{ "document": { "acknowledgments": [ { "names": [ "Vera Mens" ], "organization": "Claroty Research", "summary": "reporting these vulnerabilities to CISA" } ], "category": "csaf_security_advisory", "csaf_version": "2.0", "distribution": { "text": "Disclosure is not limited", "tlp": { "label": "WHITE", "url": "https://us-cert.cisa.gov/tlp/" } }, "lang": "en-US", "notes": [ { "category": "general", "text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov", "title": "CISA Disclaimer" }, { "category": "legal_disclaimer", "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.", "title": "Legal Notice" }, { "category": "summary", "text": "Successful exploitation of these vulnerabilities could crash the device being accessed, and buffer overflow conditions could allow remote code execution.", "title": "Risk evaluation" }, { "category": "other", "text": "Energy", "title": "Critical infrastructure sectors" }, { "category": "other", "text": "Worldwide", "title": "Countries/areas deployed" }, { "category": "other", "text": "Germany", "title": "Company headquarters location" }, { "category": "general", "text": "CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability these vulnerabilities. Specifically, users should:", "title": "Recommended Practices" }, { "category": "general", "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA also provides a section for control systems security recommended practices on the ICS webpage at cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.", "title": "Recommended Practices" }, { "category": "general", "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.", "title": "Recommended Practices" } ], "publisher": { "category": "coordinator", "contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870", "name": "CISA", "namespace": "https://www.cisa.gov/" }, "references": [ { "category": "self", "summary": "ICS Advisory ICSA-22-251-01 JSON", "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2022/icsa-22-251-01.json" }, { "category": "self", "summary": "ICS Advisory ICSA-22-251-01 Web Version", "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-22-251-01" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-22-251-01" }, { "category": "external", "summary": "Recommended Practices", "url": "https://us-cert.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf" } ], "title": "MZ Automation libIEC61850", "tracking": { "current_release_date": "2022-09-08T00:00:00.000000Z", "generator": { "engine": { "name": "CISA CSAF Generator", "version": "1.0.0" } }, "id": "ICSA-22-251-01", "initial_release_date": "2022-09-08T00:00:00.000000Z", "revision_history": [ { "date": "2022-09-08T00:00:00.000000Z", "legacy_version": "Initial", "number": "1", "summary": "Publication Date" } ], "status": "final", "version": "1" } }, "product_tree": { "branches": [ { "branches": [ { "branches": [ { "category": "product_version_range", "name": ">= 1.5 | <= a3b04b7bc4872a5a39e5de3fdc5fbde52c09e10e", "product": { "name": "libIEC61850: Version 1.5 prior to commit a3b04b7bc4872a5a39e5de3fdc5fbde52c09e10e", "product_id": "CSAFPID-0001" } } ], "category": "product_name", "name": "libIEC61850" }, { "branches": [ { "category": "product_version_range", "name": "<= 1.4", "product": { "name": "libIEC61850: Versions 1.4 and prior", "product_id": "CSAFPID-0002" } } ], "category": "product_name", "name": "libIEC61850" } ], "category": "vendor", "name": "MZ Automation GmbH" } ] }, "vulnerabilities": [ { "cve": "CVE-2022-2970", "cwe": { "id": "CWE-121", "name": "Stack-based Buffer Overflow" }, "notes": [ { "category": "summary", "text": "The affected product does not sanitize input before memcpy is used, which could allow an attacker to crash the device or remotely execute arbitrary code.CVE-2022-2970 has been assigned to this vulnerability. A CVSS v3 base score of 10.0 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-2970" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H" } ], "remediations": [ { "category": "vendor_fix", "details": "MZ Automation recommends users update to the latest version: libIEC61850.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002" ], "url": "https://github.com/mz-automation/libiec61850" } ], "scores": [ { "cvss_v3": { "baseScore": 10.0, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002" ] } ] }, { "cve": "CVE-2022-2972", "cwe": { "id": "CWE-121", "name": "Stack-based Buffer Overflow" }, "notes": [ { "category": "summary", "text": "The affected product is vulnerable to a stack-based buffer overflow, which could allow an attacker to crash the device or remotely execute arbitrary code. 3.2.3 ACCESS OF RESOURCE USING INCOMPATIBLE TYPE ('TYPE CONFUSION') CWE 843. The affected product accesses a resource using an incompatible type, which could allow an attacker to crash the server with a malicious payload.CVE-2022-2972 has been assigned to this vulnerability. A CVSS v3 base score of 10.0 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-2972" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H" } ], "remediations": [ { "category": "vendor_fix", "details": "MZ Automation recommends users update to the latest version: libIEC61850.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002" ], "url": "https://github.com/mz-automation/libiec61850" } ], "scores": [ { "cvss_v3": { "baseScore": 8.6, "baseSeverity": "HIGH", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002" ] } ] }, { "cve": "CVE-2022-2973", "cwe": { "id": "CWE-476", "name": "NULL Pointer Dereference" }, "notes": [ { "category": "summary", "text": "The affected product uses a NULL pointer in certain situations. which could allow an attacker to crash the server.CVE-2022-2973 has been assigned to this vulnerability. A CVSS v3 base score of 8.6 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-2973" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H" } ], "remediations": [ { "category": "vendor_fix", "details": "MZ Automation recommends users update to the latest version: libIEC61850.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002" ], "url": "https://github.com/mz-automation/libiec61850" } ], "scores": [ { "cvss_v3": { "baseScore": 8.6, "baseSeverity": "HIGH", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002" ] } ] } ] }