{ "document": { "acknowledgments": [ { "organization": "Rockwell Automation", "summary": "reported this vulnerability to CISA." } ], "category": "csaf_security_advisory", "csaf_version": "2.0", "distribution": { "text": "Disclosure is not limited", "tlp": { "label": "WHITE", "url": "https://www.cisa.gov/news-events/news/traffic-light-protocol-tlp-definitions-and-usage" } }, "lang": "en-US", "notes": [ { "category": "legal_disclaimer", "text": "This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy).", "title": "Legal Notice and Terms of Use" }, { "category": "summary", "text": "Successful exploitation of this vulnerability could give an attacker the ability to run any commands or code of the attacker's choice on a target machine at the logged-in user's permission level.", "title": "Advisory Summary" }, { "category": "other", "text": "Critical Manufacturing, Energy, Water and Wastewater", "title": "Critical infrastructure sectors" }, { "category": "other", "text": "Worldwide", "title": "Countries/areas deployed" }, { "category": "other", "text": "United States", "title": "Company headquarters location" }, { "category": "general", "text": "CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.", "title": "Recommended Practices" }, { "category": "general", "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA also recommends users take the following measures to protect themselves from social engineering attacks: Do not click web links or open attachments in unsolicited email messages. Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams. Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.", "title": "Recommended Practices" }, { "category": "general", "text": "No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. This vulnerability is not exploitable remotely.", "title": "Recommended Practices" } ], "publisher": { "category": "coordinator", "contact_details": "central@cisa.dhs.gov", "name": "CISA", "namespace": "https://www.cisa.gov/" }, "references": [ { "category": "self", "summary": "ICS Advisory ICSA-26-246-03 JSON", "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2026/icsa-26-246-03.json" }, { "category": "self", "summary": "ICSA Advisory ICSA-26-246-03 - Web Version", "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-26-246-03" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/resources-tools/resources/ics-recommended-practices" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/sites/default/files/publications/Cybersecurity_Best_Practices_for_Industrial_Control_Systems.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/topics/industrial-control-systems" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/sites/default/files/publications/emailscams0905.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ncas/tips/ST04-014" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/news-events/ics-alerts/ics-alert-10-301-01" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/news-events/news/targeted-cyber-intrusion-detection-and-mitigation-strategies-update-b" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/secure-our-world/teach-employees-avoid-phishing" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/news-events/news/avoiding-social-engineering-and-phishing-attacks" } ], "title": "Rockwell Automation ControlFLASH", "tracking": { "current_release_date": "2026-09-03T06:00:00.000000Z", "generator": { "date": "2026-09-01T15:24:16.493745Z", "engine": { "name": "CISA CSAF Generator", "version": "1.0.0" } }, "id": "ICSA-26-246-03", "initial_release_date": "2026-09-03T06:00:00.000000Z", "revision_history": [ { "date": "2026-09-03T06:00:00.000000Z", "legacy_version": "Initial", "number": "1", "summary": "Initial Republication of Rockwell Automation security advisory." } ], "status": "final", "version": "1" } }, "product_tree": { "branches": [ { "branches": [ { "branches": [ { "category": "product_version_range", "name": "<=V15.07", "product": { "name": "Rockwell Automation ControlFLASH: <=V15.07", "product_id": "CSAFPID-0001" } } ], "category": "product_name", "name": "ControlFLASH" } ], "category": "vendor", "name": "Rockwell Automation" } ] }, "vulnerabilities": [ { "cve": "CVE-2026-12663", "cwe": { "id": "CWE-306", "name": "Missing Authentication for Critical Function" }, "notes": [ { "category": "summary", "text": "A security issue exists within ControlFLASH, where the installer grants write permissions to the \"Everyone\" group on a product installation directory. This could allow arbitrary code execution, resulting in an attacker being given the ability to run any commands or code of the attacker's choice on a target machine at the logged-in user's permission level.", "title": "Vulnerability Summary" }, { "category": "details", "text": "SSVCv2/E:N/A:N/2026-09-01T06:00:00.000000Z", "title": "SSVC" } ], "product_status": { "known_affected": [ "CSAFPID-0001" ] }, "references": [ { "category": "external", "summary": "cwe.mitre.org", "url": "https://cwe.mitre.org/data/definitions/306.html" }, { "category": "external", "summary": "www.cve.org", "url": "https://www.cve.org/CVERecord?id=CVE-2026-12663" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:L/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:L/AC:L/AT:N/PR:L/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N" } ], "remediations": [ { "category": "mitigation", "details": "Rockwell Automation has corrected this issue in software version 15.08, and encourages all users to update to the newest version.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Users of the affected software who are not able to upgrade to one of thecorrected versions should implement the following mitigation: To protect the files, do the following steps to remove the Everyone group: \n 1. Right-click the C:\\Program Files (x86)\\ControlFLASH\\0001 folder, and then select Properties. \n 2. In the 0001 Properties dialog, select the Security tab, and then select Edit. \n 3. In the Permissions for 0001 dialog, in Group or user names, select Everyone, and then select Remove. \n 4. Select OK.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "If the mitigation above cannot be implemented, Rockwell Automation recommends following their security best practices.", "product_ids": [ "CSAFPID-0001" ], "url": "https://support.rockwellautomation.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight" }, { "category": "mitigation", "details": "For more information on this issue, see the Rockwell Automation security advisory at: https://www.rockwellautomation.com/en-us/trust-center/security-advisories.html", "product_ids": [ "CSAFPID-0001" ], "url": "https://www.rockwellautomation.com/en-us/trust-center/security-advisories.html" } ], "scores": [ { "cvss_v3": { "baseScore": 7.3, "baseSeverity": "HIGH", "vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H", "version": "3.1" }, "products": [ "CSAFPID-0001" ] } ] } ] }