{ "$schema": "https://raw.githubusercontent.com/nobrega8/mbmap-library/main/schema/mbmap-2.schema.json", "mbmap": 2, "vendor": "Solis", "model": "Energy storage (hybrid) inverters", "vendor_website": "solisinverters.com", "description": "Hybrid and energy storage inverters with RS485 Modbus RTU and Modbus TCP", "revision": 1, "revised": "2026-11-11", "source": "Solis, Communication Protocol for Energy Storage Inverters, version 3.5", "sources": [ { "title": "Communication Protocol for Energy Storage Inverters (RS485_MODBUS ESINV-33000ID Hybrid Inverter)", "version": "3.5", "url": "https://oss.soliscloud.com/file/RS485_MODBUS%28ESINV-33000ID%29%20Hybrid%20Inverter.pdf", "note": "Sections 5.1 (function 0x04, registers 25000 to 36999) and 5.2 (functions 0x03, 0x06, 0x10, registers 43000 to 44999)" } ], "notes": [ "Covers Solis hybrid and energy storage inverters (the S5-EH1P and later generations; some registers apply only to the S6 generation or to models with a backup port, as the descriptions say). Grid-connected string inverters have a separate document and map.", "Addresses are the decimal numbers of the manual and are sent as they are (address_base 0). Input registers (25000 to 36999) are read with function 0x04; setting registers (43000 to 44999) with 0x03, 0x06 and 0x10. Registers a model does not implement read 0.", "32-bit values (U32, S32) use two registers with the high word first (big word order). Slave address 1, 9600 baud, no parity, 8 data bits, 1 stop bit by default; Modbus TCP on port 502 (one connection) on models with a LAN port.", "The query interval must be above 300 ms and the control interval above 700 ms; only one write per frame (use function 0x06).", "These tables were read from the manual's table layout; scale and unit come from the unit column (for example 0.1 V). The appendices (device type codes, national standard codes, alarm codes, status bits, battery model numbers, control switch states) and the application chapters (frequency control ancillary service, EMS) are not mapped, so values that refer to them are raw codes.", "Some registers have remarks spanning several rows in the manual; the description is attached to the first row it covers." ], "protocol": "tcp+rtu", "unit_id": 1, "port": 502, "baud_rate": 9600, "data_bits": 8, "parity": "N", "stop_bits": 1, "byte_order": "big", "word_order": "big", "address_base": 0, "x_status": "official", "registers": [ { "name": "5. Detailed Protocol Description 5.1. Definition of Operational Information Addresses Corresponding to function code 0x04. Register Data Address Description Type (Decimal) Definition of Solis inverter types", "group": "Operation", "area": "input", "address": 35000, "type": "uint16", "access": "R", "unit": "Unit", "description": "Refer to Appendix 1 for specific details (M35000)" }, { "name": "Product Model Number", "group": "Operation", "area": "input", "address": 33000, "type": "uint16", "access": "R", "description": "Byte: Reserved, any value other the Sub-DSP" }, { "name": "DSP Software Major Version", "group": "Operation", "area": "input", "address": 33001, "type": "uint16", "access": "R", "description": "Version (displayed High-order default 0x00; than 0x00 indicates Major Version. Low-order Byte: The Main DSP Major in hexadecimal). the Descr" }, { "name": "HMI Software Major Version", "group": "Operation", "area": "input", "address": 33002, "type": "uint16", "access": "R", "description": "High-order byte: Reserved, default 0x00 Low-order byte: Major version number (displayed in hexadecimal) Description: Together with the low-o" }, { "name": "Inverter Serial Number SN_1", "group": "Operation", "area": "input", "address": 33004, "type": "uint16", "access": "R", "description": "then Inverter (Hexadecimal Display) Serial Number" }, { "name": "Inverter Serial Number SN_2", "group": "Operation", "area": "input", "address": 33005, "type": "uint16", "access": "R", "description": "Example: If the value uploaded from register 33004 is ‘01’, and the value from register 33005 is ‘23’, then the corresponding display is ‘01" }, { "name": "Inverter Serial Number SN_3", "group": "Operation", "area": "input", "address": 33006, "type": "uint16", "access": "R" }, { "name": "Inverter Serial Number SN_4", "group": "Operation", "area": "input", "address": 33007, "type": "uint16", "access": "R" }, { "name": "Inverter Serial Number SN_5", "group": "Operation", "area": "input", "address": 33008, "type": "uint16", "access": "R" }, { "name": "Inverter Serial Number SN_6", "group": "Operation", "area": "input", "address": 33009, "type": "uint16", "access": "R" }, { "name": "Inverter Serial Number SN_7", "group": "Operation", "area": "input", "address": 33010, "type": "uint16", "access": "R" }, { "name": "Inverter Serial Number SN_8", "group": "Operation", "area": "input", "address": 33011, "type": "uint16", "access": "R" }, { "name": "Inverter Serial Number SN_9", "group": "Operation", "area": "input", "address": 33012, "type": "uint16", "access": "R" }, { "name": "Inverter Serial Number SN_10", "group": "Operation", "area": "input", "address": 33013, "type": "uint16", "access": "R" }, { "name": "Inverter Serial Number SN_11", "group": "Operation", "area": "input", "address": 33014, "type": "uint16", "access": "R" }, { "name": "Inverter Serial Number SN_12", "group": "Operation", "area": "input", "address": 33015, "type": "uint16", "access": "R" }, { "name": "Inverter Serial Number SN_13", "group": "Operation", "area": "input", "address": 33016, "type": "uint16", "access": "R" }, { "name": "Inverter Serial Number SN_14", "group": "Operation", "area": "input", "address": 33017, "type": "uint16", "access": "R" }, { "name": "Inverter Serial Number SN_15", "group": "Operation", "area": "input", "address": 33018, "type": "uint16", "access": "R" }, { "name": "Inverter Serial Number SN_16", "group": "Operation", "area": "input", "address": 33019, "type": "uint16", "access": "R" }, { "name": "DSP Software Sub Version", "group": "Operation", "area": "input", "address": 33021, "type": "uint16", "access": "R", "description": "(displayed High-order byte: Reserved, default 0x00; Low-order byte: Main DSP Sub version number in hexadecimal) the Description: Together wi" }, { "name": "Total PV Energy Generation", "group": "Operation", "area": "input", "address": 33029, "type": "uint32", "access": "R", "unit": "kWh", "description": "For Hybrid Energy Storage Inverter models: Indicates the PV energy generation data of this unit itself. For S6 Single-Phase Low-Voltage AC-C" }, { "name": "Today's PV Energy Generation", "group": "Operation", "area": "input", "address": 33035, "type": "uint16", "access": "R", "unit": "kWh", "scale": 0.1 }, { "name": "Maximum Charge/Discharge Current of this device’s battery", "group": "Operation", "area": "input", "address": 33041, "type": "uint16", "access": "R", "unit": "A", "scale": 0.1 }, { "name": "Rated Output Current of this device‘s AC Grid Port", "group": "Operation", "area": "input", "address": 33042, "type": "uint16", "access": "R", "unit": "A", "scale": 0.1 }, { "name": "Battery 1 Temperature", "group": "Operation", "area": "input", "address": 33043, "type": "int16", "access": "R", "unit": "°C", "scale": 0.1, "description": "Description: From Battery 1 BMS" }, { "name": "Inverter Battery MOSFET Temperature", "group": "Operation", "area": "input", "address": 33046, "type": "int16", "access": "R", "unit": "°C", "scale": 0.1, "description": "Description: Supported by S6 Generation Energy Storage Models" }, { "name": "DC Input Type", "group": "Operation", "area": "input", "address": 33048, "type": "uint16", "access": "R", "description": "0: Indicates 1 input 1: Indicates 2 inputs 2: Indicates 3 inputs 3: Indicates 4 inputs ……" }, { "name": "PV DC Voltage 1", "group": "Operation", "area": "input", "address": 33049, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1 }, { "name": "PV DC Current 1", "group": "Operation", "area": "input", "address": 33050, "type": "uint16", "access": "R", "unit": "A", "scale": 0.1 }, { "name": "PV DC Voltage 2", "group": "Operation", "area": "input", "address": 33051, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1 }, { "name": "PV DC Current 2", "group": "Operation", "area": "input", "address": 33052, "type": "uint16", "access": "R", "unit": "A", "scale": 0.1 }, { "name": "PV DC Voltage 3", "group": "Operation", "area": "input", "address": 33053, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1 }, { "name": "PV DC Current 3", "group": "Operation", "area": "input", "address": 33054, "type": "uint16", "access": "R", "unit": "A", "scale": 0.1 }, { "name": "PV DC Voltage 4", "group": "Operation", "area": "input", "address": 33055, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1 }, { "name": "PV DC Current 4", "group": "Operation", "area": "input", "address": 33056, "type": "uint16", "access": "R", "unit": "A", "scale": 0.1 }, { "name": "Total PV Input Power", "group": "Operation", "area": "input", "address": 33057, "type": "uint32", "access": "R", "unit": "W", "description": "Represents the real-time total PV power of this unit" }, { "name": "PV DC Voltage 5", "group": "Operation", "area": "input", "address": 33059, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1 }, { "name": "PV DC Current 5", "group": "Operation", "area": "input", "address": 33060, "type": "uint16", "access": "R", "unit": "A", "scale": 0.1 }, { "name": "PV DC Voltage 6", "group": "Operation", "area": "input", "address": 33061, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1 }, { "name": "PV DC Current 6", "group": "Operation", "area": "input", "address": 33062, "type": "uint16", "access": "R", "unit": "A", "scale": 0.1 }, { "name": "PV DC Voltage 7", "group": "Operation", "area": "input", "address": 33063, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1 }, { "name": "PV DC Current 7", "group": "Operation", "area": "input", "address": 33064, "type": "uint16", "access": "R", "unit": "A", "scale": 0.1 }, { "name": "PV DC Voltage 8", "group": "Operation", "area": "input", "address": 33065, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1 }, { "name": "PV DC Current 8", "group": "Operation", "area": "input", "address": 33066, "type": "uint16", "access": "R", "unit": "A", "scale": 0.1 }, { "name": "This device’s Rated Apparent Power", "group": "Operation", "area": "input", "address": 33067, "type": "uint16", "access": "R", "unit": "VA", "scale": 10.0 }, { "name": "Safety Regulation", "group": "Operation", "area": "input", "address": 33068, "type": "uint16", "access": "R", "description": "version byte: Sub" }, { "name": "Version Number HMI Software Sub Version", "group": "Operation", "area": "input", "address": 33069, "type": "uint16", "access": "R", "description": "High-order byte: Reserved, default 0x00 Low-order number (displayed in hexadecimal) Description: Together with the low-order byte of registe" }, { "name": "Warning/Fault Message Data", "group": "Operation", "area": "input", "address": 33070, "type": "uint16", "access": "R", "description": "5G/S5 generation Refer to Appendix 3 (M33095) for details. Description: Used in conjunction to with register address 33095 subdivide and dis" }, { "name": "AB Line Voltage / A Phase Voltage", "group": "Operation", "area": "input", "address": 33073, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1 }, { "name": "BC Line Voltage / B Phase Voltage", "group": "Operation", "area": "input", "address": 33074, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1, "description": "S6 Single-Phase High-Voltage US Version Energy Storage Inverter: L2-N voltage." }, { "name": "CA Line Voltage / C Phase Voltage", "group": "Operation", "area": "input", "address": 33075, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1, "description": "S6 Single-Phase High-Voltage US Version Energy Storage Inverter: L1-L2 voltage." }, { "name": "A Phase Current", "group": "Operation", "area": "input", "address": 33076, "type": "uint16", "access": "R", "unit": "A", "scale": 0.1, "description": "5G/S5 generation For energy storage units: represents the internal inverter-side AC current. For S6 generation energy storage units: represe" }, { "name": "B Phase Current", "group": "Operation", "area": "input", "address": 33077, "type": "uint16", "access": "R", "unit": "A", "scale": 0.1, "description": "S6 Single-Phase High-Voltage US Version Energy Storage Inverter: L2-N current." }, { "name": "C Phase Current", "group": "Operation", "area": "input", "address": 33078, "type": "uint16", "access": "R", "unit": "A", "scale": 0.1, "description": "S6 Single-Phase High-Voltage US Version Energy Storage Inverter: This register is invalid when N (Neutral) is connected; when N is register " }, { "name": "Active Power Value", "group": "Operation", "area": "input", "address": 33079, "type": "int32", "access": "R", "unit": "W", "description": "Active inverter/rectifier. power of the" }, { "name": "Reactive Power Value", "group": "Operation", "area": "input", "address": 33081, "type": "int32", "access": "R", "unit": "var", "description": "Reactive inverter/rectifier. power of the" }, { "name": "Apparent Power Value", "group": "Operation", "area": "input", "address": 33083, "type": "int32", "access": "R", "unit": "VA", "description": "Apparent inverter/rectifier. power of the" }, { "name": "National Standard Number (33092)", "group": "Operation", "area": "input", "address": 33092, "type": "uint16", "access": "R", "description": "Refer to Appendix 2 (M33092) for details." }, { "name": "Inverter Module Temperature Note: AC NTC (IGBT)", "group": "Operation", "area": "input", "address": 33093, "type": "int16", "access": "R", "unit": "°C", "scale": 0.1 }, { "name": "Grid Frequency", "group": "Operation", "area": "input", "address": 33094, "type": "uint16", "access": "R", "unit": "Hz", "scale": 0.01 }, { "name": "Inverter Current Status", "group": "Operation", "area": "input", "address": 33095, "type": "uint16", "access": "R", "description": "Refer to Appendix 3 (M33095) for details. Description: Used in conjunction with register address 33070 to subdivide and display detailed inf" }, { "name": "Lead-Acid Battery Ambient Temperature", "group": "Operation", "area": "input", "address": 33096, "type": "int16", "access": "R", "unit": "°C", "scale": 0.1 }, { "name": "Current DRM Status", "group": "Operation", "area": "input", "address": 33098, "type": "uint16", "access": "R" }, { "name": "Operating Status", "group": "Battery", "area": "input", "address": 33121, "type": "uint16", "access": "R", "description": "Refer to Appendix 4: Status Bit Definitions for details." }, { "name": "Standard Operating Mode Startup Status", "group": "Battery", "area": "input", "address": 33123, "type": "uint16", "access": "R", "description": "Each bit indicates the startup status of an operating mode: 0 = not started, 1 = started. BIT00: Volt-watt Active Power). BIT01: Volt-var (V" }, { "name": "Battery 1 Real-time Voltage", "group": "Battery", "area": "input", "address": 33133, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1, "description": "Description: Battery 1 real-time voltage value." }, { "name": "Battery 1 Real-time Current", "group": "Battery", "area": "input", "address": 33134, "type": "int16", "access": "R", "unit": "A", "scale": 0.1, "description": "Description: (1) Charge/discharge direction is determined by register 33135; (2) The absolute value of represents register current of Batter" }, { "name": "Battery 1 Real-time Charge/Discharge Direction", "group": "Battery", "area": "input", "address": 33135, "type": "uint16", "access": "R", "description": "0: Charging; 1: Discharging." }, { "name": "Backup Port AC Voltage A", "group": "Battery", "area": "input", "address": 33137, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1, "description": "For Description: (1) Backup port information for single-phase systems; (2) systems, split-phase represents L1-N voltage when connected to Ne" }, { "name": "Backup Port AC Current A", "group": "Battery", "area": "input", "address": 33138, "type": "uint16", "access": "R", "unit": "A", "scale": 0.1, "description": "Description: (1) Backup port information for single-phase systems; (2) represents current on L1 line; (3) represents current on L1 line. thr" }, { "name": "Battery 1 State of Charge (SOC)", "group": "Battery", "area": "input", "address": 33139, "type": "uint16", "access": "R", "unit": "%" }, { "name": "Battery 1 State of Health (SOH)", "group": "Battery", "area": "input", "address": 33140, "type": "uint16", "access": "R", "unit": "%", "description": "100<-->100% grid only" }, { "name": "Grid Load Power (Low Register)", "group": "Battery", "area": "input", "address": 33147, "type": "uint16", "access": "R", "unit": "W", "description": "load; load, Represents for excluding Backup three-phase systems, represents the total active power sum of all grid phase loads. Description:" }, { "name": "Backup Load Power (Low Register)", "group": "Battery", "area": "input", "address": 33148, "type": "int16", "access": "R", "unit": "W", "description": "A positive value indicates power flowing out of the energy storage inverter Backup port, and a negative value indicates power flowing into t" }, { "name": "Battery 1 Real-time Power", "group": "Battery", "area": "input", "address": 33149, "type": "int32", "access": "R", "unit": "W", "description": "2. Power = -1,000 W; -1,000 (Dec) = 0xFFFCFC18 (Hex); thus, register 34344 data is 0xFFF, and register 33148 data is 0xFC18. Description: (1" }, { "name": "Inverter AC Grid Port Real-time Total Active Power", "group": "Battery", "area": "input", "address": 33151, "type": "int32", "access": "R", "unit": "W", "description": "Positive value: Power flowing out of the AC Grid port; Negative value: Power flowing into the AC Grid port 10<-->1V,Description: (1) For sin" }, { "name": "Backup Port AC Voltage B", "group": "Battery", "area": "input", "address": 33153, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1, "description": "systems," }, { "name": "Backup Port AC Current B", "group": "Battery", "area": "input", "address": 33154, "type": "uint16", "access": "R", "unit": "A", "scale": 0.1, "description": "For split-phase three-phase systems, systems, For" }, { "name": "Backup Port AC Voltage C", "group": "Battery", "area": "input", "address": 33155, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1, "description": "systems, For" }, { "name": "Backup Port AC Current C", "group": "Battery", "area": "input", "address": 33156, "type": "uint16", "access": "R", "unit": "A", "scale": 0.1, "description": "three-phase systems, For" }, { "name": "Battery Total Charging Energy", "group": "Battery", "area": "input", "address": 33161, "type": "uint32", "access": "R", "unit": "kWh", "description": "Description: For models with dual battery ports, this value represents the cumulative charging energy of both batteries." }, { "name": "Battery Daily Charging Energy", "group": "Battery", "area": "input", "address": 33163, "type": "uint16", "access": "R", "unit": "kWh", "scale": 0.1, "description": "Description: For models with dual battery ports, this value represents the cumulative charging energy of both batteries." }, { "name": "Battery Total Discharging Energy", "group": "Battery", "area": "input", "address": 33165, "type": "uint32", "access": "R", "unit": "kWh", "description": "Description: For models with dual battery ports, this value represents the cumulative charging energy of both batteries." }, { "name": "Battery Daily Discharging Energy", "group": "Battery", "area": "input", "address": 33167, "type": "uint16", "access": "R", "unit": "kWh", "scale": 0.1, "description": "Description: For models with dual battery ports, this value represents the cumulative charging energy of both batteries." }, { "name": "Grid Total Power Consumption", "group": "Battery", "area": "input", "address": 33169, "type": "uint32", "access": "R", "unit": "kWh", "description": "Represents Description: the cumulative energy consumed from the public grid" }, { "name": "Grid Daily Power Consumption", "group": "Battery", "area": "input", "address": 33171, "type": "uint16", "access": "R", "unit": "kWh", "scale": 0.1, "description": "Represents Description: the cumulative energy consumed from the public grid" }, { "name": "Grid Total Power Feed-in", "group": "Battery", "area": "input", "address": 33173, "type": "uint32", "access": "R", "unit": "kWh", "description": "Represents Description: the cumulative energy feed in to the public grid" }, { "name": "Grid Daily Power Feed-in", "group": "Battery", "area": "input", "address": 33175, "type": "uint16", "access": "R", "unit": "kWh", "scale": 0.1, "description": "Represents Description: the cumulative energy feed in to the public grid" }, { "name": "Load Total Power Consumption", "group": "Battery", "area": "input", "address": 33177, "type": "uint32", "access": "R", "unit": "kWh", "description": "Represents Description: the cumulative energy consumption of the Grid Load AND the Backup Load." }, { "name": "Load Daily Power Consumption", "group": "Battery", "area": "input", "address": 33179, "type": "uint16", "access": "R", "unit": "kWh", "scale": 0.1, "description": "Represents Description: the cumulative energy consumption of the Grid Load AND the Backup Load." }, { "name": "Inverter AC Grid Port Total Power Feed-in", "group": "Battery", "area": "input", "address": 33186, "type": "uint32", "access": "R", "unit": "kWh" }, { "name": "Inverter AC Grid Port Total Power Consumption", "group": "Battery", "area": "input", "address": 33188, "type": "uint32", "access": "R", "unit": "kWh" }, { "name": "Italian Single Test Function Setting (Italian Self-check Project - Single Item Self-check)", "group": "Operation", "area": "input", "address": 33221, "type": "uint16", "access": "R", "description": "0---Null 01---59.S1(253.0V 3000ms) 02---59.S2(264.5V 200ms) 03---27.S1(195.5V 1500ms) 04---27.S2( 34.5V 200ms) 05---81>.S1(50.2Hz 100ms) 06-" }, { "name": "Italian One-Key Full Test (Complete Self-check of Italian Self-check Items 01-10)", "group": "Operation", "area": "input", "address": 33222, "type": "uint16", "access": "R", "description": "Value: Start Complete Self Test 1—In single-item self-check state. 2—In one-key full-test state." }, { "name": "59.S1 Measurement Voltage Value", "group": "Operation", "area": "input", "address": 33223, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1 }, { "name": "59.S1 Measurement Time Value", "group": "Operation", "area": "input", "address": 33224, "type": "uint16", "access": "R", "unit": "ms" }, { "name": "59.S2 Measurement Voltage Value", "group": "Operation", "area": "input", "address": 33225, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1 }, { "name": "59.S2 Measurement Time Value", "group": "Operation", "area": "input", "address": 33226, "type": "uint16", "access": "R", "unit": "ms" }, { "name": "27.S1 Measurement Voltage Value", "group": "Operation", "area": "input", "address": 33227, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1 }, { "name": "27.S1 Measurement Time Value", "group": "Operation", "area": "input", "address": 33228, "type": "uint16", "access": "R", "unit": "ms" }, { "name": "27.S2 Measurement Voltage Value", "group": "Operation", "area": "input", "address": 33229, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1 }, { "name": "27.S2 Measurement Time Value", "group": "Operation", "area": "input", "address": 33230, "type": "uint16", "access": "R", "unit": "ms" }, { "name": "81>.S1 Measurement Frequency Value", "group": "Operation", "area": "input", "address": 33231, "type": "uint16", "access": "R", "unit": "Hz", "scale": 0.01 }, { "name": "81>.S1 Measurement Time Value", "group": "Operation", "area": "input", "address": 33232, "type": "uint16", "access": "R", "unit": "ms" }, { "name": "81<.S1 Measurement Frequency Value", "group": "Operation", "area": "input", "address": 33233, "type": "uint16", "access": "R", "unit": "Hz", "scale": 0.01 }, { "name": "81<.S1 Measurement Time Value", "group": "Operation", "area": "input", "address": 33234, "type": "uint16", "access": "R", "unit": "ms" }, { "name": "81>.S2F Measurement Frequency Value", "group": "Operation", "area": "input", "address": 33235, "type": "uint16", "access": "R", "unit": "Hz", "scale": 0.01 }, { "name": "81>.S2F Measurement Time Value", "group": "Operation", "area": "input", "address": 33236, "type": "uint16", "access": "R", "unit": "ms" }, { "name": "81<.S2F Measurement Frequency Value", "group": "Operation", "area": "input", "address": 33237, "type": "uint16", "access": "R", "unit": "Hz", "scale": 0.01 }, { "name": "81<.S2F Measurement Time Value", "group": "Operation", "area": "input", "address": 33238, "type": "uint16", "access": "R", "unit": "ms" }, { "name": "81>.S2S Measurement", "group": "Operation", "area": "input", "address": 33239, "type": "uint16", "access": "R", "unit": "Hz", "scale": 0.01 }, { "name": "Frequency Value 81>.S2S Measurement Time Value", "group": "Operation", "area": "input", "address": 33240, "type": "uint16", "access": "R", "unit": "ms" }, { "name": "81<.S2S Measurement Frequency Value", "group": "Operation", "area": "input", "address": 33241, "type": "uint16", "access": "R", "unit": "Hz", "scale": 0.01 }, { "name": "81<.S2S Measurement Time Value", "group": "Operation", "area": "input", "address": 33242, "type": "uint16", "access": "R", "unit": "ms" }, { "name": "Parallel Inverter Power", "group": "Operation", "area": "input", "address": 33245, "type": "uint16", "access": "R", "unit": "kW", "scale": 0.1, "description": "Applicable only low-voltage AC Coupled systems. to single-phase is greater than 500W," }, { "name": "Parallel Inverter CT Detection Switch", "group": "Operation", "area": "input", "address": 33246, "type": "uint16", "access": "R", "description": "Value: 0: Off. When register 33245 value it indicates that the parallel inverter has a CT installed and power is present. Value: 1: On. Rega" }, { "name": "Meter AC Voltage A", "group": "Operation", "area": "input", "address": 33251, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1, "description": "read from Registers 10<-->1V 33251~33286 (1) the represent data external meter/CT itself, when installed on the public grid side or the load" }, { "name": "Meter AC Current A", "group": "Operation", "area": "input", "address": 33252, "type": "uint16", "access": "R", "unit": "A", "scale": 0.01 }, { "name": "Meter AC Voltage B", "group": "Operation", "area": "input", "address": 33253, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1 }, { "name": "Meter AC Current B", "group": "Operation", "area": "input", "address": 33254, "type": "uint16", "access": "R", "unit": "A", "scale": 0.01 }, { "name": "Meter AC Voltage C", "group": "Operation", "area": "input", "address": 33255, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1 }, { "name": "Meter AC Current C", "group": "Operation", "area": "input", "address": 33256, "type": "uint16", "access": "R", "unit": "A", "scale": 0.01 }, { "name": "Meter Active Power A", "group": "Operation", "area": "input", "address": 33257, "type": "int32", "access": "R", "unit": "W", "description": "the external meter/CT 1000<-->1kW, Description: is When installed on the public grid side, a indicates power positive value flowing toward t" }, { "name": "Meter Active Power B", "group": "Operation", "area": "input", "address": 33259, "type": "int32", "access": "R", "unit": "W", "description": "1000<-->1kW, Description: When is installed on the public grid side, a positive value indicates power flowing toward the public grid, while " }, { "name": "Meter Active Power C", "group": "Operation", "area": "input", "address": 33261, "type": "int32", "access": "R", "unit": "W", "description": "the external meter/CT 1000<-->1kW, Description: is When installed on the public grid side, a positive value indicates power flowing toward t" }, { "name": "Meter Total Active Power", "group": "Operation", "area": "input", "address": 33263, "type": "int32", "access": "R", "unit": "W", "description": "the external meter/CT 1000<-->1kW, Description: When is installed on the public grid side, a positive value indicates power flowing toward t" }, { "name": "Meter Reactive Power A", "group": "Operation", "area": "input", "address": 33265, "type": "int32", "access": "R", "unit": "var" }, { "name": "Meter Reactive Power B", "group": "Operation", "area": "input", "address": 33267, "type": "int32", "access": "R", "unit": "var" }, { "name": "Meter Reactive Power C", "group": "Operation", "area": "input", "address": 33269, "type": "int32", "access": "R", "unit": "var" }, { "name": "Meter Total Reactive Power", "group": "Operation", "area": "input", "address": 33271, "type": "int32", "access": "R", "unit": "var" }, { "name": "Meter Apparent Power A", "group": "Operation", "area": "input", "address": 33273, "type": "int32", "access": "R", "unit": "VA" }, { "name": "Meter Apparent Power B", "group": "Operation", "area": "input", "address": 33275, "type": "int32", "access": "R", "unit": "VA" }, { "name": "Meter Apparent Power C", "group": "Operation", "area": "input", "address": 33277, "type": "int32", "access": "R", "unit": "VA" }, { "name": "Meter Total Apparent Power", "group": "Operation", "area": "input", "address": 33279, "type": "int32", "access": "R", "unit": "VA" }, { "name": "Meter Power Factor", "group": "Operation", "area": "input", "address": 33281, "type": "int16", "access": "R", "scale": 0.01, "description": "100<-->1.0 Range: -1.0~-0.8 , +0.8~+1.0" }, { "name": "Meter Grid Frequency", "group": "Operation", "area": "input", "address": 33282, "type": "uint16", "access": "R", "unit": "Hz", "scale": 0.01 }, { "name": "Meter Total Active Energy Imported from Grid", "group": "Operation", "area": "input", "address": 33283, "type": "uint32", "access": "R", "unit": "kWh", "scale": 0.01 }, { "name": "Meter Total Active Energy Exported to Grid", "group": "Operation", "area": "input", "address": 33285, "type": "uint32", "access": "R", "unit": "kWh", "scale": 0.01 }, { "name": "Optimal Revenue Function Version Identification", "group": "Operation", "area": "input", "address": 33289, "type": "uint16", "access": "R", "description": "Optimization Revenue V2 Function Enable Status: 0xAA55: Active; Others: Inactive" }, { "name": "Battery 1 BMS Real-time Status", "group": "Operation", "area": "input", "address": 33295, "type": "uint16", "access": "R", "description": "Charging 1—No bit00~01: Forced 0—Invalid, 2—Request, 3—Invalid bit02~03: Auxiliary 0—Invalid, 2—Request, 3—Invalid bit04~15: Reserved Heatin" }, { "name": "Meter 2 Total Active W Power", "group": "Operation", "area": "input", "address": 33314, "type": "int32", "access": "R", "description": "is 1000<-->1KW Notes: When register 43140 is set to 0x0304 or 0x0305, and the grid-tied the inverter secondary power meter, the total grid-s" }, { "name": "Parallel System Inverter Online Status", "group": "Operation", "area": "input", "address": 33388, "type": "uint16", "access": "R", "description": "Each BIT indicates the online status of the corresponding inverter ID. BIT00: Not used. BIT01~15: Indicate the online status of inverters wi" }, { "name": "Inverter Warning", "group": "Operation", "area": "input", "address": 33339, "type": "uint16", "access": "R", "description": "For details, refer to Appendix 4: Status Bit Definitions." }, { "name": "59.S1 Measurement Voltage Value (Phase B)", "group": "Operation", "area": "input", "address": 33470, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1, "description": "10<-->1V. Note: Registers 33470-33509 are used for the Phase B and Phase C results of the Italian CEI 0-21 standard self-test function and a" }, { "name": "59.S1 Measurement Time Value (Phase B)", "group": "Operation", "area": "input", "address": 33471, "type": "uint16", "access": "R", "unit": "ms" }, { "name": "59.S2 Measurement Voltage Value (Phase B)", "group": "Operation", "area": "input", "address": 33472, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1 }, { "name": "59.S2 Measurement Time Value (Phase B)", "group": "Operation", "area": "input", "address": 33473, "type": "uint16", "access": "R", "unit": "ms" }, { "name": "27.S1 Measurement Voltage Value (Phase B)", "group": "Operation", "area": "input", "address": 33474, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1 }, { "name": "27.S1 Measurement Time Value (Phase B)", "group": "Operation", "area": "input", "address": 33475, "type": "uint16", "access": "R", "unit": "ms" }, { "name": "27.S2 Measurement Voltage Value (Phase B)", "group": "Operation", "area": "input", "address": 33476, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1 }, { "name": "27.S2 Measurement Time Value (Phase B)", "group": "Operation", "area": "input", "address": 33477, "type": "uint16", "access": "R", "unit": "ms" }, { "name": "81>.S1 Measurement Frequency Value (Phase B)", "group": "Operation", "area": "input", "address": 33478, "type": "uint16", "access": "R", "unit": "Hz", "scale": 0.01 }, { "name": "81>.S1 Measurement Time Value (Phase B)", "group": "Operation", "area": "input", "address": 33479, "type": "uint16", "access": "R", "unit": "ms" }, { "name": "81<.S1 Measurement Frequency Value (Phase B)", "group": "Operation", "area": "input", "address": 33480, "type": "uint16", "access": "R", "unit": "Hz", "scale": 0.01 }, { "name": "81<.S1 Measurement Time Value (Phase B)", "group": "Operation", "area": "input", "address": 33481, "type": "uint16", "access": "R", "unit": "ms" }, { "name": "81>.S2F Measurement Frequency Value (Phase B)", "group": "Operation", "area": "input", "address": 33482, "type": "uint16", "access": "R", "unit": "Hz", "scale": 0.01 }, { "name": "81>.S2F Measurement Time Value (Phase B)", "group": "Operation", "area": "input", "address": 33483, "type": "uint16", "access": "R", "unit": "ms" }, { "name": "81<.S2F Measurement Frequency Value (Phase B)", "group": "Operation", "area": "input", "address": 33484, "type": "uint16", "access": "R", "unit": "Hz", "scale": 0.01 }, { "name": "81<.S2F Measurement Time Value (Phase B)", "group": "Operation", "area": "input", "address": 33485, "type": "uint16", "access": "R", "unit": "ms" }, { "name": "81>.S2S Measurement Frequency Value (Phase B)", "group": "Operation", "area": "input", "address": 33486, "type": "uint16", "access": "R", "unit": "Hz", "scale": 0.01 }, { "name": "81>.S2S Measurement Time Value (Phase B)", "group": "Operation", "area": "input", "address": 33487, "type": "uint16", "access": "R", "unit": "ms" }, { "name": "81<.S2S Measurement Frequency Value (Phase B)", "group": "Operation", "area": "input", "address": 33488, "type": "uint16", "access": "R", "unit": "Hz", "scale": 0.01 }, { "name": "81<.S2S Measurement Time Value (Phase B)", "group": "Operation", "area": "input", "address": 33489, "type": "uint16", "access": "R", "unit": "ms" }, { "name": "59.S1 Measurement Voltage Value (Phase C)", "group": "Operation", "area": "input", "address": 33490, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1 }, { "name": "59.S1 Measurement Time Value (Phase C)", "group": "Operation", "area": "input", "address": 33491, "type": "uint16", "access": "R", "unit": "ms" }, { "name": "59.S2 Measurement Voltage Value (Phase C)", "group": "Operation", "area": "input", "address": 33492, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1 }, { "name": "59.S2 Measurement Time Value (Phase C)", "group": "Operation", "area": "input", "address": 33493, "type": "uint16", "access": "R", "unit": "ms" }, { "name": "27.S1 Measurement Voltage Value (Phase C)", "group": "Operation", "area": "input", "address": 33494, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1 }, { "name": "27.S1 Measurement Time Value (Phase C)", "group": "Operation", "area": "input", "address": 33495, "type": "uint16", "access": "R", "unit": "ms" }, { "name": "27.S2 Measurement Voltage Value (Phase C)", "group": "Operation", "area": "input", "address": 33496, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1 }, { "name": "27.S2 Measurement Time Value (Phase C)", "group": "Operation", "area": "input", "address": 33497, "type": "uint16", "access": "R", "unit": "ms" }, { "name": "81>.S1 Measurement Frequency Value (Phase C)", "group": "Operation", "area": "input", "address": 33498, "type": "uint16", "access": "R", "unit": "Hz", "scale": 0.01 }, { "name": "81>.S1 Measurement Time Value (Phase C)", "group": "Operation", "area": "input", "address": 33499, "type": "uint16", "access": "R", "unit": "ms" }, { "name": "81<.S1 Measurement Frequency Value (Phase C)", "group": "Operation", "area": "input", "address": 33500, "type": "uint16", "access": "R", "unit": "Hz", "scale": 0.01 }, { "name": "81<.S1 Measurement Time Value (Phase C)", "group": "Operation", "area": "input", "address": 33501, "type": "uint16", "access": "R", "unit": "ms" }, { "name": "81>.S2F Measurement Frequency Value (Phase C)", "group": "Operation", "area": "input", "address": 33502, "type": "uint16", "access": "R", "unit": "Hz", "scale": 0.01 }, { "name": "81>.S2F Measurement Time Value (Phase C)", "group": "Operation", "area": "input", "address": 33503, "type": "uint16", "access": "R", "unit": "ms" }, { "name": "81<.S2F Measurement Frequency Value (Phase C)", "group": "Operation", "area": "input", "address": 33504, "type": "uint16", "access": "R", "unit": "Hz", "scale": 0.01 }, { "name": "81<.S2F Measurement Time Value (Phase C)", "group": "Operation", "area": "input", "address": 33505, "type": "uint16", "access": "R", "unit": "ms" }, { "name": "81>.S2S Measurement Frequency Value (Phase C)", "group": "Operation", "area": "input", "address": 33506, "type": "uint16", "access": "R", "unit": "Hz", "scale": 0.01 }, { "name": "81>.S2S Measurement Time Value (Phase C)", "group": "Operation", "area": "input", "address": 33507, "type": "uint16", "access": "R", "unit": "ms" }, { "name": "81<.S2S Measurement Frequency Value (Phase C)", "group": "Operation", "area": "input", "address": 33508, "type": "uint16", "access": "R", "unit": "Hz", "scale": 0.01 }, { "name": "81<.S2S Measurement Time Value (Phase C)", "group": "Operation", "area": "input", "address": 33509, "type": "uint16", "access": "R", "unit": "ms" }, { "name": "Inverter AC Grid Port Phase A Active Power", "group": "Operation", "area": "input", "address": 33512, "type": "int16", "access": "R", "unit": "W", "scale": 10.0, "description": "into Positive value indicates power flowing out of the energy storage inverter, negative value indicates power flowing the energy storage in" }, { "name": "Inverter AC Grid Port Phase A Reactive Power", "group": "Operation", "area": "input", "address": 33513, "type": "int16", "access": "R", "unit": "var", "scale": 10.0, "description": "Range: -327680Var~327680Var" }, { "name": "Inverter AC Grid Port Phase A Apparent Power", "group": "Operation", "area": "input", "address": 33514, "type": "int16", "access": "R", "unit": "VA", "scale": 10.0, "description": "Range: 0VA~327680VA" }, { "name": "Inverter AC Grid Port Phase B Active Power", "group": "Operation", "area": "input", "address": 33515, "type": "int16", "access": "R", "unit": "W", "scale": 10.0, "description": "Positive value indicates power flowing out of the energy storage inverter, negative value indicates power flowing the energy storage in-vert" }, { "name": "Inverter AC Grid Port Phase B Reactive Power", "group": "Operation", "area": "input", "address": 33516, "type": "int16", "access": "R", "unit": "var", "scale": 10.0, "description": "Range: -327680Var~327680Var" }, { "name": "Inverter AC Grid Port Phase B Apparent Power", "group": "Operation", "area": "input", "address": 33517, "type": "int16", "access": "R", "unit": "VA", "scale": 10.0, "description": "Range: 0VA~327680VA" }, { "name": "Inverter AC Grid Port Phase C Active Power", "group": "Operation", "area": "input", "address": 33518, "type": "int16", "access": "R", "unit": "W", "scale": 10.0, "description": "Positive value indicates power flowing out of the energy storage inverter, negative value indicates power flowing the energy storage inverte" }, { "name": "Inverter AC Grid Port Phase C Reactive Power", "group": "Operation", "area": "input", "address": 33519, "type": "int16", "access": "R", "unit": "var", "scale": 10.0, "description": "Range: -327680Var~327680Var" }, { "name": "Inverter AC Grid Port Phase C Apparent Power", "group": "Operation", "area": "input", "address": 33520, "type": "int16", "access": "R", "unit": "VA", "scale": 10.0, "description": "Range: 0VA~327680VA" }, { "name": "Inverter Backup Port Phase A Active Power", "group": "Operation", "area": "input", "address": 33521, "type": "int16", "access": "R", "unit": "W", "scale": 10.0, "description": "A positive value indicates power flowing out of the Backup port, while a negative value indicates power flowing into the Backup port. Range:" }, { "name": "Inverter Backup Port Phase A Reactive Power", "group": "Operation", "area": "input", "address": 33522, "type": "int16", "access": "R", "unit": "var", "scale": 10.0, "description": "Range: -327680Var~327680Var For U.S. models, it represents the reactive power calculated using L1-N voltage and L1 current. Range: 0VA~32768" }, { "name": "Inverter Backup Port Phase A Apparent Power", "group": "Operation", "area": "input", "address": 33523, "type": "int16", "access": "R", "unit": "VA", "scale": 10.0 }, { "name": "Inverter Backup Port Phase B Active Power", "group": "Operation", "area": "input", "address": 33524, "type": "int16", "access": "R", "unit": "W", "scale": 10.0, "description": "A positive value indicates power flowing out of the Backup port, while a negative value indicates power flowing into the Backup port. Range:" }, { "name": "Inverter Backup Port Phase B Reactive Power", "group": "Operation", "area": "input", "address": 33525, "type": "int16", "access": "R", "unit": "var", "scale": 10.0, "description": "Range: -327680Var~327680Var For U.S. models, it represents the reactive power calculated using L2-N voltage and L2 current. Range: 0VA~32768" }, { "name": "Inverter Backup Port Phase B Apparent Power", "group": "Operation", "area": "input", "address": 33526, "type": "int16", "access": "R", "unit": "VA", "scale": 10.0 }, { "name": "Inverter Backup Port Phase C Active Power", "group": "Operation", "area": "input", "address": 33527, "type": "int16", "access": "R", "unit": "W", "scale": 10.0, "description": "A positive value indicates power flowing out of the Backup port, while a negative value indicates power flowing into the Backup port. Range:" }, { "name": "Inverter Backup Port Phase C Reactive Power", "group": "Operation", "area": "input", "address": 33528, "type": "int16", "access": "R", "unit": "var", "scale": 10.0, "description": "Range: -327680Var~327680Var For U.S. models, the value is 0." }, { "name": "Inverter Backup Side Phase C Apparent Power", "group": "Operation", "area": "input", "address": 33529, "type": "int16", "access": "R", "unit": "VA", "scale": 10.0, "description": "Range: 0VA~327680VA; For U.S. models, the value is 0." }, { "name": "Generator Phase A Active Power", "group": "Operation", "area": "input", "address": 33530, "type": "int16", "access": "R", "unit": "W", "scale": 10.0, "description": "Single-phase systems use Phase A power." }, { "name": "Generator Daily Power Generation", "group": "Operation", "area": "input", "address": 33531, "type": "uint16", "access": "R", "unit": "kWh", "scale": 0.1 }, { "name": "Generator Total Power Generation", "group": "Operation", "area": "input", "address": 33532, "type": "uint32", "access": "R", "unit": "kWh" }, { "name": "Generator Phase B Active Power", "group": "Operation", "area": "input", "address": 33534, "type": "int16", "access": "R", "unit": "W", "scale": 10.0 }, { "name": "Generator Phase C Active Power", "group": "Operation", "area": "input", "address": 33535, "type": "int16", "access": "R", "unit": "W", "scale": 10.0 }, { "name": "Inverter AC Grid Port Daily Power Export", "group": "Operation", "area": "input", "address": 33577, "type": "uint16", "access": "R", "unit": "kWh", "scale": 0.1 }, { "name": "Inverter AC Grid Port Daily Power Import", "group": "Operation", "area": "input", "address": 33578, "type": "uint16", "access": "R", "unit": "kWh", "scale": 0.1 }, { "name": "Grid Load Total Power Consumption", "group": "Operation", "area": "input", "address": 33580, "type": "uint32", "access": "R", "unit": "kWh" }, { "name": "Grid Load Daily Power Consumption", "group": "Operation", "area": "input", "address": 33586, "type": "uint16", "access": "R", "unit": "kWh", "scale": 0.1 }, { "name": "Backup Load Total Power Consumption", "group": "Operation", "area": "input", "address": 33590, "type": "uint32", "access": "R", "unit": "kWh", "description": "Standalone Mode: Represents the energy flowing out of the local unit's Backup port. Parallel Mode: The master unit's Backup load energy data" }, { "name": "Backup Load Daily Power Consumption", "group": "Operation", "area": "input", "address": 33596, "type": "uint16", "access": "R", "unit": "kWh", "scale": 0.1 }, { "name": "LG Battery 10H/16H Master Battery SOC", "group": "Battery", "area": "input", "address": 34200, "type": "uint16", "access": "R", "scale": 0.001, "description": "1000<-->100% From LG High Voltage Battery BMS" }, { "name": "LG Battery 10H/16H Master Battery SOH", "group": "Battery", "area": "input", "address": 34201, "type": "uint16", "access": "R", "scale": 0.001 }, { "name": "LG Battery 10H/16H Master Battery Voltage", "group": "Battery", "area": "input", "address": 34202, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1 }, { "name": "LG Battery 10H/16H Master Battery Current", "group": "Battery", "area": "input", "address": 34203, "type": "int16", "access": "R", "unit": "V", "scale": 0.1, "description": "10<-->1A Positive indicates charging, negative indicates discharging." }, { "name": "LG Battery 10H/16H Master Battery Maximum Charging Power", "group": "Battery", "area": "input", "address": 34204, "type": "uint16", "access": "R", "unit": "W" }, { "name": "LG Battery 10H/16H Master Battery Maximum Discharging Power", "group": "Battery", "area": "input", "address": 34205, "type": "uint16", "access": "R", "unit": "W" }, { "name": "LG Battery 10H/16H Master Battery DCDC Firmware Version (Main)", "group": "Battery", "area": "input", "address": 34206, "type": "uint16", "access": "R" }, { "name": "LG Battery 10H/16H Master Battery DCDC Firmware Version (Test)", "group": "Battery", "area": "input", "address": 34207, "type": "uint16", "access": "R" }, { "name": "LG Battery 10H/16H Master Battery BMS Firmware Version High Byte", "group": "Battery", "area": "input", "address": 34208, "type": "uint16", "access": "R" }, { "name": "LG Battery 10H/16H Master Battery BMS Firmware Version Low Byte", "group": "Battery", "area": "input", "address": 34209, "type": "uint16", "access": "R" }, { "name": "LG Battery 10H/16H Master Battery Fault ID", "group": "Battery", "area": "input", "address": 34210, "type": "uint16", "access": "R" }, { "name": "LG Battery 10H/16H Master Battery Diagnostic Result", "group": "Battery", "area": "input", "address": 34211, "type": "uint16", "access": "R", "description": "0: No abnormality detected 1: Level 1 Warning – Warning1 battery available (limits charging/discharging power) 2: Level 2 Warning – Warning2" }, { "name": "LG Battery 10H/16H Master Battery Status/Mode", "group": "Battery", "area": "input", "address": 34212, "type": "uint16", "access": "R", "description": "0: Initial State 1: Standby State 3: Operation State 4: Update State (battery firmware update via inverter) recover (cannot 5: Fault State a" }, { "name": "LG Battery 10H/16H Master Battery Current Power", "group": "Battery", "area": "input", "address": 34213, "type": "int16", "access": "R", "unit": "W", "description": "1<-->1W Positive value indicates charging." }, { "name": "LG Battery 10H/16H Master Battery Maximum Temperature", "group": "Battery", "area": "input", "address": 34214, "type": "int16", "access": "R", "unit": "Degc", "scale": 0.1 }, { "name": "LG Battery 10H/16H Master Battery Status Flags", "group": "Battery", "area": "input", "address": 34215, "type": "uint16", "access": "R", "description": "BIT00: Full Charge Flag – 0: Not fully charged, 1: Fully charged BIT01: Full Discharge Flag – 0: Not fully discharged, 1: Fully discharged B" }, { "name": "LG Battery 10H/16H Secondary Battery SOC", "group": "Battery", "area": "input", "address": 34216, "type": "uint16", "access": "R", "scale": 0.001, "description": "1000<-->100% From LG High Voltage Battery BMS" }, { "name": "LG Battery 10H/16H Secondary Battery SOH", "group": "Battery", "area": "input", "address": 34217, "type": "uint16", "access": "R", "scale": 0.001 }, { "name": "LG Battery 10H/16H Secondary Battery Voltage", "group": "Battery", "area": "input", "address": 34218, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1 }, { "name": "LG Battery 10H/16H Secondary Battery Current", "group": "Battery", "area": "input", "address": 34219, "type": "int16", "access": "R", "unit": "A", "scale": 0.1, "description": "10<-->1A Positive indicates charging, negative indicates discharging." }, { "name": "LG Battery 10H/16H Secondary Battery Maximum Charging Power", "group": "Battery", "area": "input", "address": 34220, "type": "uint16", "access": "R", "unit": "W" }, { "name": "LG Battery 10H/16H Secondary Battery Maximum Discharging Power", "group": "Battery", "area": "input", "address": 34221, "type": "uint16", "access": "R", "unit": "W" }, { "name": "LG Battery 10H/16H Secondary Battery DCDC Firmware Version (Main)", "group": "Battery", "area": "input", "address": 34222, "type": "uint16", "access": "R" }, { "name": "LG Battery 10H/16H Secondary Battery", "group": "Battery", "area": "input", "address": 34223, "type": "uint16", "access": "R" }, { "name": "DCDC Firmware Version (Test) LG Battery 10H/16H Secondary Battery BMS Firmware Version High Byte", "group": "Battery", "area": "input", "address": 34224, "type": "uint16", "access": "R" }, { "name": "LG Battery 10H/16H Secondary Battery BMS Firmware Version Low Byte", "group": "Battery", "area": "input", "address": 34225, "type": "uint16", "access": "R" }, { "name": "LG Battery 10H/16H Secondary Battery Fault ID", "group": "Battery", "area": "input", "address": 34226, "type": "uint16", "access": "R" }, { "name": "LG Battery 10H/16H Secondary Battery Diagnostic Result", "group": "Battery", "area": "input", "address": 34227, "type": "uint16", "access": "R", "description": "0: No abnormality detected 1: Level 1 Warning – Warning1 (limits battery available charging/discharging power) 2: Level 2 Warning – Warning2" }, { "name": "LG Battery 10H/16H Secondary Battery Status/Mode", "group": "Battery", "area": "input", "address": 34228, "type": "uint16", "access": "R", "description": "0: Initial State 1: Standby State 3: Operation State 4: Update State (battery firmware update via inverter) 5: Fault State automatically) 6:" }, { "name": "LG Battery 10H/16H Secondary Battery Current Power", "group": "Battery", "area": "input", "address": 34229, "type": "int16", "access": "R", "unit": "W", "description": "1<-->1W Positive value indicates charging." }, { "name": "LG Battery 10H/16H Secondary Battery Maximum Temperature", "group": "Battery", "area": "input", "address": 34230, "type": "int16", "access": "R", "unit": "°C", "scale": 0.1 }, { "name": "LG Battery 10H/16H Secondary Battery Status Flags", "group": "Battery", "area": "input", "address": 34231, "type": "uint16", "access": "R", "description": "BIT00: Full Charge Flag – 0: Not fully charged, 1: Fully charged BIT01: Full Discharge Flag – 0: Not fully discharged, 1: Fully discharged B" }, { "name": "AFCI Board Software Version", "group": "Battery", "area": "input", "address": 34240, "type": "uint16", "access": "R", "description": "(Displayed in Hexadecimal) Description: This version number of detection board. The high byte represents the major version number of the AFC" }, { "name": "BMS2 Temperature", "group": "Battery", "area": "input", "address": 34277, "type": "int16", "access": "R", "unit": "°C", "scale": 0.1, "description": "Description: Data from Battery 2 BMS. BMS2 data is only applicable to energy storage models supporting dual batteries." }, { "name": "BMS2 SOC", "group": "Battery", "area": "input", "address": 34278, "type": "uint16", "access": "R", "unit": "%", "description": "Description: From Battery 2 BMS." }, { "name": "BMS2 SOH", "group": "Battery", "area": "input", "address": 34279, "type": "uint16", "access": "R", "unit": "%", "description": "Description: From Battery 2 BMS." }, { "name": "BMS2 Charging Voltage Limit", "group": "Battery", "area": "input", "address": 34280, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1, "description": "Description: From Battery 2 BMS." }, { "name": "BMS2 Charging Current Limit", "group": "Battery", "area": "input", "address": 34281, "type": "uint16", "access": "R", "unit": "A", "scale": 0.1, "description": "Description: From Battery 2 BMS." }, { "name": "BMS2 Discharging Current Limit", "group": "Battery", "area": "input", "address": 34282, "type": "uint16", "access": "R", "unit": "A", "scale": 0.1, "description": "Description: From Battery 2 BMS." }, { "name": "Battery 2 Real-time Voltage Value", "group": "Battery", "area": "input", "address": 34289, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1, "description": "Description: Battery 2 Real-time Voltage Value. Inverter Battery 2 data is only applicable to energy storage models supporting dual batterie" }, { "name": "Battery 2 Real-time Current Value", "group": "Battery", "area": "input", "address": 34290, "type": "int16", "access": "R", "unit": "A", "scale": 0.1, "description": "Description: (1) The charge/discharge direction is determined by register 34291. (2) The absolute value of register the represents current v" }, { "name": "Battery 2 Real-time Charge/Discharge Direction", "group": "Battery", "area": "input", "address": 34291, "type": "uint16", "access": "R", "description": "0: Charging 1: Discharging" }, { "name": "Smartport Phase A AC Voltage", "group": "Battery", "area": "input", "address": 34328, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1, "description": "Registers 34328~34333 represent the real-time voltage and current of the Smart Port (which can be configured as a generator, smart load, or " }, { "name": "Smartport Phase B AC Voltage", "group": "Battery", "area": "input", "address": 34329, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1 }, { "name": "Smartport Phase C AC Voltage", "group": "Battery", "area": "input", "address": 34330, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1 }, { "name": "Smartport Phase A AC Current", "group": "Battery", "area": "input", "address": 34331, "type": "uint16", "access": "R", "unit": "A", "scale": 0.1 }, { "name": "Smartport Phase B AC Current", "group": "Battery", "area": "input", "address": 34332, "type": "uint16", "access": "R", "unit": "A", "scale": 0.1 }, { "name": "Smartport Phase C AC Current", "group": "Battery", "area": "input", "address": 34333, "type": "uint16", "access": "R", "unit": "A", "scale": 0.1 }, { "name": "Grid Load Power (High Register)", "group": "Battery", "area": "input", "address": 34343, "type": "uint16", "access": "R", "unit": "W", "description": "Combined with register 33147 to form the grid load power. Example: Power = 700,000 W, 700,000 (Dec) = 0x00011170 (Hex). Therefore, register " }, { "name": "Backup Load Power (High Register)", "group": "Battery", "area": "input", "address": 34344, "type": "int16", "access": "R", "unit": "W", "description": "Combined with register 33148 to form the Backup load power. Examples: 1. Power = 700,000 W, 700,000 (Dec) = 0x00011170 (Hex). Thus, register" }, { "name": "Battery 1 BMS Minimum Cell Voltage", "group": "Battery", "area": "input", "address": 34348, "type": "uint16", "access": "R", "unit": "V", "scale": 0.001, "description": "2. Power = -1,000 W, -1,000 (Dec) = 0xFFFFFC18 (Hex). Thus, register 34344 data is 0xFFFF, is and register 33148 data 0xFC18." }, { "name": "Battery 1 BMS Maximum Cell Voltage", "group": "Battery", "area": "input", "address": 34349, "type": "uint16", "access": "R", "unit": "V", "scale": 0.001 }, { "name": "Battery 1 BMS Minimum Cell Temperature", "group": "Battery", "area": "input", "address": 34350, "type": "int16", "access": "R", "unit": "°C", "scale": 0.1 }, { "name": "Battery 1 BMS Maximum Cell Temperature", "group": "Battery", "area": "input", "address": 34351, "type": "int16", "access": "R", "unit": "°C", "scale": 0.1 }, { "name": "HMI-LCD Firmware Version", "group": "Battery", "area": "input", "address": 34367, "type": "uint16", "access": "R", "description": "High Byte: Major Version Number Low Byte: Minor Version Number" }, { "name": "Battery 2 Real-time Power Value", "group": "Battery", "area": "input", "address": 34368, "type": "int32", "access": "R", "unit": "W", "description": "Description: (1) The charge/discharge direction is determined by register 34291. (2) The absolute value of the represents register power val" }, { "name": "BMS2 Discharge Voltage Limit Value", "group": "Battery", "area": "input", "address": 34371, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1, "description": "Description: From Battery 2 BMS." }, { "name": "BMS2 Minimum Cell Voltage", "group": "Battery", "area": "input", "address": 34373, "type": "uint16", "access": "R", "unit": "V", "scale": 0.001 }, { "name": "BMS2 Maximum Cell Voltage", "group": "Battery", "area": "input", "address": 34374, "type": "uint16", "access": "R", "unit": "V", "scale": 0.001 }, { "name": "BMS2 Minimum Cell Temperature", "group": "Battery", "area": "input", "address": 34375, "type": "uint16", "access": "R", "unit": "°C", "scale": 0.1 }, { "name": "BMS2 Maximum Cell Temperature", "group": "Battery", "area": "input", "address": 34376, "type": "uint16", "access": "R", "unit": "°C", "scale": 0.1 }, { "name": "Smart Port Phase A Active Power (for connected smart load or grid-tied inverter)", "group": "Battery", "area": "input", "address": 34391, "type": "int16", "access": "R", "unit": "W", "scale": 10.0, "description": "A positive value indicates power flowing out of the energy storage inverter's Smart Port, while a indicates power negative value flowing int" }, { "name": "Smart Port Phase B Active Power (connected smart load or grid-tied inverter)", "group": "Battery", "area": "input", "address": 34392, "type": "int16", "access": "R", "unit": "W", "scale": 10.0, "description": "Positive values indicate power flowing out of the energy storage inverter's Smart Port; negative values indicate power flowing into the Smar" }, { "name": "Smart Port Phase C Active Power (connected smart load or grid-tied inverter)", "group": "Battery", "area": "input", "address": 34393, "type": "int16", "access": "R", "unit": "W", "scale": 10.0, "description": "indicate power Positive values flowing out of the energy storage inverter's Smart Port; negative values indicate power flowing into the Smar" }, { "name": "Generator Frequency", "group": "Battery", "area": "input", "address": 34410, "type": "uint16", "access": "R", "unit": "Hz", "scale": 0.01 }, { "name": "Smart Load Total Power Consumption", "group": "Battery", "area": "input", "address": 34411, "type": "uint32", "access": "R", "unit": "kWh", "description": "For parallel systems, the data in this register of the master unit represents the total power consumption of the Smart load in the parallel " }, { "name": "Smart Load Daily Power Consumption", "group": "Battery", "area": "input", "address": 34413, "type": "uint32", "access": "R", "unit": "kWh", "description": "For parallel systems, the data in this register of the master unit represents the daily power consumption of the Smart load in the parallel " }, { "name": "Grid Load Phase A Active Power", "group": "Battery", "area": "input", "address": 34424, "type": "uint16", "access": "R", "unit": "W", "scale": 10.0, "description": "Currently only supports the S6 generation of three-phase energy storage machines." }, { "name": "Grid Load Phase B Active Power", "group": "Battery", "area": "input", "address": 34425, "type": "uint16", "access": "R", "unit": "W", "scale": 10.0, "description": "Currently only supports the S6 generation of three-phase energy storage machines." }, { "name": "Grid Load Phase C Active Power", "group": "Battery", "area": "input", "address": 34426, "type": "uint16", "access": "R", "unit": "W", "scale": 10.0, "description": "Currently only supports the S6 generation of three-phase energy storage machines." }, { "name": "Parallel System Information Valid Flag", "group": "Battery", "area": "input", "address": 34427, "type": "uint16", "access": "R", "description": "(registers 0xAA55 – Parallel system power values 34428~34434, 34490~34491) are valid. Any other value – invalid." }, { "name": "Parallel System Total PV Power", "group": "Battery", "area": "input", "address": 34428, "type": "int16", "access": "R", "unit": "W", "scale": 100.0 }, { "name": "Parallel System Total Generator Active Power", "group": "Battery", "area": "input", "address": 34429, "type": "int16", "access": "R", "unit": "W", "scale": 100.0 }, { "name": "Parallel System Total Battery Power", "group": "Battery", "area": "input", "address": 34430, "type": "int16", "access": "R", "unit": "W", "scale": 100.0, "description": "indicates battery Positive value charging, negative value indicates battery discharging." }, { "name": "Parallel System Total Backup Load Active Power", "group": "Battery", "area": "input", "address": 34431, "type": "int16", "access": "R", "unit": "w", "scale": 100.0 }, { "name": "Parallel System Total Inverter Active Power", "group": "Battery", "area": "input", "address": 34432, "type": "int16", "access": "R", "unit": "w", "scale": 100.0, "description": "indicates power Positive value flowing toward the grid, negative value indicates power being drawn from the grid." }, { "name": "Parallel System Total Smart Load Active Power", "group": "Battery", "area": "input", "address": 34433, "type": "int16", "access": "R", "unit": "w", "scale": 100.0, "description": "Positive value indicates power flowing out of the Smart Port, negative value indicates power flowing into the Smart Port." }, { "name": "Parallel System AC Couple Total Active Power", "group": "Battery", "area": "input", "address": 34434, "type": "int16", "access": "R", "unit": "w", "scale": 100.0, "description": "Positive value indicates power flowing out of the AC Coupling port, negative value indicates power flowing into the AC Coupling port. storag" }, { "name": "AC Coupling Total Power Generation", "group": "Battery", "area": "input", "address": 34445, "type": "uint32", "access": "R", "unit": "kWh", "description": "Indicates the energy output from the grid-tied the energy storage system after the Smart Port of the energy storage inverter is configured f" }, { "name": "AC Coupling Daily Power Generation", "group": "Battery", "area": "input", "address": 34451, "type": "uint16", "access": "R", "unit": "kWh", "scale": 0.1 }, { "name": "Parallel System Grid Load Total Active Power", "group": "Battery", "area": "input", "address": 34490, "type": "int16", "access": "R", "unit": "W", "scale": 100.0 }, { "name": "Parallel System Public Grid Total Active Power", "group": "Battery", "area": "input", "address": 34491, "type": "int16", "access": "R", "unit": "W", "scale": 100.0, "description": "Positive value indicates power flowing toward the grid, negative value indicates power being drawn from the grid." }, { "name": "PV DC Voltage 9", "group": "Battery", "area": "input", "address": 34498, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1 }, { "name": "PV DC Current 9", "group": "Battery", "area": "input", "address": 34499, "type": "uint16", "access": "R", "unit": "A", "scale": 0.1 }, { "name": "PV DC Voltage 10", "group": "Battery", "area": "input", "address": 34500, "type": "uint16", "access": "R", "unit": "V", "scale": 0.1 }, { "name": "PV DC Current 10", "group": "Battery", "area": "input", "address": 34501, "type": "uint16", "access": "R", "unit": "A", "scale": 0.1 }, { "name": "Remote Dispatch Mode Valid Flag", "group": "Battery", "area": "input", "address": 34502, "type": "uint16", "access": "R", "description": "0xAA55: Remote Dispatch Mode available within address range 44100~44199 Others: Invalid 0x0001: Represents Version V01, the initial version." }, { "name": "Remote Dispatch Mode Function Version", "group": "Battery", "area": "input", "address": 34503, "type": "uint16", "access": "R", "description": "timing control, control modes 5 and 6 are added to register 44105/44119. In real-time control and timing control, enable switches for batter" }, { "name": "Remote Dispatch Mode Running Status", "group": "Battery", "area": "input", "address": 34504, "type": "uint16", "access": "R", "description": "0x01: Battery Standby Control 0x02: Battery Charge/Discharge Control 0x03: Grid Connection Point Import/Export Control 0x04: AC Grid Port Im" }, { "name": "Parallel System AC Grid Port Total Active Power", "group": "Battery", "area": "input", "address": 34537, "type": "int16", "access": "R", "unit": "w", "scale": 100.0, "description": "Control 0x05: Self-use Priority Control 0x06: Grid Feed-in Priority Control indicates power Positive value flowing out of the AC Grid port; " }, { "name": "Battery 2 BMS Real-time Status", "group": "Battery", "area": "input", "address": 34578, "type": "uint16", "access": "R", "description": "bits 00–01: Forced charging request – 0: invalid, 1: no request, 2: request, 3: invalid bits 02–03: Auxiliary heating request – 0: invalid, " }, { "name": "Generator Preheat/Cooling Operation Status", "group": "Battery", "area": "input", "address": 34590, "type": "uint16", "access": "R", "description": "1: Generator Stopped 2: Generator Supplying Power 3: Generator Preheating 4: Generator Cooling 5–65535: Invalid" }, { "name": "Module ID 1 [For each ports’ power values (For this device)]", "group": "Battery", "area": "input", "address": 34600, "type": "uint16", "access": "R", "description": "0x0001 indicates the power values of this unit's ports. Any other value is invalid. Description: (1) The content of Module 1 was added from " }, { "name": "Module 1 Register Count", "group": "Battery", "area": "input", "address": 34601, "type": "uint16", "access": "R", "description": "Low byte: Number of valid registers in 34602~34649, not exceeding 48. High byte: Reserved, default 0x00. Note: When Module 1 is active, the " }, { "name": "Valid Identifier – For each ports’ power values (For this device)", "group": "Battery", "area": "input", "address": 34602, "type": "uint16", "access": "R", "description": "0xAA55 – The power values of this unit's ports (registers 34603~34649) are valid. Any other value – invalid." }, { "name": "PV Power", "group": "Battery", "area": "input", "address": 34603, "type": "int32", "access": "R", "unit": "W", "description": "Positive values are valid; negative values are invalid. 0x80000000 indicates invalid. Note: For models without a PV port (e.g., AC Coupled)," }, { "name": "Battery 1 Power", "group": "Battery", "area": "input", "address": 34605, "type": "int32", "access": "R", "unit": "W", "description": "Positive value indicates charging; indicates value negative discharging. 0x80000000 indicates invalid." }, { "name": "Battery 2 Power", "group": "Battery", "area": "input", "address": 34607, "type": "int32", "access": "R", "unit": "W", "description": "Positive value indicates charging; negative indicates value discharging. 0x80000000 indicates invalid. Description: Only applicable to model" }, { "name": "Inverting Bridge Total Active Power", "group": "Battery", "area": "input", "address": 34609, "type": "int32", "access": "R", "unit": "W", "description": "Positive value indicates feeding power to the grid; negative value indicates drawing power from the grid. 0x80000000 indicates invalid." }, { "name": "Backup Load Total Active Power", "group": "Battery", "area": "input", "address": 34611, "type": "int32", "access": "R", "unit": "W", "description": "Positive value indicates power flowing out of the Backup port; indicates power negative value flowing into the Backup port. 0x80000000 indic" }, { "name": "Backup Load Total Apparent Power", "group": "Battery", "area": "input", "address": 34613, "type": "int32", "access": "R", "unit": "VA", "description": "Positive values are valid; negative values are invalid. 0x80000000 indicates invalid." }, { "name": "Inverter AC Grid Port Total Active Power", "group": "Battery", "area": "input", "address": 34615, "type": "int32", "access": "R", "unit": "W", "description": "Positive value indicates power flowing out of the energy storage inverter; negative value indicates power flowing the energy storage inverte" }, { "name": "Generator Total Active Power (34617)", "group": "Battery", "area": "input", "address": 34617, "type": "int32", "access": "R", "unit": "W", "description": "Positive values are valid; negative values are invalid. 0x80000000 indicates invalid. Note: When no generator is connected, this register is" }, { "name": "Smart Load Total Active Power", "group": "Battery", "area": "input", "address": 34619, "type": "int32", "access": "R", "unit": "W", "description": "Positive value indicates power flowing out of the Smart port; indicates power negative value flowing into the Smart port. 0x80000000 indicat" }, { "name": "Grid-tied Inverter Output Total Active Power 34623~ Grid Load Total Active", "group": "Battery", "area": "input", "address": 34621, "type": "int32", "access": "R", "unit": "W", "description": "Positive values are valid; negative values are invalid. 0x80000000 indicates invalid. Note: When no grid‑tied inverter is connected, this re" }, { "name": "Public Grid Total Active Power", "group": "Battery", "area": "input", "address": 34625, "type": "int32", "access": "R", "unit": "W", "description": "Positive value indicates feeding power to the grid; negative value indicates drawing power from the grid. 0x80000000 indicates invalid. Note" }, { "name": "Local PV Power", "group": "Operation", "area": "input", "address": 34753, "type": "int32", "access": "R", "unit": "W" }, { "name": "Total Power of the Local Battery", "group": "Operation", "area": "input", "address": 34755, "type": "int32", "access": "R", "unit": "W" }, { "name": "Total Active Power of the Local AC Grid Port", "group": "Operation", "area": "input", "address": 34765, "type": "int32", "access": "R", "unit": "W" }, { "name": "Parallel System PV Power Value Parallel System Battery Charge/Discharge Power Value Parallel System AC Grid Port Active Power Value Parallel System PCC Active Power Value", "group": "Operation", "area": "input", "address": 34781, "type": "int32", "access": "R", "unit": "W", "description": "+:Charge power -: Discharge power" }, { "name": "Max Battery SOC Of Parallel System", "group": "Operation", "area": "input", "address": 34797, "type": "uint16", "access": "R", "unit": "W", "description": "0: no battery 1~100: battery SOC 101~65535: Invalid Note: Refers to the maximum SOC of each battery in the parallel system. 0: no battery 1~" }, { "name": "Min Battery SOC Of Parallel System", "group": "Operation", "area": "input", "address": 34798, "type": "uint16", "access": "R", "unit": "W" }, { "name": "Remote Control (e.g., for frequency regulation) Protocol Version", "group": "Operation", "area": "input", "address": 34799, "type": "uint16", "access": "R", "description": "of each battery in the parallel system. High byte: Major version number Low byte: Minor version number Example: If the register value is 0x0" }, { "name": "Module ID 6 [For hybrid system with PV and hybrid inverters]", "group": "Operation", "area": "input", "address": 34900, "type": "uint16", "access": "R", "description": "is 0x0006 — Photovoltaic & Storage System Information Any other value is invalid. Description: (1) The content of Module 6 was added startin" }, { "name": "Module 6 Register Count", "group": "Operation", "area": "input", "address": 34901, "type": "uint16", "access": "R", "description": "Low byte: Number of valid registers in the range 34902~34949, not exceeding 48. High byte: Reserved, default 0x00. Note: When Module 6 is ac" }, { "name": "Valid Identifier - For hybrid system with PV and hybrid inverters", "group": "Operation", "area": "input", "address": 34902, "type": "uint16", "access": "R", "description": "0xAA55–Photovoltaic & Storage System (registers Information 34903~34949) is valid. Any other value – invalid." }, { "name": "Hybrid inverters’ PV Total Power", "group": "Operation", "area": "input", "address": 34903, "type": "int32", "access": "R", "unit": "W", "description": "Positive value indicates power flowing out of the energy storage inverter; negative value indicates power flowing the energy storage inverte" }, { "name": "Hybrid inverters’ Total Battery Power", "group": "Operation", "area": "input", "address": 34905, "type": "int32", "access": "R", "unit": "W", "description": "Positive value indicates battery charging; negative value indicates battery discharging. 0x80000000 indicates the value is invalid. Descript" }, { "name": "Hybrid inverters’ Total Inverter Active Power", "group": "Operation", "area": "input", "address": 34907, "type": "int32", "access": "R", "unit": "W", "description": "into Positive value indicates power flowing out of the energy storage inverter; negative value indicates power flowing the energy storage in" }, { "name": "System Backup Load Total Active Power", "group": "Operation", "area": "input", "address": 34909, "type": "int32", "access": "R", "unit": "W", "description": "into Positive value indicates power flowing out of the energy storage inverter; negative value indicates power flowing the energy storage in" }, { "name": "Hybrid inverters’ AC Grid Port Total Active Power", "group": "Operation", "area": "input", "address": 34911, "type": "int32", "access": "R", "unit": "W", "description": "indicates power Positive value flowing out of the energy storage inverter; negative value indicates the energy power flowing storage inverte" }, { "name": "Generator Total Active Power (34913)", "group": "Operation", "area": "input", "address": 34913, "type": "int32", "access": "R", "unit": "W", "description": "indicates power Positive value flowing out of the energy storage inverter; negative value indicates the energy power flowing storage inverte" }, { "name": "Hybrid inverters’ Smart Load Total Active Power", "group": "Operation", "area": "input", "address": 34915, "type": "int32", "access": "R", "unit": "W", "description": "Positive value indicates power flowing out of the Smart Port; indicates power negative value flowing into the Smart Port. 0x80000000 indicat" }, { "name": "Grid‑tied Inverters’ Total Active Power", "group": "Operation", "area": "input", "address": 34917, "type": "int32", "access": "R", "unit": "W", "description": "into Positive value indicates power flowing out of the energy storage inverter; negative value indicates power flowing the energy storage in" }, { "name": "System Grid Load Total Active Power", "group": "Operation", "area": "input", "address": 34919, "type": "int32", "access": "R", "unit": "W", "description": "Positive value indicates power flowing out of the energy storage inverter; negative value indicates power flowing the energy storage inverte" }, { "name": "System Public Grid Total Active Power", "group": "Operation", "area": "input", "address": 34921, "type": "int32", "access": "R", "unit": "W", "description": "indicates power Positive value flowing toward the grid; negative value indicates power being drawn from the grid. 0x80000000 indicates the v" }, { "name": "Number of Grid-tied Inverters Online", "group": "Operation", "area": "input", "address": 34923, "type": "uint16", "access": "R", "description": "– Remote Control Range: 0~20, other values are invalid. Currently, only C&I storage models are supported. 0x0007 Information Any other value" }, { "name": "Module ID 7 [Remote Control Information]", "group": "Operation", "area": "input", "address": 25000, "type": "uint16", "access": "R" }, { "name": "Module 7 Register Count", "group": "Operation", "area": "input", "address": 25001, "type": "uint16", "access": "R", "description": "Low byte: Number of valid registers in the range 25002–25099, range 2~98. High byte: Reserved, default 0x00." }, { "name": "Valid Identifier – For Remote Control Information", "group": "Operation", "area": "input", "address": 25002, "type": "uint16", "access": "R", "description": "– Remote Control (registers 0xAA55 Information 25003~25099) is valid. Any other value – invalid." }, { "name": "Remote Control Status", "group": "Operation", "area": "input", "address": 25003, "type": "uint16", "access": "R", "description": "BIT00: 0 unready for Remote Control 1 ready for Remote Control BIT01: 0 available remote control power is not limited by BMS 1 available rem" }, { "name": "Available", "group": "Operation", "area": "input", "address": 25004, "type": "uint32", "access": "R", "unit": "W", "description": "Note: For FCAS." }, { "name": "Available Power", "group": "Operation", "area": "input", "address": 25006, "type": "uint32", "access": "R", "unit": "W", "description": "Note: For FCAS." }, { "name": "Battery Charge Power Value Battery Discharge Value AC Grid Port Available Import Active Power Value AC Grid Port Available Export Active Power Value", "group": "Operation", "area": "input", "address": 25008, "type": "uint32", "access": "R", "unit": "W", "description": "Note: For FCAS." }, { "name": "Parallel System Battery Available Charge Power Value", "group": "Operation", "area": "input", "address": 25012, "type": "uint32", "access": "R", "unit": "W", "description": "Note: For FCAS." }, { "name": "Parallel System Battery Available Discharge Power Value", "group": "Operation", "area": "input", "address": 25014, "type": "uint32", "access": "R", "unit": "W", "description": "Note: For FCAS." }, { "name": "Parallel System AC Grid Port Available Import Active Power Value", "group": "Operation", "area": "input", "address": 25016, "type": "uint32", "access": "R", "unit": "W", "description": "Note: For FCAS." }, { "name": "Parallel System AC Grid Port Available Export Active Power Value", "group": "Operation", "area": "input", "address": 25018, "type": "uint32", "access": "R", "unit": "W", "description": "Note: For FCAS." }, { "name": "Online Status of Each Energy Storage Inverter in the Parallel System", "group": "Operation", "area": "input", "address": 25020, "type": "uint32", "access": "R", "description": "BIT00: Reserved BIT01~BIT31: 0: Energy Storage Inverter ID 1~31 offline 1: Energy Storage Inverter ID 1~31 online Remarks" }, { "name": "5.2. Definition of Set Parameter Addresses Corresponding function codes 0x03, 0x06, and 0x10. Register Data Address Description Type (Decimal) Real-Time Clock: Year", "group": "Settings", "area": "holding", "address": 43000, "type": "uint16", "access": "RW", "unit": "Unit", "description": "Range: 0~99, representing the years 2000~2099. Range: 1~12, representing month 1~12" }, { "name": "Real-Time Clock: Month", "group": "Settings", "area": "holding", "address": 43001, "type": "uint16", "access": "RW" }, { "name": "Real-Time Clock: Day", "group": "Settings", "area": "holding", "address": 43002, "type": "uint16", "access": "RW", "description": "Range: 1–31, representing day 1–31" }, { "name": "Real-Time Clock: Hour", "group": "Settings", "area": "holding", "address": 43003, "type": "uint16", "access": "RW", "description": "Range: 0–23, representing hour 0–23" }, { "name": "Real-Time Clock: Minute", "group": "Settings", "area": "holding", "address": 43004, "type": "uint16", "access": "RW", "description": "Range: 0–59, representing minute 0–59" }, { "name": "Real-Time Clock: Second", "group": "Settings", "area": "holding", "address": 43005, "type": "uint16", "access": "RW", "description": "Range: 0–59, representing second 0–59" }, { "name": "Slave Address Setting", "group": "Settings", "area": "holding", "address": 43006, "type": "uint16", "access": "RW", "description": "Setting range: 1–10, default 1. Note: Only set using function code 0x06." }, { "name": "Startup/Shutdown", "group": "Settings", "area": "holding", "address": 43007, "type": "uint16", "access": "RW", "description": "0xBE–Startup , 0xDE–Shutdown" }, { "name": "Current Battery Model", "group": "Settings", "area": "holding", "address": 43009, "type": "uint16", "access": "RW", "description": "Low byte: Low-voltage battery manufacturer (see Appendix 5 for low-voltage battery codes) High byte: High-voltage battery manufacturer (see " }, { "name": "Maximum Charging SOC", "group": "Settings", "area": "holding", "address": 43010, "type": "uint16", "access": "RW", "unit": "%", "description": "Setting range: 80–100%, default 100%. Note: Represents the charge cutoff SOC for communication-capable lithium batteries." }, { "name": "Over-Discharge SOC", "group": "Settings", "area": "holding", "address": 43011, "type": "uint16", "access": "RW", "unit": "%", "description": "Setting range: 5–40%, default 20%; must be greater than the forced address charge SOC 43018). (register" }, { "name": "Forced Charge SOC", "group": "Settings", "area": "holding", "address": 43018, "type": "uint16", "access": "RW", "unit": "%", "description": "4% range: Setting – (Over-Discharge SOC – 1%), default 10% (Note: Over-Discharge SOC register address 43011)." }, { "name": "Rated Capacity", "group": "Settings", "area": "holding", "address": 43019, "type": "uint16", "access": "RW", "unit": "Ah", "description": "Range: 0–9999 Ah, default 200 Ah. Note: Supports lead-acid and 48/51.2V non‑communication lithium batteries." }, { "name": "Over-Discharge Voltage", "group": "Settings", "area": "holding", "address": 43020, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "Lead‑acid battery: S5 models, range 40.0–48.0 V, default 44.5 V; S6 models, range 40.0–52.0 V, default 44.5 V. 48V lithium battery: range 45" }, { "name": "Forced Charge Voltage", "group": "Settings", "area": "holding", "address": 43021, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "Lead‑acid battery: S5 models, range 40.0–48.0 V, default 43.8 V; S6 models, range 40.0–50.0 V, default 43.8 V." }, { "name": "Lead‑Acid Battery Temperature Compensation Coefficient", "group": "Settings", "area": "holding", "address": 43022, "type": "uint16", "access": "RW", "unit": "mV", "description": "Range: 0–180 mV/°C, Default: 0 mV/°C; Note: Only supported for lead‑acid batteries." }, { "name": "Ambient Temperature Status Selection", "group": "Settings", "area": "holding", "address": 43023, "type": "uint16", "access": "RW", "description": "3: 1: Normal Temperature, 2: Low Temperature, High Temperature,Other values invalid; Default: 1; Note: Only supported for lead‑acid batterie" }, { "name": "Battery Reserved SOC", "group": "Settings", "area": "holding", "address": 43024, "type": "uint16", "access": "RW", "unit": "%", "description": "to Range: Over-discharge SOC 100%, default 80% (Note: Over-discharge SOC register 43011) Description: Parameter setting for enabling battery" }, { "name": "81>S1", "group": "Settings", "area": "holding", "address": 43038, "type": "uint16", "access": "RW", "unit": "Hz", "scale": 0.01, "description": "The configurable range and default values are determined according to the national standard parameter table. Note: Registers 43038-43049 are" }, { "name": "81>S1-T", "group": "Settings", "area": "holding", "address": 43039, "type": "uint16", "access": "RW", "unit": "s", "scale": 0.01, "description": "The configurable range and default values are determined according to the national standard parameter table." }, { "name": "81S2F", "group": "Settings", "area": "holding", "address": 43042, "type": "uint16", "access": "RW", "unit": "Hz", "scale": 0.01, "description": "The configurable range and default values are determined according to the national standard parameter table." }, { "name": "81>S2F-T", "group": "Settings", "area": "holding", "address": 43043, "type": "uint16", "access": "RW", "unit": "s", "scale": 0.01, "description": "The configurable range and default values are determined according to the national standard parameter table." }, { "name": "81S2S", "group": "Settings", "area": "holding", "address": 43046, "type": "uint16", "access": "RW", "unit": "Hz", "scale": 0.01, "description": "The configurable range and default values are determined according to the national standard parameter table." }, { "name": "81>S2S-T", "group": "Settings", "area": "holding", "address": 43047, "type": "uint16", "access": "RW", "unit": "s", "scale": 0.01, "description": "The configurable range and default values are determined according to the national standard parameter table." }, { "name": "81S1 – 50.2 Hz / 0.1 s – Inverter 81S2 – 51.5 Hz / 0.1 s – Lo" }, { "name": "One‑Key Full Test (Complete Italian Self‑check Items 01‑10)", "group": "Settings", "area": "holding", "address": 43079, "type": "uint16", "access": "RW", "description": "Value: Start Complete Self Test 0---One‑key full test stopped or not started 2---One‑key full test started" }, { "name": "Grid Upper Voltage Limit Required for Post‑Fault Recovery", "group": "Settings", "area": "holding", "address": 43082, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "The configurable range and default values are determined according to the national standard parameter table." }, { "name": "Grid Lower Voltage Limit Required for Post‑Fault Recovery", "group": "Settings", "area": "holding", "address": 43083, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "The configurable range and default values are determined according to the national standard parameter table." }, { "name": "Grid Upper Frequency Limit Required for Post‑Fault Recovery", "group": "Settings", "area": "holding", "address": 43084, "type": "uint16", "access": "RW", "unit": "Hz", "scale": 0.01, "description": "The configurable range and default values are determined according to the national standard parameter table." }, { "name": "Grid Lower Frequency Limit Required for Post‑Fault Recovery", "group": "Settings", "area": "holding", "address": 43085, "type": "uint16", "access": "RW", "unit": "Hz", "scale": 0.01, "description": "The configurable range and default values are determined according to the national standard parameter table." }, { "name": "Grid Upper Voltage Limit Required for First Power‑On", "group": "Settings", "area": "holding", "address": 43086, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "The configurable range and default values are determined according to the national standard parameter table." }, { "name": "Grid Lower Voltage Limit Required for First Power‑On", "group": "Settings", "area": "holding", "address": 43087, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "The configurable range and default values are determined according to the national standard parameter table." }, { "name": "Grid Upper Frequency Limit Required for First Power‑On", "group": "Settings", "area": "holding", "address": 43088, "type": "uint16", "access": "RW", "unit": "Hz", "scale": 0.01, "description": "The configurable range and default values are determined according to the national standard parameter table." }, { "name": "Grid Lower Frequency Limit Required for First Power‑On", "group": "Settings", "area": "holding", "address": 43089, "type": "uint16", "access": "RW", "unit": "Hz", "scale": 0.01, "description": "The configurable range and default values are determined according to the national standard parameter table." }, { "name": "Grid Primary Over‑Voltage Threshold", "group": "Settings", "area": "holding", "address": 43090, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "The configurable range and default values are determined according to the national standard parameter table. For represents 59 Hz S2. the CE" }, { "name": "Grid Primary Over‑Voltage Delay Threshold", "group": "Settings", "area": "holding", "address": 43091, "type": "uint16", "access": "RW", "unit": "ms", "scale": 10.0, "description": "The configurable range and default values are determined according to the national standard parameter table. For represents 59.S2 Time the C" }, { "name": "Grid Secondary Over‑Voltage Threshold", "group": "Settings", "area": "holding", "address": 43092, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "The configurable range and default values are determined according to the national standard parameter table." }, { "name": "Grid Secondary Over‑Voltage Delay Threshold", "group": "Settings", "area": "holding", "address": 43093, "type": "uint16", "access": "RW", "unit": "ms", "scale": 10.0, "description": "The configurable range and default values are determined according to the national standard parameter table." }, { "name": "Grid Primary Under‑Voltage Threshold", "group": "Settings", "area": "holding", "address": 43094, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "The configurable range and default values are determined according to the national standard parameter table. For represents 27.S1 the CEI 0‑" }, { "name": "Grid Primary Under‑Voltage Delay Threshold", "group": "Settings", "area": "holding", "address": 43095, "type": "uint16", "access": "RW", "unit": "ms", "scale": 10.0, "description": "The configurable range and default values are determined according to the national standard parameter table. For represents 27.S1 Time the C" }, { "name": "Grid Secondary Under‑Voltage Threshold", "group": "Settings", "area": "holding", "address": 43096, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "The configurable range and default values are determined according to the national standard parameter table. For represents 27.S2 the CEI 0‑" }, { "name": "Grid Secondary Under‑Voltage Delay Threshold", "group": "Settings", "area": "holding", "address": 43097, "type": "uint16", "access": "RW", "unit": "ms", "scale": 10.0, "description": "The configurable range and default values are determined according to the national standard parameter table. For represents 27.S2 Time the C" }, { "name": "Grid Primary Over‑Frequency Threshold", "group": "Settings", "area": "holding", "address": 43098, "type": "uint16", "access": "RW", "unit": "Hz", "scale": 0.01, "description": "The configurable range and default values are determined according to the national standard parameter table." }, { "name": "Grid Primary Over‑Frequency Delay Threshold", "group": "Settings", "area": "holding", "address": 43099, "type": "uint16", "access": "RW", "unit": "ms", "scale": 10.0, "description": "The configurable range and default values are determined according to the national standard parameter table. For the Hawaiian and new U.S. s" }, { "name": "Grid Secondary Over‑Frequency Threshold", "group": "Settings", "area": "holding", "address": 43100, "type": "uint16", "access": "RW", "unit": "Hz", "scale": 0.01, "description": "The configurable range and default values are determined according to the national standard parameter table." }, { "name": "Grid Secondary Over‑Frequency Delay Threshold", "group": "Settings", "area": "holding", "address": 43101, "type": "uint16", "access": "RW", "unit": "ms", "scale": 10.0, "description": "The configurable range and default values are determined according to the national standard parameter table. For the Hawaiian and new U.S. s" }, { "name": "Grid Primary Under‑Frequency Threshold", "group": "Settings", "area": "holding", "address": 43102, "type": "uint16", "access": "RW", "unit": "Hz", "scale": 0.01, "description": "The configurable range and default values are determined according to the national standard parameter table." }, { "name": "Grid Primary Under‑Frequency Delay Threshold", "group": "Settings", "area": "holding", "address": 43103, "type": "uint16", "access": "RW", "unit": "ms", "scale": 10.0, "description": "The configurable range and default values are determined according to the national standard parameter table. For the Hawaiian and new U.S. s" }, { "name": "Grid Secondary Under‑Frequency Threshold", "group": "Settings", "area": "holding", "address": 43104, "type": "uint16", "access": "RW", "unit": "Hz", "scale": 0.01, "description": "The configurable range and default values are determined according to the national standard parameter table." }, { "name": "Grid Secondary Under‑Frequency Delay Threshold", "group": "Settings", "area": "holding", "address": 43105, "type": "uint16", "access": "RW", "unit": "ms", "scale": 10.0, "description": "The configurable range and default values are determined according to the national standard parameter table. For the Hawaiian and new U.S. s" }, { "name": "Start‑up Time", "group": "Settings", "area": "holding", "address": 43106, "type": "uint16", "access": "RW", "unit": "s", "description": "The configurable range and default values are determined according to the national standard parameter table." }, { "name": "Fault Recovery Time", "group": "Settings", "area": "holding", "address": 43107, "type": "uint16", "access": "RW", "unit": "s", "description": "The configurable range and default values are determined according to the national standard parameter table." }, { "name": "10‑Minute Average Over‑Voltage Protection Threshold", "group": "Settings", "area": "holding", "address": 43108, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "The configurable range and default values are determined according to the national standard parameter table. For represents 59 Hz S1. the CE" }, { "name": "Energy Storage Control Switch", "group": "Settings", "area": "holding", "address": 43110, "type": "uint16", "access": "RW", "description": "and For details, refer to Appendix 7: Energy Storage Control Switch Status Description. (Self‑Consumption Note: BIT00 (Grid Feed‑in Priority" }, { "name": "Backup Load Function Enable Setting", "group": "Settings", "area": "holding", "address": 43111, "type": "uint16", "access": "RW", "description": "0000H – Disabled, 0001H – Enabled, default: Enabled." }, { "name": "Backup Port AC Output Voltage Setting", "group": "Settings", "area": "holding", "address": 43112, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "Standard Voltage Grid: Phase voltage range: 190–250 V; Default: 230 V. Low Voltage Grid: Phase voltage range: 110–140 V, Default: 132 V; Lin" }, { "name": "Battery 1 Maximum Charging Current Setting", "group": "Settings", "area": "holding", "address": 43117, "type": "uint16", "access": "RW", "unit": "A", "scale": 0.1, "description": "5G Series: Range: 1–100 A, Default: 100 A. S5 Series: Range: 1 – unit's battery maximum current, charging Default: unit's battery maximum ch" }, { "name": "Battery 1 Maximum Discharging Current Setting", "group": "Settings", "area": "holding", "address": 43118, "type": "uint16", "access": "RW", "unit": "A", "scale": 0.1, "description": "5G Series: Range: 1–100 A, Default: 100 A. S5 Series: Range: 1 – unit's battery maximum current, discharging Default: unit's battery maximum" }, { "name": "Overload Voltage Droop Setting", "group": "Settings", "area": "holding", "address": 43123, "type": "uint16", "access": "RW", "description": "0000H – Disabled, 0001H – Enabled, default: Disabled." }, { "name": "Phase A Reverse Power Flow Setting", "group": "Settings", "area": "holding", "address": 43125, "type": "int16", "access": "RW", "unit": "W", "scale": 100.0, "description": "Range: 0–99, default 0. Effective only when BIT06 (power control mode) of register 43073 is set to \"three‑phase unbalanced output\". to S6 No" }, { "name": "Phase B Reverse Power Flow Setting", "group": "Settings", "area": "holding", "address": 43126, "type": "int16", "access": "RW", "unit": "W", "scale": 100.0, "description": "to S6" }, { "name": "Phase C Reverse Power Flow Setting", "group": "Settings", "area": "holding", "address": 43127, "type": "int16", "access": "RW", "unit": "W", "scale": 100.0, "description": "three‑phase high‑voltage 10 kW single‑phase S6 series and high‑voltage series kW 11.4 software versions that have not been simplified; corre" }, { "name": "Remote Control: Inverter AC Grid Port Active Power Setting", "group": "Settings", "area": "holding", "address": 43128, "type": "int16", "access": "RW", "unit": "W", "scale": 10.0 }, { "name": "Remote Control: Battery Discharging Power Setting", "group": "Settings", "area": "holding", "address": 43129, "type": "uint16", "access": "RW", "unit": "W", "scale": 10.0 }, { "name": "Remote Control: Battery Charging Limit Power", "group": "Settings", "area": "holding", "address": 43130, "type": "uint16", "access": "RW", "unit": "W", "scale": 10.0, "description": "Range: 10 W – device Backup rated output power; default 0 (invalid). Note: Settings are not retained after power loss." }, { "name": "Remote Control: Battery Discharging Limit Power", "group": "Settings", "area": "holding", "address": 43131, "type": "uint16", "access": "RW", "unit": "W", "scale": 10.0, "description": "Range: 10 W – device Backup rated output power; default 0 (invalid). Note: Settings are not retained after power loss." }, { "name": "Remote Control: Grid Regulation via Remote Control", "group": "Settings", "area": "holding", "address": 43132, "type": "uint16", "access": "RW", "description": "0: Off 1: Reserved 2: Enable remote control of inverter AC Grid port (active power setting register 43128) 3–65535: Reserved If no continuou" }, { "name": "Remote Control: Battery Charge/Discharge Mode Setting", "group": "Settings", "area": "holding", "address": 43135, "type": "uint16", "access": "RW", "description": "0: Off 1: Battery Charging 2: Battery Discharging 3~65535: Reserved Description: (1) After receiving the charge/discharge enable command, th" }, { "name": "Remote Control: Battery Charging Power Setting", "group": "Settings", "area": "holding", "address": 43136, "type": "uint16", "access": "RW", "unit": "W", "scale": 10.0, "description": "after power-off. Range: 0–300 kW Description: (1) Effective only after remote is control of battery charging enabled (register 43135 = 1). (" }, { "name": "EPS Switchover Time", "group": "Settings", "area": "holding", "address": 43139, "type": "uint16", "access": "RW", "unit": "ms", "scale": 10.0, "description": "Host computer setting range: 1–500 s; default: 2000 ms. the addition of Note: Before register 43705, setting register 43139 to 0 meant the E" }, { "name": "Meter Type and Its Installation Location", "group": "Settings", "area": "holding", "address": 43140, "type": "uint16", "access": "RW", "description": "to Eastron single‑phase, Eastron three‑phase, and Chint byte High installation location: 0x0100 – Grid side 0x0200 – Reserved 0x0300 – Grid " }, { "name": "TOU Scheduled", "group": "Settings", "area": "holding", "address": 43141, "type": "uint16", "access": "RW", "unit": "A", "scale": 0.1, "description": "standard Eastron Range: 0 – maximum rated of the current charging corresponding model, default 50 A. Description: (1) Only used for paramete" }, { "name": "Charging Current Setting TOU Scheduled Discharging Current Setting", "group": "Settings", "area": "holding", "address": 43142, "type": "uint16", "access": "RW", "unit": "A", "scale": 0.1, "description": "rated Range: 0 – maximum the of discharging corresponding model, default 50 A. current" }, { "name": "TOU Scheduled Charging Start Hour Setting", "group": "Settings", "area": "holding", "address": 43143, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Scheduled Charging Start Minute min Setting", "group": "Settings", "area": "holding", "address": 43144, "type": "uint16", "access": "RW" }, { "name": "TOU Scheduled Charging End Hour Setting", "group": "Settings", "area": "holding", "address": 43145, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Scheduled Charging End Minute min Setting", "group": "Settings", "area": "holding", "address": 43146, "type": "uint16", "access": "RW" }, { "name": "TOU Scheduled Discharging Start Hour Setting", "group": "Settings", "area": "holding", "address": 43147, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Scheduled Discharging Start min Minute Setting", "group": "Settings", "area": "holding", "address": 43148, "type": "uint16", "access": "RW" }, { "name": "TOU Scheduled Discharging End Hour Setting (43149)", "group": "Settings", "area": "holding", "address": 43149, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Scheduled Discharging End min Minute Setting", "group": "Settings", "area": "holding", "address": 43150, "type": "uint16", "access": "RW" }, { "name": "TOU Scheduled Charging Start Hour Setting 2", "group": "Settings", "area": "holding", "address": 43153, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Scheduled Charging Start Minute min Setting 2", "group": "Settings", "area": "holding", "address": 43154, "type": "uint16", "access": "RW" }, { "name": "TOU Scheduled Charging End Hour Setting 2", "group": "Settings", "area": "holding", "address": 43155, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Scheduled Charging End Minute min Setting 2", "group": "Settings", "area": "holding", "address": 43156, "type": "uint16", "access": "RW" }, { "name": "TOU Scheduled Discharging Start Hour Setting 2", "group": "Settings", "area": "holding", "address": 43157, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Scheduled Discharging Start min Minute Setting 2", "group": "Settings", "area": "holding", "address": 43158, "type": "uint16", "access": "RW" }, { "name": "TOU Scheduled Discharging End Hour Setting 2", "group": "Settings", "area": "holding", "address": 43159, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Scheduled Discharging End min Minute Setting 2", "group": "Settings", "area": "holding", "address": 43160, "type": "uint16", "access": "RW" }, { "name": "TOU Scheduled Charging Start Hour Setting 3", "group": "Settings", "area": "holding", "address": 43163, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Scheduled Charging Start Minute min Setting 3", "group": "Settings", "area": "holding", "address": 43164, "type": "uint16", "access": "RW" }, { "name": "TOU Scheduled Charging End Hour Setting 3", "group": "Settings", "area": "holding", "address": 43165, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Scheduled Charging End Minute min Setting 3", "group": "Settings", "area": "holding", "address": 43166, "type": "uint16", "access": "RW" }, { "name": "TOU Scheduled Discharging Start Hour Setting 3", "group": "Settings", "area": "holding", "address": 43167, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Scheduled Discharging Start min Minute Setting 3", "group": "Settings", "area": "holding", "address": 43168, "type": "uint16", "access": "RW" }, { "name": "TOU Scheduled Discharging End Hour Setting 3", "group": "Settings", "area": "holding", "address": 43169, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Scheduled Discharging End min Minute Setting 3", "group": "Settings", "area": "holding", "address": 43170, "type": "uint16", "access": "RW" }, { "name": "TOU Scheduled Charging Start Hour Setting 4", "group": "Settings", "area": "holding", "address": 43173, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Scheduled min Charging Start Minute", "group": "Settings", "area": "holding", "address": 43174, "type": "uint16", "access": "RW" }, { "name": "Setting 4 TOU Scheduled Charging End Hour Setting 4", "group": "Settings", "area": "holding", "address": 43175, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Scheduled Charging End Minute min Setting 4", "group": "Settings", "area": "holding", "address": 43176, "type": "uint16", "access": "RW" }, { "name": "TOU Scheduled Discharging Start Hour Setting 4", "group": "Settings", "area": "holding", "address": 43177, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Scheduled Discharging Start min Minute Setting 4", "group": "Settings", "area": "holding", "address": 43178, "type": "uint16", "access": "RW" }, { "name": "TOU Scheduled Discharging End Hour Setting 4", "group": "Settings", "area": "holding", "address": 43179, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Scheduled Discharging End min Minute Setting 4", "group": "Settings", "area": "holding", "address": 43180, "type": "uint16", "access": "RW" }, { "name": "TOU Scheduled Charging Start Hour Setting 5", "group": "Settings", "area": "holding", "address": 43183, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Scheduled Charging Start Minute min Setting 5", "group": "Settings", "area": "holding", "address": 43184, "type": "uint16", "access": "RW" }, { "name": "TOU Scheduled Charging End Hour Setting 5", "group": "Settings", "area": "holding", "address": 43185, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Scheduled Charging End Minute min Setting 5", "group": "Settings", "area": "holding", "address": 43186, "type": "uint16", "access": "RW" }, { "name": "TOU Scheduled Discharging Start Hour Setting 5", "group": "Settings", "area": "holding", "address": 43187, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Scheduled Discharging Start min Minute Setting 5", "group": "Settings", "area": "holding", "address": 43188, "type": "uint16", "access": "RW" }, { "name": "TOU Scheduled Discharging End Hour Setting (43189)", "group": "Settings", "area": "holding", "address": 43189, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Scheduled Discharging End min Minute Setting 5", "group": "Settings", "area": "holding", "address": 43190, "type": "uint16", "access": "RW" }, { "name": "Total Grid‑side Active", "group": "Settings", "area": "holding", "address": 43195, "type": "int16", "access": "RW", "unit": "W", "description": "Range: For units with rated power ≤ 20 kW: –1000 W to +1000 W For units with rated power > 20 kW: –10 kW to +10 kW Default: –30 W PV" }, { "name": "Power Control Compensation Remote Control: Function Switch", "group": "Settings", "area": "holding", "address": 43279, "type": "uint16", "access": "RW", "description": "BIT00–BIT01: Shutdown control – 0: invalid, 1: disabled, 2: enabled, 3: invalid, default 0. BIT02–BIT15: Reserved. Description: (1) Effectiv" }, { "name": "Remote Control: Timeout Setting", "group": "Settings", "area": "holding", "address": 43282, "type": "uint16", "access": "RW", "unit": "min", "description": "Range: 2–30; default 5. Note: Settings are not retained after power loss." }, { "name": "Meter Communication Access Method", "group": "Settings", "area": "holding", "address": 43283, "type": "uint16", "access": "RW", "description": "0 – Wired, 1 – Wireless; other values invalid, default 0." }, { "name": "Special Function Control Word 02", "group": "Settings", "area": "holding", "address": 43284, "type": "uint16", "access": "RW", "description": "BIT00: PV‑Only Load Enable – 0: disabled, 1: enabled, default 0. BIT01: Fan Low‑Noise Mode – 0: disabled, 1: enabled, default 0. BIT02: Batt" }, { "name": "AC Coupling Start SOC", "group": "Settings", "area": "holding", "address": 43285, "type": "uint16", "access": "RW", "description": "Range: 0 to (AC Coupling Stop SOC – 10%), default 0. Only applicable to battery types with communication capability." }, { "name": "AC Coupling Start Voltage", "group": "Settings", "area": "holding", "address": 43286, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "Range: Over‑discharge voltage to (AC Coupling Stop Voltage – 2 V), default 48 V. Only applicable to battery types without communication capa" }, { "name": "AC Coupling Start Frequency", "group": "Settings", "area": "holding", "address": 43287, "type": "uint16", "access": "RW", "unit": "Hz", "scale": 0.01, "description": "50 Hz Standard: 50 Hz ~ (primary over‑frequency threshold + 0.1 Hz), default 50 Hz. 60 Hz Standard: 60 Hz ~ (primary over‑frequency threshol" }, { "name": "G100‑2022 Standard Public Grid‑side Apparent Current Output Limit Setting", "group": "Settings", "area": "holding", "address": 43300, "type": "uint16", "access": "RW", "unit": "A", "scale": 0.01, "description": "this indicates three‑phase energy storage For machines, the apparent current output limit per phase. Standalone range: 0 ~ 4 × unit rated AC" }, { "name": "Clear AFCI Fault", "group": "Settings", "area": "holding", "address": 43313, "type": "uint16", "access": "RW", "description": "Used to manually clear the fault after 5 cumulative AFCI faults have occurred on the same day. 0xAA55 – enable, other values invalid. Only w" }, { "name": "Lead‑Acid Battery Equalization Enable", "group": "Settings", "area": "holding", "address": 43333, "type": "uint16", "access": "RW", "description": "0: Disable; 1: Enable. Default: 0." }, { "name": "Lead‑Acid Battery Equalization Voltage", "group": "Settings", "area": "holding", "address": 43334, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "Range: 55–59.5 V; default 57.6 V." }, { "name": "Lead‑Acid Battery Equalization Time", "group": "Settings", "area": "holding", "address": 43335, "type": "uint16", "access": "RW", "unit": "min", "description": "Range: 120–360 min; default 180 min." }, { "name": "Lead‑Acid Battery Equalization Timeout", "group": "Settings", "area": "holding", "address": 43336, "type": "uint16", "access": "RW", "unit": "min", "description": "Range: 5–900 min; default 120 min." }, { "name": "Lead‑Acid Battery Equalization Interval", "group": "Settings", "area": "holding", "address": 43337, "type": "uint16", "access": "RW", "unit": "day", "description": "Range: 20–180 days; default 30 days." }, { "name": "Lead‑Acid Battery Equalization Immediate Activation", "group": "Settings", "area": "holding", "address": 43338, "type": "uint16", "access": "RW", "description": "0: Disable, 1: Enable; default 0. equalization Requires enable to be turned on first. battery" }, { "name": "Lead‑Acid Battery", "group": "Settings", "area": "holding", "address": 43339, "type": "uint16", "access": "RW", "unit": "A", "scale": 0.1, "description": "Range: 4.0–10.0 A; default 4.0 A." }, { "name": "Float Current Limit Generator Setting Enable Switch", "group": "Settings", "area": "holding", "address": 43340, "type": "uint16", "access": "RW", "description": "BIT00: Generator connection mode – 0: Manual, 1: Automatic; default 0. BIT01: Generator charging enable – 0: Enable, 1: Disable; default 0. " }, { "name": "Generator Start Lithium Battery SOC", "group": "Settings", "area": "holding", "address": 43344, "type": "uint16", "access": "RW", "unit": "%", "description": "In generator mode, the SOC at which the generator starts and charges the lithium battery. Range: 1–95%; default 25%." }, { "name": "Generator Lithium Battery Charge Cut‑off SOC", "group": "Settings", "area": "holding", "address": 43345, "type": "uint16", "access": "RW", "unit": "%", "description": "Range: (Start SOC + 5%) – 100%; default 80%. Note: Start SOC < Cut‑off SOC." }, { "name": "Generator Start Lead‑Acid Battery Voltage", "group": "Settings", "area": "holding", "address": 43346, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "Range: 40–55 V; default 46 V." }, { "name": "Generator Lead‑Acid Battery Charge Cut‑off Voltage", "group": "Settings", "area": "holding", "address": 43347, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "Range: (Start voltage + 2 V) – 60 V; default 55 V." }, { "name": "Battery Wake‑up Voltage Setting", "group": "Settings", "area": "holding", "address": 43348, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "40 V. Low‑voltage energy storage unit: 40–60 V, default 40 V. Off‑grid energy storage unit: 40–58 V, default Single‑phase high‑voltage energ" }, { "name": "Battery Wake-up Time Setting", "group": "Settings", "area": "holding", "address": 43349, "type": "uint16", "access": "RW", "unit": "s", "description": "Range: 20–3600 s, default: 20 s" }, { "name": "MPPT Active Scanning Interval", "group": "Settings", "area": "holding", "address": 43361, "type": "uint16", "access": "RW", "unit": "s", "description": "Range: 600–10800 (10 min–180 min); default: 1800 (30 min)" }, { "name": "CT Ratio", "group": "Settings", "area": "holding", "address": 43362, "type": "uint16", "access": "RW", "description": "Range: 1–30000. Note: (1) Effective only when BIT13 of register 43073 is set to CT. (2) For kW kW, 50 commercial/industrial storage series, " }, { "name": "Generator Start/Stop in Manual Mode", "group": "Settings", "area": "holding", "address": 43363, "type": "uint16", "access": "RW", "description": "(1) Before setting: Forced generator start – 0: invalid, 1: valid; default 0; other values invalid. After a single write of “1”, the inverte" }, { "name": "Generator Rated Input Power", "group": "Settings", "area": "holding", "address": 43364, "type": "uint16", "access": "RW", "unit": "kW", "scale": 0.1, "description": "be Cannot" }, { "name": "Generator Setting Switch", "group": "Settings", "area": "holding", "address": 43365, "type": "uint16", "access": "RW", "description": "BIT00: Generator connection location – 0: generator port, 1: grid port; default 0. BIT01: With Generator – 0: No, 1: Yes; default 0. Note: e" }, { "name": "Forced Stop Generator", "group": "Settings", "area": "holding", "address": 43366, "type": "uint16", "access": "RW", "description": "(1) Before simplified setting: Forced stop generator – 0: invalid, 1: valid; default 0; other values invalid. When the generator is running," }, { "name": "Generator Maximum Allowable Percentage", "group": "Settings", "area": "holding", "address": 43367, "type": "uint16", "access": "RW", "unit": "%", "description": "(2) After simplified setting: Deactivate. Gen_Max_Run_Pct; Range: 1%–120%, default: 100%. Gen_Target_Power, Default: 90% of generator rated " }, { "name": "Generator Target Power", "group": "Settings", "area": "holding", "address": 43368, "type": "uint16", "access": "RW", "unit": "kW", "scale": 0.1 }, { "name": "Generator Charging Power", "group": "Settings", "area": "holding", "address": 43369, "type": "uint16", "access": "RW", "unit": "kW", "scale": 0.1, "description": "Range: 0 – maximum charging power of the corresponding model, default 0. BIT00: AC Output Control Switch 0: Disable, 1: Enable; default: Dis" }, { "name": "Function Setting Enable Switch", "group": "Settings", "area": "holding", "address": 43374, "type": "uint16", "access": "RW", "description": "upon enable switch) detecting When Enable is selected, the grid inverter, presence, forcibly (regardless of the Backup stops Backup‑side out" }, { "name": "Battery Auto‑Wake‑up Duration Setting", "group": "Settings", "area": "holding", "address": 43376, "type": "uint16", "access": "RW", "unit": "S", "description": "Range: 20–300 s, default: 60 s S6 single‑phase high‑voltage 11.4 kW US models: Range: 20–300 s, default: 180 s Other S6 models: Range: 20–36" }, { "name": "Upgrade Type Selection", "group": "Settings", "area": "holding", "address": 43377, "type": "uint16", "access": "RW", "description": "00: Main DSP upgrade 01: Secondary DSP upgrade (for 100 kW energy storage inverter) 05: AFCI board upgrade Note: Before performing an upgrad" }, { "name": "Single‑Function Operation", "group": "Settings", "area": "holding", "address": 43378, "type": "uint16", "access": "RW", "description": "0x0000: Invalid 0x0001: CT detection function – after setting, read register 33290 to obtain the detection result. 0x0002: G100‑2022 fault m" }, { "name": "Manual Master/Slave Setting", "group": "Settings", "area": "holding", "address": 43382, "type": "uint16", "access": "RW", "description": "is used for 0: Slave; 1: Master; Other values invalid." }, { "name": "Inverter Connection Phase Setting", "group": "Settings", "area": "holding", "address": 43384, "type": "uint16", "access": "RW", "description": "Range: 0–9; default 1. 0: Not set. 1: Single‑phase system. 2: Phase A of three‑phase system. 3: Phase B of three‑phase system. 4: Phase C of" }, { "name": "Standalone/Parallel Setting", "group": "Settings", "area": "holding", "address": 43391, "type": "uint16", "access": "RW", "description": "0 – Standalone, 1 – Parallel; default 0." }, { "name": "Standard Operating Mode Switch", "group": "Settings", "area": "holding", "address": 43451, "type": "uint16", "access": "RW", "description": "BIT00: Volt-watt mode. 1 = Enabled, 0 = Disabled BIT01: Volt-var mode. 1 = Enabled, 0 = Disabled BIT02: Fixed power factor mode. 1 = Enabled" }, { "name": "Over‑Discharge Hysteresis SOC", "group": "Settings", "area": "holding", "address": 43481, "type": "uint16", "access": "RW", "unit": "%", "description": "Range: 1–20%, default 1%. Description: When battery SOC reaches the over‑discharge SOC, is prohibited. battery discharge Battery becomes dis" }, { "name": "Battery Healing SOC", "group": "Settings", "area": "holding", "address": 43482, "type": "uint16", "access": "RW", "unit": "%", "description": "Range: 80–100%; default: 100%." }, { "name": "Energy Storage Function Control Word", "group": "Settings", "area": "holding", "address": 43483, "type": "uint16", "access": "RW", "description": "BIT00: Smart Load enable – 0: disabled, 1: enabled, default 0. BIT01: AC Coupling enable – 0: – Cannot be with (BIT01 of disabled, 1: enable" }, { "name": "AC Coupling Stop SOC", "group": "Settings", "area": "holding", "address": 43484, "type": "uint16", "access": "RW", "unit": "%", "description": "Range: 60–90%; default: 60%." }, { "name": "AC Coupling Stop Voltage", "group": "Settings", "area": "holding", "address": 43485, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "Range: 50 V ~ equalization charge voltage setting; Default: 50 V; Note: Only applicable to battery types without communication capability." }, { "name": "AC Coupling Maximum", "group": "Settings", "area": "holding", "address": 43486, "type": "uint16", "access": "RW", "unit": "Hz", "scale": 0.01, "description": "Range: corresponding (National standard primary (National" }, { "name": "Load‑Shedding Frequency Peak SOC", "group": "Settings", "area": "holding", "address": 43487, "type": "uint16", "access": "RW", "unit": "%", "description": "over‑frequency threshold + 0.1 Hz) ~ 54 Hz (50 Hz grid) / 65 Hz (60 Hz grid), standard Default: corresponding primary over‑frequency thresho" }, { "name": "Maximum Allowable Total Grid‑side Power Import", "group": "Settings", "area": "holding", "address": 43488, "type": "uint16", "access": "RW", "unit": "W", "scale": 100.0, "description": "Standalone: 0 ~ unit rated input power × 4, default: unit rated input power Parallel: 0 ~ (unit rated input power × 4 × number of parallel u" }, { "name": "TOU Scheduled Charging Start Hour Setting 6", "group": "Settings", "area": "holding", "address": 43493, "type": "uint16", "access": "RW", "unit": "h", "description": "Upper limit uniformly set to 3 MW. Description: (1) Only used for parameter settings in Optimization Revenue V1 version. (2) Takes effect wh" }, { "name": "TOU Scheduled Charging Start Minute min Setting 6", "group": "Settings", "area": "holding", "address": 43494, "type": "uint16", "access": "RW" }, { "name": "TOU Scheduled Charging End Hour Setting 6", "group": "Settings", "area": "holding", "address": 43495, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Scheduled Charging End Minute min Setting 6", "group": "Settings", "area": "holding", "address": 43496, "type": "uint16", "access": "RW" }, { "name": "TOU Scheduled Discharging Start Hour Setting 6", "group": "Settings", "area": "holding", "address": 43497, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Scheduled min Discharging Start", "group": "Settings", "area": "holding", "address": 43498, "type": "uint16", "access": "RW" }, { "name": "Minute Setting 6 TOU Scheduled Discharging End Hour Setting 6", "group": "Settings", "area": "holding", "address": 43499, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Scheduled Discharging End min Minute Setting 6", "group": "Settings", "area": "holding", "address": 43500, "type": "uint16", "access": "RW" }, { "name": "LG High Voltage Battery Parallel Switch", "group": "Settings", "area": "holding", "address": 43630, "type": "uint16", "access": "RW", "description": "0: Off, 1: On." }, { "name": "LG High Voltage Battery Dead‑Zone Lower Limit", "group": "Settings", "area": "holding", "address": 43631, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "Range: 350–450V; default: 410 V." }, { "name": "LG High Voltage Battery Dead‑Zone Upper Limit", "group": "Settings", "area": "holding", "address": 43632, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "Range: 350~450V; default: 420V;" }, { "name": "LG High Voltage Battery Charging Slope", "group": "Settings", "area": "holding", "address": 43633, "type": "uint16", "access": "RW", "unit": "W", "description": "Range: 20–2000; 10H battery default: 250, 16H battery default: 350." }, { "name": "LG High Voltage Battery Maximum Charging Voltage", "group": "Settings", "area": "holding", "address": 43634, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "Range: 350–450 V; default: 450 V." }, { "name": "LG High Voltage Battery Discharging Slope", "group": "Settings", "area": "holding", "address": 43635, "type": "uint16", "access": "RW", "unit": "W", "description": "Range: 20–2000; 10H battery default: 250, 16H battery default: 350." }, { "name": "LG High Voltage Battery Maximum Discharging Voltage", "group": "Settings", "area": "holding", "address": 43636, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "Range: 350–450 V; default: 350 V." }, { "name": "LG High Voltage Battery Charging Limit Power", "group": "Settings", "area": "holding", "address": 43637, "type": "uint16", "access": "RW", "unit": "W", "description": "10H battery range: 0–5000 W; 16H battery range: 0–7000 W." }, { "name": "LG High Voltage Battery Discharging Limit Power", "group": "Settings", "area": "holding", "address": 43638, "type": "uint16", "access": "RW", "unit": "W", "description": "10H battery range: 0–7000 W; 16H battery range: 0–11000 W." }, { "name": "LG High Voltage Battery Communication Fault Timeout", "group": "Settings", "area": "holding", "address": 43639, "type": "uint16", "access": "RW", "unit": "min", "scale": 0.5, "description": "Range: 0.5–1440 min; default: 10 minutes." }, { "name": "LG High Voltage Battery Sleep Hold Time", "group": "Settings", "area": "holding", "address": 43640, "type": "uint32", "access": "RW", "unit": "s", "description": "Range: 0–86400; default: 86400." }, { "name": "LG High Voltage Battery Black‑Start Enable", "group": "Settings", "area": "holding", "address": 43642, "type": "uint16", "access": "RW", "description": "Range: 0–1; default: 0. In battery parallel configuration, only sent to the master battery." }, { "name": "LG High‑Voltage Battery Black‑Start", "group": "Settings", "area": "holding", "address": 43643, "type": "uint16", "access": "RW", "unit": "s", "description": "Range: 5–200 s; default: 15 s." }, { "name": "Initialization Time Backup Load Droop Control Minimum Voltage", "group": "Settings", "area": "holding", "address": 43650, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "Standard‑voltage models: phase voltage range 120–230 V, default 180 V. Low‑voltage models: phase voltage range 70–130 V, default 100 V; Line" }, { "name": "Smart Load Turn‑off SOC", "group": "Settings", "area": "holding", "address": 43672, "type": "uint16", "access": "RW", "unit": "%", "description": "Range: over‑discharge SOC (start SOC = 5%) to default 85%. Note: This setting takes effect only when BIT02 (smart load port forced grid‑tied" }, { "name": "Smart Load Turn‑on SOC", "group": "Settings", "area": "holding", "address": 43673, "type": "uint16", "access": "RW", "unit": "%", "description": "Range: (over‑discharge SOC + 5%) to 100%, default 90%, and turn‑off SOC ≤ turn‑on SOC – 5%. Note: This setting takes effect only when BIT02 " }, { "name": "Smart Load Turn‑off Battery Voltage", "group": "Settings", "area": "holding", "address": 43674, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "Range: 45–57 V, default 52 V, and turn‑off battery voltage ≤ turn‑on battery voltage – 3 V. Note: (1) Takes effect only after \"Follow Grid\" " }, { "name": "Smart Load Turn‑on Battery Voltage", "group": "Settings", "area": "holding", "address": 43675, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "Range: 50–60 V, default 55 V. Note: (1) Takes effect only after \"Follow Grid\" is set to Enable. (2) This takes effect only when setting load" }, { "name": "Over‑Discharge Full Recovery Voltage", "group": "Settings", "area": "holding", "address": 43676, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "Range: 2.0–7.0 V, default 3 V. Note: Used for lead‑acid batteries and 48 V/51.2 V non‑communication lithium batteries." }, { "name": "Off‑Grid Battery Over‑Discharge SOC", "group": "Settings", "area": "holding", "address": 43677, "type": "uint16", "access": "RW", "description": "1: Off, 2: On (register 43137 function takes effect), other values invalid. Default: 1." }, { "name": "Function Switch EPS Function Control", "group": "Settings", "area": "holding", "address": 43705, "type": "uint16", "access": "RW", "description": "0xA5 – Disabled; Backup relay is controlled according to register 43111 “Backup Load Function Enable”. 0x5A – Enabled; when grid‑tied, the B" }, { "name": "TOU Grid‑Tied Optimization Revenue V2 Switch", "group": "Settings", "area": "holding", "address": 43707, "type": "uint16", "access": "RW", "description": "When using this function, first read register 33289 to determine whether Optimization Revenue V2 is valid. If it is invalid, the Optimizatio" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Charging Period 1 Cut‑off SOC", "group": "Settings", "area": "holding", "address": 43708, "type": "uint16", "access": "RW", "unit": "%", "description": "Range: (Over‑discharge SOC + 1%) to 100%, Default: 50%." }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Charging Period 1 Battery Current", "group": "Settings", "area": "holding", "address": 43709, "type": "uint16", "access": "RW", "unit": "A", "scale": 0.1, "description": "Range: 0 – unit rated battery maximum charging current, Default: unit maximum charging current. battery rated batteries without" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Charging Period 1 Cut‑off Voltage", "group": "Settings", "area": "holding", "address": 43710, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "SOC For capability, lead‑acid including batteries and 48 V/51.2 V batteries. Lead‑acid battery range: (Over‑discharge voltage + 0.5 V) ~ (Fl" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Charging Period 1 Start Hour", "group": "Settings", "area": "holding", "address": 43711, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Charging Period 1 Start Minute", "group": "Settings", "area": "holding", "address": 43712, "type": "uint16", "access": "RW", "unit": "min" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied (43713)", "group": "Settings", "area": "holding", "address": 43713, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "Charging Period 1 End Hour TOU Optimization Revenue V2: Grid‑Tied Charging Period 1 End Minute", "group": "Settings", "area": "holding", "address": 43714, "type": "uint16", "access": "RW", "unit": "min" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Charging Period 2 Cut‑off SOC", "group": "Settings", "area": "holding", "address": 43715, "type": "uint16", "access": "RW", "unit": "%", "description": "Range: (Over‑discharge SOC + 1%) to 100%, Default: 50%. Note: For lithium batteries with SOC capability." }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Charging Period 2 Battery Current", "group": "Settings", "area": "holding", "address": 43716, "type": "uint16", "access": "RW", "unit": "A", "scale": 0.1, "description": "Range: 0 – unit rated battery maximum charging current, unit Default: maximum charging current. battery rated batteries without" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Charging Period 2 Cut‑off Voltage", "group": "Settings", "area": "holding", "address": 43717, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "For SOC lead‑acid including capability, batteries and 48 V/51.2 V batteries. Lead‑acid battery range: (Over‑discharge voltage + 0.5 V) ~ (Fl" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Charging Period 2 Start Hour", "group": "Settings", "area": "holding", "address": 43718, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Charging Period 2 Start Minute", "group": "Settings", "area": "holding", "address": 43719, "type": "uint16", "access": "RW", "unit": "min" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Charging Period 2 End Hour", "group": "Settings", "area": "holding", "address": 43720, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied (43721)", "group": "Settings", "area": "holding", "address": 43721, "type": "uint16", "access": "RW", "unit": "min" }, { "name": "Charging Period 2 End Minute TOU Optimization Revenue V2: Grid‑Tied Charging Period 3 Cut‑off SOC", "group": "Settings", "area": "holding", "address": 43722, "type": "uint16", "access": "RW", "unit": "%", "description": "Range: (Over‑discharge SOC + 1%) to 100%, Default: 50%. Note: For lithium batteries with SOC capability." }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Charging Period 3 Battery Current", "group": "Settings", "area": "holding", "address": 43723, "type": "uint16", "access": "RW", "unit": "A", "scale": 0.1, "description": "Range: 0 – unit rated battery maximum charging current, unit Default: maximum charging current. battery rated batteries without" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Charging Period 3 Cut‑off Voltage", "group": "Settings", "area": "holding", "address": 43724, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "SOC For capability, lead‑acid including batteries and 48 V/51.2 V batteries. Lead‑acid battery range: (Over‑discharge voltage + 0.5 V) ~ (Fl" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Charging Period 3 Start Hour", "group": "Settings", "area": "holding", "address": 43725, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Charging Period 3 Start Minute", "group": "Settings", "area": "holding", "address": 43726, "type": "uint16", "access": "RW", "unit": "min" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Charging Period 3 End Hour", "group": "Settings", "area": "holding", "address": 43727, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Charging Period 3 End Minute", "group": "Settings", "area": "holding", "address": 43728, "type": "uint16", "access": "RW", "unit": "min" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied (43729)", "group": "Settings", "area": "holding", "address": 43729, "type": "uint16", "access": "RW", "unit": "%", "description": "Range: (Over‑discharge SOC + 1%) to 100%, Default: 50%. Note: For lithium batteries with SOC capability." }, { "name": "Charging Period 4 Cut‑off SOC TOU Optimization Revenue V2: Grid‑Tied Charging Period 4 Battery Current", "group": "Settings", "area": "holding", "address": 43730, "type": "uint16", "access": "RW", "unit": "A", "scale": 0.1, "description": "Range: 0 – unit rated battery maximum charging current, Default: unit maximum charging current. battery rated batteries without" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Charging Period 4 Cut‑off Voltage", "group": "Settings", "area": "holding", "address": 43731, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "SOC For capability, lead‑acid including batteries and 48 V/51.2 V batteries. Lead‑acid battery range: (Over‑discharge voltage + 0.5 V) ~ (Fl" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Charging Period 4 Start Hour", "group": "Settings", "area": "holding", "address": 43732, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Charging Period 4 Start Minute", "group": "Settings", "area": "holding", "address": 43733, "type": "uint16", "access": "RW", "unit": "min" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Charging Period 4 End Hour", "group": "Settings", "area": "holding", "address": 43734, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Charging Period 4 End Minute", "group": "Settings", "area": "holding", "address": 43735, "type": "uint16", "access": "RW", "unit": "min" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Charging Period 5 Cut‑off SOC", "group": "Settings", "area": "holding", "address": 43736, "type": "uint16", "access": "RW", "unit": "%", "description": "Range: (Over‑discharge SOC + 1%) to 100%, Default: 50%. Note: For lithium batteries with SOC capability." }, { "name": "TOU Optimization (43737)", "group": "Settings", "area": "holding", "address": 43737, "type": "uint16", "access": "RW", "unit": "A", "scale": 0.1, "description": "Range: 0 – unit rated battery maximum charging current, Default: unit maximum charging current. rated battery batteries without" }, { "name": "Revenue V2: Grid‑Tied Charging Period 5 Battery Current TOU Optimization Revenue V2: Grid‑Tied Charging Period 5 Cut‑off Voltage", "group": "Settings", "area": "holding", "address": 43738, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "SOC For capability, lead‑acid including batteries and 48 V/51.2 V batteries. Lead‑acid battery range: (Over‑discharge voltage + 0.5 V) ~ (Fl" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Charging Period 5 Start Hour", "group": "Settings", "area": "holding", "address": 43739, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Charging Period 5 Start Minute", "group": "Settings", "area": "holding", "address": 43740, "type": "uint16", "access": "RW", "unit": "min" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Charging Period 5 End Hour", "group": "Settings", "area": "holding", "address": 43741, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Charging Period 5 End Minute", "group": "Settings", "area": "holding", "address": 43742, "type": "uint16", "access": "RW", "unit": "min" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Charging Period 6 Cut‑off SOC", "group": "Settings", "area": "holding", "address": 43743, "type": "uint16", "access": "RW", "unit": "%", "description": "Range: (Over‑discharge SOC + 1%) to 100%, Default: 50%. Note: For lithium batteries with SOC capability." }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Charging Period 6 Battery Current", "group": "Settings", "area": "holding", "address": 43744, "type": "uint16", "access": "RW", "unit": "A", "scale": 0.1, "description": "Range: 0 – unit rated battery maximum charging current, unit Default: maximum charging current. battery rated" }, { "name": "TOU Optimization (43745)", "group": "Settings", "area": "holding", "address": 43745, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "For batteries without SOC lead‑acid including capability, batteries and 48 V/51.2 V batteries. Lead‑acid battery range: (Over‑discharge volt" }, { "name": "Revenue V2: Grid‑Tied Charging Period 6 Cut‑off Voltage TOU Optimization Revenue V2: Grid‑Tied Charging Period 6 Start Hour", "group": "Settings", "area": "holding", "address": 43746, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Charging Period 6 Start Minute", "group": "Settings", "area": "holding", "address": 43747, "type": "uint16", "access": "RW", "unit": "min" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Charging Period 6 End Hour", "group": "Settings", "area": "holding", "address": 43748, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Charging Period 6 End Minute", "group": "Settings", "area": "holding", "address": 43749, "type": "uint16", "access": "RW", "unit": "min" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Discharging Period 1 Cut‑off SOC", "group": "Settings", "area": "holding", "address": 43750, "type": "uint16", "access": "RW", "unit": "%", "description": "Range: (Over‑discharge SOC + 1%) to 100%, Default: 50%. Note: For lithium batteries with SOC capability." }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Discharging Period 1 Battery Current", "group": "Settings", "area": "holding", "address": 43751, "type": "uint16", "access": "RW", "unit": "A", "scale": 0.1, "description": "Range: 0 – unit rated battery maximum discharging current, Default: unit maximum discharging current. battery rated" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Discharging Period 1 Cut‑off Voltage", "group": "Settings", "area": "holding", "address": 43752, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "batteries without SOC For capability, lead‑acid including batteries and 48 V/51.2 V batteries. Lead‑acid battery range: (Over‑discharge volt" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Discharging Period 1 Start Hour", "group": "Settings", "area": "holding", "address": 43753, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Discharging Period 1 Start Minute", "group": "Settings", "area": "holding", "address": 43754, "type": "uint16", "access": "RW", "unit": "min" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Discharging Period 1 End Hour", "group": "Settings", "area": "holding", "address": 43755, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Discharging Period 1 End Minute", "group": "Settings", "area": "holding", "address": 43756, "type": "uint16", "access": "RW", "unit": "min" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Discharging Period 2 Cut‑off SOC", "group": "Settings", "area": "holding", "address": 43757, "type": "uint16", "access": "RW", "unit": "%", "description": "Range: (Over‑discharge SOC + 1%) to 100%, Default: 50%. Note: For lithium batteries with SOC capability." }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Discharging Period 2 Battery Current", "group": "Settings", "area": "holding", "address": 43758, "type": "uint16", "access": "RW", "unit": "A", "scale": 0.1, "description": "Range: 0 – unit rated battery maximum discharging current, Default: unit maximum discharging current. battery rated batteries without" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Discharging Period 2 Cut‑off Voltage", "group": "Settings", "area": "holding", "address": 43759, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "SOC For capability, lead‑acid including batteries and 48 V/51.2 V batteries. Lead‑acid battery range: (Over‑discharge voltage + 0.5 V) ~ (Fl" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Discharging Period 2 Start Hour", "group": "Settings", "area": "holding", "address": 43760, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Discharging Period 2 Start Minute", "group": "Settings", "area": "holding", "address": 43761, "type": "uint16", "access": "RW", "unit": "min" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Discharging Period 2 End Hour", "group": "Settings", "area": "holding", "address": 43762, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Discharging Period 2 End Minute", "group": "Settings", "area": "holding", "address": 43763, "type": "uint16", "access": "RW", "unit": "min" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Discharging Period 3 Cut‑off SOC", "group": "Settings", "area": "holding", "address": 43764, "type": "uint16", "access": "RW", "unit": "%", "description": "Range: (Over‑discharge SOC + 1%) to 100%, Default: 50%. Note: For lithium batteries with SOC capability." }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Discharging Period 3 Battery Current", "group": "Settings", "area": "holding", "address": 43765, "type": "uint16", "access": "RW", "unit": "A", "scale": 0.1, "description": "Range: 0 – unit rated battery maximum discharging current, unit Default: maximum discharging current. battery rated batteries without" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Discharging Period 3 Cut‑off Voltage", "group": "Settings", "area": "holding", "address": 43766, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "For SOC lead‑acid including capability, batteries and 48 V/51.2 V batteries. Lead‑acid battery range: (Over‑discharge voltage + 0.5 V) ~ (Fl" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Discharging Period 3 Start Hour", "group": "Settings", "area": "holding", "address": 43767, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Discharging Period 3 Start Minute", "group": "Settings", "area": "holding", "address": 43768, "type": "uint16", "access": "RW", "unit": "min" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Discharging Period 3 End Hour", "group": "Settings", "area": "holding", "address": 43769, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Discharging Period 3 End Minute", "group": "Settings", "area": "holding", "address": 43770, "type": "uint16", "access": "RW", "unit": "min" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Discharging Period 4 Cut‑off SOC", "group": "Settings", "area": "holding", "address": 43771, "type": "uint16", "access": "RW", "unit": "%", "description": "Range: (Over‑discharge SOC + 1%) to 100%, Default: 50%. Note: For lithium batteries with SOC capability." }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Discharging Period 4 Battery Current", "group": "Settings", "area": "holding", "address": 43772, "type": "uint16", "access": "RW", "unit": "A", "scale": 0.1, "description": "rated battery Range: 0 – unit rated battery maximum discharging current, unit Default: maximum discharging current. 10<-->1V ; For batteries" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Discharging Period 4 Cut‑off Voltage", "group": "Settings", "area": "holding", "address": 43773, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1 }, { "name": "TOU Optimization Revenue V2: Grid‑Tied (43774)", "group": "Settings", "area": "holding", "address": 43774, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "Discharging Period 4 Start Hour TOU Optimization Revenue V2: Grid‑Tied Discharging Period 4 Start Minute", "group": "Settings", "area": "holding", "address": 43775, "type": "uint16", "access": "RW", "unit": "min" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Discharging Period 4 End Hour", "group": "Settings", "area": "holding", "address": 43776, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Discharging Period 4 End Minute", "group": "Settings", "area": "holding", "address": 43777, "type": "uint16", "access": "RW", "unit": "min" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Discharging Period 5 Cut‑off SOC", "group": "Settings", "area": "holding", "address": 43778, "type": "uint16", "access": "RW", "unit": "%", "description": "Range: (Over‑discharge SOC + 1%) to 100%, Default: 50%. Note: For lithium batteries with SOC capability." }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Discharging Period 5 Battery Current", "group": "Settings", "area": "holding", "address": 43779, "type": "uint16", "access": "RW", "unit": "A", "scale": 0.1, "description": "Range: 0 – unit rated battery maximum discharging current, Default: unit maximum discharging current. battery rated batteries without" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Discharging Period 5 Cut‑off Voltage", "group": "Settings", "area": "holding", "address": 43780, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "SOC For capability, lead‑acid including batteries and 48 V/51.2 V batteries. Lead‑acid battery range: (Over‑discharge voltage + 0.5 V) ~ (Fl" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Discharging Period 5 Start Hour", "group": "Settings", "area": "holding", "address": 43781, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied (43782)", "group": "Settings", "area": "holding", "address": 43782, "type": "uint16", "access": "RW", "unit": "min" }, { "name": "Discharging Period 5 Start Minute TOU Optimization Revenue V2: Grid‑Tied Discharging Period 5 End Hour", "group": "Settings", "area": "holding", "address": 43783, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Discharging Period 5 End Minute", "group": "Settings", "area": "holding", "address": 43784, "type": "uint16", "access": "RW", "unit": "min" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Discharging Period 6 Cut‑off SOC", "group": "Settings", "area": "holding", "address": 43785, "type": "uint16", "access": "RW", "unit": "%", "description": "Range: (Over‑discharge SOC + 1%) to 100%, Default: 50%. Note: For lithium batteries with SOC capability." }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Discharging Period 6 Battery Current", "group": "Settings", "area": "holding", "address": 43786, "type": "uint16", "access": "RW", "unit": "A", "scale": 0.1, "description": "rated battery Range: 0 – unit rated battery maximum discharging current, Default: unit maximum discharging current. 10<-->1V ; For batteries" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Discharging Period 6 Cut‑off Voltage", "group": "Settings", "area": "holding", "address": 43787, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "battery battery V" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Discharging Period 6 Start Hour", "group": "Settings", "area": "holding", "address": 43788, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied Discharging Period 6 Start Minute", "group": "Settings", "area": "holding", "address": 43789, "type": "uint16", "access": "RW", "unit": "min" }, { "name": "TOU Optimization Revenue V2: Grid‑Tied (43790)", "group": "Settings", "area": "holding", "address": 43790, "type": "uint16", "access": "RW", "unit": "h" }, { "name": "Discharging Period 6 End Hour TOU Optimization Revenue V2: Grid‑Tied Discharging Period 6 End Minute", "group": "Settings", "area": "holding", "address": 43791, "type": "uint16", "access": "RW", "unit": "min" }, { "name": "Generator Minimum Input Power", "group": "Settings", "area": "holding", "address": 43792, "type": "uint16", "access": "RW", "unit": "W", "scale": 10.0, "description": "Range: 0 – unit rated value × number of parallel units Default: 1 kW." }, { "name": "Dual‑Battery Connection Mode", "group": "Settings", "area": "holding", "address": 43802, "type": "uint16", "access": "RW", "description": "1: Battery Independent, 2Batt2DC 2: Battery Shared, 1Batt2DC 3: Single battery connected to one battery port – 1Batt1DC Other values: Invali" }, { "name": "Battery 2 Type Setting", "group": "Settings", "area": "holding", "address": 43803, "type": "uint16", "access": "RW", "description": "For details, see Appendix 6: Battery Numbering. Battery 2 settings are only applicable to energy storage models that support dual‑battery co" }, { "name": "Battery 2 Maximum Charging Current Setting", "group": "Settings", "area": "holding", "address": 43804, "type": "uint16", "access": "RW", "unit": "A", "scale": 0.1 }, { "name": "Battery 2 Maximum Discharging Current Setting", "group": "Settings", "area": "holding", "address": 43805, "type": "uint16", "access": "RW", "unit": "A", "scale": 0.1 }, { "name": "Battery 2 Under‑Voltage Protection Setting", "group": "Settings", "area": "holding", "address": 43806, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1 }, { "name": "Battery 2 Equalization Charge Voltage Setting", "group": "Settings", "area": "holding", "address": 43808, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1 }, { "name": "Battery 2 Over‑Voltage Protection Setting", "group": "Settings", "area": "holding", "address": 43809, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1 }, { "name": "Battery 2 Over‑Discharge SOC", "group": "Settings", "area": "holding", "address": 43810, "type": "uint16", "access": "RW", "unit": "%" }, { "name": "Battery 2 Over‑Discharge Hysteresis SOC", "group": "Settings", "area": "holding", "address": 43811, "type": "uint16", "access": "RW", "unit": "%" }, { "name": "Battery 2 Forced Charge SOC", "group": "Settings", "area": "holding", "address": 43812, "type": "uint16", "access": "RW", "unit": "%" }, { "name": "Battery 2", "group": "Settings", "area": "holding", "address": 43813, "type": "uint16", "access": "RW", "unit": "s", "description": "Range: 20–3600 s, default: 180 s. the" }, { "name": "Auto‑Wake‑up Duration Setting Battery 2 Type Setting Follows Battery 1.", "group": "Settings", "area": "holding", "address": 43814, "type": "uint16", "access": "RW", "description": "read 0xAA55: Follow – for Battery 2 are parameters consistent with Battery 1, and writing to the Battery 2 type setting register is invalid." }, { "name": "Battery 2 Wake‑up Voltage", "group": "Settings", "area": "holding", "address": 43858, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "Low‑voltage energy storage unit: 40–60 V, default 40 V. Off‑grid energy storage unit: 40–60 V, default 40 V. Single‑phase high‑voltage energ" }, { "name": "Battery 2 Wake‑up Time", "group": "Settings", "area": "holding", "address": 43859, "type": "uint16", "access": "RW", "unit": "s", "description": "Range: 20–3600 s, default: 20 s." }, { "name": "PCS Limiting Mode Setting", "group": "Settings", "area": "holding", "address": 43860, "type": "uint16", "access": "RW", "description": "PCS Anti‑Reverse‑Flow Limiting Mode Settings: 0: No limit mode (no restriction on energy exchange between battery and grid). 1: Output limit" }, { "name": "Grid‑Side Load Single‑Phase Protection Current Limit", "group": "Settings", "area": "holding", "address": 43861, "type": "uint16", "access": "RW", "unit": "A", "description": "load When connected to the distribution panel exceeds the protection limit of the inverter distribution panel, switches to off‑grid operatio" }, { "name": "PCS Input Limit Battery Current Limit", "group": "Settings", "area": "holding", "address": 43862, "type": "uint16", "access": "RW", "unit": "A", "scale": 0.1, "description": "When the PCS limiting mode is configured as input limit mode, this is the allowable current limit for the grid. battery charging from Settin" }, { "name": "PCS Output Limit Battery Current Limit", "group": "Settings", "area": "holding", "address": 43863, "type": "uint16", "access": "RW", "unit": "A", "scale": 0.1, "description": "When the PCS limiting mode is configured as output limit mode, this is the allowable current limit for battery discharging to the grid. Sett" }, { "name": "PV Inverter AC Output Side CT Ratio", "group": "Settings", "area": "holding", "address": 43864, "type": "uint16", "access": "RW", "description": "Range: 1–2000, default: 1000. Settings are retained after power loss. Currently only supported for S6 AC Coupled models." }, { "name": "Grid‑Side Load Single‑Phase Overcurrent Protection Switch", "group": "Settings", "area": "holding", "address": 43871, "type": "uint16", "access": "RW", "description": "0 – Off, 1 – On, default: 1. Other values: Invalid." }, { "name": "Heat Pump Function Switch", "group": "Settings", "area": "holding", "address": 43885, "type": "uint16", "access": "RW", "description": "BIT00: Heat pump function master switch – 0: Off, 1: On, default 0. BIT01: Heat pump manual mode – 0: Normal, 1: Enhanced, default 0. BIT02:" }, { "name": "Heat Pump Minimum Control Time Interval", "group": "Settings", "area": "holding", "address": 43886, "type": "uint16", "access": "RW", "unit": "min", "description": "Range: 5–60, default: 10." }, { "name": "Heat Pump Intelligent Control Mode Start SOC", "group": "Settings", "area": "holding", "address": 43971, "type": "uint16", "access": "RW", "unit": "%", "description": "Range: (Over‑discharge SOC + 5%) to 100%, default: 90%. Note: Over‑discharge SOC register address is 43011." }, { "name": "Heat Pump Intelligent Control Mode Stop SOC", "group": "Settings", "area": "holding", "address": 43972, "type": "uint16", "access": "RW", "unit": "%", "description": "Range: Over‑discharge SOC (Start SOC – 5%), default: 70%. to" }, { "name": "Heat Pump Intelligent Control Mode Start Voltage", "group": "Settings", "area": "holding", "address": 43973, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "Start voltage ≥ (Stop voltage + 2 V) Range: 42.0 – 60.0 V (max 59.5 V) Default: Lead‑acid battery: 55 V, 48 V non‑communication lithium batt" }, { "name": "Heat Pump Intelligent Control Mode Stop Voltage", "group": "Settings", "area": "holding", "address": 43974, "type": "uint16", "access": "RW", "unit": "V", "scale": 0.1, "description": "Start voltage ≥ (Stop voltage + 2 V) Range: 40.0 – 60.0 V (max 57.5 V) Default: Lead‑acid battery: 50 V, 48 V non‑communication lithium batt" }, { "name": "Maximum Total Feed‑in Active Power under Phase Unbalance Mode", "group": "Settings", "area": "holding", "address": 43975, "type": "int32", "access": "RW", "unit": "W", "description": "Indicates the sum of active power from all phases. Standalone range: 0–1,000,000 W, default: 1.1 times the unit rated power. range: 0–1,000," }, { "name": "Paid leasing function", "group": "Settings", "area": "holding", "address": 43977, "type": "uint16", "access": "RW", "description": "0x0000: Off 0x0001: On Default: 0x0000 (Off), other values invalid." }, { "name": "Paid Rental Equipment Lock Function Switch – Lock", "group": "Settings", "area": "holding", "address": 43978, "type": "uint16", "access": "RW", "description": "0x0000: Off 0x0001: On Default: 0x0000 (Off), other values invalid. Only effective when the paid rental function is enabled (register 43977 " }, { "name": "Heat Pump Intelligent Control Mode Enable Power", "group": "Settings", "area": "holding", "address": 43984, "type": "int16", "access": "RW", "unit": "kW", "scale": 0.1, "description": "Range: 0.1–1000 kW, default: 2 kW. Enable power > Disable power." }, { "name": "Heat Pump Intelligent Control Mode Disable Power", "group": "Settings", "area": "holding", "address": 43985, "type": "int16", "access": "RW", "unit": "kW", "scale": 0.1, "description": "Range: –5 to 10 kW, default: –0.5 kW. Enable power > Disable power. 0:None 1:Based on Export Power&SOC 2:Second RS485(Only for Solis INV) Ot" }, { "name": "AC coupling Max Export Control", "group": "Settings", "area": "holding", "address": 43989, "type": "uint16", "access": "RW" }, { "name": "Dynamic Reactive Power Compensation Switch", "group": "Settings", "area": "holding", "address": 43998, "type": "uint16", "access": "RW", "description": "0: Off, 1: On, default: Off. Meaning: When Dynamic Reactive Power Compensation (SVG) is enabled, the inverter automatically compensates the " }, { "name": "AC Coupling Connected to AC Side", "group": "Settings", "area": "holding", "address": 44099, "type": "uint16", "access": "RW", "description": "0x01 – Disabled, 0x02 – Enabled, Other values invalid, default: 0x01." }, { "name": "Remote Dispatch Mode Switch", "group": "Settings", "area": "holding", "address": 44100, "type": "uint16", "access": "RW", "description": "the 0: Off, 1: On, default 0, other values invalid. Description: This function takes effect when register 34502 = 0xAA55; specific function " }, { "name": "Remote Dispatch Mode – Failsafe Interval", "group": "Settings", "area": "holding", "address": 44101, "type": "uint16", "access": "RW", "unit": "min", "description": "1–1440, Range: out‑of‑range settings are invalid. default: 5;" }, { "name": "Remote Dispatch Mode – System Limiting Switch", "group": "Settings", "area": "holding", "address": 44102, "type": "uint16", "access": "RW", "description": "BIT00: System power‑draw active power upper‑limit switch – 0: (system Disabled, 1: Enabled power‑draw power takes effect), upper‑limit setti" }, { "name": "Remote Dispatch Mode – System Power‑Draw Active Power Upper Limit", "group": "Settings", "area": "holding", "address": 44103, "type": "uint16", "access": "RW", "unit": "W", "scale": 100.0, "description": "Standalone range: 0 ~ 4 × unit maximum rated value, Parallel range: 0 ~ 4 × unit maximum rated value × number of parallel units, Default: In" }, { "name": "Remote Dispatch Mode – System Feed‑in Active Power Upper Limit", "group": "Settings", "area": "holding", "address": 44104, "type": "uint16", "access": "RW", "unit": "W", "scale": 100.0, "description": "Standalone range: 0 ~ 4 × unit maximum rated value, Parallel range: 0 ~ 4 × unit maximum rated value × number of parallel units, Default: In" }, { "name": "Remote Dispatch Mode – Real‑Time Control – Control Mode", "group": "Settings", "area": "holding", "address": 44105, "type": "uint16", "access": "RW", "description": "– Battery charge/discharge 1 – Battery Standby control (no charging/discharging) 2 control 3 – Point of Common Coupling (PCC) Import/Export " }, { "name": "Remote Dispatch Mode – Real‑Time Control – Power Setting", "group": "Settings", "area": "holding", "address": 44106, "type": "int32", "access": "RW", "unit": "W", "scale": 10.0, "description": "The function is determined by the control mode in register 44105. Default: 0; out‑of‑range settings are invalid. (1) When the control mode i" }, { "name": "Remote Dispatch Mode – Real‑Time Control – Function Switch", "group": "Settings", "area": "holding", "address": 44108, "type": "uint16", "access": "RW", "description": "BIT00–BIT01: Shutdown control – 0: invalid, 1: disabled, 2: enabled, 3: invalid, default 0. BIT02–BIT03: DO control – 0: invalid, 1: open, 2" }, { "name": "Remote Dispatch Mode – Real‑Time Control – SOC Lower Limit", "group": "Settings", "area": "holding", "address": 44109, "type": "uint16", "access": "RW", "unit": "%", "description": "Range: 0 to Real‑Time Control SOC Upper Limit, default 0. If out of range or greater than/equal to the Real‑Time Control SOC Upper Limit, th" }, { "name": "Remote Dispatch Mode – Real‑Time Control – SOC Upper Limit", "group": "Settings", "area": "holding", "address": 44110, "type": "uint16", "access": "RW", "unit": "%", "description": "Range: Real‑Time Control SOC Lower Limit to 100%, default 100%. If out of range or less than/equal to the Real‑Time Control SOC Lower Limit," }, { "name": "Remote Dispatch Mode – Real‑Time Control – Battery Reserve SOC", "group": "Settings", "area": "holding", "address": 44111, "type": "uint16", "access": "RW", "unit": "%", "description": "to Range: Over‑discharge SOC Real‑Time Control Upper Limit SOC, default 40%. Description: (1) Over‑discharge SOC is set in register 43011; R" }, { "name": "Remote Dispatch Mode – Real‑Time Control – PV Power‑Limit Percentage", "group": "Settings", "area": "holding", "address": 44112, "type": "uint16", "access": "RW", "unit": "%", "scale": 0.01, "description": "100 <--> 1% Description: (1) Takes effect when the PV power‑limit percentage switch is enabled. (2) Available in remote dispatch mode versio" }, { "name": "Remote Dispatch Mode – Real‑Time Control – Reserved 3", "group": "Settings", "area": "holding", "address": 44113, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Real‑Time Control – Reserved 4", "group": "Settings", "area": "holding", "address": 44114, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Real‑Time Control – Reserved 5", "group": "Settings", "area": "holding", "address": 44115, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 1 – Switch", "group": "Settings", "area": "holding", "address": 44116, "type": "uint16", "access": "RW", "description": "0: Disabled 1: Enabled Default 0, other values invalid. range 0–23," }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 1 – Start Time Setting", "group": "Settings", "area": "holding", "address": 44117, "type": "uint16", "access": "RW", "description": "High byte: Hour, default 0, other values invalid. Low byte: Minute, range 0–59, default 0, other values invalid. time periods must not Enabl" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 1 – End Time Setting", "group": "Settings", "area": "holding", "address": 44118, "type": "uint16", "access": "RW", "description": "range 0–23, High byte: Hour, default 0, other values invalid. Low byte: Minute, range 0–59, default 0, other values invalid." }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 1 – Control Mode 44120~ Remote Dispatch Mode", "group": "Settings", "area": "holding", "address": 44119, "type": "int32", "access": "RW", "unit": "W", "scale": 10.0, "description": "– Battery charge/discharge 1 – Battery Standby control (no charging/discharging) 2 control 3 – Point of Common Coupling (PCC) Import/Export " }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 1 – Function Switch", "group": "Settings", "area": "holding", "address": 44122, "type": "uint16", "access": "RW", "description": "Range: –(inverter maximum output power × number of parallel units) ~ +(inverter maximum output power × number of parallel units). (4) When t" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 1 – SOC Lower Limit", "group": "Settings", "area": "holding", "address": 44123, "type": "uint16", "access": "RW", "description": "Range: 0 to Period 1 SOC Upper Limit, default 0. If out of range or greater than/equal to Period 1 SOC Upper Limit, the setting is invalid." }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 1 – SOC Upper Limit", "group": "Settings", "area": "holding", "address": 44124, "type": "uint16", "access": "RW", "description": "Range: Period 1 SOC Lower Limit to 100%, default 100%. If out of range or less than/equal to Period 1 SOC Lower Limit, the setting is invali" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 1 – Battery Reserve SOC", "group": "Settings", "area": "holding", "address": 44125, "type": "uint16", "access": "RW", "description": "Range: Over‑discharge SOC to Time‑Scheduled Control Period 1 Upper Limit SOC, default 40%. Description: (1) Over‑discharge SOC is set in reg" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 1 – PV", "group": "Settings", "area": "holding", "address": 44126, "type": "uint16", "access": "RW", "description": "100 ↔ 1% Notes: (1) Takes effect when the PV power is switch limiting percentage enabled. (2) Available for remote dispatch mode Version V03" }, { "name": "Power‑Limit Percentage Remote Dispatch Mode – Time‑Scheduled Control – Period 1 – Reserved 3", "group": "Settings", "area": "holding", "address": 44127, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 1 – Reserved 4", "group": "Settings", "area": "holding", "address": 44128, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 1 – Reserved 5", "group": "Settings", "area": "holding", "address": 44129, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 2 – Switch", "group": "Settings", "area": "holding", "address": 44130, "type": "uint16", "access": "RW", "description": "The content format of Segment 2 is the same as Segment 1." }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 2 – Start Time Setting", "group": "Settings", "area": "holding", "address": 44131, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 2 – End Time Setting", "group": "Settings", "area": "holding", "address": 44132, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 2 – Control Mode", "group": "Settings", "area": "holding", "address": 44133, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 2 – Power Setting", "group": "Settings", "area": "holding", "address": 44134, "type": "int32", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 2 – Function Switch", "group": "Settings", "area": "holding", "address": 44136, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 2 –", "group": "Settings", "area": "holding", "address": 44137, "type": "uint16", "access": "RW" }, { "name": "SOC Lower Limit Remote Dispatch Mode – Time‑Scheduled Control – Period 2 – SOC Upper Limit", "group": "Settings", "area": "holding", "address": 44138, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 2 – Reserved 1", "group": "Settings", "area": "holding", "address": 44139, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 2 – Reserved 2", "group": "Settings", "area": "holding", "address": 44140, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 2 – Reserved 3", "group": "Settings", "area": "holding", "address": 44141, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 2 – Reserved 4", "group": "Settings", "area": "holding", "address": 44142, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 2 – Reserved 5", "group": "Settings", "area": "holding", "address": 44143, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 3 – Switch", "group": "Settings", "area": "holding", "address": 44144, "type": "uint16", "access": "RW", "description": "The content format of Segment 3 is the same as Segment 1." }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 3 – Start Time Setting", "group": "Settings", "area": "holding", "address": 44145, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 3 – End Time Setting", "group": "Settings", "area": "holding", "address": 44146, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 3 – Control Mode", "group": "Settings", "area": "holding", "address": 44147, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 3 –", "group": "Settings", "area": "holding", "address": 44148, "type": "int32", "access": "RW" }, { "name": "Power Setting Remote Dispatch Mode – Time‑Scheduled Control – Period 3 – Function Switch", "group": "Settings", "area": "holding", "address": 44150, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 3 – SOC Lower Limit", "group": "Settings", "area": "holding", "address": 44151, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 3 – SOC Upper Limit", "group": "Settings", "area": "holding", "address": 44152, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 3 – Reserved 1", "group": "Settings", "area": "holding", "address": 44153, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 3 – Reserved 2", "group": "Settings", "area": "holding", "address": 44154, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 3 – Reserved 3", "group": "Settings", "area": "holding", "address": 44155, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 3 – Reserved 4", "group": "Settings", "area": "holding", "address": 44156, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 3 – Reserved 5", "group": "Settings", "area": "holding", "address": 44157, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 4 – Switch", "group": "Settings", "area": "holding", "address": 44158, "type": "uint16", "access": "RW", "description": "The content format of Segment 4 is the same as Segment 1." }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 4 – Start Time Setting", "group": "Settings", "area": "holding", "address": 44159, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 4 –", "group": "Settings", "area": "holding", "address": 44160, "type": "uint16", "access": "RW" }, { "name": "End Time Setting Remote Dispatch Mode – Time‑Scheduled Control – Period 4 – Control Mode", "group": "Settings", "area": "holding", "address": 44161, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 4 – Power Setting", "group": "Settings", "area": "holding", "address": 44162, "type": "int32", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 4 – Function Switch", "group": "Settings", "area": "holding", "address": 44164, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 4 – SOC Lower Limit", "group": "Settings", "area": "holding", "address": 44165, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 4 – SOC Upper Limit", "group": "Settings", "area": "holding", "address": 44166, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 4 – Reserved 1", "group": "Settings", "area": "holding", "address": 44167, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 4 – Reserved 2", "group": "Settings", "area": "holding", "address": 44168, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 4 – Reserved 3", "group": "Settings", "area": "holding", "address": 44169, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 4 – Reserved 4", "group": "Settings", "area": "holding", "address": 44170, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 4 – Reserved 5", "group": "Settings", "area": "holding", "address": 44171, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 5 – (44172)", "group": "Settings", "area": "holding", "address": 44172, "type": "uint16", "access": "RW", "description": "The content format of Segment 5 is the same as Segment 1." }, { "name": "Switch Remote Dispatch Mode – Time‑Scheduled Control – Period 5 – Start Time Setting", "group": "Settings", "area": "holding", "address": 44173, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 5 – End Time Setting", "group": "Settings", "area": "holding", "address": 44174, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 5 – Control Mode", "group": "Settings", "area": "holding", "address": 44175, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 5 – Power Setting", "group": "Settings", "area": "holding", "address": 44176, "type": "int32", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 5 – Function Switch", "group": "Settings", "area": "holding", "address": 44178, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 5 – SOC Lower Limit", "group": "Settings", "area": "holding", "address": 44179, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 5 – SOC Upper Limit", "group": "Settings", "area": "holding", "address": 44180, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 5 – Reserved 1", "group": "Settings", "area": "holding", "address": 44181, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 5 – Reserved 2", "group": "Settings", "area": "holding", "address": 44182, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 5 – Reserved 3", "group": "Settings", "area": "holding", "address": 44183, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 5 – (44184)", "group": "Settings", "area": "holding", "address": 44184, "type": "uint16", "access": "RW" }, { "name": "Reserved 4 Remote Dispatch Mode – Time‑Scheduled Control – Period 5 – Reserved 5", "group": "Settings", "area": "holding", "address": 44185, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 6 – Switch", "group": "Settings", "area": "holding", "address": 44186, "type": "uint16", "access": "RW", "description": "The content format of Segment 6 is the same as Segment 1." }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 6 – Start Time Setting", "group": "Settings", "area": "holding", "address": 44187, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 6 – End Time Setting", "group": "Settings", "area": "holding", "address": 44188, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 6 – Control Mode", "group": "Settings", "area": "holding", "address": 44189, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 6 – Power Setting", "group": "Settings", "area": "holding", "address": 44190, "type": "int32", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 6 – Function Switch", "group": "Settings", "area": "holding", "address": 44192, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 6 – SOC Lower Limit", "group": "Settings", "area": "holding", "address": 44193, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 6 – SOC Upper Limit", "group": "Settings", "area": "holding", "address": 44194, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 6 – Reserved 1", "group": "Settings", "area": "holding", "address": 44195, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 6 –", "group": "Settings", "area": "holding", "address": 44196, "type": "uint16", "access": "RW" }, { "name": "Reserved 2 Remote Dispatch Mode – Time‑Scheduled Control – Period 6 – Reserved 3", "group": "Settings", "area": "holding", "address": 44197, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 6 – Reserved 4", "group": "Settings", "area": "holding", "address": 44198, "type": "uint16", "access": "RW" }, { "name": "Remote Dispatch Mode – Time‑Scheduled Control – Period 6 – Reserved 5", "group": "Settings", "area": "holding", "address": 44199, "type": "uint16", "access": "RW" }, { "name": "ARM EMS Port Baud Rate Setting", "group": "Settings", "area": "holding", "address": 44202, "type": "uint16", "access": "RW", "description": "Baud Rate List: 96 <->9600bps, 192<->19200bps, 384<->38400bps; 576<->57600bps; 1152<->115200bps; Other values invalid. Note: Currently only " }, { "name": "Utility Bypass Function Switch Setting", "group": "Settings", "area": "holding", "address": 44205, "type": "uint16", "access": "RW" }, { "name": "PV Storage System Grid‑tied Inverter Total Capacity", "group": "Settings", "area": "holding", "address": 44220, "type": "uint32", "access": "RW", "unit": "kW", "scale": 0.1, "description": "Range:10~50000(Upper limit: 5 MW)" }, { "name": "PV Storage System Grid‑tied Inverter Quantity", "group": "Settings", "area": "holding", "address": 44222, "type": "uint16", "access": "RW", "description": "Range:0~20,default: 0" }, { "name": "PV Storage System Anti‑Reverse‑Flow Control Strategy", "group": "Settings", "area": "holding", "address": 44223, "type": "uint16", "access": "RW", "description": "1: High precision, 2: Fast, other values invalid, default 1." }, { "name": "PV Storage System Anti‑Reverse‑Flow Control Mode", "group": "Settings", "area": "holding", "address": 44224, "type": "uint16", "access": "RW", "description": "1: Three‑phase power sum mode, 2: Three‑phase minimum power mode, other values invalid, default 1." }, { "name": "PV Storage System Total Grid‑side Active Power Control Compensation", "group": "Settings", "area": "holding", "address": 44225, "type": "int32", "access": "RW", "unit": "W", "description": "Range:-243750W ~ +243750W" }, { "name": "PV Storage System Maximum Feed‑in Total Active Power Setting", "group": "Settings", "area": "holding", "address": 44227, "type": "uint32", "access": "RW", "unit": "kW", "scale": 0.001, "description": "Range:0~4875kW,Default: Unit rated AC output power × 1.1" }, { "name": "PV Storage System Maximum Feed‑in Hard Limit Power Setting", "group": "Settings", "area": "holding", "address": 44229, "type": "uint32", "access": "RW", "unit": "kW", "scale": 0.001, "description": "to Australian Range:0~4875kW,Default: Unit rated AC output power × 1.1 Applicable anti‑reverse‑flow requirements. Range : 0~7386A , Default:" }, { "name": "PV Storage System G100‑2022 Standard Total Grid‑side Current Output Limit Setting", "group": "Settings", "area": "holding", "address": 44231, "type": "uint32", "access": "RW", "unit": "A", "scale": 0.01 }, { "name": "PV Storage System Meter 1 PT Voltage Ratio", "group": "Settings", "area": "holding", "address": 44233, "type": "uint16", "access": "RW", "description": "Range:1~30000" }, { "name": "PV Storage System Meter 2 PT Voltage Ratio", "group": "Settings", "area": "holding", "address": 44236, "type": "uint16", "access": "RW", "description": "Range:1~30000" }, { "name": "PV Storage System Meter 2 CT Ratio", "group": "Settings", "area": "holding", "address": 44237, "type": "uint16", "access": "RW", "description": "Range:1~30000" }, { "name": "PV Storage System Meter 2 CT Direction", "group": "Settings", "area": "holding", "address": 44238, "type": "uint16", "access": "RW", "description": "0: Forward (CT arrow points away from the inverter, i.e., toward the grid), 1: Reverse setting, default 0. Other values invalid. installatio" }, { "name": "PV Storage System Meter 2 Type and Installation Location Settings", "group": "Settings", "area": "holding", "address": 44239, "type": "uint16", "access": "RW", "description": "High byte: Meter location: 0x0100 – Grid‑tied inverter total output side 0x0200 – Grid load total output side Low byte: Meter type: 0x0001 –" }, { "name": "TCP Port Function", "group": "Settings", "area": "holding", "address": 44240, "type": "uint16", "access": "RW", "description": "BIT00: DHCP setting – 0: Dynamic, 1: Static, default 0; BIT01–15: Reserved Note: Only applicable to models that support TCP port and its fun" }, { "name": "TCP Port IP Address", "group": "Settings", "area": "holding", "address": 44241, "type": "uint32", "access": "RW", "description": "the IP address Data Format Description: Example: If is 192.168.0.2, then register 44241 = 0xC0A8 (where 0xC0 in hex = 192 in decimal, 0xA8 i" }, { "name": "TCP Port Subnet Mask", "group": "Settings", "area": "holding", "address": 44243, "type": "uint32", "access": "RW", "description": "Data format is the same as registers 44241~44242." }, { "name": "TCP Port Gateway", "group": "Settings", "area": "holding", "address": 44245, "type": "uint32", "access": "RW", "description": "Data format is the same as registers 44241~44242." }, { "name": "TCP Port DNS Server Address", "group": "Settings", "area": "holding", "address": 44247, "type": "uint32", "access": "RW", "description": "Data format is the same as registers 44241~44242." }, { "name": "TCP Port Secondary DNS Server Address", "group": "Settings", "area": "holding", "address": 44249, "type": "uint32", "access": "RW", "description": "Data format is the same as registers 44241~44242." }, { "name": "Modbus TCP Connection Port Number Setting", "group": "Settings", "area": "holding", "address": 44251, "type": "uint16", "access": "RW", "description": "Default 502" }, { "name": "Total Grid Power Consumption Over‑Limit Load Disconnect Enable", "group": "Settings", "area": "holding", "address": 44253, "type": "uint16", "access": "RW", "description": "0x01: Not Enabled, 0x02: Enabled, Default: Not Enabled. Other values invalid;" }, { "name": "Total Grid Power Consumption Over‑Limit Load Disconnect Control", "group": "Settings", "area": "holding", "address": 44254, "type": "uint16", "access": "RW", "description": "0x01:smartload, 0x02: smartload & backup, Other values invalid. Default: smartload Note: Effective only when function 44253 is enabled. 0x00" }, { "name": "Generator Scheduled Maintenance Function Enable Switch", "group": "Settings", "area": "holding", "address": 44255, "type": "uint16", "access": "RW" }, { "name": "Generator Scheduled Maintenance Function – Interval Time", "group": "Settings", "area": "holding", "address": 44256, "type": "uint16", "access": "RW", "unit": "day", "description": "Range: 1-60day, Default: 15days" }, { "name": "Generator Scheduled Maintenance Function – Runtime", "group": "Settings", "area": "holding", "address": 44257, "type": "uint16", "access": "RW", "unit": "min", "description": "Range: 5-30min, Default:10min" }, { "name": "Generator Minimum Operating Power", "group": "Settings", "area": "holding", "address": 44258, "type": "uint16", "access": "RW", "unit": "kW", "scale": 0.1, "description": "Range: 0–65000; Default: 24% of unit rated power." }, { "name": "TCP Port MAC Address Byte 1 & 2", "group": "Settings", "area": "holding", "address": 44268, "type": "uint16", "access": "RW", "description": "Low byte represents the 1st byte, high byte represents the 2nd byte. Example: If the MAC address is 0x00-0x80-0xE1-0x00-0x01-0x02, then the " }, { "name": "TCP Port MAC Address Byte 3 & 4", "group": "Settings", "area": "holding", "address": 44269, "type": "uint16", "access": "RW", "description": "Low byte represents the 3rd byte, high byte represents the 4th byte. Example: If the MAC address is 0x00-0x80-0xE1-0x00-0x01-0x02, then the " }, { "name": "TCP Port MAC Address Byte 5 & 6", "group": "Settings", "area": "holding", "address": 44270, "type": "uint16", "access": "RW", "description": "Low byte represents the 5th byte, high byte represents the 6th byte. Example: If the MAC address is 0x00-0x80-0xE1-0x00-0x01-0x02, then the " }, { "name": "DRM Mode 2 Logic Interface S1 Public Grid Power Feed-in Limit Value 1", "group": "Settings", "area": "holding", "address": 44275, "type": "uint16", "access": "RW", "unit": "%Range", "scale": 0.01 }, { "name": "DRM Mode 2 Logic Interface S2 Public Grid Power Feed-in Limit Value 2", "group": "Settings", "area": "holding", "address": 44276, "type": "uint16", "access": "RW", "unit": "%Range", "scale": 0.01 }, { "name": "DRM Mode 2 Logic Interface S3 Public Grid Power Feed-in Limit Value 3", "group": "Settings", "area": "holding", "address": 44277, "type": "uint16", "access": "RW", "unit": "%Range", "scale": 0.01 }, { "name": "DRM Mode 2 Logic Interface S4 Grid-to-Battery Charging Power Limit Value", "group": "Settings", "area": "holding", "address": 44278, "type": "uint32", "access": "RW", "unit": "W", "description": "Standalone range: 0~Pn Parallel range: 0~(Pn × number of parallel units) Default: 4.2 kW" }, { "name": "Remote Active Power Control Port Selection Command", "group": "Settings", "area": "holding", "address": 44280, "type": "uint16", "access": "RW", "description": "BIT00~BIT03: Power Control Port Selection 0 disabled, 1 reserved, 2 enable remote control on the AC Grid Port 3 reserved, 4 enable remote co" }, { "name": "Remote Reactive Power Control Port Selection Command", "group": "Settings", "area": "holding", "address": 44281, "type": "uint16", "access": "RW", "description": "BIT13~BIT15: reserved Note: If no valid command \"2\" is received within a specified time period, this register will revert to 0. The \"specifi" }, { "name": "Power Control Battery Power Value", "group": "Settings", "area": "holding", "address": 44282, "type": "int32", "access": "RW", "unit": "W", "description": "+: charge battery -: discharge battery" }, { "name": "Power Control AC Power Value", "group": "Settings", "area": "holding", "address": 44284, "type": "int32", "access": "RW", "unit": "W", "description": "+: export to grid -: import from grid" }, { "name": "Power Control Reactive Power Value", "group": "Settings", "area": "holding", "address": 44286, "type": "int32", "access": "RW", "unit": "var", "description": "reactive Inductive +: (lagging, absorbed by the load) -: (leading, supplied to the load) capacitive reactive power power Remarks Range: 0~30" } ] }