5.02021-11-25T12:34:15ZPDU:PZ:HQTemplatesAPC_Monitor_RackPDUAPC_Monitor_RackPDUPDU:PZ:HQTemplatesload stats- High_1_Load_PointSNMP_AGENT.1.3.6.1.4.1.318.1.1.12.2.2.1.1.4.1High1Load.rPDU36007dFLOATAmpsHigh Load Threshold by Phaseload stats
- High_2_Load_PointSNMP_AGENT.1.3.6.1.4.1.318.1.1.12.2.2.1.1.4.2High2Load.rPDU36007dFLOATAmpsHigh Load Threshold by Phaseload stats
- High_3_Load_PointSNMP_AGENT.1.3.6.1.4.1.318.1.1.12.2.2.1.1.4.3High3Load.rPDU36007dFLOATAmpsHigh Load Threshold by Phaseload stats
- Phase 1SNMP_AGENT.1.3.6.1.4.1.318.1.1.12.2.3.1.1.2.1Load1Amps.rPDU60;50/1-7,00:00-24:00720dFLOATAmpsPDU load in Amps by Phaseload statsMULTIPLIER.1
- Phase 2SNMP_AGENT.1.3.6.1.4.1.318.1.1.12.2.3.1.1.2.2Load2Amps.rPDU60720dFLOATAmpsPDU load in Amps by Phaseload statsMULTIPLIER.1
- Phase 3SNMP_AGENT.1.3.6.1.4.1.318.1.1.12.2.3.1.1.2.3Load3Amps.rPDU60720dFLOATAmpsPDU load in Amps by Phaseload statsMULTIPLIER.1
- Low_1_Load_PointSNMP_AGENT.1.3.6.1.4.1.318.1.1.12.2.2.1.1.2.1Low1Load.rPDU36007dFLOATAmpsLow Load Threshold by Phaseload stats
- Low_2_Load_PointSNMP_AGENT.1.3.6.1.4.1.318.1.1.12.2.2.1.1.2.2Low2Load.rPDU36007dFLOATAmpsLow Load Threshold by Phaseload stats
- Low_3_Load_PointSNMP_AGENT.1.3.6.1.4.1.318.1.1.12.2.2.1.1.2.3Low3Load.rPDU36007dFLOATAmpsLow Load Threshold by Phaseload stats
- Near_High_1_Load_PointSNMP_AGENT.1.3.6.1.4.1.318.1.1.12.2.2.1.1.3.1NHigh1Load.rPDU36007dFLOATAmpsNear High Load Threshold by Phaseload stats
- Near_High_2_Load_PointSNMP_AGENT.1.3.6.1.4.1.318.1.1.12.2.2.1.1.3.2NHigh2Load.rPDU36007dFLOATAmpsNear High Load Threshold by Phaseload stats
- Near_High_3_Load_PointSNMP_AGENT.1.3.6.1.4.1.318.1.1.12.2.2.1.1.3.3NHigh3Load.rPDU36007dFLOATAmpsNear High Load Threshold by Phaseload stats
- State 1 Phase LoadSNMP_AGENT.1.3.6.1.4.1.318.1.1.12.2.3.1.1.3.1State1Load.rPDU180030d720dFLOATAmpsPhaseLoadNormal(1) = operating between high and low threshold OID values.
phaseLoadLow(2) = dropped below low OID value.
phaseLoadNearOverload(3) = is greater than or equal to the near overload value
phaseLoadOverload(4) = load is greater than or equal to the high load OID value.load stats
- State 2 Phase LoadSNMP_AGENT.1.3.6.1.4.1.318.1.1.12.2.3.1.1.3.2State2Load.rPDU180030d720dFLOATAmpsPhaseLoadNormal(1) = operating between high and low threshold OID values.
phaseLoadLow(2) = dropped below low OID value.
phaseLoadNearOverload(3) = is greater than or equal to the near overload value
phaseLoadOverload(4) = load is greater than or equal to the high load OID value.load stats
- State 3 Phase LoadSNMP_AGENT.1.3.6.1.4.1.318.1.1.12.2.3.1.1.3.3State3Load.rPDU180030d720dFLOATAmpsPhaseLoadNormal(1) = operating between high and low threshold OID values.
phaseLoadLow(2) = dropped below low OID value.
phaseLoadNearOverload(3) = is greater than or equal to the near overload value
phaseLoadOverload(4) = load is greater than or equal to the high load OID value.load stats
{$SNMP_COMMUNITY}CMPublicAC Unit Status12{APC_Monitor_RackPDU:Load1Amps.rPDU.avg(#2)} > {APC_Monitor_RackPDU:NHigh1Load.rPDU.last()}E: Phase1 Overload ({ITEM.LASTVALUE1}A)HIGHF: Phase1 Overload ({ITEM.LASTVALUE1}A){APC_Monitor_RackPDU:Load1Amps.rPDU.avg(#2)} > {APC_Monitor_RackPDU:High1Load.rPDU.last()}{APC_Monitor_RackPDU:Load2Amps.rPDU.avg(#2)} > {APC_Monitor_RackPDU:NHigh2Load.rPDU.last()}E: Phase2 Overload ({ITEM.LASTVALUE1}A)HIGHF: Phase2 Overload ({ITEM.LASTVALUE1}A){APC_Monitor_RackPDU:Load2Amps.rPDU.avg(#2)} > {APC_Monitor_RackPDU:High2Load.rPDU.last()}{APC_Monitor_RackPDU:Load3Amps.rPDU.avg(#2)} > {APC_Monitor_RackPDU:NHigh3Load.rPDU.last()}E: Phase3 Overload ({ITEM.LASTVALUE1}A)HIGHF: Phase3 Overload ({ITEM.LASTVALUE1}A){APC_Monitor_RackPDU:Load3Amps.rPDU.avg(#2)} > {APC_Monitor_RackPDU:High3Load.rPDU.last()}{APC_Monitor_RackPDU:Load1Amps.rPDU.avg(#2)} > {APC_Monitor_RackPDU:High1Load.rPDU.last()}F: Phase1 Overload ({ITEM.LASTVALUE1}A)DISASTER{APC_Monitor_RackPDU:Load2Amps.rPDU.avg(#2)} > {APC_Monitor_RackPDU:High2Load.rPDU.last()}F: Phase2 Overload ({ITEM.LASTVALUE1}A)DISASTER{APC_Monitor_RackPDU:Load3Amps.rPDU.avg(#2)} > {APC_Monitor_RackPDU:High3Load.rPDU.last()}F: Phase3 Overload ({ITEM.LASTVALUE1}A)DISASTER{APC_Monitor_RackPDU:Load1Amps.rPDU.avg(#2)} < {APC_Monitor_RackPDU:Low1Load.rPDU.last()}I: No load: phase1 ({ITEM.LASTVALUE1}A)INFO{APC_Monitor_RackPDU:Load2Amps.rPDU.avg(#2)} < {APC_Monitor_RackPDU:Low2Load.rPDU.last()}I: No load: phase2 ({ITEM.LASTVALUE1}A)INFO{APC_Monitor_RackPDU:Load3Amps.rPDU.avg(#2)} < {APC_Monitor_RackPDU:Low3Load.rPDU.last()}I: No load: phase3 ({ITEM.LASTVALUE1}A)INFOLOADSTACKEDNOFIXED3333FF- APC_Monitor_RackPDULoad3Amps.rPDU
133FFFF- APC_Monitor_RackPDULoad2Amps.rPDU
233FF33- APC_Monitor_RackPDULoad1Amps.rPDU