5.02021-11-21T21:33:00ZTemplatesapc_nmc_2_ap9619APC NMC 2 AP9619## Overview
This template was originaly created for the AP9619 card, but in version 2 now support more UPS's.
Tested on:
APC Symmetra PX40 3Phase UPS
APC Smart-UPS VT 20kVA 3Phase UPS
Smart-UPS RT 7500 RM XL
and more...
It gathers input and output values from all three phases. I tried to make it as universal as i could so it can be used with single phase ups's as well. I have disable some of the items on the template for the reason that my ups didn't support them, feel free to try them if they are supported by your UPS.
Changelog V2:
Added more items for single phase ups's and triggers.
thanks,
petroska
## Author
petroska
TemplatesUPS BatteryUPS InformationUPS Input [1Phase]UPS Input [3Phase]UPS Output [1Phase]UPS Output [3Phase]UPS State- Probe HumiditySNMP_AGENT1.3.6.1.4.1.318.1.1.10.2.3.2.1.6.1iemStatusProbeCurrentHumid30sDISABLED%The current humidity reading from the probe in percent
relative humidity.UPS Information
- Probe TemperatureSNMP_AGENT1.3.6.1.4.1.318.1.1.10.2.3.2.1.4.1iemStatusProbeCurrentTemp30sCThe current temperature reading from the probe displayed
in the units shown in the 'iemStatusProbeTempUnits' OID
(Celsius or Fahrenheit).UPS Information
- Probe NameSNMP_AGENT1.3.6.1.4.1.318.1.1.10.2.3.2.1.2.1iemStatusProbeName36000CHARA descriptive name for the probe set by the user.UPS Information
- Probe StatusSNMP_AGENT1.3.6.1.4.1.318.1.1.10.2.3.2.1.3.1iemStatusProbeStatus3600UPS InformationAPC Probe Status
- LocationSNMP_AGENT1.3.6.1.2.1.1.6.0sysLocation36000CHARUPS Information
- Battery actual VoltsSNMP_AGENT1.3.6.1.4.1.318.1.1.1.2.2.8.0upsAdvBatteryActualVoltage30sVThe actual battery bus voltage in Volts.UPS Battery
- Battery CapacitySNMP_AGENT1.3.6.1.4.1.318.1.1.1.2.2.1.0upsAdvBatteryCapacity30s%The remaining battery capacity expressed in
percent of full capacity.UPS Battery
- Battery AmpsSNMP_AGENT1.3.6.1.4.1.318.1.1.1.2.2.9.0upsAdvBatteryCurrent30sAThe battery current in Amps.UPS Battery
- Battery nominal VoltsSNMP_AGENT1.3.6.1.4.1.318.1.1.1.2.2.7.0upsAdvBatteryNominalVoltage30sVThe nominal battery voltage in Volts.UPS Battery
- Battery replace statusSNMP_AGENT1.3.6.1.4.1.318.1.1.1.2.2.4.0upsAdvBatteryReplaceIndicator3600Indicates whether the UPS batteries need replacing.UPS BatteryAPC Battery Replacement Status{last()}=4Battery failedDISASTER{last()}=6Battery needs replacementHIGH{last()}=5Battery overheatDISASTER{last()}=2No batteryHIGH
- Battery RuntimeSNMP_AGENT1.3.6.1.4.1.318.1.1.1.2.2.3.0upsAdvBatteryRunTimeRemaining30ssThe UPS battery run time remaining before battery
exhaustion.UPS BatteryMULTIPLIER0.01{last()}<60RECOVERY_EXPRESSION{last()}>60UPS Runtime below 1 minuteHIGH
- Battery TemperatureSNMP_AGENT1.3.6.1.4.1.318.1.1.1.2.2.2.0upsAdvBatteryTemperature30sCThe current internal UPS temperature expressed in
Celsius.UPS Battery{last()}>40RECOVERY_EXPRESSION{last()}<40Battery temp above 40CHIGH
- Date of manufactureSNMP_AGENT1.3.6.1.4.1.318.1.1.1.1.2.2.0upsAdvIdentDateOfManufacture36000CHARThe date when the UPS was manufactured in mm/dd/yy (or yyyy) format.UPS Information
- Firmware RevisionSNMP_AGENT1.3.6.1.4.1.318.1.1.1.1.2.1.0upsAdvIdentFirmwareRevision36000CHARThe firmware revision of the UPS system's microprocessor.UPS Information
- Input FrequencySNMP_AGENT1.3.6.1.4.1.318.1.1.1.3.2.4.0upsAdvInputFrequency30sHzThe current input frequency to the UPS system in Hz.UPS Input [1Phase]
- Latest cause for switching to battery powerSNMP_AGENT1.3.6.1.4.1.318.1.1.1.3.2.5.0upsAdvInputLineFailCause60sThe reason for the occurrence of the last transfer to UPS
battery power. The variable is set to:
- noTransfer(1) -- if there is no transfer yet.
- highLineVoltage(2) -- if the transfer to battery is caused
by an over voltage greater than the high transfer voltage.
- brownout(3) -- if the duration of the outage is greater than
five seconds and the line voltage is between 40% of the
rated output voltage and the low transfer voltage.
- blackout(4) -- if the duration of the outage is greater than five
seconds and the line voltage is between 40% of the rated
output voltage and ground.
- smallMomentarySag(5) -- if the duration of the outage is less
than five seconds and the line voltage is between 40% of the
rated output voltage and the low transfer voltage.
- deepMomentarySag(6) -- if the duration of the outage is less
than five seconds and the line voltage is between 40% of the
rated output voltage and ground. The variable is set to
- smallMomentarySpike(7) -- if the line failure is caused by a
rate of change of input voltage less than ten volts per cycle.
- largeMomentarySpike(8) -- if the line failure is caused by
a rate of change of input voltage greater than ten volts per cycle.
- selfTest(9) -- if the UPS was commanded to do a self test.
- rateOfVoltageChange(10) -- if the failure is due to the rate of change of
the line voltage.UPS Input [1Phase]APC Input Line Fail Cause
- Input VoltageSNMP_AGENT.1.3.6.1.4.1.318.1.1.1.3.2.1.0upsAdvInputLineVoltage30sVThe current utility line voltage in VAC.UPS Input [1Phase]{last()}<100RECOVERY_EXPRESSION{last()}>220Input voltage failedDISASTER
- Output Load CurrentSNMP_AGENT.1.3.6.1.4.1.318.1.1.1.4.2.4.0upsAdvOutputCurrent30sAUPS Output [1Phase]
- Output LoadSNMP_AGENT1.3.6.1.4.1.318.1.1.1.4.2.3.0upsAdvOutputLoad30s%The current UPS load expressed in percent
of rated capacity.UPS Output [1Phase]
- Output VoltageSNMP_AGENT.1.3.6.1.4.1.318.1.1.1.4.2.1.0upsAdvOutputVoltage30sVUPS Output [1Phase]
- Battery total DC currentSNMP_AGENT1.3.6.1.4.1.318.1.1.1.2.2.10.0upsAdvTotalDCCurrent30sAThe total DC current in Amps.UPS Battery
- Battery StatusSNMP_AGENT1.3.6.1.4.1.318.1.1.1.2.1.1.0upsBasicBatteryStatus30sThe status of the UPS batteries. A batteryLow(3) value
indicates the UPS will be unable to sustain the current
load, and its services will be lost if power is not restored.
The amount of run time in reserve at the time of low battery
can be configured by the upsAdvConfigLowBatteryRunTime.
A batteryInFaultCondition(4)value indicates that a battery
installed has an internal error condition.UPS BatteryAPC Battery Status{last()}=3RECOVERY_EXPRESSION{last()}=2UPS batteries lowDISASTER{last()}=4RECOVERY_EXPRESSION{last()}=2UPS battery fault conditionHIGH
- Time on batterySNMP_AGENT1.3.6.1.4.1.318.1.1.1.2.1.2.0upsBasicBatteryTimeOnBattery30s0TEXTThe elapsed time since the UPS has switched to battery
power.UPS Battery{last()}>60RECOVERY_EXPRESSION{last()}<=0UPS on battery for 1 minute, H/Z should be on by nowDISASTER{last()}>120RECOVERY_EXPRESSION{last()}<=0UPS on battery for 2 minutes, H/Z should be on by nowDISASTER{last()}>0RECOVERY_EXPRESSION{last()}<=0UPS on battery powerDISASTER
- ModelSNMP_AGENT1.3.6.1.4.1.318.1.1.1.1.1.1.0upsBasicIdentModel36000CHARThe UPS model name (e.g. 'APC Smart-UPS 600').UPS Information
- NameSNMP_AGENT1.3.6.1.4.1.318.1.1.1.1.1.2.0upsBasicIdentName36000CHARAn 8 byte ID string identifying the UPS. This object
can be set by the administrator.UPS Information
- Internal temperatureSNMP_AGENT1.3.6.1.4.1.318.1.1.1.4.1.4upsBasicSystemInternalTemperature30sCThe actual internal temperature of the UPS system in Celsius.UPS Information
- Battery actual Volts [HighPrec]SNMP_AGENT1.3.6.1.4.1.318.1.1.1.2.3.4.0upsHighPrecBatteryActualVoltage30sFLOATVThe actual battery bus voltage in tenths of Volts.UPS BatteryMULTIPLIER0.1
- Battery Capacity [HighPrec]SNMP_AGENT1.3.6.1.4.1.318.1.1.1.2.3.1.0upsHighPrecBatteryCapacity30sFLOAT%The remaining battery capacity expressed in
tenths of percent of full capacity.UPS BatteryMULTIPLIER0.1{last()}<10RECOVERY_EXPRESSION{last()}>10Battery capacity below 10%HIGH{last()}<20RECOVERY_EXPRESSION{last()}>20Battery capacity below 20%HIGH{last()}<30RECOVERY_EXPRESSION{last()}>30Battery capacity below 30%HIGH{last()}<40RECOVERY_EXPRESSION{last()}>40Battery capacity below 40%HIGH{last()}<50RECOVERY_EXPRESSION{last()}>50Battery capacity below 50%HIGH
- Battery Amps [HighPrec]SNMP_AGENT1.3.6.1.4.1.318.1.1.1.2.3.5.0upsHighPrecBatteryCurrent30sAThe battery current in tenths of Amps.UPS Battery
- Battery nominal Volts [HighPrec]SNMP_AGENT1.3.6.1.4.1.318.1.1.1.2.3.3.0upsHighPrecBatteryNominalVoltage30sFLOATVUPS BatteryMULTIPLIER0.1
- Battery Temperature [HighPrec]SNMP_AGENT1.3.6.1.4.1.318.1.1.1.2.3.2.0upsHighPrecBatteryTemperature30sDISABLEDFLOATCThe current internal UPS temperature expressed in
tenths of degrees Celsius.UPS BatteryMULTIPLIER0.1
- Input Frequency [HighPrec]SNMP_AGENT1.3.6.1.4.1.318.1.1.1.3.3.4.0upsHighPrecInputFrequency30sFLOATHzUPS Input [1Phase]MULTIPLIER0.1
- Input Voltage [HighPrec]SNMP_AGENT1.3.6.1.4.1.318.1.1.1.3.3.1.0upsHighPrecInputLineVoltage30sFLOATVThe current utility line voltage in tenths of VAC.UPS Input [1Phase]MULTIPLIER0.1
- Battery total DC current [HighPrec]SNMP_AGENT1.3.6.1.4.1.318.1.1.1.2.3.6.0upsHighPrecTotalDCCurrent30sAThe total DC current in tenths of Amps.
not always supportedUPS Battery
- Input Current L1SNMP_AGENT1.3.6.1.4.1.318.1.1.1.9.2.3.1.6.1.1.1upsPhaseInputCurrentL130sAThe input current in 0.1 amperes, or -1 if it's
unsupported by this UPS.UPS Input [3Phase]MULTIPLIER0.1
- Input Current L2SNMP_AGENT1.3.6.1.4.1.318.1.1.1.9.2.3.1.6.1.1.2upsPhaseInputCurrentL230sAThe input current in 0.1 amperes, or -1 if it's
unsupported by this UPS.UPS Input [3Phase]MULTIPLIER0.1
- Input Current L3SNMP_AGENT1.3.6.1.4.1.318.1.1.1.9.2.3.1.6.1.1.3upsPhaseInputCurrentL330sAThe input current in 0.1 amperes, or -1 if it's
unsupported by this UPS.UPS Input [3Phase]MULTIPLIER0.1
- Input Voltage L1SNMP_AGENT1.3.6.1.4.1.318.1.1.1.9.2.3.1.3.1.1.1upsPhaseInputVoltageL130sVThe input voltage in VAC, or -1 if it's unsupported
by this UPS.UPS Input [3Phase]{last()}<100RECOVERY_EXPRESSION{last()}>220Input voltage on phase 1 failedDISASTER
- Input Voltage L2SNMP_AGENT1.3.6.1.4.1.318.1.1.1.9.2.3.1.3.1.1.2upsPhaseInputVoltageL230sVThe input voltage in VAC, or -1 if it's unsupported
by this UPS.UPS Input [3Phase]{last()}<100RECOVERY_EXPRESSION{last()}>220Input voltage on phase 2 failedDISASTER
- Input Voltage L3SNMP_AGENT1.3.6.1.4.1.318.1.1.1.9.2.3.1.3.1.1.3upsPhaseInputVoltageL330sVThe input voltage in VAC, or -1 if it's unsupported
by this UPS.UPS Input [3Phase]{last()}<100RECOVERY_EXPRESSION{last()}>220Input voltage on phase 3 failedDISASTER
- Output Current L1SNMP_AGENT1.3.6.1.4.1.318.1.1.1.9.3.3.1.4.1.1.1upsPhaseOutputCurrentL130sAThe output current in 0.1 amperes drawn
by the load on the UPS, or -1 if it's unsupported
by this UPS.UPS Output [3Phase]MULTIPLIER0.1
- Output Current L2SNMP_AGENT1.3.6.1.4.1.318.1.1.1.9.3.3.1.4.1.1.2upsPhaseOutputCurrentL230sAThe output current in 0.1 amperes drawn
by the load on the UPS, or -1 if it's unsupported
by this UPS.UPS Output [3Phase]MULTIPLIER0.1
- Output Current L3SNMP_AGENT1.3.6.1.4.1.318.1.1.1.9.3.3.1.4.1.1.3upsPhaseOutputCurrentL330sAThe output current in 0.1 amperes drawn
by the load on the UPS, or -1 if it's unsupported
by this UPS.UPS Output [3Phase]MULTIPLIER0.1
- Output Load L1SNMP_AGENT1.3.6.1.4.1.318.1.1.1.9.3.3.1.7.1.1.1upsPhaseOutputLoadL130sVAThe output load in VA, or -1 if it's unsupported
by this UPS.UPS Output [3Phase]
- Output Load L2SNMP_AGENT1.3.6.1.4.1.318.1.1.1.9.3.3.1.7.1.1.2upsPhaseOutputLoadL230sVAThe output load in VA, or -1 if it's unsupported
by this UPS.UPS Output [3Phase]
- Output Load L3SNMP_AGENT1.3.6.1.4.1.318.1.1.1.9.3.3.1.7.1.1.3upsPhaseOutputLoadL330sVAThe output load in VA, or -1 if it's unsupported
by this UPS.UPS Output [3Phase]
- Output Phase capacity L1SNMP_AGENT1.3.6.1.4.1.318.1.1.1.9.3.3.1.16.1.1.1upsPhaseOutputPercentPowerL130s%The percentage of the UPS power capacity in Watts at
redundancy @ (n + x) presently being used on this
output phase, or -1 if it's unsupported by this UPS.UPS Output [3Phase]{last()}>50RECOVERY_EXPRESSION{last()}<50Phase 1 output capcity above 50%HIGH
- Output Phase capacity L2SNMP_AGENT1.3.6.1.4.1.318.1.1.1.9.3.3.1.16.1.1.2upsPhaseOutputPercentPowerL230s%The percentage of the UPS power capacity in Watts at
redundancy @ (n + x) presently being used on this
output phase, or -1 if it's unsupported by this UPS.UPS Output [3Phase]{last()}>50RECOVERY_EXPRESSION{last()}<50Phase 2 output capcity above 50%HIGH
- Output Phase capacity L3SNMP_AGENT1.3.6.1.4.1.318.1.1.1.9.3.3.1.16.1.1.3upsPhaseOutputPercentPowerL330s%The percentage of the UPS power capacity in Watts at
redundancy @ (n + x) presently being used on this
output phase, or -1 if it's unsupported by this UPS.UPS Output [3Phase]{last()}>50RECOVERY_EXPRESSION{last()}<50Phase 3 output capcity above 50%HIGH
- Output Power L1SNMP_AGENT1.3.6.1.4.1.318.1.1.1.9.3.3.1.13.1.1.1upsPhaseOutputPowerL130sDISABLEDWThe output power in Watts, or -1 if it's
unsupported by this UPS.UPS Output [3Phase]
- Output Power L2SNMP_AGENT1.3.6.1.4.1.318.1.1.1.9.3.3.1.13.1.1.2upsPhaseOutputPowerL230sDISABLEDWUPS Output [3Phase]
- Output Power L3SNMP_AGENT1.3.6.1.4.1.318.1.1.1.9.3.3.1.13.1.1.3upsPhaseOutputPowerL330sDISABLEDWThe output power in Watts, or -1 if it's
unsupported by this UPS.UPS Output [3Phase]
- Output Voltage L1SNMP_AGENT.1.3.6.1.4.1.318.1.1.1.9.3.3.1.3.1.1.1upsPhaseOutputVoltageL130sVACThe output voltage in VAC, or -1 if it's unsupported
by this UPS.UPS Output [3Phase]
- Output Voltage L2SNMP_AGENT1.3.6.1.4.1.318.1.1.1.9.3.3.1.3.1.1.2upsPhaseOutputVoltageL230sVACThe output voltage in VAC, or -1 if it's unsupported
by this UPS.UPS Output [3Phase]
- Output Voltage L3SNMP_AGENT1.3.6.1.4.1.318.1.1.1.9.3.3.1.3.1.1.3upsPhaseOutputVoltageL330sVACThe output voltage in VAC, or -1 if it's unsupported
by this UPS.UPS Output [3Phase]
Input Volts and Frequency12001A7C11- apc_nmc_2_ap9619upsAdvInputFrequency
1F63100- apc_nmc_2_ap9619upsAdvInputLineVoltage
22774A4- apc_nmc_2_ap9619upsPhaseInputVoltageL1
3A54F10- apc_nmc_2_ap9619upsPhaseInputVoltageL2
4FC6EA3- apc_nmc_2_ap9619upsPhaseInputVoltageL3
Output Load and Runtime12001A7C11- apc_nmc_2_ap9619upsAdvBatteryRunTimeRemaining
1F63100- apc_nmc_2_ap9619upsAdvOutputLoad
APC Battery Replacement Status1unknown2notInstalled3ok4failed5highTemperature6replaceImmediately7lowCapacityAPC Battery Status1unknown2batteryNormal3batteryLow4batteryInFaultConditionAPC Input Line Fail Cause1noTransfe2highLineVoltage3brownout4blackout5smallMomentarySag6deepMomentarySag7smallMomentarySpike8largeMomentarySpike9selfTest10rateOfVoltageChangeAPC Probe Status1Disconnected2Connected