{ "$schema": "https://raw.githubusercontent.com/nobrega8/mbmap-library/main/schema/mbmap-2.schema.json", "mbmap": 2, "vendor": "Moxa", "model": "ioThinx 45MR-7210", "models": ["ioThinx 45MR-7210"], "vendor_website": "moxa.com", "description": "System + field power input monitor ioThinx 45MR slot module. Addresses are module-relative; actual PDU address = slot_base + relative_address. FC03: spStatus (rel 0, system power status WORD), spLowerLimitValue (rel 1-2, f32 lower alarm threshold), spUpperLimitValue (rel 3-4, f32 upper alarm threshold), fpStatus (rel 5, field power status WORD). Write spLowerLimitValue/spUpperLimitValue to configure system power alarm thresholds.", "revision": 2, "source": "Omni Console device library (OmniCoreST), modbus-library/moxa-iothinx-45mr-7210.toml; Source: ioThinx 4510 Series User's Manual V2.1, August 2019, Appendix A. Not verified against the manufacturer's documentation", "notes": [ "Moxa ioThinx 45MR-7210.", "Converted automatically from the Omni Console device library (OmniCoreST).", "Not verified against the manufacturer's documentation.", "Corrections are welcome (CONTRIBUTING.md). Change x_status once this table has been checked against the manual.", "| Moxa ioThinx 45MR-7210 — System Power + Field Power Input Monitor", "|", "| Source: ioThinx 4510 Series User's Manual V2.1, August 2019, Appendix A", "| Protocol: Modbus/TCP via ioThinx 4510 adapter, port 502", "|", "| IMPORTANT: Addresses are MODULE-RELATIVE. Actual PDU address = slot_base + relative_address.", "| Slot base depends on which slot this module occupies in the ioThinx 4510 chassis.", "|", "| Monitors system power (SP) and field power (FP) rails.", "| spLowerLimitValue and spUpperLimitValue define the alarm threshold window for system power.", "|", "| FC03 (holding R/W): see [[registers]] below", "| (No FC01/FC02/FC04 entries documented for this module)" ], "byte_order": "big", "word_order": "big", "address_base": 0, "x_status": "unofficial", "x_origin": "omniconsole", "registers": [ {"name": "spStatus (system power status; R)", "area": "holding", "address": 0, "type": "uint16", "access": "R"}, {"name": "spLowerLimitValue hi-word (f32 system power lower alarm threshold; R/W)", "area": "holding", "address": 1, "type": "uint16", "access": "R"}, {"name": "spLowerLimitValue lo-word", "area": "holding", "address": 2, "type": "uint16", "access": "R"}, {"name": "spUpperLimitValue hi-word (f32 system power upper alarm threshold; R/W)", "area": "holding", "address": 3, "type": "uint16", "access": "R"}, {"name": "spUpperLimitValue lo-word", "area": "holding", "address": 4, "type": "uint16", "access": "R"}, {"name": "fpStatus (field power status; R)", "area": "holding", "address": 5, "type": "uint16", "access": "R"} ] }