{ "document": { "acknowledgments": [ { "organization": "Siemens ProductCERT", "summary": "reported this vulnerability to CISA." } ], "category": "csaf_security_advisory", "csaf_version": "2.0", "distribution": { "text": "Disclosure is not limited", "tlp": { "label": "WHITE", "url": "https://www.cisa.gov/news-events/news/traffic-light-protocol-tlp-definitions-and-usage" } }, "lang": "en", "notes": [ { "category": "summary", "text": "SENTRON 3NA COM Fuse contains a Denial-of-Service vulnerability. Improper handling of a network management message could allow an attacker to trigger a denial-of-service (DoS) condition. Successful exploitation may require the affected network to be re-established to restore normal operation.", "title": "Summary" }, { "category": "general", "text": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens' operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\nAdditional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity", "title": "General Recommendations" }, { "category": "general", "text": "For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories", "title": "Additional Resources" }, { "category": "legal_disclaimer", "text": "The use of Siemens Security Advisories is subject to the terms and conditions listed on: https://www.siemens.com/productcert/terms-of-use.", "title": "Terms of Use" }, { "category": "legal_disclaimer", "text": "This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy).", "title": "Legal Notice and Terms of Use" }, { "category": "other", "text": "This ICSA is a verbatim republication of Siemens ProductCERT SSA-099819 from a direct conversion of the vendor's Common Security Advisory Framework (CSAF) advisory. This is republished to CISA's website as a means of increasing visibility and is provided \"as-is\" for informational purposes only. CISA is not responsible for the editorial or technical accuracy of republished advisories and provides no warranties of any kind regarding any information contained within this advisory. Further, CISA does not endorse any commercial product or service. Please contact Siemens ProductCERT directly for any questions regarding this advisory.", "title": "Advisory Conversion Disclaimer" }, { "category": "general", "text": "CISA recommends users take defensive measures to minimize the exploitation risk of these vulnerabilities.", "title": "Recommended Practices" }, { "category": "general", "text": "Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the internet.", "title": "Recommended Practices" }, { "category": "general", "text": "Locate control system networks and remote devices behind firewalls and isolate them from business networks.", "title": "Recommended Practices" }, { "category": "general", "text": "When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most recent version available. Also recognize VPN is only as secure as its connected devices.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.", "title": "Recommended Practices" }, { "category": "other", "text": "Critical Manufacturing, Transportation Systems, Energy, Healthcare and Public Health, Financial Services, Government Services and Facilities", "title": "Critical infrastructure sectors" }, { "category": "other", "text": "Worldwide", "title": "Countries/areas deployed" }, { "category": "other", "text": "Germany", "title": "Company headquarters location" } ], "publisher": { "category": "other", "contact_details": "central@cisa.dhs.gov", "name": "CISA", "namespace": "https://www.cisa.gov/" }, "references": [ { "category": "self", "summary": "SSA-099819: Denial of Service Vulnerability in SENTRON 3NA COM Fuse - CSAF Version", "url": "https://cert-portal.siemens.com/productcert/csaf/ssa-099819.json" }, { "category": "self", "summary": "SSA-099819: Denial of Service Vulnerability in SENTRON 3NA COM Fuse - HTML Version", "url": "https://cert-portal.siemens.com/productcert/html/ssa-099819.html" }, { "category": "self", "summary": "ICS Advisory icsa-26-295-05 JSON", "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2026/icsa-26-295-05.json" }, { "category": "self", "summary": "ICS Advisory icsa-26-295-05 - Web Version", "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-26-295-05" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/news-events/ics-alerts/ics-alert-10-301-01" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/resources-tools/resources/ics-recommended-practices" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/topics/industrial-control-systems" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/sites/default/files/publications/Cybersecurity_Best_Practices_for_Industrial_Control_Systems.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/news-events/news/targeted-cyber-intrusion-detection-and-mitigation-strategies-update-b" } ], "title": "Siemens SENTRON 3NA COM Fuse", "tracking": { "current_release_date": "2026-10-22T06:00:00.000000Z", "generator": { "date": "2026-10-20T15:18:24.826417Z", "engine": { "name": "CISA CSAF Generator", "version": "1.5.0" } }, "id": "ICSA-26-295-05", "initial_release_date": "2026-10-13T00:00:00.000000Z", "revision_history": [ { "date": "2026-10-13T00:00:00.000000Z", "legacy_version": "Initial", "number": "1", "summary": "Publication Date" }, { "date": "2026-10-22T06:00:00.000000Z", "legacy_version": "CISA Republication", "number": "2", "summary": "Initial CISA Republication of Siemens ProductCERT SSA-099819 advisory" } ], "status": "final", "version": "2" } }, "product_tree": { "branches": [ { "branches": [ { "branches": [ { "category": "product_version_range", "name": "vers:intdot/<5.2", "product": { "name": "SENTRON 3NA COM Fuse < V5.2", "product_id": "CSAFPID-0001" } } ], "category": "product_name", "name": "SENTRON 3NA COM Fuse" } ], "category": "vendor", "name": "Siemens" } ] }, "vulnerabilities": [ { "cve": "CVE-2024-7322", "cwe": { "id": "CWE-940", "name": "Improper Verification of Source of a Communication Channel" }, "notes": [ { "category": "description", "text": "A ZigBee coordinator, router, or end device may change their node ID when an unsolicited encrypted rejoin response is received, this change\u00a0in node ID causes Denial of Service (DoS). To recover from this DoS, the network must be re-established", "title": "CVE Description" } ], "product_status": { "known_affected": [ "CSAFPID-0001" ] }, "references": [ { "category": "external", "summary": "www.cve.org", "url": "https://www.cve.org/CVERecord?id=CVE-2024-7322" }, { "category": "external", "summary": "cwe.mitre.org", "url": "https://cwe.mitre.org/data/definitions/940.html" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:H/PR:H/UI:N/S:C/C:N/I:N/A:H" } ], "remediations": [ { "category": "vendor_fix", "details": "Update to V5.2 or later version", "product_ids": [ "CSAFPID-0001" ], "url": "https://support.industry.siemens.com/cs/ww/en/view/109797242/" } ], "scores": [ { "cvss_v3": { "baseScore": 5.8, "baseSeverity": "MEDIUM", "vectorString": "CVSS:3.1/AV:N/AC:H/PR:H/UI:N/S:C/C:N/I:N/A:H", "version": "3.1" }, "products": [ "CSAFPID-0001" ] } ], "title": "CVE-2024-7322" } ] }