{ "document": { "acknowledgments": [ { "names": [ "Mark Gondree" ], "organization": "Sonoma State University", "summary": "reporting this vulnerability" }, { "names": [ "Francisco Tacliad", "Thuy Nguyen" ], "organization": "the Naval Postgraduate School", "summary": "reporting this vulnerability" } ], "category": "csaf_security_advisory", "csaf_version": "2.0", "distribution": { "text": "Disclosure is not limited", "tlp": { "label": "WHITE", "url": "https://us-cert.cisa.gov/tlp/" } }, "lang": "en-US", "notes": [ { "category": "general", "text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov", "title": "CISA Disclaimer" }, { "category": "legal_disclaimer", "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.", "title": "Legal Notice" }, { "category": "summary", "text": "Vendor: Rockwell Automation", "title": "Risk evaluation" }, { "category": "other", "text": "Worldwide", "title": "Countries/areas deployed" }, { "category": "other", "text": "Milwaukee, Wisconsin", "title": "Company headquarters location" }, { "category": "general", "text": "ICS-CERT reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.", "title": "Recommended Practices" }, { "category": "general", "text": "ICS-CERT also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "Additional mitigation guidance and recommended practices are publicly available in the ICS -CERT Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT web site.", "title": "Recommended Practices" }, { "category": "general", "text": "Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to ICS-CERT for tracking and correlation against other incidents.", "title": "Recommended Practices" }, { "category": "other", "text": "No known public exploits specifically target this vulnerability. Not remotely exploitable. High skill level is needed to exploit.", "title": "Exploitability" } ], "publisher": { "category": "coordinator", "contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870", "name": "CISA", "namespace": "https://www.cisa.gov/" }, "references": [ { "category": "self", "summary": "ICS Advisory ICSA-17-138-03 JSON", "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2017/icsa-17-138-03.json" }, { "category": "self", "summary": "ICS Advisory ICSA-17-138-03 Web Version", "url": "https://us-cert.cisa.gov/ics/advisories/ICSA-17-138-03" } ], "title": "Rockwell Automation MicroLogix 1100 Controllers", "tracking": { "current_release_date": "2017-07-18T00:00:00.000000Z", "generator": { "engine": { "name": "CISA CSAF Generator", "version": "1.0.0" } }, "id": "ICSA-17-138-03", "initial_release_date": "2017-05-18T00:00:00.000000Z", "revision_history": [ { "date": "2017-05-18T00:00:00.000000Z", "legacy_version": "Initial", "number": "1", "summary": "ICSA-17-138-03P Rockwell Automation MicroLogix 1100 Controllers" }, { "date": "2017-07-18T00:00:00.000000Z", "legacy_version": "A", "number": "2", "summary": "ICSA-17-138-03 Rockwell Automation MicroLogix 1100 Controllers (Update A)" } ], "status": "final", "version": "2" } }, "product_tree": { "branches": [ { "branches": [ { "branches": [ { "category": "product_version", "name": "1763-L16DWD", "product": { "name": "MicroLogix 1100 controllers: 1763-L16DWD", "product_id": "CSAFPID-0001" } } ], "category": "product_name", "name": "MicroLogix 1100 controllers" }, { "branches": [ { "category": "product_version", "name": "1763-L16BWA", "product": { "name": "MicroLogix 1100 controllers: 1763-L16BWA", "product_id": "CSAFPID-0002" } } ], "category": "product_name", "name": "MicroLogix 1100 controllers" }, { "branches": [ { "category": "product_version", "name": "1763-L16AWA", "product": { "name": "MicroLogix 1100 controllers: 1763-L16AWA", "product_id": "CSAFPID-0003" } } ], "category": "product_name", "name": "MicroLogix 1100 controllers" }, { "branches": [ { "category": "product_version", "name": "1763-L16BBB", "product": { "name": "MicroLogix 1100 controllers: 1763-L16BBB", "product_id": "CSAFPID-0004" } } ], "category": "product_name", "name": "MicroLogix 1100 controllers" } ], "category": "vendor", "name": "Rockwell Automation" } ] }, "vulnerabilities": [ { "cve": "CVE-2017-7924", "cwe": { "id": "CWE-20", "name": "Improper Input Validation" }, "notes": [ { "category": "summary", "text": "A remote, unauthenticated attacker could send a single, specially crafted Programmable Controller Communication Commands (PCCC) packet to the controller that could potentially cause the controller to enter a DoS condition.CVE-2017-7924 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2017-7924" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H" } ], "remediations": [ { "category": "vendor_fix", "details": "Rockwell Automation recommends updating to the latest firmware revision of MicroLogix 1100 controllers, Version FRN 16.0 or later.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004" ], "url": "http://compatibility.rockwellautomation.com/Pages/MultiProductDownload.aspx?Keyword=1763&crumb=112" }, { "category": "mitigation", "details": "For more information on this vulnerability and more detailed mitigation instructions, please see Rockwell Automation's advisory.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004" ], "url": "https://rockwellautomation.custhelp.com/app/answers/detail/a_id/1047342" }, { "category": "mitigation", "details": "Reference Rockwell Automation's security page.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004" ], "url": "http://www.rockwellautomation.com/security/overview.page" } ], "scores": [ { "cvss_v3": { "baseScore": 7.5, "baseSeverity": "HIGH", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004" ] } ] } ] }