  "document": {
    "acknowledgments": [
      {
        "organization": "Rockwell Automation",
        "summary": "reporting this vulnerability to CISA"
      }
    ],
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Disclosure is not limited",
      "tlp": {
        "label": "WHITE",
        "url": "https://us-cert.cisa.gov/tlp/"
      }
    },
    "lang": "en-US",
    "notes": [
      {
        "category": "legal_disclaimer",
        "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.",
        "title": "Legal Notice"
      },
      {
        "category": "summary",
        "text": "Successful exploitation of this vulnerability could allow a local low-privileged user to escalate their privileges by changing the macro to execute arbitrary code.",
        "title": "Risk evaluation"
      },
      {
        "category": "other",
        "text": "Critical Manufacturing",
        "title": "Critical infrastructure sectors"
      },
      {
        "category": "other",
        "text": "Worldwide",
        "title": "Countries/areas deployed"
      },
      {
        "category": "other",
        "text": "United States",
        "title": "Company headquarters location"
      },
      {
        "category": "general",
        "text": "CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Locate control system networks and remote devices behind firewalls and isolating them from business networks.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "When remote access is required, use more secure methods, such as virtual private networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.",
        "title": "Recommended Practices"
      }
    ],
    "publisher": {
      "category": "coordinator",
      "contact_details": "central@cisa.dhs.gov",
      "name": "CISA",
      "namespace": "https://www.cisa.gov/"
    },
    "references": [
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-24-317-03 JSON",
        "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2024/icsa-24-317-03.json"
      },
      {
        "category": "self",
        "summary": "ICSA Advisory ICSA-24-317-03 - Web Version",
        "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-24-317-03"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/resources-tools/resources/ics-recommended-practices"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/sites/default/files/publications/Cybersecurity_Best_Practices_for_Industrial_Control_Systems.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/topics/industrial-control-systems"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://us-cert.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/ics/tips/ICS-TIP-12-146-01B"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/sites/default/files/publications/emailscams0905.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/ncas/tips/ST04-014"
      }
    ],
    "title": "Rockwell Automation FactoryTalk View ME",
    "tracking": {
      "current_release_date": "2024-11-12T07:00:00.000000Z",
      "generator": {
        "engine": {
          "name": "CISA CSAF Generator",
          "version": "1.0.0"
        }
      },
      "id": "ICSA-24-317-03",
      "initial_release_date": "2024-11-12T07:00:00.000000Z",
      "revision_history": [
        {
          "date": "2024-11-12T07:00:00.000000Z",
          "legacy_version": "Initial",
          "number": "1",
          "summary": "Initial Publication"
        }
      ],
      "status": "final",
      "version": "1"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "<=v14.0",
                "product": {
                  "name": "Rockwell Automation FactoryTalk View ME, when using default folder privileges: <=v14.0",
                  "product_id": "CSAFPID-0001"
                }
              }
            ],
            "category": "product_name",
            "name": "FactoryTalk View ME, when using default folder privileges"
          }
        ],
        "category": "vendor",
        "name": "Rockwell Automation"
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2024-37365",
      "cwe": {
        "id": "CWE-20",
        "name": "Improper Input Validation"
      },
      "notes": [
        {
          "category": "summary",
          "text": "A remote code execution vulnerability exists in FactoryTalk View ME. The vulnerability allows users to save projects within the public directory allowing anyone with local access to modify and/or delete files. Additionally, a malicious user could potentially leverage this vulnerability to escalate their privileges by changing the macro to execute arbitrary code. ",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "www.cve.org",
          "url": "https://www.cve.org/CVERecord?id=CVE-2024-37365"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:L/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:L/AC:L/AT:N/PR:L/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Rockwell Automation has corrected this problem in V15.0.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "Rockwell Automation encourages users of the affected software, who are not able to upgrade to one of the corrected versions, to apply the following risk mitigations where possible.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "To enhance security and help prevent unauthorized modifications to HMI project files, harden the Windows OS by removing the INTERACTIVE group from the folder's security properties.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "Add specific users or user groups and assign their permissions to this folder using the least privileges principle. Users with read-only permission can still test run and run the FactoryTalk View ME Station.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "Guidance can be found in FactoryTalk View ME v14 Help topic: \"HMI projects folder settings\". It can be opened through the FactoryTalk View ME Studio menu \"help\\Contents\\FactoryTalk View ME Help\\Create a Machine Edition application->Open applications->HMI project folder settings\".",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "Security Best Practices",
          "product_ids": [
            "CSAFPID-0001"
          ],
          "url": "https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight"
        },
        {
          "category": "mitigation",
          "details": "For more information, see Rockwell Automation's security advisory",
          "product_ids": [
            "CSAFPID-0001"
          ],
          "url": "https://www.rockwellautomation.com/en-us/trust-center/security-advisories.html"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 7.3,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-0001"
          ]
        }
      ]
    }
  ]
}