{ "document": { "acknowledgments": [ { "organization": "Mitsubishi Electric", "summary": "reported this vulnerability to CISA." } ], "category": "csaf_security_advisory", "csaf_version": "2.0", "distribution": { "text": "Disclosure is not limited", "tlp": { "label": "WHITE", "url": "https://www.cisa.gov/news-events/news/traffic-light-protocol-tlp-definitions-and-usage" } }, "lang": "en-US", "notes": [ { "category": "summary", "text": "Successful exploitation of this vulnerability could allow a remote attacker to cause a denial-of-service (DoS) condition in the affected product by rapidly establishing a large number of TCP connections to it, resulting in an inconsistency in the product's internal connection management process and triggering improper memory access.", "title": "Advisory Summary" }, { "category": "other", "text": "Critical Manufacturing", "title": "Critical infrastructure sectors" }, { "category": "other", "text": "Worldwide", "title": "Countries/areas deployed" }, { "category": "other", "text": "Japan", "title": "Company headquarters location" }, { "category": "legal_disclaimer", "text": "This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy).", "title": "Legal Notice and Terms of Use" }, { "category": "other", "text": "This ICSA is a verbatim republication of Mitsubishi Electric 2026-002 from a direct conversion of the vendor's Common Security Advisory Framework (CSAF) advisory. This is republished to CISA's website as a means of increasing visibility and is provided \"as-is\" for informational purposes only. CISA is not responsible for the editorial or technical accuracy of republished advisories and provides no warranties of any kind regarding any information contained within this advisory. Further, CISA does not endorse any commercial product or service. Please contact Mitsubishi Electric directly for any questions regarding this advisory.", "title": "Advisory Conversion Disclaimer" }, { "category": "general", "text": "CISA recommends users take defensive measures to minimize the exploitation risk of these vulnerabilities. Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolate them from business networks. When remote access is required, use more secure methods, such as virtual private networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most recent version available. Also recognize VPN is only as secure as its connected devices.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.", "title": "Recommended Practices" } ], "publisher": { "category": "other", "contact_details": "central@cisa.dhs.gov", "name": "CISA", "namespace": "https://www.cisa.gov/" }, "references": [ { "category": "self", "summary": "ICS Advisory ICSA-26-169-05 JSON", "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2026/icsa-26-169-05.json" }, { "category": "self", "summary": "Mitsubishi Electric Advisory 2026-002", "url": "https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-002_en.pdf" }, { "category": "self", "summary": "ICS Advisory ICSA-26-169-05 - Web Version", "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-26-169-05" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/news-events/ics-alerts/ics-alert-10-301-01" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/resources-tools/resources/ics-recommended-practices" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/topics/industrial-control-systems" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/sites/default/files/publications/Cybersecurity_Best_Practices_for_Industrial_Control_Systems.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/news-events/news/targeted-cyber-intrusion-detection-and-mitigation-strategies-update-b" } ], "title": "Mitsubishi Electric MELSEC iQ-F Series", "tracking": { "current_release_date": "2026-06-18T06:00:00.000000Z", "generator": { "date": "2026-06-15T17:47:09.968393Z", "engine": { "name": "CISA CSAF Generator", "version": "1.5.0" } }, "id": "ICSA-26-169-05", "initial_release_date": "2026-06-18T00:00:00.000000Z", "revision_history": [ { "date": "2026-06-18T00:00:00.000000Z", "legacy_version": "Initial", "number": "1", "summary": "Initial Publication" }, { "date": "2026-06-18T06:00:00.000000Z", "legacy_version": "CISA Republication", "number": "2", "summary": "Initial CISA Republication of Mitsubishi Electric 2026-002 advisory" } ], "status": "final", "version": "2" } }, "product_tree": { "branches": [ { "branches": [ { "branches": [ { "category": "product_version_range", "name": "<=1.000", "product": { "name": "Mitsubishi Electric MELSEC iQ-F Series FX5-EIP EtherNet/IP Module FX5-EIP: <=1.000", "product_id": "CSAFPID-0001" } } ], "category": "product_name", "name": "MELSEC iQ-F Series FX5-EIP EtherNet/IP Module FX5-EIP" } ], "category": "vendor", "name": "Mitsubishi Electric" } ] }, "vulnerabilities": [ { "cve": "CVE-2026-8805", "cwe": { "id": "CWE-190", "name": "Integer Overflow or Wraparound" }, "notes": [ { "category": "summary", "text": "An integer overflow or wraparound vulnerability exists in the EtherNet/IP function of MELSEC iQ-F Series EtherNet/IP module. This vulnerability could allow a remote attacker to cause a denial-of-service condition in the affected product by rapidly establishing a large number of TCP connections to it, resulting in an inconsistency in the product's internal connection management process and triggering improper memory access.", "title": "Vulnerability Summary" }, { "category": "details", "text": "SSVCv2/E:N/A:Y/T:P/2026-06-18T00:00:00Z/", "title": "SSVC" } ], "product_status": { "known_affected": [ "CSAFPID-0001" ] }, "references": [ { "category": "external", "summary": "www.cve.org", "url": "https://www.cve.org/CVERecord?id=CVE-2026-8805" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N" }, { "category": "external", "summary": "cwe.mitre.org", "url": "https://cwe.mitre.org/data/definitions/190.html" } ], "remediations": [ { "category": "vendor_fix", "details": "Mitsubishi Electric is releasing fixed version 1.001 or later for MELSEC iQ-F Series FX5-EIP EtherNet/IP Module FX5-EIP. Download the update file for the fixed version from the link \"https://www.mitsubishielectric.com/fa/download/index.html\" and install it. For more information on the fixed version, refer to the Mitsubishi Electric security advisory at \"https://www.mitsubishielectric.com/psirt/vulnerability/pdf/2026-002_en.pdf\".", "product_ids": [ "CSAFPID-0001" ], "url": "https://www.mitsubishielectric.com/fa/download/index.html" }, { "category": "mitigation", "details": "For users who cannot immediately update the product, Mitsubishi Electric recommends using a firewall, virtual private network (VPN), etc. to prevent unauthorized access when internet access is required, to minimize the risk of exploiting this vulnerability.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "For users who cannot immediately update the product, Mitsubishi Electric recommends using the affected product within a LAN and blocking access from untrusted networks and hosts through firewalls, to minimize the risk of exploiting this vulnerability.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "For users who cannot immediately update the product, Mitsubishi Electric recommends using the IP filter function of the affected product to block access from untrusted hosts and minimize the risk of exploiting this vulnerability. For details on the IP filter function, refer to \"13.1 IP Filter Function\" in the MELSEC iQ-F FX5 User's Manual (Communication) which can be downloaded from the link \"https://www.mitsubishielectric.com/fa/download/index.html.\"", "product_ids": [ "CSAFPID-0001" ], "url": "https://www.mitsubishielectric.com/fa/download/index.html" }, { "category": "mitigation", "details": "For users who cannot immediately update the product, Mitsubishi Electric recommends restricting physical access to the affected product, as well as to PCs and network devices to which it is connected, to minimize the risk of exploiting this vulnerability.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "For users who cannot immediately update the product, Mitsubishi Electric recommends installing anti-virus software on PCs that can access the affected product, to minimize the risk of exploiting this vulnerability.", "product_ids": [ "CSAFPID-0001" ] } ], "scores": [ { "cvss_v3": { "baseScore": 7.5, "baseSeverity": "HIGH", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H", "version": "3.1" }, "products": [ "CSAFPID-0001" ] } ] } ] }