{ "document": { "acknowledgments": [ { "names": [ "Jin Kyung Lee", "Yeop Chang" ], "organization": "NSR (National Security Research Institute)", "summary": "reporting this vulnerability to CISA" } ], "category": "csaf_security_advisory", "csaf_version": "2.0", "distribution": { "text": "Disclosure is not limited", "tlp": { "label": "WHITE", "url": "https://us-cert.cisa.gov/tlp/" } }, "lang": "en-US", "notes": [ { "category": "general", "text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov", "title": "CISA Disclaimer" }, { "category": "legal_disclaimer", "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.", "title": "Legal Notice" }, { "category": "summary", "text": "Successful exploitation of this vulnerability could cause the system to change to halt-mode, resulting in a denial-of-service condition.", "title": "Risk evaluation" }, { "category": "other", "text": "Commercial Facilities, Critical Manufacturing, Dams, Defense Industrial Base, Energy, Food and Agricultural, Government Facilities, Information Technology, Transportation Systems, Water and Wastewater Systems", "title": "Critical infrastructure sectors" }, { "category": "other", "text": "Worldwide", "title": "Countries/areas deployed" }, { "category": "other", "text": "United States", "title": "Company headquarters location" }, { "category": "general", "text": "CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:", "title": "Recommended Practices" }, { "category": "general", "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.\nCISA also provides a section for control systems security recommended practices on the ICS webpage onus-cert.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.\nOrganizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.", "title": "Recommended Practices" }, { "category": "other", "text": "No known public exploits specifically target this vulnerability.", "title": "Exploitability" } ], "publisher": { "category": "coordinator", "contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870", "name": "CISA", "namespace": "https://www.cisa.gov/" }, "references": [ { "category": "self", "summary": "ICS Advisory ICSA-20-014-01 JSON", "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2020/icsa-20-014-01.json" }, { "category": "self", "summary": "ICS Advisory ICSA-20-014-01 Web Version", "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-20-014-01" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.us-cert.gov/ics/alerts/ICS-ALERT-10-301-01" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.us-cert.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.us-cert.gov/ics/tips/ICS-TIP-12-146-01B" } ], "title": "GE PACSystems RX3i", "tracking": { "current_release_date": "2020-01-14T00:00:00.000000Z", "generator": { "engine": { "name": "CISA CSAF Generator", "version": "1.0.0" } }, "id": "ICSA-20-014-01", "initial_release_date": "2020-01-14T00:00:00.000000Z", "revision_history": [ { "date": "2020-01-14T00:00:00.000000Z", "legacy_version": "Initial", "number": "1", "summary": "ICSA-20-014-01 GE PACSystems RX3i" } ], "status": "final", "version": "1" } }, "product_tree": { "branches": [ { "branches": [ { "branches": [ { "category": "product_version_range", "name": "< R9.90", "product": { "name": "CPE310: All versions prior to R9.90", "product_id": "CSAFPID-0001" } } ], "category": "product_name", "name": "CPE310" }, { "branches": [ { "category": "product_version_range", "name": "< R9.85", "product": { "name": "CPE100: All versions prior to R9.85", "product_id": "CSAFPID-0002" } } ], "category": "product_name", "name": "CPE100" }, { "branches": [ { "category": "product_version_range", "name": "< R9.90", "product": { "name": "CPE305: All versions prior to R9.90", "product_id": "CSAFPID-0003" } } ], "category": "product_name", "name": "CPE305" }, { "branches": [ { "category": "product_version_range", "name": "< R9.90", "product": { "name": "CPL410: All versions prior to R9.90", "product_id": "CSAFPID-0004" } } ], "category": "product_name", "name": "CPL410" }, { "branches": [ { "category": "product_version", "name": "vers:all/*", "product": { "name": "CRU320: (End of Life; Upgrade to CPE330)", "product_id": "CSAFPID-0005" } } ], "category": "product_name", "name": "CRU320" }, { "branches": [ { "category": "product_version_range", "name": "< R9.85", "product": { "name": "CPE115: All versions prior to R9.85", "product_id": "CSAFPID-0006" } } ], "category": "product_name", "name": "CPE115" }, { "branches": [ { "category": "product_version_range", "name": "< R9.90", "product": { "name": "CPE330: All versions prior to R9.90", "product_id": "CSAFPID-0007" } } ], "category": "product_name", "name": "CPE330" }, { "branches": [ { "category": "product_version_range", "name": "< R9.90", "product": { "name": "CPE400: All versions prior to R9.90", "product_id": "CSAFPID-0008" } } ], "category": "product_name", "name": "CPE400" }, { "branches": [ { "category": "product_version_range", "name": "< R9.90", "product": { "name": "CPE302: All versions prior to R9.90", "product_id": "CSAFPID-0009" } } ], "category": "product_name", "name": "CPE302" } ], "category": "vendor", "name": "General Electric (GE) and Emerson" } ] }, "vulnerabilities": [ { "cve": "CVE-2019-13524", "cwe": { "id": "CWE-20", "name": "Improper Input Validation" }, "notes": [ { "category": "summary", "text": "Sending specially manipulated packets can cause the module state to change to halt-mode, resulting in a denial-of-service condition. An operator must reboot the CPU module after removing battery or energy pack to recover from halt-mode.CVE-2019-13524 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008", "CSAFPID-0009" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2019-13524" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H" } ], "remediations": [ { "category": "vendor_fix", "details": "Emerson has acquired the affected products from GE. All inquiries should be directed to Emerson:1-888-565-4155;1-434-214-8532 (if toll free 800 option is unavailable);Tech Support:support.mas@emerson.com,mailto:support.mas@emerson.com;Sales/Order Support: customercare.mas@emerson.com,mailto:customercare.mas@emerson.com;',empty\nicsa-20-014-01.json,vendor_fix,Version R9.85 CPE100 - Upgrade Kit: 41G2393-MS10-000-A5.zip,https://digitalsupport.ge.com/en_US/Article/EPSCPE100-Landing-Page\nicsa-20-014-01.json,vendor_fix,Version R9.85 CPE115 - Upgrade Kit: 41G2556-MS10-000-A2.zip,https://digitalsupport.ge.com/en_US/Article/EPSCPE115-Landing-Page\nicsa-20-014-01.json,vendor_fix,Version R9.90 CPE302 - Upgrade Kit: CPE302_FW9_90_41G2552-FW01-000-A3.zip,https://digitalsupport.ge.com/communities/en_US/Download/IC695CPE302-PACSystems-RX3i-CPU-Firmware\nicsa-20-014-01.json,vendor_fix,Version R9.90 CPE305 - Upgrade Kit: CPE305_FW9_90_41G1733-MS10-000-A20.zip,https://digitalsupport.ge.com/communities/en_US/Download/IC695CPE305-PACSystems-RX3i-CPU-DN\nicsa-20-014-01.json,vendor_fix,Version R9.90 CPE310 - Upgrade Kit: CPE310_FW9_90_41G1734-MS10-000-A20.zip,https://digitalsupport.ge.com/communities/en_US/Download/IC695CPE310-PACSystems-RX3i-CPU-DN\nicsa-20-014-01.json,vendor_fix,Version R9.90 CPE330 - Upgrade Kit: CPE330_FW9_90_41G2016-FW01-000-A16.zip,https://digitalsupport.ge.com/communities/en_US/Download/IC695CPE330-PACSystems-RX3i-CPU-DN\nicsa-20-014-01.json,vendor_fix,Version R9.90 CPE400 - Upgrade Kit: CPE400_FW9_90_41G2376-FW01-000-A7.zip,https://digitalsupport.ge.com/communities/en_US/Download/IC695CPE400-PACSystems-RX3i-Rackless-CPU-with-Field-Agent\nicsa-20-014-01.json,vendor_fix,Version R9.90 CPL410 - Upgrade Kit: CPL410_FW9_90_41G2617-FW01-000-A3.zip,https://digitalsupport.ge.com/communities/en_US/Download/IC695CPL410-PACSystems-RX3i-Rackless-CPU-with-Linux\nicsa-20-014-01.json,vendor_fix,Emerson notes that CPU/CRU320 has reached end of life. They recommend users upgrade to CPE330.,empty\nicsa-22-265-01.json,vendor_fix,Measuresoft recommends the following steps to remove full access to the ORCHESTRATOR service:,empty\nicsa-22-265-01.json,vendor_fix,Open a command-line window (CMD) with 'run as administrator',empty\nicsa-22-265-01.json,vendor_fix,Use the following command to make the permission change to the ORCHESTRATOR service: sc sdset ORCHESTRATOR D:(A;;CCLCSWRPWPDTLOCRRC;;;SY)(A;;CCDCLCSWRPWPDTLOCRSDRCWDWO;;;BA)(A;;CCLCSWLOCRRC;;;IU)(A;;CCLCSWLOCRRC;;;SU),empty\nicsa-22-265-01.json,vendor_fix,As a low-level user attempt to shut down the ORCHESTRATOR service: sc stop ORCHESTRATOR. User will be denied. It will no longer be possible to edit the configuration of the service by a low-level user.'", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008", "CSAFPID-0009" ] } ], "scores": [ { "cvss_v3": { "baseScore": 7.5, "baseSeverity": "HIGH", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008", "CSAFPID-0009" ] } ] } ] }