5.02021-11-21T21:24:46ZTemplatesSNMP APC PDUSNMP APC PDU## Overview
UPDATE: Uploaded V2 to fix one of the power ratings that was the wrong OID. It was collecting watts incorrectly. All fixed now!
This APC Template contains outlet discovery and should work with any managed or switched APC PDU.
Contains sane triggers, load status, graphs, etc.
Triggers: APC Load State, Load Change, Power Alarm, etc.
Items: Basic information (model, name, firmware, etc), Power load/peak/etc, Master States (Enable for older units), All APC value mappings, and much more.
Graphs: Load and Current
Outlet Status (Dynamic Discovery)
Please enjoy and vote!
TemplatesOutlets- rPDU2DevicePropertiesMaxPhaseCurrentRating.1SNMP_AGENT.1.3.6.1.4.1.318.1.1.26.4.2.1.12.1rPDU2DevicePropertiesMaxPhaseCurrentRating.186400A
- rPDU2DeviceStatusLoadState.1SNMP_AGENT.1.3.6.1.4.1.318.1.1.26.4.3.1.4.1rPDU2DeviceStatusLoadState.130APC Status Load State{last()}<>2APC PDU Load StateHIGH
- rPDU2DeviceStatusPeakPower.1SNMP_AGENT.1.3.6.1.4.1.318.1.1.26.4.3.1.6.1rPDU2DeviceStatusPeakPower.1300KwMULTIPLIER0.01
- rPDU2DeviceStatusPeakPowerTimestamp.1SNMP_AGENT.1.3.6.1.4.1.318.1.1.26.4.3.1.7.1rPDU2DeviceStatusPeakPowerTimestamp.13000CHAR
- rPDU2DeviceStatusPower.1SNMP_AGENT.1.3.6.1.4.1.318.1.1.26.4.3.1.5.1rPDU2DeviceStatusPower.130KwMULTIPLIER0.01
- rPDU2DeviceStatusPowerSupplyAlarm.1SNMP_AGENT.1.3.6.1.4.1.318.1.1.26.4.3.1.12.1rPDU2DeviceStatusPowerSupplyAlarm.130APC Device Status Alarm{last()}<>1APC PDU Power AlarmHIGH
- rPDU2GroupTotalEnergy.0SNMP_AGENT.1.3.6.1.4.1.318.1.1.26.11.3.0rPDU2GroupTotalEnergy.030wMULTIPLIER0.1{change()}>400APC PDU Load ChangeINFO
- rPDU2IdentFirmwareRev.1SNMP_AGENT.1.3.6.1.4.1.318.1.1.26.2.1.6.1rPDU2IdentFirmwareRev.16000CHAR
- rPDU2IdentLocation.1SNMP_AGENT.1.3.6.1.4.1.318.1.1.26.2.1.4.1rPDU2IdentLocation.1864000CHAR
- rPDU2IdentModelNumber.1SNMP_AGENT.1.3.6.1.4.1.318.1.1.26.2.1.8.1rPDU2IdentModelNumber.1864000CHAR
- rPDU2IdentName.1SNMP_AGENT.1.3.6.1.4.1.318.1.1.26.2.1.3.1rPDU2IdentName.1864000CHAR
- rPDU2IdentSerialNumber.1SNMP_AGENT.1.3.6.1.4.1.318.1.1.26.2.1.9.1rPDU2IdentSerialNumber.1864000CHAR
- rPDU2PhaseStatusCurrent.1SNMP_AGENT.1.3.6.1.4.1.318.1.1.26.6.3.1.5.1rPDU2PhaseStatusCurrent.130AMULTIPLIER0.1
- rPDU2PhaseStatusPeakCurrent.1SNMP_AGENT.1.3.6.1.4.1.318.1.1.26.6.3.1.10.1rPDU2PhaseStatusPeakCurrent.130AMULTIPLIER0.1
- rPDU2PhaseStatusPeakCurrentTimestamp.1SNMP_AGENT.1.3.6.1.4.1.318.1.1.26.6.3.1.11.1rPDU2PhaseStatusPeakCurrentTimestamp.13000CHAR
- rPDU2PhaseStatusVoltage.1SNMP_AGENT.1.3.6.1.4.1.318.1.1.26.6.3.1.6.1rPDU2PhaseStatusVoltage.130V
- sPDUIdentFirmwareRev.0SNMP_AGENT.1.3.6.1.4.1.318.1.1.4.1.2.0sPDUIdentFirmwareRev.06000DISABLEDCHAR
- sPDUIdentModelNumber.0SNMP_AGENT.1.3.6.1.4.1.318.1.1.4.1.4.0sPDUIdentModelNumber.0864000DISABLEDCHAR
- sPDUMasterPending.0SNMP_AGENT.1.3.6.1.4.1.318.1.1.4.2.3.0sPDUMasterPending.0600DISABLEDCHAR
- sPDUMasterState.0SNMP_AGENT.1.3.6.1.4.1.318.1.1.4.2.2.0sPDUMasterState.0600DISABLEDCHAR
OutletsSNMP_AGENTdiscovery[{#SNMPVALUE},.1.3.6.1.4.1.318.1.1.26.9.2.1.1.1]rPDU2Outlet3600Outlet $1 NameSNMP_AGENT.1.3.6.1.4.1.318.1.1.26.9.2.1.1.3.{#SNMPINDEX}rPDU2OutletSwitchedConfigName[{#SNMPINDEX}]36000CHAROutletsOutlet $1 BankSNMP_AGENT.1.3.6.1.4.1.318.1.1.26.9.2.2.1.6.{#SNMPINDEX}rPDU2OutletSwitchedPropertiesBank[{#SNMPINDEX}]86400OutletsOutlet $1 StateSNMP_AGENT.1.3.6.1.4.1.318.1.1.26.9.2.3.1.5.{#SNMPINDEX}rPDU2OutletSwitchedStatusState[{#SNMPINDEX}]60OutletsAPC Outlet State{diff()}=1Outlet {#SNMPVALUE} State ChangeINFO{$SNMP_COMMUNITY}publicSNMP TrippliteSNMP Tripplite## Overview
UPDATE: Uploaded V2 to fix one of the power ratings that was the wrong OID. It was collecting watts incorrectly. All fixed now!
This APC Template contains outlet discovery and should work with any managed or switched APC PDU.
Contains sane triggers, load status, graphs, etc.
Triggers: APC Load State, Load Change, Power Alarm, etc.
Items: Basic information (model, name, firmware, etc), Power load/peak/etc, Master States (Enable for older units), All APC value mappings, and much more.
Graphs: Load and Current
Outlet Status (Dynamic Discovery)
Please enjoy and vote!
## Overview
UPDATE: Uploaded V2 to fix one of the power ratings that was the wrong OID. It was collecting watts incorrectly. All fixed now!
This APC Template contains outlet discovery and should work with any managed or switched APC PDU.
Contains sane triggers, load status, graphs, etc.
Triggers: APC Load State, Load Change, Power Alarm, etc.
Items: Basic information (model, name, firmware, etc), Power load/peak/etc, Master States (Enable for older units), All APC value mappings, and much more.
Graphs: Load and Current
Outlet Status (Dynamic Discovery)
Please enjoy and vote!
TemplatesUPS- upsAlarmsPresentSNMP_AGENT.1.3.6.1.2.1.33.1.6.1upsAlarmsPresent30UPS{last()}<>0UPS Alarm PresentWARNING
- upsBatteryStatusSNMP_AGENT.1.3.6.1.2.1.33.1.2.1upsBatteryStatus30UPSAPC Battery Status{last()}<>2Battery Status Not NormalHIGH
- upsBatteryTemperatureSNMP_AGENT.1.3.6.1.2.1.33.1.2.7upsBatteryTemperature60cUPS{last()}>25Battery Temperature Over NominalHIGH
- upsBatteryVoltageSNMP_AGENT.1.3.6.1.2.1.33.1.2.5upsBatteryVoltage60vUPSMULTIPLIER0.1
- upsBypassCurrent.1SNMP_AGENT.1.3.6.1.2.1.33.1.5.3.1.3.1upsBypassCurrent.130AUPSMULTIPLIER0.1
- upsBypassFrequencySNMP_AGENT.1.3.6.1.2.1.33.1.5.1upsBypassFrequency30HzUPS
- upsBypassPower.1SNMP_AGENT.1.3.6.1.2.1.33.1.5.3.1.4.1upsBypassPower.130UPS
- upsBypassVoltage.1SNMP_AGENT.1.3.6.1.2.1.33.1.5.3.1.2.1upsBypassVoltage.130vUPS
- upsEstimatedChargeRemainingSNMP_AGENT.1.3.6.1.2.1.33.1.2.4upsEstimatedChargeRemaining60UPS{last()}<20Battery Charge DepleatedHIGH{last()}<80Battery Charge Less Than 80%WARNING
- upsEstimatedMinutesRemainingSNMP_AGENT.1.3.6.1.2.1.33.1.2.3upsEstimatedMinutesRemaining30mUPS{last()}<10Battery Time Remaining Below 10 MinutesWARNING
- upsIdentAgentSoftwareVersionSNMP_AGENT.1.3.6.1.2.1.33.1.1.4upsIdentAgentSoftwareVersion6000CHARUPS
- upsIdentModelSNMP_AGENT.1.3.6.1.2.1.33.1.1.2upsIdentModel864000CHARUPS
- upsIdentUPSSoftwareVersionSNMP_AGENT.1.3.6.1.2.1.33.1.1.3upsIdentUPSSoftwareVersion6000CHARUPS
- upsInputFrequency.1SNMP_AGENT.1.3.6.1.2.1.33.1.3.3.1.2.1upsInputFrequency.130HzUPS
- upsInputLineBadsSNMP_AGENT.1.3.6.1.2.1.33.1.3.1upsInputLineBads30UPS{last()}<>0UPS Input Power Line BadDISASTER
- upsInputVoltage.1SNMP_AGENT.1.3.6.1.2.1.33.1.3.3.1.3.1upsInputVoltage.130vUPS{last(#3)}<195 or {last()}>245UPS Power Voltage Outside NominalHIGH
- upsOutputCurrent.1SNMP_AGENT.1.3.6.1.2.1.33.1.4.4.1.3.1upsOutputCurrent.130AUPSMULTIPLIER0.1
- upsOutputFrequencySNMP_AGENT.1.3.6.1.2.1.33.1.4.2upsOutputFrequency30HzUPS
- upsOutputPercentLoad.1SNMP_AGENT.1.3.6.1.2.1.33.1.4.4.1.5.1upsOutputPercentLoad.130UPS{last(#2)}>49UPS OverloadedHIGH
- upsOutputPower.1SNMP_AGENT.1.3.6.1.2.1.33.1.4.4.1.4.1upsOutputPower.130wUPS{change()}>300UPS Load ChangedINFO{last()}<1000UPS Low LoadWARNING
- upsOutputSourceSNMP_AGENT.1.3.6.1.2.1.33.1.4.1upsOutputSource30UPSTripplite Output Source{last()}<>3UPS Output Source Not NormalHIGH
- upsOutputVoltage.1SNMP_AGENT.1.3.6.1.2.1.33.1.4.4.1.2.1upsOutputVoltage.130vUPS
- upsSecondsOnBatterySNMP_AGENT.1.3.6.1.2.1.33.1.2.2upsSecondsOnBattery30sUPS{last()}>30UPS Running On BatteryHIGH
{SNMP Tripplite:upsBypassCurrent.1.last()}<>0 or {SNMP Tripplite:upsBypassPower.1.last()}<>0UPS BypassedWARNINGAPC Current Usage1A7C11- SNMP APC PDUrPDU2GroupTotalEnergy.0
APC Phase Power StatusGRADIENT_LINE00BB00- SNMP APC PDUrPDU2PhaseStatusCurrent.1
1DASHED_LINEDD0000- SNMP APC PDUrPDU2DevicePropertiesMaxPhaseCurrentRating.1
2DASHED_LINEEEEE00- SNMP APC PDUrPDU2PhaseStatusPeakCurrent.1
BatteryNONOSTACKEDDD0000- SNMP TrippliteupsBatteryTemperature
1008800- SNMP TrippliteupsEstimatedChargeRemaining
22774A4- SNMP TrippliteupsEstimatedMinutesRemaining
Current1A7C11- SNMP TrippliteupsBypassCurrent.1
1F63100- SNMP TrippliteupsOutputCurrent.1
VoltageF63100- SNMP TrippliteupsInputVoltage.1
100BB00- SNMP TrippliteupsOutputVoltage.1
APC Battery Status1unknown2batteryNormal3batteryLow4batteryDepletedAPC Device Status Alarm1normal2alarmAPC Outlet State1off2onAPC Status Load State1lowLoad2normal3nearOverload4overloadTripplite Output Source1other2none3normal4bypass5battery6booster7reducer