{ "document": { "acknowledgments": [ { "names": [ "Christopher Lusk" ], "organization": "North Echo Security Research", "summary": "reported this vulnerability to Inductive Automation." }, { "names":[ "Elhussain Fathy (0xSphinx)" ], "summary": "independently reported this vulnerability to Inductive Automation and confirmed the fix." }, { "organization": "Inductive Automation", "summary": "reported this vulnerability to CISA." } ], "category": "csaf_security_advisory", "csaf_version": "2.0", "distribution": { "text": "Disclosure is not limited", "tlp": { "label": "WHITE", "url": "https://www.cisa.gov/news-events/news/traffic-light-protocol-tlp-definitions-and-usage" } }, "lang": "en-US", "notes": [ { "category": "legal_disclaimer", "text": "This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy).", "title": "Legal Notice and Terms of Use" }, { "category": "summary", "text": "Successful exploitation of this vulnerability could allow any authenticated user to create projects.", "title": "Advisory Summary" }, { "category": "other", "text": "Critical Manufacturing, Energy, Information Technology", "title": "Critical infrastructure sectors" }, { "category": "other", "text": "Worldwide", "title": "Countries/areas deployed" }, { "category": "other", "text": "United States", "title": "Company headquarters location" }, { "category": "general", "text": "CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolating them from business networks. When remote access is required, use more secure methods, such as virtual private networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.", "title": "Recommended Practices" }, { "category": "general", "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA also recommends users take the following measures to protect themselves from social engineering attacks: Do not click web links or open attachments in unsolicited email messages. Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams. Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.", "title": "Recommended Practices" }, { "category": "general", "text": "No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.", "title": "Recommended Practices" } ], "publisher": { "category": "coordinator", "contact_details": "central@cisa.dhs.gov", "name": "CISA", "namespace": "https://www.cisa.gov/" }, "references": [ { "category": "self", "summary": "ICS Advisory ICSA-26-246-06 JSON", "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2026/icsa-26-246-06.json" }, { "category": "self", "summary": "ICSA Advisory ICSA-26-246-06 - Web Version", "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-26-246-06" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/resources-tools/resources/ics-recommended-practices" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/sites/default/files/publications/Cybersecurity_Best_Practices_for_Industrial_Control_Systems.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/topics/industrial-control-systems" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/sites/default/files/publications/emailscams0905.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ncas/tips/ST04-014" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/news-events/ics-alerts/ics-alert-10-301-01" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/news-events/news/targeted-cyber-intrusion-detection-and-mitigation-strategies-update-b" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/secure-our-world/teach-employees-avoid-phishing" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/news-events/news/avoiding-social-engineering-and-phishing-attacks" } ], "title": "Inductive Automation Ignition", "tracking": { "current_release_date": "2026-09-03T06:00:00.000000Z", "generator": { "date": "2026-09-01T15:24:15.952247Z", "engine": { "name": "CISA CSAF Generator", "version": "1.0.0" } }, "id": "ICSA-26-246-06", "initial_release_date": "2026-09-03T06:00:00.000000Z", "revision_history": [ { "date": "2026-09-03T06:00:00.000000Z", "legacy_version": "Initial", "number": "1", "summary": "Initial Republication of Inductive Automation Trust Center update." } ], "status": "final", "version": "1" } }, "product_tree": { "branches": [ { "branches": [ { "branches": [ { "category": "product_version_range", "name": "<=8.1.53", "product": { "name": "Inductive Automation Ignition: <=8.1.53", "product_id": "CSAFPID-0001" } } ], "category": "product_name", "name": "Ignition" } ], "category": "vendor", "name": "Inductive Automation" } ] }, "vulnerabilities": [ { "cve": "CVE-2026-77393", "cwe": { "id": "CWE-276", "name": "Incorrect Default Permissions" }, "notes": [ { "category": "summary", "text": "In Ignition 8.1.53 and earlier, the Gateway \"Create Project Role(s)\" setting shipped blank, which permitted any authenticated user to create projects (if they can execute gateway scripts). Ignition 8.1.54 restricts project creation to Designer sessions and no longer relies on this setting. The 8.3 series is not affected.", "title": "Vulnerability Summary" }, { "category": "details", "text": "SSVCv2/E:N/A:N/2026-09-01T06:00:00.000000Z", "title": "SSVC" } ], "product_status": { "known_affected": [ "CSAFPID-0001" ] }, "references": [ { "category": "external", "summary": "cwe.mitre.org", "url": "https://cwe.mitre.org/data/definitions/276.html" }, { "category": "external", "summary": "www.cve.org", "url": "https://www.cve.org/CVERecord?id=CVE-2026-77393" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N" } ], "remediations": [ { "category": "mitigation", "details": "Inductive Automation has determined that this issue is a default-value configuration, not a flaw in the access control itself. The security control enforces exactly what the \"Create Project Role(s)\" setting specifies; because the setting shipped blank, no role was required to create a project. Populating the setting fully closes the vulnerability.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Inductive Automation recommends users upgrade to 8.1.54 or later (or the latest 8.3 version), which restricts project creation to Designer sessions and no longer relies on this setting. Users who must remain on an earlier 8.1 version can fully remediate the issue by setting \"Create Project Role(s)\" to match their Designer Role. Once the setting is populated, only users holding that role can create projects. See Gateway General Security Settings.", "product_ids": [ "CSAFPID-0001" ], "url": "https://docs.inductiveautomation.com/docs/8.1/platform/security/gateway-general-security-settings#gateway-security-settings-table" }, { "category": "mitigation", "details": "For more information, see the publication at the Inductive Automation Trust Center.", "product_ids": [ "CSAFPID-0001" ], "url": "https://security.inductiveautomation.com/?tcuUid=34477620-731d-4b70-b22b-9450f9a659a3" } ], "scores": [ { "cvss_v3": { "baseScore": 8.8, "baseSeverity": "HIGH", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H", "version": "3.1" }, "products": [ "CSAFPID-0001" ] } ] } ] }