5.02021-11-21T21:40:27ZTemplatesSNMP APC InRowSNMP APC InRowTemplatesInformationTemperature- UPS InRow Firmware RevisionSNMP_AGENT1.3.6.1.4.1.318.1.1.13.3.4.1.1.5.0AirirscunitIdentFirmwareRevision1h0CHARA character string identifying the unit firmware version.SOFTWAREInformation
- UPS InRow Hardware RevisionSNMP_AGENT1.3.6.1.4.1.318.1.1.13.3.4.1.1.6.0AirirscunitIdentHardwareRevision1h0CHARA character string identifying the unit controller hardware revision.HARDWAREInformation
- UPS InRow LocationSNMP_AGENT1.3.6.1.4.1.318.1.1.13.3.4.1.1.2.0AirirscunitIdentLocation1h0CHARA character string identifying the unit location.LOCATIONInformation
- UPS InRow Manufacture DateSNMP_AGENT1.3.6.1.4.1.318.1.1.13.3.4.1.1.7.0AirirscunitIdentManufactureDate1h0CHARA character string identifying the unit manufacture date.Information
- UPS InRow Model NumberSNMP_AGENT1.3.6.1.4.1.318.1.1.13.3.4.1.1.3.0AirirscunitIdentModelNumber1h0CHARA character string identifying the unit model number.MODELInformation
- UPS InRow NameSNMP_AGENT1.3.6.1.4.1.318.1.1.13.3.4.1.1.1.0AirirscunitIdentName1h0CHARA character string identifying the unit name.NAMEInformation
- UPS InRow Serial NumberSNMP_AGENT1.3.6.1.4.1.318.1.1.13.3.4.1.1.4.0AirirscunitIdentSerialNumber1h0CHARA character string identifying the unit serial number.SERIALNO_AInformation
- UPS InRow Cond Inlet TempSNMP_AGENT1.3.6.1.4.1.318.1.1.13.3.4.1.2.31.0AirirscunitStatusCondInletTempMetric3mFLOATCThe unit condenser inlet air temperature in tenths of degrees Celsius.TemperatureMULTIPLIER0.1
- UPS InRow Cond Outlet TempSNMP_AGENT1.3.6.1.4.1.318.1.1.13.3.4.1.2.29.0AirirscunitStatusCondOutletTempMetric3mFLOATCThe unit condenser outlet air temperature in tenths of degrees Celsius.TemperatureMULTIPLIER0.1
- UPS InRow Rack Inlet TempSNMP_AGENT1.3.6.1.4.1.318.1.1.13.3.4.1.2.7.0AirirscunitStatusRackInletTemp3mFLOATCThe unit rack inlet temperature in tenths of degrees Celsius.TemperatureMULTIPLIER0.1
- UPS InRow Return Air TempSNMP_AGENT1.3.6.1.4.1.318.1.1.13.3.4.1.2.11.0AirirscunitStatusReturnAirTempMetric3mFLOATCThe unit return air temperature in tenths of degrees Celsius.TemperatureMULTIPLIER0.1
- UPS InRow Suction TempSNMP_AGENT1.3.6.1.4.1.318.1.1.13.3.4.1.2.13.0AirirscunitStatusSuctionTempMetric3mFLOATCThe unit suction temperature in tenths of degrees Celsius.TemperatureMULTIPLIER0.1
- UPS InRow Superheat TempSNMP_AGENT1.3.6.1.4.1.318.1.1.13.3.4.1.2.15.0AirirscunitStatusSuperheatTempMetric3mFLOATCThe unit superheat temperature in tenths of degrees Celsius.TemperatureMULTIPLIER0.1
- UPS InRow Supply Air TempSNMP_AGENT1.3.6.1.4.1.318.1.1.13.3.4.1.2.9.0AirirscunitStatusSupplyAirTempMetric3mFLOATCThe unit supply air temperature in tenths of degrees Celsius.TemperatureMULTIPLIER0.1
- UPS InRow Thresholds Rack Inlet High TempSNMP_AGENT1.3.6.1.4.1.318.1.1.13.3.4.1.5.2.0AirirscunitThresholdsRackInletHighTempMetric1hFLOATCUnit rack inlet air high temperature threshold in tenths of degrees Celsius.TemperatureMULTIPLIER0.1
- UPS InRow Thresholds Return Air High TempSNMP_AGENT1.3.6.1.4.1.318.1.1.13.3.4.1.5.6.0AirirscunitThresholdsReturnAirHighTempMetric1hFLOATCUnit return air high temperature threshold in tenths of degrees Celsius.TemperatureMULTIPLIER0.1
- UPS InRow Thresholds Supply Air High TempSNMP_AGENT1.3.6.1.4.1.318.1.1.13.3.4.1.5.4.0AirirscunitThresholdsSupplyAirHighTempMetric1hFLOATCUnit supply air high temperature threshold in tenths of degrees Celsius.TemperatureMULTIPLIER0.1
{SNMP APC InRow:AirirscunitStatusRackInletTemp.last()}>{SNMP APC InRow:AirirscunitThresholdsRackInletHighTempMetric.last()}Rack Inlet temperature is too high on {HOST.NAME}HIGH{SNMP APC InRow:AirirscunitStatusReturnAirTempMetric.last()}>{SNMP APC InRow:AirirscunitThresholdsReturnAirHighTempMetric.last()}Return Air temperature is too high on {HOST.NAME}HIGH{SNMP APC InRow:AirirscunitStatusSupplyAirTempMetric.last()}>{SNMP APC InRow:AirirscunitThresholdsSupplyAirHighTempMetric.last()}Supply Air temperature is too high on {HOST.NAME}HIGHAir temperature1A7C11- SNMP APC InRowAirirscunitStatusRackInletTemp
1F63100- SNMP APC InRowAirirscunitStatusReturnAirTempMetric
22774A4- SNMP APC InRowAirirscunitStatusSupplyAirTempMetric