{ "document": { "acknowledgments": [ { "names": [ "Ilya Karpov", "Dmitry Sklyarov" ], "organization": "Positive Technologies", "summary": "reporting this vulnerability to Siemens" } ], "category": "csaf_security_advisory", "csaf_version": "2.0", "distribution": { "text": "Disclosure is not limited", "tlp": { "label": "WHITE" } }, "lang": "en-US", "notes": [ { "category": "general", "text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov", "title": "CISA Disclaimer" }, { "category": "summary", "text": "Ilya Karpov and Dmitry Sklyarov from Positive Technologies reported this vulnerability to Siemens.", "title": "Summary" }, { "category": "other", "text": "No known public exploits specifically target this vulnerability.", "title": "Exploitability" } ], "publisher": { "category": "coordinator", "contact_details": "CISAservicedesk@cisa.dhs.gov", "name": "CISA", "namespace": "https://www.cisa.gov/" }, "references": [ { "category": "self", "summary": "ICS Advisory ICSA-18-067-02 JSON", "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2018/icsa-18-067-02.json" }, { "category": "self", "summary": "ICS Advisory ICSA-18-067-02 Web Version", "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-18-067-02" } ], "title": "ICSA-18-067-02_Siemens SIPROTEC 4, SIPROTEC Compact, and Reyrolle Devices using the EN100 Ethernet Communication Module Extension (Update B)", "tracking": { "current_release_date": "2019-02-12T00:00:00.000000Z", "generator": { "date": "2023-01-12T22:19:38.656Z", "engine": { "name": "Secvisogram", "version": "2.0.0" } }, "id": "ICSA-18-067-02", "initial_release_date": "2018-03-08T00:00:00.000000Z", "revision_history": [ { "date": "2018-03-08T00:00:00.000000Z", "legacy_version": "Initial", "number": "1", "summary": "ICSA-18-067-02 Siemens SIPROTEC 4, SIPROTEC Compact, and Reyrolle Devices using the EN100 Ethernet Communication Module Extension" }, { "date": "2018-04-19T00:00:00.000000Z", "legacy_version": "A", "number": "2", "summary": "ICSA-18-067-02 Siemens SIPROTEC 4, SIPROTEC Compact, and Reyrolle devices using the EN100 Ethernet communication module extension (Update A)" }, { "date": "2019-02-12T00:00:00.000000Z", "legacy_version": "B", "number": "3", "summary": "ICSA-18-067-02 Siemens SIPROTEC 4, SIPROTEC Compact, and Reyrolle devices using the EN100 Ethernet communication module extension (Update B)" } ], "status": "final", "version": "3" } }, "product_tree": { "branches": [ { "branches": [ { "branches": [ { "category": "product_version_range", "name": "< 1.04", "product": { "name": "EN100 Ethernet module DNP3 variant: All versions prior to v1.04", "product_id": "CSAFPID-0001" } } ], "category": "product_name", "name": "EN100 Ethernet module DNP3 variant" }, { "branches": [ { "category": "product_version_range", "name": "< 4.30", "product": { "name": "EN100 Ethernet module IEC 61850 variant: All versions prior to V4.30", "product_id": "CSAFPID-0002" } } ], "category": "product_name", "name": "EN100 Ethernet module IEC 61850 variant" }, { "branches": [ { "category": "product_version", "name": "vers:all/*", "product": { "name": "EN100 Ethernet module Modbus TCP variant: All versions", "product_id": "CSAFPID-0003" } } ], "category": "product_name", "name": "EN100 Ethernet module Modbus TCP variant" }, { "branches": [ { "category": "product_version", "name": "vers:all/*", "product": { "name": "EN100 Ethernet module PROFINET IO variant: All versions", "product_id": "CSAFPID-0004" } } ], "category": "product_name", "name": "EN100 Ethernet module PROFINET IO variant" }, { "branches": [ { "category": "product_version_range", "name": "< 1.22", "product": { "name": "EN100 Ethernet module IEC 104 variant: All versions prior to v1.22", "product_id": "CSAFPID-0005" } } ], "category": "product_name", "name": "EN100 Ethernet module IEC 104 variant" } ], "category": "vendor", "name": "Siemens" } ] }, "vulnerabilities": [ { "cve": "CVE-2018-4838", "cwe": { "id": "CWE-306", "name": "Missing Authentication for Critical Function" }, "notes": [ { "category": "summary", "text": "Successful exploitation of this vulnerability could allow an attacker to either upgrade or downgrade the firmware of the device, including downgrading to older versions with known vulnerabilities.CVE-2018-4838 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N)).", "title": "Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, "references": [ { "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N" } ], "remediations": [ { "category": "mitigation", "details": "For all other affected products, Siemens has identified the following specific workarounds and mitigations that users can apply to reduce the risk. As a general security measure Siemens strongly recommends to protect network access with appropriate mechanisms (e.g., firewalls, segmentation, VPN). It is advised to configure the environment according to Siemens ' operational guidelines in order to run the devices in a protected IT environment.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "EN100 Ethernet module DNP3 variant (All versions prior to v1.04): Update to v1.04 and configure maintenance password, which can be located here: https://support.industry.siemens.com/cs/us/en/ view/109745821", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ], "url": "https://support.industry.siemens.com/cs/us/en/%20view/109745821" }, { "category": "mitigation", "details": "EN100 Ethernet module IEC 61850 variant (All versions prior to v4.30): Update to v4.30, which can be located here: https://support.industry.siemens.com/cs/us/en/view/109745821", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ], "url": "https://support.industry.siemens.com/cs/us/en/view/109745821" }, { "category": "mitigation", "details": "EN100 Ethernet module IEC 104 variant: Update to v1.22, which can be located here: https://support.industry.siemens.com/cs/document/109745821", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ], "url": "https://support.industry.siemens.com/cs/document/109745821" } ], "scores": [ { "cvss_v3": { "baseScore": 7.5, "baseSeverity": "HIGH", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] } ], "title": "CVE-2018-4838" } ] }