{ "$schema": "http://json-schema.org/schema#", "$schemaVersion": "0.0.1", "$id": "https://smart-data-models.github.io/dataModels.CIMEnergyClasses/ExcELIN1/schema.json", "title": " Smart Data Models - ExcELIN1", "description": "Adapted from CIM data models. Static PI transformer fed excitation system: ELIN (VATECH) - simplified model. This model represents an all-static excitation system. A PI voltage controller establishes a desired field current set point for a proportional current controller. The integrator of the PI controller has a follow-up input to match its signal to the present field current. A power system stabilizer with power input is included in the model.", "type": "object", "allOf": [ { "$ref": "https://smart-data-models.github.io/data-models/common-schema.json#/definitions/GSMA-Commons" }, { "$ref": "https://smart-data-models.github.io/data-models/common-schema.json#/definitions/Location-Commons" }, { "properties": { "type": { "type": "string", "enum": [ "ExcELIN1" ], "description": "Property. NGSI type. It has to be ExcELIN1" }, "dpnf": { "description": "Property. Model:'https://schema.org/Number'. Controller follow up dead band (Dpnf). Typical Value = 0. Default: 0.0", "type": "number" }, "efmax": { "description": "Property. Model:'https://schema.org/Number'. Maximum open circuit excitation voltage (Efmax). Typical Value = 5. Default: 0.0", "type": "number" }, "efmin": { "description": "Property. Model:'https://schema.org/Number'. Minimum open circuit excitation voltage (Efmin). Typical Value = -5. Default: 0.0", "type": "number" }, "ks1": { "description": "Property. Model:'https://schema.org/Number'. Stabilizer Gain 1 (Ks1). Typical Value = 0. Default: 0.0", "type": "number" }, "ks2": { "description": "Property. Model:'https://schema.org/Number'. Stabilizer Gain 2 (Ks2). Typical Value = 0. Default: 0.0", "type": "number" }, "smax": { "description": "Property. Model:'https://schema.org/Number'. Stabilizer Limit Output (smax). Typical Value = 0.1. Default: 0.0", "type": "number" }, "tfi": { "description": "Property. Model:'https://schema.org/Number'. Current transducer time constant (Tfi). Typical Value = 0. Default: 0", "type": "number" }, "tnu": { "description": "Property. Model:'https://schema.org/Number'. Controller reset time constant (Tnu). Typical Value = 2. Default: 0", "type": "number" }, "ts1": { "description": "Property. Model:'https://schema.org/Number'. Stabilizer Phase Lag Time Constant (Ts1). Typical Value = 1. Default: 0", "type": "number" }, "ts2": { "description": "Property. Model:'https://schema.org/Number'. Stabilizer Filter Time Constant (Ts2). Typical Value = 1. Default: 0", "type": "number" }, "tsw": { "description": "Property. Model:'https://schema.org/Number'. Stabilizer parameters (Tsw). Typical Value = 3. Default: 0", "type": "number" }, "vpi": { "description": "Property. Model:'https://schema.org/Number'. Current controller gain (Vpi). Typical Value = 12.45. Default: 0.0", "type": "number" }, "vpnf": { "description": "Property. Model:'https://schema.org/Number'. Controller follow up gain (Vpnf). Typical Value = 2. Default: 0.0", "type": "number" }, "vpu": { "description": "Property. Model:'https://schema.org/Number'. Voltage controller proportional gain (Vpu). Typical Value = 34.5. Default: 0.0", "type": "number" }, "xe": { "description": "Property. Model:'https://schema.org/Number'. Excitation transformer effective reactance (Xe) (>=0). Xe represents the regulation of the transformer/rectifier unit. Typical Value = 0.06. Default: 0.0", "type": "number" } } } ] }