{ "document": { "acknowledgments": [ { "organization": "Siemens ProductCERT", "summary": "reporting this vulnerability to CISA." }, { "names": [ "Gjoko 'LiquidWorm' Krstic" ], "organization": "Zero Science Lab (MK)", "summary": "for coordinating disclosure" } ], "category": "csaf_security_advisory", "csaf_version": "2.0", "distribution": { "text": "Disclosure is not limited", "tlp": { "label": "WHITE", "url": "https://us-cert.cisa.gov/tlp/" } }, "lang": "en", "notes": [ { "category": "general", "text": "As a general security measure Siemens strongly recommends to protect network access to affected products with appropriate mechanisms. It is advised to follow recommended security practices in order to run the devices in a protected IT environment.", "title": "Additional Resources" }, { "category": "legal_disclaimer", "text": "Siemens Security Advisories are subject to the terms and conditions contained in Siemens' underlying license terms or other applicable agreements previously agreed to with Siemens (hereinafter \"License Terms\"). To the extent applicable to information, software or documentation made available in or through a Siemens Security Advisory, the Terms of Use of Siemens' Global Website (https://www.siemens.com/terms_of_use, hereinafter \"Terms of Use\"), in particular Sections 8-10 of the Terms of Use, shall apply additionally. In case of conflicts, the License Terms shall prevail over the Terms of Use.", "title": "Terms of Use" }, { "category": "legal_disclaimer", "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.", "title": "Legal Notice" }, { "category": "other", "text": "This CISA CSAF advisory was converted from a Siemens ProductCERT's advisory.", "title": "Advisory Conversion Disclaimer" }, { "category": "other", "text": "Multiple", "title": "Critical infrastructure sectors" }, { "category": "other", "text": "Worldwide", "title": "Countries/areas deployed" }, { "category": "other", "text": "Germany", "title": "Company headquarters location" }, { "category": "general", "text": "CISA recommends users take defensive measures to minimize the exploitation risk of this vulnerability.", "title": "Recommended Practices" }, { "category": "general", "text": "Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the internet.", "title": "Recommended Practices" }, { "category": "general", "text": "Locate control system networks and remote devices behind firewalls and isolate them from business networks.", "title": "Recommended Practices" }, { "category": "general", "text": "When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most recent version available. Also recognize VPN is only as secure as its connected devices.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.", "title": "Recommended Practices" } ], "publisher": { "category": "other", "contact_details": "central@cisa.dhs.gov", "name": "CISA", "namespace": "https://www.cisa.gov/" }, "references": [ { "category": "self", "summary": "SSA-898181: Desigo PX Web Remote Denial of Service Vulnerability - HTML Version", "url": "https://cert-portal.siemens.com/productcert/html/ssa-898181.html" }, { "category": "self", "summary": "ICS Advisory ICSA-19-318-03 JSON", "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2019/icsa-19-318-03.json" }, { "category": "self", "summary": "ICS Advisory ICSA-19-318-03 - Web Version", "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-19-318-03" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/resources-tools/resources/ics-recommended-practices" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/topics/industrial-control-systems" }, { "category": "external", "summary": "Recommended Practices", "url": "https://us-cert.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/sites/default/files/publications/Cybersecurity_Best_Practices_for_Industrial_Control_Systems.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ics/tips/ICS-TIP-12-146-01B" } ], "title": "Siemens Desigo PX Devices", "tracking": { "current_release_date": "2019-11-12T00:00:00.000000Z", "generator": { "engine": { "name": "CISA CSAF Generator", "version": "1.0.0" } }, "id": "ICSA-19-318-03", "initial_release_date": "2019-11-12T00:00:00.000000Z", "revision_history": [ { "date": "2019-11-12T00:00:00.000000Z", "legacy_version": "1.0", "number": "1", "summary": "Publication Date" } ], "status": "final", "version": "1" } }, "product_tree": { "branches": [ { "branches": [ { "branches": [ { "category": "product_version", "name": "PXC50-E.D", "product": { "name": "Siemens Desigo PX automation controllers PXC00-E.D PXC50-E.D", "product_id": "CSAFPID-0001" } } ], "category": "product_name", "name": "Desigo PX automation controllers PXC00-E.D" }, { "branches": [ { "category": "product_version", "name": "PXC64-U", "product": { "name": "Siemens Desigo PX automation controllers PXC00-U PXC64-U", "product_id": "CSAFPID-0002" } } ], "category": "product_name", "name": "Desigo PX automation controllers PXC00-U" }, { "branches": [ { "category": "product_version", "name": "PXC36-E.D", "product": { "name": "Siemens Desigo PX automation controllers PXC22.1-E.D PXC36-E.D", "product_id": "CSAFPID-0003" } } ], "category": "product_name", "name": "Desigo PX automation controllers PXC22.1-E.D" } ], "category": "vendor", "name": "Siemens" } ] }, "vulnerabilities": [ { "cve": "CVE-2019-13927", "cwe": { "id": "CWE-472", "name": "External Control of Assumed-Immutable Web Parameter" }, "notes": [ { "category": "summary", "text": "The device contains a vulnerability that could allow an attacker to cause a denial of service condition on the device's web server by sending a specially crafted HTTP message to the web server port (tcp/80). The security vulnerability could be exploited by an attacker with network access to an affected device. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise the availability of the device's web service. While the device itself stays operational, the web server responds with HTTP status code 404 (Not found) to any further request. A reboot is required to recover the web interface. At the time of advisory publication no public exploitation of this security vulnerability was known.", "title": "Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, "remediations": [ { "category": "mitigation", "details": "Ensure that the PX Web interface is only accessible from trusted networks.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "vendor_fix", "details": "Install V6.00.320 or a later version. https://support.industry.siemens.com/cs/document/109772802", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] } ], "scores": [ { "cvss_v3": { "baseScore": 5.3, "baseSeverity": "MEDIUM", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L/E:H/RL:O/RC:C", "version": "3.1" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] } ], "title": "CVE-2019-13927" } ] }