zabbix_export: version: '6.0' date: '2021-11-21T21:50:50Z' groups: - uuid: 57b7ae836ca64446ba2c296389c009b7 name: Templates/Modules templates: - uuid: 1a008329b0a44cf992ca88476d5e28b3 template: 'Module Cyberpower RMCARD305' name: 'Module Cyberpower RMCARD305' description: | ## Description SNMPv2 Template for Cyberpower's remote management card ver.305 (205) used in OR and PR-series UPSes. Tested on firmware version 1.3.0. Created by Taurus (https://github.com/RusTaurus) MIBs used: CPS-MIB (v2.9) https://www.cyberpowersystems.com/products/software/mib-files/ ## Overview This is Zabbix SNMPv2 Template for Cyberpower's remote management card ver.305(205) used in OR- and PR-series UPSes. Tested on Zabbix 4.0 and 4.4, PR3000ELCDRT2U, OR1500ELCDRM1U with RMCARD305 (firmware version 1.3.0). [Here](https://github.com/RusTaurus/cyberpower-rmcard305) you can find latest firmware and MIB versions of RMCARD305. --- Enhancements in v2 version of this template: * New application with UPS configuration settings * Add discovery of battery Age Recommendation parameter * Display RMCARD serial number --- MIBs used: CPS-MIB (v2.9) ## Author Sergey Romanov groups: - name: Templates/Modules items: - uuid: 7edca1541b02451fb1a188ec9943cb63 name: Capacity type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.3808.1.1.1.2.2.1.0 key: battery.Capacity delay: 30s history: 30d units: '%' description: 'CPS-MIB::upsAdvanceBatteryCapacity - the battery capacity expressed in percentage' tags: - tag: Application value: Battery triggers: - uuid: acf5a51a8e5d496e8e964b67700f63b2 expression: 'last(/Module Cyberpower RMCARD305/battery.Capacity)<=20' name: 'Battery capacity is low' priority: HIGH dependencies: - name: 'UPS on battery' expression: 'last(/Module Cyberpower RMCARD305/output.Status)=3' - uuid: 115b1a959ab246feabf710bb2c5524ad name: 'Remaining Runtime' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.3808.1.1.1.2.2.4.0 key: battery.RemainingRuntime delay: 30s history: 30d value_type: FLOAT units: min description: 'CPS-MIB::upsAdvanceBatteryRunTimeRemaining - the UPS battery remaining run time' preprocessing: - type: MULTIPLIER parameters: - '0.00016666666666' tags: - tag: Application value: Battery - uuid: 7fd22acdd4ee446ab9931ecb47d19312 name: 'Replace Indicator' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.3808.1.1.1.2.2.5.0 key: battery.ReplaceIndicator delay: 1h history: 30d trends: '0' description: 'CPS-MIB::upsAdvanceBatteryReplaceIndicator - this value indicates if UPS batteries need to be replaced' valuemap: name: 'CyberPower UPS Battery Replacement Indicator' tags: - tag: Application value: Battery - uuid: c2d75583d7a0478d9bb668cb5364f0f2 name: Status type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.3808.1.1.1.2.1.1.0 key: battery.Status delay: 15s history: 30d description: 'CPS-MIB::upsBaseBatteryStatus - the UPS battery status. A batteryLow(3) value means the battery will be exhausted soon under the current load. The amount of low battery run time can be configured by the upsAdvanceConfigLowBatteryRunTime.' valuemap: name: 'CyberPower UPS Battery Status' tags: - tag: Application value: Battery - uuid: 3c4b64807b504aa88a9e998ebebc74a1 name: 'Time on Battery' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.3808.1.1.1.2.1.2.0 key: battery.TimeOnBattery delay: 30s history: 30d value_type: FLOAT units: min description: 'CPS-MIB::upsBaseBatteryTimeOnBattery - the UPS wasted battery time since the UPS has transfered to backup mode' preprocessing: - type: MULTIPLIER parameters: - '0.00016666666666' tags: - tag: Application value: Battery - uuid: b2bfaad4a26c4961b82256b8b8379cc5 name: 'Voltage Rating' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.3808.1.1.1.2.2.8.0 key: battery.VoltageRating delay: 1h history: 30d trends: '0' units: V description: 'CPS-MIB::upsAdvanceBatteryVoltageRating - the DC voltage rating of the battery set' tags: - tag: Application value: Battery - uuid: 23238be5a0894a0cb4536e934ccd9aa1 name: 'System - Audible Alarm' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.3808.1.1.1.5.2.4.0 key: config.audibleAlarm delay: 30m history: 30d trends: '0' description: 'CPS-MIB::upsAdvanceConfigAlarm - this value is set to handle audible alarms when power failure.' valuemap: name: 'CyberPower UPS Config - Audible Alarm' tags: - tag: Application value: 'UPS Configuration Settings' - uuid: 58c9c7462c214b89b712881d340c849f name: 'Battery Low Threshold' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.3808.1.1.1.5.2.18.0 key: config.batteryLow delay: 30m history: 30d trends: '0' units: '%' description: 'CPS-MIB::upsAdvanceConfigLowBatteryThreshold - when the UPS supplies battery power and the remaining capacity is lower than this threshold, the UPS will sound an alarm. The value expressed in percentage.' tags: - tag: Application value: 'UPS Configuration Settings' - uuid: 26d04bd642034be39db01bea2951529b name: 'System - Over Discharge Protection' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.3808.1.1.1.5.2.16.0 key: config.dischargeProtection delay: 30m history: 30d trends: '0' description: 'CPS-MIB::upsAdvanceConfigDeepDischargeProtection - when the UPS is on Battery Mode with 0% load and the status remains for the time configured, the RMCARD will enforce the UPS to Sleep Mode and the output will be turned off. The possible values are 0, 20, 40, and 60 minutes. If a value other than a possible value is set, it will not be accepted.' valuemap: name: 'CyberPower UPS Config - Over Discharge Protection' tags: - tag: Application value: 'UPS Configuration Settings' - uuid: b2e8fe19482040749daac0d74221a238 name: 'Output Voltage' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.3808.1.1.1.5.2.1.0 key: config.outputVoltage delay: 30m history: 30d trends: '0' units: V description: 'CPS-MIB::upsAdvanceConfigOutputVoltage - the standard UPS output voltage in Volts. The possible values are 100, 110, 120, 127, 208, 220, 230, and 240. If a value other than a possible value is set, it will not be accepted.' tags: - tag: Application value: 'UPS Configuration Settings' - uuid: dec1a12d10414bad945e0e9f024461b3 name: 'System - Enter Sleep Mode After All Clients Shutdown' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.3808.1.1.1.5.2.17.0 key: config.sleepMode delay: 30m history: 30d trends: '0' description: 'CPS-MIB::upsAdvanceConfigSleepAfterAllClientShut - if this option is enabled, UPS will enter sleep mode after utility power failed and remaining MSDT+2 minutes.More information about MSDT please reference to help page of UPS - > PowerPanel List.' valuemap: name: 'CyberPower UPS Config - Sleep After All Clients Shutdown' tags: - tag: Application value: 'UPS Configuration Settings' - uuid: cb8495cac5cc4c11b8f450398c2bc899 name: 'Last Fail Cause' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.3808.1.1.1.3.2.5.0 key: input.FailCause delay: 1h history: 1w trends: '0' description: 'CPS-MIB::upsAdvanceInputLineFailCause - The reason of UPS power failure. This value is set to: - noTransfer(1), if UPS is in utility mode. - highLineVoltage(2), if UPS switch to battery mode by reason of input voltage over the high transfer vloltage. - brownout(3), if UPS switch to battery mode by reason of input voltage under the low transfer vloltage. - selfTest(4), if the UPS was commanded to do a self test.' valuemap: name: 'CyberPower UPS Input Fail Cause' tags: - tag: Application value: Input - uuid: 821d79a1a13443d4ae2eb634039c1c37 name: Frequency type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.3808.1.1.1.3.2.4.0 key: input.Frequency delay: 30s history: 30d units: Hz description: 'CPS-MIB::upsAdvanceInputFrequency - the input line frequency in Hz' preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Application value: Input - uuid: ffa4d187151d44f89eb7b084ad8c584f name: Status type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.3808.1.1.1.3.2.6.0 key: input.Status delay: 15s history: 30d description: 'CPS-MIB::upsAdvanceInputStatus - display the present status of the utility power supplied to the UPS' valuemap: name: 'CyberPower UPS Input Status' tags: - tag: Application value: Input - uuid: 33d18a00d6814313846a63303b65b745 name: Voltage type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.3808.1.1.1.3.2.1.0 key: input.Voltage delay: 30s history: 30d units: V description: 'CPS-MIB::upsAdvanceInputLineVoltage - the input line voltage in Volts' preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Application value: Input - uuid: c263959d58b9412d87bdc876e809e446 name: Frequency type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.3808.1.1.1.4.2.2.0 key: output.Frequency delay: 30s history: 30d units: Hz description: 'CPS-MIB::upsAdvanceOutputFrequency - the UPS output frequency in Hz' preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Application value: Output - uuid: 006b53409a4a4bf782a8e31c782a28e5 name: Load type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.3808.1.1.1.4.2.3.0 key: output.Load delay: 30s history: 30d units: '%' description: 'CPS-MIB::upsAdvanceOutputLoad - the UPS output load expressed in percentage' tags: - tag: Application value: Output - uuid: 8eb561bc3dbc43e7897c2c1f4bbbc4ff name: 'Load (watts)' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.3808.1.1.1.4.2.5.0 key: output.LoadW delay: 30s history: 30d units: '!W' description: 'CPS-MIB::upsAdvanceOutputPower - the total output active power of the UPS system in W' tags: - tag: Application value: Output - uuid: 94db2720d1a648a598ffbc2af5ad2ebd name: Status type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.3808.1.1.1.4.1.1.0 key: output.Status delay: 15s history: 30d description: 'CPS-MIB::upsBaseOutputStatus - the UPS output status' valuemap: name: 'CyberPower UPS Output Status' tags: - tag: Application value: Output triggers: - uuid: 509fff1f26b44054b791c5498a1331fa expression: 'last(/Module Cyberpower RMCARD305/output.Status)=3' name: 'UPS on battery' priority: AVERAGE - uuid: 55f02b0497b046dc86e1dcbc1d4dd323 name: Voltage type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.3808.1.1.1.4.2.1.0 key: output.Voltage delay: 30s history: 30d units: V description: 'CPS-MIB::upsAdvanceOutputVoltage - the UPS output voltage in Volts' preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Application value: Output - uuid: cc429acc046b464d937dcb2f943eae36 name: 'Firmware Revision' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.3808.1.1.1.1.2.4.0 key: rmcard.FirmwareRevision delay: 1h history: 1w trends: '0' value_type: TEXT description: 'CPS-MIB::upsAdvanceIdentAgentFirmwareRevision - the SNMP agent firmware revision' tags: - tag: Application value: RMCARD - uuid: ec3012e69ef04e8a8f6a894d70b52c4c name: 'Serial Number' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.3808.1.1.1.1.2.9.0 key: rmcard.SerialNumber delay: 1h history: 1w trends: '0' value_type: TEXT description: 'CPS-MIB::upsAdvanceIdentAgentSerialNumber - a string identifying the serial number of the Agent' tags: - tag: Application value: RMCARD - uuid: 6964365539de4aa69ceccfd4474ab659 name: 'Firmware Version' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.3808.1.1.1.1.2.1.0 key: ups.info.FirmwareVersion delay: 1h history: 1w trends: '0' value_type: TEXT description: 'CPS-MIB::upsAdvanceIdentFirmwareRevision - the UPS firmware revision' tags: - tag: Application value: Information - uuid: 3798cd9fe6014ddcbb8d5689409de1b2 name: 'Load Power' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.3808.1.1.1.1.2.7.0 key: ups.info.LoadPower delay: 1h history: 1w trends: '0' units: '!W' description: 'CPS-MIB::upsAdvanceIdentLoadPower - the power rating (Watts) of the UPS' tags: - tag: Application value: Information - uuid: 4deaedde4c9847b591daa0c04eec6406 name: Model type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.3808.1.1.1.1.1.1.0 key: ups.info.Model delay: 1h history: 1w trends: '0' value_type: TEXT description: 'CPS-MIB::upsBaseIdentModel - the UPS model name' inventory_link: MODEL tags: - tag: Application value: Information - uuid: 6463535e771f44e6ab6d59df2acff0eb name: Name type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.3808.1.1.1.1.1.2.0 key: ups.info.Name delay: 1h history: 1w trends: '0' value_type: TEXT description: 'CPS-MIB::upsBaseIdentName - the UPS identified name could be set by the administrator' inventory_link: NAME tags: - tag: Application value: Information - uuid: f05f05d2d7304c02b0f8cb8a1adc6ace name: 'Power Rating' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.3808.1.1.1.1.2.6.0 key: ups.info.PowerRating delay: 1h history: 1w trends: '0' units: '!VA' description: 'CPS-MIB::upsAdvanceIdentPowerRating - the Volt-Amp rating of the UPS' tags: - tag: Application value: Information discovery_rules: - uuid: 3c9a327d1a754bfb9ef36034b957f9b5 name: 'Battery Age Recommendation Discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#SNMPVALUE},1.3.6.1.4.1.3808.1.1.1.2.1.4]' key: BatteryAge.discovery delay: 30s filter: conditions: - macro: '{#SNMPVALUE}' value: '(^0{1})' operator: NOT_MATCHES_REGEX formulaid: A description: 'Discovery because CPS-MIB::upsBaseBatteryAgeRecommand returns 0 (zero) on OR-series UPSes.' item_prototypes: - uuid: 3cc4ce1930374a9b85befdff50646073 name: 'Age Recommendation' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.3808.1.1.1.2.1.4.{#SNMPINDEX}' key: 'battery.ageRecommend.[{#SNMPINDEX}]' delay: 1h history: 1w trends: '0' units: months description: 'CPS-MIB::upsBaseBatteryAgeRecommand - Recommended battery life in months' tags: - tag: Application value: Battery - uuid: 29c8899d0f6c47ccbf0b3847f3554299 name: 'Last Replace Date' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.3808.1.1.1.2.1.3.{#SNMPINDEX}' key: 'battery.lastReplaceDate.[{#SNMPINDEX}]' delay: 1h history: 1w trends: '0' value_type: CHAR description: 'CPS-MIB::upsBaseBatteryLastReplaceDate - the UPS batteries last replaced date in mm/dd/yyyy format. This value is originally set when manufactured. If batteries replaced, administrator should reset this value.' valuemap: name: 'CyberPower UPS Last Replace Date' tags: - tag: Application value: Battery - uuid: 44b68ec2bc254a1daa098990403c5063 name: 'Configuration Discovery #1' type: SNMP_AGENT snmp_oid: 'discovery[{#SNMPVALUE},1.3.6.1.4.1.3808.1.1.1.5.2.15]' key: config.discovery.1 delay: 30s filter: conditions: - macro: '{#SNMPVALUE}' value: '(^NULL{1})' operator: NOT_MATCHES_REGEX formulaid: A description: 'Discovery because CPS-MIB::upsAdvanceConfigColdStart returns NULL on OR-series UPSes.' item_prototypes: - uuid: 10f69643fb294ba7a3ac6fb8cab66abd name: 'System - Cold Start' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.3808.1.1.1.5.2.15.{#SNMPINDEX}' key: 'config.coldStart.[{#SNMPINDEX}]' delay: 30m history: 30d trends: '0' description: 'CPS-MIB::upsAdvanceConfigColdStart - set the ability of the UPS can start in the absence of input power. When this option is enabled the UPS can be turned on without having input power.' valuemap: name: 'CyberPower UPS Config - Cold Start' tags: - tag: Application value: 'UPS Configuration Settings' - uuid: dfaf688d52994618b4f18302cc8a75df name: 'Configuration Discovery #2' type: SNMP_AGENT snmp_oid: 'discovery[{#SNMPVALUE},1.3.6.1.4.1.3808.1.1.1.5.2.14]' key: config.discovery.2 delay: 30s filter: conditions: - macro: '{#SNMPVALUE}' value: '(^NULL{1})' operator: NOT_MATCHES_REGEX formulaid: A description: 'Discovery because CPS-MIB::upsAdvanceConfigRechargedCapacity returns NULL on OR-series UPSes.' item_prototypes: - uuid: 03298d91ba944bcc80d4fc677d57fd2d name: 'Power Restore - Recharged Capacity' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.3808.1.1.1.5.2.14.{#SNMPINDEX}' key: 'config.rechargedCapacity.[{#SNMPINDEX}]' delay: 30m history: 30d trends: '0' description: 'CPS-MIB::upsAdvanceConfigRechargedCapacity - when the utility power restores, the UPS will start to recharge until the specified battery capacity in percentage is met before restoring output power. The possible values are 0, 15, 30, 45, 60, 75, and 90. If a value other than a possible value is set, it will not be accepted.' valuemap: name: 'CyberPower UPS Config - Recharged Capacity' tags: - tag: Application value: 'UPS Configuration Settings' - uuid: ae66cdad8cb249bb862cf100f4e55abf name: 'Configuration Discovery #3' type: SNMP_AGENT snmp_oid: 'discovery[{#SNMPVALUE},1.3.6.1.4.1.3808.1.1.1.5.2.9]' key: config.discovery.3 delay: 30s filter: conditions: - macro: '{#SNMPVALUE}' value: '(^NULL{1})' operator: NOT_MATCHES_REGEX formulaid: A description: 'Discovery because CPS-MIB::upsAdvanceConfigReturnDelay returns NULL on OR-series UPSes.' item_prototypes: - uuid: 0abe8eae801d469998206fea1d4d034f name: 'Power Restore - Returned Delay' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.3808.1.1.1.5.2.9.{#SNMPINDEX}' key: 'config.returnedDelay.[{#SNMPINDEX}]' delay: 30m history: 30d trends: '0' value_type: FLOAT units: min description: 'CPS-MIB::upsAdvanceConfigReturnDelay - the delay time the UPS will turn on after power recovery. The value is also used in a ''reboot'' or ''wake up'' sequence. The possible values are 0 to 600 seconds. If a value other than a supported value is set, the value will not be accepted.' preprocessing: - type: MULTIPLIER parameters: - '0.00016666666666' tags: - tag: Application value: 'UPS Configuration Settings' - uuid: 3390f1ec6e9d434f9f09b5953f2c4388 name: 'Configuration Discovery #4' type: SNMP_AGENT snmp_oid: 'discovery[{#SNMPVALUE},1.3.6.1.4.1.3808.1.1.1.5.2.10]' key: config.discovery.4 delay: 30s filter: conditions: - macro: '{#SNMPVALUE}' value: '(^NULL{1})' operator: NOT_MATCHES_REGEX formulaid: A description: 'Discovery because CPS-MIB::upsAdvanceConfigShutoffDelay returns NULL on OR-series UPSes.' item_prototypes: - uuid: 066a53b2b2744301914b8ffd6c5e71f2 name: 'Timers - ShutOff Delay' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.3808.1.1.1.5.2.10.{#SNMPINDEX}' key: 'config.shutoffDelay.[{#SNMPINDEX}]' delay: 30m history: 30d trends: '0' value_type: FLOAT units: min description: 'CPS-MIB::upsAdvanceConfigShutoffDelay - the delay time the UPS will remain on after receiving a turn off command. The possible values are between 60 to 5940 seconds. If a value other than a supported value is set, the value will not be accepted.' preprocessing: - type: MULTIPLIER parameters: - '0.00016666666666' tags: - tag: Application value: 'UPS Configuration Settings' - uuid: 07c712d1cab64846808820a161e41a8f name: 'Configuration Discovery #5' type: SNMP_AGENT snmp_oid: 'discovery[{#SNMPVALUE},1.3.6.1.4.1.3808.1.1.1.5.2.11]' key: config.discovery.5 delay: 30s filter: conditions: - macro: '{#SNMPVALUE}' value: '(^NULL{1})' operator: NOT_MATCHES_REGEX formulaid: A description: 'Discovery because CPS-MIB::upsAdvanceConfigSleepDelay returns NULL on OR-series UPSes.' item_prototypes: - uuid: 86b8908236bc4b6daa334550b41f9a3a name: 'Timers - Sleep Delay' type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.3808.1.1.1.5.2.11.{#SNMPINDEX}' key: 'config.sleepDelay.[{#SNMPINDEX}]' delay: 30m history: 30d trends: '0' value_type: FLOAT units: min description: 'CPS-MIB::upsAdvanceConfigSleepDelay - the delay time the UPS will enter sleep mode after receiving a sleep command. The possible values are between 60 to 5940 seconds. If a value other than a supported value is set, the value will not be accepted.' preprocessing: - type: MULTIPLIER parameters: - '0.00016666666666' tags: - tag: Application value: 'UPS Configuration Settings' - uuid: 008fdc06ccf14edd954bcf8303def68b name: 'Output Current Discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#SNMPVALUE},1.3.6.1.4.1.3808.1.1.1.4.2.4]' key: Output.current.discovery delay: 30s filter: conditions: - macro: '{#SNMPVALUE}' value: '(^0{1})' operator: NOT_MATCHES_REGEX formulaid: A description: 'Discovery because CPS-MIB::upsAdvanceOutputCurrent returns 0 (zero) on OR-series UPSes.' item_prototypes: - uuid: e5e6d301715e43d6893f54c77ddd6e57 name: Current type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.3808.1.1.1.4.2.4.{#SNMPINDEX}' key: 'output.current.[{#SNMPINDEX}]' value_type: FLOAT units: A description: 'CPS-MIB::upsAdvanceOutputCurrent - the UPS output current in Amps' preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Application value: Output - uuid: 65a1b6cf1b7a4d31bd0a180ce07aaa4a name: 'Temperature Discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#SNMPVALUE},1.3.6.1.4.1.3808.1.1.1.2.2.3]' key: Temperature.discovery delay: 30s filter: conditions: - macro: '{#SNMPVALUE}' value: '(^0{1})' operator: NOT_MATCHES_REGEX formulaid: A description: 'Discovery because CPS-MIB::upsAdvanceBatteryTemperature returns 0 (zero) on OR-series UPSes.' item_prototypes: - uuid: e727a62cf6ec4a469c6e3f75347c8e59 name: Temperature type: SNMP_AGENT snmp_oid: '1.3.6.1.4.1.3808.1.1.1.2.2.3.{#SNMPINDEX}' key: 'ups.info.Temperature.[{#SNMPINDEX}]' value_type: FLOAT units: °C description: 'CPS-MIB::upsAdvanceBatteryTemperature - the UPS battery temperature expressed in Celsius' tags: - tag: Application value: Information macros: - macro: '{$SNMP_COMMUNITY}' value: public valuemaps: - uuid: c2a42587685b4f7a8ebb089ecbafc30f name: 'CyberPower UPS Battery Replacement Indicator' mappings: - value: '1' newvalue: noBatteryNeedsReplacing - value: '2' newvalue: batteryNeedsReplacing - uuid: 2a3d20be428647d794781c1bf98e1e2a name: 'CyberPower UPS Battery Status' mappings: - value: '1' newvalue: unknown - value: '2' newvalue: batteryNormal - value: '3' newvalue: batteryLow - value: '4' newvalue: batteryNotPresent - uuid: 40439379ac9e4480ae9276f2487fbd67 name: 'CyberPower UPS Config - Audible Alarm' mappings: - value: '1' newvalue: timed - value: '2' newvalue: enable - value: '3' newvalue: disable - value: '4' newvalue: mute - uuid: 0181a92352674bbbb38d8e3442f72a1b name: 'CyberPower UPS Config - Cold Start' mappings: - value: '1' newvalue: disable - value: '2' newvalue: enable - uuid: 211c7337cac94afc8156eb8c85b32ae3 name: 'CyberPower UPS Config - Over Discharge Protection' mappings: - value: '0' newvalue: disable - uuid: 85dfeb128a2643b0b0c73a5d1ff386ae name: 'CyberPower UPS Config - Recharged Capacity' mappings: - value: '0' newvalue: instant - uuid: f35f6acb44b447d88ab1c635c2eb2689 name: 'CyberPower UPS Config - Sleep After All Clients Shutdown' mappings: - value: '1' newvalue: disable - value: '2' newvalue: enable - uuid: 76af2f0c907f4869a2a308d8386e12ea name: 'CyberPower UPS Input Fail Cause' mappings: - value: '1' newvalue: noTransfer - value: '2' newvalue: highLineVoltage - value: '3' newvalue: brownout - value: '4' newvalue: selfTest - uuid: ff075d9d266246479aab43c23e2feb67 name: 'CyberPower UPS Input Status' mappings: - value: '1' newvalue: normal - value: '2' newvalue: overVoltage - value: '3' newvalue: underVoltage - value: '4' newvalue: frequencyFailure - value: '5' newvalue: blackout - uuid: d75e8a4243184cfaab4e5d86b73b336b name: 'CyberPower UPS Last Replace Date' mappings: - value: 'NULL' newvalue: 'Pls (re)set this value in web-interface' - uuid: b43bafe992a240079940a1aa6419168c name: 'CyberPower UPS Output Status' mappings: - value: '1' newvalue: unknown - value: '2' newvalue: onLine - value: '3' newvalue: onBattery - value: '4' newvalue: onBoost - value: '5' newvalue: onSleep - value: '6' newvalue: 'off' - value: '7' newvalue: rebooting