{ "$schema": "https://raw.githubusercontent.com/nobrega8/mbmap-library/main/schema/mbmap-2.schema.json", "mbmap": 2, "vendor": "Wellpro", "model": "WP8025ADAM", "models": [ "WP8025ADAM" ], "vendor_website": "shwellpro.com", "description": "8-channel relay output module (SPST) with RS485 Modbus RTU", "revision": 1, "revised": "2026-10-20", "source": "WP8025ADAM User's Manual V1.42", "sources": [ { "title": "WP8025ADAM User's Manual", "version": "1.42" } ], "notes": [ "Relays are coils 0 to 7 (RY1 to RY8): read with FC01, write with FC05 or FC15.", "Unit ID 0 is a broadcast: use it to set the address only with a single module on the RS485 line, or all modules take the same address.", "The address and the communication parameter are kept after power off; a new communication parameter takes effect after the module restarts.", "Written from the manufacturer's manual; not tested on a device." ], "protocol": "rtu", "unit_id": 1, "baudrate": 9600, "parity": "N", "databits": 8, "stopbits": 1, "address_base": 0, "x_status": "official", "enums": { "comm_param": {"1": "4800, N, 8, 1", "2": "9600, N, 8, 1", "3": "19200, N, 8, 1", "4": "38400, N, 8, 1", "5": "4800, E, 8, 1", "6": "9600, E, 8, 1", "7": "19200, E, 8, 1", "8": "38400, E, 8, 1"} }, "registers": [ {"name": "Relay 01", "group": "Relays", "area": "coil", "address": 0, "type": "bool", "access": "RW", "description": "Relay output 1 (RY1)"}, {"name": "Relay 02", "group": "Relays", "area": "coil", "address": 1, "type": "bool", "access": "RW", "description": "Relay output 2 (RY2)"}, {"name": "Relay 03", "group": "Relays", "area": "coil", "address": 2, "type": "bool", "access": "RW", "description": "Relay output 3 (RY3)"}, {"name": "Relay 04", "group": "Relays", "area": "coil", "address": 3, "type": "bool", "access": "RW", "description": "Relay output 4 (RY4)"}, {"name": "Relay 05", "group": "Relays", "area": "coil", "address": 4, "type": "bool", "access": "RW", "description": "Relay output 5 (RY5)"}, {"name": "Relay 06", "group": "Relays", "area": "coil", "address": 5, "type": "bool", "access": "RW", "description": "Relay output 6 (RY6)"}, {"name": "Relay 07", "group": "Relays", "area": "coil", "address": 6, "type": "bool", "access": "RW", "description": "Relay output 7 (RY7)"}, {"name": "Relay 08", "group": "Relays", "area": "coil", "address": 7, "type": "bool", "access": "RW", "description": "Relay output 8 (RY8)"}, {"name": "Device Address", "group": "Configuration", "area": "holding", "address": 100, "type": "uint16", "access": "RW", "write_min": 1, "write_max": 254, "description": "Modbus slave address (range 1-254)"}, {"name": "Communication Parameter", "group": "Configuration", "area": "holding", "address": 101, "type": "uint16", "access": "RW", "enum": "comm_param", "description": "Baudrate and parity settings (requires restart)"} ] }