{ "document": { "acknowledgments": [ { "organization": "Siemens ProductCERT", "summary": "reporting these vulnerabilities to CISA." }, { "names": [ "Eran Jacob" ], "organization": "OTORIO", "summary": "coordinating disclosure" } ], "category": "csaf_security_advisory", "csaf_version": "2.0", "distribution": { "text": "Disclosure is not limited", "tlp": { "label": "WHITE", "url": "https://us-cert.cisa.gov/tlp/" } }, "notes": [ { "category": "summary", "text": "Siemens Automation License Manager contains two vulnerabilities which, when combined, could allow an attacker to modify and rename license files, extract licenses and overwrite arbitrary files on the target system potentially leading to privilege escalation and remote code execution. The affected functionality is not available for remote attackers in the default configuration since version V6.0 SP2 of Automation License Manager.\n\nSiemens has released an update for Automation License Manager V6 and recommends to update to the latest version. Siemens recommends specific countermeasures for products where updates are not, or not yet available.", "title": "Summary" }, { "category": "general", "text": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens' operational guidelines for Industrial Security (Download: \nhttps://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\nAdditional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity", "title": "General Recommendations" }, { "category": "general", "text": "For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories", "title": "Additional Resources" }, { "category": "legal_disclaimer", "text": "Siemens Security Advisories are subject to the terms and conditions contained in Siemens' underlying license terms or other applicable agreements previously agreed to with Siemens (hereinafter \"License Terms\"). To the extent applicable to information, software or documentation made available in or through a Siemens Security Advisory, the Terms of Use of Siemens' Global Website (https://www.siemens.com/terms_of_use, hereinafter \"Terms of Use\"), in particular Sections 8-10 of the Terms of Use, shall apply additionally. In case of conflicts, the License Terms shall prevail over the Terms of Use.", "title": "Terms of Use" }, { "category": "legal_disclaimer", "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.", "title": "Legal Notice" }, { "category": "other", "text": "This CISA CSAF advisory was converted from Siemens ProductCERT's CSAF advisory.", "title": "Advisory Conversion Disclaimer" }, { "category": "other", "text": "Multiple", "title": "Critical infrastructure sectors" }, { "category": "other", "text": "Worldwide", "title": "Countries/areas deployed" }, { "category": "other", "text": "Germany", "title": "Company headquarters location" }, { "category": "general", "text": "CISA recommends users take defensive measures to minimize the exploitation risk of this vulnerability.", "title": "Recommended Practices" }, { "category": "general", "text": "Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the internet.", "title": "Recommended Practices" }, { "category": "general", "text": "Locate control system networks and remote devices behind firewalls and isolate them from business networks.", "title": "Recommended Practices" }, { "category": "general", "text": "When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most recent version available. Also recognize VPN is only as secure as its connected devices.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.", "title": "Recommended Practices" } ], "publisher": { "category": "other", "contact_details": "central@cisa.dhs.gov", "name": "CISA", "namespace": "https://www.cisa.gov/" }, "references": [ { "category": "self", "summary": "SSA-476715: Two Vulnerabilities in Automation License Manager - CSAF Version", "url": "https://cert-portal.siemens.com/productcert/csaf/ssa-476715.json" }, { "category": "self", "summary": "SSA-476715: Two Vulnerabilities in Automation License Manager - TXT Version", "url": "https://cert-portal.siemens.com/productcert/txt/ssa-476715.txt" }, { "category": "self", "summary": "SSA-476715: Two Vulnerabilities in Automation License Manager - PDF Version", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-476715.pdf" }, { "category": "self", "summary": "ICS Advisory ICSA-23-012-10 JSON", "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2023/icsa-23-012-10.json" }, { "category": "self", "summary": "ICS Advisory ICSA-23-012-10 - Web Version", "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-23-012-10" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/resources-tools/resources/ics-recommended-practices" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/topics/industrial-control-systems" }, { "category": "external", "summary": "Recommended Practices", "url": "https://us-cert.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/sites/default/files/publications/Cybersecurity_Best_Practices_for_Industrial_Control_Systems.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ics/tips/ICS-TIP-12-146-01B" } ], "title": "Siemens Automation License Manager", "tracking": { "current_release_date": "2023-03-14T00:00:00.000000Z", "generator": { "engine": { "name": "CISA CSAF Generator", "version": "1.0.0" } }, "id": "ICSA-23-012-10", "initial_release_date": "2023-01-10T00:00:00.000000Z", "revision_history": [ { "date": "2023-01-10T00:00:00.000000Z", "legacy_version": "1.0", "number": "1", "summary": "Publication Date" }, { "date": "2023-03-14T00:00:00.000000Z", "legacy_version": "1.1", "number": "2", "summary": "Updated workarounds and mitigations; clarified, that the affected functionality is not available for remote attackers in the default configuration" } ], "status": "final", "version": "2" } }, "product_tree": { "branches": [ { "branches": [ { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "Automation License Manager V5", "product_id": "CSAFPID-0001" } } ], "category": "product_name", "name": "Automation License Manager V5" }, { "branches": [ { "category": "product_version_range", "name": "<V6.0_SP9_Upd4", "product": { "name": "Automation License Manager V6", "product_id": "CSAFPID-0002" } } ], "category": "product_name", "name": "Automation License Manager V6" } ], "category": "vendor", "name": "Siemens" } ] }, "vulnerabilities": [ { "cve": "CVE-2022-43513", "cwe": { "id": "CWE-73", "name": "External Control of File Name or Path" }, "notes": [ { "category": "summary", "text": "The affected components allow to rename license files with user chosen input without authentication.\r\nThis could allow an unauthenticated remote attacker to rename and move files as SYSTEM user.", "title": "Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002" ] }, "remediations": [ { "category": "mitigation", "details": "If no remote connections are needed, disable \u201cAllow Remote Connections\u201d on the Automation License Manager settings menu (default since version V6.0 SP2)", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002" ] }, { "category": "no_fix_planned", "details": "Currently no fix is planned", "product_ids": [ "CSAFPID-0001" ] }, { "category": "vendor_fix", "details": "Update to V6.0 SP9 Upd4 or later version", "product_ids": [ "CSAFPID-0002" ], "url": "https://support.industry.siemens.com/cs/ww/en/view/114358/" }, { "category": "workaround", "details": "If remote connections are needed, limit remote access to port 4410/tcp to trusted systems only", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002" ] } ], "scores": [ { "cvss_v3": { "baseScore": 8.2, "baseSeverity": "HIGH", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:L/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "CSAFPID-0001", "CSAFPID-0002" ] } ], "title": "CVE-2022-43513" }, { "cve": "CVE-2022-43514", "cwe": { "id": "CWE-22", "name": "Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal')" }, "notes": [ { "category": "summary", "text": "The affected component does not correctly validate the root path on folder related operations, allowing to modify files and folders outside the intended root directory.\r\nThis could allow an unauthenticated remote attacker to execute file operations of files outside of the specified root folder. Chained with CVE-2022-43513 this could allow Remote Code Execution.", "title": "Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002" ] }, "remediations": [ { "category": "mitigation", "details": "If no remote connections are needed, disable \u201cAllow Remote Connections\u201d on the Automation License Manager settings menu (default since version V6.0 SP2)", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002" ] }, { "category": "no_fix_planned", "details": "Currently no fix is planned", "product_ids": [ "CSAFPID-0001" ] }, { "category": "vendor_fix", "details": "Update to V6.0 SP9 Upd4 or later version", "product_ids": [ "CSAFPID-0002" ], "url": "https://support.industry.siemens.com/cs/ww/en/view/114358/" }, { "category": "workaround", "details": "If remote connections are needed, limit remote access to port 4410/tcp to trusted systems only", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002" ] } ], "scores": [ { "cvss_v3": { "baseScore": 7.7, "baseSeverity": "HIGH", "vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:L/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "CSAFPID-0001", "CSAFPID-0002" ] } ], "title": "CVE-2022-43514" } ] }