{ "document": { "acknowledgments": [ { "organization": "Rockwell Automation", "summary": "reported these vulnerabilities to CISA" } ], "category": "csaf_security_advisory", "csaf_version": "2.0", "distribution": { "text": "Disclosure is not limited", "tlp": { "label": "WHITE", "url": "https://www.cisa.gov/news-events/news/traffic-light-protocol-tlp-definitions-and-usage" } }, "lang": "en-US", "notes": [ { "category": "legal_disclaimer", "text": "This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy).", "title": "Legal Notice and Terms of Use" }, { "category": "summary", "text": "Successful exploitation of these vulnerabilities could allow an attacker to obtain a valid authentication token, perform a denial of service, or crash the system.", "title": "Advisory Summary" }, { "category": "other", "text": "Critical Manufacturing", "title": "Critical infrastructure sectors" }, { "category": "other", "text": "Worldwide", "title": "Countries/areas deployed" }, { "category": "other", "text": "United States", "title": "Company headquarters location" }, { "category": "general", "text": "CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities.", "title": "Recommended Practices" }, { "category": "general", "text": "Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.", "title": "Recommended Practices" }, { "category": "general", "text": "Locate control system networks and remote devices behind firewalls and isolating them from business networks.", "title": "Recommended Practices" }, { "category": "general", "text": "When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.", "title": "Recommended Practices" }, { "category": "general", "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA also recommends users take the following measures to protect themselves from social engineering attacks:", "title": "Recommended Practices" }, { "category": "general", "text": "Do not click web links or open attachments in unsolicited email messages.", "title": "Recommended Practices" }, { "category": "general", "text": "Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.", "title": "Recommended Practices" }, { "category": "general", "text": "Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.", "title": "Recommended Practices" }, { "category": "general", "text": "No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.", "title": "Recommended Practices" } ], "publisher": { "category": "coordinator", "contact_details": "central@cisa.dhs.gov", "name": "CISA", "namespace": "https://www.cisa.gov/" }, "references": [ { "category": "self", "summary": "ICS Advisory ICSA-26-169-03 JSON", "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2026/icsa-26-169-03.json" }, { "category": "self", "summary": "ICSA Advisory ICSA-26-169-03 - Web Version", "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-26-169-03" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/resources-tools/resources/ics-recommended-practices" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/sites/default/files/publications/Cybersecurity_Best_Practices_for_Industrial_Control_Systems.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/topics/industrial-control-systems" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/sites/default/files/publications/emailscams0905.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ncas/tips/ST04-014" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/news-events/ics-alerts/ics-alert-10-301-01" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/news-events/news/targeted-cyber-intrusion-detection-and-mitigation-strategies-update-b" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/secure-our-world/teach-employees-avoid-phishing" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/news-events/news/avoiding-social-engineering-and-phishing-attacks" } ], "title": "Rockwell Automation FactoryTalk Historian Site Edition", "tracking": { "current_release_date": "2026-06-18T06:00:00.000000Z", "generator": { "date": "2026-06-17T16:55:05.273987Z", "engine": { "name": "CISA CSAF Generator", "version": "1.0.0" } }, "id": "ICSA-26-169-03", "initial_release_date": "2026-06-18T06:00:00.000000Z", "revision_history": [ { "date": "2026-06-18T06:00:00.000000Z", "legacy_version": "Initial", "number": "1", "summary": "Initial Republication of Rockwell Automation Security Advisory SD1773" } ], "status": "final", "version": "1" } }, "product_tree": { "branches": [ { "branches": [ { "branches": [ { "category": "product_version", "name": "11", "product": { "name": "Rockwell Automation FactoryTalk Historian SE: 11", "product_id": "CSAFPID-0001" } } ], "category": "product_name", "name": "FactoryTalk Historian SE" }, { "branches": [ { "category": "product_version_range", "name": "<=11.00", "product": { "name": "Rockwell Automation FactoryTalk Historian SE: <=11.00", "product_id": "CSAFPID-0002" } } ], "category": "product_name", "name": "FactoryTalk Historian SE" }, { "branches": [ { "category": "product_version_range", "name": "<=11.00", "product": { "name": "Rockwell Automation FactoryTalk Historian SE: <=11.00", "product_id": "CSAFPID-0003" } } ], "category": "product_name", "name": "FactoryTalk Historian SE" } ], "category": "vendor", "name": "Rockwell Automation" } ] }, "vulnerabilities": [ { "cve": "CVE-2025-13036", "cwe": { "id": "CWE-362", "name": "Concurrent Execution using Shared Resource with Improper Synchronization ('Race Condition')" }, "notes": [ { "category": "summary", "text": "An authentication bypass security issue exists within FactoryTalk Historian Site Edition. By continually sending requests to the login endpoint, an attacker may obtain a valid authentication token.", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001" ] }, "references": [ { "category": "external", "summary": "cwe.mitre.org", "url": "https://cwe.mitre.org/data/definitions/362.html" }, { "category": "external", "summary": "www.cve.org", "url": "https://www.cve.org/CVERecord?id=CVE-2025-13036" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:L" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:N/AC:L/AT:P/PR:N/UI:N/VC:H/VI:H/VA:L/SC:N/SI:N/SA:N" } ], "remediations": [ { "category": "mitigation", "details": "Rockwell Automation recommends the following: Mitigations and Workarounds for CVE-2025-13036: Customers using the affected software, who are not able to upgrade to one of the corrected versions, should use our security best practices and consider applying the available patch (BF32850) for their current version (https://support.rockwellautomation.com/app/answers/answer_view/a_id/1157978/loc/en_US).", "product_ids": [ "CSAFPID-0001" ], "url": "https://support.rockwellautomation.com/app/answers/answer_view/a_id/1157978/loc/en_US" }, { "category": "mitigation", "details": "For more information, see Rockwell Automation Security Advisory SD1773 (https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1773.html)", "product_ids": [ "CSAFPID-0001" ], "url": "https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1773.html" } ], "scores": [ { "cvss_v3": { "baseScore": 7.7, "baseSeverity": "HIGH", "vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:L", "version": "3.1" }, "products": [ "CSAFPID-0001" ] } ] }, { "cve": "CVE-2025-44019", "cwe": { "id": "CWE-248", "name": "Uncaught Exception" }, "notes": [ { "category": "summary", "text": "AVEVA PI Data Archive products are vulnerable to an uncaught exception that, if exploited, could allow an authenticated user to shut down certain necessary PI Data Archive subsystems, resulting in a denial of service. Depending on the timing of the crash, data present in snapshots/write cache may be lost.", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0002" ] }, "references": [ { "category": "external", "summary": "cwe.mitre.org", "url": "https://cwe.mitre.org/data/definitions/248.html" }, { "category": "external", "summary": "www.cve.org", "url": "https://www.cve.org/CVERecord?id=CVE-2025-44019" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:L/A:H" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:N/VI:L/VA:H/SC:N/SI:N/SA:N" } ], "remediations": [ { "category": "mitigation", "details": "For more information, see Rockwell Automation Security Advisory SD1773 (https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1773.html)", "product_ids": [ "CSAFPID-0002" ], "url": "https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1773.html" } ], "scores": [ { "cvss_v3": { "baseScore": 7.1, "baseSeverity": "HIGH", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:L/A:H", "version": "3.1" }, "products": [ "CSAFPID-0002" ] } ] }, { "cve": "CVE-2025-36539", "cwe": { "id": "CWE-248", "name": "Uncaught Exception" }, "notes": [ { "category": "summary", "text": "AVEVA PI Data Archive products are vulnerable to an uncaught exception that, if exploited, could allow an authenticated user to shut down certain necessary PI Data Archive subsystems, resulting in a denial of service.", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0003" ] }, "references": [ { "category": "external", "summary": "cwe.mitre.org", "url": "https://cwe.mitre.org/data/definitions/248.html" }, { "category": "external", "summary": "www.cve.org", "url": "https://www.cve.org/CVERecord?id=CVE-2025-36539" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N" } ], "remediations": [ { "category": "mitigation", "details": "Mitigations and Workarounds for CVE-2025-36539 & CVE-2025-44109: Customers using the affected software, who are not able to upgrade to one of the corrected versions, should use our security best practices and also consider the following: Monitor liveness of PI Network Manager and PI Archive Subsystem services. Set the PI Network Manager and PI Archive Subsystem services to automatically restart. Limit port 5450 access to trusted workstations and software. For a list of PI System firewall port requirements, see knowledge base article KB01162 - Firewall Port Requirements. For a starting point on PI system security best practices, see knowledge base article KB00833 - Best practices for securing your PI Server.", "product_ids": [ "CSAFPID-0003" ] }, { "category": "mitigation", "details": "For more information, see Rockwell Automation Security Advisory SD1773 (https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1773.html)", "product_ids": [ "CSAFPID-0003" ], "url": "https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1773.html" } ], "scores": [ { "cvss_v3": { "baseScore": 6.5, "baseSeverity": "MEDIUM", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H", "version": "3.1" }, "products": [ "CSAFPID-0003" ] } ] } ] }