{ "document": { "acknowledgments": [ { "names": [ "Phlebas" ], "organization": "Lumintel", "summary": "reported these vulnerabilities to CISA" } ], "category": "csaf_security_advisory", "csaf_version": "2.0", "distribution": { "text": "Disclosure is not limited", "tlp": { "label": "WHITE", "url": "https://www.cisa.gov/news-events/news/traffic-light-protocol-tlp-definitions-and-usage" } }, "lang": "en-US", "notes": [ { "category": "legal_disclaimer", "text": "This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy).", "title": "Legal Notice and Terms of Use" }, { "category": "summary", "text": "Successful exploitation of these vulnerabilities could allow an attacker with access to the IT network to manipulate industrial control devices without requiring physical access, specialized insider knowledge, or advanced tooling. ", "title": "Advisory Summary" }, { "category": "other", "text": "Critical Manufacturing, Energy, Information Technology, Water and Wastewater", "title": "Critical infrastructure sectors" }, { "category": "other", "text": "Worldwide", "title": "Countries/areas deployed" }, { "category": "other", "text": "Netherlands", "title": "Company headquarters location" }, { "category": "general", "text": "CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities.", "title": "Recommended Practices" }, { "category": "general", "text": "Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the Internet.", "title": "Recommended Practices" }, { "category": "general", "text": "Locate control system networks and remote devices behind firewalls and isolating them from business networks.", "title": "Recommended Practices" }, { "category": "general", "text": "When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.", "title": "Recommended Practices" }, { "category": "general", "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA also recommends users take the following measures to protect themselves from social engineering attacks:", "title": "Recommended Practices" }, { "category": "general", "text": "Do not click web links or open attachments in unsolicited email messages.", "title": "Recommended Practices" }, { "category": "general", "text": "Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.", "title": "Recommended Practices" }, { "category": "general", "text": "Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.", "title": "Recommended Practices" }, { "category": "general", "text": "No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.", "title": "Recommended Practices" } ], "publisher": { "category": "coordinator", "contact_details": "central@cisa.dhs.gov", "name": "CISA", "namespace": "https://www.cisa.gov/" }, "references": [ { "category": "self", "summary": "ICS Advisory ICSA-26-204-04 JSON", "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2026/icsa-26-204-04.json" }, { "category": "self", "summary": "ICSA Advisory ICSA-26-204-04 - Web Version", "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-26-204-04" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/resources-tools/resources/ics-recommended-practices" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/sites/default/files/publications/Cybersecurity_Best_Practices_for_Industrial_Control_Systems.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/topics/industrial-control-systems" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/sites/default/files/publications/emailscams0905.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ncas/tips/ST04-014" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/news-events/ics-alerts/ics-alert-10-301-01" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/news-events/news/targeted-cyber-intrusion-detection-and-mitigation-strategies-update-b" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/secure-our-world/teach-employees-avoid-phishing" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/news-events/news/avoiding-social-engineering-and-phishing-attacks" } ], "title": "Panduit IntraVUE", "tracking": { "current_release_date": "2026-07-23T06:00:00.000000Z", "generator": { "date": "2026-07-22T15:40:21.196106Z", "engine": { "name": "CISA CSAF Generator", "version": "1.0.0" } }, "id": "ICSA-26-204-04", "initial_release_date": "2026-07-23T06:00:00.000000Z", "revision_history": [ { "date": "2026-07-23T06:00:00.000000Z", "legacy_version": "Initial", "number": "1", "summary": "Initial Publication" } ], "status": "final", "version": "1" } }, "product_tree": { "branches": [ { "branches": [ { "branches": [ { "category": "product_version_range", "name": "<=3.2.1a14", "product": { "name": "Pronetiqs IntraVUE: <=3.2.1a14", "product_id": "CSAFPID-0001" } } ], "category": "product_name", "name": "IntraVUE" } ], "category": "vendor", "name": "Pronetiqs" } ] }, "vulnerabilities": [ { "cve": "CVE-2026-40430", "cwe": { "id": "CWE-256", "name": "Plaintext Storage of a Password" }, "notes": [ { "category": "summary", "text": "Pronetiqs IntraVUE Versions 3.2.1a14 and prior have a plaintext storage of a password vulnerability that could expose cleartext credentials through the API.", "title": "Vulnerability Summary" }, { "category": "details", "text": "SSVCv2/E:N/A:Y/2026-07-22T06:00:00.000000Z", "title": "SSVC" } ], "product_status": { "known_affected": [ "CSAFPID-0001" ] }, "references": [ { "category": "external", "summary": "cwe.mitre.org", "url": "https://cwe.mitre.org/data/definitions/256.html" }, { "category": "external", "summary": "www.cve.org", "url": "https://www.cve.org/CVERecord?id=CVE-2026-40430" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N" } ], "remediations": [ { "category": "vendor_fix", "details": "Pronetiqs advises users to update to the latest version of the IntraVUE software, version 3.2.1a16 or later.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "For further questions, please contact Pronetiqs at info@pronetiqs.com.", "product_ids": [ "CSAFPID-0001" ], "url": "mailto:info@pronetiqs.com" } ], "scores": [ { "cvss_v3": { "baseScore": 7.5, "baseSeverity": "HIGH", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N", "version": "3.1" }, "products": [ "CSAFPID-0001" ] } ] }, { "cve": "CVE-2026-42933", "cwe": { "id": "CWE-441", "name": "Unintended Proxy or Intermediary ('Confused Deputy')" }, "notes": [ { "category": "summary", "text": "Pronetiqs IntraVUE versions 3.2.1a14 and prior have an unintended proxy or intermediary vulnerability which could allow an attacker to use an active proxy, which would bypass OT segmentation.", "title": "Vulnerability Summary" }, { "category": "details", "text": "SSVCv2/E:N/A:Y/2026-07-22T06:00:00.000000Z", "title": "SSVC" } ], "product_status": { "known_affected": [ "CSAFPID-0001" ] }, "references": [ { "category": "external", "summary": "cwe.mitre.org", "url": "https://cwe.mitre.org/data/definitions/441.html" }, { "category": "external", "summary": "www.cve.org", "url": "https://www.cve.org/CVERecord?id=CVE-2026-42933" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H" } ], "remediations": [ { "category": "vendor_fix", "details": "Pronetiqs advises users to update to the latest version of the IntraVUE software, version 3.2.1a16 or later.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "For further questions, please contact Pronetiqs at info@pronetiqs.com.", "product_ids": [ "CSAFPID-0001" ], "url": "mailto:info@pronetiqs.com" } ], "scores": [ { "cvss_v3": { "baseScore": 10.0, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H", "version": "3.1" }, "products": [ "CSAFPID-0001" ] } ] }, { "cve": "CVE-2026-44955", "cwe": { "id": "CWE-497", "name": "Exposure of Sensitive System Information to an Unauthorized Control Sphere" }, "notes": [ { "category": "summary", "text": "Pronetiqs IntraVUE versions 3.2.1a14 and prior have an exposure of sensitive system information to an unauthorized control sphere vulnerability which could allow for asset discovery by unauthenticated users.", "title": "Vulnerability Summary" }, { "category": "details", "text": "SSVCv2/E:N/A:Y/2026-07-22T06:00:00.000000Z", "title": "SSVC" } ], "product_status": { "known_affected": [ "CSAFPID-0001" ] }, "references": [ { "category": "external", "summary": "cwe.mitre.org", "url": "https://cwe.mitre.org/data/definitions/497.html" }, { "category": "external", "summary": "www.cve.org", "url": "https://www.cve.org/CVERecord?id=CVE-2026-44955" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:L/VI:N/VA:N/SC:N/SI:N/SA:N" } ], "remediations": [ { "category": "vendor_fix", "details": "Pronetiqs advises users to update to the latest version of the IntraVUE software, version 3.2.1a16 or later.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "For further questions, please contact Pronetiqs at info@pronetiqs.com.", "product_ids": [ "CSAFPID-0001" ], "url": "mailto:info@pronetiqs.com" } ], "scores": [ { "cvss_v3": { "baseScore": 5.3, "baseSeverity": "MEDIUM", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N", "version": "3.1" }, "products": [ "CSAFPID-0001" ] } ] }, { "cve": "CVE-2026-50044", "cwe": { "id": "CWE-326", "name": "Inadequate Encryption Strength" }, "notes": [ { "category": "summary", "text": "Pronetiqs IntraVUE versions 3.2.1a14 and prior have an inadequate encryption strength vulnerability which could allow an attacker to steal admin credentials via weak hash or a pass-the-hash attack.", "title": "Vulnerability Summary" }, { "category": "details", "text": "SSVCv2/E:N/A:N/2026-07-22T06:00:00.000000Z", "title": "SSVC" } ], "product_status": { "known_affected": [ "CSAFPID-0001" ] }, "references": [ { "category": "external", "summary": "cwe.mitre.org", "url": "https://cwe.mitre.org/data/definitions/326.html" }, { "category": "external", "summary": "www.cve.org", "url": "https://www.cve.org/CVERecord?id=CVE-2026-50044" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:N" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:N/AC:H/AT:P/PR:L/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N" } ], "remediations": [ { "category": "vendor_fix", "details": "Pronetiqs advises users to update to the latest version of the IntraVUE software, version 3.2.1a16 or later.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "For further questions, please contact Pronetiqs at info@pronetiqs.com.", "product_ids": [ "CSAFPID-0001" ], "url": "mailto:info@pronetiqs.com" } ], "scores": [ { "cvss_v3": { "baseScore": 6.8, "baseSeverity": "MEDIUM", "vectorString": "CVSS:3.1/AV:N/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:N", "version": "3.1" }, "products": [ "CSAFPID-0001" ] } ] }, { "cve": "CVE-2026-28698", "cwe": { "id": "CWE-497", "name": "Exposure of Sensitive System Information to an Unauthorized Control Sphere" }, "notes": [ { "category": "summary", "text": "Pronetiqs IntraVUE versions 3.2.1a14 and prior have an exposure of sensitive system information to an unauthorized control sphere vulnerability which could expose the underlying host/share filesystem.", "title": "Vulnerability Summary" }, { "category": "details", "text": "SSVCv2/E:N/A:Y/2026-07-22T06:00:00.000000Z", "title": "SSVC" } ], "product_status": { "known_affected": [ "CSAFPID-0001" ] }, "references": [ { "category": "external", "summary": "cwe.mitre.org", "url": "https://cwe.mitre.org/data/definitions/497.html" }, { "category": "external", "summary": "www.cve.org", "url": "https://www.cve.org/CVERecord?id=CVE-2026-28698" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:N/A:N" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:H/SI:N/SA:N" } ], "remediations": [ { "category": "vendor_fix", "details": "Pronetiqs advises users to update to the latest version of the IntraVUE software, version 3.2.1a16 or later.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "For further questions, please contact Pronetiqs at info@pronetiqs.com.", "product_ids": [ "CSAFPID-0001" ], "url": "mailto:info@pronetiqs.com" } ], "scores": [ { "cvss_v3": { "baseScore": 8.6, "baseSeverity": "HIGH", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:N/A:N", "version": "3.1" }, "products": [ "CSAFPID-0001" ] } ] } ] }