50-CABD-4557-952A-42B87DF9B507}
UEL lead time constant iTiisubU3subi gt 0. Typical value 0.
tu3
{FC40F1E9-BD13-440d-93A3-FE9A04CE44CC}
UEL lag time constant iTiisubU4subi gt 0. Typical value 0.
tu4
{89D67718-CAF8-40fd-B776-9C8CFE779735}
Time constant associated with optional integrator feedback input signal to UEL iTiisubULsubi gt 0. Typical value 0.
tul
{C4145812-72D6-4160-A11D-A754E8E6509B}
Real power filter time constant iTiisubUPsubi gt 0. Typical value 5.
tup
{214758BD-1260-4bb6-BF0E-831FF3EECEB7}
Reactive power filter time constant iTiisubUQsubi gt 0. Typical value 0.
tuq
{BCF3CB8A-3E8C-44c3-97CA-8FC2728BC9CD}
Voltage filter time constant iTiisubUVsubi gt 0. Typical value 5.
tuv
{35453060-020C-4ef9-99CE-F203C7822D4C}
UEL integrator output maximum limit iViisubUIMAXsubi gt UnderexcLimIEEE2.vuimin. Typical value 025.
vuimax
{D0363285-3A59-48fb-A774-07352E446BFC}
UEL integrator output minimum limit iViisubUIMINsubi lt UnderexcLimIEEE2.vuimax. Typical value 0.
vuimin
{0DFFCB2E-EA7D-4ef9-88FD-2318FF02820F}
UEL output maximum limit iViisubULMAXsubi gt UnderexcLimIEEE2.vulmin. Typical value 025.
vulmax
{29808C5A-033D-49d6-AA2C-4B4244C83B91}
UEL output minimum limit iViisubULMINsubi lt UnderexcLimIEEE2.vulmax. Typical value 0.
vulmin
{EBF244D6-78BC-48de-BA08-591E5AC62C84}
Minimum excitation limit slope iKi gt 0.
k
{393861D0-4831-4a0b-8A47-8A6705AA4B61}
Differential gain iKiisubF2subi.
kf2
{38205257-9623-4ad4-A69F-215C8ABCAC8A}
Minimum excitation limit gain iKiisubMsubi.
km
{C0BAAC97-0910-4b91-99D7-FAEA81D6666D}
Minimum excitation limit value iMELMAXi.
melmax
{F283213F-4E1B-4a1e-9738-C415747C7FB4}
Differential time constant iTiisubF2subi gt 0.
tf2
{06CB3671-4833-4eb0-9EC2-0044EB0D54D1}
Minimum excitation limit time constant iTiisubMsubi gt 0.
tm
{0B9CEC1C-8751-43e1-A44A-6EA02C8F2B5A}
Differential gain iKiisubF2subi.
kf2
{6788CA10-5EE0-4bd1-98E4-1803BE1F6E5F}
Minimum excitation limit gain iKiisubMsubi.
km
{DDAD4165-7BEF-43d4-931D-45F28BFA2269}
Minimum excitation limit value iMELMAXi.
melmax
{B7F4A273-8C3F-47e1-A3E3-D516FDC0288A}
Excitation centre setting iQiisubOsubi.
qo
{05135508-D21A-4931-9287-C8206F7B76F8}
Excitation radius iRi.
r
{3653B548-15A7-4567-AF03-FB105BB888BD}
Differential time constant iTiisubF2subi gt 0.
tf2
{84764C85-8303-4ce0-AF51-3795FA7421EE}
Minimum excitation limit time constant iTiisubMsubi gt 0.
tm
{D96C94D2-4D71-4995-B4BE-AFB1752956EB}
Excitation system model with which this underexcitation limiter model is associated.
ExcitationSystemDynamics
{280D64B5-2696-4d89-8390-C68A8F827258}.SupplierEnd
Remote input signal used by this underexcitation limiter model.
RemoteInputSignal
{926FD0F1-B98A-492d-AD1E-CCA64FBEB605}.SupplierEnd
Parameter of this proprietary userdefined model.
ProprietaryParameterDynamics
{B7D39B4A-5132-4f2d-8450-A510C4F0B92A}.ClientEnd
True if vault is ventilating.
kind
{DEFA1FFB-3BA1-4ee9-9397-8B080F2F1413}
AceTariffType
{ED2E671C-C32B-4348-BE5F-95F220417E34}.ClientEnd
TimeSeries
{2CD55C37-FF3C-4881-B74E-437DAEAFB82E}.SupplierEnd
GeneratingUnit
{F5E62ED0-90DD-4d2f-AAD2-99DD94F92779}.SupplierEnd
Cumulative energy production over trading period.
cumEnergy
{1704C461-51E5-4fea-B90C-993A7596EFAB}
Resource MW output at the end of previous clearing period.
resourceMW
{81C0AEEA-DB38-4dd0-B3AB-34E20523A6EF}
FieldDispatchHistory
{D82C3366-0534-4013-898A-7202071B4EF5}.ClientEnd
Incident
{F41F931E-15E0-43ea-9BBE-8F6DB650B1D9}.ClientEnd
TroubleOrder
{D36FE243-EBDF-427d-841A-BF9DD24E97E4}.SupplierEnd
TroubleTicket
{76C1C366-6D04-44f8-B3FA-BD123E9196FD}.SupplierEnd
causeKind
{E7CB3D63-CEE5-4a8e-BBB0-0CF9B08C9FCD}
WorkTask
{AADBFD79-5E2A-47b4-A108-F25824E68687}.ClientEnd
status
{DA37264B-748A-4905-83DA-5922BA220AC2}
All configuration events created for this usage point.
ConfigurationEvents
{BA6788B9-B467-4d11-81A1-9DFE88730490}.SupplierEnd
Customer agreement regulating this service delivery point.
CustomerAgreement
{0FEA25EE-6DB0-45d0-99F9-D5895A91A455}.ClientEnd
All end device controls sending commands to this usage point.
EndDeviceControls
{86BE91D2-4532-408d-85BE-C4192311A77E}.ClientEnd
All end device events reported for this usage point.
EndDeviceEvents
{8DB1B043-3C92-412a-967D-F037C7FA8E36}.ClientEnd
All end devices at this usage point.
EndDevices
{6B05F0D3-B04B-4b78-AF42-4AC3046EF869}.SupplierEnd
EnvironmentalMonitoringStation
{11F52D5E-EFC9-4c29-A3F6-7C2E9E192F0C}.ClientEnd
All equipment connecting this usage point to the electrical grid.
Equipments
{3E4B9C55-FCC6-42ec-B364-27C62004847F}.SupplierEnd
All meter readings obtained from this usage point.
MeterReadings
{EB5C430A-F69D-402a-9806-69357BFC879C}.ClientEnd
All meter service work tasks at this usage point.
MeterServiceWorkTasks
{30B864E4-AFB6-47b2-BF72-C36AA03A3F68}.ClientEnd
All metrology requirements for this usage point.
MetrologyRequirements
{28F71A07-2CD9-466b-BB76-3CAC30AEEC8F}.ClientEnd
All outages at this usage point.
Outage
{13D27FCF-5727-416e-9B7E-FCE3388F7C11}.ClientEnd
{97DDAF6C-65B2-463f-8202-046CC1702F4C}.ClientEnd
All pricing structures applicable to this service delivery point with prepayment meter running as a standalone device with no CustomerAgreement or Customer.
PricingStructures
{E0F674C9-204B-4aa1-9887-8B17137752E6}.ClientEnd
Register
{04237804-35ED-45c5-A932-B74209BBA2C0}.SupplierEnd
Service category delivered by this usage point.
ServiceCategory
{E8ABDA4A-FD10-41db-B40A-285E3E93266A}.SupplierEnd
Service location where the service delivered by this usage point is consumed.
ServiceLocation
{9FD59FA1-2361-4259-948C-56433EAAF9B0}.ClientEnd
All multipliers applied at this usage point.
ServiceMultipliers
{79BFF755-2D9F-4654-B2FF-58E647CF5C97}.SupplierEnd
ServiceSupplier utility utilising this usage point to deliver a service.
ServiceSupplier
{543EBBDE-C4D2-433d-AA02-21917EA65375}.ClientEnd
All groups to which this usage point belongs.
UsagePointGroups
{335E5091-3753-4b0d-A678-4F7E2FC7939E}.ClientEnd
Location of this usage point.
UsagePointLocation
{A316F4EB-589A-4ae7-B7EC-033A447035E7}.ClientEnd
Tracks the lifecycle of the metering installation at a usage point with respect to readiness for billing via advanced metering infrastructure reads.
amiBillingReady
{FE7C731F-08A5-4b5f-8BAF-76DBF14FBB92}
State of the usage point with respect to connection to the network.
connectionState
{BC27BB0A-1E26-401a-9B22-7589BA214A67}
Estimated load.
estimatedLoad
{898BD45F-3FC0-496c-AB0E-B3F2F5AA82E8}
Nominal service voltage.
nominalServiceVoltage
{55F34C1B-875B-416f-AEA5-5B3A8B49ED28}
Phase code. Number of wires and specific nominal phases can be deduced from enumeration literal values. For example ABCN is threephase fourwire s12n splitSecondary12N is singlephase threewire and s1n and s2n are singlephase twowire.
phaseCode
{62172E4F-C15C-401b-BD41-16E98E4CD81C}
Quantitative information about the maximum physical capacity of the connection for the usage point.
physicalConnectionCapacity
{0925388C-D1EC-47ba-8DC4-79BC4A110D4B}
Current flow that this usage point is configured to deliver.
ratedCurrent
{142F3AD8-CABE-43ae-9AF3-A6D2F3118862}
Active power that this usage point is configured to deliver.
ratedPower
{7FA07ABB-E5D0-4635-B946-967B8DD8F39A}
All demand response programs this usage point group is enrolled in.
DemandResponsePrograms
{36AB849B-4EDC-45e7-98B2-FCA2BC154E2B}.ClientEnd
All end device controls sending commands to this usage point group.
EndDeviceControls
{DD9C2BA9-EDBB-4e7b-852C-9AD603C00339}.ClientEnd
All usage points in this group.
UsagePoints
{335E5091-3753-4b0d-A678-4F7E2FC7939E}.SupplierEnd
All usage points at this location.
UsagePoints
{A316F4EB-589A-4ae7-B7EC-033A447035E7}.SupplierEnd
ErpInvoiceLineItems
{5DECAD82-C8FA-4209-A6DC-EC593C447EE3}.ClientEnd
ErpLedgerEntries
{930F2019-2141-4f10-80A0-CECF3D224F2D}.ClientEnd
ProcedureDataSets
{779BA9D1-950E-4184-B4C5-D887B32ECEDB}.SupplierEnd
PropertySpecification
{77BA456A-7BFE-460d-9B1F-6CFF50541E78}.SupplierEnd
RatingSpecification
{A095B451-1D6E-48b1-8999-6944FB2D21D0}.SupplierEnd
Transaction for which this snapshot has been recorded.
Transaction
{2749DDBF-3B2B-40e4-AF4B-40B8874DF1F9}.SupplierEnd
Value of an attribute including unit information.
value
{2FCC8C5A-9B5B-4bb9-9AE3-A9BE83ACBD93}
Time that adjuster pulses are off iTiisubAOFFsubi gt 0. Typical value 05.
taoff
{6C268358-8AE5-4f8d-8B29-0238E71101E8}
Time that adjuster pulses are on iTiisubAONsubi gt 0. Typical value 01.
taon
{6D27B57A-5F30-402d-861F-26BA63FD411C}
Maximum output of the adjuster iViisubADJMAXsubi gt VAdjIEEE.vadjmin. Typical value 11.
vadjmax
{59BBB8E6-1F97-4e17-9F06-42FC7F297EB0}
Minimum output of the adjuster iViisubADJMINsubi lt VAdjIEEE.vadjmax. Typical value 09.
vadjmin
{A2D5F296-0E9C-408d-A62E-1EBD165805ED}
font color0f0f0fResistive component of compensation of a generator iRci gt 0.font
rc
{E797D9B3-C339-4333-830D-ABF7A3C52C4E}
font color0f0f0fTime constant which is used for the combined voltage sensing and compensation signal iTri gt 0.font
tr
{D1040A70-C25C-41fe-8E2F-9DC914E76223}
font color0f0f0fReactive component of compensation of a generator iXci gt 0.font
xc
{C7EF60C2-87A9-432b-973B-072320CE7AFD}
Compensation of this voltage compensators generator for current flow out of another generator.
GenICompensationForGenJ
{85A30109-1473-4ba8-A00B-DA4D28CE2463}.ClientEnd
font color0f0f0fTime constant which is used for the combined voltage sensing and compensation signal iTri gt 0.font
tr
{82548F40-3D95-4117-A774-371E257F2A08}
Delay
{DA56FBC7-3797-4264-AE29-61FEBA3C58F7}.ClientEnd
HVDCLookUpTable
{14C2B235-371D-4ebf-BFF8-1E462660C3D0}.ClientEnd
IdcInverterControl
{D9D8D23C-3E4B-4af0-B456-954687DFA9E6}.SupplierEnd
Voltage source converter to which voltage source converter dynamics model applies.
VsConverter
{0D53C0FB-F7F9-4e32-BFFE-42DC43308D29}.SupplierEnd
Parameter of this proprietary userdefined model.
ProprietaryParameterDynamics
{AB07F11F-12BF-40f7-A3A5-86F42927D688}.SupplierEnd
BlockingFunction
{EA954A70-DF63-404b-98A9-063F5571B46A}.ClientEnd
DCvoltageControl
{86E86FC3-61BD-4a5f-A4F1-6BDFD8ADE591}.SupplierEnd
PFmodel
{E76FDA89-DE78-4412-88D5-5554DBCA51D8}.ClientEnd
Pcontrol
{3E4C2CFA-1298-41b3-9038-5F139DAC76C3}.ClientEnd
Qlimiter
{28C86EC6-3D7B-4965-99CB-2AB0622D2C24}.ClientEnd
Qmode
{3EEAA87A-6141-43c6-AE82-9A6DAC9A62E9}.ClientEnd
Qregulator
{4CCAE11F-2B9B-48f1-B5A0-6357DC443AD7}.ClientEnd
Umode
{ABBAB2B2-1509-4175-A3E8-48DBC8251AFA}.ClientEnd
The Commands using the set for translation.
Commands
{E47F1C07-76A3-4828-BB41-624EB0C9DAE0}.ClientEnd
The Measurements using the set for translation.
Discretes
{27083F43-08EC-487a-A912-C969A351E021}.SupplierEnd
The Commands using the set for translation.
RaiseLowerCommands
{689EAD20-E5B3-46ae-BABC-7A32ADA8F247}.ClientEnd
The ValueToAlias mappings included in the set.
Values
{24118167-9D7E-45ac-967E-8BE0BD4E1375}.SupplierEnd
The ValueAliasSet having the ValueToAlias mappings.
ValueAliasSet
{24118167-9D7E-45ac-967E-8BE0BD4E1375}.ClientEnd
Odometer reading of this vehicle as of the odometerReadingDateTime. Refer to associated ActivityRecords for earlier readings.
odometerReading
{17651248-7852-4708-BB6D-DC8D83BA2413}
Kind of usage of the vehicle.
usageKind
{8BE9F017-D4FC-47d4-BD18-39C1888B845B}
All vendor shifts opened and owned by this vendor.
VendorShifts
{B8537A91-B364-489c-BB0B-6BA861574DC1}.SupplierEnd
Merchant account this vendor shift periodically debits based on aggregated transactions.
MerchantAccount
{28C890D5-DD6C-419b-AC03-0323BBD41D10}.ClientEnd
All receipts recorded during this vendor shift.
Receipts
{652E0D7A-D247-45a6-80F2-A0339EFE02D7}.SupplierEnd
All transactions recorded during this vendor shift.
Transactions
{C7BF480F-86A2-4fe5-BB3D-D4EA91B0C386}.SupplierEnd
Vendor that opens and owns this vendor shift.
Vendor
{B8537A91-B364-489c-BB0B-6BA861574DC1}.ClientEnd
The amount that is to be debited from the merchant account for this vendor shift. This amount reflects the sumPaymentTransaction.transactionAmount.
merchantDebitAmount
{0ED883FA-D8C0-4f3d-B6D1-ADFF9B663BC4}
PowerSystemResource
{4F85BB5D-133B-4060-B422-86E5B9320EE2}.SupplierEnd
Flowgate
{60BE8E0E-9F8A-4813-93AA-E5DC48BEF7A5}.SupplierEnd
MktMeasurement
{7B62C3C6-7398-40f5-BDE5-CBD6C32FC0EF}.SupplierEnd
A visibility layer can contain one or more diagram objects.
VisibleObjects
{86380B03-52EA-473d-9BFA-DCDAAE9D1275}.ClientEnd
Particulate density of the ash cloud during the time interval.
density
{2FEF2762-BE41-4966-902F-21C2B962D4C3}
The diameter of the particles during the time interval.
particleSize
{2563D202-782B-405b-950C-92598A5831DA}
multiplier
{5CFD034E-D7E1-4d20-BE0B-BB9E4F9D2D4B}
unit
{6E959BD4-0ACC-4884-99F5-0B158661A3D9}
Power factor or VAr controller type 1 model with which this voltage adjuster is associated.
PFVArControllerType1Dynamics
{7A74A658-111A-4af6-B1B7-CAA3F6F7BA11}.SupplierEnd
Parameter of this proprietary userdefined model.
ProprietaryParameterDynamics
{DF4D0AAC-C129-47a1-ADAF-DB0071F13178}.ClientEnd
Excitation system model with which this voltage compensator is associated.
ExcitationSystemDynamics
{261F59A6-26BA-4cfc-9309-36D92F002250}.SupplierEnd
Remote input signal used by this voltage compensator model.
RemoteInputSignal
{F5F154AE-0B1E-4436-BB0A-FB640908FA63}.SupplierEnd
Parameter of this proprietary userdefined model.
ProprietaryParameterDynamics
{8A60B7E2-A760-4eba-9D83-DDFC09AE0C14}.ClientEnd
A VoltageControlZone is controlled by a designated BusbarSection.
BusbarSection
{77D2F437-1BDA-463c-AC93-F25EAC4B04AF}.ClientEnd
A VoltageControlZone may have a voltage regulation schedule.
RegulationSchedule
{56DF2E78-015D-485f-9708-D84FAFD9124C}.ClientEnd
The base voltage used for all equipment within the voltage level.
BaseVoltage
{F610FDC8-D98D-4367-99A9-E9CA1C8A8CC5}.SupplierEnd
The bays within this voltage level.
Bays
{5E328091-5BC1-4fa8-9BA3-F087A215492A}.SupplierEnd
The substation of the voltage level.
Substation
{0E9E9E28-C575-47c5-BF01-7F4EB8B36D16}.ClientEnd
The bus bars high voltage limit.The limit applies to all equipment and nodes contained in a given VoltageLevel. It is not required that it is exchanged in pair with lowVoltageLimit. It is preferable to use operational VoltageLimit which prevails if present.
highVoltageLimit
{D1BAD493-B22A-497f-B6A6-CDFDF46EA012}
The bus bars low voltage limit.The limit applies to all equipment and nodes contained in a given VoltageLevel. It is not required that it is exchanged in pair with highVoltageLimit. It is preferable to use operational VoltageLimit which prevails if present.
lowVoltageLimit
{EB17FEAC-CDBA-4bbd-B45E-86D3EA333C08}
The normal limit on voltage. High or low limit nature of the limit depends upon the properties of the operational limit type. The attribute shall be a positive value or zero.
normalValue
{3AF6D9EB-CF4A-4a6a-9981-91BC90013436}
Limit on voltage. High or low limit nature of the limit depends upon the properties of the operational limit type. The attribute shall be a positive value or zero.
value
{8FB525FF-AD28-448b-A341-12A345E4F498}
multiplier
{39EBF43D-BF3B-422f-8AFC-F6270D86CE37}
unit
{0D0A9B79-90D9-49de-A575-7F0FF7992C42}
multiplier
{5BA1C598-89A3-406f-996B-9CF6DAC63C7E}
unit
{D0E1658C-A431-4226-BAC0-DD2B9F148D2D}
multiplier
{3140412A-C74C-40b5-950C-0022CB841EDC}
unit
{A829C826-5E30-413d-B779-035125B7FAD3}
All converters with this capability curve.
VsConverterDCSides
{088AB6E2-983D-4208-B04F-916A1B2C598B}.ClientEnd
Capability curve of this converter.
CapabilityCurve
{088AB6E2-983D-4208-B04F-916A1B2C598B}.SupplierEnd
Voltage source converter dynamics model used to describe dynamic behaviour of this converter.
VSCDynamics
{0D53C0FB-F7F9-4e32-BFFE-42DC43308D29}.ClientEnd
Angle between VsConverter.uv and ACDCConverter.uc. It is converters state variable used in power flow. The attribute shall be a positive value or zero.
delta
{2189316A-172E-44de-824E-A54EC07B70C2}
Droop constant. The pu value is obtained as D kVMW x Sb Ubdc. The attribute shall be a positive value.
droop
{09DF9A01-EFD3-483a-B7A2-00A69CFEBCD4}
Compensation constant. Used to compensate for voltage drop when controlling voltage at a distant bus. The attribute shall be a positive value.
droopCompensation
{0C9168D8-85A0-4744-8BE8-15988CAD1B4E}
The maximum current through a valve. It is converters configuration data.
maxValveCurrent
{49F91CB7-09CB-414b-8DBA-C54CC75EFDBA}
Kind of control of real power andor DC voltage.
pPccControl
{5FA48BB1-3740-42bd-9B95-58218BB9B057}
Kind of reactive power control.
qPccControl
{566B426C-68EF-4aa8-97EA-EEE5345A722F}
Reactive power sharing factor among parallel converters on Uac control. The attribute shall be a positive value or zero.
qShare
{23E9AEE5-97B8-4a61-95F2-E91D567FAB7A}
Phase target at AC side at point of common coupling. The attribute shall be a positive value.
targetPhasePcc
{B2315AB9-3665-4aed-BF4E-409B8B241E41}
Reactive power injection target in AC grid at point of common coupling. Load sign convention is used i.e. positive sign means flow out from a node.
targetQpcc
{B7B87909-9557-4459-98B0-380ED4A93C30}
Voltage target in AC grid at point of common coupling. The attribute shall be a positive value.
targetUpcc
{90F337A1-08D6-4eed-8416-47EC2B390E2D}
Linetoline voltage on the valve side of the converter transformer. It is converters state variable result from power flow. The attribute shall be a positive value.
uv
{3A33C9B0-B1FE-46e0-B489-EA92C58DD05A}
Edition of WEP standard.
standardEdition
{B738DDE1-247A-4ef8-A466-2527680AA1B1}
WEP standard number.
standardNumber
{C7562412-18BC-4fbf-9208-2C97DC90F5E6}
multiplier
{3F719CBC-2202-44be-B94E-6BEBC34F61A2}
unit
{03F9AD2F-6E74-4484-9EB6-38209DC617A4}
Equipment
{C35B9B9D-C271-4005-801D-B7B44FF8D8C7}.ClientEnd
RegisteredInterTie
{A446E5B3-C506-49f2-A28E-A19EEAB812A7}.SupplierEnd
Wind turbine type 1A model with which this wind aerodynamic model is associated.
WindGenTurbineType1aIEC
{DAD6324C-3404-453d-B801-EE89B1034AF5}.SupplierEnd
Wind turbine type 3 model with which this wind aerodynamic model is associated.
WindTurbineType3IEC
{0A379016-96C1-4d07-8589-6AE172CD1DA8}.SupplierEnd
Initial pitch angle ithetaiisubomega0subi. It is a casedependent parameter.
thetaomega
{25856E22-B92F-4ae2-A2DF-D2DF9665619E}
Wind turbine type 3 model with which this wind aerodynamic model is associated.
WindTurbineType3IEC
{A9340DAA-2D75-4953-8AB2-F705D0EF27D6}.SupplierEnd
Partial derivative of aerodynamic power with respect to changes in WTR speed idpiisubomegasubi. It is a typedependent parameter.
dpomega
{77894102-33FE-42d0-8C69-5A78456D6C54}
Partial derivative of aerodynamic power with respect to changes in pitch angle idpiisubthetasubi. It is a typedependent parameter.
dptheta
{B8179740-D164-4929-AF75-085340CE97D8}
Partial derivative idpiisubv1subi. It is a typedependent parameter.
dpv1
{BB70D550-A30F-478c-B099-4BCD1D8ABC05}
Rotor speed if the wind turbine is not derated iomegaiisub0subi. It is a typedependent parameter.
omegazero
{50D30958-9EC8-4630-B439-4062802E0534}
Available aerodynamic power ipiisubavailsubiii. It is a casedependent parameter.
pavail
{CDD8685B-0D1D-4e26-921D-65E57C35B979}
Blade angle at twice rated wind speed ithetaiisubv2subi. It is a typedependent parameter.
thetav2
{F3EA8003-633F-4643-9993-B7701F88E0DA}
Pitch angle if the wind turbine is not derated ithetaiisub0subi. It is a casedependent parameter.
thetazero
{9864969E-3C94-4660-BD25-00677AE0CE02}
The wind dynamics lookup table associated with this current control limitation model.
WindDynamicsLookupTable
{AADAA3E0-9016-4044-A073-CB41756815C3}.ClientEnd
Wind turbine type 3 or type 4 model with which this wind control current limitation model is associated.
WindTurbineType3or4IEC
{B15E3709-C78C-4e94-AF81-81277B45B7F1}.SupplierEnd
Maximum continuous current at the wind turbine terminals iiiisubmaxsubi. It is a typedependent parameter.
imax
{9BC14E87-7F01-49a5-8338-8F700DDCE48A}
Maximum current during voltage dip at the wind turbine terminals iiiisubmaxdipsubi. It is a projectdependent parameter.
imaxdip
{01DCA53F-E465-44bc-BC5C-121D2C7090F5}
Partial derivative of reactive current limit iKiisubpqusubi versus voltage. It is a typedependent parameter.
kpqu
{A699AE14-77C6-4d4a-A0EC-21E7FFE2BD45}
Voltage measurement filter time constant iTiisubufiltclsubi gt 0. It is a typedependent parameter.
tufiltcl
{85854FDE-4244-492a-8C35-9BEE5EEE3A31}
Wind turbine voltage in the operation point where zero reactive current can be delivered iuiisubpqumaxsubi. It is a typedependent parameter.
upqumax
{0BFFB084-CCEA-45ef-97EC-87A01767718A}
The wind dynamics lookup table associated with this P control type 3 model.
WindDynamicsLookupTable
{38915014-704F-43c1-8F16-D050EE005809}.ClientEnd
Wind turbine type 3 model with which this wind control P type 3 model is associated.
WindTurbineType3IEC
{1125BB6A-BC13-4945-8BBC-ABB49A1938CE}.SupplierEnd
Maximum wind turbine power ramp rate idpiisubmaxsubi. It is a typedependent parameter.
dpmax
{14AE625C-69FC-4d9d-8A3B-6038B20B1B45}
Maximum ramp rate of wind turbine reference power idpiisubrefmaxsubi. It is a projectdependent parameter.
dprefmax
{E2C2E735-8B4D-4d0f-AA8B-3C2F2A1A3E8C}
Minimum ramp rate of wind turbine reference power idpiisubrefminsubi. It is a projectdependent parameter.
dprefmin
{0B71894B-67C4-40e0-A9E0-C51022AC9CC9}
Ramp limitation of torque required in some grid codes idtiisubmaxsubi. It is a projectdependent parameter.
dthetamax
{3F30470B-8C37-4477-AECB-6B5BD66CBBC4}
Limitation of torque rise rate during UVRT idthetaiisubmaxUVRTsubi. It is a projectdependent parameter.
dthetamaxuvrt
{0C7553B6-1000-49a3-8EC3-828323127A74}
Gain for active drive train damping iKiisubDTDsubi. It is a typedependent parameter.
kdtd
{2A6582BE-A66D-4462-9471-DFC650E20E06}
PI controller integration parameter iKisubIpsub. It is a typedependent parameter.
kip
{27060C22-2320-435f-9026-08AA5841E582}
PI controller proportional gain iKisubPpsub. It is a typedependent parameter.
kpp
{E7B9AC70-DD0C-4ed5-8FC3-83B272A53801}
Active drive train damping frequency iomegaiisubDTDsubi. It can be calculated from two mass model parameters. It is a typedependent parameter.
omegadtd
{4F1A9B58-0F9E-4c57-A23B-07EF638F9B22}
Offset to reference value that limits controller action during rotor speed changes iomegaiisuboffsetsubi. It is a casedependent parameter.
omegaoffset
{F3D8AF72-7AE4-46da-AC04-1CFD8091993E}
Maximum active drive train damping power ipisubDTDmaxsub. It is a typedependent parameter.
pdtdmax
{D93E5688-ABD0-47bb-AFA5-5F88EDB1F6B1}
Timesub subdelay after deep voltage sags iTiisubDVSsubi gt 0. It is a projectdependent parameter.
tdvs
{F1D92A86-FF8A-46b5-9191-C4BC9D7296E4}
Minimum electrical generator torque itisubeminsub. It is a typedependent parameter.
thetaemin
{A5B91875-A172-4ede-AFC9-C0065B0C15EF}
Voltage scaling factor of resettorque itisubuscalesub. It is a projectdependent parameter.
thetauscale
{E969BD5C-1E28-4ee2-B66D-22309EA4E7A7}
Filter time constant for generator speed measurement iTisubomegafiltp3sub gt 0. It is a typedependent parameter.
tomegafiltp3
{639011EC-0E08-48fd-B854-63EC7A4ED2F7}
Time constant in speed reference filter iTisubomegarefsub gt 0. It is a typedependent parameter.
tomegaref
{739A6C35-F9F6-4908-A1E1-E97CBC91D3F4}
Filter time constant for power measurement iTisubpfiltp3sub gt 0. It is a typedependent parameter.
tpfiltp3
{80E91633-36F8-4df7-A47A-B33F4B10A361}
Time constant in power order lag iTisubpordsub. It is a typedependent parameter.
tpord
{4D5DCC45-BF32-4e81-973E-5584F68EE3C4}
Filter time constant for voltage measurement iTisubufiltp3sub gt 0. It is a typedependent parameter.
tufiltp3
{394D12B5-70DA-45a7-BC2D-C88AA4505DCD}
Voltage limit for hold UVRT status after deep voltage sags iuiisubDVSsubi. It is a projectdependent parameter.
udvs
{8BA50F61-AD66-47f5-BE03-A1E2A389A5E9}
Voltage dip threshold for Pcontrol iuisubPdipsub. Part of turbine control often different e.g 0.8 from converter thresholds. It is a projectdependent parameter.
updip
{2A4F2828-1735-4c1a-AE25-F4A272C50B22}
Wind turbine type 4A model with which this wind control P type 4A model is associated.
WindTurbineType4aIEC
{DA5D31C7-93C5-460a-887B-F6F3620C8AB7}.SupplierEnd
Maximum wind turbine power ramp rate idpiisubmaxp4Asubi. It is a projectdependent parameter.
dpmaxp4a
{5937836E-B408-4800-9ED7-1D53ACBD0EC1}
Time constant in power order lag iTiisubpordp4Asubi gt 0. It is a typedependent parameter.
tpordp4a
{4AD005E4-70D5-4153-90EE-2CBAAD64DACC}
Voltage measurement filter time constant iTiisubufiltp4Asubi gt 0. It is a typedependent parameter.
tufiltp4a
{DC49301D-E1E5-4f46-AB43-E16ACE4A84C6}
Wind turbine type 4B model with which this wind control P type 4B model is associated.
WindTurbineType4bIEC
{674DEC61-D931-4c8f-95C6-127BDFBD3C9A}.SupplierEnd
Maximum wind turbine power ramp rate idpiisubmaxp4Bsubi. It is a projectdependent parameter.
dpmaxp4b
{A44F18B6-1014-45fe-89C7-DA88A60D04CF}
Time constant in aerodynamic power response iTiisubpaerosubi gt 0. It is a typedependent parameter.
tpaero
{03035F3F-A209-4655-A342-C1836187D91E}
Time constant in power order lag iTiisubpordp4Bsubi gt 0. It is a typedependent parameter.
tpordp4b
{4B1A6B14-BDEF-48ba-8E9F-EE75E292D972}
Voltage measurement filter time constant iTiisubufiltp4Bsubi gt 0. It is a typedependent parameter.
tufiltp4b
{3B82A793-6C2B-4ebd-B0A2-55A03400C7F2}
Wind turbine type 3 model with which this pitch control model is associated.
WindTurbineType3IEC
{6C1D2665-2EAD-48e1-8020-FED105CE3F96}.SupplierEnd
Power PI controller integration gain iKiisubIcsubi. It is a typedependent parameter.
kic
{4C4E3437-054F-4a21-B948-4FF973E34687}
Speed PI controller integration gain iKiisubIomegasubi. It is a typedependent parameter.
kiomega
{71A2E5DB-DC12-405b-B950-DD021DCADB35}
Power PI controller proportional gain iKiisubPcsubi. It is a typedependent parameter.
kpc
{4F0E4016-E3A1-4fdf-A64E-CD3967604373}
Speed PI controller proportional gain iKiisubPomegasubi. It is a typedependent parameter.
kpomega
{7D5057C5-33C8-493d-8500-23CC9DDBC8E1}
Pitch cross coupling gain iKiisubPXsubi. It is a typedependent parameter.
kpx
{8282719A-920F-4cae-8B55-A9BBE2A56B6D}
Maximum pitch angle ithetaiisubmaxsubi gt WindContPitchAngleIEC.thetamin. It is a typedependent parameter.
thetamax
{7F157065-34CF-4ea0-BA27-E2373B1F57E9}
Minimum pitch angle ithetaiisubminsubi lt WindContPitchAngleIEC.thetamax. It is a typedependent parameter.
thetamin
{F51D84B7-D87F-4541-8145-6579C8A6602D}
Pitch time constant itthetai gt 0. It is a typedependent parameter.
ttheta
{59736BAD-6516-4df7-B683-1078B54CA855}
Wind turbine type 3 or type 4 model with which this reactive control model is associated.
WindTurbineType3or4IEC
{30981A01-0238-4403-ADC6-906C4187F62A}.SupplierEnd
Maximum reactive current injection during dip iiiisubqh1subi. It is a typedependent parameter.
iqh1
{0C8911DF-BD69-40b1-A451-EA5DECDB9CE0}
Maximum reactive current injection iiiisubqmaxsubi gt WindContQIEC.iqmin. It is a typedependent parameter.
iqmax
{4DD2C0A7-1C8A-4e67-889D-DD9EFCF1FBBC}
Minimum reactive current injection iiiisubqminsubi lt WindContQIEC.iqmax. It is a typedependent parameter.
iqmin
{E6922880-7E99-47dc-8EFE-7A5885AD089D}
Post fault reactive current injection iiiisubqpostsubi. It is a projectdependent parameter.
iqpost
{27A21870-0F96-49fb-90A6-BD70CB539BAB}
Reactive power PI controller integration gain iKiisubIqsubi. It is a typedependent parameter.
kiq
{D7AAE1DF-4260-45bf-8B97-E8B6BB3FC88C}
Voltage PI controller integration gain iKiisubIusubi. It is a typedependent parameter.
kiu
{A228380E-56FA-4618-B1EE-2898DC0814E0}
Reactive power PI controller proportional gain iKiisubPqsubi. It is a typedependent parameter.
kpq
{A524204E-A3E8-47ae-8EFF-2D48F3F915B3}
Voltage PI controller proportional gain iKiisubPusubi. It is a typedependent parameter.
kpu
{35A2EAF9-BF21-40d6-B878-241A73D0DBBF}
Voltage scaling factor for UVRT current iKiisubqvsubi. It is a projectdependent parameter.
kqv
{B1406641-4E8F-4778-8C5D-047F9C836C41}
Resistive component of voltage drop impedance iriisubdroopsubi gt 0. It is a projectdependent parameter.
rdroop
{B6FA8038-FA60-44b0-B8E1-D7A95C55E2D6}
Power measurement filter time constant iTiisubpfiltqsubi gt 0. It is a typedependent parameter.
tpfiltq
{100EAF7C-D940-4446-8975-312E086FBB4E}
Length of time period where post fault reactive power is injected iTiisubpostsubi gt 0. It is a projectdependent parameter.
tpost
{4813D25A-9B96-43e3-A558-BB8E98329254}
Time constant in reactive power order lag iTiisubqordsubi gt 0. It is a typedependent parameter.
tqord
{93B68A05-BF83-4d81-9B71-089AF0A486EB}
Voltage measurement filter time constant iTiisubufiltqsubi gt 0. It is a typedependent parameter.
tufiltq
{681B2820-FBE5-4622-A1F2-ED4E3FDFA516}
Voltage deadband lower limit iuiisubdb1subi. It is a typedependent parameter.
udb1
{72D155DB-DD39-4065-80D2-A492877759FF}
Voltage deadband upper limit iuiisubdb2subi. It is a typedependent parameter.
udb2
{CFCC87DF-C495-4ab5-9FFD-90DA17FD07FA}
Maximum voltage in voltage PI controller integral term iuiisubmaxsubi gt WindContQIEC.umin. It is a typedependent parameter.
umax
{7058E625-CA26-4a95-9512-95BD0AC09095}
Minimum voltage in voltage PI controller integral term iuiisubminsubi lt WindContQIEC.umax. It is a typedependent parameter.
umin
{7CFF046C-4647-4a39-8A08-E13024DA28DB}
Voltage threshold for UVRT detection in Q control iuiisubqdipsubi. It is a typedependent parameter.
uqdip
{688AAA9C-54E6-42da-AA90-220CA155D906}
Userdefined bias in voltage reference iuiisubref0subi. It is a casedependent parameter.
uref0
{F36AD473-7963-4e52-8D34-0BA9C79E8439}
Types of general wind turbine Q control modes iMiisubqGsubi. It is a projectdependent parameter.
windQcontrolModesType
{9A783FE2-3B0D-4de5-A4E5-1A07C56944E3}
Types of UVRT Q control modes iMiisubqUVRTsubi. It is a projectdependent parameter.
windUVRTQcontrolModesType
{E15D6894-4910-4aca-B0B5-81C9B9E9552F}
Inductive component of voltage drop impedance ixiisubdroopsubi gt 0. It is a projectdependent parameter.
xdroop
{BB27A9E3-0C0D-42fe-A5AD-C466F4905938}
Wind generator type 3 or type 4 model with which this constant Q limitation model is associated.
WindTurbineType3or4IEC
{0017E503-888C-407e-A297-BB307A040C9A}.SupplierEnd
Maximum reactive power iqiisubmaxsubi gt WindContQLimIEC.qmin. It is a typedependent parameter.
qmax
{A89C54BD-A1E1-4d10-877C-893932674865}
Minimum reactive power iqiisubminsubi lt WindContQLimIEC.qmax. It is a typedependent parameter.
qmin
{6E33D596-DD23-4655-AE16-8E2E7E01CD33}
The wind dynamics lookup table associated with this QP and QU limitation model.
WindDynamicsLookupTable
{B8ADA92B-7E1A-4977-BE55-E8C3C952D529}.ClientEnd
Wind generator type 3 or type 4 model with which this QP and QU limitation model is associated.
WindTurbineType3or4IEC
{B403375C-0F8C-45f3-92A9-700935E21AD2}.SupplierEnd
Power measurement filter time constant for Q capacity iTiisubpfiltqlsubi gt 0. It is a typedependent parameter.
tpfiltql
{F4228B0E-2501-4854-A5CF-83704FDEDEFC}
Voltage measurement filter time constant for Q capacity iTiisubufiltqlsubi gt 0. It is a typedependent parameter.
tufiltql
{82A92A58-DFAF-42b1-9993-72176C10ED8B}
The wind dynamics lookup table associated with this rotor resistance control model.
WindDynamicsLookupTable
{DF3BE6FA-0490-4959-97AD-E2F9E7E8B72B}.ClientEnd
Wind turbine type 2 model with whitch this wind control rotor resistance model is associated.
WindGenTurbineType2IEC
{B197F42D-0871-46cb-9470-FB7C83C76D53}.SupplierEnd
Integral gain in rotor resistance PI controller iKiisubIrrsubi. It is a typedependent parameter.
kirr
{2EBA1C05-DEA6-41fc-B2FA-BFD872893BFF}
Proportional gain in rotor resistance PI controller iKiisubPrrsubi. It is a typedependent parameter.
kprr
{68B9D395-C2A3-4dc7-A86E-99AB08F68BE4}
Maximum rotor resistance iriisubmaxsubi gt WindContRotorRIEC.rmin. It is a typedependent parameter.
rmax
{98E0B7BF-35A6-40f8-96B8-433938E168BF}
Minimum rotor resistance iriisubminsubi lt WindContRotorRIEC.rmax. It is a typedependent parameter.
rmin
{AD5028B6-684A-4f6c-A8A9-516181593AA1}
Filter time constant for generator speed measurement iTiisubomegafiltrrsubi gt 0. It is a typedependent parameter.
tomegafiltrr
{1800DF42-CD71-49d6-8707-D85A3B5EC6BD}
Filter time constant for power measurement iTiisubpfiltrrsubi gt 0. It is a typedependent parameter.
tpfiltrr
{46EF755E-5A61-4df6-AEBB-275B0C25C11F}
The current control limitation model with which this wind dynamics lookup table is associated.
WindContCurrLimIEC
{AADAA3E0-9016-4044-A073-CB41756815C3}.SupplierEnd
The P control type 3 model with which this wind dynamics lookup table is associated.
WindContPType3IEC
{38915014-704F-43c1-8F16-D050EE005809}.SupplierEnd
The QP and QU limitation model with which this wind dynamics lookup table is associated.
WindContQPQULimIEC
{B8ADA92B-7E1A-4977-BE55-E8C3C952D529}.SupplierEnd
The rotor resistance control model with which this wind dynamics lookup table is associated.
WindContRotorRIEC
{DF3BE6FA-0490-4959-97AD-E2F9E7E8B72B}.SupplierEnd
The generator type 3B model with which this wind dynamics lookup table is associated.
WindGenType3bIEC
{07DB8FC1-6EFF-4245-916A-DB83D61B50D6}.SupplierEnd
The pitch control power model with which this wind dynamics lookup table is associated.
WindPitchContPowerIEC
{43C4AEB1-F841-4657-AD07-5DCC12ECD3FB}.SupplierEnd
The frequency and active power wind plant control model with which this wind dynamics lookup table is associated.
WindPlantFreqPcontrolIEC
{270439E2-372B-4fe6-97E5-0B33363C463D}.SupplierEnd
The voltage and reactive power wind plant control model with which this wind dynamics lookup table is associated.
WindPlantReactiveControlIEC
{28BA1D32-A6C1-4d3c-9E93-99FC047529D4}.SupplierEnd
The grid protection model with which this wind dynamics lookup table is associated.
WindProtectionIEC
{C3C3FBA5-3DF3-43fb-B61D-884F27F86A76}.SupplierEnd
Type of the lookup table function.
lookupTableFunctionType
{63FC5B5B-9FB1-4982-B612-BB9BD18DA175}
Wind aerodynamic model associated with this wind turbine type 1A model.
WindAeroConstIEC
{DAD6324C-3404-453d-B801-EE89B1034AF5}.ClientEnd
Pitch control power model associated with this wind turbine type 1B model.
WindPitchContPowerIEC
{16C044ED-F9D1-4331-8143-13D0E5D17A9F}.SupplierEnd
Wind control rotor resistance model associated with wind turbine type 2 model.
WindContRotorRIEC
{B197F42D-0871-46cb-9470-FB7C83C76D53}.ClientEnd
Pitch control power model associated with this wind turbine type 2 model.
WindPitchContPowerIEC
{9D56255A-58CA-4569-AC81-725F7E0262B0}.ClientEnd
Wind turbine type 3 model with which this wind generator type 3 is associated.
WindTurbineType3IEC
{46227D47-50B8-490b-A51B-3E8D8812364C}.SupplierEnd
Maximum active current ramp rate idiiisubpmaxsubi. It is a projectdependent parameter.
dipmax
{8AD7ED6E-7C11-47bc-AFC0-BF3C7B287664}
Maximum reactive current ramp rate idiiisubqmaxsubi. It is a projectdependent parameter.
diqmax
{63D01275-C601-4efe-B244-C95E58CC78C4}
Electromagnetic transient reactance ixiisubSsubi. It is a typedependent parameter.
xs
{854150C6-CC99-4125-84E9-0261FDD78467}
Wind turbine type 4 model with which this wind generator type 3A model is associated.
WindTurbineType4IEC
{CADDE3B0-B9F9-4524-8093-96B4A07DCEB0}.SupplierEnd
Current PI controller integration time constant iTiisubIcsubi gt 0. It is a typedependent parameter.
tic
{04D419CD-198C-469a-81BE-C293B02F9BF9}
The wind dynamics lookup table associated with this generator type 3B model.
WindDynamicsLookupTable
{07DB8FC1-6EFF-4245-916A-DB83D61B50D6}.ClientEnd
Current generation time constant iTiisubgsubi gt 0. It is a typedependent parameter.
tg
{85DA4F3F-5BC7-45a5-9FB1-1B1F39033184}
Time constant for crowbar washout filter iTiisubwosubi gt 0. It is a casedependent parameter.
two
{0AA36B18-1CD9-4386-A06B-7402285B1A95}
Wind turbine type 4A model with which this wind generator type 4 model is associated.
WindTurbineType4aIEC
{11A4D311-CB84-4368-A12C-4259083A726C}.SupplierEnd
Wind turbine type 4B model with which this wind generator type 4 model is associated.
WindTurbineType4bIEC
{CF7D044B-E56E-4d33-ABD3-F06CEB5C6888}.SupplierEnd
Maximum active current ramp rate idiiisubpmaxsubi. It is a projectdependent parameter.
dipmax
{BA0D3C43-090D-49ac-BBFA-DB621E339E36}
Maximum reactive current ramp rate idiiisubqmaxsubi. It is a projectdependent parameter.
diqmax
{0CFFD36D-4811-4608-8A7A-65AC6E8DAE6E}
Minimum reactive current ramp rate idiiisubqminsubi. It is a projectdependent parameter.
diqmin
{0F64C553-CD05-46f3-987A-EBABC9C62B51}
Time constant iTiisubgsubi gt 0. It is a typedependent parameter.
tg
{29ECC791-252C-42db-B11E-71ABF51FA479}
The kind of wind generating unit.
windGenUnitType
{CE84D052-100C-4ce8-AC2A-9A9DEEA8DE18}
Wind generator type 1 or type 2 model with which this wind mechanical model is associated.
WindTurbineType1or2IEC
{36490F42-A405-4d4a-B4FD-D070F544D39F}.SupplierEnd
Wind turbine type 3 model with which this wind mechanical model is associated.
WindTurbineType3IEC
{6DFF546C-9D1C-42e3-B137-EB0D010C21D1}.SupplierEnd
Wind turbine type 4B model with which this wind mechanical model is associated.
WindTurbineType4bIEC
{B31E0647-9F5B-4d5d-91A2-C5F15B48924F}.SupplierEnd
Drive train damping iciisubdrtsubiii. It is a typedependent parameter.
cdrt
{369F30EB-7A69-4d9e-A001-9C38F31FB560}
Inertia constant of generator iHiisubgensubi gt 0. It is a typedependent parameter.
hgen
{A9FDD0FD-16BE-40db-B824-B296BB1A004F}
Inertia constant of wind turbine rotor iHiisubWTRsubi gt 0. It is a typedependent parameter.
hwtr
{CBF4C2E5-978A-4fa6-A500-5CE0B94F0E15}
Drive train stiffness ikiisubdrtsubi. It is a typedependent parameter.
kdrt
{948C22E5-DF89-4497-8AE8-65897DB85495}
The wind dynamics lookup table associated with this pitch control power model.
WindDynamicsLookupTable
{43C4AEB1-F841-4657-AD07-5DCC12ECD3FB}.ClientEnd
Wind turbine type 1B model with which this pitch control power model is associated.
WindGenTurbineType1bIEC
{16C044ED-F9D1-4331-8143-13D0E5D17A9F}.ClientEnd
Wind turbine type 2 model with which this pitch control power model is associated.
WindGenTurbineType2IEC
{9D56255A-58CA-4569-AC81-725F7E0262B0}.SupplierEnd
Rate limit for increasing power idpiisubmaxsubi gt WindPitchContPowerIEC.dpmin. It is a typedependent parameter.
dpmax
{54AC2D61-B542-48fc-BC5E-9E5BB8D8EB6F}
Rate limit for decreasing power idpiisubminsubi lt WindPitchContPowerIEC.dpmax. It is a typedependent parameter.
dpmin
{D8E76175-17AF-405a-9F10-9FD1D51D3305}
Minimum power setting ipiisubminsubi. It is a typedependent parameter.
pmin
{F210E10E-FA24-4778-B1D4-3064A7CB0D02}
If ipiisubinitsubisub sublt ipiisubsetsubisub subthen power will be ramped down to ipiisubminsubi. It is ipiisubsetsubi in the IEC 614002712015. It is a typedependent parameter.
pset
{6914DA61-3243-4294-935E-DB35E6CF9020}
Lag time constant iTiisub1subi gt 0. It is a typedependent parameter.
t1
{2731822F-1E6C-4215-BEBD-DAB989F6E305}
Voltage measurement time constant iTiisubrsubi gt 0. It is a typedependent parameter.
tr
{3D85E934-89B4-4c33-9004-860CECC24306}
Dip detection threshold iuiisubUVRTsubi. It is a typedependent parameter.
uuvrt
{ED9AB655-E925-4ccd-B58B-4BDD30C42195}
The remote signal with which this power plant is associated.
RemoteInputSignal
{A386534A-CECA-4cf5-B0FB-5C4A4D5EA497}.SupplierEnd
The wind turbine type 3 or type 4 associated with this wind plant.
WindTurbineType3or4Dynamics
{C63D4493-2486-43ff-9F01-3552D8AA93FE}.SupplierEnd
The wind dynamics lookup table associated with this frequency and active power wind plant model.
WindDynamicsLookupTable
{270439E2-372B-4fe6-97E5-0B33363C463D}.ClientEnd
Wind plant model with which this wind plant frequency and active power control is associated.
WindPlantIEC
{2E9106F6-53D0-4e64-ADF7-56F69BF49942}.SupplierEnd
Maximum ramp rate of ipiisubWTrefsubi request from the plant controller to the wind turbines idpiisubrefmaxsubi gt WindPlantFreqPcontrolIEC.dprefmin. It is a casedependent parameter.
dprefmax
{DF676706-43EC-42b9-BA95-B3125ABBF2C8}
Minimum negative ramp rate of ipiisubWTrefsubi request from the plant controller to the wind turbines idpiisubrefminsubi lt WindPlantFreqPcontrolIEC.dprefmax. It is a projectdependent parameter.
dprefmin
{7124716F-E419-4411-B4AD-302B0E5509B4}
Maximum positive ramp rate for wind plant power reference idpiisubWPrefmaxsubi gt WindPlantFreqPcontrolIEC.dpwprefmin. It is a projectdependent parameter.
dpwprefmax
{F89C74D5-4443-4634-84C2-9B5BD9A54042}
Maximum negative ramp rate for wind plant power reference idpiisubWPrefminsubi lt WindPlantFreqPcontrolIEC.dpwprefmax. It is a projectdependent parameter.
dpwprefmin
{7A99CB00-42BE-451d-84B0-B7992628CAB4}
Maximum PI integrator term iKiisubIWPpmaxsubi gt WindPlantFreqPcontrolIEC.kiwppmin. It is a projectdependent parameter.
kiwppmax
{B92C5A9F-0F1B-4e72-B16F-5AA9A81CA0BC}
Minimum PI integrator term iKiisubIWPpminsubi lt WindPlantFreqPcontrolIEC.kiwppmax. It is a projectdependent parameter.
kiwppmin
{FEEDDDF7-D54E-456b-A47D-47F55ED44CB1}
Power reference gain iKiisubWPprefsubi. It is a projectdependent parameter.
kwppref
{723F66A9-EB7D-4d64-8005-EEECE80C7ED6}
Maximum ipiisubWTrefsubi request from the plant controller to the wind turbines ipiisubrefmaxsubi gt WindPlantFreqPcontrolIEC.prefmin. It is a projectdependent parameter.
prefmax
{06F0FC1F-537C-423e-A07B-9BD5FCC4AE4C}
Minimum ipiisubWTrefsubi request from the plant controller to the wind turbines ipiisubrefminsubi lt WindPlantFreqPcontrolIEC.prefmax. It is a projectdependent parameter.
prefmin
{1790AB59-133A-47aa-A5B1-5A00821D84CB}
Lead time constant in reference value transfer function iTiisubpftsubi gt 0. It is a projectdependent parameter.
tpft
{FB37D3E3-0C6F-46e1-9FC8-D84EB4B4C16E}
Lag time constant in reference value transfer function iTiisubpfvsubi gt 0. It is a projectdependent parameter.
tpfv
{9ABA17F1-800C-495d-8AF8-4446EC9D48AC}
Filter time constant for frequency measurement iTiisubWPffiltpsubi gt 0. It is a projectdependent parameter.
twpffiltp
{278C7EB3-E847-4d13-8943-BB8F227C20B9}
Filter time constant for active power measurement iTiisubWPpfiltpsubi gt 0. It is a projectdependent parameter.
twppfiltp
{1202D059-C098-428b-BE09-7F81B35270A7}
Wind plant frequency and active power control model associated with this wind plant.
WindPlantFreqPcontrolIEC
{2E9106F6-53D0-4e64-ADF7-56F69BF49942}.ClientEnd
Wind plant model with which this wind reactive control is associated.
WindPlantReactiveControlIEC
{106A7682-9DCE-4670-B630-80B1555E4A66}.SupplierEnd
The wind dynamics lookup table associated with this voltage and reactive power wind plant model.
WindDynamicsLookupTable
{28BA1D32-A6C1-4d3c-9E93-99FC047529D4}.ClientEnd
Wind plant reactive control model associated with this wind plant.
WindPlantIEC
{106A7682-9DCE-4670-B630-80B1555E4A66}.ClientEnd
Maximum positive ramp rate for wind turbine reactive powervoltage reference idxiisubrefmaxsubi gt WindPlantReactiveControlIEC.dxrefmin. It is a projectdependent parameter.
dxrefmax
{9F1D6E92-6885-41ea-8EE5-67FBD0E68DB2}
Maximum negative ramp rate for wind turbine reactive powervoltage reference idxiisubrefminsubi lt WindPlantReactiveControlIEC.dxrefmax. It is a projectdependent parameter.
dxrefmin
{24CB0B9C-3538-46ad-844C-2F5A219B4A25}
Maximum reactive powervoltage reference from integration iKiisubIWPxmaxsubi gt WindPlantReactiveControlIEC.kiwpxmin. It is a projectdependent parameter.
kiwpxmax
{993C9A59-F78F-413b-86BE-BF639E98C5D5}
Minimum reactive powervoltage reference from integration iKiisubIWPxminsubi lt WindPlantReactiveControlIEC.kiwpxmax. It is a projectdependent parameter.
kiwpxmin
{1069CA82-358B-476f-91D5-393BEEA774B0}
Reactive power reference gain iKiisubWPqrefsubi. It is a projectdependent parameter.
kwpqref
{BE64B7B0-90C8-4ad2-A140-1DD896EB3B3C}
Plant voltage control droop iKiisubWPqusubi. It is a projectdependent parameter.
kwpqu
{338E6148-4BF5-4cb9-A6CA-6DECD750181E}
Filter time constant for voltagedependent reactive power iTiisubuqfiltsubi gt 0. It is a projectdependent parameter.
tuqfilt
{0E36E3C6-74B5-487e-B772-0AEDF1CE4265}
Filter time constant for active power measurement iTiisubWPpfiltqsubi gt 0. It is a projectdependent parameter.
twppfiltq
{C06F778B-75BD-495e-A8AB-C6D244929E0C}
Filter time constant for reactive power measurement iTiisubWPqfiltqsubi gt 0. It is a projectdependent parameter.
twpqfiltq
{9CC1ECD7-3B56-467c-96CF-45783C2ABC0E}
Filter time constant for voltage measurement iTiisubWPufiltqsubi gt 0. It is a projectdependent parameter.
twpufiltq
{AB6C51D7-2DD3-4740-AE4F-EA58E97FC69B}
Lead time constant in reference value transfer function iTiisubxftsubi gt 0. It is a projectdependent parameter.
txft
{B724D26E-37B7-4379-A607-97AC1B1FF19F}
Lag time constant in reference value transfer function iTiisubxfvsubi gt 0. It is a projectdependent parameter.
txfv
{B1849A88-6791-4bda-B74C-2ECD83274551}
Voltage threshold for UVRT detection in Q control iuiisubWPqdipsubi. It is a projectdependent parameter.
uwpqdip
{2951891F-CF05-4f6c-8E52-C69CE3AA2F5D}
Reactive powervoltage controller mode iMiisubWPqmodesubi. It is a casedependent parameter.
windPlantQcontrolModesType
{781C9B32-D351-40f8-8DE5-D353D49C6336}
Maximum ixisubWTrefsub iqiisubWTrefsubi or deltai uiisubWTrefsubi request from the plant controller ixiisubrefmaxsubi gt WindPlantReactiveControlIEC.xrefmin. It is a casedependent parameter.
xrefmax
{C90EBAB3-10ED-4d50-9ADD-68C6C07F9095}
Minimum ixiisubWTrefsubi iqiisubWTrefsubi or delta iuiisubWTrefsubi request from the plant controller ixiisubrefminsubi lt WindPlantReactiveControlIEC.xrefmax. It is a projectdependent parameter.
xrefmin
{86A3E49F-1059-4956-A437-A29B97281E4E}
Parameter of this proprietary userdefined model.
ProprietaryParameterDynamics
{92B518F0-1BFC-4f7d-A5E3-B076C3298208}.SupplierEnd
The wind dynamics lookup table associated with this grid protection model.
WindDynamicsLookupTable
{C3C3FBA5-3DF3-43fb-B61D-884F27F86A76}.ClientEnd
Wind generator type 1 or type 2 model with which this wind turbine protection model is associated.
WindTurbineType1or2IEC
{3C3632FA-BE2B-49dd-88C8-E46159B964DB}.SupplierEnd
Wind generator type 3 or type 4 model with which this wind turbine protection model is associated.
WindTurbineType3or4IEC
{4FAB4F77-0662-42f6-B383-068B941B8877}.SupplierEnd
Maximum rate of change of frequency idFiisubmaxsubi. It is a typedependent parameter.
dfimax
{33D75444-7D6A-428a-9610-75BAA1C915DB}
Wind turbine over frequency protection activation threshold ifiisuboversubi. It is a projectdependent parameter.
fover
{3723800E-4BF0-495f-9656-051631E77E0D}
Wind turbine under frequency protection activation threshold ifiisubundersubi. It is a projectdependent parameter.
funder
{10EFDEC9-54EB-4da0-BFFF-BFBDE01EB834}
Time interval of moving average window iTfMAi gt 0. It is a typedependent parameter.
tfma
{A632CA90-2955-4def-A008-8B96B473EC14}
Wind turbine over voltage protection activation threshold iuiisuboversubi. It is a projectdependent parameter.
uover
{B83AD84B-CECC-43e4-9393-26A1F999D3F6}
Wind turbine under voltage protection activation threshold iuiisubundersubi. It is a projectdependent parameter.
uunder
{C463FC22-9EFA-4066-A905-1584D805AE36}
Wind turbine type 3 or type 4 model with which this reference frame rotation model is associated.
WindTurbineType3or4IEC
{2F7B4345-63FE-4a94-A3A0-0FA22E7F9E64}.SupplierEnd
Time constant for PLL first order filter model iTiisubPLLsubi gt 0. It is a typedependent parameter.
tpll
{EDD13201-A420-4b3e-9242-2CFC69E652B1}
Voltage below which the angle of the voltage is filtered and possibly also frozen iuiisubPLL1subi. It is a typedependent parameter.
upll1
{D603B0E1-CB76-4840-B001-926357BDA7EE}
Voltage iuiisubPLL2subi below which the angle of the voltage is frozen if iuiisubPLL2subisub subis smaller or equal to iuiisubPLL1subi . It is a typedependent parameter.
upll2
{1B636322-5BAF-4600-876E-8DEF619CA9F1}
Asynchronous machine model with which this wind generator type 1 or type 2 model is associated.
AsynchronousMachineDynamics
{28333A44-C128-4d1f-91A9-C4815D05A17C}.SupplierEnd
Remote input signal used by this wind generator type 1 or type 2 model.
RemoteInputSignal
{87FA8C90-E6B5-40bb-A4FC-AD947AB5E303}.SupplierEnd
Wind mechanical model associated with this wind generator type 1 or type 2 model.
WindMechIEC
{36490F42-A405-4d4a-B4FD-D070F544D39F}.ClientEnd
Wind turbune protection model associated with this wind generator type 1 or type 2 model.
WindProtectionIEC
{3C3632FA-BE2B-49dd-88C8-E46159B964DB}.ClientEnd
Wind aerodynamic model associated with this wind generator type 3 model.
WindAeroOneDimIEC
{0A379016-96C1-4d07-8589-6AE172CD1DA8}.ClientEnd
Wind aerodynamic model associated with this wind turbine type 3 model.
WindAeroTwoDimIEC
{A9340DAA-2D75-4953-8AB2-F705D0EF27D6}.ClientEnd
Wind control P type 3 model associated with this wind turbine type 3 model.
WindContPType3IEC
{1125BB6A-BC13-4945-8BBC-ABB49A1938CE}.ClientEnd
Wind control pitch angle model associated with this wind turbine type 3.
WindContPitchAngleIEC
{6C1D2665-2EAD-48e1-8020-FED105CE3F96}.ClientEnd
Wind generator type 3 model associated with this wind turbine type 3 model.
WindGenType3IEC
{46227D47-50B8-490b-A51B-3E8D8812364C}.ClientEnd
Wind mechanical model associated with this wind turbine type 3 model.
WindMechIEC
{6DFF546C-9D1C-42e3-B137-EB0D010C21D1}.ClientEnd
The power electronics connection associated with this wind turbine type 3 or type 4 dynamics model.
PowerElectronicsConnection
{55DFB003-A30A-4242-A110-1251E461ED28}.SupplierEnd
Remote input signal used by these wind turbine type 3 or type 4 models.
RemoteInputSignal
{6BAC6893-7D0D-407c-903E-4E5F0755C0CE}.SupplierEnd
The wind plant with which the wind turbines type 3 or type 4 are associated.
WindPlantDynamics
{C63D4493-2486-43ff-9F01-3552D8AA93FE}.ClientEnd
Wind control Q model associated with this wind turbine type 3 or type 4 model.
WIndContQIEC
{30981A01-0238-4403-ADC6-906C4187F62A}.ClientEnd
Wind control current limitation model associated with this wind turbine type 3 or type 4 model.
WindContCurrLimIEC
{B15E3709-C78C-4e94-AF81-81277B45B7F1}.ClientEnd
Constant Q limitation model associated with this wind generator type 3 or type 4 model.
WindContQLimIEC
{0017E503-888C-407e-A297-BB307A040C9A}.ClientEnd
QP and QU limitation model associated with this wind generator type 3 or type 4 model.
WindContQPQULimIEC
{B403375C-0F8C-45f3-92A9-700935E21AD2}.ClientEnd
Wind turbune protection model associated with this wind generator type 3 or type 4 model.
WindProtectionIEC
{4FAB4F77-0662-42f6-B383-068B941B8877}.ClientEnd
Reference frame rotation model associated with this wind turbine type 3 or type 4 model.
WindRefFrameRotIEC
{2F7B4345-63FE-4a94-A3A0-0FA22E7F9E64}.ClientEnd
Wind generator type 3A model associated with this wind turbine type 4 model.
WindGenType3aIEC
{CADDE3B0-B9F9-4524-8093-96B4A07DCEB0}.ClientEnd
Wind control P type 4A model associated with this wind turbine type 4A model.
WindContPType4aIEC
{DA5D31C7-93C5-460a-887B-F6F3620C8AB7}.ClientEnd
Wind generator type 4 model associated with this wind turbine type 4A model.
WindGenType4IEC
{11A4D311-CB84-4368-A12C-4259083A726C}.ClientEnd
Wind control P type 4B model associated with this wind turbine type 4B model.
WindContPType4bIEC
{674DEC61-D931-4c8f-95C6-127BDFBD3C9A}.ClientEnd
Wind generator type 4 model associated with this wind turbine type 4B model.
WindGenType4IEC
{CF7D044B-E56E-4d33-ABD3-F06CEB5C6888}.ClientEnd
Wind mechanical model associated with this wind turbine type 4B model.
WindMechIEC
{B31E0647-9F5B-4d5d-91A2-C5F15B48924F}.ClientEnd
Parameter of this proprietary userdefined model.
ProprietaryParameterDynamics
{88DDF410-39C9-46c0-AC56-EC92DA7D9E97}.SupplierEnd
Parameter of this proprietary userdefined model.
ProprietaryParameterDynamics
{7F96DE9C-5421-45cc-A5C5-B8C03C2B4B23}.SupplierEnd
FromWinding
{85692DA6-1368-431a-B29A-40C8C1AD42B8}.SupplierEnd
ToWinding
{F014FE41-F5D2-4748-870B-0A78530405BD}.SupplierEnd
TransformerObservation
{97F8FF5D-183D-4b1c-B364-25B5C98E0F5F}.ClientEnd
As of statusDate the leakage reactance measured at the from winding with the to winding shortcircuited and all other windings opencircuited.
leakageReactance
{B02F7CD4-B6E4-4c25-99AD-E47B4D2E43F2}
status
{7C859540-4B46-401f-A3F9-4B4358A6FAC9}
Per length line parameter associated with this wire assembly.
PerLengthLineParameter
{07F81D46-A7D6-403d-9687-5A39ABF063FB}.SupplierEnd
Wire phase information associated with this wire assembly.
WirePhaseInfo
{E3D703D3-3A7D-42e4-A77D-C721E2D255F0}.ClientEnd
ACLineSegmentPhase
{B5F55F86-9C19-4914-99C2-1ACBA0197A2E}.ClientEnd
Wire phase information associated with this wire information.
WirePhaseInfo
{BCFA8491-3B39-46bd-8D33-37BC4F2F5259}.SupplierEnd
if there is a different core material Radius of the central core.
coreRadius
{965E91D6-A32D-4947-9716-E47B628E4569}
Geometric mean radius. If we replace the conductor by a thin walled tube of radius GMR then its reactance is identical to the reactance of the actual conductor.
gmr
{906DF7D6-9FAF-4a39-85BF-B80EFEB2665D}
if insulated conductor Material used for insulation.
insulationMaterial
{07B5CBFF-F12B-4352-8ABB-713BA7EF186B}
if insulated conductor Thickness of the insulation.
insulationThickness
{D6A74A69-23AC-4736-AA86-7450B4629D48}
Conductor material.
material
{111A854C-ED35-40aa-81ED-EC3F0BCA37EE}
AC resistance per unit length of the conductor at 25 C.
rAC25
{C90C8E7D-13A7-4e41-92B3-F93765F97436}
AC resistance per unit length of the conductor at 50 C.
rAC50
{804728E3-F54E-4655-91A3-2BDE96A91D5C}
AC resistance per unit length of the conductor at 75 C.
rAC75
{61931852-3E39-4ad6-BEF3-B8199E448CF7}
DC resistance per unit length of the conductor at 20 C.
rDC20
{6A3C81F3-B595-4d5d-A45A-39FDFF55105D}
Outside radius of the wire.
radius
{664AAFE3-E0AF-4ce5-B4EA-144630C22698}
Current carrying capacity of the wire under stated thermal conditions.
ratedCurrent
{870797AC-296B-476f-8DFC-B05E8FE8F90A}
Wire assembly information using this wire phase information.
WireAssemblyInfo
{E3D703D3-3A7D-42e4-A77D-C721E2D255F0}.SupplierEnd
Wire information contributing to this wire phase information.
WireInfo
{BCFA8491-3B39-46bd-8D33-37BC4F2F5259}.ClientEnd
Wire position with this wire phase information.
WirePosition
{50E5B6AE-D7FB-4224-829C-5C6DF11ADD61}.ClientEnd
Phase information.
phaseInfo
{266D8E98-246C-48cd-826A-7D0C07C09D8C}
Wire phase information for this wire position.
WirePhaseInfo
{50E5B6AE-D7FB-4224-829C-5C6DF11ADD61}.SupplierEnd
Wire spacing data this wire position belongs to.
WireSpacingInfo
{BC21C0DF-A6A4-48a0-A740-0369DB2A9ECA}.ClientEnd
Signed horizontal distance from the wire at this position to a common reference point.
xCoord
{D8D120C8-F5D4-443d-9956-561B67DB5A4C}
Signed vertical distance from the wire at this position above ground positive value or burial depth below ground negative value.
yCoord
{B0FE6241-691B-4f0b-B8ED-B3FB7916A7C9}
The wire segment phases which belong to the wire segment.
WireSegmentPhases
{0431D530-090C-4821-A609-681E0D77E2EF}.ClientEnd
The wire segment to which the phase belongs.
WireSegment
{0431D530-090C-4821-A609-681E0D77E2EF}.SupplierEnd
The phase connection of the wire at both ends.
phase
{87D543DC-B9E0-4f0d-83F6-B7330796183A}
ACLineSegment
{F29D4402-D392-434d-9E98-8C35F21BD856}.ClientEnd
DuctBank
{18C29DE2-77AC-4a90-9E3D-065A8BC002CE}.SupplierEnd
Structures
{7995689F-9BD5-49e1-BAE8-C986A5446310}.SupplierEnd
All positions of single wires phase or neutral making the conductor.
WirePositions
{BC21C0DF-A6A4-48a0-A740-0369DB2A9ECA}.SupplierEnd
Distance between wire subconductors in a symmetrical bundle.
phaseWireSpacing
{2FAEA954-5307-42ee-8782-30DA4AAF0D8B}
Usage of the associated wires.
usage
{FE991EA9-B3BD-46a6-93EB-DD9AA4599065}
All appointments for this work.
Appointments
{A1F0785E-E4E6-4ce3-8297-16F47D531998}.ClientEnd
BusinessCase
{9F2397D7-15D3-42a6-9C58-F7D06A58CEAF}.ClientEnd
All the customers for which this work is performed.
Customers
{07E56F99-F27D-4363-90E9-D912F7C8DEC7}.ClientEnd
Designs
{B42E2297-AE8B-42e0-A3FF-529C6B2C87D8}.ClientEnd
ErpProjectAccounting
{09AE0E89-9CDA-4e45-9D26-E7A6B10F9B3A}.SupplierEnd
All incidents being addressed by this work.
Incidents
{49B9A841-26C8-423d-94AD-33ADD3293D00}.ClientEnd
Project
{FD74BD30-960D-447e-B2BA-F87F95FF9001}.SupplierEnd
WorkBillingInfo
{D0B05EFE-A8D0-4d29-A1FA-53015A22BA40}.ClientEnd
WorkCostDetails
{D2FB8A1E-45DF-418c-A043-681494BF85D6}.ClientEnd
WorkFlowSteps
{976229E2-09D8-43d8-95CA-98BF57DBCB3F}.ClientEnd
All tasks in this work.
WorkTasks
{ED65B7F6-9AFD-4fe0-909C-79D02AA238C6}.SupplierEnd
Base work that this activity record tracks.
BaseWork
{916C5FEE-0A53-4844-A34C-EA28BF6FA153}.ClientEnd
Estimated percentage of completion of this individual work task or overall work order.
percentComplete
{700DE45F-5134-4996-A064-363FFE94C67F}
CUWorkEquipmentAsset
{855EE031-A0C0-4d02-9660-78C8C2427736}.ClientEnd
Crew using this work asset.
Crew
{762660F7-4910-42bc-8748-C7841507E17A}.SupplierEnd
CustomerAccount
{86A9BD70-A4A7-4530-B205-5F62F9C1C7DB}.ClientEnd
ErpLineItems
{A0C60390-969D-4a91-B406-83ABE393F0BC}.SupplierEnd
Works
{D0B05EFE-A8D0-4d29-A1FA-53015A22BA40}.SupplierEnd
Estimated cost for work.
costEstimate
{F8C8B691-3F1E-424b-9846-EB5C21B24526}
Amount of price on deposit.
deposit
{A77E8600-D046-4583-A9B3-B7FD474EC97E}
Amount of bill.
workPrice
{3D621E83-F3CE-4f1b-9D19-54ED66CD1AFC}
ContractorItems
{96CD6C4B-B625-48f2-823B-F52CD16FCC1F}.SupplierEnd
CostType
{5446E847-F2C9-4006-ABE5-5682B880301D}.ClientEnd
Design
{80D53051-C6F7-4c80-B186-FF6AFCC33A66}.ClientEnd
ErpProjectAccounting
{4005B7A5-5B74-4c65-921E-9254AAD5A266}.SupplierEnd
LaborItems
{955B011F-CCEE-4126-A607-513F05388ADE}.ClientEnd
MiscCostItems
{D3D92A8C-C7B5-4a95-B1BF-113EA20D2A57}.ClientEnd
OverheadCost
{C5ADCDD4-2638-408f-9377-13A155EB81D7}.ClientEnd
PropertyUnits
{A4CC1ED7-99AE-40a3-8386-8274E4C431D9}.SupplierEnd
WorkCostSummary
{850D5F1D-AAAC-4e12-8DCC-C3750ED1C33E}.SupplierEnd
WorkTask
{7F10B6C7-082B-4d2d-B95B-E5DF634041D3}.SupplierEnd
Works
{D2FB8A1E-45DF-418c-A043-681494BF85D6}.SupplierEnd
Amount in designated currency for work either a total or an individual element. As defined in the attribute type multiple instances are applicable to each work for planned cost actual cost authorized cost budgeted cost forecasted cost other.
amount
{D5667FFB-6C42-4ee0-A4F6-888B57A3E00D}
WorkCostDetail
{850D5F1D-AAAC-4e12-8DCC-C3750ED1C33E}.ClientEnd
Work
{976229E2-09D8-43d8-95CA-98BF57DBCB3F}.SupplierEnd
WorkTasks
{C76E630D-24B2-45f0-8B97-801F51060C44}.SupplierEnd
status
{6C297E5A-2A72-46bc-82B5-CBEFD34D4467}
All workstasks at this location.
BaseWorks
{4674DC66-FC6D-4b4e-B78A-2BA63838F75D}.ClientEnd
DesignLocations
{A50D6CAA-AFDC-4c79-A4FF-B15AE7381D4F}.ClientEnd
OneCallRequest
{ECA7D24D-E18E-412d-BD83-31B1B68A4448}.SupplierEnd
All assets on which this nonreplacement work task is performed.
Assets
{7D2E82EC-1CC5-4b1b-8FF3-DFA1835C7E49}.SupplierEnd
All crews participating in this work task.
Crews
{D3920004-AE6C-439a-9CED-543CFED22657}.SupplierEnd
MaterialItems
{BFEEB8FC-4560-4027-829D-304562ADB795}.SupplierEnd
Old asset replaced by this work task.
OldAsset
{DEDB052F-30DA-4503-94F8-99F03155CB7F}.SupplierEnd
Procedure data set associated with this work task.
ProcedureDataSet
{78EB6E9E-9B0C-466e-B813-E041B622EF3D}.ClientEnd
Switching plan executed by this work task.
SwitchingPlan
{1B1B92E7-633C-4e30-BCDE-9C62496BE1E8}.ClientEnd
TroubleOrder
{0C2AE19D-0F46-483f-BA2C-8AFA95A466F6}.SupplierEnd
Work this task belongs to.
Work
{ED65B7F6-9AFD-4fe0-909C-79D02AA238C6}.ClientEnd
Total contractor costs associated with the work task.
contractorCost
{096BB856-397D-4299-904E-22B047F523E3}
Total labor costs associated with the work task.
laborCost
{77174F8A-39D7-4eea-B1B5-FFBBABE95B0C}
Hours of labor expended under work task.
laborHours
{215CD2C9-2733-44e2-A029-378B553D8A9C}
Total material costs associated with the work task.
materiallCost
{25935B2D-841E-4212-9977-5CC1A72F0BA1}
Kind of work.
taskKind
{FC77B89B-160A-4b34-A904-FBE58286E2DD}
Total tool costs associated with the work task.
toolCost
{24C72508-3BC3-48ed-81FF-03888AA03695}
Time schedule for this work or work task.
BaseWork
{43F7FE4D-DD21-436e-B70A-E2FCDD0B6928}.ClientEnd
Kind of this work schedule.
kind
{A628C0AD-7505-49dc-91CA-79B391A9B325}
Actual work time schedule.
actual
{4A7DDC08-A33B-496a-8109-F9DEDDED28BD}
Earliest work time schedule.
earliest
{D71C72B0-9ADF-4a16-98E1-633DC4710A26}
Estimate work time schedule.
estimate
{B3081235-198B-47da-8187-C425BA576FDE}
??.
immediate
{486D7F9D-18E4-4630-9AAA-7659CDD82270}
Latest work time schedule.
latest
{BF0E733C-C6F7-4251-988E-7C83746A2957}
Request work time schedule.
request
{EA40C9ED-10B3-4898-B316-F6ABB82C3AD6}
Kind of this zone.
kind
{D30C2170-B38E-4bdd-83FD-B530C63C59A2}
Number of valves in the converter. Used in loss calculations.
numberOfValves
{AC44001F-F907-400d-A44D-BE0A7598F930}
The connected status is related to a busbranch model and the topological node to terminal relation. True implies the terminal is connected to the related topological node and false implies it is not. In a busbranch model the connected status is used to tell if equipment is disconnected without having to change the connectivity described by the topological node to terminal relation. A valid case is that conducting equipment can be connected in one end and open in the other. In particular for an AC line segment where the reactive line charging can be significant this is a relevant case.
connected
{C97C0B38-C62F-4f03-A3DE-A67F29A6C6DB}
The orientation of the terminal connections for a multiple terminal conducting equipment. The sequence numbering starts with 1 and additional terminals should follow in increasing order. The first terminal is the starting point for a two terminal branch.
sequenceNumber
{7C7195D3-DFCD-487f-BF92-F359BBE7AFD0}
Number designation for this line segment phase. Each line segment phase within a line segment should have a unique sequence number. This is useful for unbalanced modelling to bind the mathematical model PhaseImpedanceData of PerLengthPhaseImpedance with the connectivity model this class and the physical model WirePosition without tight coupling.
sequenceNumber
{ACC3476D-8979-46f3-A071-224D1BF4D7DD}
The start of the time interval for which requirement is defined.
intervalStartTime
{1DD465A4-D2D9-477f-9D94-80BA3A7DC1BC}
Date and time the asset was last tested using the type of test and yielding the current status in success attribute.
dateTime
{4FFD9786-EEFF-4620-AE9B-9D17639880AF}
True if asset has passed acceptance test and may be placed in or is in service. It is set to false if asset is removed from service and is required to be tested again before being placed back in service possibly in a new location. Since asset may go through multiple tests during its lifecycle the date of each acceptance test may be recorded in Asset.ActivityRecord.status.dateTime.
success
{FB62E81E-63EF-4f9c-A355-6F288D9A581E}
Type of test or group of tests that was conducted on dateTime.
type
{0FEE3FD2-7D70-4ee4-8264-CFF85F657565}
Permit application number that is used by municipality state province etc.
applicationNumber
{638E86A6-F326-4891-9820-734B3C29E3E0}
Date that permit became official.
effectiveDate
{23C8867D-3537-4ce8-AD94-24B52A542A03}
Permit expiration date.
expirationDate
{8C159495-EDF9-470e-B98C-77196502DDF1}
Permit identifier.
permitID
{C463DA91-790E-4181-A1D8-4F60DCEC46B8}
Date and time when the creditdebit transaction was performed.
dateTime
{D0D262E8-C251-4552-8F93-7BBDA4AD410E}
Reason for creditdebit transaction on an account. Example payment receivedarrears interest levied.
reason
{646CDE04-FEFD-411f-898E-99C1E725D1BE}
customerNotificationType
{E31C32A9-6C3E-4cbe-9FE4-47D5532BEDE1}
methodType
{F529C151-5EB1-423d-B977-50109A986953}
note
{7A8608D2-F76A-4199-98B0-453D3F56A324}
time
{97B57200-C543-4c9f-AAA4-10DF8FE318F5}
Value expressed in applicable units.
value
{6A47AA12-0575-4d16-BAF8-F4CE2E654209}
Normal value range maximum for any of the MeasurementValue.values. Used for scaling e.g. in bar graphs or of telemetered raw values.
maxValue
{7C9AE84F-6621-4dae-9591-C303B417B3B3}
The value to supervise against. The value is positive.
value
{C965BF25-FBC7-4cec-B39F-CC8CDD3CD272}
The value to supervise. The value is positive.
value
{14D2EFFB-6096-4cde-9CF3-02655CBB9C5A}
The coded type of an ACE tariff.
type
{32E9FECB-0B8B-4475-AB18-395F6FCFF767}
value
{133597D7-9050-4335-B968-86AF7E16558C}
value
{9AC71195-FE05-4022-805D-524DFF496593}
value
{4A5E6FCF-E14C-413e-A596-5EA78FA133AB}
value
{358E511C-E364-4c9f-BB02-83A1E5F56D53}
Date and time this activity record has been created different from the status.dateTime which is the time of a status change of the associated object if applicable.
createdDateTime
{6F7593D9-FC41-4433-8F90-A5A84FE358A5}
Reason for event resulting in this activity record typically supplied when user initiated.
reason
{AD0CAFF7-7E64-4631-8F4C-8B76E7158CE4}
Severity level of event resulting in this activity record.
severity
{07741B27-D453-4dea-80B0-7ADE4E72D9F2}
Type of event resulting in this activity record.
type
{C48CB2C9-BE6B-4cd8-A666-75BE5D047A78}
Loss percentage
lossPercentage
{B1883E0B-026C-4ff7-BF30-14B10E88E33F}
value
{BC1D6C27-8993-488f-BD6F-E0AD0C4FB6A8}
Processing Order for AS selfprovisions for this region. The priority of this attribute directs the awards of any resource that resides in overlapping regions. The regions are processed in priority manner.
qualifASOrder
{90FE8C49-0ACA-4f26-A45C-EFAC1E87AB8C}
Date this agreement was consummated among associated persons andor organisations.
signDate
{461C5BAD-289C-4d31-8D8E-539470E30A5B}
Rating of the CAES air compressor.
airCompressorRating
{504D5BD8-A892-4fbc-9600-A6E90BE3D29F}
The version of the named list of alert types.
version
{AC598F14-4F3D-4ee8-99D7-FF5D9E3345AB}
intervalStartTime
{4B38B663-CA9A-4c0d-9A83-2B6DBA87F560}
updateTimeStamp
{AF94F466-B0CE-4eb5-B240-DC456C2CE0F4}
updateUser
{76E870E7-3A82-46e5-95E0-894823AC4C28}
1 Detail2 Aggregate by Market service type in which case the AllocationEnergyType field will not be filled3 Aggregate by AllocationEnergyType in which case MarketServiceType will not be filled.
aggregateType
{66B1BD07-4C8C-4f88-8F29-F092E5572C08}
allocationMwHour
{74E47F30-E3A2-4739-B8EE-7038835EA041}
allocationPrice
{8BA67A40-9EC3-4a9a-BC7B-9B5DD8072ED6}
energyTypeCode
{426CE882-051B-4ea0-BEFF-5DF239659D15}
Choices are ME Market Energy Capacity SR Spinning Reserve Capacity NR NonSpinning Reserve Capacity DAC Day Ahead Capacity DEC Derate Capacity
marketServiceType
{B1371B63-8BAD-4f4b-9EF5-18A9C9B3938D}
Priority of a measurement usage. Lower numbers have first priority.
priority
{A30AB6E8-0C11-4b5e-A030-8E3A69991E1D}
Priority of a measurement usage. Lower numbers have first priority.
priority
{E7365964-FC6E-4f3c-83E9-CF4A6AB953C2}
Normal value range maximum for any of the MeasurementValue.values. Used for scaling e.g. in bar graphs or of telemetered raw values.
maxValue
{82692D33-57C7-408c-86B0-29998C3189F9}
Normal value range minimum for any of the MeasurementValue.values. Used for scaling e.g. in bar graphs or of telemetered raw values.
minValue
{E3279DF2-4529-48c9-9820-A1B69188431D}
Normal measurement value e.g. used for percentage calculations.
normalValue
{F093581C-DE48-4c14-963A-34C739750A61}
If true then this measurement is an active power reactive power or current with the convention that a positive value measured at the Terminal means power is flowing into the related PowerSystemResource.
positiveFlowIn
{25855E61-5D6B-4b06-A221-C580AF35A5D5}
Normal value range maximum for any of the Control.value. Used for scaling e.g. in bar graphs.
maxValue
{0E31E9A4-3EF8-48cc-AF43-93B68C8F87BC}
Normal value range minimum for any of the Control.value. Used for scaling e.g. in bar graphs.
minValue
{B703E8A4-DB01-4e17-BD8F-69B24966EB57}
The value to supervise against.
value
{095EE989-237B-444f-88E6-78DD83F64E72}
The quality code for the given Analog Value.
scadaQualityCode
{E6C4FFA1-E8D5-4d92-8FC9-1516439C6642}
The value to supervise.
value
{833E2600-DFEE-47d8-BF8D-13A23E5031B1}
Value that indicates best possible numeric value.
bestValue
{63E9A77F-F0DA-4f43-849B-D027BFF23496}
Value that indicates worst possible numeric value.
worstValue
{E6E4B735-6DE7-4346-A296-8758122F1E47}
Timestamp of when the score was calculated.
calculationDateTime
{FCBF2F60-C576-4a77-B610-A91925ACE5C9}
Datetime for when the score applies.
effectiveDateTime
{FD394C10-1CFE-48ec-94B4-28E94182ABAD}
Asset health score value.
value
{6AEDFCE0-E9ED-41ff-80D6-46CDA5857E37}
value
{8C467CE2-6EA5-4aed-810B-32597261DB61}
value
{08CB4299-C5CB-4f08-810B-C8DD2ADB26DA}
value
{FEE24CD4-5876-4e4c-B179-AEAA3E11B738}
True if requested to call customer when someone is about to arrive at their premises.
callAhead
{75D9D80A-694C-4110-B834-9FB7F53C2429}
value
{E8C2C47C-6308-4c7e-BA6A-D38EF8BB0DA9}
The Demand Bid Megawatt for the area case. Attribute Usage This is Scheduled demand MW in Day Ahead
demandBidMW
{5F41DF1F-597A-4b0d-865B-A2428C6A552E}
Description of the object or instance.
Description
{9BF662CF-2D9B-4972-8A6E-BB268C6018B5}
Condition of asset at last baseline. Examples include new rebuilt overhaul required other. Refer to inspection data for information on the most current condition of the asset.
baselineCondition
{4E64DF01-9197-4bf2-8326-BE492F6EB5EA}
True if asset is considered critical for some reason for example a pole with critical attachments.
critical
{C20AB687-5B9D-4140-8BEC-40B09E070FCC}
Lot number for this asset. Even for the same model and version number many assets are manufactured in lots.
lotNumber
{DD5288CC-AFD7-4e0c-9A5A-B458256B1E43}
Position of asset or asset component. May often be in relation to other assets or components.
position
{6E7B8B82-4B2C-40ea-8286-39EB60824436}
Serial number of this asset.
serialNumber
{38BCF463-9045-45f3-A63E-FCB96998A392}
Utilityspecific classification of Asset and its subtypes according to their corporate standards practices and existing IT systems e.g. for management of assets maintenance work outage customers etc..
type
{430B0352-10C7-4708-8348-0C28F4B227CB}
Uniquely tracked commodity UTC number.
utcNumber
{EB657D28-EC57-4cef-8ADD-D8FB40CA2C55}
Detection limit of related analog value if different from detection limit of test standard or if there is no test standard. The detection limit also known as lower limit of detection or limit of detection LOD is the lowest quantity of a substance that can be distinguished from the absence of that substance a blank value within a stated confidence limit generally 1.
detectionLimit
{B296FEE6-A24A-4a6a-9E9B-DD594660185B}
Precision of related analog value if different from precision of test standard or if there is no test standard. Precision is a measure of how closely individual measurements agree with one another. Expressed as plus or minus the value of this attribute.
precision
{1382B91D-DB7A-46b0-B589-10301C17FE2A}
Likelihood of asset failure on a scale of 1low to 100 high.
likelihoodOfFailure
{FD7B3163-8B17-4661-852F-781785047B9C}
Configuration specified for this function.
configID
{20C4F516-9032-481c-B217-8C7A20A54CA6}
Firmware version.
firmwareID
{959DAD9B-DB45-48e8-B4DF-D106B51609CD}
Hardware version.
hardwareID
{FFA0EE8C-88E7-4378-A382-1C59122AD090}
Password needed to access this function.
password
{142745A0-00EA-415a-8DE5-3EEC3A15711E}
Name of program.
programID
{C6816BDF-8DBD-4a3b-92D1-16CD48E4C4A7}
Recommendation for action.
actionRecommendation
{F54E17E8-8CB8-4857-83F6-B606A38380AA}
Time horizon for action.
actionTimeline
{ED7A149B-0858-4be4-8F4C-0AE5A6DF345D}
The date and time when the event is effective.
effectiveDateTime
{2A874A3E-1E10-4dac-8352-D575F026E687}
Indicates whether the machine is a converter fed drive. Used for short circuit data exchange according to IEC 60909.
converterFedDrive
{2D0ABFAD-5524-4839-992E-427EDB49569A}
Ratio of lockedrotor current to the rated current of the motor IaIr. Used for short circuit data exchange according to IEC 60909.
iaIrRatio
{6B830706-4F9D-40d7-BB25-9CB32BE5982F}
Number of pole pairs of stator. Used for short circuit data exchange according to IEC 60909.
polePairNumber
{C2D7D457-6BD4-436b-8F2A-17AD64AC94CB}
Indicates for converter drive motors if the power can be reversible. Used for short circuit data exchange according to IEC 60909.
reversible
{D064CD3B-17AA-4a0e-9F52-2C43776FC32F}
Locked rotor ratio RX. Used for short circuit data exchange according to IEC 60909.
rxLockedRotorRatio
{CF346A15-5379-44bf-B21A-3AFD391B6F47}
Behaviour is based on a proprietary model as opposed to a detailed model.true userdefined model is proprietary with behaviour mutually understood by sending and receiving applications and parameters passed as general attributesfalse userdefined model is explicitly defined in terms of control blocks and their input and output signals.
proprietary
{D230A2B6-5733-4cfe-B4B0-7796CC5A035F}
The identification of the formal name of an attribute.
attribute
{0FBD59EE-F566-44c4-9C0B-8E10CD91E05E}
The instance value of the attribute.
attributeValue
{AAE2E2E8-DABD-4ba1-83AE-F05F2DAB5035}
A sequential value representing a relative sequence number.
position
{C1CB23A1-89A8-4168-8F92-BF147A904503}
propertyName
{F546BBEA-7A08-4a29-815E-26937877A51A}
propertyValue
{2C9DB80A-5479-40f6-AFAF-D731CD37C35C}
sequence
{F578E05F-ABEB-41e6-BBA7-297BC6F756B2}
Identification of the method of allocation in an auction.
allocationMode
{F41CCA4E-22DF-4371-8804-FBD174BC50B2}
An indicator that signifies that the auction has been cancelled.
cancelled
{D8F3C9D9-D21C-4dcd-BD52-698E5F51B682}
The product category of an auction.
category
{903E537E-0A03-4edc-8C08-29339719D70B}
The terms which dictate the determination of the bid payment price.
paymentTerms
{CDA79844-852E-4aa8-814D-E14A2967A31E}
The rights of use the transmission capacity acquired in an auction.
rights
{8FF7990E-BAB0-4736-998C-441D925B1012}
The kind of the Auction e.g. implicit explicit ....
type
{6C33E2C4-D67A-4c0d-8F0F-AD378FAAF82B}
The frequency for automatically recurring auxiliary charges where AuxiliaryAccount.initialCharge is recursively added to AuxiliaryAccount.dueCurrent at the start of each auxCycle. For example on a specified date and time hourly daily weekly monthly 3monthly 6monthly 12monthly etc.
auxCycle
{E0DA06F7-5549-4d2f-BFF9-E2AE281536D1}
The coded priority indicating the priority that this auxiliary agreement has above other auxiliary agreements associated with the same customer agreement when it comes to competing for settlement from a payment transaction or token purchase.
auxPriorityCode
{5484F044-925A-434b-8420-9064729D9C1D}
The contractually expected payment frequency by the customer. Examples are adhoc on specified date hourly daily weekly monthly. etc.
payCycle
{821FDC90-B952-41fc-8B61-3D6D1B6130FA}
Subclassification of the inherited type for this AuxiliaryAgreement.
subType
{A2658DD4-1255-4eab-B60A-BD67E8F03C0C}
intervalStartTime
{470D6511-3AC4-412e-A8EB-D167CEE223C7}
updateTimeStamp
{166F39D9-3ACF-4f4f-96EA-42C7AF101791}
updateUser
{5EBC78B6-7446-456b-BD2E-AF5151869DC1}
availUndispatchedQ
{4217449A-2958-4da3-834F-1FEC963CC876}
incrementalORAvail
{27C11241-2C00-42b2-ABC0-52C84AF15BFA}
maxExpostCapacity
{989EE825-BC10-48c2-93FC-BC99475E2CAF}
minExpostCapacity
{FDC1CE8D-5672-4e7b-BB61-79639DD4FA03}
noLoadCost
{C43E5D6E-508D-4853-97CA-DA1233971AFD}
startUpCost
{B8D50D43-6615-4080-AA6A-DB0A7A1BF19F}
Integral gain.
integralGain
{86CAF110-A86E-47fa-8728-B1385050F139}
Pressure setpoint gain adjuster.
pressureSetpointGA
{C04CC74E-4B09-4010-A0A0-7B4D494D0168}
Proportional gain.
proportionalGain
{E50BF249-B9B4-455a-8590-B42B77C73B02}
Constant associated with rod pattern.
rodPatternConstant
{43F070BE-A56B-4544-8AE4-ED199B6B9920}
Bank identifier code as defined in ISO 9362 for use in countries wher IBAN is not yet in operation.
bic
{581F8A25-DDBD-4192-B445-DCE0AA68491C}
International bank account number defined in ISO 13616 for countries where IBAN is not in operation the existing BIC or SWIFT codes may be used instead see ISO 9362.
iban
{E33D83DF-4B34-4099-8648-A452D1875E5C}
Account reference number.
accountNumber
{5D77174B-D342-43ac-B7DA-D25CA3C181AC}
Operational account reference number.
accountNumber
{1BACCB15-6E84-4b37-83A6-5281BB03EC6A}
Name of bank where account is held.
bankName
{0644F13E-EBDF-4666-A81C-4193E88D631B}
Branch of bank where account is held.
branchCode
{E4659845-6DC8-4933-8048-145F952D2ACE}
National identity number or equivalent of account holder.
holderID
{4C777630-E66F-41bf-AEAE-743296150917}
Name of account holder.
holderName
{A9A26E12-FEF8-4238-B181-FBC14654F047}
used only when there are detailed auditing requirements Date and time at which the reading was first delivered to the metering system.
reportedDateTime
{1EFBADCF-C043-4b42-A958-3E33FEAE424D}
System that originally supplied the reading e.g. customer AMI system handheld reading system another enterprise system etc..
source
{5E0394BB-E9C4-4292-B470-6DC151E4A3B8}
Value of this reading.
value
{4940C156-BAF1-4ed1-A8E7-BCFE8AF70C33}
The time for the first time point. The value can be a time of day not a specific date.
startTime
{3ACCE58A-16D7-4605-BA2E-BC0F2B4DDC51}
Indicates the presenceabsence of energy measurements.
bayEnergyMeasFlag
{26D3924E-0222-4e9a-9373-CD7D256E9B19}
Indicates the presenceabsence of activereactive power measurements.
bayPowerMeasFlag
{B5F9E0A2-7BE7-4bb1-A035-0F5F849847F0}
value
{242F2D41-B838-448e-AD36-B197E8CC54CF}
Start time and date for which bid applies.
startTime
{9B636BFE-278E-44a8-8578-BFDDDB2C916C}
Stop time and date for which bid is applicable.
stopTime
{ECEE9946-AADD-458b-80B9-02B88FEBFF23}
End of the time interval n which bid is valid yyyymmdd hh24 mi ss
timeIntervalEnd
{3F4C4676-701C-498e-A801-30BB4FA0B5A0}
Start of the time interval in which bid is valid yyyymmdd hh24 mi ss.
timeIntervalStart
{68EE68BA-1417-4f66-84E3-B1AB53587DE9}
componentType
{4A1F44CA-1FE5-4b6d-8185-674FEEF955EE}
hour wihthin the bid for which the error applies
endTime
{7423F6F6-A703-4aba-A18E-6A165481DC0C}
error message
errMessage
{BFCEDCA1-4371-42ea-A6EA-031A8DD538A6}
Priority number for the error message
errPriority
{23E14325-6FCA-47d0-BC5F-AE08FF252A9E}
logTimeStamp
{02D675B1-0369-4b16-A7FD-D8391D728A15}
msgLevel
{11349151-38B6-4cb8-B79D-40820B167F94}
ruleID
{5BC0BF99-3D21-43d2-85FD-DF7DBA8714B3}
hour wihthin the bid for which the error applies
startTime
{DFE2A0D2-E2F2-4a0e-B254-E4B696747888}
Contains the PriceTaker ExistingTransmissionContract TransmissionOwnershipRights pumping self schedule quantity. If this value is not null then the unit is in pumping mode.
pumpSelfSchedMw
{84453304-3979-4192-84DD-E0A90EDEE1D9}
Self scheduled value
selfSchedMw
{49885581-F2BE-4b65-B54A-70AB538C594F}
Price Taker Export Self Sched Support Resource
selfSchedSptResource
{55136132-5356-4862-86A3-C8D9DAF3FC54}
A unique identifier of a wheeling transaction. A wheeling transaction is a balanced Energy exchange among Supply and Demand Resources.
wheelingTransactionReference
{9BD74639-7B69-4bf3-ACC0-1E7B2629699A}
Indication that the values in the period are considered as a whole. They cannot be changed or subdivided.
blockBid
{E8885A93-9691-4cb4-80D5-7128403E2259}
The coded identification of the energy flow.
direction
{17AB2D1C-2A3B-428f-8CE5-F7C6ACD747C3}
An indication whether or not each element of the bid may be partially accepted or not.
divisible
{2043AB91-F00F-4448-B423-9585AA7A6BC2}
Unique identification associated with all linked tenders.The identification of a set of tenders that are linked together signifying that only one can be accepted. This identification is defined by the tenderer and must be unique for a given auction.
exclusiveBidsIdentification
{61A81A96-9463-43b0-B2D6-57E6D3E68A7B}
Unique identification associated with all linked bids.
linkedBidsIdentification
{DA90E89E-A3A4-42fb-A53C-E814F3B600D6}
The minimum quantity of energy that can be activated at a given time interval.
minimumActivationQuantity
{C0873E69-A736-4659-AF41-9AFDB31878D2}
The numeric local priority given to a bid. Lower numeric values will have higher priority.
priority
{CFA75F08-D88C-48ed-BFF0-D06E01F92D3E}
The information about the status of the bid such as shared restricted ...
status
{B890EAF9-0541-499e-BD70-5E97FB5F254B}
The minimum increment that can be applied for an increase in an activation request.
stepIncrementQuantity
{C5941D40-E5CA-483b-8656-B10D04D9E1E7}
Maximum curtailment time in number of trading intervals
curtailTimeMax
{1FA08F52-372C-4ae4-BD60-E11B726EEB3A}
Minimum curtailment time in number of trading intervals
curtailTimeMin
{DB1038AC-B30D-47db-B55C-44900B2BDFBE}
Market type defaultDADA Day AheadRT Real TimeHA Hour Ahead
marketType
{290C94D6-B5F4-4c65-8206-C01963A1F2CD}
Maximum purchase time in number of trading intervals
purchaseTimeMax
{4B9F1161-86DA-4c4d-83DB-A9E4C7FE6B5E}
Minimum purchase time in number of trading intervals
purchaseTimeMin
{1E3B746A-9F12-44ce-8FFB-FBFDED59CC34}
Transaction scopeInternal defaultExternal
scope
{459E5791-DCD3-4c2c-A8F0-4492D610AF50}
Transaction type default 11 Fixed2 Dispatchable continuous3 Dispatchable blockloading
transactionType
{2F95D0AF-361F-48f1-8E82-660250BC83D3}
Level in charge calculation order.
calculationLevel
{2A540150-588D-4803-A6AD-1C5BD1D0A571}
The version of configuration of calculation logic in the settlement.
configVersion
{CEBE65AE-7C04-46bf-9B1E-59FBF0EEEE59}
deleteStatus
{A3C5B4FD-9DE9-4aef-91C6-5B8BF21BAC17}
effectiveDate
{793F4C87-0F83-4866-AFDD-8E300F10A341}
exception
{ED997157-812E-4a0b-BA16-AFB558B4394D}
factor
{ABE551BD-ED20-46b1-951D-A3156D10D16B}
frequency
{85C35E31-A2E8-40bf-B99E-0E78B1CEF978}
Number of intervals of bill determiant in trade day e.g. 300 for five minute intervals.
numberInterval
{48CEEAE8-9642-4920-9366-390D60AB6CBA}
offset
{DBA1638E-C286-47aa-BD94-9CAF9CDB41AE}
The level of precision in the current value.
precisionLevel
{1260821F-91EE-4d35-8A73-847E0FBBC149}
primaryYN
{FAD57C3E-C6A8-4e2b-B47D-78B662E85168}
referenceFlag
{884B6063-6A84-4016-88C9-1936D07D9B50}
reportable
{481E6F8A-CAEF-48f1-98A1-99D8D23468CA}
roundOff
{EF9E4AA7-6C4C-4d48-9F71-A2144886022C}
source
{A2ED9E99-708E-4c2c-AF99-72A3AEF8E6FB}
terminationDate
{F877E939-8182-431f-8405-0374E8F9B749}
The UOM for the current value of the Bill Determinant.
unitOfMeasure
{9956AABB-127E-452c-9E00-747B3132D3E4}
sequence
{DC07156D-FEE4-45f2-A26A-916CB539ADA6}
The Load Dump Rating for the branch
loadDumpRating
{AB9608F9-FE22-4ac7-9AC3-D376DF6E71C4}
The Long Term Rating for the branch
longTermRating
{57A835EC-E024-4485-A93D-C68462D68213}
The MVAR flow on the branch Attribute Usage Reactive power flow at the series device transformer phase shifter or line end
mVARFlow
{B09566DA-DC18-41c4-9907-763674C31C18}
The MW flow on the branch Attribute Usage Active power flow at the series device transformer phase shifter or line end
mwFlow
{EFC4B5AA-CE62-4feb-A6DA-E30D21AA2544}
The Normal Rating for the branch
normalRating
{FA049830-FF5A-4060-AD80-727201ECAA92}
The Short Term Rating for the branch
shortTermRating
{E6A911FE-8B0D-48f3-890C-1158F3DA4880}
Monitor the active power flow.
monitorActivePower
{054412F1-EA7D-48f3-A946-73FB2A9AC5AC}
Monitor the reactive power flow.
monitorReactivePower
{3CCD93AD-E066-4429-93CF-4A75307DAAD3}
The flow into the terminal is summed if set true. The flow out of the terminal is summed if set false.
positiveFlowIn
{B8475766-314D-41cf-9DA0-61DF5D14D2A6}
Priority of bus name marker for use as topology bus name. Use 0 for do not care. Use 1 for highest priority. Use 2 as priority is less than 1 and so on.
priority
{42DD7D7D-947F-400f-94F2-BE2C04827C64}
A codified representation of the business case i.e. codes for highway relocation replace substation transformers etc..
corporateCode
{68010FA4-340E-4cfb-B2F9-4C9B3EC0333D}
Classification by utilitys corporate standards and practices.
type
{843AA391-E6A1-4cd6-884E-3570B77E4E3C}
labelID an ID for a set of apnodespnodes used in a CRR market
labelID
{8C8D1C56-9CA3-4b5c-BC2E-D00C877BE090}
segment end date time
endDateTime
{817345BB-E920-4120-86D6-7B12B5A0179D}
The MW amount associated with the CRR
quantity
{56B83640-6685-4642-B194-18F40D7BB5B6}
segment start date time
startDateTime
{EB4CB545-26E9-4a9f-A5A7-B30B91D4799B}
Behaviour is based on a proprietary model as opposed to a detailed model.true userdefined model is proprietary with behaviour mutually understood by sending and receiving applications and parameters passed as general attributesfalse userdefined model is explicitly defined in terms of control blocks and their input and output signals.
proprietary
{E13E8CFF-168A-41a6-9266-D8B4D20D580B}
Activity code identifies a specific and distinguishable unit of work.
activityCode
{9E695683-C2CF-426a-955E-C3A8E1454D32}
Labor code.
code
{A6F667B5-330C-4455-AB85-11311DE53FDA}
Activity code identifies a specific and distinguishable unit of work.
activityCode
{201FC700-3AA1-49c1-BF25-803B60D383F0}
Code for material.
corporateCode
{B5ABD970-4E73-4d49-B3A0-D2B047BA2341}
The equipment type code.
equipCode
{0F4A6BE8-8FEC-4a76-B358-486194C88A66}
True if wire strands are extruded in a way to fill the voids in the cable.
isStrandFill
{B3CE6228-F6AE-4e51-8275-3B7C2FDA37BA}
True if sheath shield is used as a neutral i.e. bonded.
sheathAsNeutral
{97DFC3D1-475C-49fb-B050-2FA7C58CAA02}
Order of the statistical calculation method within the calculation method hierarchy.
order
{080044BD-D480-40cd-86AD-3FFDBC56F751}
Capability performance factor.
performanceFactor
{242F3279-F71B-4ae2-ADE5-B1DEBFBE700D}
Classification by utilitys work management standards and practices.
type
{C1A9E5F1-2B82-4989-8599-4B942ED46472}
value
{DD5CA50E-8CF4-4d9d-B637-E3028CDD0DC8}
value
{D86CCBDD-AB37-4d35-8A40-24064DEA2769}
Name of account holder.
accountHolderName
{4C0BB750-D65F-42a9-B758-74B5FCD3C1DE}
The card verification number.
cvNumber
{D70FA221-259E-4c6f-A5FD-EBC8B62F4DC7}
The date when this card expires.
expiryDate
{BE63D46B-9ABA-446a-AFB8-11FB7EEC8697}
The primary account number.
pan
{2AC0085A-CF44-4e60-B81F-41FA24DA1ADD}
True if item is a stock item default.
stockItem
{94B89383-850C-47ed-BC41-A1105D18D166}
Description of type of asset.
type
{069D3729-A67C-4573-8A70-00C84CED59A9}
If true the data is being calculated by an enterprise system rather than metered directly.
isVirtual
{71DF17F0-D8B0-47ac-9A03-0062B4868F8C}
deleteStatus
{FAFC0BF4-DEAC-49e2-9D86-14FFDD70F270}
effectiveDate
{7FA4D357-539A-442a-B3B0-A937EBD2FA4C}
equation
{E79261B7-BE9D-42e3-994C-4FAF67A1D89C}
message
{FEDD52B7-AB53-4940-9170-906404584146}
roundOff
{D4C0965A-E2F8-483c-977C-54418D15EC4C}
sum
{CCD643C1-A078-4c50-AB7B-BF999CAEF7C3}
terminationDate
{82341A8E-D54C-49d8-A7D5-286333C49B6A}
type
{69095778-68FE-40dc-AD17-74A54A10065A}
effectiveDate
{3E947F8F-3C53-4bf9-B78A-40A5045C50B5}
marketCode
{1D6AE503-978B-4b4b-A59B-6269A25C1736}
terminationDate
{D7A5841A-7539-4d10-B6B3-8C199F15C101}
The calculation frequency daily or monthly.
frequency
{543A1D72-47E5-4bb4-B003-A388EA582FE6}
The number of intervals in the profile data.
numberInterval
{5724E16E-4C51-449c-81FE-2C70C65B9732}
The type of profile. It could be amount price or quantity.
type
{2A8F4C98-A1A7-44ea-B725-5D9DBBB50EF6}
The unit of measure applied to the value attribute of the profile data.
unitOfMeasure
{61638093-C8EC-4657-BBB2-EA5DBA8A4D62}
The sequence number of the profile.
sequence
{EC051423-ABBE-415a-B5F3-A41E84467218}
The date and time of an interval.
timeStamp
{0D55F42D-A6CB-4f2c-8F2E-3D5FE4B71CFD}
The value of an interval given a profile type amount price or quantity subject to the UOM.
value
{5EF16AAA-B95B-4673-ACF9-BA85C08F0362}
chargeOrder
{EF0BAC78-4548-4ea4-A2F7-0D5219BB0E59}
chargeVersion
{4E6687A3-13FA-4543-9D0A-3BB9F796C455}
effectiveDate
{94BC39EB-6CF6-44e6-8568-C7E814337E02}
factor
{1283AF97-6B0B-44e5-8489-FB0ACFA67B70}
frequencyType
{5647123F-04F4-4200-9116-26AB6F355D31}
terminationDate
{760CCC7D-1D43-4365-AF3A-8C1B2A266562}
totalInterval
{BC782E70-8365-4ad0-AD4C-C71F9CA85949}
Cheque reference number as printed on the cheque.
chequeNumber
{34CB8AB7-59FE-4c69-A5AB-83A55DBC6219}
Date when cheque becomes valid.
date
{C3450A5F-DBBC-46da-9B1E-F82835F709AC}
The magnetic ink character recognition number printed on the cheque.
micrNumber
{2505F1E1-6FE3-4429-95D2-808B196B1740}
value
{5C094F69-3827-4a03-AB0F-98BA656396E9}
If true the equipment must be deenergised.
mustBeDeenergised
{8102C6B9-BFDF-4102-8071-C547C8984D08}
If true the equipment must be grounded.
mustBeGrounded
{4C096287-27B6-4481-B59D-9418396B80FB}
Used to calculate participation of Cnode in an AggregateNode
factor
{4A18D416-D28B-4da1-B201-A88BD1C7FA97}
Point of delivery loss factor
podLossFactor
{9CE7F1FC-2A68-4545-84D8-CADE161C0A22}
The high pressure steam sendout.
cogenHPSendoutRating
{58364926-2356-49f2-8FEB-BFBE60CB258A}
The high pressure steam rating.
cogenHPSteamRating
{962F4362-7444-4925-B187-B995011FEDF2}
The low pressure steam sendout.
cogenLPSendoutRating
{577F0232-FE4A-4ed8-A5C0-3586A290D6FD}
The low pressure steam rating.
cogenLPSteamRating
{144D8B2A-3B7B-47a6-A0B1-5AAD86233E0C}
Communication ID number e.g. serial number IP address telephone number etc. of the AMR module which serves this meter.
amrAddress
{770410B7-727A-49bd-A3A1-7907D402462B}
Communication ID number e.g. port number serial number data collector ID etc. of the parent device associated to this AMR module.
amrRouter
{06F3A500-BB20-4f3c-939D-FEDF9B4FBD85}
Automated meter reading AMR system communicating with this com module.
amrSystem
{9BF887D3-7B0F-4e62-B1C6-79CA35E81A37}
If true autonomous daylight saving time DST function is supported.
supportsAutonomousDst
{6229BFBD-910D-4752-B6CD-31F879525811}
Whether Combined Cycle Plant can be shutdown in this Configuration?
ShutdownFlag
{54B14599-FD05-429f-9C50-BC6EC9E73AB1}
Whether Combined Cycle Plant can be started in this Logical Configuration?
StartupFlag
{BF6C9458-37EB-47aa-8836-53EBADD33626}
Whether this CombinedCycleConfiguration is the primary configuration in the associated Logical configuration?
primaryConfiguration
{04A6423D-C5DF-4b31-827E-1EA76565DF80}
primary configuration.
primary
{CF280400-93E0-4912-89E4-58771817B8AB}
Steam plant.
steam
{3EA9BDFD-5FAE-49f8-A8EF-B8C4C75D5C8E}
Flag indicating whether this is an UP transition.If not it is a DOWN transition.
upTransition
{12749A12-D195-4c11-821F-E47B9AA0C531}
Flag that is set to true if the combustion turbine is associated with a heat recovery boiler.
heatRecoveryFlag
{1415519E-2DBF-47d8-9B1E-DACCEB57F065}
Normal value for Control.value e.g. used for percentage scaling.
normalValue
{437D2D11-A2B3-49b4-9609-7210BA175EA5}
The value representing the actuator output.
value
{29976C5A-6DB4-4916-B523-50F7858960A8}
Total cost associated with changing the status of the resource.
instructionCost
{578EFA4E-7FD0-45b0-A6B8-57A748F87C5A}
End time for the commitment period. This will be on an interval boundary.
intervalEndTime
{50556AF7-DC96-4147-8C7A-FDA9AA4D4017}
Start time for the commitment period. This will be on an interval boundary.
intervalStartTime
{90E388DC-A26F-4245-8B10-5725AB7D9637}
SCUC commitment period startup time. Calculated start up time based on the StartUpTimeCurve provided with the Bid.This is a combination of StartUp time bid and Unit down time. Units is minutes
minStatusChangeTime
{2819E1D6-C130-4a97-AC21-BFE4762100EE}
Unit no load cost in case of energy commodity
noLoadCost
{B053BC2D-C61E-4d09-A9E2-537C58F83F3F}
updateTimeStamp
{5BE94617-C528-4f99-A3F9-625EA54FD721}
updateUser
{0D607B81-5F53-49fa-B225-567AD187BDCF}
The price of the Commodity expressed as a floating point value with the currency and unit of measure defined in the associated CommodityDefinition class.
value
{0B6F7B9D-133A-426e-98C0-D150700FC78F}
The quantity unit of measure and multiplier at the CU level that applies to the materials.
quantity
{84C74AD9-B462-4a74-AC12-66784AA8E5F9}
The deadline for compliance.
deadline
{6DF556D7-D4BC-475c-8399-31E6CD2BA271}
An alphanumeric code that can be used as a reference to extra information such as the description of the interlocking scheme if any.
compositeSwitchType
{97E05A7E-4259-438b-8705-00D60DB068EF}
True if multiphase switch controls all phases concurrently.
ganged
{15E93293-031E-4cc3-8990-81B19133B945}
Initial operating mode with the following values Automatic Manual.
initOpMode
{0336A72B-92DB-4f39-9EED-2CE15DAEB7A0}
Supported number of phases typically 0 1 or 3.
phaseCount
{93078995-1B47-47cf-8635-FAC6669633E2}
True if device is capable of being operated by remote control.
remote
{7C276369-05F5-4fd2-9D29-835C41C17C92}
Number of switch states represented by the composite switch.
switchStateCount
{56E37B5A-CCB1-4747-A847-450647A90857}
Number of concentric neutral strands.
neutralStrandCount
{CB711D44-7BA3-4b53-A6D7-7D68C70C922D}
The actual value of the condition factor such as labor flat fee or percentage.
cfValue
{60BF8DF2-B00A-4b78-AA80-DF484A82D05A}
value
{A37F340D-8291-465f-8A0A-FF87B2676B0E}
value
{F819D02A-9432-4aa9-B3F5-077392D77154}
Date and time this event has or will become effective.
effectiveDateTime
{64824EF1-3465-4c34-A0D9-943BA218B43B}
Sourceinitiator of modification.
modifiedBy
{31F52668-C2CC-4ef6-BAF7-1826A90450BB}
Free text remarks.
remark
{DD01E9CE-D519-4aa5-8F2D-C0C3BCA37101}
Segment of the CRR described in the current record.
tradeSliceID
{BCB88400-1E7C-4670-B48C-CA6460FC1852}
Running cumulative count of connect or disconnect events for the lifetime of this function or until the value is cleared.
eventCount
{B6A5E2F9-1D95-4fc1-A087-393446A8F880}
True if this function is in the connected state.
isConnected
{25518075-8A12-4e4d-9CDF-25AE11648382}
If set true the switch may disconnect the service at the end of a specified time delay after the disconnect signal has been given. If set false the switch may disconnect the service immediately after the disconnect signal has been given. This is typically the case for over current circuitbreakers which are classified as either instantaneous or slow acting.
isDelayedDiscon
{7DBD3A29-99F7-48c7-B885-BE4144F67C8B}
If set true and if disconnection can be operated locally the operation happens automatically. Otherwise it happens manually.
isLocalAutoDisconOp
{CA9E0CBF-7504-4f90-9B16-493A45E40DEC}
If set true and if reconnection can be operated locally then the operation happens automatically. Otherwise it happens manually.
isLocalAutoReconOp
{45731B3D-65FD-49d1-8C6F-6168EB0403CE}
If set true and if disconnection can be operated remotely then the operation happens automatically. If set false and if disconnection can be operated remotely then the operation happens manually.
isRemoteAutoDisconOp
{43279BC9-6A77-479a-AA77-DF30DA8387C9}
If set true and if reconnection can be operated remotely then the operation happens automatically. If set false and if reconnection can be operated remotely then the operation happens manually.
isRemoteAutoReconOp
{5EAF4B18-51E5-4025-9760-308042A302BB}
The duration of the constraint.
duration
{7D03DFAB-432A-4f58-B1D4-21B2027964E5}
The type of the constraint.
type
{96234AD7-9E0E-41df-A2D3-75E5E1411700}
This value is determined in DA and RTM. The SCUC optimization ensures that the MW flow on the Branch Group will not exceed this limit in the relevant direction.
BGLimit
{3A1E590C-CFFE-4bbf-B83F-3251034E8B28}
Branch Group TR Reservation Capacity This value is determined in DA and RTM. It is the amount of spare transmission capacity that is left for the TR holder to use.
BGTRResCap
{5F933B83-A2DE-4a8a-A195-D4E0E4549E7A}
Branch base Power Flow.
baseFlow
{B223B1CC-02DB-4d9a-B9A8-23DB6AEBD44F}
MW Limit.
bindingLimit
{53A935FA-6BE8-4d3c-8FB8-FC963D41F508}
Cleared MW.
clearedValue
{567BBBA7-A602-468b-860D-63A52C8D4973}
Transmission overload MW.
overloadMW
{2D0D8023-0663-49e5-AF0E-BA2FBAD73B4D}
Actual MW flow as percent of limit.
percentMW
{8B4BDB13-A064-4273-A921-1B6E157ACCF7}
Shadow Price MW for the commodity. Shadow price for the corresponding constraint.
shadowPrice
{38DCCFC5-8DBC-4d3b-B9E9-90A373D05135}
Update time stamp.
updateTimeStamp
{B79B6C6B-BFF6-4a52-9773-A2ECF7006751}
Updated user.
updateUser
{C49E6203-93E8-40a8-94B8-E6C4493721DB}
factor
{A3332EE4-CECA-4487-A550-30BBDC62F99F}
The function is an enumerated value that can be active reactive or VA to indicate the type of flow.
function
{A6751AF4-2737-4b1e-AF05-B0542253CBA9}
A sequential reference that defines the identity of this interval and its relative position with respect to other intervals in a sequence of intervals.
sequenceNumber
{13BC3024-CED2-41bc-9BF6-2AD075B8F4C3}
The lowest level of consumption that defines the starting point of this interval. The interval extends to the start of the next interval or until it is reset to the start of the first interval by TariffProfile.tariffCycle.
startValue
{C9B4159D-FD48-4f08-81A5-2C715F675CD8}
Set true if must study this contingency.
mustStudy
{1006D019-9EA0-4068-BBE8-7DD65C0C9E67}
MW value that this resource provides to the overall contract.
factor
{B91798E0-DDA9-4618-A849-C7E96A209A90}
When used in conjunction with a Transmission Right contract chain this is the precedence for the contracts.
chainOrder
{1FE814D3-9CC5-43ed-99C5-F1EE87D780D8}
MW value of the contract
contractMW
{D4C2E876-9A57-4158-8538-E9E2E7945630}
Priority for the contract. This should be unique amoung all contracts for a specific resource. This value is the directive for the SCUC algorithm on the order to satisfycut contracts.
contractPriority
{8B4A477C-88E5-4829-8F65-DD4F5FDE0F70}
Contract status
contractStatus
{57879043-AB9C-4296-9DFE-F0107063427B}
Estimated Fuel Adder
fuelAdder
{4E86FA44-61A5-462e-8ADC-F951EFAE9331}
This indicates the latest schedule minutes e.g. t xx that this resource can be notified to respond. This attribute is only used if the market type is not supplied.
latestSchedMinutes
{3DAAD7FC-8821-4919-ACB3-9F7BF8CFB9CC}
Maximum Net Dependable Capacity
maxNetDependableCapacity
{897F5B07-A24C-411a-A5FF-92974D196008}
Maximum schedule MW quantity
maximumScheduleQuantity
{9E96222F-F142-468a-A0BA-C53BF2577A58}
Maximum service hours
maximumServiceHours
{DB6A03D9-CD14-419e-B95A-8E80AFBCB823}
Maximum startups
maximumStartups
{CD042392-070A-45ff-AEED-A165D28FB7A2}
Minimum Load
minimumLoad
{D5D4A6CF-C570-4f9a-9597-0E3975D84BE9}
Minimum schedule quanity
minimumScheduleQuantity
{D254C0AE-F31D-4c96-B7B9-A6F367B63FD9}
Start up lead time
startupLeadTime
{FE9455D5-F58B-45ec-8D37-390124E0C24A}
Activity code identifies a specific and distinguishable unit of work.
activityCode
{724DFDC6-1877-41fd-86E6-1D32A63B98A3}
Specifies the type of Control e.g. BreakerOnOff GeneratorVoltageSetPoint TieLineFlow etc. The ControlType.name shall be unique among all specified types and describe the type.
controlType
{6AFDC59F-2A6A-41ab-9987-323A1C1CF331}
Indicates that a client is currently sending control commands that has not completed.
operationInProgress
{DC617446-9739-4c4f-8104-988D373E6B60}
The last time a control output was sent.
timeStamp
{019300D3-C764-4818-AA31-EE00F8FB2886}
The analog value used for the analog control the raiselower control and the set point control
analogValue
{8AF9ACFF-9BCF-448c-A2C1-E2E293F700F7}
The integer value used for the command or the accumulator reset.
discreteValue
{9FC1AB85-0AD0-4300-8927-62A216B594C0}
Pool MW Interchange Attribute Usage The active power interchange of the pool
solvedInterchange
{4CFE232C-7651-4654-B5D7-69B00F0A9B62}
Pool Losses MW Attribute Usage The active power losses of the pool in MW
solvedLosses
{0A30D1ED-41B5-44a2-B882-C25954D40D4E}
True if the appliance is an electric vehicle.
isElectricVehicle
{AB22ECAF-6616-4845-A49D-81A1CC4A7684}
True if the appliance is exterior lighting.
isExteriorLighting
{ECC061BA-09EC-4336-85CC-D3611DA1680C}
True if the appliance is a generation system.
isGenerationSystem
{CE3CDA23-E4F1-4c95-AD6F-B80BD1308A58}
True if the appliance is HVAC compressor or furnace.
isHvacCompressorOrFurnace
{F58DAD5C-5903-40c4-8441-C43F41051997}
True if the appliance is interior lighting.
isInteriorLighting
{5680776E-9981-422f-84E7-EE0F459E167E}
True if the appliance is an irrigation pump.
isIrrigationPump
{C61BF63B-609E-4594-A933-E2959F80CF0B}
True if the appliance is managed commercial or industrial load.
isManagedCommercialIndustrialLoad
{7715CEF9-9EDC-4551-8715-AEEC59EBC1F4}
True if the appliance is a pool pump spa or jacuzzi.
isPoolPumpSpaJacuzzi
{08C353AF-4C0B-4487-B50D-D51EC1DA4ED3}
True if the appliance is a simple miscellaneous load.
isSimpleMiscLoad
{67F0C49B-1B4C-4f86-A4E5-8CB1A215C437}
True if the appliance is a smart appliance.
isSmartAppliance
{67F103F1-967C-4c06-8AA7-DFCD5DBFD80A}
True if the appliance is a stip or baseboard heater.
isStripAndBaseboardHeater
{A12278C6-BC53-48d6-A36B-A795C5AA06F7}
True if the appliance is a water heater.
isWaterHeater
{01CDCE80-C542-410c-97DA-5A549815D0B9}
Stage of cooling and associated power rating.
stage
{00A22567-01EF-4081-9A80-BAF75B02327F}
A Uniform Resource Name URN for the coordinate reference system crs used to define Location.PositionPoints.An example would be the European Petroleum Survey Group EPSG code for a coordinate reference system defined in URN under the Open Geospatial Consortium OGC namespace as urnogcdefcrsEPSGXXXX where XXXX is an EPSG code a full list of codes can be found at the EPSG Registry web site httpwww.epsgregistry.org. To define the coordinate system as being WGS84 latitude longitude using an EPSG OGC this attribute would be urnogcdefcrsEPSG4236.A profile should limit this code to a set of allowed URNs agreed to by all sending and receiving parties.
crsUrn
{961FC72C-29B9-4d09-B575-0140E5585552}
value
{FE8D36F6-50A2-4391-B9FB-5B12267F7608}
value
{DEC55B23-344E-41a7-A8FA-8E21A6305E14}
value
{CBA262DB-1A7B-4562-813C-16E939256A67}
value
{D4BDBA35-032E-4aa0-AA21-7B4E4694BAE3}
True if an amount can be assigned to the resource element e.g. building in service transmission plant software development capital false otherwise e.g. internal labor material components.
amountAssignable
{E18872D1-1F16-4033-96D3-3E454041BCB5}
A codified representation of the resource element.
code
{66003815-729C-4ace-B437-0441F73684EE}
The level of the resource element in the hierarchy of resource elements recursive relationship.
level
{89764D37-FE17-4e94-834B-E0A23E4BD94B}
The stage for which this costType applies estimated design estimated actual or actual actual.
stage
{5F794B8E-0443-41c3-A22E-CE12ED456C3C}
Classification by utilitys work mangement standards and practices.
type
{EC4D9877-70D5-4366-8DB0-0D650B39E801}
Net tie MW. These are three entries the current emergency schedule interchange and the two future schedules if they exist.
emergencyScheduleMW
{B53EB58A-2509-455c-AD80-18A8BC0C9A1C}
Ramp time the ramping time for a schedule. This is calculated as the remaining time to ramp if a schedule is ramping. Measured in seconds but can be negattive.
emergencyScheduleRampTime
{CEAA82DA-77AD-4b8d-B70A-9CE53FB1EB63}
Net tie time the start time for a schedule. This is calculated as the current time if a schedule is ramping.
emergencyScheduleStartTime
{E060B453-0DE3-429f-BD35-27223E05C8A2}
value
{83BDDC04-3689-432d-BF6E-0712C32CE504}
Set true if the current relay has inverse time characteristic.
inverseTimeFlag
{7499121A-8A2C-48db-985D-971ADE0D1B62}
Current control area net tie MW the sum of the tie line flows i.e the sum of flows into and out of the control area the current instantaneous scheduled interchange.
currentNetTieMW
{F52B6E46-0018-400b-9011-F7DB4A2C2A7A}
Use Emergency Schedule Attribute Usage Emergency use indicator false Emergency Schedular OFF true Emergency Schedular ON.
useEmergencySchedule
{8A820CCE-E30E-4414-98F0-1A518292E03E}
CT accuracy classification.
accuracyClass
{82552632-7502-4d65-BBB1-8E6A067F4873}
CT classification i.e. class 10P.
ctClass
{80E77345-5BB0-40b8-B123-5DCB928951D2}
Intended usage of the CT i.e. metering protection.
usage
{56466CE3-6700-41c3-B756-DB92CB062BEF}
CT accuracy classification.
accuracyClass
{BBE29588-E564-4049-9BC1-3BEF60AEFEFA}
Number of cores.
coreCount
{A3439D96-56FC-4203-BCA4-72F08DF7E63A}
ctClass
{9706AC2D-13CB-421c-AB8D-0D3D4D150139}
Usage eg. metering protection etc.
usage
{48BD9430-4FFB-4cdc-9019-FEC9036835F3}
The data value of the Xaxis variable depending on the Xaxis units.
xvalue
{25202638-FF67-4a74-9190-EFB0B473BAAB}
The data value of the first Yaxis variable depending on the Yaxis units.
y1value
{5BE57251-18BF-4e7f-A02D-3B42C9DC1222}
The data value of the second Yaxis variable if present depending on the Yaxis units.
y2value
{88D16D6F-312D-4a45-B322-E742A16DDB3F}
The data value of the third Yaxis variable if present depending on the Yaxis units.
y3value
{53A1221F-D9D4-4ade-8918-ADB189907ABD}
Locale designating language to use in communications with this customer.
locale
{6C272E71-959E-4d69-B143-6DC49AB2A0D5}
if applicable Public utilities commission PUC identification number.
pucNumber
{4044CC00-B628-44a1-BCB3-5864B96E66ED}
True if customer organisation has special service needs such as life support hospitals etc.
specialNeed
{DC524344-393C-44d5-849C-B2B08481B7A9}
deprecated use priority instead True if this is an important customer. Importance is for matters different than those in specialNeed attribute.
vip
{EDA95871-C80E-4d3c-AFEA-79575780E2FE}
Cycle day on which the associated customer account will normally be billed used to determine when to produce the billing.
billingCycle
{71DC2D6E-AF5F-4b99-BD52-6452CEA27F8C}
Budget bill code.
budgetBill
{789C5B33-25FB-4e44-B978-FEBDBFCE7AE5}
If true the customer is a prepay customer for the specified service.
isPrePay
{83C54792-A73E-42c0-89BF-2704EB0CFCB6}
Load management code.
loadMgmt
{15CE1E0E-9A95-48ba-B098-11C89F09061F}
Final date and time the service will be billed to the previous customer.
shutOffDateTime
{8FD31051-3798-4023-8527-6B57A4DC49D8}
Business date designated for the billing run which produced this CustomerBillingInfo.
billingDate
{12D186DD-95FD-4517-842D-385342B64506}
Calculated date upon which a customer billing amount is due used in the invoicing process to determine when a Customers Payment is delinquent. It takes into consideration the regulatory criteria and the Customers requested due date. In the absence of a Customer requested due date the due date is typically calculated from the regulated number of days and the billingDate.
dueDate
{CA7C613F-F1BC-4b31-A039-A3B5D07E146F}
Date of the last payment received from the customer. It is retained in the Customer Billing system although the details of each payment are tracked in the ERP system.
lastPaymentDate
{44E5BD4D-16FB-47e3-A7BC-D9986E8114C7}
Type of payment plan.
pymtPlanType
{8DF9572D-F773-4178-8496-ECF4F5EAF471}
Type of contact e.g. phone email etc..
contactType
{88B92073-B229-40ae-A4ED-B9C6B5D11AEF}
Value of contact type e.g. phone number email address etc..
contactValue
{48BFCAF6-872E-48a0-9BC4-571637693AA3}
Earliest date time to call the customer.
earliestDateTimeToCall
{F26E31AA-5C85-45d0-AEB0-8016C070FE01}
Latest date time to call the customer.
latestDateTimeToCall
{BFC1B4D2-0ED1-44b4-B29B-35BAC89EF480}
Wind Force as classified on the Beaufort Scale 012 during the time interval.
windForce
{205F3C8E-F5CE-432e-A904-67EE2E7D36F1}
intervalNumber
{2CEA5B0D-5C22-4005-8809-EF81B2368CA7}
maxYValue
{457C948A-86B7-47c7-AF69-AE9CCE1A78E7}
minYValue
{286AB868-27C0-490e-BDC6-614D0CA50C95}
nominalYValue
{49E8C08F-F968-474d-A937-C3BB832D73C0}
timeStamp
{F27D2492-4951-4870-9EEF-03B787335ADA}
connectDisconnect
{038AB681-95CA-4260-B164-C05028A458A7}
frequencyWattCurveFunction
{0D3690F5-90F9-4eba-AE52-160BD143AD87}
maxRealPowerLimiting
{378EE0AC-39F7-4b4a-AB8B-052E946C50A5}
rampRateControl
{C13BA408-60AF-472c-80B4-EF70955EA44F}
reactivePowerDispatch
{6FE87DDE-CAF6-44da-92B0-11B3464031D4}
realPowerDispatch
{89B5111F-4C71-48e4-AF53-A32C16D4B7C0}
voltVarCurveFunction
{CC717899-83B4-4919-AE5E-F766AF4293EB}
voltWattCurveFunction
{4CF3A52F-1D86-426d-95D6-A992782F29D8}
voltageRegulation
{14F7BDCA-3C1A-41d0-AD01-F2F5409FEEBC}
The timestamp for when a prediction was created
predictionCreationDate
{41C4E067-0F3F-4a40-9FBC-BFE14BB0FB23}
yUnitInstalledMax
{518E0D95-7456-405b-BF96-2D507A5D3DE7}
yUnitInstalledMin
{55B20B63-082A-4779-8A64-D61E73057059}
value
{0F8AB6DB-14D2-4ff4-8F9D-04C8EE513931}
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
description
{14F272FF-25AE-4d6a-9BFE-FF46458C9848}
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID as specified in RFC 4122 for the mRID. The use of UUID is strongly recommended.For CIMXML data files in RDF syntax conforming to IEC 61970552 Edition 1 the mRID is mapped to rdfID or rdfabout attributes that identify CIM object elements.
mRID
{38079BA5-9C66-4e27-9C98-D6221A666E31}
The name is any free human readable and possibly non unique text naming the object.
name
{4DFBBA72-867F-4d84-8F39-69AFECF9990E}
Date as yyyymmdd which conforms with ISO 8601
date
{AB78A7E6-4326-47df-BDD7-19020BFD7955}
Time as hhmmss.sssZ which conforms with ISO 8601.
time
{D47B6165-A270-4a65-80DB-C64BDF3384EB}
End date of this interval.
end
{339CEC7A-2AAE-4b35-A4F0-D99489647814}
Start date of this interval.
start
{E4C6879F-771E-45e8-8ABB-77B9C038EECC}
End date and time of this interval. The end date and time where the interval is defined up to but excluded.
end
{55C5DBB1-2BC7-4ff6-9AE1-5D9BD2F9C376}
Start date and time of this interval. The start date and time is included in the defined interval.
start
{6B83DB52-1642-4a44-8CCC-C20165ABEF2D}
Value of this quantity.
value
{10B7E679-825E-4a69-B100-0BDB78764BE4}
To indicate a type used for a default energy bid curve such as LMP cost or consultative based.
curveType
{21406AC0-4224-43cb-860E-F9D10BFE2A15}
Type of demand response program examples are CPP criticalpeak pricing RTP realtime pricing DLC direct load control DBP demand bidding program BIP base interruptible program. Note that possible types change a lot and it would be impossible to enumerate them all.
type
{73995657-2421-4621-BAA7-4C3A392F9D45}
Date and time asset most recently put in service.
inServiceDate
{74B6735C-750A-4691-A153-43D9FA159702}
Date and time asset most recently installed.
installedDate
{47DC0F80-8D6E-431c-A4E7-3493FD1D87A0}
Date and time of asset deployment transition to not yet installed.
notYetInstalledDate
{2DD37832-4235-44cc-8AB3-85D18F40C5F8}
Date and time asset most recently taken out of service.
outOfServiceDate
{57ECC0B7-29A0-43da-91E6-2DA5883C308A}
Date and time asset most recently removed.
removedDate
{53B5359B-5F55-48f2-AD8A-BF0DCD623ABE}
A code that helps direct accounting capital expense or accounting treatment.
cuAccount
{3E3F4920-E49F-47be-89D6-7F354CFE0215}
As the same CU can be used for different purposes and accounting purposes usage must be specified. Examples include distribution transmission substation.
cuUsage
{336A65BC-7340-4e6d-8D1A-DAF39EE828FB}
Year when a CU that represents an asset is removed.
removalDate
{94B1A40C-D493-4d9f-B798-C1BEBEC495EC}
True if associated electrical equipment is intended to be energized while work is being performed.
toBeEnergised
{AB1BE96D-4FEB-4790-B605-3E761438F03D}
Effect of problem.
effect
{9D24B977-2916-419b-AEB0-C992DFB2E3D8}
Failuer mode for example Failure to Insulate Failure to conduct Failure to contain oil Failure to provide ground plane Other.
failureMode
{20867EBB-0B64-4e42-8BD7-5C35EB325E4C}
Cause of problem determined during diagnosis.
finalCause
{F733F1CC-263D-474c-BEB0-968985A3B5A5}
Code for diagnosed probem type.
finalCode
{FFC539E2-1CD0-42c5-AF27-00B0E505E143}
Origin of problem determined during diagnosis.
finalOrigin
{CAFBD581-3686-485b-97DD-919B0936E4A1}
Remarks pertaining to findings during problem diagnosis.
finalRemark
{DD8F1982-C0F0-4614-B85B-8F6C1C86EE32}
Code for problem type determined during preliminary assessment.
preliminaryCode
{82B6D5BE-5A23-4de6-918A-6AF05ED4FFC7}
Date and time preliminary assessment of problem was performed.
preliminaryDateTime
{BCC48BA2-EB9C-4997-BDE1-AF0E28B50110}
Remarks pertaining to preliminary assessment of problem.
preliminaryRemark
{F53CA5FA-DA56-4cc5-BDE5-E759CD257D66}
Root cause of problem determined during diagnosis.
rootCause
{283B037A-8BA2-4354-AC49-449DD43A7EFB}
Root origin of problem determined during diagnosis.
rootOrigin
{A0A688A9-EA41-415a-A095-F4BB99F03134}
Remarks pertaining to root cause findings during problem diagnosis.
rootRemark
{F2028E43-700A-4139-B392-299371B11E17}
X coordinate of the first corner of the initial view.
x1InitialView
{C3E7979E-7009-4acc-BEFD-4EE6C76AC48B}
X coordinate of the second corner of the initial view.
x2InitialView
{8D98579B-5D7F-44a7-B694-6ADA4287C5AB}
Y coordinate of the first corner of the initial view.
y1InitialView
{F9ED2529-E452-4556-ACAD-C33EA342768B}
Y coordinate of the second corner of the initial view.
y2InitialView
{FC6220EE-D6C6-4c8c-A6AF-02463B048936}
The drawing order of this element. The higher the number the later the element is drawn in sequence. This is used to ensure that elements that overlap are rendered in the correct order.
drawingOrder
{9C8F08EF-6539-4118-BEA5-1E00C412E809}
Defines whether or not the diagram objects points define the boundaries of a polygon or the routing of a polyline. If this value is true then a receiving application should consider the first and last points to be connected.
isPolygon
{E105F67A-F735-40c8-828B-50637B38AEBC}
The offset in the X direction. This is used for defining the offset from centre for rendering an icon the default is that a single point specifies the centre of the icon.The offset is in perunit with 0 indicating there is no offset from the horizontal centre of the icon. 0.5 indicates it is offset by 50 to the left and 0.5 indicates an offset of 50 to the right.
offsetX
{9E1EABB6-8384-40b8-B97D-CAC2F81D25CC}
The offset in the Y direction. This is used for defining the offset from centre for rendering an icon the default is that a single point specifies the centre of the icon.The offset is in perunit with 0 indicating there is no offset from the vertical centre of the icon. The offset direction is dependent on the orientation of the diagram with 0.5 and 0.5 indicating an offset of 50 on the vertical axis.
offsetY
{10731F3A-76D6-488f-8C14-CC488A1F8B2D}
The sequence position of the point used for defining the order of points for diagram objects acting as a polyline or polygon with more than one point. The attribute shall be a positive value.
sequenceNumber
{DD5337A3-21F0-414c-B772-EC69C25CB9C0}
The X coordinate of this point.
xPosition
{A3590665-8EB6-420f-B38D-80EDBB9A2879}
The Y coordinate of this point.
yPosition
{997CF101-75B1-45e4-9EEE-974A5021B21A}
The Z coordinate of this point.
zPosition
{DD934E69-A026-4e5c-8806-B82F21273BEE}
A description of the orientation of the object relative to the dimensions. As an example a vault may have northsouth orientation for the sizeLength measurement and sizeDepth may be the height of the vault.
orientation
{A79BC47D-365C-4c49-801D-CDE794D7BB1D}
Behaviour is based on a proprietary model as opposed to a detailed model.true userdefined model is proprietary with behaviour mutually understood by sending and receiving applications and parameters passed as general attributesfalse userdefined model is explicitly defined in terms of control blocks and their input and output signals.
proprietary
{E6E3C01A-8E9E-43d4-9557-EC69B205A70E}
Normal value range maximum for any of the MeasurementValue.values. Used for scaling e.g. in bar graphs or of telemetered raw values.
maxValue
{01F2E304-8F1E-411f-8E9E-F7ABE6EBFDF9}
Normal value range minimum for any of the MeasurementValue.values. Used for scaling e.g. in bar graphs or of telemetered raw values.
minValue
{B037804B-F711-402b-B970-3783F39F5D39}
Normal measurement value e.g. used for percentage calculations.
normalValue
{C5F7B7AF-8F82-4817-AE28-E89B438AC440}
Switch Manual Replace Indicator. Flag indicating that the switch is manual replace.
manualReplaceIndicator
{0F5EB050-1945-4087-B917-F1386235174A}
Removed From Operation Indicator. Flag indicating that the switch is removed from operation.
removeFromOperationIndicator
{8FA4980E-4422-4dcc-A6A9-281639701434}
The value to supervise.
value
{8BEDF964-90B8-4560-85C4-AB072DA60F17}
The Subject DN is the X509 Certificate Subject DN. This is the essentially the certificate name presented by the client. In the case of ADS Certificates this will be the user name. It may be from an API Client or the MP Client GUI.The Subject ID normally includes more than just the user name Common Name it can also contain information such as City Company ID etc.
certificationName
{2F0BD8D9-3850-45cf-8064-E713769E503F}
The target datetime for the received instruction.
instructionTime
{DF69EF06-AD72-4e42-BA97-13EFB9885E8E}
instruction typecommitmentout of sequencedispatch
instructionType
{BB8F257E-A6B7-4383-90DC-48575D271573}
Timestamp indicating the time at which the instruction was received.
receivedTime
{01352FBA-1FA8-409b-AF74-AD7249F13B92}
start time
startTime
{60B3E187-DD10-4762-A31A-8E31E5668E25}
Used to specify the number of intervals when requesting a forecast or a dispatch.
numberOfIntervals
{7CF4BD27-56D1-44f1-939B-97AE671F3FAB}
The start time of the first interval in the dispatch schedule
startTime
{D59461F4-D44A-4a43-8B0F-19108BE7B8E7}
The length of time for each interval in the dispatch schedule.
timeIntervalDuration
{26ECA103-D7A2-4e84-BC4C-4F2BA77FF543}
value
{46E3485A-62DB-425a-B900-3AA4DF718F14}
The end of the time interval for which requirement is defined.
intervalEndTime
{CF797456-529F-4a87-AF1F-10970741A498}
The start of the time interval for which requirement is defined.
intervalStartTime
{923A6AEA-D882-4741-B721-4D9953096F26}
Name of the author of this document.
authorName
{3CAF8786-CCB2-4aac-9223-4099DBF0A5AF}
Free text comment.
comment
{A754AC3E-62CC-4559-8275-82B3391ACEC4}
Date and time that this document was created.
createdDateTime
{2AADF13C-3746-4a53-9569-4D4F32C28CF4}
Date and time this document was last modified. Documents may potentially be modified many times during their lifetime.
lastModifiedDateTime
{779D509D-F4F0-4279-8E0D-CA2FC2B461C9}
Revision number for this document.
revisionNumber
{BB9A66A5-1F53-423b-B1D7-328BB2D64C84}
Document subject.
subject
{9876F55E-396A-4b45-969E-5EF24A46DAB0}
Document title.
title
{D5DB91DF-E1E6-4d77-A2D8-D070A03B9422}
Utilityspecific classification of this document according to its corporate standards practices and existing IT systems e.g. for management of assets maintenance work outage customers etc..
type
{6A6BC1C9-8818-43ca-BFB0-A1A43EFAAD20}
A value used to establish priority of the DOP when plotting. This is only applicable when two DOPs exist for the same time but with different MW values. E.g. when indicating a step in the curve. Its used to determine if the curve steps up or down.
plotPriority
{D15D423F-AFDC-4b55-A01D-6BC69AE3B85D}
DOP time stamp
timestampDOP
{37C842F5-E920-4aed-BB71-C52EBC28C159}
updateTimeStamp
{42FB380E-784A-47b9-9029-726B8C1879CB}
updateUser
{7BD0DDD2-C99C-4955-A471-0F9902D3EBDC}
Dispatch operating target value.
DOT
{C924C44A-2BE0-421f-916C-41AC7FF43AEB}
Actual ramp rate.
actualRampRate
{AABFDE8F-AAF6-45a5-84D7-43DD87AC0215}
Economic Max Limit override for unit this value is null if it is not this value overrides the Energy column value. Allows dispatcher to override the units energy value.
economicMaxOverride
{8AE849EC-4989-4c51-9746-44C9D17B8DCC}
Expected energy.
expectedEnergy
{0D1B3ECD-85B8-40c0-853A-D3AAF1A18DEC}
The Degree of Generator Performance DGP used for the unit. Measure of how a generator responds to raise lower signals. Calculated every five minutes.
generatorPerformanceDegree
{81D47F65-2C70-4e6e-BCD7-C849FBEAD6BD}
HASP results.
hourAheadSchedEnergy
{5A6B1B79-E227-47b8-9448-B9580C8EF722}
Hourly Schedule DA Energy Schedule.
hourlySchedule
{9621C54A-2600-45a1-B43A-2A0C9675C2D7}
The datetime for the instruction.
instructionTime
{B65905A1-FF98-40f5-AA15-228D4B9FDAD2}
True if maximum emergency limit activated false otherwise. If unit is requested to move up to its max emergency limit. this flag is set to true.
maximumEmergencyInd
{5644A1D9-6F4B-4572-8207-B27916EDF715}
Meter Sub System Load Following.
meterLoadFollowing
{C21B8592-E424-4c8f-910C-E40E238C92EA}
Desired MW that is not ramp restricted. If no ramp rate limit existed for the unit this is the MW value tha t the unit was requested to move to.
nonRampRestrictedMW
{51695684-7F17-453d-801E-EE2D5652715B}
Non Spin Reserve used to procure energy.
nonSpinReserve
{F9CECFCC-FD28-48fd-8FBC-269AD59281BE}
Timestamp when the previous DOT value was issued.
previousDOTTimeStamp
{B1382EAF-343E-49d2-8BFB-2C9548C745B8}
The ramp rate limit for the unit in MWs per minute. Participant bidding data.
rampRateLimit
{E1BAF5D7-4C43-4846-9C6A-D5D148BF5E93}
Spin Reserve used to procure energy.
spinReserve
{6BB3E8FB-4AE7-4c5e-BFCA-EA9D11BEE54E}
Standard ramping energy MWH.
standardRampEnergy
{F9988408-3BE0-4b86-A66B-A9117F354493}
Supplemental Energy procure by Real Time Dispatch.
supplementalEnergy
{552B8DCB-414D-4b36-A94E-09FAE594628F}
Output results from the case identifying the reason the unit was committed by the software.
unitStatus
{84754C00-5BFA-4f3b-B1EB-644A35A8AC9F}
Rating of drum boiler in steam units.
drumBoilerRating
{5696E189-9278-4faa-8681-EE8497E8F3F7}
Number of circuits in duct bank. Refer to associations between a duct ConductorAsset and an ACLineSegment to understand which circuits are in which ducts.
circuitCount
{5A3C628A-5B05-46f0-9F6F-06903BD764AC}
Dynamic schedule sign reversal required truefalse
dynSchedSignRev
{BAAD951E-ECBF-4aa7-9C88-F4D718FAB2B5}
The active or inactive status of the dynamic schedule
dynSchedStatus
{AD2F2B96-E195-4c52-A1DD-008C6CA0663E}
Function block used indicator.true use of function block is enabledfalse use of function block is disabled.
enabled
{CEE5F07B-8F7C-4f2b-A690-D0D7F0511216}
The intensity of the earthquake as defined by the Modified Mercalli Intensity MMI scale. Possible values are 112 corresponding to IXII.
intensity
{550A759C-5DB8-4be8-9477-6792BF21F02F}
The magnitude of the earthquake as defined on the Moment Magnitude Msubwsub scale which measures the size of earthquakes in terms of the energy released. Must be greater than zero.
magnitude
{D19FDDEE-5DB4-48df-8B6E-254B7510B1E8}
Primary email address.
email1
{DA76BEA2-70FF-49a9-8FE0-15F027685F54}
Alternate email address.
email2
{A93BB320-542C-411e-A25F-7175F8506C96}
Address on local area network.
lan
{BA953C4D-C5E3-455c-9CFE-3071857ABE3C}
MAC Media Access Control address.
mac
{75AD5365-618B-43ab-B105-C665EA975D92}
Password needed to log in.
password
{9A958851-98D3-49d3-851E-D8A30C44B656}
Radio address.
radio
{E8017C5C-0A76-4cf9-A9C2-77CB35B22A30}
User ID needed to log in which can be for an individual person an organisation a location etc.
userID
{50656270-0E10-4914-9FB1-8907617F90AC}
World wide web address.
web
{19B00DDF-F9E2-4a65-816A-12BE13228934}
value
{C8D2EF5E-4C31-4971-A8F8-4E180EE01040}
Flag is set to true when output is expressed in net active power.
isNetGrossP
{BAB97F88-4F02-4068-BB50-28A0A7E67206}
Automated meter reading AMR or other communication system responsible for communications to this end device.
amrSystem
{BF5942B2-10FF-4829-8C33-C5E109FBA558}
Installation code.
installCode
{1367671F-A0FE-433c-B6E9-6B1CA6E65938}
If true this is a premises area network PAN device.
isPan
{480AB23B-6622-4119-B5D0-A02C35F00C8C}
isSmartInverter
{76E8FF63-8F1A-4236-B7A5-43CD378113EE}
If true there is no physical device. As an example a virtual meter can be defined to aggregate the consumption for two or more physical meters. Otherwise this is a physical hardware device.
isVirtual
{6F065A0C-6D76-4504-B9C1-5283A9DBE66F}
Command text.
command
{44A9E4CF-C396-4026-8450-AAF899F4A721}
True if the action of this control is indefinite.
durationIndefinite
{8F9B70BB-94C3-4385-B8C3-3C60289302C0}
Start date and time for action of this control.
startDateTime
{C5A321BE-7FE7-4aca-8A41-175F04BE09A3}
True if autonomous DST daylight saving time function is supported.
autonomousDst
{D0621056-7652-4d68-ACF8-25D481D8AA2A}
True if communication function is supported.
communication
{9D60E799-5170-4611-B07D-37D2994DF2EC}
True if connect and disconnect function is supported.
connectDisconnect
{483B73C3-A187-47fd-B3C2-9C20C84A41DB}
True if demand response function is supported.
demandResponse
{F405AC35-8DF7-483a-A400-B1201584F6F0}
True if electric metering function is supported.
electricMetering
{752479A9-387B-4d4c-818A-D526CA02A0E8}
True if gas metering function is supported.
gasMetering
{A0A35A59-2C2B-42bf-9B7F-983DAA57824E}
True if metrology function is supported.
metrology
{B585026D-DBE1-4a14-A4E3-D8112BB36AAD}
True if on request read function is supported.
onRequestRead
{3D8EB7C8-D6EB-429a-9379-76710C454E16}
True if outage history function is supported.
outageHistory
{9902B7C2-3D23-441f-BB6A-2221AEED6E52}
True if device performs pressure compensation for metered quantities.
pressureCompensation
{9E1822BD-C9E5-43d5-8104-CE2022588589}
True if pricing information is supported.
pricingInfo
{81151227-D1EB-407c-9660-96B986D50C1D}
True if device produces pulse outputs.
pulseOutput
{73778C03-44E6-433e-ABFC-65130DE1A3B2}
True if relays programming function is supported.
relaysProgramming
{947EBE17-818A-4f43-B7C2-E4971E97C99B}
True if reverse flow function is supported.
reverseFlow
{5463F168-5EEC-4fc1-A707-BFF3CDB3705F}
True if device performs super compressibility compensation for metered quantities.
superCompressibilityCompensation
{D44EC7D9-7D26-4b20-9C4D-ECDDE08BF695}
True if device performs temperature compensation for metered quantities.
temperatureCompensation
{C3092EB3-05F6-41c8-9A18-A703A334532E}
True if the displaying of text messages is supported.
textMessage
{FD453833-A43F-4252-8577-AFA52682E318}
True if water metering function is supported.
waterMetering
{94C5FF37-B19A-4f3d-ABD3-7685CC67D315}
Level of a demand response program request where 0emergency. Note Attribute is not defined on DemandResponseProgram as it is not its inherent property it serves to control it.
drProgramLevel
{361DFF6B-9249-489f-A4EC-B1CCF50D5E7E}
Whether a demand response program request is mandatory. Note Attribute is not defined on DemandResponseProgram as it is not its inherent property it serves to control it.
drProgramMandatory
{5DAB80A8-2513-4627-BC23-91A8A3307404}
Unique identifier of the business entity originating an end device control.
issuerID
{BD9B9B7E-8A1A-4029-AC56-42F901B96AF4}
Identifier assigned by the initiator e.g. retail electric provider of an end device control action to uniquely identify the demand response event text message or other subject of the control action. Can be used when cancelling an event or text message request or to identify the originating event or text message in a consequential end device event.
issuerTrackingID
{B16A2CDD-7E27-4af6-825D-6C8F5A452D7F}
Reason for the control action that allows to determine how to continue processing. For example disconnect meter command may require different processing by the receiving system if it has been issued for a networkrelated reason protection or for a paymentrelated reason.
reason
{21FFC655-460E-4328-9665-50D149C15358}
Highlevel nature of the control.
domain
{0F5F0BE5-F400-4f90-9719-3E9F85437851}
The most specific part of this control type. It is mainly in the form of a verb that gives action to the control that just occurred.
eventOrAction
{C95D1B0C-B29D-4165-A70A-CAFA8E888FE3}
More specific nature of the control as a further subcategorisation of domain.
subDomain
{035EDA6F-4BFB-4beb-AC32-107DF7A0564C}
Type of physical device from which the control was created. A value of zero 0 can be used when the source is unknown.
type
{A990244D-143A-4d58-AF5C-155EC002B101}
Unique identifier of the business entity originating an end device control.
issuerID
{8EC275B9-0B82-45ef-A8DE-33671CAB9CA7}
Identifier assigned by the initiator e.g. retail electric provider of an end device control action to uniquely identify the demand response event text message or other subject of the control action. Can be used when cancelling an event or text message request or to identify the originating event or text message in a consequential end device event.
issuerTrackingID
{14ECC181-8099-44bf-B053-44609BAB463D}
if user initiated ID of user who initiated this end device event.
userID
{9F85911C-8623-4bc5-8CB8-5C58A3E54AF8}
Name.
name
{DC69156D-AAD3-4a56-A300-E88DE10E42F4}
Highlevel nature of the event. By properly classifying events by a small set of domain codes a system can more easily run reports based on the types of events that have occurred or been received.
domain
{253EAC1A-20A2-4f76-B1CF-B2E3AB768C64}
The most specific part of this event type. It is mainly in the form of a verb that gives action to the event that just occurred.
eventOrAction
{50325D8B-DBA3-4df6-9378-35C2605E660A}
More specific nature of the event as a further subcategorisation of domain.
subDomain
{DC206603-1A13-45fb-9DF3-BAC39935408F}
Type of physical device from which the event was created. A value of zero 0 can be used when the source is unknown.
type
{D13065E2-EB45-4b24-9CB7-89FB99F5FC41}
True if the function is enabled.
enabled
{390D762D-C7F9-4c1f-9707-0B03BA5A9C46}
Type of this group.
type
{D0A63F4A-0346-4e67-9E5A-68C9C30CF910}
If true this is a solid state end device as opposed to a mechanical or electromechanical device.
isSolidState
{A6ABA5DD-8711-4727-946F-C84C017BB613}
Number of potential phases the end device supports typically 0 1 or 3.
phaseCount
{FCFAC8D1-C036-4864-9911-9E981B524FCE}
True if duration is indefinite.
durationIndefinite
{EBE804B8-225F-489a-8A00-CEFD415DB073}
Number of individual customers represented by this demand.
customerCount
{EEA34371-CAE6-49b7-A544-81DD3192C676}
Used for Yn and Zn connections. True if the neutral is solidly grounded.
grounded
{56A0DAAA-8C90-4e10-B63E-47E544C63EF6}
isSlack
{3B16B23D-6571-45c6-BC1E-B5D5988511F4}
Energy price index
energyPriceIndex
{3ED23352-20AF-45bf-8D79-908955BAD239}
Time updated
lastModified
{65049BD1-5CAA-46ad-B1F4-F4BDD86C12B6}
Interchange capacity flag. When the flag is set to true it indicates a transaction is capacity backed.
capacityBacked
{F10E101F-E3AE-4b94-AF86-AC4298D02921}
Firm interchange flag indicates whether or not this energy transaction can be changed without potential financial consequences.
firmInterchangeFlag
{DD6E78AE-2C4F-48a6-80F2-6DA9181EAE28}
Willing to Pay congestion flag
payCongestion
{17D8EF73-8AD9-487d-B63C-792A4005D5EB}
Reason for energy transaction.
reason
{0970CD30-651A-40ab-994C-996C98539603}
The type of the issued alert which is drawn from the specified alert type list.
alertType
{B61476BB-A5C4-4c7a-9687-1EFE4D54BE36}
Time and date alert cancelled. Used only if alert is cancelled before it expires.
cancelledDateTime
{61671C52-30AE-42c2-B8AC-9BC22BD30B4B}
An abbreviated textual description of the alert issued. Note the full text of the alert appears in the .description attribute inherited from IdentifiedObject.
headline
{1F4FA496-48C2-485c-8047-A750DD962298}
The timestamp of when the forecast was created
created
{3888907A-F121-4e27-BA62-81FFD19899EF}
Whether this station is currently reporting using daylight saving time. Intended to aid a utility Weather Service in interpreting information coming from a station and has no direct relationship to the manner in which time is expressed in EnvironmentalValueSet.
dstObserved
{7CEFCF49-C763-419b-BE8A-32BD900163DD}
Indication that station is part of a network of stations used to monitor weather phenomena covering a large geographical area.
isNetworked
{7E6E7AB8-C39C-499c-92CD-275E5A3E09B6}
The aggregate flag provides an alternative way of representing an aggregated equivalent element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to true the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine. The attribute is not used for EquivalentBranch EquivalentShunt and EquivalentInjection.
aggregate
{3C000D48-C67D-4cc3-89D6-5F336420B325}
Specifies the availability of the equipment. True means the equipment is available for topology processing which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
inService
{84B66A12-0723-4edf-BC0E-5CD2F4034CC3}
The equipment is enabled to participate in network analysis. If unspecified the value is assumed to be true.
networkAnalysisEnabled
{0B1D0D20-436A-42a0-AD04-DECFCE5CFCF3}
Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
normallyInService
{410CEA04-CA77-46d9-A093-019230A2DE17}
Specifies whether or not the EquivalentInjection has the capability to regulate the local voltage. If true the EquivalentInjection can regulate. If false the EquivalentInjection cannot regulate. ReactiveCapabilityCurve can only be associated with EquivalentInjection if the flag is true.
regulationCapability
{8D94C9DC-F706-4810-96B0-1A08EE8837E4}
Specifies the regulation status of the EquivalentInjection. True is regulating. False is not regulating.
regulationStatus
{79E03A9B-2B54-4de5-BAFE-20735F747738}
Bank ABA.
bankABA
{B2CD78D6-65B3-4528-9B8E-2D5632E820A2}
Calculated date upon which the Invoice amount is due.
dueDate
{8D53F7AD-8126-4a9d-BA88-01D1C21DE4D4}
Date on which the customer billing statementinvoice was printedmailed.
mailedDate
{6731C31D-BCC0-415c-BE70-90D1132C8F6D}
True if payment is to be paid by a Customer to accept a particular ErpQuote with associated Design and have work initiated at which time an associated ErpInvoice should automatically be generated. EprPayment.subjectStatus satisfies terms specificed in the ErpQuote.
proForma
{46430F95-9874-40ab-AF17-32BD0B096923}
Number of an invoice to be reference by this invoice.
referenceNumber
{6382F970-EA3A-4a65-AEE8-46A16C131BDB}
Date and time when the invoice is issued.
transactionDateTime
{54176B4E-F7F5-44df-82EB-58FFBC1BEED7}
Type of invoice transfer.
transferType
{9409F692-8ECA-4d7f-8020-CFECCAB1C8C0}
General Ledger account code must be a valid combination.
glAccount
{82B95CE9-1295-473d-BC59-57671A05A86F}
Date and time line item will be posted to the General Ledger.
glDateTime
{C7BEA464-8250-48a9-B1F8-47070D26243D}
Amount due for this line item.
lineAmount
{BFE467E3-7E55-4804-881D-64E6DA0D592F}
Line item number on invoice statement.
lineNumber
{766920A0-DCEB-464f-873E-0411625AB8E6}
Version number of the bill run.
lineVersion
{26DAA334-4B56-4af3-A53D-86BF6D28936A}
Net line item charge amount.
netAmount
{5114E10D-48ED-43e2-B733-998F0D693226}
Previous line item charge amount.
previousAmount
{3C420DC9-B031-4cbb-9D98-5E24F829A56D}
Account identifier for this entry.
accountID
{4E2C82C7-38D9-41e6-A7D0-35B699198F03}
Date and time this entry is to be posted to the ledger.
postingDateTime
{3311876C-79F6-4bb9-8A20-2DB7707D9D4B}
The identifer of the source for this entry.
sourceID
{73504C54-0C17-47a9-B7BA-398BE859DDB2}
Date and time journal entry was recorded.
transactionDateTime
{4FCB3458-4FCE-44fb-B57B-DE561EFFAA2E}
Account identifier for this entry.
accountID
{77AC00FD-7727-4d42-A2FB-9612FF099467}
Date and time this entry was posted to the ledger.
postedDateTime
{8012748C-8D8E-4d25-9544-20EFEFB243FF}
Date and time journal entry was recorded.
transactionDateTime
{5259D4D8-49FF-4593-82AE-A15FB31065AA}
Payment terms e.g. net 30.
termsPayment
{6C9E4485-78AC-4e69-A7F6-CB9CD83315CB}
code
{8CE8A9A5-20DE-4aba-B505-75DA469D089E}
deliveryDate
{A539A33F-06C0-4f01-AEC9-808F8B685FDD}
Quantity of item requisitioned.
quantity
{A92FBA8F-90CB-46f3-B6F1-858AB8ADDDFE}
estimated time the outage will be restored
ert
{E8CD10EA-E4A7-4741-A408-3D7D30252659}
defines the source that provided the ERT value.
ertSource
{70933541-7619-40b4-AF9E-7C9EFE8C7362}
EHV MW losses in the company Attribute Usage Information purposes Output of LPA engine.
ehvLossMW
{AD826022-CBD7-4a14-87EF-29F1973E973D}
Total MW losses in the company Attribute Usage Information purposes Output of LPA engine.
totalLossMW
{E0672466-2D05-44ee-9A3E-508463002D94}
exPostClearedPrice
{E4CBF494-EF98-4790-9F72-F33048E11A1F}
market energy price
energyPrice
{2FAF176F-93C5-4247-B315-F1B66D444DE1}
Congestion component of Location Marginal Price LMP in monetary units per MW congestion component of the hourly LMP at a specific pricing node Attribute Usage Result of the Security Pricing and DispatchSPDSimultaneous Feasibility TestSFT software and denotes the hourly congestion component of LMP for each pricing node.
congestLMP
{AFBD1903-D336-437c-827F-2BD08F9A06B3}
5 min weighted average LMP the Location Marginal Price of the Pnode for which price calculation is carried out. Attribute Usage 5 min weighted average LMP to be displayed on UI
lmp
{BDC4DBA7-243C-42b8-9BE6-333A29FD494A}
Loss component of Location Marginal Price LMP in monetary units per MW loss component of the hourly LMP at a specific pricing node Attribute Usage Result of the Security Pricing and DispatchSPDSimultaneous Feasibility TestSFT software and denotes the hourly loss component of LMP for each pricing node.
lossLMP
{2BE2B4DD-E47C-47a4-B979-3BB5AF3418AD}
LMP component in USD deprecated
congestionLMP
{D028013A-DEDC-464a-A60E-40D69F0AA0A2}
Desired output of unit
desiredMW
{DBFA9DF0-1342-485c-B818-3923EFB6A2E9}
Unit Dispatch rate from real time unit dispatch.
dispatchRate
{84D0E387-0130-475e-BFFB-FE746462CEA0}
LMP Local Marginal Price in USD at the equipment deprecated
lmp
{09338D77-2444-4dac-89D2-A5A85208496F}
loss lmp deprecated
lossLMP
{9A3E5E51-4A35-46af-8BEE-844C1346EC69}
Economic Maximum MW
maxEconomicMW
{81C7F0DF-A9DE-4699-975A-76330B319D97}
Economic Minimum MW
minEconomicMW
{31A905CF-5127-4469-8DB2-597E958D6EFD}
Current MW output of the equipment Attribute Usage Information purposes Information purposes Output of LPA engine.
resourceMW
{68ED1489-3FA2-4838-86E0-A562397AE2A5}
Indicates if both HV gate and LV gate are active iHVLVgatesi.true gates are usedfalse gates are not used.Typical value true.
hvlvgates
{971A1448-AAAD-46fa-8EBF-298B11A7A9E5}
Exciter saturation function value at the corresponding exciter voltage iVeiisub1subi back of commutating reactance iSeVeiisub1subiii gt 0. Typical value 01.
seve1
{48C7B76B-CF2C-4e80-84DA-5E247986CB84}
Exciter saturation function value at the corresponding exciter voltage iVeiisub2subi back of commutating reactance iSeVeiisub2subiii gt 0. Typical value 003.
seve2
{6574DA42-482B-4b08-8FFE-D705FABC0DDF}
Indicates if HV gate is active iHVgatei.true gate is usedfalse gate is not used.Typical value true.
hvgate
{F4BCA4B2-83CA-479e-83E1-FEDDE079349E}
Indicates if LV gate is active iLVgatei.true gate is usedfalse gate is not used.Typical value true.
lvgate
{88575ABD-CDFA-429d-990B-90A7612C7C95}
Exciter saturation function value at the corresponding exciter voltage iVeiisub1subi back of commutating reactance iSeVeiisub1subiii gt 0. Typical value 0037.
seve1
{F7FA3472-2117-473a-BB79-CFB3218910FD}
Exciter saturation function value at the corresponding exciter voltage iVeiisub2subi back of commutating reactance iSeVeiisub2subiii gt 0. Typical value 0012.
seve2
{EE2FA498-B7B2-498a-BFE0-418C67E8A765}
Exciter saturation function value at the corresponding exciter voltage iVeiisub1subi back of commutating reactance iSeVeiisub1subiii gt 0. Typical value 1143.
seve1
{5CB74FC7-AF77-4b20-9074-E7F8FE157DC2}
Exciter saturation function value at the corresponding exciter voltage iVeiisub2subi back of commutating reactance iSeVeiisub2subiii gt 0. Typical value 01.
seve2
{ACA2A09A-1C95-43b6-B5FF-A1B323F100F8}
Coefficient to allow different usage of the model iai. Typical value 1.
a
{245D492E-2BDB-4a07-B200-F100F94E836B}
Exciter saturation function value at the corresponding exciter voltage iEfdiisub1subi iSeEfdiisub1subiii gt 0. Typical value 086.
seefd1
{3B09F8F3-E5DC-4163-97AF-44BFEF672094}
Exciter saturation function value at the corresponding exciter voltage iEfdiisub2subi iSeEfdiisub2subiii gt 0. Typical value 05.
seefd2
{57F952A9-AF49-478e-96F6-51B6C7A73F16}
Exciter saturation function value at the corresponding exciter voltage iVeiisub1subi back of commutating reactance iSeVeiisub1subiii gt 0. Typical value 0214.
seve1
{8866B5A1-66BC-47d3-8F9C-178E10F15C04}
Exciter saturation function value at the corresponding exciter voltage iVeiisub2subi back of commutating reactance iSeVeiisub2subiii gt 0. Typical value 0044.
seve2
{0BF9F6DD-A0F8-49b3-AD30-5396A4303A8D}
Input limiter indicator.true input limiter iVimaxi and iVimini is consideredfalse input limiter iVimax iand iVimini is not considered.Typical value true.
inlim
{845B6E20-74AB-4c4b-9D22-3C5AD3734A64}
PID limiter indicator.true input limiter iVpidmaxi and iVpidmini is consideredfalse input limiter iVpidmaxi and iVpidmini is not considered.Typical value true.
pidlim
{AD029846-B4B3-4d47-81FA-AE0E8356FF51}
Exciter saturation function value at the corresponding exciter voltage iVeiisub1subi back of commutating reactance iSeVeiisub1subiii gt 0. Typical value 03.
seve1
{C0289295-1816-4510-9AA6-C9280FB932AB}
Exciter saturation function value at the corresponding exciter voltage iVeiisub2subi back of commutating reactance iSeVeiisub2subiii gt 0. Typical value 3.
seve2
{FFBDEE11-E9DD-49c0-A1FD-AFC00D71072A}
Selector for the limiter on the block i1sTei. See diagram for meaning of true and false.Typical value false.
telim
{FE8039D3-B35C-44ac-844E-EE09AA5C0C36}
Multiply by generators terminal voltage indicator.true the limits iVrmaxi and iVrmini are multiplied by the generators terminal voltage to represent a thyristor power stage fed from the generator terminalsfalse limits are not multiplied by generators terminal voltage. Typical value false.
vtmult
{C3AA0638-EA16-4a96-B9D7-BF8B1FDFC9B2}
Governor control flag iBLINTi. 0 leadlag regulator1 proportional integral regulator.Typical value 0.
blint
{ADB7C7AB-BAB8-4939-8BCC-65373511D8A3}
Exciter gain iKiisub2subi. Typical value 20.
k2
{4252EB5F-C096-44e9-9410-1415D9E9A08C}
AVR gain iKiisub3subi. Typical value 1000.
k3
{4AA45B50-82F8-417d-99C0-6400339A1A54}
Ceiling factor iKiisubCEsubi. Typical value 1.
kce
{3751B80B-1CE2-4675-9A09-366C211231C4}
Feedback enabling iKiisubRVECCsubi. 0 open loop control1 closed loop control.Typical value 1.
krvecc
{5EA3BE96-E79F-4ce4-826E-B869FCFC0419}
Rate feedback signal flag iKiisubVFIFsubi. 0 output voltage of the exciter1 exciter field current.Typical value 0.
kvfif
{C758EBEA-BE53-4256-9599-1823CFA566B7}
AVR gain iKiisubAsubi. Typical value 500.
ka
{23A81F36-7918-4c5a-80F3-DACDBBFAA90D}
Rate feedback gain iKiisubFsubi. Typical value 012.
kf
{A66FC96A-D837-4839-9AAC-6D2307C5361B}
Saturation factor at iEiisub1subi iSEiisub1subiii. Typical value 01.
se1
{A450D456-D29D-4f13-AB1D-B782A6308442}
Saturation factor at iEiisub2subi iSEiisub2subiii. Typical value 003.
se2
{560B7978-D976-43dd-A565-80DB7807A657}
AVR gain iKiisubAsubi. Typical value 500.
ka
{C7E4A97A-F8EA-4888-BD2B-0678C608D911}
Rate feedback gain iKiisubFsubi. Typical value 012.
kf
{06B712E0-FF45-456b-828C-391E11F7305E}
Saturation factor at iEiisub1subi iSEiisub1subiii. Typical value 0.1.
se1
{79FF18E7-66C0-471a-B91E-4749C5307CFB}
Saturation factor at iEiisub2subi iSEiisub2subiii. Typical value 003.
se2
{3014A25E-F6AF-41b4-8CFF-72D86F8FBE8B}
AVR gain iKiisubAsubi. Typical value 100.
ka
{476AE42A-60AA-4542-96B5-3BAFC6417E08}
Saturation factor at iEiisub1subii iiSEiisub1subiii. Typical value 01.
se1
{16A35A8B-249F-4d5c-99B7-4D3B1D5A59A9}
Saturation factor at iEiisub2subii iiSEiisub2subiii. Typical value 003.
se2
{0E067215-432D-4be0-9606-2C80DC19B5A5}
AVR output voltage dependency selector iIiisubMULsubi.true selector is connectedfalse selector is not connected.Typical value true.
imul
{A83D1C80-58C3-49d2-A414-0C5997E9B8D3}
AVR gain iKiisubAsubi. Typical value 300.
ka
{5173E778-715B-4e8a-BABB-9F6F08A5FFB9}
Exciter gain iKiisubEsubiii. Typical value 1.
ke
{7AE9490D-26A4-4579-A9B7-264B12B135AA}
Exciter internal reactance iKiisubIFsubi. Typical value 0.
kif
{1A8FE213-DE3A-42cd-8B7B-8FD0E16B62FC}
Supplementary signal routing selector iswitchi.true iVsi connected to 3rd summing pointfalse iVsi connected to 1st summing point see diagram.Typical value false.
switch
{9B8B51F4-9197-4d15-893F-0FC6B7D0F1B1}
iexclimi. IEEE standard is ambiguous about lower limit on exciter output. true a lower limit of zero is applied to integrator outputfalse a lower limit of zero is not applied to integrator output.Typical value true.
exclim
{F6772296-58D3-4ad8-B03D-A4A0DB9616B3}
Exciter saturation function value at the corresponding exciter voltage iEfdiisub1subi iSeEefdiisub1subiii gt 0. Typical value 033.
seefd1
{BA09D802-A2C4-4154-91E0-ED8AE32BDE1F}
Exciter saturation function value at the corresponding exciter voltage iEfdiisub2subi iSeEefdiisub2subiii gt 0. Typical value 01.
seefd2
{561A08D3-A350-4080-B4AD-FF3876C84E90}
iexclimi. IEEE standard is ambiguous about lower limit on exciter output.true a lower limit of zero is applied to integrator outputfalse a lower limit of zero is not applied to integrator output.Typical value true.
exclim
{74E2E48F-7952-4980-BC83-5ED53BC081F6}
Exciter saturation function value at the corresponding exciter voltage iEfdiisub1subi iSeEfdiisub1subiii gt 0. Typical value 0279.
seefd1
{C2018CA0-F49E-4309-BB81-B0FD0704E212}
Exciter saturation function value at the corresponding exciter voltage iEfdiisub2subi iSeEfdiisub2subiii gt 0. Typical value 0117.
seefd2
{F82E7AE4-4FE7-4e2e-B858-2B124C50CEA4}
iVtlimi.true limiter at the block iKa 1 sTai is dependent on iVt ifalse limiter at the block is not dependent on iVti.Typical value true.
vtlim
{56A88055-8164-4405-909A-813E4DF99268}
iEfdlimi.true exciter output limiter is activefalse exciter output limiter not active.Typical value true.
efdlim
{CA5C8CF6-0BA4-4ae2-89B5-EE09ED810C5E}
iexclimi. IEEE standard is ambiguous about lower limit on exciter output.true a lower limit of zero is applied to integrator outputfalse a lower limit of zero not applied to integrator output.Typical value true.
exclim
{493D6B50-A7B6-4a34-87C8-E6EB8EF852D7}
Exciter saturation function value at the corresponding exciter voltage iEfdiisub1subi iSeEfdiisub1subiii gt 0. Typical value 01.
seefd1
{6FEE3EC7-DDC3-4050-A7CC-24809314D140}
Exciter saturation function value at the corresponding exciter voltage iEfdiisub2subi iSeEfdiisub2subiii gt 0. Typical value 035.
seefd2
{AD0ADFFE-6FE1-4f86-94A3-AE6B48BB99AE}
iexclimi.true lower limit of zero is applied to integrator outputfalse lower limit of zero not applied to integrator output.Typical value true.
exclim
{67BACD0E-1B5D-4db5-A237-A3AD470B1062}
Vb limiter indicator.true exciter iVbmaxi limiter is activefalse iVb1maxi is active. Typical value true.
vblim
{0643055E-27A0-4822-8B53-22E4DD461AEB}
Voltage base conversion constant iKei. Typical value 4666.
ke
{5769BF55-A790-4a7d-83E4-9D52CF3F298E}
Current base conversion constant iKii. Typical value 021428.
ki
{5248F81B-1D48-41df-B9CC-2A6964B0D8E8}
Exciter saturation function value at the corresponding exciter voltage iViisubE1subi back of commutating reactance iSiisubEsubiiViisubE1subiii gt 0. Typical value 01.
seve1
{DB8EE451-F00D-4345-91DF-76788471A867}
Exciter saturation function value at the corresponding exciter voltage iViisubE2subi back of commutating reactance iSiisubEsubiiViisubE2subiii gt 0. Typical value 003.
seve2
{5040884C-91CA-483b-92C1-764CCEEBFDF7}
Exciter saturation function value at the corresponding exciter voltage iViisubE1subi back of commutating reactance iSiisubEsubiiViisubE1subiii gt 0. Typical value 0037.
seve1
{59780752-CD47-4dc3-B4EA-1F4D2D2CD00F}
Exciter saturation function value at the corresponding exciter voltage iViisubE2subi back of commutating reactance iSiisubEsubiiViisubE2subiii gt 0. Typical value 0012.
seve2
{60F3E03D-A073-4b83-840B-16AAE273EFC8}
Exciter saturation function value at the corresponding exciter voltage iViisubE1subi back of commutating reactance iSiisubEsubiiViisubE1subiii gt 0. Typical value 1143.
seve1
{857CF7D9-4D69-403b-A1E0-899D707C3502}
Exciter saturation function value at the corresponding exciter voltage iViisubE2subi back of commutating reactance iSiisubEsubiiViisubE2subiii gt 0. Typical value 01.
seve2
{BAE75C79-8F63-444f-9486-863933DD29E5}
Exciter saturation function value at the corresponding exciter voltage iEiisubFD1subi iSiisubEsubiiEiisubFD1subiii gt 0. Typical value 086.
seefd1
{995A78B6-48C1-40eb-940A-25CC88B46269}
Exciter saturation function value at the corresponding exciter voltage iEiisubFD2subi iSiisubEsubiiEiisubFD2subiii gt 0. Typical value 05.
seefd2
{1DD0B8D0-600F-4aac-97F6-109B41CB13D7}
Exciter saturation function value at the corresponding exciter voltage iViisubE1subi back of commutating reactance iSiisubEsubiiViisubE1subiii gt 0. Typical value 0214.
seve1
{127B17E2-19AA-461a-A6F5-B1ACB71A79E6}
Exciter saturation function value at the corresponding exciter voltage iViisubE2subi back of commutating reactance iSiisubEsubiiViisubE2subiii gt 0. Typical value 0044.
seve2
{950BA46D-7147-421d-BBD0-24D9F2AC43BE}
Exciter saturation function value at the corresponding exciter voltage iViisubE1subi back of commutating reactance iSiisubEsubiiViisubE1subiii gt 0. Typical value 044.
seve1
{63F1D856-9A79-4dcb-9C02-63EAB30A0476}
Exciter saturation function value at the corresponding exciter voltage iViisubE2subi back of commutating reactance iSiisubEsubiiViisubE2subiii gt 0. Typical value 0075.
seve2
{90A8F4BB-CE36-45fd-9E5E-B44A9A27A86A}
Exciter saturation function value at the corresponding exciter voltage iViisubE1subi back of commutating reactance iSiisubEsubiiViisubE1subiii gt 0. Typical value 03.
seve1
{DBFC6806-485A-4944-9461-9327CEDD05A3}
Exciter saturation function value at the corresponding exciter voltage iViisubE2subi back of commutating reactance iSiisubEsubiiViisubE2subiii gt 0. Typical value 3.
seve2
{9C345CC4-84DE-4110-9D73-9BE657FD1D4F}
iexclimi. IEEE standard is ambiguous about lower limit on exciter output.true a lower limit of zero is applied to integrator outputfalse a lower limit of zero is not applied to integrator output.Typical value true.
exclim
{A8CC72E6-B221-4df6-8512-901EC73B106A}
Exciter saturation function value at the corresponding exciter voltage iEiisubFD1subi iSiisubEsubiiEiisubFD1subiii gt 0. Typical value 0.33.
seefd1
{AE072325-5BB2-4520-A1C0-F4363CDCD38D}
Exciter saturation function value at the corresponding exciter voltage iEiisubFD2subi iSiisubEsubiiEiisubFD2subiii gt 0. Typical value 01.
seefd2
{81E0A29E-4BA0-413c-9FA3-319426FC5108}
UEL input iuelini.true input is connected to the HV gatefalse input connects to the error signal.Typical value true.
uelin
{0AD26100-3CFD-475e-87ED-6056BB10D2AB}
Exciter saturation function value at the corresponding exciter voltage iEiisubFD1subi iSiisubEsubiiEiisubFD1subiii gt 0. Typical value 0279.
seefd1
{9443FE9C-EAFA-4c69-8C4B-3E99C652452A}
Exciter saturation function value at the corresponding exciter voltage iEiisubFD2subi iSiisubEsubiiEiisubFD2subiii gt 0. Typical value 0117.
seefd2
{DE1FE73D-137A-4921-9264-ABBC8A97BF29}
UEL input iuelini.true input is connected to the HV gatefalse input connects to the error signal.Typical value true.
uelin
{4DD79FCA-E438-4659-81AB-6ED216F18A4F}
iexclimi. IEEE standard is ambiguous about lower limit on exciter output.true a lower limit of zero is applied to integrator outputfalse a lower limit of zero is not applied to integrator output.Typical value true.
exclim
{EE0498C2-5761-48f8-AA0B-F9F0683C01D4}
Exciter saturation function value at the corresponding exciter voltage iEiisubFD1subi iSiisubEsubiiEiisubFD1subiii gt 0. Typical value 0267.
seefd1
{286AA295-1129-4000-A7C3-AAA2704AC8BD}
Exciter saturation function value at the corresponding exciter voltage iEiisubFD2subi iSiisubEsubiiEiisubFD2subiii gt 0. Typical value 0068.
seefd2
{90CD7D02-3C97-4c68-A207-2760D27A71F9}
OEL input iOELini.true LV gatefalse subtract from error signal.Typical value true.
oelin
{46880FA6-779F-4a87-8C9D-5C7C4A815C57}
Exciter saturation function value at the corresponding exciter voltage iEiisubFD1subi iSiisubEsubiiEiisubFD1subiii gt 0. Typical value 008.
seefd1
{F0F5A5BC-EB93-40cf-B4CB-4DE77B1150CD}
Exciter saturation function value at the corresponding exciter voltage iEiisubFD2subi iSiisubEsubiiEiisubFD2subiii gt 0. Typical value 027.
seefd2
{F35D1879-5442-4788-A966-A36335426B77}
UEL input iUELini.true HV gatefalse add to error signal.Typical value true.
uelin
{DC53D240-059A-40ef-9337-8FF898F1B149}
Selector of the Power System Stabilizer PSS input iPSSini.true PSS input iVsi added to error signalfalse PSS input iVsi added to voltage regulator output.Typical value true.
pssin
{1333FCED-55F2-41e7-A961-E87D72843546}
UEL input iUELini.true HV gatefalse add to error signal.Typical value true.
uelin
{51994929-6954-4bf6-85C1-E955187B5E15}
Fed by selector iBusFedSelectori. true bus fed switch is closedfalse solid fed switch is open.Typical value true.
busFedSelector
{E92EC7AE-D456-4ac3-9CC9-CCC8F5EA7206}
Voltage reference input gain iKi0i. Typical value 127.
ki0
{B493D123-40C6-4d54-BB37-324D37E7B58B}
Voltage input gain iKi1i. Typical value 168.
ki1
{CF8C5BF0-C0EC-4814-98A4-5F62A3959B5E}
OEL input gain iKLIRi. Typical value 1213.
klir
{3B7C47BD-BD93-4e54-849D-F3830B065933}
Limiter gain iKLUSi. Typical value 50.
klus
{AAB000CA-5586-42ea-B9B3-99DA20A8A415}
Power source switch iCswitchi.true fixed voltage of 1.0 PUfalse generator terminal voltage.
cswitch
{C074CB80-072C-4e94-8549-61A422EBE381}
Ratio of field discharge resistance to field winding resistance irc rfdi. Typical value 0.
rcrfd
{E9A327DF-C4C7-4b09-B83B-EB1B93D47B0F}
Gain reduction ratio of laglead element iTai iTbi. The parameter iTai is not defined explicitly. Typical value 0.1.
tatb
{AEFE1FBC-C9AE-4337-AF1D-0781DF8EE7DC}
Gain reduction ratio of laglead element iTa Tbi. Typical value 01.
tatb
{4AE50BB0-88B8-4bdf-BE88-73A4B6115B9F}
Secondary voltage control state iQconoffi.true secondary voltage control is onfalse secondary voltage control is off.Typical value false.
qconoff
{FF19F789-1DF6-45e7-8865-1B0014A41D0F}
Selector to apply automatic calculation in secondary controller model iremotei.true automatic calculation is activatedfalse manual set is active the use of desired value of reactive power iQzi is required.Typical value true.
remote
{7C164CD6-B160-4ec5-8EA4-34D336810E57}
UEL input iUELini.true HV gatefalse add to error signal.Typical value false.
uelin
{D4130127-D1FA-4c62-963B-70591D41EDD9}
Selector iLVGatei.true iLVGatei is part of the block diagramfalse iLVGatei is not part of the block diagram. Typical value false.
lvgate
{9BBCC5A0-EBCB-4bd2-9C87-4B2685723C6B}
Selector iUELi.true iUELi is part of block diagramfalse iUELi is not part of block diagram. Typical value false.
uel
{68A6C837-3C9A-4693-94A1-516F54D3C8F8}
Selector iK1i.true feedback is from iIfdifalse feedback is not from iIfdi.Typical value true.
k1
{CACE10C1-DF79-4632-87D5-7C61DD6EA942}
Selector iVilimi.true iViminiiVimaxi limiter is activefalse iViminiiVimaxi limiter is not active.Typical value true.
vilim
{A4DEC66C-1034-467d-B0C7-B1884D6D9CE1}
Selector ivmulti.true multiply regulator output by terminal voltagefalse do not multiply regulator output by terminal voltage. Typical value true.
vmult
{1C4E0B4F-40A8-4a21-A44A-1F7945DE6EB7}
Behaviour is based on a proprietary model as opposed to a detailed model.true userdefined model is proprietary with behaviour mutually understood by sending and receiving applications and parameters passed as general attributesfalse userdefined model is explicitly defined in terms of control blocks and their input and output signals.
proprietary
{86F95A3E-DDC1-4785-B0E4-926F616635BD}
intervalStartTime
{4BF0246B-5735-4a23-998F-E56F8D907327}
updateTimeStamp
{13007307-4778-4028-BE29-8050780E6B64}
updateUser
{56736E2C-5D60-4d27-B52E-8B1FBE4E14D6}
energyTypeCode
{5B44E17B-9EB8-44e9-A30C-6C99649DD2DC}
expectedMwh
{FEAF95C4-FFE7-4026-9A71-939329F66292}
extName
{2424595E-296B-4c62-991F-9F00CF7E6B50}
extType
{8D63A655-FF51-4598-8DD0-B744700BB701}
extValue
{9E51695E-B885-4386-A558-626EC7909BB3}
Indicates whether initial symmetrical shortcircuit current and power have been calculated according to IEC Ik. Used only if short circuit calculations are done according to superposition method.
ikSecond
{8CE33CA0-BF90-4ffb-8094-3E13248C294D}
Maximum ratio of zero sequence resistance of Network Feeder to its zero sequence reactance R0X0 max. Used for short circuit data exchange according to IEC 60909.
maxR0ToX0Ratio
{DEEA4970-8179-4c0c-835B-448F523182C6}
Maximum ratio of positive sequence resistance of Network Feeder to its positive sequence reactance R1X1 max. Used for short circuit data exchange according to IEC 60909.
maxR1ToX1Ratio
{38290CCA-41EE-43e1-A7C4-FC39CFB33C7C}
Maximum ratio of zero sequence impedance to its positive sequence impedance Z0Z1 max. Used for short circuit data exchange according to IEC 60909.
maxZ0ToZ1Ratio
{FC3C5788-3C3E-41a9-B90F-01C842E72DEE}
Indicates whether initial symmetrical shortcircuit current and power have been calculated according to IEC Ik. Used for short circuit data exchange according to IEC 6090.
minR0ToX0Ratio
{BCD7177E-8D88-4797-949C-3068CE234417}
Minimum ratio of positive sequence resistance of Network Feeder to its positive sequence reactance R1X1 min. Used for short circuit data exchange according to IEC 60909.
minR1ToX1Ratio
{A2644704-DF87-4b44-8C4D-F4D202095BB0}
Minimum ratio of zero sequence impedance to its positive sequence impedance Z0Z1 min. Used for short circuit data exchange according to IEC 60909.
minZ0ToZ1Ratio
{224FEA10-D384-4c38-87D8-5B84DA49BD3F}
Priority of unit for use as powerflow voltage phase angle reference bus selection. 0 don t care default 1 highest priority. 2 is less than 1 and so on.
referencePriority
{FFD18DCF-6376-4723-B60B-AC8A81B4F137}
Buy Sell
action
{9BD3A6B7-999D-4ab7-995D-6EFA5D957B0C}
Peak Offpeak 24hour
class
{3CEB668B-EB29-4356-BA7E-AE996421A421}
Type of rights being offered product allowed to be auctioned option obligation.
ftrType
{716C38B8-9A57-4a96-BB17-514ACB08D40A}
Fixed covers reconfiguration grandfathering or Optimized up for salepurchase
optimized
{FA4480C9-2B55-47f0-9F12-FC173A0FD439}
Kind of this facility.
kind
{FF15BEF0-DD46-40e7-A1E3-C4045F50C87A}
Code for asset failure.
corporateCode
{BC0A1588-289A-48d2-8DC3-1ECA185AF1C9}
Time and date of asset failure.
failureDateTime
{05ED4F1E-5A60-45f5-924A-40000EF40685}
The method used for locating the faulted part of the asset. For example cable options include Cap DischargeThumping Bridge Method Visual Inspection Other.
faultLocatingMethod
{544149E0-9B4A-4baf-8374-8E6A6A08A2BE}
Failure location on an object.
location
{5B5B0023-5670-4f17-89BF-BB3C4161A05B}
Root cause of asset failure.
rootCause
{664D7023-3674-4b41-AB44-9CA0A37A0592}
The date and time at which the fault occurred.
occurredDateTime
{A564D5B3-A502-4507-A8B7-8134E17FDA4E}
The date and time at which the dispatch status occurred.
occurredDateTime
{38688B4D-E353-4dad-9FF7-7543D70D491F}
freeform comments related to the dispatch to perform field work.
remarks
{35E22BA8-BF26-4fba-9CBE-395DB4BFB660}
The sequence number of the field dispatch step within the field dispatch history. Begins with 1 and increments up.
sequenceNumber
{C88B525A-CB47-4781-8FF9-C1F15B82F353}
The account to which this actual material item is charged.
account
{5E65F3EF-B411-4420-9BF2-7CA3553D2A28}
Description of the cost.
costDescription
{DAFA0F90-F985-4d9d-9F37-5388AC176999}
Type of cost to which this Material Item belongs.
costType
{57680149-B42B-4c6a-8B78-D88A6FD1842D}
Date and time assets financial value was put in plant for regulatory accounting purposes e.g. for rate base calculations. This is sometime referred to as the inservice date.
plantTransferDateTime
{98C87236-3163-4be6-A3D1-8C04C10343E0}
Date and time asset was purchased.
purchaseDateTime
{7BC01C58-833F-457f-8340-877E574D71DF}
Purchase order identifier.
purchaseOrderNumber
{F6E01293-2490-46cb-AC01-4A687C9115F2}
Date and time at which the financial value was last established.
valueDateTime
{9B3F8DAC-2349-455a-ADE8-D2D7D451C356}
Date and time warranty on asset expires.
warrantyEndDateTime
{3BF06345-071E-4850-A331-E589FA670BDF}
intervalStartTime
{360A3631-84DB-495f-ABCD-3B521D40BB53}
updateTimeStamp
{3B07678A-2E49-40b4-92DF-FA6FE6C0B07A}
updateUser
{BC79ADAA-69D4-41ed-9371-100CA07F2ED4}
Value of this quantity.
value
{5E8E552B-F83E-4980-805D-4D158E4E97CA}
The coded identification of the direction of energy flow.
direction
{F3B42A18-C9A0-4e82-9363-68D5FBEFA898}
DateTime when record becomes effective Used to determine when a record becomes effective.
effectiveDate
{672DB5BF-19A6-4de7-AB36-754894803108}
Energy Flow level that should be maintained according to the TLR rules as specified by the IDC. For Realtime Markets use in dispatch to control constraints under TLR and calculate unconstrained market flows
idcTargetMktFlow
{684CE646-566D-433c-B71A-8AF2713EDFC8}
DateTime when record is no longer effective Used to determine when a record is no longer effective
terminateDate
{1C6D40BE-BF3F-4c23-A7DC-EF5815300B96}
Limit for Economic Dispatch priority 6 energy flow on the specified flowgate for the specified time period.
economicDispatchLimit
{8579296C-5600-4731-BF1D-10BA1FD50096}
DateTime when record becomes effective Used to determine when a record becomes effective
effectiveDate
{D30DAB67-7DBD-4a7c-BA37-9FE57DB2A1C2}
Limit for firm flow on the specified flowgate for the specified time period. The amount of energy flow over a specifed flowgate due to generation in the market which can be classified as Firm Network priority.
firmNetworkLimit
{066A7B63-FEE8-4ec0-A39E-CFFCC5FA1B85}
The amount of energy flow over a specifed flowgate due to generation in the market.
mktFlow
{CBF555DE-AD61-49e4-A3EC-D24CFAFEF509}
Net Energy flow in flowgate for the associated FlowgatePartner
netFirmNetworkLimit
{DE1F7658-1D49-4f7d-BB15-E5E9A87C4D55}
Time to cross the forbidden region in minutes.
crossTime
{37663C0E-0AC7-4b37-A26A-EB6CD191F457}
Cost associated with crossing the forbidden region
crossingCost
{3BF0D02C-CE07-4bb9-9AFA-8F1664D740A4}
High end of the region definition
highMW
{2B24B12B-69CB-4120-ABE4-C0B0CFE55542}
Low end of the region definition.
lowMW
{9372EFA9-7C28-4e74-86EE-5146FCA6E049}
The amount of heat per weight or volume of the given type of fuel.
fuelHeatContent
{015BCC20-6735-4f96-98F8-3F76D09FF7EE}
Active power error bias ratio.
controlErrorBiasP
{2465489F-93F1-4e03-B147-7AEB3BCB4C3D}
Integral constant.
controlIC
{F6ECDB33-EC5C-4331-8CAF-CB4FA1E0DDC2}
Proportional constant.
controlPC
{3E31C8E3-D0E1-4470-AC21-AECEFAA587D3}
Pressure error bias ratio.
controlPEB
{877704D3-C236-44cd-838B-340F3046F472}
Time constant.
controlTC
{C8CEC5DB-3D44-432a-88D8-6DBE23594E7B}
Feedwater integral gain ratio.
feedWaterIG
{D367B901-4670-482b-8B8E-7B4F6C967BD8}
Feedwater proportional gain ratio.
feedWaterPG
{EF2F8E46-83D2-42da-AB4D-2A1CAC5E0ECC}
Active power maximum error rate limit.
maxErrorRateP
{123B3594-1A16-4554-B4AE-4ACCAA5D07BC}
Active power minimum error rate limit.
minErrorRateP
{8E5CE183-191F-492f-86B4-BF8640C2CFBB}
Pressure control derivative gain ratio.
pressureCtrlDG
{D6F0B17C-8414-4eed-8EDE-E5DA08EDCC11}
Pressure control integral gain ratio.
pressureCtrlIG
{4CAC03F1-364F-402f-8A36-2E683685E7BF}
Pressure control proportional gain ratio.
pressureCtrlPG
{5ACE586A-890A-4fb8-AB1A-388B934C263B}
Pressure feedback indicator.
pressureFeedback
{1097FA75-EB4A-400a-8C63-0B94B18D1159}
Drumprimary superheater capacity.
superHeater1Capacity
{1E936ADE-3C2D-4635-8005-685C2CEDBD46}
Secondary superheater capacity.
superHeater2Capacity
{9D1898CD-0EEC-4747-A935-FF6D01F6C12D}
Superheater pipe pressure drop constant.
superHeaterPipePD
{56E7A7FA-CEF9-411e-849C-84119FE62329}
value
{1CC12D60-90B2-4e21-BD77-F209F6F728FF}
The end time and date of the fuel allocation schedule.
fuelAllocationEndDate
{9FC1D7F8-69D8-4f17-995B-B54C93AA1350}
The start time and date of the fuel allocation schedule.
fuelAllocationStartDate
{B12E17BB-85DD-4456-A819-3EEC89BDAB05}
The maximum amount of fuel that is allocated for consumption for the scheduled time period.
maxFuelAllocation
{0EC3CD8C-365E-4192-9BDA-152C02D056CC}
The minimum amount of fuel that is allocated for consumption for the scheduled time period e.g. based on a takeorpay contract.
minFuelAllocation
{EE916503-410E-4bb2-9251-20DE555D98DC}
The type of fuel region
fuelRegionType
{AF55DD4A-C4F6-4585-8D74-7E732C876C78}
Time of last update
lastModified
{2ACCB12D-341D-4aac-A4C6-6957D1D561CA}
The average natural gas price at a defined fuel region.
gasPriceIndex
{8A1ED58F-C713-486a-82E5-F90AADF15C02}
If true use the absolute value for compare..
absoluteValue
{FCD69B93-BD2B-42c1-8FFC-14CAA4F0FDBD}
Invertnegate the result of the compare.
negate
{57662A74-7AB0-464d-9C1C-4E735E89E55B}
The threshold value that should be used for compare with the input value.
thresholdValue
{59CA253A-1EE5-4192-A27F-388F80703FA9}
Used to calculate generation participation of an individual pnond in an AggregatePnode.
factor
{2FC84093-36C6-4bcf-A247-E0C98E852B19}
Flag is set to true when output is expressed in net active power.
isNetGrossP
{8EFD6391-C73C-45f1-A334-721A9B751FC3}
Amount of load in the control zone Attribute Usage hourly load value for the specific area
totalLoad
{E2E858F3-E1B6-461c-8ADA-0CF28847876E}
Amount of interchange for the control zone Attribute Usage hourly interchange value for the specific area
totalNetInterchange
{60E7974B-B192-463e-8055-5A325884D009}
Will indicate if the unit is part of a CC offer or not
combinedCycleUnitOffer
{57ACBC9F-9C37-4ce6-B886-4E59E342D585}
Maximum down time.
downTimeMax
{0859DD24-BADD-4189-BA08-4C0D925E8866}
Installed Capacity value
installedCapacity
{C9A06448-BE92-4f1c-83EB-18CE43655B2E}
Maximum high economic MW limit that should not exceed the maximum operating MW limit
maximumEconomicMW
{D938C2FF-5DCE-43ba-9524-0C8FA9EE818F}
Low economic MW limit that shall be greater than or equal to the minimum operating MW limit
minimumEconomicMW
{E6EFC602-CD7E-4dbe-9903-0F4491A89B7F}
Resource fixed no load cost.
noLoadCost
{41F39618-2E9C-45ab-A74F-6ACB2E00150E}
Time required for crew notification prior to start up of the unit.
notificationTime
{FE1017DB-8365-4465-BB5A-986B2A3B2F6F}
Bid operating mode C cycling F fixed M must run U unavailable
operatingMode
{AEEC8F5C-4664-433f-A6DD-591863E95FB0}
Ramp curve type0 Fixed ramp rate independent of rate function unit MW output1 Static ramp rates as a function of unit MW output only 2 Dynamic ramp rates as a function of unit MW output and ramping time
rampCurveType
{BA84B0DF-C164-4878-B947-16C593E9A7A1}
Resource startup type1 Fixed startup time and fixed startup cost2 Startup time as a function of down time and fixed startup cost3 Startup cost as a function of down time
startUpType
{D041FD53-9267-494a-A6BF-0DD69AE770B2}
Startup costprice
startupCost
{85767EF9-0AD6-436a-A1D0-2F5B5D1E4692}
Maximum up time.
upTimeMax
{1A7DE6C7-EDC8-46cb-BED4-7AB384081DC2}
Generating unit long term economic participation factor.
longPF
{814E1820-70AE-4773-8776-0D3AA9728977}
Generating unit economic participation factor. The sum of the participation factors across generating units does not have to sum to one. It is used for representing distributed slack participation factor. The attribute shall be a positive value or zero.
normalPF
{5C5B950D-8DCC-4ec0-A054-5B1A1F99B724}
Defined as 1 1 Incremental Transmission Loss with the Incremental Transmission Loss expressed as a plus or minus value. The typical range of penalty factors is 0.9 to 1.1.
penaltyFactor
{75B099B9-2375-42c3-AD10-F54FBBCAA4FA}
Generating unit short term economic participation factor.
shortPF
{EFD06B26-999F-492d-B482-C8EE20F3AF6E}
Generating unit economic participation factor.
tieLinePF
{B0D4B4E5-5975-493b-9401-7F13F1D6A824}
Loss Factor
lossFactor
{1EC86402-55A6-46c9-9D2E-BF650BAC5019}
Unit reactive power generation in MVAR
mVAR
{FA1C8DF2-7CCB-4828-98CA-BA3935B261DD}
The maximum active power generation of the unit in MW
maximumMW
{CC2F56E7-B1E0-4754-99CF-CA5B7F0F85D3}
The minimum active power generation of the unit in MW
minimumMW
{9359A3E7-53B8-4e04-B0EC-985E08960789}
Unit active power generation in MW
mw
{2226A9AA-18B1-4f2b-AD72-8C70A25ED01A}
Unit sencivity factor. The distribution factors DFAX for the unit
sensitivity
{119B4D4D-96AE-4539-AD6A-B559878BAA9E}
Interval End Time
intervalEndTime
{7A90559E-067F-41d5-9470-0558AF10403D}
Interval Start Time
intervalStartTime
{6CCC99B1-BE6B-4c55-9E78-F4985231F26F}
Maximum Limit MW
maxLimit
{C661D952-3810-4239-9DD3-AF9290D014C2}
Minimum Limit MW
minLimit
{2A7DE582-F470-4056-AADC-210EAF5A0D82}
The universal CIM version name describing a consistent set of packages.
majorVersion
{C95DF1AC-45B6-4749-BB5F-0780762CB7FE}
Describe minor updates and error corrections.
minorVersion
{FFFB2C42-020B-4561-81D8-93A831D4AC7F}
The date when the complete CIM canonical model is published and made available for use After the publication the major version and name space are updated.
published
{D1602C8A-0004-4edc-A797-1A4F32BF4905}
Acceleration limiter setpoint iAseti. Unit PU s. Typical value 001.
aset
{257C6F96-A6F6-4c69-BC2C-2419DCACE098}
Minimum valve closing rate iRclosei. Unit PU s. Typical value 01.
rclose
{0A646A3E-1697-4f53-B21C-131243FEDA8C}
Maximum valve opening rate iRopeni. Unit PU s. Typical value 0.10.
ropen
{6DC5228C-7937-4a96-8B05-BB465F1E0FC1}
Switch for fuel source characteristic to recognize that fuel flow for a given fuel valve stroke can be proportional to engine speed iWfspdi.true fuel flow proportional to speed for some gas turbines and diesel engines with positive displacement fuel injectorsfalse fuel control system keeps fuel flow independent of engine speed.Typical value true.
wfspd
{7E83B056-E060-4256-B604-86D1AD1A5671}
Acceleration limiter setpoint iAseti. Unit PU s. Typical value 10.
aset
{0291153F-DCB6-4fc1-A0AD-45B0F5B5FB2B}
Minimum valve closing rate iRclosei. Unit PU s. Typical value 99.
rclose
{A1C2BDBB-7631-4069-851F-B95E834D0F46}
Maximum valve opening rate iRopeni. Unit PU s. Typical value 99.
ropen
{7FD30DB6-2FDD-42b7-B62F-009C719D3FD6}
Switch for fuel source characteristic to recognize that fuel flow for a given fuel valve stroke can be proportional to engine speed iWfspdi.true fuel flow proportional to speed for some gas turbines and diesel engines with positive displacement fuel injectorsfalse fuel control system keeps fuel flow independent of engine speed.Typical value false.
wfspd
{A09DFA99-5733-4aa0-8CF8-393EEF97F285}
Turbine power time constant numerator scale factor iai. Typical value 08.
a
{4B713CC1-D1B2-4a2e-99CA-747ABD7FC3E9}
Turbine power time constant denominator scale factor ibi gt0. Typical value 1.
b
{EF7FF898-4236-4cec-B099-944E149DC713}
Maximum long term fuel valve opening rate iLtratei. Typical value 002.
ltrate
{63E96E0F-CB6D-4751-8A0B-E8FA22DE56E8}
Maximum fuel valve opening rate iRmaxi. Unit PU s. Typical value 1.
rmax
{1B70A83E-B1A6-4655-B605-56C76F224921}
Valve positioner iAi.
a
{DBC6215C-807D-4448-960E-AB70C2E9DE6F}
Valve positioner iBi.
b
{54D6EFA9-E20A-47e3-A9D1-7ACBB2C87C94}
Valve positioner iCi.
c
{88EFB7C5-48FC-4404-8AAA-6502D736DFEE}
Governor mode iZi.1 droop0 isochronous.
z
{F7F03573-6CBF-4934-AC1C-54DA8CE00587}
Acceleration limit setpoint iBcai. Unit 1s. Typical value 001.
bca
{B3E6B32D-9443-4f94-B541-CAE1EA41296A}
Fuel system feedback iKiisubACsubi. Typical value 0.
kac
{24F8C5F9-6D46-4f68-B52F-7FC4C5B92D06}
Acceleration control integral gain iKcai. Unit 1s. Typical value 100.
kca
{2B4CB294-3052-43eb-A8BB-025B2114C42A}
Gain of radiation shield iKsii. Typical value 08.
ksi
{F3A38C97-B132-4192-A8EA-35C7B1D717EC}
Coefficient of transfer function of fuel valve positioner iKyi. Typical value 1.
ky
{8E14F5CB-7D84-4b69-B4F0-4A4B250EC553}
Valve positioner iAi.
a
{E9B2E67F-148B-45f5-A20F-290EAC2978B6}
Valve positioner iBi.
b
{E1B8747C-D70F-4508-8F4B-E1DF1E2C7281}
Valve positioner iCi.
c
{96C07468-DA80-4933-A3E9-A775511108A5}
Maximum gate velocity iVlemi gt 0. Typical value 02.
velm
{DE782CB5-7653-4c66-A929-C9019477CF51}
Maximum gate closing velocity iUci lt 0. Unit PU s. Typical value 01.
uc
{C616225F-12E9-47d2-B938-09291EB15658}
Maximum gate opening velocity iUoi. Unit PU s. Typical value 01.
uo
{B16FFD3B-ED67-4351-A07F-1EAD0985F168}
Governor control flag iCflagi.true PID control is activefalse double derivative control is active.Typical value true.
governorControl
{23B04075-EE03-4759-AC44-A5B6F96E177A}
Maximum gate closing velocity iVelcli. Unit PU s. Typical value 02.
velcl
{EDB42260-2AFB-498f-B0D9-2FD449839F3D}
Maximum gate opening velocity iVelopi. Unit PU s. Typical value 02.
velop
{5542A86A-E2FE-410e-B01A-CE4805A7EAD8}
Maximum blade adjustment factor iBmaxi 0 for simple 0 for FrancisPelton. Typical value for Kaplan 11276.
bmax
{BE809A7F-1B77-40be-B908-230D1288AD6E}
Max gate closing velocity iUci. Typical value 02.
uc
{2F511A10-938D-4c28-BD41-6A175D8D353C}
Max gate opening velocity iUoi. Typical value 02.
uo
{ED6AEE7C-0928-4df9-86D1-0BBB70F8EBE1}
Input signal switch iFlagi. true iPei input is usedfalse feedback is received from iCVi.iFlagi is normally dependent on iTti. If iTti is zero iFlagi is set to false. If iTti is not zero iFlagi is set to true. Typical value true.
inputSignal
{84EF753B-18AE-4768-B2F2-944C15ACF1D4}
Maximum gate closing velocity iVelcli. Unit PU s. Typical value 014.
velcl
{8DC31A74-2994-4696-8C23-85607752AF54}
Maximum gate opening velocity iVelopi. Unit PU s. Typical value 009.
velop
{A251DF5C-DB9A-47e5-8224-DFFB430A4ACF}
Maximum gate opening velocity iVai. Unit PU s. Typical value 006.
va
{8E8B42A3-F36E-4033-BCD0-25FD73EA7E4D}
Maximum gate closing velocity iVci. Unit PU s. Typical value 006.
vc
{C6F820A3-5A3B-4b57-9F16-6D270EFD9075}
Water tunnel and surge chamber simulation iTflagi.true enable of water tunnel and surge chamber simulationfalse inhibit of water tunnel and surge chamber simulation.Typical value false.
waterTunnelSurgeChamberSimulation
{6AD46094-5EBE-414c-96BC-971D89B26E73}
Maximum gate closing velocity iUci lt0. Typical value 01.
uc
{26862ED2-6564-4d4c-8794-672739DE0392}
Maximum gate opening velocity iUoi. Unit PU s. Typical value 01.
uo
{70A05529-828D-4681-9705-8AFC36908C9F}
Input signal switch iFlagi. true iPei input is usedfalse feedback is received from iCVi.iFlagi is normally dependent on iTti. If iTt iis zero iFlagi is set to false. If iTti is not zero iFlagi is set to true. Typical value true.
inputSignal
{5AE17F32-8F81-4822-BBDC-5F45412566B7}
Maximum gate closing velocity iVelcli. Unit PU s. Typical value 014.
velcl
{9D53A441-55A1-4806-A44B-A839A5721E2F}
Maximum gate opening velocity iVelopi. Unit PU s. Typical value 009.
velop
{EE997207-A1BD-4914-BDBA-8F95023051C6}
Feedback signal type flag iFlagi.true use gate position feedback signalfalse use Pe.
feedbackSignal
{41E39C0C-EEB8-4203-B7C2-40BC9A8CD8F4}
Reset gain iKii. Unit PUs. Typical value 0.
ki
{F22CA9F8-7D61-4bee-BC68-D3835435D1B9}
Maximum gate opening velocity iVelmaxi lt GovHydroPID2.velmin. Unit PU s. Typical value 0.
velmax
{D95288EB-2146-4052-A86E-8160C4F701EB}
Maximum gate closing velocity iVelmini gt GovHydroPID2.velmax. Unit PU s. Typical value 0.
velmin
{1284640F-7608-447b-BA32-5E66033AA822}
Simplified Pelton model simulation iSflagi.true enable of simplified Pelton model simulationfalse enable of complete Pelton model simulation nonlinear gain.Typical value true.
simplifiedPelton
{B7D78B57-709E-4b07-8398-E2AE570EC996}
Static compensating characteristic iCflagi. It should be true if simplifiedPelton false.true enable of static compensating characteristic false inhibit of static compensating characteristic.Typical value false.
staticCompensating
{B8704167-B5F7-4c5f-8499-3BDC556EDC93}
Maximum gate opening velocity iVai. Unit PU s. Typical value 006.
va
{78BE03AB-2862-4f50-8D74-6CF9B251D4D1}
Maximum gate closing velocity iVci. Unit PU s. Typical value 006.
vc
{47822E94-14FA-4526-8188-230BFC165A5B}
Water tunnel and surge chamber simulation iTflagi.true enable of water tunnel and surge chamber simulationfalse inhibit of water tunnel and surge chamber simulation.Typical value false.
waterTunnelSurgeChamberSimulation
{AF5B673E-82D7-4268-9087-6909A72307A0}
Input signal switch iFlagi.true iPei input is usedfalse feedback is received from iCVi.iFlagi is normally dependent on iTti. If iTt iis zero iFlagi is set to false. If iTti is not zero iFlagi is set to true. Typical value true.
inputSignal
{F4312C37-EAFA-45e0-9D3E-8F64425214E9}
Maximum gate closing velocity iVelcli. Unit PU s. Typical value 02.
velcl
{F59B8D7E-0EA9-488d-9F26-AE1D97AD5BC4}
Maximum gate opening velocity iVelopi. Unit PU s. Typical value 02.
velop
{DF4D6038-DE4A-403e-B7AC-70E46154F9B3}
Feedback signal selection iSwi.true PID output if iRPermGate i droop and iRPermPe i 0false electrical power if iRPermGate i 0 and iRPermPe i droop orfalse gate position if RiPermGate i droop and iRPermPe i 0.Typical value false.
feedbackSignal
{45D2E866-1186-4fb8-BF62-1585CD9BC0D4}
Permanent droop for governor output feedback iRPermGatei.
rpg
{11CBC264-5B9B-4599-A392-A773EEAF7D4A}
Permanent droop for electrical power feedback iRPermPei.
rpp
{C0DD6E76-9A4E-457e-9706-E99B8A5082C5}
Fraction of HP shaft power after first boiler pass iK1i. Typical value 02.
k1
{7ED4BFDC-8F10-4e4f-A768-CCA8E3753436}
Fraction of LP shaft power after first boiler pass iK2i. Typical value 0.
k2
{9DF83AD1-E200-4aa8-BF02-AD1EAAAC6236}
Fraction of HP shaft power after second boiler pass iK3i. Typical value 03.
k3
{A1E70CF0-8353-4c85-A3D4-F82DE2F12277}
Fraction of LP shaft power after second boiler pass iK4i. Typical value 0.
k4
{38A9D6DC-7C4D-4ffe-A311-2C65038B5B01}
Fraction of HP shaft power after third boiler pass iK5i. Typical value 05.
k5
{95468D3F-CBC7-42cc-B868-BEF15C392002}
Fraction of LP shaft power after third boiler pass iK6i. Typical value 0.
k6
{B523EDAD-56A3-40ce-88CF-C45ECF58D405}
Fraction of HP shaft power after fourth boiler pass iK7i. Typical value 0.
k7
{FB5B049C-0DFA-4109-943F-4976AF2064B4}
Fraction of LP shaft power after fourth boiler pass iK8i. Typical value 0.
k8
{BFA4E602-372D-4e58-BE79-9B13A674339D}
Intentional deadband indicator.true intentional deadband is appliedfalse intentional deadband is not applied.Typical value true.
sdb1
{A7B34ECC-72F8-4ccb-9B16-253E5760D64D}
Unintentional deadband location.true intentional deadband is applied before point Afalse intentional deadband is applied after point A.Typical value true.
sdb2
{550A9C48-19D3-4d38-9DEA-57E5558C9F38}
Maximum valve closing velocity iUci lt 0. Unit PU s. Typical value 10.
uc
{7BB46CBF-5834-469b-B5E8-BB03F6779E8E}
Maximum valve opening velocity iUoi gt 0. Unit PU s. Typical value 1.
uo
{2C8ABBF9-1054-4638-959B-C3EA5576430A}
Nonlinear valve characteristic.true nonlinear valve characteristic is usedfalse nonlinear valve characteristic is not used.Typical value true.
valve
{D01C182E-8057-4b88-ACA9-1635208668DB}
Governor gain reciprocal of droop iKi. Typical value 20.
k
{C03A97C6-5301-4113-A23F-65754161A639}
Electric power input selection Peflag. true electric power inputfalse feedback signal.Typical value false.
peflag
{EB307DE6-D498-45e4-A85A-7246C3BA0938}
Control valves rate closing limit iChci. Unit PU s. Typical value 33.
chc
{DEF590D4-75E3-45dc-869C-9D534C324C59}
Control valves rate opening limit iChoi. Unit PU s. Typical value 017.
cho
{2F6B20C0-095F-44ab-B486-E8EA79C896FB}
Maximum valve closing velocity iUci. Unit PU s. Typical value 1.
uc
{8A7D8783-C393-4b18-9C08-CD70CE5B7225}
Maximum valve opening velocity iUoi. Unit PU s. Typical value 01.
uo
{62FFF2FC-E43F-4c08-9042-3A63B4EF0636}
Maximum regulator gate closing velocity iSvmni. Typical value 00333.
svmn
{931BE282-21CA-40ec-8FA4-6AE8ACF31304}
Maximum regulator gate opening velocity iSvmxi. Typical value 00333.
svmx
{86D59C44-E403-42c7-B871-3F5DA29ED25C}
Fraction of HP shaft power after first boiler pass iK1i. Typical value 02.
k1
{A060B705-473C-4759-8722-F969343AE905}
Fraction of LP shaft power after first boiler pass iK2i. Typical value 0.
k2
{B0B3C600-89FE-49dd-8BE5-0329DB19BED2}
Fraction of HP shaft power after second boiler pass iK3i. Typical value 03.
k3
{C1E03DCC-834D-48ff-BF02-C4A6BD824048}
Fraction of LP shaft power after second boiler pass iK4i. Typical value 0.
k4
{A8101D28-E0EF-46ae-98F5-8971B0A67A9F}
Fraction of HP shaft power after third boiler pass iK5i. Typical value 05.
k5
{9C327305-9C97-4c50-8F82-4588422553FF}
Fraction of LP shaft power after third boiler pass iK6i. Typical value 0.
k6
{685AB351-306B-47f2-A371-2600CB4EB8EC}
Fraction of HP shaft power after fourth boiler pass iK7i. Typical value 0.
k7
{8CD0911F-2504-4fd2-8D74-ABC801E1D654}
Fraction of LP shaft power after fourth boiler pass iK8i. Typical value 0.
k8
{6B1B64DE-7290-41e6-9585-F82E0BF93C3E}
Maximum valve closing velocity iUci lt 0. Unit PU s. Typical value 10.
uc
{84320485-7039-4a2a-BCCC-AEC25896CF5B}
Maximum valve opening velocity iUoi gt 0. Unit PU s. Typical value 1.
uo
{9FE36435-360D-4cee-9774-BBBBAC457B3C}
input
{45EF945B-44C7-46e7-8EE1-8A6EB2EF4198}
output
{4FA08DCF-D7DC-4d76-9F7E-6D3373F63AEB}
sequence
{9C227FE9-4D64-4872-A897-33D950B968D7}
Type of this hazard.
type
{D614E68B-37A0-4459-8A19-317F9727F63F}
Flag is set to true when output is expressed in net active power.
isNetGrossP
{8BCB6AC1-048F-4c69-ACBE-DA212B529872}
value
{850F6606-EA94-47e5-8B66-D1FF8A0A4EFA}
Flag is set to true when output is expressed in net active power.
isNetGrossP
{27662118-95E1-44c3-93E7-76E793CB3DD7}
The steam supply rating in kilopounds per hour if dual pressure boiler.
steamSupplyRating2
{18166755-4BEE-4852-AC00-FB70A422C8F6}
The control areas frequency bias factor in MW0.1 Hz for automatic generation control AGC
frequencyBiasFactor
{F9138327-D4A1-4d5d-8994-FC32942062A3}
Flag defining that for this hour in the resource bid the resource shall have an hourly predispatch.
value
{4958C881-4C68-4f97-B98C-482B57F0F22D}
value
{42EFC868-753D-41ef-B4ED-C116231492E3}
The hurricanes category during the time interval using SaffirSimpson Hurricane Wind Scale a 1 to 5 rating based on a hurricanes sustained wind speed.
category
{C67D6897-B00D-4e7f-8CD6-BE602E0C79F1}
Type and configuration of hydro plant penstocks.
penstockType
{9FE6046A-C52A-40b1-B7B7-B3A5820CCE7D}
A code describing the type or absence of surge tank that is associated with the hydro power plant.
surgeTankCode
{5C9A5E8A-FBF5-428e-B3F1-60A2F8A0E8F4}
Gate rate limit.
gateRateLimit
{5AF1C0E3-9138-4929-8CB3-D173A308732F}
The Local Reference attribute specifies a value agreed upon between sender and receiver of the Information Message. It further identifies the Information Message.
localReference
{A2962A38-643E-4dc6-8012-24927484F35B}
Used to indicate if the Provider is responsible for initiating the TASE.2 connection. If the value is TRUE the provider is responsible for establishing the association. If the value is FALSE the peer provider of the Bilateral Table will need to establish the association.
calling
{F4CE1A53-F799-4391-91CD-F8C19396E808}
If True the value indicates that the entity represented by the bilateral table is capable of issuing requests and responding to request e.g. bidirectional support of ICCP requests.If False this indicates that a calling entity e.g. calling True will not be able to respond to ICCP requests. If False and callingFalse this indicates that the entity will only respond to ICCP requests and not issue ICCP requests.
clientAndServer
{570D1089-9BB0-4011-B47A-7D5C0E9B4949}
Specifies the fastest update interval that can be provided for integrity information and Transfer Set creation. The value is in seconds.
minimumUpdateInterval
{91145068-4973-4b2d-AE1F-8F5C348D9A31}
Specifies the ICC scope name that the remote can use to access the information in the Bilateral Table if the information is not VCC scoped. This value may not be null.
nameOfLocalICC
{B42B35C8-D080-4ef0-9B2A-053AF8117B35}
Per IEC 608706702 If true indicates support for basic services. Must always be true.
supportForBlock1
{4328CCAD-0A37-4216-A47B-E5C8AC1BA630}
Per IEC 608706702 If true indicates support for extended conditions.
supportForBlock2
{126521CA-0970-404a-8284-77C77058CCAD}
Per IEC 608706702 If true indicates support for blocked transfers.
supportForBlock3
{309E572B-4263-4007-BC03-1768B7E7C6B0}
Per IEC 608706702 If true indicates support for information messages.
supportForBlock4
{577F16A1-A20D-4b49-808C-D7ABB8330DE9}
Per IEC 608706702 If true indicates support for device control.
supportForBlock5
{9D232F12-EB25-4348-A274-14E06E2DE03F}
Per IEC 608706702 If true indicates support for accounts. The use of this block was deprecated in Edition 3.
supportForDepriciatedBlock8
{0C33DBCA-53F5-4a87-83AC-FD164CD45BD1}
If true then transport level security as specified by IEC 623516 is required.
transportSecurityRequirement
{515BDDFD-3CA7-4b93-AF9F-6950FFEBB9A8}
const20161031 Form is YYYYMMDD for example for January 5 2009 it is 20090105.
date
{353BDA8B-E1C1-4e55-BE22-8BF6A658E355}
constIEC61968CIM13v09 Form is IEC61968CIMXXvYY where XX is the major CIM package version and the YY is the minor version. For example IEC61968CIM10v17.
version
{4FE5B579-CDEC-42c6-87FE-65797A3E9E03}
Form is YYYYMMDD for example for January 5 2009 it is 20090105.
date
{8DADB97F-283D-40c7-A25A-D75E4C0D8507}
Form is IEC61970CIMXXvYY where XX is the major CIM package version and the YY is the minor version. For example IEC61970CIM13v18.
version
{B4E0B1B6-8794-406a-A4C6-CBB395E37A52}
Form is YYYYMMDD for example for January 5 2009 it is 20090105.
date
{A832713E-4991-478c-A9F3-950E5D26380C}
Form is IEC62325CIMXXvYY where XX is the major CIM package version and the YY is the minor version. For example IEC62325CIM10v03.
version
{324CBD5B-D3C6-4c9d-94DD-3E78DDB5DDDA}
Is the dotted decimal IP Address resolve the IP address. The format is controlled by the value of the addressType.
address
{3797024E-6F8F-4970-835B-5AA4EF50678E}
Is the dotted decimal IPAddress of the first hop router. Format is controlled by the addressType.
gateway
{285AB90D-ED6D-45b3-B5E6-57240966F56F}
This is the IP subnet mask which controls the local vs nonlocal routing.
subnet
{7081E6FF-D824-4f51-B9FC-CA3102C2EB7D}
Is part of the Application Entity addressing as specified by ISO Addressing.
aeInvoke
{45125E3E-D2B8-455d-9355-E74DB6923601}
Is the AE qualifier and represents further application level addressing information.
aeQual
{0270C184-02E5-424b-A75C-B5D31A9FDE3E}
Is a further application level OSI addressing parameter.
apInvoke
{BF45760D-20B5-4f8b-8235-F2D820EE5B81}
Is a sequence of integer strings separated by .. The value in conjunction with other application addressing attributes e.g. other APs are used to select a specific application e.g. the ICCP application entity per the OSI reference model. The sequence and its values represent a namespace whose values are governed by ISOIEC 74983.
apTitle
{7E7E4F69-3FA8-43be-8616-47490338F236}
Is the addressing selector for OSI presentation addressing.
osiPsel
{14C1B232-15B4-4d3c-87CA-338FB7CACF8A}
Is the OSI session layer addressing information.
osiSsel
{63DAE666-97E7-4397-BFEB-8E51A1BD956A}
Is the OSI Transport Layer addressing information.
osiTsel
{97BA7C1A-D88B-436a-88C6-251FBDDBEC8A}
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
aliasName
{D4F8B75D-CDAD-4440-8092-1425101E5ABC}
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
description
{13104BE9-CB1E-4dde-9A52-D7EE95DF7B65}
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID as specified in RFC 4122 for the mRID. The use of UUID is strongly recommended.For CIMXML data files in RDF syntax conforming to IEC 61970552 the mRID is mapped to rdfID or rdfabout attributes that identify CIM object elements.
mRID
{C775F80A-A23D-4f38-AB9D-49D1FA882337}
The name is any free human readable and possibly non unique text naming the object.
name
{870F033B-EDA6-4a32-A5AD-47DCBBFE2997}
value
{6C71F109-A754-41ed-88E0-B9DA18EAF543}
Date asset was most recently put in use.
inUseDate
{D327CF70-AF93-4e42-A189-E3BA4E75A296}
Date of most recent asset transition to not ready for use state.
notReadyForUseDate
{E4F9187C-A1AD-4454-AED9-08AD9D09780B}
Date of most recent asset transition to ready for use state.
readyForUseDate
{47F58F13-B8BC-4c05-8E37-C571EF36AD07}
Cause of this incident.
cause
{D9CF34B1-42FB-4ecd-82C0-C3E1215408E9}
Flag is set to true when output is expressed in net active power.
isNetGrossP
{6658D33F-5901-4068-B659-F851F517ECEE}
value
{83AE2102-F0CF-4ab8-BBB6-03E5262DCC86}
value
{165B20CD-D566-4ac4-83F9-2989DE99DEFA}
Answer to question.
answer
{FE348524-99F6-4474-9E30-BABBFA11AE53}
The date and time the quesiton was answered.
answerDateTime
{9B797A64-7291-496e-A711-ACD22E1A90A8}
Remarks to qualify the answer.
answerRemark
{8191AB2B-7DE1-4b7a-A685-BEF3E8232062}
The question code. If blank refer to questionText.
questionCode
{26212987-0976-4ce1-B780-0CAE0DD29B88}
Remarks to qualify the question in this situation.
questionRemark
{A7B4B038-382E-4290-9BAE-5C388ED2F458}
For noncoded questions the question is provided here.
questionText
{00576FB3-D1F0-4c51-AB5A-18B6EF4E6CCC}
The type of the question.
questionType
{88C3EDC6-0737-4b4d-9835-E980D6501AFD}
Description of the conditions of the location where the asset resides.
locationCondition
{B3236466-AC6B-4534-8403-BBB1462D89EE}
Binding dispatch operating delta provides a relative delta to be applied. Typically used in demand response instructions. The bindingfont color0f0f0fDOD instructions are cumulative in other words a second DOD instruction does not replace the previous DOD instead the second DOD adds to the previous DODs.font
bindingDOD
{3AB5BB18-5183-45d4-BF5F-241E98B4EF37}
bindingDOT
{2E51D0DF-8686-4a85-BBD4-1418C326C160}
Total cost associated with changing the status of the resource.
instructionCost
{67446729-30BA-4692-8A0E-7D87C31B8C3D}
Time the resource should be at Pmin for start ups.Time the resource is off line.
instructionStartTime
{605A5BE0-8122-4f62-8ED9-BD85AFCEABA9}
Minimum start up time required to bring the unit online minutes.SCUC commitment period startup time. Calculated start up time based on the StartUpTimeCurve provided with the Bid.This is a combination of StartUp time bid and Unit down time. Units is minutes
minStatusChangeTime
{2DD8AD83-AE4F-4179-B4D9-56720958F4A5}
updateTimeStamp
{075653C8-07C1-4d10-895C-EC4986611FAC}
updateUser
{E72345ED-0308-41bf-AFF3-408D6934896C}
The default method by which interchange schedules are to be integrated to obtain hourly MWh schedules for accounting. Method 1 is to integrate the instantaneous schedule between the hourly boundaries. Method 2 compensates for any updown ramping that occurs across the hourly boundary this is called block accounting.
defaultIntegrationMethod
{CC6D1262-0B43-480a-9087-4DE8AB5BC36D}
Value of this quantity.
value
{9ECF56CF-5869-4003-A850-3C3787F6EBE1}
The minimum hourly block for an InterTie Resource supplied within the bid.
minHourlyBlock
{9BB13447-77B1-47a3-8BBB-EE2897D8F6F0}
The accepted mw amount by the responder. aka response mw.
acceptMW
{8E3039DF-A092-4726-99FA-A244F1705A07}
MW amount associated with instruction. For 5 minute binding dispatches this is the Goto MW or DOT
clearedMW
{A64B5344-FA77-46a1-824F-B90729BFFECA}
Part of the Composite key that downstream app uses to match the instruction
startTime
{A3D44154-1EC5-42e7-9E9E-63196451FB66}
Net Actual MW Flow
baseMW
{D2959287-9D99-4945-B626-3274BD9C231D}
Net Dispatched MW
clearedValue
{3B6DEFDA-0D3B-435b-B7AD-48AA876E7E14}
Existing transmission contract number
contractNumber
{8813C172-1C8D-453d-8B7F-45B450343A00}
Existing transmission contract usage MW value
usageMW
{7502733E-5CB2-4372-9925-739821215502}
Interval length.
intervalLength
{2536EA51-AAFD-4901-A2D7-4B782F0808E1}
Operating date hour.
operatingDate
{D9EC6FFA-D2A4-47a7-BCA5-B5FAABE58C78}
To indicate an outofmarket OOM schedule.
outOfMarketType
{866CCB87-449D-4004-87AE-CD21EDE940C3}
Wheeling CounterResource ID required when Schedule TypeWheel.
wcrID
{0AA198B8-F5F0-463d-BAB1-6BDE904EE4F6}
Indicates whether a resource is eligible for PIRP program for a given hour
eligibilityStatus
{21CE1352-7DFA-47a9-854A-B547BDF1A2B2}
Name of building where location is.
buildingName
{EBC7D706-D38B-4ddc-95A3-ACA29F530142}
Number of building where location is.
buildingNumber
{BA96D88C-B729-4609-9168-ED4B4BE39C34}
Floor of location.
floor
{00BA84BE-DA16-4867-B0F3-61958AECCA7A}
Room number of location.
roomNumber
{764EC990-0E59-4475-8D97-41358E8E65DC}
The first value at the time. The meaning of the value is defined by the derived type of the associated schedule.
value1
{9D8B5A55-35E1-40b2-ADE8-4DF725D136CC}
The second value at the time. The meaning of the value is defined by the derived type of the associated schedule.
value2
{5577A9F6-8B29-43dd-9885-64909F799BEE}
The type of insulation around the joint classified according to the utilitys asset management standards and practices.
insulation
{0B0DED74-3F20-41f7-8778-9097C59CF268}
value
{5B27F433-ED87-49d6-81BB-ECFEA60B9979}
Conclusion drawn from test results.
conclusion
{5B0BDE26-6A56-46eb-85F5-D815D2BA7AFB}
Description of confidence in conclusion.
conclusionConfidence
{CD575F21-6875-48fe-97CB-0CF30E48E370}
Identity of lab equipment used to perform test.
testEquipmentID
{87810D30-C5B2-4f09-8C90-B99E2ABB4C66}
Activity code identifies a specific and distinguishable unit of work.
activityCode
{5F50A5A9-4B07-4e4a-ACA3-4EE97920081E}
Reference allocated by the governing organisation such as municipality to this piece of land that has a formal reference to Surveyor Generals records. The governing organisation is specified in associated Organisation.
externalRecordReference
{6C3D6DE5-C0AE-41d1-B19B-BA09389A098F}
value
{C594A615-29EA-4d24-8984-B8844EE042B2}
Date current installation was completed which may not be the same as the inservice date. Asset may have been installed at other locations previously. Ignored if asset is 1 not currently installed e.g. stored in a depot or 2 not intended to be installed e.g. vehicle tool.
installationDate
{569B7CC2-79C1-422c-B4C3-6551377163D0}
Date the asset was manufactured.
manufacturedDate
{4C5A0697-6497-44c6-B167-21833EA42DCD}
Date the asset was purchased. Note that even though an asset may have been purchased it may not have been received into inventory at the time of purchase.
purchaseDate
{DAFA856B-5B25-408f-A57C-E2B5B3676D49}
Date the asset was received and first placed into inventory.
receivedDate
{A5EC1B77-3011-45cb-AF41-30C1C33ECC64}
Date when the asset was last removed from service. Ignored if 1 not intended to be in service or 2 currently in service.
removalDate
{73ADF6AC-F535-4131-A7F1-8F28B1CB8BF3}
Date the asset is permanently retired from service and may be scheduled for disposal. Ignored if asset is 1 currently in service or 2 permanently removed from service.
retiredDate
{86EFDA3A-F38C-4fa6-8F1E-8BA6D002730B}
The polarity of the strike with T meaning negative. About 90 of all lightning strokes are negative strokes meaning that they were initiated by a large concentration of negative charge in the cloudbase this tends to induce an area of positive charge on the ground.
negativePolarity
{750A6414-900E-4457-9818-8BDFE53A671F}
Tells if the limit values are in percentage of normalValue or the specified Unit for Measurements and Controls.
isPercentageLimits
{47BA45BD-55DC-4051-9C7F-BAAF73825DB3}
Date and time when this line was created in the application process.
dateTime
{B5193FB2-406B-43fc-9A24-90A84FB8C7C9}
Free format note relevant to this line.
note
{0D4BF5CB-FDCC-4204-BFE8-939EDCD08EAF}
load reduction initiation time
loadRedInitiationTime
{44DF6703-0B98-45be-A442-89150C27BDC2}
The date represents the NextMarketDate for which the load response bids apply to.
marketDate
{ED808F87-0F39-4810-83CC-AEAF62A9A1CC}
Flag indicated that the load reduction is metered. See aboveIf priceSetting and meteredValue both equal 1 then the facility is eligible to set LMP in the real time market.
meteredValue
{AE9763D2-72E8-4ece-9D3F-E13409CA2623}
Shortest period load reduction shall be maintained before load can be restored to normal levels.
minLoadReductionInterval
{79E7CD7E-0A40-4f6a-8105-16BE49D34B4C}
Shortest time that load shall be left at normal levels before a new load reduction.
minTimeBetLoadRed
{EBEC1A15-18D3-4cc9-ADDB-285D864FBC45}
Flag to indicate that the facility can set LMP Works in tandem with Metered Value. Greater chance of this being dynamic than the Metered Value however it is requested that Price Setting and Metered Value stay at the same source. Currently no customers have implemented the metering capability but if this option is implemented then Price Setting could become dynamic. However Metered Value will remain static.
priceSetting
{3A410659-A1FB-4737-874A-C4BB0BF2F974}
Time period that is required from an order to reduce a load to the time that it takes to get to the minimum load reduction.
reqNoticeTime
{E4C7252C-35AD-4ca9-AA76-8703572A9F2A}
Active loadfrequency dependence index dynamic iEpfdi. Typical value 15.
epfd
{F7B947C0-C3A0-45f7-9796-DF787FDF4153}
Active loadfrequency dependence index static iEpfsi. Typical value 15.
epfs
{8429D43B-EF51-432a-A02E-2A886600565D}
Active loadvoltage dependence index dynamic iEpvdi. Typical value 07.
epvd
{D0A50971-317E-43d8-BD56-92601F29B460}
Active loadvoltage dependence index static iEpvsi. Typical value 07.
epvs
{4990BD89-41F5-4423-A4A0-4E134AB1BD6E}
Reactive loadfrequency dependence index dynamic iEqfdi. Typical value 0.
eqfd
{D4C07CDA-B8E2-4b7f-9415-004DC64B7CC8}
Reactive loadfrequency dependence index static iEqfsi. Typical value 0.
eqfs
{23148A82-CAB9-4c08-8851-EB5BE690A005}
Reactive loadvoltage dependence index dynamic iEqvdi. Typical value 2.
eqvd
{099E8689-45D8-4b63-ACAA-FEBFA57DF54B}
Reactive loadvoltage dependence index static iEqvsi. Typical value 2.
eqvs
{94C533E5-0B86-4612-A4BB-D42DBC0B3AFD}
Loading factor iLiisubfacsubi. The ratio of initial iPi to motor MVA base. Typical value 08.
lfac
{4D80F496-63A7-4b13-B587-E9DF6A486523}
Fraction of constantpower load to be represented by this motor model iPiisubFRACsubi gt 00 and lt 10. Typical value 05.
pfrac
{2D8FAD05-749B-4f96-B2D2-4CE5BF50469D}
Real power MW load distribution factor
pDistFactor
{4E402FD4-06EF-426b-9E4F-040F305571F4}
Reactive power MVAr load distribution factor
qDistFactor
{FEE98F42-6694-4caa-9E09-46589EBDB0C1}
Instruction End Time
endTime
{1DEAC45A-BDCB-4218-A478-C0EB5FAB79EF}
Load Following MW Positive for followup and negative for followdown
loadFollowingMW
{FB0807D3-5970-4049-B9B9-63A6C32A8805}
Unique instruction id per instruction assigned by the SC and provided to ADS. ADS passes through.
mssInstructionID
{727926DE-DCB8-45d0-8EA7-1D5F81397861}
Instruction Start Time
startTime
{EAB6EB68-19F5-4829-B50F-4D949CC8AE77}
Time the data entry was performed
dataEntryTimeStamp
{7DD72623-EDA0-4d8f-B6D7-321F1D582C8E}
temporarily manually entered LFD capacity
tempLoadFollowingDownManualCap
{604BC411-AB8D-4586-889E-2D68B6F5841E}
temporarily manually entered LFU capacity.
tempLoadFollowingUpManualCap
{15C3EF08-CE3F-4e07-A2C0-D8A7CF7CBDF6}
updateTimeStamp
{CD6F520D-318A-47e2-B8B3-48A166DA6A05}
updateUser
{5BF75C1F-B679-4fd2-949D-96382466125A}
Steady state voltage index for reactive power iBSi.
bs
{38F9B935-2DA2-4f51-B985-6E8239F697EF}
Transient voltage index for reactive power iBTi.
bt
{C96066B4-E411-4037-9394-1055CAB38285}
Steady state voltage index for active power iLSi.
ls
{6F1D546B-2FD9-4f5b-9A29-A987724FECB5}
Transient voltage index for active power iLTi.
lt
{6E434EE1-6562-4740-98B5-2588E480C1C7}
Damping factor iDi. Unit delta iPidelta speed. Typical value 2.
d
{E924980F-8F48-4fbd-A0F0-F1D6AFD10A3D}
Loading factor iLfaci. The ratio of initial iPi to motor MVA base. Typical value 08.
lfac
{7B55D1AF-F5B6-4c9b-85AC-44A71019BDCD}
Fraction of constantpower load to be represented by this motor model iPfraci gt 00 and lt 10. Typical value 03.
pfrac
{1D8468A9-BB75-439b-9CDD-031979BEDDAD}
Interval End Time
intervalEndTime
{E8ADFD1D-9964-47f2-B1A4-8E363B48380F}
Interval Start Time
intervalStartTime
{7B8FB69D-0BA5-41f7-90AA-537A9F5E7BF6}
type of the curve Possible values are but not limited toMax Min
loadReductionTimeCurveType
{1487FFFA-AAF3-4c6c-BEEB-FCAAEB6EDCA1}
Indicates the exponential voltage dependency model is to be used. If false the coefficient model is to be used.The exponential voltage dependency model consist of the attributes pVoltageExponent qVoltageExponent pFrequencyExponent qFrequencyExponent.The coefficient model consist of the attributes pConstantImpedance pConstantCurrent pConstantPower qConstantImpedance qConstantCurrent qConstantPower.The sum of pConstantImpedance pConstantCurrent and pConstantPower shall equal 1.The sum of qConstantImpedance qConstantCurrent and qConstantPower shall equal 1.
exponentModel
{167B72F6-0FB5-4c24-AD5B-E7D5CEAAFB08}
Portion of active power load modelled as constant current.
pConstantCurrent
{8173030F-BA74-4d14-9EAF-5BB596D214B2}
Portion of active power load modelled as constant impedance.
pConstantImpedance
{2BA696F5-28B3-47b8-9C5A-312BDD6C4325}
Portion of active power load modelled as constant power.
pConstantPower
{8FBB39E5-76EE-4c10-8312-F7C95EAE8DFF}
Exponent of per unit frequency effecting active power.
pFrequencyExponent
{239AEC84-9D6C-48ae-B39A-E727E8011266}
Exponent of per unit voltage effecting real power.
pVoltageExponent
{0D189BB7-C047-44b2-897B-43C9F90554A4}
Portion of reactive power load modelled as constant current.
qConstantCurrent
{13BEED75-919E-4609-9FBC-560293500E7C}
Portion of reactive power load modelled as constant impedance.
qConstantImpedance
{7D1D30A6-9C72-42de-991C-EC9D1D5742B1}
Portion of reactive power load modelled as constant power.
qConstantPower
{DB0D438A-33C3-4390-B6AA-B32EBC7EE187}
Exponent of per unit frequency effecting reactive power.
qFrequencyExponent
{197ADE9E-E59C-444f-9761-15E420D25F3C}
Exponent of per unit voltage effecting reactive power.
qVoltageExponent
{E22F1B76-3348-468a-98F3-9D31182229EE}
First term voltage exponent for active power iEp1i. Used only when .staticLoadModelType exponential.
ep1
{73B18F54-8825-4761-A56E-32F4CD464919}
Second term voltage exponent for active power iEp2i. Used only when .staticLoadModelType exponential.
ep2
{23188E52-1D97-44c9-A401-6E9F96E2AFE5}
Third term voltage exponent for active power iEp3i. Used only when .staticLoadModelType exponential.
ep3
{123F8B72-CD85-4540-B740-66F8BEFAF909}
First term voltage exponent for reactive power iEq1i. Used only when .staticLoadModelType exponential.
eq1
{49E45725-736B-4a44-9ACA-B6679F6A6221}
Second term voltage exponent for reactive power iEq2i. Used only when .staticLoadModelType exponential.
eq2
{52436692-2C04-4383-A16C-22EDA77F0530}
Third term voltage exponent for reactive power iEq3i. Used only when .staticLoadModelType exponential.
eq3
{C81902D0-C3DE-48ac-8AD8-E8FA2D09857C}
First term voltage coefficient for active power iKiisubp1subi. Not used when .staticLoadModelType constantZ.
kp1
{B0997870-4CE1-4c52-8B8B-8A05325F3EF8}
Second term voltage coefficient for active power iKiisubp2subi. Not used when .staticLoadModelType constantZ.
kp2
{C5468FFC-CD8B-4e7f-8210-C93CF03DF0F2}
Third term voltage coefficient for active power iKiisubp3subi. Not used when .staticLoadModelType constantZ.
kp3
{9395A751-7826-4baf-8BB8-768E22CE36C8}
Frequency coefficient for active power iKiisubp4subi not 0 if .staticLoadModelType zIP2. Used only when .staticLoadModelType zIP2.
kp4
{4BD6EDD0-E320-49e0-B917-05BFA105B04C}
Frequency deviation coefficient for active power iKiisubpfsubi. Not used when .staticLoadModelType constantZ.
kpf
{974F0B03-584D-4eb6-A780-A32CABA4CCC6}
First term voltage coefficient for reactive power iKiisubq1subi. Not used when .staticLoadModelType constantZ.
kq1
{2CB965D6-070E-4acf-A8FA-3C1681EA10A8}
Second term voltage coefficient for reactive power iKiisubq2subi. Not used when .staticLoadModelType constantZ.
kq2
{3CBEC0C5-AB09-427f-955C-A40A04776E93}
Third term voltage coefficient for reactive power iKiisubq3subi. Not used when .staticLoadModelType constantZ.
kq3
{F183074D-6CF6-401b-828E-D61137B18790}
Frequency coefficient for reactive power iKiisubq4subi not 0 when .staticLoadModelType zIP2. Used only when .staticLoadModelType zIP2.
kq4
{17E983C0-DF7D-4b45-B0C7-FC8E4BB19902}
Frequency deviation coefficient for reactive power iKiisubqfsubi. Not used when .staticLoadModelType constantZ.
kqf
{2D2BCF88-86DD-49f3-9DA0-9819749FA6BA}
Behaviour is based on a proprietary model as opposed to a detailed model.true userdefined model is proprietary with behaviour mutually understood by sending and receiving applications and parameters passed as general attributesfalse userdefined model is explicitly defined in terms of control blocks and their input and output signals.
proprietary
{B8FC77A3-E9FD-41af-8CB8-029281C34232}
if applicable Direction that allows field crews to quickly find a given asset. For a given location such as a street address this is the relative direction in which to find the asset. For example a streetlight may be located at the NW northwest corner of the customers site or a usage point may be located on the second floor of an apartment building.
direction
{08837BC4-44DA-4af5-A8CA-D2158DB60CCB}
if applicable Reference to geographical information source often external to the utility.
geoInfoReference
{42D25DB2-D892-4511-8D66-5ADC0654C723}
Classification by utilitys corporate standards and practices relative to the location itself e.g. geographical functional accounting etc. not a given property that happens to exist at that location.
type
{55804064-3AA5-48ce-99BE-ECF43B41B5B0}
Property related information that describes the Grants land parcel. For example it may be a deed book number deed book page number and parcel number.
propertyData
{3BA672F3-86AB-4ed4-B5C2-433470DA443C}
lossMW
{728052D0-FCB5-4f4b-8B8B-626FBF0F3EBF}
Loss penalty factor.Defined as 1 1 Incremental Transmission Loss with the Incremental Transmission Loss expressed as a plus or minus value. The typical range of penalty factors is 09 to 11.
lossFactor
{F1B7C014-7A9C-4fa0-93EA-8BAC43B57BCA}
Interval Test StatusN not applicable
resourceStatus
{6895CBD1-8389-46c0-A844-942678CF96A8}
This is the default loss factor for the Metered SubSystem MSS zone. The actual losses are calculated during the RT market.
lossFactor
{53FC00D7-3D53-4e43-A46D-ED010B3CC736}
value
{E8A9ED0E-4D87-4afc-A1CB-3C23D7DDED5F}
Condition of asset just following maintenance procedure.
conditionAfter
{B3307F5D-715C-455b-A5AF-1FD7E6611009}
Description of the condition of the asset just prior to maintenance being performed.
conditionBefore
{92EC2BB3-EB9C-446a-BD14-BB0D622C1D53}
Code for the type of maintenance performed.
maintCode
{FC04C0ED-F5F4-405f-8DE7-4A98F48C26D6}
if applicable Name identifier or description of the block in which work is to occur.
block
{77B96DCC-5721-42ae-B49A-08A48556669E}
if applicable Name identifier or description of the lot in which work is to occur.
lot
{561DB6D9-CD00-40da-AE4B-3C804080B5B3}
The names of streets at the nearest intersection to work area.
nearestIntersection
{910A4B46-7E76-47b1-A080-EDD2D3872C36}
if applicable Name identifier or description of the subdivision in which work is to occur.
subdivision
{EC4D823B-C339-4deb-ADC3-F178E2F520D9}
effectiveDate
{E1E5967C-8BCA-40ae-BF34-1ABABC6A700A}
frequencyType
{1BE1D957-5AF6-4b0d-ACBD-FADF5B0F0BC8}
invoiceType
{6967ABC2-C756-4094-BA48-E58D2AFB26FE}
requireAutorun
{2EE8DCD0-9C42-4b28-B77B-FECF821BB17A}
Revision number for the major charge group
revisionNumber
{BAF4FAD2-1760-441e-AF96-7EC3BDC95814}
runType
{D62A757F-1D92-4f6c-A194-7D19226899A3}
runVersion
{B6BCBCA1-DA35-4b46-BF75-7DD4E50D77DA}
terminationDate
{D4FAE52A-CD79-469a-86D7-B607DAD0C0BF}
Market ending time actual market end
actualEnd
{5E69C5D3-9B77-440e-BC5B-03248540EFEF}
Market starting time actual market start
actualStart
{DE6A61B9-9E34-4acc-86E1-54634576C1C9}
True if daylight savings time DST is in effect.
dst
{3462AFA4-12A0-4713-9BAD-6149AEB3433A}
Market end time.
end
{B30ABEA5-4045-4217-A804-D2B53BD7D85E}
Local time zone.
localTimeZone
{D1088F71-0BDD-41f9-ADD0-222D3824A932}
Market start time.
start
{1D932894-E217-4d3f-8122-41EEA157D324}
Market Status OPEN CLOSED CLEARED BLOCKED
status
{FCFC14B3-2619-440e-B2DE-7B6B25D9D19A}
Trading time interval length.
timeIntervalLength
{229C9B4E-8A30-4b95-8533-719D42806F0C}
Market trading date
tradingDay
{168F6324-8FA5-40a4-8F74-5736BA86BE71}
Trading period that describes the market possibilities could be for an Energy MarketDayHourFor a CRR MarketYearMonthSeason
tradingPeriod
{F939EABE-2AB9-42cc-8FE2-8C5082A6F698}
Free format comments for the event for any purpose needed.
eventComments
{7C23371D-ECA0-43f1-B5B9-2719C6D853F4}
End time of the event.
eventEndTime
{AACC9B84-5395-40d2-AADE-C9A14FA9B366}
Start time of the event.
eventStartTime
{252EBB54-4830-4fa2-8914-E132CC882EDE}
Actual event type.
eventType
{131C3E2A-F3F7-48bf-8649-EDFB4E14653D}
Settlement periodDA BidinDA ReliabilityDA Amp1DA Amp2RT ExAnteRT ExPostRT Amp1RT Amp2
caseType
{43C85EDF-E36F-48af-B1A0-25916F39127E}
Last time and date clearing results were manually modified.
modifiedDate
{81DC6EB4-7448-46fb-8C65-117A54E825BA}
Bid clearing results posted time and date.
postedDate
{0391B073-3FAF-4f72-B258-B848F3776771}
The end of the time interval for which requirement is defined.
intervalEndTime
{4B41CD8F-9D59-49bc-9FB3-7A24007E872D}
The start of the time interval for which requirement is defined.
intervalStartTime
{E07A9E3B-3BC0-4638-9AA0-30E71AA02895}
Calculated date upon which the Invoice amount is due.
dueDate
{CDB725A4-15F8-4e96-A034-2643E5BF1D5F}
Date on which the customer billing statementinvoice was printedmailed.
mailedDate
{C887903F-0AEA-4775-9535-C3F683C0B50D}
True if payment is to be paid by a Customer to accept a particular ErpQuote with associated Design and have work initiated at which time an associated ErpInvoice should automatically be generated. EprPayment.subjectStatus satisfies terms specificed in the ErpQuote.
proForma
{0E523839-D815-4c8c-8645-FD50B511800A}
Number of an invoice to be reference by this invoice.
referenceNumber
{CA3010DE-8C4A-4ae7-A7F0-631000A394B0}
Date and time when the invoice is issued.
transactionDateTime
{0B15CFDB-BBC7-4f49-9DDB-3600604F1562}
Type of invoice transfer.
transferType
{7514BE8F-8225-4c93-9BAB-BC374CA108E1}
General Ledger account code shall be a valid combination.
glAccount
{E326FB4C-743B-42a6-9491-5BABA475213D}
Date and time line item will be posted to the General Ledger.
glDateTime
{3DD89411-A3D2-4ddd-A386-4F5BAC511919}
Amount due for this line item.
lineAmount
{C0B0FAAB-EF7C-46a0-90BF-FF32C761FF17}
Line item number on invoice statement.
lineNumber
{BB462B2E-8C6B-4265-9D30-EA52C5E47E6D}
Version number of the bill run.
lineVersion
{DB7E1220-E2D3-4dac-929F-5725D3427BFF}
Net line item charge amount.
netAmount
{E2179F12-4D81-4b32-818A-95ADCF9315E6}
Previous line item charge amount.
previousAmount
{C8DE6B1C-4FB8-425c-9F45-8172DD571D6F}
Account identifier for this entry.
accountID
{18499FF2-16DA-4401-8397-1DBB08CB66ED}
Date and time this entry was posted to the ledger.
postedDateTime
{D7312FA1-69F9-4ac6-952A-BF5DFDDC4D9D}
Date and time journal entry was recorded.
transactionDateTime
{4014604C-A551-4901-AA51-E11108BF5A07}
The coded condition or position of an object with regard to its standing.
status
{AD08B171-672D-4d8c-9A29-0F14BA1F3D32}
Category of this person relative to utility operations classified according to the utilitys corporate standards and practices. Examples include employee contractor agent not affiliated etc.This field is not used to indicate whether this person is a customer of the utility. Often an employee or contractor is also a customer. Customer information is gained with relationship to Organisation and CustomerData. In similar fashion this field does not indicate the various roles this person may fill as part of utility operations.
category
{7BCEE6E0-F6F7-4928-A356-A872C3F8A0F7}
Persons first name.
firstName
{31E8C736-2EC6-4217-A190-F63C60057364}
Unique identifier for person relative to its governing authority for example a federal tax identifier such as a Social Security number in the United States.
governmentID
{1436A65F-1030-4d31-BDC0-81FE8A0C7079}
Persons last family sir name.
lastName
{B3B5308E-447F-4445-B69A-BFBB4A0F3488}
Middle names or initials.
mName
{97B95DF8-6AEF-431a-81B1-8065D585A887}
A prefix or title for the persons name such as Miss Mister Doctor etc.
prefix
{1FA68757-F994-483f-8820-12E58DBDBFB1}
Special service needs for the person contact are described examples include life support etc.
specialNeed
{CAD05567-3E3F-4df5-905E-DFC4976F2075}
A suffix for the persons name such as II III etc.
suffix
{D11C1FA8-CCA3-4680-86F5-A8CE377B9D56}
The user name for the person required to log in.
userID
{A15386B0-9163-40fc-A686-E574F9044E47}
Planned market trading day.
tradingDay
{DDC70E68-8F3F-4f76-9A6B-B4C5339BE387}
Ramping time interval for the specific market product type specified by marketProductType attribute. For example if marketProductType EN from enumeration MarketProductType then the rampInterval is the ramping time interval for Energy.
rampInterval
{49419B5B-D158-451a-A8BD-9D4D00507DE8}
Effective date of the privilege terminate date of the privilege or effective date of the application for the organization
effectiveDate
{4DA620F2-C8AD-480e-94CE-42F37F6F1A8F}
This is the terminate date of the application for the organizationThe specific organization can no longer access the application as of the terminate date
expirationDate
{5875BA62-6112-4008-B4AE-ACA780836AF6}
Qualification identifier.
qualificationID
{033EC4B6-F2CC-4f6a-BD29-44EC9534A00D}
The status of the privilege. Shows the status of the users qualification. The current statuses are 1New 2Active 3Refused 4Terminated 5Withdrawnand it is subject to update.
status
{7FED54E8-547D-42db-8002-A270CC9CB456}
This is the name of the status of the qualification and is used to display the status of the users or organizations status.
statusType
{C00EADDA-1FC5-466e-B929-DBA8BD180EDD}
Cleared generation Value in MW. For AS this value is clearedMW AS Total. For AS clearedMW selfScheduleMW AS Procured
clearedMW
{24C7A0FA-0099-4a68-AB84-64EE9E2535C6}
Marginal Price MW for the commodity Energy Regulation Up Regulation Down Spinning Reserve or Nonspinning reserve based on the pricing run.
clearedPrice
{7E9DBD3E-3AF3-4125-A2DB-B0199A830C8B}
Dispatchable MW for Combustion units.
dispatchCtMW
{A344528E-383F-4d88-A07C-7D9358D4905E}
Dispatchable MW for Hydro units.
dispatchHydroMW
{A702307B-BFF0-422d-93D8-236ED6E880C0}
Dispatch rate in MWminutes.
dispatchRate
{25D395B3-4702-430e-B5A9-058CD17E44E2}
Dispatchable MW for Steam units.
dispatchSteamMW
{E1016103-42B0-4c9f-BF31-00A36F835F23}
Imbalance Energy Bias MW by Time Period 5 only
imbalanceEnergyBias
{6CC211E5-2A47-41c3-8251-824CC81CBF26}
Region requirement maximum limit
maxSufficiencyIndex
{30AED1ED-3238-4812-A1DC-5BF2554F5BBC}
Region requirement minimum limit
minSufficiencyIndex
{94BD8526-FC6C-4885-B9B1-C8A992135E96}
Region requirement maximum limit
reqMaxMW
{C8EF162F-1D48-4084-8EBE-BAB8EF680B16}
Region requirement minimum limit
reqMinMW
{839A065C-5B33-46b9-9E69-69083FF68309}
Aof AS selfScheduleMW AS SelfProvided
selfScheduleMW
{7E5D8D82-E6FE-427c-9C6F-D1319FDCACB6}
Total AS Cost i.e. payment over the time horizon
ancillarySvcCost
{1E276D77-8818-4fa8-AE97-AAEB28D68694}
Total Energy Cost over the time horizon
energyCost
{11393337-7C11-49f2-9495-2AEF77184896}
Total Minimum Load Cost over the time horizon
minimumLoadCost
{4DC46E2E-29BE-4b0e-A537-365E6622E197}
Total Startup Cost over the time horizon
startUpCost
{E42CCD79-C084-42c5-B08B-1653B04891ED}
Total Cost Energy AS cost by over the time horizon
totalCost
{6AE93F37-6546-451a-8C86-33F8068766D1}
The total RUC capacity cost for this interval
totalRucCost
{81E513DF-FF20-45d8-A4AB-4B4900406229}
The kind of market roles that can be played by parties for given domains within the electricity market. Types are flexible using dataType of string for freeentry of role types.
type
{C624FDB0-F4CE-4af4-8DA9-D43058F1A060}
Approved time for case. Identifies the time that the dispatcher approved a specific real time unit dispatch case
marketApprovalTime
{87818354-2F6C-4b3c-8737-6FC915C357BE}
Set to true when the plan is approved by authority and becomes the official plan for the day ahead market. Identifies the approved case for the market for the specified time interval.
marketApprovedStatus
{938FA2A6-4C8A-49e3-A6F7-23A86F263DF2}
The end time defined as the end of the market market end time.
marketEndTime
{B608D398-38F3-4ae6-BE72-E316CDE1A715}
The start time defined as the beginning of the market market start time.
marketStartTime
{9CB9CFB6-521F-4ad6-8874-F4DFBAEE0431}
This is the state of market run activity as reported by market systems to the market definition services.
reportedState
{110876DD-36F9-411e-8A82-AB4A698B49C6}
This is the state controlled by market defintion service.Possible values could be but not limited by Open Close.
runState
{5BA76CDA-BFAC-4df0-8773-899BB1BA8DFD}
Category of scheduled event.
category
{3F067C62-1AD8-433b-A62F-E682FC4E6B05}
Date and time the skill became effective.
effectiveDateTime
{40E49FFB-94D3-4393-A310-8B2D2077C257}
Level of skill for a Craft.
level
{6F157A53-C185-4fe4-BF59-E0B7CEC82F47}
The end of a bill period.
end
{302FE5A3-B3B3-4260-959D-B7D64CE3FAA8}
The version number of previous statement in the case of true up.
referenceNumber
{82ADA027-0F38-4aa2-BFB6-2AA7C01D7CED}
The start of a bill period.
start
{08140298-C4B7-4edd-892F-DDB042BA8855}
The date of which Settlement is run.
tradeDate
{5003BA23-3D99-4466-A24A-A42F9A0B2ECC}
The date of which this statement is issued.
transactionDate
{5FDBB629-85E6-417b-B2C1-E72AC476F597}
Current settlement amount.
currentAmount
{BDDF2867-9EC5-477e-8BFB-E2F9D59C6877}
Current ISO settlement amount.
currentISOAmount
{4F460E72-9F8F-49fc-A42B-FF9A98EC3BD0}
Current ISO settlement quantity.
currentISOQuantity
{68931B37-2D63-4617-A22B-5BBA420F4709}
Current settlement price.
currentPrice
{4ACFF648-1B93-4951-82F6-4E692DE41ACA}
Current settlement quantity subject to the UOM.
currentQuantity
{EC738BC7-F731-4bbd-9C5C-19B141C2DD9D}
The date of which the settlement is run.
intervalDate
{C6A2CCF9-67E5-4b69-90C1-3915D4CA189A}
The number of intervals.
intervalNumber
{2B5C2956-E730-494b-BCB6-692BCE493746}
Net settlement amount.
netAmount
{0D9D46C5-2F86-4c99-9CAC-443296C03E0A}
Net ISO settlement amount.
netISOAmount
{5207A915-2570-4bf7-9FBD-56084A46BD4D}
Net ISO settlement quantity.
netISOQuantity
{23350D3D-E34A-4c8e-9325-118A1BF98869}
Net settlement price.
netPrice
{28BBE022-060A-45d8-A295-54A39B134D04}
Net settlement quantity subject to the UOM.
netQuantity
{F19A6001-57E4-4943-B40D-0F2A76FCABD1}
Previous settlement amount.
previousAmount
{0B33E2A5-517A-4aa7-9270-858E28E25321}
Previous ISO settlement amount.
previousISOAmount
{789BC974-2D5C-42ba-B918-88EAAA6743FB}
Previous ISO settlement quantity.
previousISOQuantity
{48CE3DFC-3D35-4efb-91D0-BEC05E8A8017}
Previous settlement price.
previousPrice
{C39D279F-9250-4d48-ADAB-E796D1E86F49}
Previous settlement quantity subject to the UOM.
previousQuantity
{3327EB68-75A0-4766-B6A8-DF360B855E59}
The unit of measure for the quantity element of the line item.
quantityUOM
{8C9B3E5D-5D0F-4b2a-BD85-12C27C5F8BB4}
value
{2B34EA04-ECD7-45ae-A68A-43F2B5164237}
Specifies the type of measurement. For example this specifies if the measurement represents an indoor temperature outdoor temperature bus voltage line flow etc.When the measurementType is set to Specialization the type of Measurement is defined in more detail by the specialized class which inherits from Measurement.
measurementType
{A0E1519B-5C0C-40ba-8596-0A94D2FE4BAB}
If true use the absolute value for the calculation.
absoluteValue
{3BA7323C-2D42-4400-95BE-56B7D3F1A274}
Positive number that defines the order of the operant in the calculation. 0 default. The order is not relevant e.g. summation.
order
{3E9966B5-7592-4933-A194-6736927F9CAE}
The time when the value was last updated.
timeStamp
{DB94617E-83D2-4cd4-A38F-64B0524D28DF}
Speed squared coefficient iai.
a
{0EA5ECA8-93B7-41a9-9A55-E9CDEC8C3335}
Speed coefficient ibi.
b
{71E0F9DB-3021-483f-A1FF-1DF3BB404200}
Speed to the exponent coefficient idi.
d
{BEE3D939-4A13-47f4-9A1B-0927DAAFCD3D}
Exponent iei.
e
{C84BE72A-27FF-428d-8E10-C34F58BF5291}
Behaviour is based on a proprietary model as opposed to a detailed model.true userdefined model is proprietary with behaviour mutually understood by sending and receiving applications and parameters passed as general attributesfalse userdefined model is explicitly defined in terms of control blocks and their input and output signals.
proprietary
{56223F2E-6860-4700-99BB-0305AAD03A60}
A code used to specify the connection category e.g. low voltage where the meter operates.
connectionCategory
{622874D1-2F3A-4826-99F7-A77EFAD997CD}
Meter form designation per ANSI C12.10 or other applicable standard. An alphanumeric designation denoting the circuit arrangement for which the meter is applicable and its specific terminal arrangement.
formNumber
{7F31FDC5-A964-4bd8-808F-F5FD797C0672}
Multiplier value.
value
{ABB08FC7-3402-4506-85A4-ED18B95832D7}
If true this meter reading is the meter reading for which other coincident meter readings are requested or provided.
isCoincidentTrigger
{DAB53223-CC2D-4d57-B0C3-02C4E285778B}
value
{1356BE21-6F87-4337-A03B-CC647C105BBD}
This drives the accounting treatment for this misc. item.
account
{E02A8A65-D385-4851-B440-3E92DE69F111}
The cost type for accounting such as material labor vehicle contractor equipment overhead.
costType
{43AF93E4-2C39-4642-A2E9-C0F60FB07CD0}
External reference identifier e.g. purchase order number serial number .
externalRefID
{BE90DAC9-DD62-4e5b-B470-AC8EBD69F540}
intervalStartTime
{FDC17CBA-1DE0-4932-AE99-75CF9C65A1BD}
Mitigated bid segment MW value
segmentMW
{5C57DAD8-1C0C-4a5e-91BF-A3B131A4658E}
Mitigated Bid Segment Number
segmentNumber
{B38A9950-E0E9-4b50-A80C-AA070D5EE47D}
thresholdType
{FEE5BD2A-0F32-446d-8935-D2787A06D062}
true if limit exceeded
exceededLimit
{0D3EF607-DF9A-4105-99B7-630A59D53FC4}
Rating set numbers
ratingSet
{60E291BE-E5FD-4bd3-9722-6E1F4CACC2EA}
load change flag Flag that indicates whether load rollover and load pickup should be processed for this contingency
loadRolloverFlag
{9A7D4774-1D64-4156-A4A0-0FFA5EAE1BB6}
ltc enable flag Flag that indicates if LTCs regulate voltage during the solution of the contingency
ltcControlFlag
{18416467-0816-44fd-A590-F7C1D3A1474D}
Participation Factor flag An indication which set of generator participation factors should be used to reallocate generation in this contingency
participationFactorSet
{F90FB99D-8C1A-49be-8302-4CEA475CFFEA}
sceening flag for outage Flag that indicated whether screening is bypassed for the contingency
screeningFlag
{60C3E6E1-DFA0-4386-B854-107B46AE2D97}
The coded type of a power system resource.
psrType
{8E95C8F7-1EFB-4522-8AD7-189D6F3BF99C}
Sequence number within a operation sequence lower is first. Normally starts with 1.
sequenceNumber
{FCE1226B-AD80-4464-9FF7-89C1FFD68D74}
The sequence number of the argument in an operation. Argument entries are considered in numerical order where the operation requires an ordering.
sequenceNumber
{83B9E792-F08C-4ee5-B00E-94FBA8273296}
The maximum multiplicity of the instance arguments that should be supplied for a single operation. Use 1 to indicate unlimited.
multiplicityMaximum
{C7915124-BD8D-469e-859A-A662FD28656B}
The minimum multiplicity of the instance arguments that should be supplied for a single operation. Use zero to indicate optional.
multiplicityMinimum
{73ECB561-CD30-479e-B6C3-00C9BDB82D88}
value
{FD1C5A68-05E0-448a-9515-88FB188D1A41}
End time of this interval.
end
{33539151-664A-4d98-95A1-991B84C84CF9}
Start time of this interval.
start
{87DA0F8E-0F49-4525-A5CC-52843D7C4420}
Any free text that name the object.
name
{A2162B14-022E-4cda-AC84-B9D32A0C6C00}
Description of the name type.
description
{B831899F-A8DB-470e-B41E-AE8F085A6225}
Name of the name type.
name
{EEC57734-55A8-4d7d-BCBB-44785732CBD8}
Description of the name type authority.
description
{90C20513-82B6-4090-89AE-2FE6E6F81954}
Name of the name type authority.
name
{3D2A9B24-AB04-454f-BD8E-01ECCEAE4103}
A user provided comment describing the changes in this version from the previous version.
comment
{D93C941F-9EAD-40bb-901E-645D477E89B6}
The datetime the change set is included in the model.
effectiveDateTime
{AE2C8158-C22D-49ab-852C-CF13BF73C3F1}
The datetime this version was finalized and thus made immutable.
timeStamp
{21DDF9F4-9D82-4353-A476-4B36BBA53017}
closed
{2F264EB1-7E6B-437c-86C9-A61E23D4ADDF}
created
{3CAEDC22-9EDC-45bd-911E-7640F075658D}
updated
{6C78A04A-879B-42d1-9F8B-72EF2A2DF4BB}
version
{A4691763-AA51-409c-ADC6-C2B7B8DFD94D}
changesetVersion
{FD18FAD7-404B-453e-ADF5-A64D64E9FF85}
commissionedDate
{2E5A9062-F9F9-43bd-B8F8-6D7D2805F2CE}
plannedCommissionedDate
{8E3B8F90-E8A5-4f88-86EA-E6AA2957201F}
The number of the section.
sectionNumber
{2B3AA796-1811-4a0b-BD0B-1D16B11F8912}
The number of the section.
sectionNumber
{3039EC90-899C-4381-9C73-A62F7CEF9854}
The average oil price at a defined fuel region.
oilPriceIndex
{36B36062-3CF2-4c20-9D33-20D565AEF352}
Classification by utilitys work management standards and practices.
type
{F8946D8D-3171-49ea-913D-3D1767888EA8}
Utilityspecific classification for this person according to the utilitys corporate standards and practices. Examples include employee contractor agent not affiliated etc.Note that this field is not used to indicate whether this person is a customer of the utility. Often an employee or contractor is also a customer. Customer information is gained with relationship to Organisation and CustomerData. In similar fashion this field does not indicate the various roles this person may fill as part of utility operations.
type
{071CC7DD-F6F9-4317-A122-8698E58225AA}
True if switch has load breaking capabiity. Unless specified false this is always assumed to be true for breakers and reclosers.
loadBreak
{E42360AB-9249-4102-98A5-90E11E09C893}
Number of poles i.e. of current carrying conductors that are switched.
poleCount
{8EAE3E37-CA67-465b-A35E-D7D27A7EDDFC}
True if device is capable of being operated by remote control.
remote
{5F56AAC8-C2A9-42cb-B01A-3C1FD4CCD075}
True if explosives have been or are planned to be used.
explosivesUsed
{E4B30714-6356-4429-8240-29CEEFE194C3}
True if work location has been marked for example for a dig area.
markedIndicator
{7F2BD3BC-5419-4bde-8729-CD9F58BFF915}
Instructions for marking a dig area if applicable.
markingInstruction
{7EA3F5C0-FA84-4af7-A55A-1FA9D80137C1}
Tap step number for the energised end of the test pair.
energisedEndStep
{5D7088AD-AC3B-4992-8C06-D2DF4A72753E}
Tap step number for the open end of the test pair.
openEndStep
{5FFDF198-9498-42b9-8210-1294F1D3C914}
value
{47172EC0-3F6B-4b0d-8139-FAA801CD58FB}
Defines if the operational limit type has infinite duration. If true the limit has infinite duration. If false the limit has definite duration which is defined by the attribute acceptableDuration.
isInfiniteDuration
{B23A3007-13C1-4330-983F-08B81F130AF9}
Type of operational updated rating e.g. a derate a rerate or a return to normal.
changeType
{6DE4EB71-00FF-41fc-919D-49BA3D755AD1}
Identifiers of the organisation held by another organisation such as a government agency federal state province city county financial institution Dun and Bradstreet etc.
clientID
{3A3EE3F2-0A0B-4ef3-980D-BEF5EBC84E8C}
a name to denote the community this could be a name or a code of some kind.
communityDescriptor
{8C38F9E5-6C87-4c4f-9880-51186D05090F}
number of customers that have been restored in the area.
customersRestored
{96EC7A1B-7F86-4742-A6DE-DAB1E3BA1ED2}
The updated number of meters affected by the outage as reported by the OMS within the utility. It is assumed this number will be updated repeatedly until the full outage is resolved.
metersAffected
{5793A622-95C4-41c3-B43A-075FBD01DCC4}
the total number of customers that are served in the area both outaged and not outaged.
originalCustomersServed
{81471418-91EA-4a7a-BF26-04C830755313}
The original number of meters that were affected as reported by the OMS within the utility. That is this is the total number of meters that were out at the beginning of the outage.
originalMetersAffected
{831EAA33-59E8-45c6-A7E0-AD1E0F65E806}
This contains an disclaimers the utility would like to place on the data provided to any stakeholder. This may be different for different stakeholders. This should possibly be an attribute under the Organization class but it is placed here for now.
utilityDisclaimer
{B8DD462E-CD50-45dd-B640-C2E9C0D7A292}
This is the reported time of the first outage report
earliestReportedTime
{12A02525-DF1B-499c-872E-47D57B49845E}
defines the number of meters served in the defined area.
metersServed
{BA8C464B-7AF0-4565-92FF-C4121EC8CC6B}
Freeform comment associated with the outage order
comment
{951491DA-3948-4521-B621-2FF848323433}
The date and time the outage plan was approved
approvedDateTime
{97729C42-A9A2-495e-9ED3-60F05F77EB55}
Date and Time the planned outage was canceled.
cancelledDateTime
{DEA72F1F-9BAF-48d7-B194-94075F7F99C1}
Purpose of this outage plan such as whether it is to replace equipment or perform maintenance or repairs or to reconfigure network topology.
purpose
{529D7F19-8F50-4a43-A14F-12D99A20C4E7}
OEL ramped limit rate iKiisubRAMPsubi. Unit PU s. Typical value 10.
kramp
{FB5970BD-9979-43d3-B60F-094FE6B44F87}
imi.true IFD limitingfalse EFD limiting.
m
{374FB821-28AC-4eef-B9C6-491FE7E5E856}
Behaviour is based on a proprietary model as opposed to a detailed model.true userdefined model is proprietary with behaviour mutually understood by sending and receiving applications and parameters passed as general attributesfalse userdefined model is explicitly defined in terms of control blocks and their input and output signals.
proprietary
{37E442B3-4EDC-4687-BA37-499BEC0D9B11}
Overhead code.
code
{D1AF82EF-D512-4926-B426-BC351D15F20B}
Behaviour is based on a proprietary model as opposed to a detailed model.true userdefined model is proprietary with behaviour mutually understood by sending and receiving applications and parameters passed as general attributesfalse userdefined model is explicitly defined in terms of control blocks and their input and output signals.
proprietary
{33D2A381-E3EB-4831-B4D7-C2B57B2FCD9A}
Behaviour is based on a proprietary model as opposed to a detailed model.true userdefined model is proprietary with behaviour mutually understood by sending and receiving applications and parameters passed as general attributesfalse userdefined model is explicitly defined in terms of control blocks and their input and output signals.
proprietary
{74ACE0E0-24AD-42bc-8B8F-02283355F675}
Overexcitation Flag iOVEXitrue overexcitedfalse underexcited.
ovex
{C06CD261-159D-4913-9750-5FB80F5283AF}
PF controller deadband iViisubPFCBWsubi. Typical value 005.
vpfcbw
{05BFA2E1-613F-4b7f-93B5-37E90009E587}
Var controller deadband iViisubVARCBWsubi. Typical value 002.
vvarcbw
{6996BD76-2761-4a50-BD8B-F71F46A56AA1}
Selector iJi.true control mode for reactive powerfalse control mode for power factor.
j
{1847D74E-8220-4456-AF87-04375CE3FC87}
Overexcitation or under excitation flag iEXLONitrue 1 not in the overexcitation or underexcitation state integral action is activefalse 0 in the overexcitation or underexcitation state so integral action is disabled to allow the limiter to play its role.
exlon
{BF1C0E34-219E-4a3e-B171-E0D30C9ED234}
Generator sensing voltage iViisubSsubi.
vs
{F4E5148F-7C59-4f6f-9454-9E43266808B5}
Overexcitation or under excitation flag iEXLONitrue 1 not in the overexcitation or underexcitation state integral action is activefalse 0 in the overexcitation or underexcitation state so integral action is disabled to allow the limiter to play its role.
exlon
{7BBD8676-15AE-4ce5-9EF7-4A90B6479CFC}
Generator sensing voltage iViisubSsubi.
vs
{8A63948E-CB60-4fc9-9C14-1F6F4AC38EDA}
value
{9E5F92B8-7F02-49bd-BC52-81240FB30E84}
Date of last change to the main package dependencies in format YYYYMMDD. This is updated when the version attribute is updated.
date
{020082B1-54FC-44dc-8ECA-9AFF7F0B882F}
The version of the main subpackages of the combined CIM model. The format is simply an integer. The version and date initial values should be updated any time the dependencies in the model change and require an actual change to the diagrams within this package.
version
{533F205D-A518-4746-807D-8C7D6BC58718}
Encoding of cancel control.
cancelControlMode
{53C0B772-C6B2-48da-82BF-FA2CEE179C97}
Timestamp when a canceling of the event is scheduled to start.
cancelDateTime
{73EB7715-9F21-4074-98DA-89ED1F2E1272}
If true a canceling of the event should start immediately.
cancelNow
{D44316CF-6D36-41b0-9420-653BFCE0764B}
Level of criticality for the action of this control. The action taken by load control devices for an event can be solely based on this value or in combination with other load control event fields supported by the device.
criticalityLevel
{C85BFB13-6B5E-43ff-8CC3-18AF2446AB1D}
Provides a mechanism to direct load control actions to groups of PAN devices. It can be used in conjunction with the PAN device types.
enrollmentGroup
{07E0C79E-A170-47d5-95E1-22BB2534FA33}
If true the requesting entity e.g. retail electric provider requires confirmation of the successful display of the text message.
confirmationRequired
{890832AF-EDE6-46dc-9F25-24D3C7CDFEA6}
Priority associated with the text message to be displayed.
priority
{56BD00B5-72C6-474e-8DB7-1F927917725A}
Text to be displayed by a PAN device.
textMessage
{8376A101-FA49-42bd-BF79-9DC66B1CF89C}
Unique identifier for the commodity provider.
providerID
{8CB87BDC-F600-4908-926F-9140B0A9C178}
Alternative measure of the cost of the energy consumed. An example might be the emissions of CO2 for each kWh of electricity consumed providing a measure of the environmental cost.
alternateCostDelivered
{9D4DB9F1-C034-44c6-89C9-79F8E35A7CC0}
Cost unit for the alternate cost delivered field. One example is kg of CO2 per unit of measure.
alternateCostUnit
{CB63AE4C-4C47-4204-8B0A-BA8DC72F0C12}
Current time as determined by a PAN device.
currentTimeDate
{1677916F-6193-4c1f-A208-5037F37C955A}
Ratio of generationPrice to the normal price chosen by the commodity provider.
generationPriceRatio
{FD0A8465-6939-4f4c-A8DE-8EFCDF4DEBA5}
Ratio of price to the normal price chosen by the commodity provider.
priceRatio
{8CC62802-7EBB-44eb-A70B-B1DFD02524BE}
Pricing tier as chosen by the commodity provider.
priceTier
{F4791193-717A-4821-939F-CFC00AA0E854}
Maximum number of price tiers available.
priceTierCount
{559203C2-BEAB-4d88-923F-230B11E3B950}
Label for price tier.
priceTierLabel
{F15298A0-41D1-4d82-B77E-BA38B62BC457}
Label of the current billing rate specified by commodity provider.
rateLabel
{384028DF-4158-404e-B6CD-F9AF42D4C597}
Register tier accumulating usage information.
registerTier
{4729FC25-48EF-48e5-A056-B4EE905219E3}
Defines commodity as well as its base unit of measure.
unitOfMeasure
{FBDAC539-8B49-4cd1-ADD4-666004F092DC}
Used to calculate participation of Pnode in an AggregatePnode. For example for regulation region this factor is 1 and total sum of all factors for a specific regulation region does not have to be 1. For pricing zone the total sum of all factors has to be 1.
factor
{E80A70B9-85CD-46a9-9FEB-75166CFA021D}
value
{EA0BFAA8-C6F6-4267-938E-9F60DD6BD30F}
Bill period end date
billEnd
{33129B09-36F9-4209-BA06-761C2906BF84}
The settlement run type for example prelim final and rerun.
billRunType
{7F7ED7F0-F6DD-4510-A60F-F21BB5532291}
Bill period start date
billStart
{5A6452BC-D3D1-4c8a-B3EC-9E2A0F8110CF}
The company to which the PTB transaction is billed.
billedTo
{11AF0C88-C01F-49f1-B235-4E4F30CF6DBC}
The effective date of the transaction
effectiveDate
{A5B03725-29E8-4602-99EF-5D6B017CDC61}
Disputed transaction indicator
isDisputed
{87FFEBCE-7D8A-43e9-B86A-9CAE1A7C9ED5}
A flag indicating whether there is a profile data associated with the PTB.
isProfiled
{0043A2F2-0C11-4dde-AAE2-4FBFE8FFCB11}
The company to which the PTB transaction is paid.
paidTo
{A2F93159-F7AE-49f5-B728-499D67E8D909}
The previous bill period end date
previousEnd
{93B19D45-DB6F-441d-8037-22AB6AA9DB2A}
The previous bill period start date
previousStart
{24584977-F3F7-4322-8337-DDE69F0B9863}
The product identifier for determining the charge type of the transaction.
productCode
{946D6460-AA13-4fd1-9C14-FB2C4F0136F0}
The company by which the PTB transaction service is provided.
providedBy
{BCA57DAF-B80D-43fe-9833-5B679A5924D0}
The end date of service provided if periodic.
serviceEnd
{5ACC3A68-0553-44ce-AEE1-F887DC3C1A6E}
The start date of service provided if periodic.
serviceStart
{A75B85E5-9173-4c00-9E35-1FDB45B8BEB0}
The company to which the PTB transaction is sold.
soldTo
{018309D3-D3E4-4b53-A1E5-1A59148FF7A8}
The time zone code
timeZone
{703AE722-EBA1-4181-A63A-2137BF1D86F3}
The trade date
tradeDate
{BED316C1-0279-45c5-9CD6-13885D681E47}
The date the transaction occurs.
transactionDate
{3373C7E9-541F-4d9e-B528-41659363E0BD}
The type of transaction. For example charge customer bill customer matching ARAP or bill determinant
transactionType
{74C3F782-FFCF-4b21-AF40-993488E13AA1}
Whether scalars should be applied before adding the offset.
multiplyBeforeAdd
{83C1E126-7DDD-4e2e-85AF-78085F9723B2}
if applicable Offset to be added as well as multiplication using scalars.
offset
{EA7A005C-CC97-4edd-8D97-74A85EC5886C}
if scalar is rational number When IntervalReading.value is multiplied by scalarNumerator and divided by this value it causes a unit of measure conversion to occur resulting in the ReadingType.unit.
scalarDenominator
{C1A0458B-7A3D-4f62-993F-38E046631ED5}
if scalar is floating number When multiplied with IntervalReading.value it causes a unit of measure conversion to occur according to the ReadingType.unit.
scalarFloat
{2EEB0DE4-0F59-4edb-B66B-FB396D661124}
if scalar is integer or rational number When the scalar is a simple integer and this attribute is presented alone and multiplied with IntervalReading.value it causes a unit of measure conversion to occur resulting in the ReadingType.unit. It is never used in conjunction with scalarFloat only with scalarDenominator.
scalarNumerator
{B46284FF-68CC-4b35-B805-E3951AC0FF64}
Normally 0 to 100 on a defined base.
value
{3F3F1095-2284-438d-89FF-699BCA187532}
Number of phase neutral and other wires retained. Constrains the number of matrix elements and the phase codes that can be used with this matrix.
conductorCount
{B1A3AD9B-B326-480a-AA6F-4905351CDB64}
The number of units of time that compose an individual step within a period.
resolution
{C59B0D48-250B-476c-8861-BAA72529975E}
Number of units of calculationIntervalUnit in the calculation interval.
calculationIntervalMagnitude
{8758B1AC-AAAC-4206-850C-762A4813E787}
Persons first name.
firstName
{77ACE572-5BDF-44e9-86AF-2CD6B7F00B2C}
Persons last family sir name.
lastName
{6008933E-3372-4111-A607-3913A72D8718}
Middle names or initials.
mName
{BFBB68F0-9442-494c-9869-E5405B24DF65}
A prefix or title for the persons name such as Miss Mister Doctor etc.
prefix
{3D223B70-2955-4e74-BE3B-0A1D5431442E}
Special service needs for the person contact are described examples include life support etc.
specialNeed
{F0CB10E7-4D38-4338-9446-B7674F165FCD}
A suffix for the persons name such as II III etc.
suffix
{F373226B-344D-4a68-941F-34FC1B8F696E}
Identifiers of the person held by an organisation such as a government agency federal state province city county financial institutions etc.
clientID
{D6AB28EF-C4BC-4e52-BA86-C7503E3CF3A9}
The matrix elements column number in the range 1 to row. Only the lower triangle needs to be stored. This column number matches ACLineSegmentPhase.sequenceNumber.
column
{CB6694A0-F76F-4b69-A8A9-C9CF26E64C78}
The matrix elements row number in the range 1 to PerLengthPhaseImpedance.conductorCount. Only the lower triangle needs to be stored. This row number matches ACLineSegmentPhase.sequenceNumber.
row
{F247BE15-2165-4832-A1D5-8B27BFA58C2B}
Market end time.
marketEndTime
{C29815A2-6145-4da0-82D4-0ADADBAA561D}
Market start time.
marketStartTime
{83BFFE49-8403-4c46-985E-E97F6AB4F438}
Planned event type.
eventType
{CAD4EB97-87C1-4e51-BB3D-276655328AB7}
This is relative time so that this attribute can be used by more than one planned market. For example the bid submission is 10am everyday.
plannedTime
{72D70C55-CDFB-45f1-B022-D90F7749F6CF}
The reason for the planned outage.
reason
{D3D3D4BC-E73E-4ed6-92E8-F8B34CB83F0D}
If true this Pnode is public prices are published for DART and FTR markets otherwise it is private location is not usable by market for biddingFTRstransactions.
isPublic
{FCD2A273-D0AE-4f09-AD5C-518647CC1B46}
Used to calculate participation of Pnode in an AggregatePnode. For example for regulation region this factor is 1 and total sum of all factors for a specific regulation region does not have to be 1. For pricing zone the total sum of all factors has to be 1.
factor
{6D45DB67-9BC8-4616-8785-C5DA2ED3C57A}
Point of delivery loss factor
podLossFactor
{7E2A5978-D690-4c48-B58A-5172333C6EC9}
Congestion component of Location Marginal Price LMP in monetary units per MW.
congestLMP
{10E2DDBC-3BE0-41c0-9D08-F72122EE2A46}
Cost component of Locational Marginal Pricing LMP in monetary units per MW.
costLMP
{5CA45BDE-B3EE-445d-B09A-38C869DEDC50}
Loss component of Location Marginal Price LMP in monetary units per MW.
lossLMP
{2A53042F-9FFE-482b-9540-07A923FA390E}
Locational Marginal Price LMP MWh
marginalClearingPrice
{25A6BE2B-6BD5-4ceb-9061-670622A4DAD7}
total MW schedule at the pnode
scheduledMW
{DFF61D74-0457-42b9-A4DD-DA9D29EE7948}
updateTimeStamp
{F67728DD-C968-43ed-9A18-71E32E8BC0F7}
updateUser
{5544800D-9E3A-4659-8499-6986D1B0338F}
A sequential value representing the relative position within a given time interval.
position
{C0718C4B-0FC2-4f02-8F55-3C94CEC4FCA4}
The quality of the information being provided. This quality may be estimated not available as provided etc.
quality
{6A1D771D-37FC-423d-9E77-E9187116DE69}
Principal quantity identified for a point.
quantity
{21FE2306-1C79-43fe-BBF7-76B1C8FBF2B9}
Secondary quantity identified for a point.
secondaryQuantity
{021826F6-FB21-4bee-8635-4F7E9AA94FA6}
Local description for where this point of sale is physically located.
location
{5D2A71D2-A4AC-4e84-979D-13685AA51641}
True if a block of material has been attached to base of pole in ground for stability. This technique is used primarily when anchors can not be used.
breastBlock
{30AFAE49-2B0A-47b7-9328-BD428DB18008}
Pole class 1 2 3 4 5 6 7 H1 H2 Other Unknown.
classification
{BAB4B7EB-930D-44fd-A589-B10DCC774D48}
The framing structure mounted on the pole.
construction
{3EF6E50E-8DEE-4fe4-B964-D1682D76405B}
Joint pole agreement reference number.
jpaReference
{06F77118-1E08-4d94-BC09-89FA617E262C}
Pole species. Aluminum Aluminum Davit Concrete Fiberglass Galvanized Davit Galvanized Steel Davit Primed Steel Davit Steel Standard Primed Steel Truncated WoodTreated WoodHard WoodSalt Treated WoodSoft Wood Other Unknown.
speciesType
{A3A888A4-81E0-4180-83EA-5F6B9F225CBD}
Date and time pole was last treated with preservative.
treatedDateTime
{412A87B4-E7EF-4bd7-B3C5-EF21FFEBB774}
Zerorelative sequence number of this group within a series of points used when there is a need to express disjoint groups of points that are considered to be part of a single location.
groupNumber
{A6E3E73C-A099-4fc2-87EF-CB70E39C88C2}
Zerorelative sequence number of this point within a series of points.
sequenceNumber
{9C1FA17F-EC70-452a-9BD5-2F5E29234B28}
X axis position.
xPosition
{2C06CBF6-1564-417b-98DF-24B9E0040DCC}
Y axis position.
yPosition
{150622F9-462B-4479-9DC4-F9035E140110}
if applicable Z axis position.
zPosition
{A0537144-D5D9-4a24-805C-D4478E98690C}
PT accuracy classification.
accuracyClass
{1C83085C-B00F-4a08-84C9-31F4F8983620}
Nominal ratio between the primary and secondary voltage.
nominalRatio
{D4188CEB-ABD3-4b22-B141-1014ED802DC2}
Potential transformer PT classification covering burden.
ptClass
{C62F1ED6-7467-491d-B29E-5F1B02510E10}
accuracyClass
{8C1D4658-31A4-4086-92CE-6A4DC77A9842}
ptClass
{DCA7C549-ADFB-4652-B4F6-46DF54FCC43E}
Threshold minimum power factor for this PricingStructure specified in instances where a special charge is levied if the actual power factor for a Service falls below the value specified here.
powerFactorMin
{70E9676C-0AF2-4361-BFE8-9B16613AF154}
Value of uninterrupted service Cost per active power.
valueUninterruptedServiceP
{4971A693-EAA2-4b1e-99C6-28DD55F41187}
Voltage imbalance violation cost Cost per unit Voltage.
voltImbalanceViolCost
{961C47D2-CA85-43a3-B68C-6517C5CFD16D}
Voltage limit violation cost Cost per unit Voltage.
voltLimitViolCost
{BD023A28-FD65-4e2f-9B29-14182FA848AF}
The date the Power System Project is in cancelled stage.
cancelled
{150F5E1E-AFD4-435f-B79F-AE23D38D4BB3}
The date Power System Project is in committed stage.
committed
{D6AFD0AA-BB96-4c65-A593-7C64982EE70B}
The date Power System Project is in build stage.
inBuild
{D405B545-9121-4e8d-8DF6-0EFE787B1093}
The date Power System Project is in planning stage.
inPlan
{A18B0A36-51D2-4823-85A1-2C9901BF89AE}
Behaviour is based on a proprietary model as opposed to a detailed model.true userdefined model is proprietary with behaviour mutually understood by sending and receiving applications and parameters passed as general attributesfalse userdefined model is explicitly defined in terms of control blocks and their input and output signals.
proprietary
{2CF58DB7-BDAE-4e11-91A1-0651D6E514E3}
Indicates whether the machine is part of a power station unit. Used for short circuit data exchange according to IEC 60909. It has an impact on how the correction factors are calculated for transformers since the transformer is not necessarily part of a synchronous machine and generating unit. It is not always possible to derive this information from the model. This is why the attribute is necessary.
isPartOfGeneratorUnit
{90536F90-2FEE-4023-A72F-58DACED054DC}
It is used to define if the data other attributes related to short circuit data exchange defines long term operational conditions or not. Used for short circuit data exchange according to IEC 60909.
operationalValuesConsidered
{48CE1171-4EB3-4eb0-981D-28AE7ABB7F49}
Vector group of the transformer for protective relaying e.g. Dyn1. For unbalanced transformers this may not be simply determined from the constituent winding connections and phase angle displacements.The vectorGroup string consists of the following components in the order listed high voltage winding connection mid voltage winding connection for three winding transformers phase displacement clock number from 0 to 11 low voltage winding connection phase displacement clock number from 0 to 11. The winding connections are D delta Y wye YN wye with neutral Z zigzag ZN zigzag with neutral A auto transformer. Upper case means the high voltage lower case mid or low. The high voltage winding always has clock position 0 and is not included in the vector group string. Some examples YNy0 two winding wye to wye with no phase displacement YNd11 two winding wye to delta with 330 degrees phase displacement YNyn0d5 three winding transformer wye with neutral high voltage wye with neutral mid voltage and no phase displacement delta low voltage with 150 degrees displacement.Phase displacement is defined as the angular difference between the phasors representing the voltages between the neutral point real or imaginary and the corresponding terminals of two windings a positive sequence voltage system being applied to the highvoltage terminals following each other in alphabetical sequence if they are lettered or in numerical sequence if they are numbered the phasors are assumed to rotate in a counterclockwise sense.
vectorGroup
{5A4A0AC2-AE76-4849-9563-015909DD9F2F}
Terminal voltage phase angle displacement where 360 degrees are represented with clock hours. The valid values are 0 to 11. For example for the secondary side end of a transformer with vector group code of Dyn11 specify the connection kind as wye with neutral and specify the phase angle of the clock as 11. The clock value of the transformer end number specified as 1 is assumed to be zero. Note the transformer end number is not assumed to be the same as the terminal sequence number.
phaseAngleClock
{D2BA85F8-D4BC-4f1a-824A-2B7E701EC65B}
value
{E6D105E4-B62D-456f-B72A-2A29D839F0F6}
A number of monetary units specified in a unit of currency.
amount
{093D3CF7-93B1-400b-9426-362029D0D0CA}
The category of a price to be used in a price calculation. The price category is mutually agreed between System Operators.
category
{2969A791-6AF1-4569-BD54-318627ED9BF0}
The direction indicates whether a System Operator pays the Market Parties or inverse.
direction
{B0A2D49B-B8F9-485a-891E-6C2C6F5D63E4}
Unique userallocated key for this pricing structure used by company representatives to identify the correct price structure for allocating to a customer. For rate schedules it is often prefixed by a state code.
code
{D69394C5-9254-4968-8624-BC4F0A8239D9}
Absolute maximum valid nondemand usage quantity used in validating a customers billed nondemand usage.
dailyCeilingUsage
{537108AF-E92B-4120-8500-6FB730ED517F}
Used in place of actual computed estimated average when history of usage is not available and typically manually entered by customer accounting.
dailyEstimatedUsage
{147D3D24-7AA8-4bda-902C-28857A29E5D5}
Absolute minimum valid nondemand usage quantity used in validating a customers billed nondemand usage.
dailyFloorUsage
{BB53179E-E177-4bed-81E1-1D2A773910A0}
True if this pricing structure is not taxable.
taxExemption
{CD9823BB-8C78-4484-802F-E0335505EE26}
Rating of prime mover.
primeMoverRating
{EE52178E-A51A-4d21-A4D8-6AFEE994F9BE}
Justification for rank.
justification
{E98CF76B-FE70-427f-8547-BC61CF0E318A}
Priority level usually lower number means high priority but the details are provided in type.
rank
{34AE2D85-7350-43ef-A7E5-D918200CF4B3}
Type describing rank e.g. high emergency etc.
type
{8699FBAF-4C60-449d-92AA-F4FB4C3FB0D1}
Textual description of this procedure.
instruction
{1A4ED9AF-6B28-41a2-A64E-A74330234D06}
Sequence number in a sequence of procedures being performed.
sequenceNumber
{C176AD36-9F60-4752-AAE9-81D507A41D14}
Date and time procedure was completed.
completedDateTime
{AD226C7F-6B32-415b-83A2-B560CDB67DF9}
The classification mechanism used to group a set of objects together within a business process. The grouping may be of a detailed or a summary nature.
classificationType
{61387D64-75FE-465e-AE65-F9434CE76E10}
The kind of business process.
processType
{12B4C7F6-B24F-4264-8F27-F6E29F1654A2}
Catalogue number for asset model.
catalogueNumber
{EE84D526-AF29-4f56-9971-17AFD121273B}
Drawing number for asset model.
drawingNumber
{F79043A4-2C5B-49b3-A559-892C475DE663}
Reference manual or instruction book for this asset model.
instructionManual
{5711572B-2381-4651-9992-19951B55C9EB}
Manufacturers model number.
modelNumber
{9F9D99E2-BF4E-480c-9F36-DF6232678DEA}
Version number for product model which indicates vintage of the product.
modelVersion
{76499278-B021-4ccb-B94F-2C4908D322D3}
Style number of asset model.
styleNumber
{5F872A8E-C74B-4058-A791-716B9882F1C0}
Bid price associated with contract
bidPrice
{4AA91973-E36C-4ae3-9451-383F39170A32}
Minimum MW value of contract
minimumLevel
{A210469E-9305-4eab-8768-B792209F6735}
Sequence to provide item numbering for the profile. greater than or equal to 1
sequenceNumber
{DFBD0BCA-7A15-428b-8CAA-C0071658D5A8}
Start datetime for this profile.
startDateTime
{9A0143AA-454E-43a7-8B4F-02E8451D11D4}
Stop datetime for this profile.
stopDateTime
{EC1FE564-537B-457b-901F-3A1768B35980}
A code that identifies appropriate type of property accounts such as distribution streetlgihts communications.
accountingUsage
{F42341DB-C87A-4945-85EE-1D388CA6FEED}
Used for property record accounting. For example in the USA this would be a FERC account.
propertyAccount
{D29FBA1B-4BB1-41a0-8C1A-B3B23AD2BC15}
Boolean parameter value. If this attribute is populated integerParameterValue and floatParameterValue will not be.
booleanParameterValue
{0E61FD56-554E-465d-9AE4-9B289A8647BD}
Floating point parameter value. If this attribute is populated booleanParameterValue and integerParameterValue will not be.
floatParameterValue
{12110E5F-7A18-491a-A9E1-3A586ED32A40}
Integer parameter value. If this attribute is populated booleanParameterValue and floatParameterValue will not be.
integerParameterValue
{A49DE176-514B-4da0-9F0A-5B915A3AAB6C}
Sequence number of the parameter among the set of parameters associated with the related proprietary userdefined model.
parameterNumber
{0CC89B5C-41AC-4172-B1E6-4036410F4512}
The maximum allowable value.
highLimit
{F305239C-BFB2-4371-8720-1F5DE2E09469}
The minimum allowable value.
lowLimit
{0CC901DB-A2AB-42e4-9447-8FEA31CFCC0F}
Direction same as positive active power flow value.
powerDirectionFlag
{AE7BDAEB-F6E5-4730-8A14-A04B9717DC86}
The status of the class set by operation or by signal. Optional field that will override other status fields.
enabled
{D865239A-5B6F-4ce9-85AE-7E6B5A7A96A3}
The defaultnormal value used when other active signalvalues are missing.
normalEnabled
{28D90BA4-7AA1-4abd-A99F-84AB484195BD}
The adjustment is given in value of the active value.
byValue
{BE83ED67-773A-4e17-A1A4-29722A57B41C}
If true the adjusted value is an reduction. Other wise it is an increase in the value.
reduce
{FB86C37D-8228-4030-B4E2-11825871E2BA}
The adjustment is given by a new active value.
setValue
{67AC81F0-98D9-47c1-A1E3-123A05600F46}
If true the equipment is put inservice otherwise outofservice.
inService
{21446F33-36FE-4e95-AC9C-E7CDCD153031}
If true the regulator is put inservice otherwise outofservice no regulation.
isRegulating
{A38F654D-B5D9-4af7-BC01-CA61BB93F59F}
The target value specified the new case input for the regulator. The value has the units appropriate to the mode attribute. The protective action does not change the mode attribute.
targetValue
{EE438BF0-AC2B-470b-8920-399AA23443FB}
Frequency power input gain iKiisubFsubi. Typical value 5.
kf
{2378BC64-904B-4742-968C-88B7B0DE0F57}
Shaft speed power input gain iKiisubomegasubi. Typical value 0.
komega
{7B6FCB6C-182B-4019-99E6-FFDCA615C6C1}
Electric power input gain iKiisubPEsubi. Typical value 03.
kpe
{64AB48CF-15BC-479e-B61C-58A7E0889E4C}
PSS gain iKsi. Typical value 1.
ks
{6D525B2C-F8A2-470f-A668-591EA55636C8}
font color0f0f0fSignal selector iViisubADATsubi.fontfont color0f0f0ftrue closed generator power is greater than iPminifontfont color0f0f0ffalse open iPei is smaller than iPmini.fontfont color0f0f0fTypical value true.font
vadat
{AA0C65C3-4C07-4991-BC6C-2C4ABA6A7F8F}
Selector iKdi. true esupsTdelaysup usedfalse esupsTdelaysup not used.
kd
{D55E3AF3-A9FB-42bc-B9B9-4C0D464475FA}
Numerator constant iai. Typical value 1.
a
{B7B33888-E2AF-45a6-B135-551B74F620DE}
Denominator order of ramp tracking filter imi. Typical value 5.
m
{717D2A5F-F7A9-4e1b-A6CF-344B5F3E957B}
Order of ramp tracking filter ini. Typical value 1.
n
{803DB770-5743-45ce-8C20-834DD902F433}
Selector for second washout enabling iCiisubTW2subi.true second washout filter is bypassedfalse second washout filter in use.Typical value true.
ctw2
{77ABA1A5-FA04-4b6e-B43C-90B89FCB7A2A}
Selector for frequencyshaft speed input iisFreqi.true speed same meaning as InputSignaKind.rotorSpeedfalse frequency same meaning as InputSignalKind.busFrequency.Typical value true same meaning as InputSignalKind.rotorSpeed.
isfreq
{9F8F44E6-304A-4c39-8C82-21430BA6C20D}
Frequencyshaft speed input gain iKiisubFsubi. Typical value 5.
kf
{CDE15429-27DD-4cc9-B8D7-6ED31D5C5A9A}
Electric power input gain iKiisubPEsubi. Typical value 03.
kpe
{777561DD-FD01-42dd-BB60-913009CC641A}
PSS gain iKiisubPSSsubi. Typical value 1.
kpss
{4D072C18-30BD-47a1-9B59-8E3C6D1E470A}
font color0f0f0fSignal selector iViisubadAttsubi.fontfont color0f0f0ftrue closed generator power is greater than iPminifontfont color0f0f0ffalse open iPei is smaller than iPmini.fontfont color0f0f0fTypical value true.font
vadat
{E97A15BF-11CB-48e4-ADB1-42C3481B5971}
Denominator order of ramp tracking filter iMi. Typical value 5.
m
{B93F120F-4EF0-4a41-BE52-ADA74DB90957}
Order of ramp tracking filter iNi. Typical value 1.
n
{CA27CFE3-AE81-41b1-A261-6E1387F96DFF}
Notch filter 1 highfrequency band three dB bandwidth iBiisubwisubi.
bwh1
{2675EA1B-FBB9-4735-8B95-407C9E7B3A1A}
Notch filter 2 highfrequency band three dB bandwidth iBiisubwisubi.
bwh2
{615AFDA6-AFB3-4fb3-9625-718C8690F956}
Notch filter 1 lowfrequency band three dB bandwidth iBiisubwisubi.
bwl1
{7DFB80FD-07F1-4bc0-B931-215326B06667}
Notch filter 2 lowfrequency band three dB bandwidth iBiisubwisubi.
bwl2
{F11DF8B0-D827-4b3d-9647-55148EFA678B}
Notch filter 1 highfrequency band filter frequency iomegaiisubnisubi.
omeganh1
{4DB867AF-870F-470b-9059-4A32463B5CDC}
Notch filter 2 highfrequency band filter frequency iomegaiisubnisubi.
omeganh2
{2A16CB89-49A7-4ad9-9089-C4482587A4BB}
Notch filter 1 lowfrequency band filter frequency iomegaiisubnisubi.
omeganl1
{BD409892-68E8-4297-9520-F5A83D9EB42E}
Notch filter 2 lowfrequency band filter frequency iomegaiisubnisubi.
omeganl2
{59E9B850-DEEE-45ab-9B6E-DFCD93F14A26}
Digitalanalogue output switch iIswi.true produce analogue outputfalse convert to digital output using tap selection table.
isw
{C27FA3BA-6B34-46dc-B36E-55A47DA1FC69}
Number of control outputs to average iNAVi 1 lt iNAVi lt 16. Typical value 4.
nav
{31B5D989-CCF9-49a6-AFDD-6AB512001E52}
Number of counts at limit to active limit function iNCLi gt 0.
ncl
{6C9B718F-90B1-48af-86C8-580085DA9144}
Number of counts until reset after limit function is triggered iNCRi.
ncr
{65B58BB6-AE01-46ba-A795-F48E009059B9}
Lead lag gain iKDPMi. Typical value 0185.
kdpm
{66542AFA-D5FB-4dfc-99CF-9F4D42F1D8AD}
Speed input gain iKi2i. Typical value 343.
ki2
{AAC42C70-DBCC-4c70-9825-1DB568FE8022}
Electrical power input gain iKi3i. Typical value 1145.
ki3
{ABC6F786-28E7-4906-9560-E1C864D0D463}
Mechanical power input gain iKi4i. Typical value 1186.
ki4
{D68ED8AF-6E44-4d4a-94B7-8BB572908985}
Represents the CA that issued the certificate. Defined to be per X.509.
issuerName
{F6EDACBE-9EC1-40a4-80CD-D45D3E4FE9E8}
Is the serial number of the certificate per X.509 definition.
serialNumber
{A498CF92-3F35-4b46-802D-A4D028FD45A4}
value
{CE3523DF-2923-4c23-91A5-845194FD296B}
value
{E705B485-9C6E-487a-9192-A0D14EAC36FF}
value
{4E4ADD0A-674C-4e87-9434-5DF76BFA57D8}
Qualification identifier.
qualificationID
{5E9C902C-045D-48a6-B432-756B5D6D2A1C}
Measurement value may be incorrect due to a reference being out of calibration.
badReference
{582D1BE5-8C79-448e-83AE-473834C0380C}
Value has been replaced by State Estimator. estimatorReplaced is not an IEC61850 quality bit but has been put in this class for convenience.
estimatorReplaced
{11CA6A0B-FEAC-41a0-AF45-AE159D352461}
This identifier indicates that a supervision function has detected an internal or external failure e.g. communication failure.
failure
{2B640DD0-57EC-4c03-BF9A-B40906336431}
Measurement value is old and possibly invalid as it has not been successfully updated during a specified time interval.
oldData
{4E74DF87-D586-4fdb-AFBC-968BDCC024A1}
Measurement value is blocked and hence unavailable for transmission.
operatorBlocked
{2686EF18-BE9A-4037-8A3F-032FBE4AADD0}
To prevent some overload of the communication it is sensible to detect and suppress oscillating fast changing binary inputs. If a signal changes in a defined time twice in the same direction from 0 to 1 or from 1 to 0 then oscillation is detected and the detail quality identifier oscillatory is set. If it is detected a configured numbers of transient changes could be passed by. In this time the validity status questionable is set. If after this defined numbers of changes the signal is still in the oscillating state the value shall be set either to the opposite state of the previous stable value or to a defined default value. In this case the validity status questionable is reset and invalid is set as long as the signal is oscillating. If it is configured such that no transient changes should be passed by then the validity status invalid is set immediately in addition to the detail quality identifier oscillatory used for status information only.
oscillatory
{5785D8A1-BB09-466c-AF85-CB88C54AD5DC}
Measurement value is beyond a predefined range of value.
outOfRange
{36E6C225-3F42-446f-873B-7CBAB71DE307}
Measurement value is beyond the capability of being represented properly. For example a counter value overflows from maximum count back to a value of zero.
overFlow
{35920B57-826D-4b5d-A0CE-82526D3C7610}
A correlation function has detected that the value is not consistent with other values. Typically set by a network State Estimator.
suspect
{F925B417-2665-40e7-89ED-F22698B8207E}
Measurement value is transmitted for test purposes.
test
{7EA53CA3-B88B-4fd4-9AF5-E19B4AEF968F}
The quality of the information being provided. This quality may be estimated not available as provided etc.
quality
{774A9E73-1211-41ac-9FA3-84A021D961B6}
The description of the type of the quantity.
type
{3FD8967F-3245-42da-AA04-74A591D8C6BB}
The lower of the original predispatch or the AC run schedule Also known as the RMR Reguirement becomes the predispatch value.
manuallySchedRMRMw
{A2808980-CA85-4214-93B7-9B7A14DD9390}
updateTimeStamp
{5B402505-B4A2-4efe-9D55-4C2F1584727A}
updateUser
{02D681C8-3711-4db3-9E3A-2D2711133823}
The RUC Award of a resource is the portion of the RUC Capacity that is not under RA or RMR contracts. The RUC Award of a resource is the portion of the RUC Capacity that is eligible for RUC Availability payment.
RUCAward
{71BE92A8-A6C5-48dd-B61E-36949755A7E3}
The RUC Capacity of a resource is the difference between i the RUC Schedule and ii the higher of the DA Schedule and the Minimum Load.
RUCCapacity
{A2D6DE99-A9AF-4fcb-9236-61917FC1B04D}
The RUC Schedule of a resource is its output level that balances the load forecast used in RUC. The RUC Schedule in RUC is similar to the DA Schedule in DAM.
RUCSchedule
{9E6AF283-3DFB-4b39-8901-F1E959B507AE}
Marginal Price MW for the commodity Regulation Up Regulation Down Spinning Reserve or Nonspinning reserve for pricing run.
clearedPrice
{2F105D8E-3556-4cff-9B40-4402DD0A4003}
updateTimeStamp
{8DA426EB-C242-4ee0-8E31-BF5E091E032E}
updateUser
{3AF4D1F8-78EF-471b-A419-C380C928168E}
The part of a fraction that is below the line and that functions as the divisor of the numerator.
denominator
{A4EB68EF-AC41-4b3b-9CF6-C2CF14199F79}
The part of a fraction that is above the line and signifies the number to be divided by the denominator.
numerator
{36E8CBA1-3ED7-4c9f-9581-27EE38B0548A}
Denominator. Value 1 indicates the number is a simple integer.
denominator
{145A5952-26F7-4fd2-9E3E-2176EC9E136E}
Numerator.
numerator
{FDE93DE3-8CB5-447a-8501-F904B30B9C93}
value
{1010C898-C3A2-45b0-BF5D-C0DEDEBA27CC}
value
{7CA4EC71-C6F8-4e22-96E2-19908B0F8533}
value
{4AEEBF1D-260E-4615-95F2-8219EA8B0AC9}
A sequential value representing the relative position within a given time interval.
position
{9FF69212-92EE-40eb-9A7A-4755584F2062}
The indication of whether or not the quantity of this reading is missing.
valueMissing
{87C7729A-76FC-44d1-9036-A16C057BA3AC}
Interharmonic denominator. Value 0 means not applicable. Value 2 is used in combination with numerator1 to represent interharmonic 12. Finally value 1 indicates the harmonic of the order specified with numerator.
denominator
{49AC48A8-C21C-4f72-A178-D6F5B3ED0F43}
Interharmonic numerator. Value 0 means not applicable. Value 1 is used in combination with denominator2 to represent interharmonic 12 and with denominator1 it represents fundamental frequency. Finally values greater than 1 indicate the harmonic of that order e.g. numerator5 is the fifth harmonic.
numerator
{7742BFFE-803C-4bbf-B91F-FE668C04F2A2}
Elaboration on the quality code.
comment
{70A62C61-5CCF-4dfa-AEC3-F2DB1C8B9FCE}
System acting as the source of the quality code.
source
{35498F43-1567-4243-841C-F5B36900D0BC}
Date and time at which the quality code was assigned or ascertained.
timeStamp
{7C91965E-E991-46ba-9581-AB42B2D25ED2}
Highlevel nature of the reading value quality.
category
{9D0C1E50-B838-4a7f-BA20-80BC82A0EAE1}
More specific nature of the reading value quality as a further subcategorisation of category.
subCategory
{8A882F61-9C1B-4509-A272-B3F0B4FC1B35}
Identification of the system which has declared the issue with the data or provided commentary on the data.
systemId
{30D4236C-A6CA-4da6-838F-E93C16488524}
In case of common flatrate pricing for power in which all purchases are at a given rate consumptionTier0. Otherwise the value indicates the consumption tier which can be used in conjunction with TOU or CPP pricing.Consumption tier pricing refers to the method of billing in which a certain block of energy is purchasedsold at one price after which the next block of energy is purchased at another price and so on all throughout a defined period. At the start of the defined period consumption is initially zero and any usage is measured against the first consumption tier consumptionTier1. If this block of energy is consumed before the end of the period energy consumption moves to be reconed against the second consumption tier consumptionTier2 and so on. At the end of the defined period the consumption accumulator is reset and usage within the consumptionTier1 restarts.
consumptionTier
{D3DFD4F3-FBD6-4571-8EBE-16EA045C41B4}
Critical peak period CPP bucket the reading value is attributed to. Value 0 means not applicable. Even though CPP is usually considered a specialised form of time of use tou this attribute is defined explicitly for flexibility.
cpp
{C90C5422-85AD-4377-A645-13F05385F2DD}
Time of use TOU bucket the reading value is attributed to. Value 0 means not applicable.
tou
{6162A0BD-1069-4a6a-950C-3357F81CAC99}
value
{2E378A28-DBB2-43ee-8264-7E45516E19A6}
The motivation of an act in coded form.
code
{FA6537D4-73E8-4c30-A0C3-97EECD3B4E0F}
The textual explanation corresponding to the reason code.
text
{495E50E9-E07A-4efc-9BC6-33E038B922A8}
True if this receipted payment is manually bankable otherwise it is an electronic funds transfer.
isBankable
{F4F0A1B0-D6E4-47c9-9CC4-FB8068A6A1B1}
Indicates the ordinal position of the reclose step relative to other steps in the sequence.
recloseStep
{033893EA-F93E-47ab-94D1-44CA5A3A9B3E}
True if device has ground trip capability.
groundTripCapable
{CA6614F0-C969-4936-8DC9-0ABB40F4FC67}
True if normal status of ground trip is enabled.
groundTripNormalEnabled
{2A70FE76-7BA5-4fee-A631-C63A925D146C}
Total number of phase reclose operations.
recloseLockoutCount
{198AD782-D482-4539-9247-444F63DAC611}
Date and time this reconditioning or a major overhaul has been performed.
dateTime
{3CF26758-DE94-4d2c-8CCD-B17805B8B735}
If true the data it produces is calculated or measured by a device other than a physical end devicemeter. Otherwise any data streams it produces are measured by the hardware of the end devicemeter itself.
isVirtual
{CF6AB1A8-2466-441b-B0CD-5A13A1C96F18}
Number of digits dials on a mechanical meter to the left of the decimal place default is normally 5.
leftDigitCount
{0C46D2F4-7F7D-4a85-9181-639F99A65B64}
Number of digits dials on a mechanical meter to the right of the decimal place.
rightDigitCount
{82C8EB70-469E-40ef-AF09-9F6F894F8B7C}
Name used for the time of use tier also known as bin or bucket. For example peak offpeak TOU Category A etc.
touTierName
{32DEC698-03EA-4e54-8CE4-F17B3B0DEED9}
Maximum Deployment time seconds
maxDeploymentTime
{B382B0B7-51E3-4950-8687-2B6CF311FC6B}
Maximum Number of Daily Load Curtailments
maxLoadRedTimesPerDay
{E674CF02-214F-43da-9D38-65E1C1CD5802}
Maxiimum Load Reduction Time min per Participating Load Resource
maxReductionTime
{EB7D903B-8CA2-40f2-A072-0D141306182D}
Maximum weekly deployments
maxWeeklyDeployment
{4B24096C-A269-473e-9B4C-85C8368605EB}
Shortest period load reduction shall be maintained before load can be restored to normal levels.This attribute may be used also in the LoadBid class. The reason that the attribute is also modeled in this class is that it is resource attribute and needs to be persistently stored.
minLoadReductionInterval
{C8DAD1E4-E0F9-4229-BB1C-8600DB1ED3A7}
Minimum Load Reduction Time min per Participating Load Resource
minReductionTime
{91BDAD99-21F3-4469-8FB0-74C9C925AC3A}
Shortest time that load shall be left at normal levels before a new load reduction.This attribute may be used also in the LoadBid class. The reason that the attribute is also modeled in this class is that it is resource attribute and needs to be persistently stored.
minTimeBetLoadRed
{0226735F-400B-493e-A677-B903D7D9A44F}
Time period that is required from an order to reduce a load to the time that it takes to get to the minimum load reduction.This attribute may be used also in the LoadBid class. The reason that the attribute is also modeled in this class is that it is resource attribute and needs to be persistently stored.
reqNoticeTime
{0F7AAB35-BDF0-4789-AD7C-07C6263CCF50}
The type of resource. Examples include fuel cell flywheel photovoltaic microturbine CHP combined heat power V2G vehicle to grid DES distributed energy storage and others.
distributedResourceType
{3770DAEC-B840-42bc-8683-D8D066430891}
Cold start time.
coldStartTime
{55DADDB4-933C-4a86-A544-9FCD2CA48A5B}
Combined Cycle operating mode.
combinedCycleOperatingMode
{6C4CDF5B-6F78-424b-B261-BC591BC28AAA}
commericialOperationDate
{575F85C6-CB48-4afb-9162-7E5DDDEE4597}
Hottointermediate time Seasonal
hotIntTime
{671490F2-F524-4f1b-A324-CE1C3A22D844}
Hot start time.
hotStartTime
{7BA1B678-5518-48e3-980F-8ADB910F538A}
Intermediatetocold time Seasonal
intColdTime
{3E621176-FEEA-4dfe-8B87-61BA584EC297}
Intermediate start time.
intStartTime
{0D984EBD-23EF-420b-9A92-B551BCB95B2A}
Maximum time this device can be shut down.
maxShutdownTime
{41C3CAA0-F9ED-4350-80C3-A9FBB0A869EA}
maximum start ups per day
maxStartUpsPerDay
{43C52424-21B1-4eac-A46D-CBB8C58FA214}
Maximum weekly Energy Seasonal
maxWeeklyEnergy
{EF663956-1740-4c10-9C6E-5FD57EBC15A3}
Maximum weekly starts seasonal parameter
maxWeeklyStarts
{63EFF7D9-B987-40cd-9AB4-A595A971CCF6}
The minimum down time for the pump in a pump storage unit.
pumpMinDownTime
{C3675AC0-83FD-4fc7-A697-7460E98F2350}
The minimum up time aspect for the pump in a pump storage unit
pumpMinUpTime
{6D1D0FE7-CD49-421c-9C67-8A67B578F16F}
The cost to shutdown a pump during the pump aspect of a pump storage unit.
pumpShutdownCost
{7C3DA9D2-0B67-4f08-8358-91C0865EBA3B}
The shutdown time minutes of the pump aspect of a pump storage unit.
pumpShutdownTime
{0E6008BD-3F09-4fb0-A4A3-BDB33A785952}
Pumping factor for pump storage units conversion factor between generating and pumping.
pumpingFactor
{85DD50DF-7E72-4c12-8CFB-94D0AB67387C}
Unit sub type used by Settlements or scheduling application. Application use of the unit sub type may define the necessary types as applicable.
resourceSubType
{DFD2F0AB-1EC2-4a4f-BF3C-C7517FF6B7BA}
River System the Resource is tied to.
riverSystem
{FDA2AAAD-2687-4c40-B5A8-3E867E1FB114}
The registered upper bound of minimum hourly block for an InterTie Resource.
minHourlyBlockLimit
{579E27F1-EBCA-4136-838A-7079038B27E6}
Emergency operating procedure Flag to indicate that the Resource is Block Load pseudo resource.
blockLoadTransfer
{D80F0D1D-7B48-4f6d-817C-381D56650C1B}
Flag to indicate that a Load Resource is part of a DSR Load
dynamicallyScheduledLoadResource
{C7EDCE9D-6572-4374-BF92-15DCFFA76779}
Qualification status used for DSR qualification.
dynamicallyScheduledQualification
{8DCCFA7B-9490-4f7a-85EF-F3563FC8FC10}
Resource Commercial Operation Date.
commercialOpDate
{2FDEC1B4-8E91-484e-B928-840F66A0E464}
Dispatchable indicates whether the resource is dispatchable. This implies that the resource intends to submit Energy bidsoffers or Ancillary Services bidsoffers or selfprovided schedules.
dispatchable
{F6634618-C613-4d63-A779-A43466A8A2EA}
Indication of the last time this item was modifiedversioned.
lastModified
{85FE9965-750B-4bc6-8892-7925D53FB7DA}
Maximum base self schedule quantity.
maxBaseSelfSchedQty
{CFAE5BB4-CC53-40d3-B79C-8DAFD6471B3D}
Maximum on time after start up.
maxOnTime
{90FA8FE0-BBF5-4999-8DE0-70A1ABE1C277}
Minimum off time after shut down.
minOffTime
{2CCCFAE5-2140-4752-B889-41975A150FD4}
Minimum on time after start up.
minOnTime
{9A51BD09-304A-4402-83AA-A354109614B7}
The time for the last time point. The value can be a time of day not a specific date.
endTime
{61C25045-8C8B-4bb8-82A6-5BCDA64CC9E9}
The position of the regular time point in the sequence. Note that time points dont have to be sequential i.e. time points may be omitted. The actual time for a RegularTimePoint is computed by multiplying the associated regular interval schedules time step with the regular time point sequence number and adding the associated schedules start time. To specify values for the start time use sequence number 0. The sequence number cannot be negative.
sequenceNumber
{D417E462-D31A-4df8-9912-76A29BFACE60}
The first value at the time. The meaning of the value is defined by the derived type of the associated schedule.
value1
{DD725FB3-91EB-480f-A9B0-355AEBE4CD7D}
The second value at the time. The meaning of the value is defined by the derived type of the associated schedule.
value2
{CD812D5E-3799-4584-A7DC-4EBBB72838A2}
Specifies the regulation status of the equipment. True is regulating false is not regulating.
controlEnabled
{59FD3220-4AC6-4fe5-ADDE-2317ACD8F701}
The regulation is performed in a discrete mode. This applies to equipment with discrete controls e.g. tap changers and shunt compensators.
discrete
{402FA12A-ED05-4ef2-812F-3C26BB27936D}
The flag tells if regulation is enabled.
enabled
{BB18638D-6DC9-43a9-8631-380ED5BF18B6}
Maximum allowed target value RegulatingControl.targetValue.
maxAllowedTargetValue
{2417F359-3B33-4d71-B942-17654980DAEB}
Minimum allowed target value RegulatingControl.targetValue.
minAllowedTargetValue
{B5AC0B65-B094-4d23-AB5D-FA9F1CF06D2D}
This is a deadband used with discrete control to avoid excessive update of controls like tap changers and shunt compensator banks while regulating. The units of those appropriate for the mode. The attribute shall be a positive value or zero. If RegulatingControl.discrete is set to false the RegulatingControl.targetDeadband is to be ignored.Note that for instance if the targetValue is 100 kV and the targetDeadband is 2 kV the range is from 99 to 101 kV.
targetDeadband
{646962B2-3D10-4e78-AA89-12D0A41BB43B}
The target value specified for case input. This value can be used for the target value without the use of schedules. The value has the units appropriate to the mode attribute.
targetValue
{9827F679-5CE0-4b9e-A7B4-219CE46E466E}
External reference to regulation if applicable.
referenceNumber
{E8BF8D7C-52A6-44f5-94F6-813D4E29DFAF}
The status of the class set by operation or by signal. Optional field that will override other status fields.
armed
{58ABBE6F-7A04-4f65-AD37-59F30A3EAE25}
The defaultnormal value used when other active signalvalues are missing.
normalArmed
{2827FCA9-9331-4e93-B76E-64863E83F1BE}
Start date and time to accumulate energy for energy usage limiting.
energyUsageStartDateTime
{F216C778-14EB-4a6b-9849-48FF9D3134DC}
True if the RCD switch has to be armed before a connect action can be initiated.
isArmConnect
{769AA1A6-92ED-433b-9656-55D6CCFEBBEC}
True if the RCD switch has to be armed before a disconnect action can be initiated.
isArmDisconnect
{C3EEB2B3-7543-4772-9D3B-A74F816E14AF}
True if the energy usage is limited and the customer will be disconnected if they go over the limit.
isEnergyLimiting
{04D0341F-B9A4-45ad-BBE8-E0D248CAD27E}
True if load limit has to be checked to issue an immediate disconnect after a connect if load is over the limit.
needsPowerLimitCheck
{98D652DA-9D08-4295-96AC-42032A79EED0}
True if voltage limit has to be checked to prevent connect if voltage is over the limit.
needsVoltageLimitCheck
{41E919E1-537B-4949-96DE-FFED2398781F}
True if pushbutton has to be used for connect.
usePushbutton
{4AA773BF-F3A0-405b-98D0-924F2EF833B0}
The maximum set point value accepted by the remote control point.
actuatorMaximum
{9C84D7FF-1A6A-4b41-8F8E-D374F4363CF5}
The minimum set point value accepted by the remote control point.
actuatorMinimum
{10CD0F3E-58E3-4bf1-BB58-7A366E82D25F}
Set to true if the actuator is remotely controlled.
remoteControlled
{FA37D934-7FD5-42d3-A3E1-0555712A3E28}
The smallest change in value to be reported.
deadband
{BAE984E8-5AEC-4b3e-9F90-D74CB4BFC16D}
The maximum value the telemetry item can return.
sensorMaximum
{4A4526F8-4FB1-43e3-B075-01846E1D7CB4}
The minimum value the telemetry item can return.
sensorMinimum
{446E8C3F-540A-4d66-B8FD-6E6C80778117}
Repair work is emergency.
emergency
{8105B867-4116-4fa0-8FD3-2A26CD2D1908}
Number of units of time making up reporting period.
reportingIntervalPeriod
{D89FAACB-360E-4e4b-8B4A-1F1D663BED88}
Region requirement maximum limit
reqMaxMW
{9B957A18-FA2C-4e5b-89B2-04F0F9CBF0AB}
The reservoirs energy storage rating in energy for given head conditions.
energyStorageRating
{1D2BE652-8A84-4e0e-90BF-6F21AFAB9A43}
River outlet works for riparian right releases or other purposes.
riverOutletWorks
{7EBFA889-4712-41d3-B241-79E6305E7F5C}
Type of spillway gate including parameters.
spillWayGateType
{AB355717-E841-4fab-A383-63221736524B}
The flow capacity of the spillway in cubic meters per second.
spillwayCapacity
{6CB37874-BA9F-402a-8347-B283B4018E42}
value
{CFCFA1A2-5401-4f99-81B4-5B5441697F60}
value
{E4ECE412-83A1-4181-9E29-DE88C54FB005}
For DA Energy Not Applicable For DA AS DA AS market award For RT Energy Not Applicable For RT AS RT AS market award excluding DA AS market or selfproviison awards
awardMW
{DDF5155C-7ADB-4765-9F4D-79D446AA3E15}
For DA Energy Total Schedule DA market schedule DA selfschedule award For DA AS DA Ancillary Service Awards DA AS market award DA AS selfprovision award For RT Energy Total Schedule RT market schedule RT selfschedule award For RT AS RT Ancillary Service Awards RT AS selfprovision award RT AS market award DA AS market award DA AS selfprovision award
clearedMW
{F1EF86CD-0F8C-4bf0-9598-9A2E5839A8DF}
Marginal Price MW for the commodity Regulation Up Regulation Down Spinning Reserve or Nonspinning reserve for pricing run.
clearedPrice
{3C4B6A18-98AF-44e6-ACD2-E0E33BA5F454}
Congestion component of Location Marginal Price LMP in monetary units per MW.
congestLMP
{1ACC24CD-B067-48ea-BF42-D0F3E60E2AAA}
Cost component of Locational Marginal Pricing LMP in monetary units per MW.
costLMP
{EF90FDB3-6B4F-4211-9032-A5260C2CE544}
The tier2 mw added by dispatcher action Market results of the synchronized reserve market
dispatcherAddedMW
{4589CF1B-6953-4fd6-A105-94B8591615FD}
Unit max output for dispatch bid in economic maximum
economicMax
{3865BBAC-DCEE-4491-AFDE-78A85BEAFCF0}
Unit min output for dispatch bid in economic minimum
economicMin
{5233C78D-D315-4fab-8FEC-26CE3FABB2BB}
Effective Regulation Down Limit MW
effRegulationDownLimit
{22C31833-2561-4c7c-B3EA-89C1887C0D3F}
Effective Regulation Up Limit
effRegulationUpLimit
{362F41FC-F626-4618-9DA9-277C1893D45E}
Locational marginal price value
lmp
{FB783ECF-8292-41c6-894E-3F08E8C34352}
Loss component of Location Marginal Price LMP in monetary units per MW.
lossLMP
{0100A689-A0BD-43b8-98B5-4D4C6E9A744B}
Identifes if the unit was set to must run by the market participant responsible for bidding in the unit
mustRunInd
{CE54EA35-91CE-4164-8386-6CD7677B396D}
Unit noload cost in case of energy commodity
noLoadCost
{0E84CFF5-BC9F-4ab1-980C-284BA4094975}
Optimal Bid cost
optimalBidCost
{52A9E0B8-201C-4bec-AFCD-D84970F19B1B}
Optimal Bid production payment based on LMP
optimalBidPay
{49138345-8B7D-42fc-832B-FD520990A380}
Optimal Bid production margin
optimalMargin
{4427C4F6-B930-4200-BA27-3838EA614C3C}
Time the manual data entry occured.
overrideTimeStamp
{248A703B-93F7-4efe-9677-AE0719CBEAAF}
Provides the ability for the grid operator to override items such as spin capacity requirements prior to running the algorithm. This value is market product based spin nonspin reg up reg down or RUC.
overrideValue
{13C37DBA-DFBE-4ac9-B6B9-01E577C1C48A}
For DA Energy DA total selfschedule award For DA AS DA AS selfprovision award For RT Energy RT total selfschedule award For RT AS RT AS selfprovision award excluding DA AS market or selfprovision awards
selfSchedMW
{AE99FBCA-3164-4617-846D-3AE4E37D95DF}
Unit start up cost in case of energy commodity
startUpCost
{2118CDF6-D1DC-4fb6-AC62-ED6C99D388CB}
In or out status of resource
status
{5FC8CE0E-5BBC-4e32-96CF-6FD600EE7E46}
Total bid revenue startupcost noloadcost bidpay
totalRevenue
{5EFDBD3B-8BBC-4a90-BE3C-FA6B7ED2FAB8}
updateTimeStamp
{D698BA1F-C17D-4b3a-810B-188C939FFBA3}
updateUser
{51EC4729-6EE5-46a1-BB01-BEBCD7AB9FC8}
Aggregation flag 0 individual resource level1 Aggregated node location2 Aggregated price location
aggregationFlag
{ADCA44B4-F70B-4cf1-99D9-4DC77D16C58A}
bidStatus
{FF7D5213-9A5C-4e42-B4CB-602B14231EB9}
Energy product commodity typeEn EnergyRu Regulation UpRd Regulation DnSr Spinning ReserveNr NonSpinning ReserveOr Operating Reserve
commodityType
{2A4E8B9E-09B9-4ab5-AD3C-824B273E244C}
Maximum amount of energy per day which can be produced during the trading period in MWh
energyMaxDay
{F7C84694-DB91-4eb1-82C4-AD1F1E694754}
Minimum amount of energy per day which has to be produced during the trading period in MWh
energyMinDay
{615993D8-50ED-4b05-81CC-1FC8920F7F7E}
Market Separation FlagY Enforce market separation constraints for this bid N Dont enforce market separation constraints for this bid.
marketSepFlag
{5FEBDCB4-33ED-4e5d-8B5D-5123E4D42D0C}
minimum number of consecutive hours a resource shall be dispatched if bid is accepted
minDispatchTime
{82365FB4-2245-460d-AC6F-AF51E20AC6CC}
Resource loading curve type1 stepwise continuous loading2 piecewise linear continuous loading3 block loading
resourceLoadingType
{E1EA6B39-8FCD-4ca6-AEB3-4E94CC2BA39D}
Maximum number of shutdowns per day.
shutDownsMaxDay
{FD4FA6A5-B41D-4f40-BF5A-6F73264A5351}
Maximum number of shutdowns per week.
shutDownsMaxWeek
{ECA28A83-21C7-4374-BCFF-A2E0EBB0C5AE}
Maximum number of startups per day.
startUpsMaxDay
{1A5E0B1D-1F7B-45ec-AD37-9486A5DAE136}
Maximum number of startups per week.
startUpsMaxWeek
{A2C524DD-3E89-4ee6-A3F3-EE04391BAE00}
True if bid is virtual. Bid is assumed to be nonvirtual if attribute is absent
virtual
{98F6EA70-2C46-4f1e-9C33-1E15BF19A672}
default capacity
defaultCapacity
{C2275FAB-0D52-42e4-A22C-B4F01D679FC9}
maximum capacity
maximumCapacity
{BEC12E36-9DD8-4453-A2E3-ECF2BE7B809B}
minimum capacity
minimumCapacity
{96DABEB7-8FA8-4024-86D1-0A373E197A65}
certifiedNonspinDAMMw
{6E426F03-5FF9-49e2-A8CC-772C1AB6CACD}
certifiedNonspinRTMMw
{3EEB6939-937D-4e80-971F-700A2705810F}
certifiedRegulationMw
{683A2BDB-72E0-4fb5-A4B4-630B3330583D}
certifiedSpinMw
{59B16A92-7E6F-4262-BD9B-BF243E9CC8CF}
Commenst to explain why the acceptance status. For example to explain why a request is accepted only partially instead of fully.
acceptComments
{071472A2-95C2-4487-BEA5-36B81DA0EA14}
Status of the resource for this deployment. Values include full compliance partial compliance optout etc.
acceptStatus
{74B3E3A5-8518-460d-A811-A29A5EA0DAE2}
The MW amount the resource can contribute for this deployment. This is from the DR provider as a response? Or actual? Does this belong in settlement? Discuss more.
resourceResponseMW
{BB9F2DF9-A29D-4b23-B704-ADDA3368D33C}
Blocked Dispatch Indicator YesNo
blockedDispatch
{F45560E7-C484-4d1c-8442-D6425F9892FB}
Block sending DOP to ADS YN
blockedPublishDOP
{88AC4A3E-72EA-4c21-A33D-FEFD90EA6C57}
indicate which limit is the constraints
limitIndicator
{AA50B2D0-8923-4cd8-9429-A7D14A634B68}
resource energy ramping lower limit
lowerLimit
{9C7BABEC-986F-421d-AF6E-6B3125993011}
maximum ramp rate
maxRampRate
{F1C7971F-A992-47b2-8F90-61CC230005EF}
The upper operating limit incorporating any derate used by the RTD for the Binding Interval.
operatingLimitHigh
{1988C90A-D81F-4a7c-B4E6-85926DD9958C}
The lower operating limit incorporating any derate used by the RTD for the Binding Interval.
operatingLimitLow
{445A99E4-58EB-4f71-A8B6-3B1F3878DE32}
The upper regulating limit incorporating any derate used by the RTD for the Binding Interval.
regulatingLimitHigh
{5E47AAEE-B818-4566-BEE3-5AA342C03186}
The lower regulating limit incorporating any derate used by the RTD for the Binding Interval.
regulatingLimitLow
{59894E81-264B-4e51-8021-B3C866860399}
Unit Commitment Status OnOffStarting
resourceStatus
{E769D448-0F9E-4692-AF68-37EF2A390125}
Resource total upward schedule. total schedule En all AS per resource per interval
totalSchedule
{B49A640A-567A-48a0-9311-3BFE7E9D520D}
updateTimeStamp
{830328A6-BFCA-44c7-B15A-F7B020B2CF22}
updateUser
{18985560-A22C-4af8-924A-51128A1A107E}
resource energy ramping upper limit
upperLimit
{B9E153D6-DE03-48d7-8FB6-6092A296706D}
Type of this group.
type
{0700679C-348D-4223-95FA-6F09D0F33822}
weighted average for RTPD and RTCD and same for RTID
calcLoadFollowingMW
{AF0EA6D5-8552-4efe-8E78-898FA26C784A}
dispWindowHighLimt
{F770DB06-A853-49ca-8E7B-9A20A6D70761}
dispWindowLowLimt
{6C95510E-A69C-461a-B3FC-A8AFEC15CF6D}
Unique instruction id per instruction assigned by the SC and provided to ADS. ADS passes through.
instructionID
{E84B0DD5-1BF5-496c-AE29-1D68FE6213CB}
The start of the time interval for which requirement is defined.
intervalStartTime
{9A521D60-DD0F-4952-9DC3-615DA76AA593}
Verifiable OampM Cost Cold Startup
omCostColdStartup
{192181D3-5752-4176-B9AB-C6302A3718C5}
Verifiable OampM Cost Hot Startup
omCostHotStartup
{8DFEECE8-B042-475e-990B-72239D26F922}
Verifiable OampM Cost Intermediate Startup
omCostIntermediateStartup
{2664C4FC-E547-4560-AE20-8BAD0B351540}
Verifiable OampM Cost MWh LSL
omCostLowSustainedLimit
{7041420E-BF06-43f3-A6BC-CEFF49297FD2}
effectiveEndTime
{7FD9D769-A9D2-4a2b-A613-6037499A8EA3}
effectiveStartTime
{8D8E2D4C-45E4-4137-80AF-C97E8C59F783}
Description of the performance evaluation e.g. the rating classification used any is allowed why the evaluation was performed anything that describes the demand response performance evaluation.
evaluationDescription
{06147450-AB8F-4d4c-95F9-7DB957E38F03}
The value of the performance. as a String any rating scheme is supported e.g. 123 or low medium high. The rating scheme is described in the performanceValueDescription attribute.
evaluationValue
{A2968EE8-F705-4159-B2B2-3D6400EE0CDD}
Description name of the property factor.
factorDescription
{EF857CC6-C883-4932-95E3-24170CA6F026}
Value of the property factor.
factorValue
{6A7FFF8B-D38A-42a9-879B-753D3EA7EF97}
starting date time that the rating is valid for
effectiveEndTime
{C60BBE60-37A8-44f7-ABA1-6757B5B5A81D}
ending date time that the rating is valid for
effectiveStartTime
{20A6C9E3-1013-4169-A977-7E546A121FD1}
the resources demand response rating description
ratingDescription
{BF37DE31-A90A-427f-BF6C-18DC0345ED41}
the type of performance rating e.g. which market or product the rating is for
ratingType
{507F1297-FEA1-492a-B1BC-202A2823C377}
the resources demand response rating
ratingValue
{AB1B47CB-4A31-4075-9D20-5F66F2E158A5}
Type of the time series data e.g. baseline data meter read data computed performance data.
timeSeriesDataType
{BE982C80-8088-4d8c-90E4-9A0AB614CB3C}
Optional description of the time series data e.g. baseline data meter read data computed performance data.
timeSeriesDescription
{C1E10AC6-1873-4410-BE43-9272E11DABCC}
Description for the value1 contained within the TimeSeriesFactor.
value1Description
{69E44D0D-778E-4bc2-AE74-5889B34EDF93}
Description for the value2 contained within the TimeSeriesFactor.
value2Description
{1C8CBF64-452D-4e3b-A419-FE070A275E55}
Verifiable Cold Start Up Fuel MMBtu per start
fuelColdStartup
{AAB81330-0690-437e-AC43-34D7ECC143A5}
Verifiable Hot Start Up Fuel MMBtu per start
fuelHotStartup
{0497A286-D1FE-4e14-9F32-3FEDC9F2C7A7}
Verifiable Intermediate Start Up Fuel MMBtu per start
fuelIntermediateStartup
{E291E0BD-C737-4cf6-B834-4576FEB6F50D}
MinimumEnergy fuel MMBtuMWh
fuelLowSustainedLimit
{D92E6E6E-749A-4214-A715-D5E23AE0FE07}
The active power value for the demand adjustment type. This supports requests to be made to a resource for some amount of active power provided by a particular response method as specified by the method attribute e.g. lighting HVAC wall mounted air conditioners etc..
activePower
{5D0D596E-8538-4e65-872B-D9902186B04A}
The unit of measure of active power e.g. kiloWatts kW megaWatts mW etc.
activePowerUOM
{0761A6BD-9504-4e76-95A0-9678E09FDE6B}
The response method e.g. lighting HVAC wall mounted air conditioners etc..
method
{4D5252AC-BF4D-49f4-AC51-C4E8C0640FC5}
This value provides for scaling of a response methods active power. For example a response method of air conditioning could utilize a small amount of active power from each air conditioning unit e.g. 0.1 kiloWatt but the site multiplier could be used to produce a the total active power adjustment by multiplying the response method active power by this value e.g. a building with 100 window air conditioning units so 100 0.1 kW 10 kW.
siteMultiplier
{0214AFA0-EFD1-41c8-9164-F77472B5C51F}
Property related information that describes the ROWs land parcel. For example it may be a deed book number deed book page number and parcel number.
propertyData
{604852F3-7580-458f-91B1-8CDFD9C5FA41}
Type of role.
type
{660E0D6C-4274-4184-995D-F8932685CE1F}
Power factor nameplate data. It is primarily used for short circuit data exchange according to IEC 60909. The attribute cannot be a negative value.
ratedPowerFactor
{B5179363-B1D6-44bc-949C-449AA1934ACE}
Damping torque coefficient iDi gt 0. A proportionality constant that when multiplied by the angular velocity of the rotor poles with respect to the magnetic field frequency results in the damping torque. This value is often zero when the sources of damping torques generator damper windings load damping effects etc. are modelled in detail. Typical value 0.
damping
{5F801ECC-E3CF-481c-B5F9-FED2D71F679A}
Saturation factor at rated terminal voltage iS1i gt 0. Not used by simplified model. Defined by defined by iSiiE1i in the SynchronousMachineSaturationParameters diagram. Typical value 002.
saturationFactor
{43DE8A9C-88A1-48c1-BC53-2022481FD579}
Saturation factor at 120 of rated terminal voltage iS12i gt RotatingMachineDynamics.saturationFactor. Not used by the simplified model defined by iSiiE2i in the SynchronousMachineSaturationParameters diagram. Typical value 012.
saturationFactor120
{E4937370-1EC7-4358-8FC2-3A6D3AF17808}
value
{F2A70238-8D27-4b54-AD10-EFF7F53201E5}
Classification by utilitys work management standards and practices.
type
{6395BDEB-FCB9-4ca0-887F-421AEC4670C7}
time of the update from SCADA
timeStamp
{EB683575-E93D-479b-B554-A049DEEE7532}
Behaviour is based on a proprietary model as opposed to a detailed model.true userdefined model is proprietary with behaviour mutually understood by sending and receiving applications and parameters passed as general attributesfalse userdefined model is explicitly defined in terms of control blocks and their input and output signals.
proprietary
{5B9A28EC-586A-4768-891D-DBDDAA0D77EC}
Date and time this safety document has been issued.
issuedDateTime
{06B39557-E213-45e4-BA87-EF6E23458375}
Date and time this safety document has been released.
releasedDateTime
{05643D1D-FFC2-43e3-AB97-CAB50A908FC3}
Type of scheduled event.
type
{3D337F25-5696-49d0-B177-2B94C8334173}
Date that the scheduling coordinator becomes creditworthy.
creditStartEffectiveDate
{E44244BC-3803-48ae-B89B-84AAEB0B1C42}
Indication of the last time this scheduling coordinator information was modified.
lastModified
{76262E08-0E04-42c8-832D-8E266B21627B}
Scheduling coordinator qualification status Qualified Not Qualified or Disqualified.
qualificationStatus
{B5262D45-86D2-4a65-B8E9-2009F29AFDE5}
This is the short name or Scheduling Coordinator ID field.
scid
{C4D2624D-4A48-4e2a-942C-5356A5C4698B}
Login ID
loginID
{275B03D3-A5AA-480b-9E87-413EBEF0C254}
Assigned roles these are roles with either Read or ReadWrite privileges on different Market Systems
loginRole
{38B2006F-13D7-4551-89A5-E5AD85D63D1F}
Date and time this seal has been applied.
appliedDateTime
{A2FD6612-ADAA-4307-8A3C-2631F6043775}
reserved word Seal number.
sealNumber
{6E885028-ED9A-4f37-8506-47A175C98E7A}
Date season ends.
endDate
{863F06C3-15B4-4292-833B-3CF72A8ABD23}
Date season starts.
startDate
{4F960CB2-0438-48dd-A134-A7398B3C4C61}
Time in seconds
value
{EC69405D-C44E-4c12-BAD5-58A3C1375649}
Cleared value for the specific self schedule type listed.
selfSchedMW
{7EC71EF8-D79C-4388-BE1A-52B515050DB3}
The date of the last update related to this market object.
lastUpdateDate
{7339EBC4-5F86-443f-8660-36CE0867DE4E}
Type of method used in the business process related to this Series e.g. metering method.
methodType
{6632E2EB-70AC-4a2b-B5EA-E60B71B42405}
For a market object the date of registration of a contract e.g. the date of change of supplier for a customer.
registrationDate
{BFF04E36-FA5F-4d20-BFD9-8371780D3E36}
Describe if a metal oxide varistor mov for over voltage protection is configured in parallel with the series compensator. It is used for short circuit calculations.
varistorPresent
{7D1BDB14-3258-4f63-B2B4-D55EEB08EC07}
True if utility must autmatically pay the specified amount whenever the condition is not satisified otherwise customer must make a claim to receive payment.
automaticPay
{3E0521F2-073D-4ba0-96E2-4C1B9AA26DB2}
Explanation of the requirement and conditions for satisfying it.
serviceRequirement
{44E73159-6BF7-4772-B2ED-7B85FCBE995D}
Method for the service person to access this service location. For example a description of where to obtain a key if the facility is unmanned and secured.
accessMethod
{0037D380-8BCE-443a-A471-2A60AA36271F}
True if inspection is needed of facilities at this service location. This could be requested by a customer due to suspected tampering environmental concerns e.g. a fire in the vicinity or to correct incompatible data.
needsInspection
{6C778C83-6FED-4a77-A515-E082EBA483E9}
Problems previously encountered when visiting or performing work on this location. Examples include bad dog violent customer verbally abusive occupant obstructions safety hazards etc.
siteAccessProblem
{F391522D-EBB4-4e50-84FB-B5E100C93CC3}
Multiplier value.
value
{40BB2D3D-FD5F-4ebb-B1FF-5D681F893D7B}
Number of critical service delivery points affected by an outage.
criticalCount
{55AD8E4F-0658-4eaa-9A4B-E2B5A530B8C1}
Number of all service delivery points affected by an outage.
totalCount
{931644DD-C199-4b7c-9996-298AD5ED0DA9}
Unique transaction reference prefix number issued to an entity by the International Organization for Standardization for the purpose of tagging onto electronic financial transactions as defined in ISOIEC 78121 and ISOIEC 78122.
issuerIdentificationNumber
{D918C8B9-0BE2-4ee0-B63A-9D41CB71DA99}
Normal value for Control.value e.g. used for percentage scaling.
normalValue
{7261D276-52C2-49df-9B88-2C69F225F21B}
The value representing the actuator output.
value
{F73DC098-9B6A-4c02-AF7D-7CE330617A2C}
The trade date on which the settlement is run.
tradeDate
{E891CF3D-DB7E-41db-9377-ABAE81190BB6}
Type of assignement intended to be worked on this shift for example temporary standard etc.
assignmentType
{6E42A146-AF71-4f6f-99C5-C0F9B779EA1F}
Number of cycles for a temporary shift.
cycleCount
{0C848437-B6CA-4eb8-BC34-7E84C3BB3D23}
Tap step number for the energised end of the test pair.
energisedEndStep
{48C771BA-9E75-448d-A4BF-FEF94FE9B915}
Tap step number for the grounded end of the test pair.
groundedEndStep
{5F1796F7-DB42-4572-95A8-207DF6A5655B}
Used for Yn and Zn connections. True if the neutral is solidly grounded.
grounded
{819FDD3F-56BC-4323-A11A-0E3DF06D929D}
The maximum number of sections that may be switched in.
maximumSections
{A38AEF78-95E1-44c8-B060-2ABC1D8C921E}
The normal number of sections switched in. The value shall be between zero and ShuntCompensator.maximumSections.
normalSections
{98B74E3C-2205-4981-9E38-8E394C2A4D79}
Shunt compensator sections in use. Starting value for steady state solution. The attribute shall be a positive value or zero. Non integer values are allowed to support continuous variables. The reasons for continuous value are to support study cases where no discrete shunt compensators has yet been designed a solutions where a narrow voltage band force the sections to oscillate or accommodate for a continuous solution as input. For LinearShuntConpensator the value shall be between zero and ShuntCompensator.maximumSections. At value zero the shunt compensator conductance and admittance is zero. Linear interpolation of conductance and admittance between the previous and next integer section is applied in case of noninteger values.For NonlinearShuntCompensators shall only be set to one of the NonlinearShuntCompenstorPoint.sectionNumber. There is no interpolation between NonlinearShuntCompenstorPoints.
sections
{092847A7-BC7D-4682-BA72-84E03733C148}
The switch on count since the capacitor count was last reset or initialized.
switchOnCount
{29F942BE-335A-4233-88AA-8F66D2BA8E58}
The date and time when the capacitor bank was last switched on.
switchOnDate
{8D542910-E6DF-4244-A561-DC898FCF6924}
For VAR amp or power factor locally controlled shunt impedances the flow direction in out.
branchDirect
{AD002C5C-C511-43e2-BC31-528C5951E9D3}
Upper control setting.
localOffLevel
{3BBC36D1-37C7-4d45-9F4F-48A81B33BFB9}
Lower control setting.
localOnLevel
{18873C57-44E9-4a74-9D59-84EDEE8E85EB}
True if the locally controlled capacitor has voltage override capability.
localOverride
{5171389C-7C1C-4394-9292-CD966A29A7EF}
IdmsShuntImpedanceData.maxNumSwitchOps.
maxSwitchOperationCount
{2E839DBA-2073-40e0-BBDC-18053EC6E0DE}
True if open is normal status for a fixed capacitor bank otherwise normal status is closed.
normalOpen
{A9E80E20-6FD9-47d7-9675-EF01177947BD}
For VAR amp or power factor locally controlled shunt impedances the index of the regulation branch.
regBranch
{150E560D-D77A-45bc-875D-B7C22F7231B4}
For VAR amp or power factor locally controlled shunt impedances the end of the branch that is regulated. The field has the following values from side to side and tertiary only if the branch is a transformer.
regBranchEnd
{044D2971-4EDC-46db-8180-A2A5E9B71AD8}
True if regulated voltages are measured line to line otherwise they are measured line to ground.
vRegLineLine
{996F55D3-DD71-454b-97D6-2E1FBBE2F6EF}
The current status for the Voltage Control Capacitor 1 Connected 0 Disconnected
connectionStatus
{07A334F1-C745-4457-887E-83257096DA0A}
The desired voltage for the Voltage Control Capacitor
desiredVoltage
{379F7D91-2F72-4f4b-A12A-B1E06BDFD9CE}
The injection of reactive power of the filter bank in the NA solution or VCS reactive power production
mVARInjection
{6EAC6FDA-32A7-4dc2-AC22-49EC6628FD30}
Voltage control capacitor step position
stepPosition
{1AF0C71D-B59A-48ba-A432-78B22B2F9AE4}
Indicator if the voltage control this is regulating True Yes False No
voltageRegulationStatus
{385D588C-9282-4282-AD4B-4DF20A7BBA92}
The maximum number of sections that may be switched in for this phase.
maximumSections
{2C99794B-45D6-49f5-A824-9C28E00B58DD}
For the capacitor phase the normal number of sections switched in. The value shall be between zero and ShuntCompensatorPhase.maximumSections.
normalSections
{F758CEC8-481C-4189-BDBE-93C124F74BF5}
Shunt compensator sections in use. Starting value for steady state solution. The attribute shall be a positive value or zero. Non integer values are allowed to support continuous variables. The reasons for continuous value are to support study cases where no discrete shunt compensators has yet been designed a solutions where a narrow voltage band force the sections to oscillate or accommodate for a continuous solution as input.For LinearShuntConpensator the value shall be between zero and ShuntCompensatorPhase.maximumSections. At value zero the shunt compensator conductance and admittance is zero. Linear interpolation of conductance and admittance between the previous and next integer section is applied in case of noninteger values.For NonlinearShuntCompensators shall only be set to one of the NonlinearShuntCompenstorPhasePoint.sectionNumber. There is no interpolation between NonlinearShuntCompenstorPhasePoints.
sections
{3BA39BCB-56D3-4739-B4E8-CB34290BF25C}
The date and time of the most recent generating unit shutdown.
shutdownDate
{C495CFA2-919C-4cec-975C-F8DC926A91E6}
Date and time the skill became effective.
effectiveDateTime
{E6E3DB2B-AE0E-450a-BE66-13C6315E9C0A}
Identifier of specimen used in inspection or test.
specimenID
{3AC42772-D031-4b9b-A365-F68F5EF6A25D}
Date and time sample specimen taken.
specimenSampleDateTime
{5ACA13EE-9821-4079-BDA2-EEDDCE035E4C}
Date and time the specimen was received by the lab.
specimenToLabDateTime
{C9BF41F1-26E4-4455-824D-CB5A0944F13F}
value
{E21F1358-2DFC-4a4c-8D74-FB69C43FAF00}
The priority of the stage. 0 don t care default 1 highest priority. 2 is less than 1 and so on. A stage with higher priority needs be activated before a lower stage can be activated.
priority
{9BC3DCEC-B6A2-4426-8DB0-A499DFAE0A57}
The status of the class set by operation or by signal. Optional field that will override other status fields.
armed
{9BF4B5C0-18A5-475b-BF28-BC017FE2734E}
The defaultnormal value used when other active signalvalues are missing.
normalArmed
{8404B97F-2B87-4fef-B6DB-558AF99BE4B8}
Priority of trigger. 0 don t care default 1 highest priority. 2 is less than 1 and so on. A trigger with the highest priority will trigger first.
priority
{4A46F23C-C9A3-4c78-A813-C74143B6A3D1}
Standard alphanumeric code assigned to a particular productservice within an industry.
code
{0CEB6E97-7E3B-47cd-B2B6-C70AAA067269}
The date and time of the most recent generating unit startup.
startupDate
{0EEE810A-ACC6-4abb-9343-B79416836876}
Startup priority within control area where lower numbers indicate higher priorities. More than one unit in an area may be assigned the same priority.
startupPriority
{78E0F1CC-90AC-4129-B39E-B5E0B33ED065}
Date and time for which status value applies.
dateTime
{F75CAF5C-DCC0-40fc-A2AF-D10354C0E735}
Reason code or explanation for why an object went to the current status value.
reason
{BF4685AC-F0E0-40f0-87F2-5D4714B1D11F}
Pertinent information regarding the current value as free form text.
remark
{BD8B05D0-CEC7-4f60-8CC3-7C88DA03505F}
Status value at dateTime prior status changes may have been kept in instances of activity records associated with the object to which this status applies.
value
{7BAA985C-D13D-4282-91ED-90FBCF326D6B}
Rating of steam supply.
steamSupplyRating
{3DB026F2-5780-43ac-B301-9177CE31217B}
Fraction of power from shaft 1 high pressure turbine output.
shaft1PowerHP
{30AED556-D03A-48d7-A08B-64476C4F5889}
Fraction of power from shaft 1 intermediate pressure turbine output.
shaft1PowerIP
{0AB4FE34-3498-4bd9-AA6A-958BBFB49718}
Fraction of power from shaft 1 first low pressure turbine output.
shaft1PowerLP1
{E28C564F-EBEC-4ad8-83F2-F5CB91054B08}
Fraction of power from shaft 1 second low pressure turbine output.
shaft1PowerLP2
{8D4D447A-65BF-4f6d-B711-5F38C56CCE3C}
Fraction of power from shaft 2 high pressure turbine output.
shaft2PowerHP
{2AD424EA-6398-4f48-A710-5ADF501FA834}
Fraction of power from shaft 2 intermediate pressure turbine output.
shaft2PowerIP
{17DC375F-3B1C-43e4-9630-1CBFB6EFEB6A}
Fraction of power from shaft 2 first low pressure turbine output.
shaft2PowerLP1
{CDB649BB-9A07-4918-90C5-ED4A86AF1C2A}
Fraction of power from shaft 2 second low pressure turbine output.
shaft2PowerLP2
{33C256C1-2AD1-44e9-B41D-9C2517ECBDA7}
The language in which the address is specified using ISO 6391 two digit language code.
language
{7BD40FC3-3D5F-4229-ADAF-7CFC1AC97F0B}
Post office box.
poBox
{AE33800A-1AD9-45e6-8415-1B9FB3A789C8}
Postal code for the address.
postalCode
{8F962EBC-8805-4e03-8051-45E7382F0649}
First line of a free form address or some additional address information for example a mail stop.
addressGeneral
{5CE3C56A-A8CB-4d17-8F13-B1D56813F9B0}
if applicable Second line of a free form address.
addressGeneral2
{DC974BBD-371B-400a-BECB-7D8F8A5C58E2}
if applicable Third line of a free form address.
addressGeneral3
{07C70D18-5538-4645-B13D-BBD72DE32C97}
if applicable In certain cases the physical location of the place of interest does not have a direct point of entry from the street but may be located inside a larger structure such as a building complex office block apartment etc.
buildingName
{7537B883-F71B-4189-B0C4-036277339DEF}
if applicable Utilities often make use of external reference systems such as those of the townplanners department or surveyor generals mapping system that allocate global reference codes to streets.
code
{9C44FAD9-C465-4c6b-A403-E6F1E66D9BE1}
The identification by name or number expressed as text of the floor in the building as part of this address.
floorIdentification
{24B16BCA-4094-43e8-9867-BC2E9EDC5D04}
Name of the street.
name
{CFEA2CAE-B7AA-4efd-ADCA-844A71759BFD}
Designator of the specific location on the street.
number
{DF4B02A3-F827-403b-AF42-3EDF7C5AB26E}
Prefix to the street name. For example North South East West.
prefix
{C0D97DAC-BB35-430e-B7F4-8C9FFBBED05D}
Suffix to the street name. For example North South East West.
suffix
{E00200CA-8258-41be-8D82-475C894ECD59}
Number of the apartment or suite.
suiteNumber
{2292B0DB-9622-4f91-A86B-C8067BCB34DF}
Type of street. Examples include street circle boulevard avenue road drive etc.
type
{C1813D47-8834-4076-8C7D-A2A86410A073}
True if this street is within the legal geographical boundaries of the specified town default.
withinTownLimits
{9B131882-C1C7-4ecc-B52A-FC25C2AFFCC7}
The value to supervise.
value
{CD179EE2-08E0-422c-8DC7-22CC8ADDDE71}
Value of this quantity.
value
{BAD170CB-1619-4202-A717-0253140C6495}
Date fumigant was last applied.
fumigantAppliedDate
{A7EC168D-91A7-4adf-A262-BC18CE2751C0}
Name of fumigant.
fumigantName
{5A990EE4-A247-4d51-8292-6BCA67D5E453}
True if weeds are to be removed around asset.
removeWeed
{BF6DDC13-711A-4566-B0A2-8165E35443DD}
Date weed were last removed.
weedRemovedDate
{AE7A7236-019E-4b3d-864A-4E7FB0964870}
if anchor Number of rods used.
anchorRodCount
{B4BB2EBE-65EF-401a-8056-77F44A804ABA}
Size of this support structure.
size
{D9811D22-A4FC-431e-9F62-7B3A9C4F130F}
Market area short name which is the regulation zone. It references AGC regulation zone name.
areaShortName
{4517C598-1961-4006-98F4-FC065361BF0B}
Loss estimate constant coefficient
constantCoefficient
{79D175AA-21A5-4785-B269-2482FF00AFE4}
Loss estimate linear coefficient
linearCoefficient
{870F1DA9-9DA3-49d7-BD70-7BF15012DD0F}
Maximum amount of self schedule MWs allowed for an embedded control area.
maxSelfSchedMW
{FEC5C00B-AFE1-4826-BADF-2D57AC7D2ADC}
Minimum amount of self schedule MW allowed for an embedded control area.
minSelfSchedMW
{CE49DB13-6706-46de-A03E-AE06B3A7FE36}
Loss estimate quadratic coefficient
quadraticCoefficient
{F36C7A04-A9EF-4148-913C-A59B9C08DE1D}
An indicator of the order a resource should be substituted. The lower the number the higher the precedence.
precedence
{8876BA44-ADEC-45a3-A12E-814357D6A651}
If true the arrester has a polymer housing porcelain otherwise.
isPolymer
{03584C79-2C6E-42c3-9ABE-B78C1CC4A8A5}
Determines the arrester energy discharge capability. Choices are limited to 0 none through 5 highest by IEC 60099. Classes 1..3 require a 10kA nominal discharge current. Classes 4..5 require a 20kA nominal discharge current. Lower nominal discharge currents must use class 0.
lineDischargeClass
{7267083E-E1D5-44c1-8A6D-294C43C55410}
value
{5AB38FF3-6ED0-4479-947D-CB7B7FF06765}
value
{194691F2-4589-4c33-904D-5FC9FE41AC3A}
The number of sections in service as a continuous variable. The attribute shall be a positive value or zero. To get integer value scale with ShuntCompensator.bPerSection.
sections
{9CF2E84D-246A-4e10-9289-A42B1F563EBB}
The in service status as a result of topology processing. It indicates if the equipment is considered as energized by the power flow. It reflects if the equipment is connected within a solvable island. It does not necessarily reflect whether or not the island was solved by the power flow.
inService
{4031A324-BC7D-46da-A4F8-F5FF3AD7C480}
The attribute tells if the computed state of the switch is considered open.
open
{B4297F1E-EA65-4837-8A2C-65C5DA1D97FF}
The floating point tap position. This is not the tap ratio but rather the tap step position as defined by the related tap changer model and normally is constrained to be within the range of minimum and maximum tap positions.
position
{640BC88B-D310-47fc-85CA-893FE11565EB}
If true the switch is locked. The resulting switch state is a combination of locked and Switch.open attributes as followsullilockedtrue and Switch.opentrue. The resulting state is open and lockedlililockedfalse and Switch.opentrue. The resulting state is openlililockedfalse and Switch.openfalse. The resulting state is closed.liul
locked
{D72B9A82-CD67-425e-AF36-802920CFAF3F}
The attribute is used in cases when no Measurement for the status value is present. If the Switch has a status measurement the Discrete.normalValue is expected to match with the Switch.normalOpen.
normalOpen
{42C10E32-018C-4f7d-81E1-3687F5A7FCFD}
The attribute tells if the switch is considered open when used as input to topology processing.
open
{7FC100AA-9641-4d45-AC84-8B90D9FC4D3F}
Branch is retained in the topological solution. The flow through retained switches will normally be calculated in power flow.
retained
{5E9C873C-F052-49f6-9247-D7274CDA570A}
The switch on count since the switch was last reset or initialized.
switchOnCount
{0FA70685-F30F-4d40-9CA6-65C5C7AC0543}
The date and time when the switch was last switched o