zabbix_export: version: '5.4' date: '2021-11-21T21:24:48Z' groups: - uuid: 7df96b18c230490a9a0a9e2307226338 name: Templates templates: - uuid: 3b53a9abf6a14b0a8d34227b5251992b template: 'SNMP APC PDU' name: 'SNMP APC PDU' description: | ## Overview UPDATE: Uploaded V2 to fix one of the power ratings that was the wrong OID. It was collecting watts incorrectly. All fixed now! This APC Template contains outlet discovery and should work with any managed or switched APC PDU. Contains sane triggers, load status, graphs, etc. Triggers: APC Load State, Load Change, Power Alarm, etc. Items: Basic information (model, name, firmware, etc), Power load/peak/etc, Master States (Enable for older units), All APC value mappings, and much more. Graphs: Load and Current Outlet Status (Dynamic Discovery) Please enjoy and vote! groups: - name: Templates items: - uuid: fd7da68d7bab440cb6375129e4247d53 name: rPDU2DevicePropertiesMaxPhaseCurrentRating.1 type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.318.1.1.26.4.2.1.12.1 key: rPDU2DevicePropertiesMaxPhaseCurrentRating.1 delay: '86400' units: A - uuid: 99de1f3aef94482cba93ea03fc6d2c38 name: rPDU2DeviceStatusLoadState.1 type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.318.1.1.26.4.3.1.4.1 key: rPDU2DeviceStatusLoadState.1 delay: '30' valuemap: name: 'APC Status Load State' triggers: - uuid: ff2f2311ac0b45a386e70b7f5c27e394 expression: 'last(/SNMP APC PDU/rPDU2DeviceStatusLoadState.1)<>2' name: 'APC PDU Load State' priority: HIGH - uuid: 5a0a234c67f14ca9a62538fbbc6cb6b5 name: rPDU2DeviceStatusPeakPower.1 type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.318.1.1.26.4.3.1.6.1 key: rPDU2DeviceStatusPeakPower.1 delay: '300' units: Kw preprocessing: - type: MULTIPLIER parameters: - '0.01' - uuid: c99ddc867d074cca84c1d378cbb46d33 name: rPDU2DeviceStatusPeakPowerTimestamp.1 type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.318.1.1.26.4.3.1.7.1 key: rPDU2DeviceStatusPeakPowerTimestamp.1 delay: '300' trends: '0' value_type: CHAR - uuid: 8a9c8266dc514e53944bf59b64d0303d name: rPDU2DeviceStatusPower.1 type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.318.1.1.26.4.3.1.5.1 key: rPDU2DeviceStatusPower.1 delay: '30' units: Kw preprocessing: - type: MULTIPLIER parameters: - '0.01' - uuid: 187f1a27ad244248a678bc87348b6357 name: rPDU2DeviceStatusPowerSupplyAlarm.1 type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.318.1.1.26.4.3.1.12.1 key: rPDU2DeviceStatusPowerSupplyAlarm.1 delay: '30' valuemap: name: 'APC Device Status Alarm' triggers: - uuid: f714a8b083b6412798b1f26143f4fcc4 expression: 'last(/SNMP APC PDU/rPDU2DeviceStatusPowerSupplyAlarm.1)<>1' name: 'APC PDU Power Alarm' priority: HIGH - uuid: dd14f285a54b4c66bda8ccc4eb2e2962 name: rPDU2GroupTotalEnergy.0 type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.318.1.1.26.11.3.0 key: rPDU2GroupTotalEnergy.0 delay: '30' units: w preprocessing: - type: MULTIPLIER parameters: - '0.1' triggers: - uuid: ff12b2f241ae480aac5944b296c8b8d9 expression: 'change(/SNMP APC PDU/rPDU2GroupTotalEnergy.0)>400' name: 'APC PDU Load Change' priority: INFO - uuid: c256f90f5fb84cecb99b91d51a253037 name: rPDU2IdentFirmwareRev.1 type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.318.1.1.26.2.1.6.1 key: rPDU2IdentFirmwareRev.1 delay: '600' trends: '0' value_type: CHAR - uuid: 64516935470946b1bba9013dd9ef110c name: rPDU2IdentLocation.1 type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.318.1.1.26.2.1.4.1 key: rPDU2IdentLocation.1 delay: '86400' trends: '0' value_type: CHAR - uuid: bb2138c8dc934590be85cb41cc9059cf name: rPDU2IdentModelNumber.1 type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.318.1.1.26.2.1.8.1 key: rPDU2IdentModelNumber.1 delay: '86400' trends: '0' value_type: CHAR - uuid: 6eacefdd9b6b4a2aa21f6de126b4c24e name: rPDU2IdentName.1 type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.318.1.1.26.2.1.3.1 key: rPDU2IdentName.1 delay: '86400' trends: '0' value_type: CHAR - uuid: d26d8f23e0ac4e9cb403d23290afbe1d name: rPDU2IdentSerialNumber.1 type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.318.1.1.26.2.1.9.1 key: rPDU2IdentSerialNumber.1 delay: '86400' trends: '0' value_type: CHAR - uuid: e7de9c88149348918c782a820c21b2cd name: rPDU2PhaseStatusCurrent.1 type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.318.1.1.26.6.3.1.5.1 key: rPDU2PhaseStatusCurrent.1 delay: '30' units: A preprocessing: - type: MULTIPLIER parameters: - '0.1' - uuid: f222e8e3eb7049bdb748eea205b0be4c name: rPDU2PhaseStatusPeakCurrent.1 type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.318.1.1.26.6.3.1.10.1 key: rPDU2PhaseStatusPeakCurrent.1 delay: '30' units: A preprocessing: - type: MULTIPLIER parameters: - '0.1' - uuid: 2cec2d178643472e8d95e0f41d98c288 name: rPDU2PhaseStatusPeakCurrentTimestamp.1 type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.318.1.1.26.6.3.1.11.1 key: rPDU2PhaseStatusPeakCurrentTimestamp.1 delay: '300' trends: '0' value_type: CHAR - uuid: 41c31fb5464b44bcb4c3421915b156a8 name: rPDU2PhaseStatusVoltage.1 type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.318.1.1.26.6.3.1.6.1 key: rPDU2PhaseStatusVoltage.1 delay: '30' units: V - uuid: 571c72b5e73f434a8be83f4abb1fac03 name: sPDUIdentFirmwareRev.0 type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.318.1.1.4.1.2.0 key: sPDUIdentFirmwareRev.0 delay: '600' trends: '0' status: DISABLED value_type: CHAR - uuid: ceb95648a60b4abd9271cf6bca965a13 name: sPDUIdentModelNumber.0 type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.318.1.1.4.1.4.0 key: sPDUIdentModelNumber.0 delay: '86400' trends: '0' status: DISABLED value_type: CHAR - uuid: f179a40cfb6646b6947886f96e27456e name: sPDUMasterPending.0 type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.318.1.1.4.2.3.0 key: sPDUMasterPending.0 delay: '60' trends: '0' status: DISABLED value_type: CHAR - uuid: 125729f759cc43658d45b3c41977eb6b name: sPDUMasterState.0 type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.318.1.1.4.2.2.0 key: sPDUMasterState.0 delay: '60' trends: '0' status: DISABLED value_type: CHAR discovery_rules: - uuid: 69c23ce227664395a870836c042d20ba name: Outlets type: SNMP_AGENT snmp_oid: 'discovery[{#SNMPVALUE},.1.3.6.1.4.1.318.1.1.26.9.2.1.1.1]' key: rPDU2Outlet delay: '3600' item_prototypes: - uuid: 92fdc0f5edb94e4fb93b2e619a3a38c5 name: 'Outlet $1 Name' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.318.1.1.26.9.2.1.1.3.{#SNMPINDEX}' key: 'rPDU2OutletSwitchedConfigName[{#SNMPINDEX}]' delay: '3600' trends: '0' value_type: CHAR tags: - tag: Application value: Outlets - uuid: 2bbb43aa28034defb80b751fc27aeabb name: 'Outlet $1 Bank' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.318.1.1.26.9.2.2.1.6.{#SNMPINDEX}' key: 'rPDU2OutletSwitchedPropertiesBank[{#SNMPINDEX}]' delay: '86400' tags: - tag: Application value: Outlets - uuid: 45bece696d3f45bf9a496bb47b9a6094 name: 'Outlet $1 State' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.318.1.1.26.9.2.3.1.5.{#SNMPINDEX}' key: 'rPDU2OutletSwitchedStatusState[{#SNMPINDEX}]' delay: '60' valuemap: name: 'APC Outlet State' tags: - tag: Application value: Outlets trigger_prototypes: - uuid: 255ed55d687a4c81926dd999a0a15b14 expression: '(last(/SNMP APC PDU/rPDU2OutletSwitchedStatusState[{#SNMPINDEX}],#1)<>last(/SNMP APC PDU/rPDU2OutletSwitchedStatusState[{#SNMPINDEX}],#2))=1' name: 'Outlet {#SNMPVALUE} State Change' priority: INFO macros: - macro: '{$SNMP_COMMUNITY}' value: public valuemaps: - uuid: d69cddd566264391944d4d334c099b9f name: 'APC Device Status Alarm' mappings: - value: '1' newvalue: normal - value: '2' newvalue: alarm - uuid: 838b39954da54bad8ce71b396124d5e9 name: 'APC Outlet State' mappings: - value: '1' newvalue: 'off' - value: '2' newvalue: 'on' - uuid: bf24b1c220f7418f9d2c7de26ccd8e76 name: 'APC Status Load State' mappings: - value: '1' newvalue: lowLoad - value: '2' newvalue: normal - value: '3' newvalue: nearOverload - value: '4' newvalue: overload - uuid: 94ad14b37b4e48548915ec8b465fab8b template: 'SNMP Tripplite' name: 'SNMP Tripplite' description: | ## Overview UPDATE: Uploaded V2 to fix one of the power ratings that was the wrong OID. It was collecting watts incorrectly. All fixed now! This APC Template contains outlet discovery and should work with any managed or switched APC PDU. Contains sane triggers, load status, graphs, etc. Triggers: APC Load State, Load Change, Power Alarm, etc. Items: Basic information (model, name, firmware, etc), Power load/peak/etc, Master States (Enable for older units), All APC value mappings, and much more. Graphs: Load and Current Outlet Status (Dynamic Discovery) Please enjoy and vote! ## Overview UPDATE: Uploaded V2 to fix one of the power ratings that was the wrong OID. It was collecting watts incorrectly. All fixed now! This APC Template contains outlet discovery and should work with any managed or switched APC PDU. Contains sane triggers, load status, graphs, etc. Triggers: APC Load State, Load Change, Power Alarm, etc. Items: Basic information (model, name, firmware, etc), Power load/peak/etc, Master States (Enable for older units), All APC value mappings, and much more. Graphs: Load and Current Outlet Status (Dynamic Discovery) Please enjoy and vote! groups: - name: Templates items: - uuid: f6cf7b0b98f44fe2bb055d9973fc3a95 name: upsAlarmsPresent type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.6.1 key: upsAlarmsPresent delay: '30' tags: - tag: Application value: UPS triggers: - uuid: 5f8414c8ec2240db890fba3d1c63ad48 expression: 'last(/SNMP Tripplite/upsAlarmsPresent)<>0' name: 'UPS Alarm Present' priority: WARNING - uuid: 769994f8f03f4ec4826082ed33b2c6f5 name: upsBatteryStatus type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.2.1 key: upsBatteryStatus delay: '30' valuemap: name: 'APC Battery Status' tags: - tag: Application value: UPS triggers: - uuid: 01d2b2f8c055485daa52df5d0bb605e7 expression: 'last(/SNMP Tripplite/upsBatteryStatus)<>2' name: 'Battery Status Not Normal' priority: HIGH - uuid: a26e3d1cfb2b4e58acbd8f94556e2ed8 name: upsBatteryTemperature type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.2.7 key: upsBatteryTemperature delay: '60' units: c tags: - tag: Application value: UPS triggers: - uuid: 392d62d95e9f492db1a5d693672d1af6 expression: 'last(/SNMP Tripplite/upsBatteryTemperature)>25' name: 'Battery Temperature Over Nominal' priority: HIGH - uuid: 3305acd4ab484cb0b575eb32fcbe5b33 name: upsBatteryVoltage type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.2.5 key: upsBatteryVoltage delay: '60' units: v preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Application value: UPS - uuid: 3783b495cc8742caa394b52064a2e4a5 name: upsBypassCurrent.1 type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.5.3.1.3.1 key: upsBypassCurrent.1 delay: '30' units: A preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Application value: UPS - uuid: dcb2fc4e17e64b4c8ad95f612a6886ce name: upsBypassFrequency type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.5.1 key: upsBypassFrequency delay: '30' units: Hz tags: - tag: Application value: UPS - uuid: 2be3e22a7b144a5189c33c89f6c90f35 name: upsBypassPower.1 type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.5.3.1.4.1 key: upsBypassPower.1 delay: '30' tags: - tag: Application value: UPS - uuid: d7d0d4f7abda45ea83104f5afd0c2a26 name: upsBypassVoltage.1 type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.5.3.1.2.1 key: upsBypassVoltage.1 delay: '30' units: v tags: - tag: Application value: UPS - uuid: a731d973a7064199a5e18742f09a89b8 name: upsEstimatedChargeRemaining type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.2.4 key: upsEstimatedChargeRemaining delay: '60' tags: - tag: Application value: UPS triggers: - uuid: 5d19ec209b0a44afa7b7e9211e80ccc3 expression: 'last(/SNMP Tripplite/upsEstimatedChargeRemaining)<20' name: 'Battery Charge Depleated' priority: HIGH - uuid: 2f86a675b9544bf99fba0479fab86938 expression: 'last(/SNMP Tripplite/upsEstimatedChargeRemaining)<80' name: 'Battery Charge Less Than 80%' priority: WARNING - uuid: 9893db8e1a9e44adbb7b9d72f2bb2191 name: upsEstimatedMinutesRemaining type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.2.3 key: upsEstimatedMinutesRemaining delay: '30' units: m tags: - tag: Application value: UPS triggers: - uuid: e7f02b30f6eb4ca2bbae904a025ff4cf expression: 'last(/SNMP Tripplite/upsEstimatedMinutesRemaining)<10' name: 'Battery Time Remaining Below 10 Minutes' priority: WARNING - uuid: 37049f28975c4d45bba328d2a72abec1 name: upsIdentAgentSoftwareVersion type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.1.4 key: upsIdentAgentSoftwareVersion delay: '600' trends: '0' value_type: CHAR tags: - tag: Application value: UPS - uuid: e44f5315f8c14d469802d38cc74984bf name: upsIdentModel type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.1.2 key: upsIdentModel delay: '86400' trends: '0' value_type: CHAR tags: - tag: Application value: UPS - uuid: 7a5d3cedc4b848db8ee1922837d82a2e name: upsIdentUPSSoftwareVersion type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.1.3 key: upsIdentUPSSoftwareVersion delay: '600' trends: '0' value_type: CHAR tags: - tag: Application value: UPS - uuid: 2eafbe62cab84a6e8703568efdd9e350 name: upsInputFrequency.1 type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.3.3.1.2.1 key: upsInputFrequency.1 delay: '30' units: Hz tags: - tag: Application value: UPS - uuid: 3c945cdca6804fd3b70d60d87a0266b2 name: upsInputLineBads type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.3.1 key: upsInputLineBads delay: '30' tags: - tag: Application value: UPS triggers: - uuid: eab132c435f84624aec589d3d7c68cf8 expression: 'last(/SNMP Tripplite/upsInputLineBads)<>0' name: 'UPS Input Power Line Bad' priority: DISASTER - uuid: 284c4ee24aab4f1bbcfdc83f7164c05d name: upsInputVoltage.1 type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.3.3.1.3.1 key: upsInputVoltage.1 delay: '30' units: v tags: - tag: Application value: UPS triggers: - uuid: 33ef86ee0d3c442ea685ad68fcae659c expression: 'last(/SNMP Tripplite/upsInputVoltage.1,#3)<195 or last(/SNMP Tripplite/upsInputVoltage.1)>245' name: 'UPS Power Voltage Outside Nominal' priority: HIGH - uuid: 071ea2aa68fd44ab82bde5fcbea20ee1 name: upsOutputCurrent.1 type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.4.4.1.3.1 key: upsOutputCurrent.1 delay: '30' units: A preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Application value: UPS - uuid: 9c01c8f1afea46058718a3ff945a9977 name: upsOutputFrequency type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.4.2 key: upsOutputFrequency delay: '30' units: Hz tags: - tag: Application value: UPS - uuid: 8abe151241c24f639f77907a8c5ee060 name: upsOutputPercentLoad.1 type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.4.4.1.5.1 key: upsOutputPercentLoad.1 delay: '30' tags: - tag: Application value: UPS triggers: - uuid: 8234ccc910d54d9090b5537e7d076960 expression: 'last(/SNMP Tripplite/upsOutputPercentLoad.1,#2)>49' name: 'UPS Overloaded' priority: HIGH - uuid: 8f99252eea3e4a768cad8451bff14c47 name: upsOutputPower.1 type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.4.4.1.4.1 key: upsOutputPower.1 delay: '30' units: w tags: - tag: Application value: UPS triggers: - uuid: 24b0e309a062489b9f7a19683aee51cb expression: 'change(/SNMP Tripplite/upsOutputPower.1)>300' name: 'UPS Load Changed' priority: INFO - uuid: 4ad8be2814ee4747941993782c07ea12 expression: 'last(/SNMP Tripplite/upsOutputPower.1)<1000' name: 'UPS Low Load' priority: WARNING - uuid: 7661a92ad52e4fbc8f58293db3fce2c4 name: upsOutputSource type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.4.1 key: upsOutputSource delay: '30' valuemap: name: 'Tripplite Output Source' tags: - tag: Application value: UPS triggers: - uuid: 03d9e2cf0aa445da8660a5d672195c0d expression: 'last(/SNMP Tripplite/upsOutputSource)<>3' name: 'UPS Output Source Not Normal' priority: HIGH - uuid: 911a4e4a73ce458c96c52f9ad61efdbd name: upsOutputVoltage.1 type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.4.4.1.2.1 key: upsOutputVoltage.1 delay: '30' units: v tags: - tag: Application value: UPS - uuid: 91e8522f562641d0ac3f789c12a753bb name: upsSecondsOnBattery type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.2.2 key: upsSecondsOnBattery delay: '30' units: s tags: - tag: Application value: UPS triggers: - uuid: 5406d9061b1e4ef3879badb0b4735f83 expression: 'last(/SNMP Tripplite/upsSecondsOnBattery)>30' name: 'UPS Running On Battery' priority: HIGH valuemaps: - uuid: 1abc9bb22ae44e3497d95c48328c9aa0 name: 'APC Battery Status' mappings: - value: '1' newvalue: unknown - value: '2' newvalue: batteryNormal - value: '3' newvalue: batteryLow - value: '4' newvalue: batteryDepleted - uuid: b581c194dd0f40daad74b4ea274418e1 name: 'Tripplite Output Source' mappings: - value: '1' newvalue: other - value: '2' newvalue: none - value: '3' newvalue: normal - value: '4' newvalue: bypass - value: '5' newvalue: battery - value: '6' newvalue: booster - value: '7' newvalue: reducer triggers: - uuid: 867cb0681d68474494c5db7e7848d660 expression: 'last(/SNMP Tripplite/upsBypassCurrent.1)<>0 or last(/SNMP Tripplite/upsBypassPower.1)<>0' name: 'UPS Bypassed' priority: WARNING graphs: - uuid: 100200efcc014aa695bea733bb074018 name: 'APC Current Usage' graph_items: - color: 1A7C11 item: host: 'SNMP APC PDU' key: rPDU2GroupTotalEnergy.0 - uuid: 260f292281274da9a7fefb80b6f33bbf name: 'APC Phase Power Status' graph_items: - drawtype: GRADIENT_LINE color: 00BB00 item: host: 'SNMP APC PDU' key: rPDU2PhaseStatusCurrent.1 - sortorder: '1' drawtype: DASHED_LINE color: DD0000 item: host: 'SNMP APC PDU' key: rPDU2DevicePropertiesMaxPhaseCurrentRating.1 - sortorder: '2' drawtype: DASHED_LINE color: EEEE00 item: host: 'SNMP APC PDU' key: rPDU2PhaseStatusPeakCurrent.1 - uuid: 451d460fc9fa46faa1081353726c70a5 name: Battery show_work_period: 'NO' show_triggers: 'NO' type: STACKED graph_items: - color: DD0000 item: host: 'SNMP Tripplite' key: upsBatteryTemperature - sortorder: '1' color: '008800' item: host: 'SNMP Tripplite' key: upsEstimatedChargeRemaining - sortorder: '2' color: 2774A4 item: host: 'SNMP Tripplite' key: upsEstimatedMinutesRemaining - uuid: 5756e8ba4f0c48ed8232d79ede33ea48 name: Current graph_items: - color: 1A7C11 item: host: 'SNMP Tripplite' key: upsBypassCurrent.1 - sortorder: '1' color: F63100 item: host: 'SNMP Tripplite' key: upsOutputCurrent.1 - uuid: 6662891afc184db099810fb5f4401922 name: Voltage graph_items: - color: F63100 item: host: 'SNMP Tripplite' key: upsInputVoltage.1 - sortorder: '1' color: 00BB00 item: host: 'SNMP Tripplite' key: upsOutputVoltage.1