{ "document": { "acknowledgments": [ { "names": [ "Roman Ezhov" ], "organization": "Kaspersky", "summary": "reporting this vulnerability to Yokogawa" } ], "category": "csaf_security_advisory", "csaf_version": "2.0", "distribution": { "text": "Disclosure is not limited", "tlp": { "label": "WHITE", "url": "https://us-cert.cisa.gov/tlp/" } }, "lang": "en-US", "notes": [ { "category": "legal_disclaimer", "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.", "title": "Legal Notice" }, { "category": "summary", "text": "Successful exploitation of this vulnerability could allow a remote attacker to cause a denial-of-service condition to the FCN/FCJ controller by sending a specially crafted packet. ", "title": "Risk evaluation" }, { "category": "other", "text": "Multiple", "title": "Critical infrastructure sectors" }, { "category": "other", "text": "Worldwide", "title": "Countries/areas deployed" }, { "category": "other", "text": "Japan", "title": "Company headquarters location" }, { "category": "general", "text": "CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:", "title": "Recommended Practices" }, { "category": "general", "text": "Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.", "title": "Recommended Practices" }, { "category": "general", "text": "Locate control system networks and remote devices behind firewalls and isolating them from business networks.", "title": "Recommended Practices" }, { "category": "general", "text": "When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.", "title": "Recommended Practices" }, { "category": "general", "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.", "title": "Recommended Practices" }, { "category": "general", "text": "No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.", "title": "Recommended Practices" } ], "publisher": { "category": "coordinator", "contact_details": "central@cisa.dhs.gov", "name": "CISA", "namespace": "https://www.cisa.gov/" }, "references": [ { "category": "self", "summary": "ICS Advisory ICSA-23-334-02 JSON", "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2023/icsa-23-334-02.json" }, { "category": "self", "summary": "ICSA Advisory ICSA-23-334-02 - Web Version", "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-23-334-02" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/resources-tools/resources/ics-recommended-practices" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/sites/default/files/publications/Cybersecurity_Best_Practices_for_Industrial_Control_Systems.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/topics/industrial-control-systems" }, { "category": "external", "summary": "Recommended Practices", "url": "https://us-cert.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ics/tips/ICS-TIP-12-146-01B" } ], "title": "Yokogawa STARDOM", "tracking": { "current_release_date": "2023-11-30T07:00:00.000000Z", "generator": { "engine": { "name": "CISA CSAF Generator", "version": "1.0.0" } }, "id": "ICSA-23-334-02", "initial_release_date": "2023-11-30T07:00:00.000000Z", "revision_history": [ { "date": "2023-11-30T07:00:00.000000Z", "legacy_version": "Initial", "number": "1", "summary": "Initial Publication" } ], "status": "final", "version": "1" } }, "product_tree": { "branches": [ { "branches": [ { "branches": [ { "category": "product_version_range", "name": ">=R1.01|<=R4.31", "product": { "name": "STARDOM FCN/FCJ: >=R1.01|<=R4.31", "product_id": "CSAFPID-0001" } } ], "category": "product_name", "name": "STARDOM FCN/FCJ" } ], "category": "vendor", "name": "Yokogawa" } ] }, "vulnerabilities": [ { "cve": "CVE-2023-5915", "cwe": { "id": "CWE-400", "name": "Uncontrolled Resource Consumption" }, "notes": [ { "category": "summary", "text": "This vulnerability may allow to a remote attacker to cause a denial-of-service condition to the FCN/FCJ controller by sending a crafted packet. While sending the packet, the maintenance homepage of the controller could not be accessed. Therefore, functions of the maintenance homepage, changing configuration, viewing logs, etc. are not available. But the controller's operation is not stopped by the condition.", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2023-5915" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L" } ], "remediations": [ { "category": "mitigation", "details": "Yokogawa has released the following mitigations for users to implement:", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "By using the packet filter function of the FCN/FCJ controller, only allow connection from trusted hosts. Revision up FCN/FCJ basic software to R4.20 or later for using the function.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Take measures against the network so that an attacker cannot send a malicious packet", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Yokogawa strongly recommends all customers to establish and maintain a full security program, not only for the vulnerability identified in this YSAR. Security program components are: Patch updates, Anti-virus, Backup and recovery, zoning, hardening, whitelisting, firewall, etc. Yokogawa can assist in setting up and running the security program continuously. For considering the most effective risk mitigation plan, as a starting point, Yokogawa can perform a security risk assessment.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "More details can also be found in Yokogawa's security advisory report number YSAR-23-0003.", "product_ids": [ "CSAFPID-0001" ], "url": "https://web-material3.yokogawa.com/1/29820/files/YSAR-23-0003.pdf" } ], "scores": [ { "cvss_v3": { "baseScore": 5.3, "baseSeverity": "MEDIUM", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L", "version": "3.1" }, "products": [ "CSAFPID-0001" ] } ] } ] }