{ "document": { "acknowledgments": [ { "names": [ "Abdiwelli Guled" ], "summary": "reported these vulnerabilities to CISA" } ], "category": "csaf_security_advisory", "csaf_version": "2.0", "distribution": { "text": "Disclosure is not limited", "tlp": { "label": "WHITE", "url": "https://www.cisa.gov/news-events/news/traffic-light-protocol-tlp-definitions-and-usage" } }, "lang": "en-US", "notes": [ { "category": "legal_disclaimer", "text": "This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy).", "title": "Legal Notice and Terms of Use" }, { "category": "summary", "text": "Successful exploitation of these vulnerabilities could allow for an attacker to perform a man-in-the-middle (MitM) attack, cause a factory reset, wipe credentials, or retrieve sensitive information.", "title": "Advisory Summary" }, { "category": "other", "text": "Critical Manufacturing, Energy", "title": "Critical infrastructure sectors" }, { "category": "other", "text": "Worldwide", "title": "Countries/areas deployed" }, { "category": "other", "text": "United States", "title": "Company headquarters location" }, { "category": "general", "text": "CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities.", "title": "Recommended Practices" }, { "category": "general", "text": "Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.", "title": "Recommended Practices" }, { "category": "general", "text": "Locate control system networks and remote devices behind firewalls and isolating them from business networks.", "title": "Recommended Practices" }, { "category": "general", "text": "When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.", "title": "Recommended Practices" }, { "category": "general", "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA also recommends users take the following measures to protect themselves from social engineering attacks:", "title": "Recommended Practices" }, { "category": "general", "text": "Do not click web links or open attachments in unsolicited email messages.", "title": "Recommended Practices" }, { "category": "general", "text": "Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.", "title": "Recommended Practices" }, { "category": "general", "text": "Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.", "title": "Recommended Practices" }, { "category": "general", "text": "No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.", "title": "Recommended Practices" } ], "publisher": { "category": "coordinator", "contact_details": "central@cisa.dhs.gov", "name": "CISA", "namespace": "https://www.cisa.gov/" }, "references": [ { "category": "self", "summary": "ICS Advisory ICSA-26-246-08 JSON", "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2026/icsa-26-246-08.json" }, { "category": "self", "summary": "ICSA Advisory ICSA-26-246-08 - Web Version", "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-26-246-08" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/resources-tools/resources/ics-recommended-practices" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/sites/default/files/publications/Cybersecurity_Best_Practices_for_Industrial_Control_Systems.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/topics/industrial-control-systems" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/sites/default/files/publications/emailscams0905.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ncas/tips/ST04-014" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/news-events/ics-alerts/ics-alert-10-301-01" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/news-events/news/targeted-cyber-intrusion-detection-and-mitigation-strategies-update-b" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/secure-our-world/teach-employees-avoid-phishing" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/news-events/news/avoiding-social-engineering-and-phishing-attacks" } ], "title": "Tycon Systems TPDIN-Monitor-WEB3", "tracking": { "current_release_date": "2026-09-03T06:00:00.000000Z", "generator": { "date": "2026-09-02T22:03:56.341311Z", "engine": { "name": "CISA CSAF Generator", "version": "1.0.0" } }, "id": "ICSA-26-246-08", "initial_release_date": "2026-09-03T06:00:00.000000Z", "revision_history": [ { "date": "2026-09-03T06:00:00.000000Z", "legacy_version": "Initial", "number": "1", "summary": "Initial Publication" } ], "status": "final", "version": "1" } }, "product_tree": { "branches": [ { "branches": [ { "branches": [ { "category": "product_version_range", "name": "<=2.2.9", "product": { "name": "Tycon Systems TPDIN-Monitor-WEB3: <=2.2.9", "product_id": "CSAFPID-0001" } } ], "category": "product_name", "name": "TPDIN-Monitor-WEB3" } ], "category": "vendor", "name": "Tycon Systems" } ] }, "vulnerabilities": [ { "cve": "CVE-2026-77847", "cwe": { "id": "CWE-798", "name": "Use of Hard-coded Credentials" }, "notes": [ { "category": "summary", "text": "Tycon Systems TPDIN-Monitor-WEB3 versions 2.2.9 and prior are vulnerable to a Use of Hard-coded Credential vulnerability. This could allow an attacker to intercept sensitive information or credentials.", "title": "Vulnerability Summary" }, { "category": "details", "text": "SSVCv2/E:N/A:N/2026-09-02T06:00:00.000000Z", "title": "SSVC" } ], "product_status": { "known_affected": [ "CSAFPID-0001" ] }, "references": [ { "category": "external", "summary": "cwe.mitre.org", "url": "https://cwe.mitre.org/data/definitions/798.html" }, { "category": "external", "summary": "www.cve.org", "url": "https://www.cve.org/CVERecord?id=CVE-2026-77847" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N" } ], "remediations": [ { "category": "vendor_fix", "details": "Tycon Systems has released TPDIN-Monitor-WEB3 Firmware v2.4.2.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Units already running v2.4.2, for subsequent updates (signed container): https://firm.tyconsystems.com/tpdin-monitor-web3-v2/TPDIN-MONITOR-WEB3-V2_v2.4.2.tfw", "product_ids": [ "CSAFPID-0001" ], "url": "https://firm.tyconsystems.com/tpdin-monitor-web3-v2/TPDIN-MONITOR-WEB3-V2_v2.4.2.tfw" }, { "category": "mitigation", "details": "All units currently in the field, including the v2.2.9 covered by this report (legacy Intel HEX): https://firm.tyconsystems.com/tpdin-monitor-web3-v2/TPDIN-MONITOR-WEB3-V2_v2.4.2T.hex", "product_ids": [ "CSAFPID-0001" ], "url": "https://firm.tyconsystems.com/tpdin-monitor-web3-v2/TPDIN-MONITOR-WEB3-V2_v2.4.2T.hex" }, { "category": "mitigation", "details": "A unit running v2.2.9 installs the .hex build directly and arrives at v2.4.2 in a single step; no intermediate version is required. The signed .tfw container cannot be read by a v2.2.9 updater, which accepts only Intel HEX, so the .hex artifact is the one every deployed unit needs.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "For more information, contact Tycon Systems https://www.tyconsystems.com/contact", "product_ids": [ "CSAFPID-0001" ], "url": "https://www.tyconsystems.com/contact" } ], "scores": [ { "cvss_v3": { "baseScore": 6.5, "baseSeverity": "MEDIUM", "vectorString": "CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N", "version": "3.1" }, "products": [ "CSAFPID-0001" ] } ] }, { "cve": "CVE-2026-82712", "cwe": { "id": "CWE-352", "name": "Cross-Site Request Forgery (CSRF)" }, "notes": [ { "category": "summary", "text": "Tycon Systems TPDIN-Monitor-WEB3 versions 2.2.9 and prior are vulnerable to a Cross-Site Request Forgery vulnerability. This could allow an attacker to perform state changing operations on the device. ", "title": "Vulnerability Summary" }, { "category": "details", "text": "SSVCv2/E:N/A:N/2026-09-02T06:00:00.000000Z", "title": "SSVC" } ], "product_status": { "known_affected": [ "CSAFPID-0001" ] }, "references": [ { "category": "external", "summary": "cwe.mitre.org", "url": "https://cwe.mitre.org/data/definitions/352.html" }, { "category": "external", "summary": "www.cve.org", "url": "https://www.cve.org/CVERecord?id=CVE-2026-82712" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:A/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N" } ], "remediations": [ { "category": "vendor_fix", "details": "Tycon Systems has released TPDIN-Monitor-WEB3 Firmware v2.4.2.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Units already running v2.4.2, for subsequent updates (signed container): https://firm.tyconsystems.com/tpdin-monitor-web3-v2/TPDIN-MONITOR-WEB3-V2_v2.4.2.tfw", "product_ids": [ "CSAFPID-0001" ], "url": "https://firm.tyconsystems.com/tpdin-monitor-web3-v2/TPDIN-MONITOR-WEB3-V2_v2.4.2.tfw" }, { "category": "mitigation", "details": "All units currently in the field, including the v2.2.9 covered by this report (legacy Intel HEX): https://firm.tyconsystems.com/tpdin-monitor-web3-v2/TPDIN-MONITOR-WEB3-V2_v2.4.2T.hex", "product_ids": [ "CSAFPID-0001" ], "url": "https://firm.tyconsystems.com/tpdin-monitor-web3-v2/TPDIN-MONITOR-WEB3-V2_v2.4.2T.hex" }, { "category": "mitigation", "details": "A unit running v2.2.9 installs the .hex build directly and arrives at v2.4.2 in a single step; no intermediate version is required. The signed .tfw container cannot be read by a v2.2.9 updater, which accepts only Intel HEX, so the .hex artifact is the one every deployed unit needs.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "For more information, contact Tycon Systems https://www.tyconsystems.com/contact", "product_ids": [ "CSAFPID-0001" ], "url": "https://www.tyconsystems.com/contact" } ], "scores": [ { "cvss_v3": { "baseScore": 8.8, "baseSeverity": "HIGH", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H", "version": "3.1" }, "products": [ "CSAFPID-0001" ] } ] }, { "cve": "CVE-2026-82684", "cwe": { "id": "CWE-862", "name": "Missing Authorization" }, "notes": [ { "category": "summary", "text": "Tycon Systems TPDIN-Monitor-WEB3 versions 2.2.9 and prior are vulnerable to a Missing Authorization vulnerability. This could allow an attacker to extract system credentials, configurations, or flash contents. ", "title": "Vulnerability Summary" }, { "category": "details", "text": "SSVCv2/E:N/A:N/2026-09-02T06:00:00.000000Z", "title": "SSVC" } ], "product_status": { "known_affected": [ "CSAFPID-0001" ] }, "references": [ { "category": "external", "summary": "cwe.mitre.org", "url": "https://cwe.mitre.org/data/definitions/862.html" }, { "category": "external", "summary": "www.cve.org", "url": "https://www.cve.org/CVERecord?id=CVE-2026-82684" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:N" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N" } ], "remediations": [ { "category": "vendor_fix", "details": "Tycon Systems has released TPDIN-Monitor-WEB3 Firmware v2.4.2.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Units already running v2.4.2, for subsequent updates (signed container): https://firm.tyconsystems.com/tpdin-monitor-web3-v2/TPDIN-MONITOR-WEB3-V2_v2.4.2.tfw", "product_ids": [ "CSAFPID-0001" ], "url": "https://firm.tyconsystems.com/tpdin-monitor-web3-v2/TPDIN-MONITOR-WEB3-V2_v2.4.2.tfw" }, { "category": "mitigation", "details": "All units currently in the field, including the v2.2.9 covered by this report (legacy Intel HEX): https://firm.tyconsystems.com/tpdin-monitor-web3-v2/TPDIN-MONITOR-WEB3-V2_v2.4.2T.hex", "product_ids": [ "CSAFPID-0001" ], "url": "https://firm.tyconsystems.com/tpdin-monitor-web3-v2/TPDIN-MONITOR-WEB3-V2_v2.4.2T.hex" }, { "category": "mitigation", "details": "A unit running v2.2.9 installs the .hex build directly and arrives at v2.4.2 in a single step; no intermediate version is required. The signed .tfw container cannot be read by a v2.2.9 updater, which accepts only Intel HEX, so the .hex artifact is the one every deployed unit needs.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "For more information, contact Tycon Systems https://www.tyconsystems.com/contact", "product_ids": [ "CSAFPID-0001" ], "url": "https://www.tyconsystems.com/contact" } ], "scores": [ { "cvss_v3": { "baseScore": 8.1, "baseSeverity": "HIGH", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:N", "version": "3.1" }, "products": [ "CSAFPID-0001" ] } ] } ] }