5.02021-11-21T21:29:58ZUPSEATON MistralEATON Mistral## Overview
Import and enjoy
tested with EATON 9PX 6000i model
Should work with other models too. Triggers for temperature and humidity are also added.
Created in zabbix v3.2.x
## Author
Nijaz Sehic
UPS- UPS-LocationSNMP_AGENT.1.3.6.1.2.1.1.6.0SNMP-UPS-Location300TEXT
- UPS-NameSNMP_AGENT.1.3.6.1.2.1.1.1.0SNMP-UPS-Name300TEXT
- UPS-ACNormal-VoltageSNMP_AGENT.1.3.6.1.2.1.33.1.5.3.1.2.1UPS-ACNormal-Voltage300TEXT{last(,0)}<120NO ELECTRICITY on {HOST.NAME}DISASTERMULTIPLE
- UPS-BatteryChargerFaultSNMP_AGENT.1.3.6.1.4.1.705.1.5.15.0UPS-BatteryChargerFault300TEXT{last()}=1UPS Battery Charger Fault on {HOST.NAME}HIGH
- UPS-BatteryChargeStatusSNMP_AGENT.1.3.6.1.2.1.33.1.2.4.0UPS-BatteryChargeStatus300TEXT
- UPS-BatteryFaultBatterySNMP_AGENT.1.3.6.1.4.1.705.1.5.9.0UPS-BatteryFaultBattery300TEXT{last()}=1UPS Battery Fault on {HOST.NAME}HIGH
- UPS-BatteryMinutesRemainingSNMP_AGENT.1.3.6.1.2.1.33.1.2.3.0UPS-BatteryMinutesRemaining300TEXT{last(,0)}<20LESS than 20 minutest battery remaining on {HOST.NAME}DISASTERMULTIPLE{last(,0)}<65LESS than 65 minutest battery remaining on {HOST.NAME}DISABLEDINFOMULTIPLE
- UPS-ConfigOutputVoltageSNMP_AGENT.1.3.6.1.2.1.33.1.9.3.0UPS-ConfigOutputVoltage300TEXT
- UPS-HumiditySNMP_AGENT.1.3.6.1.4.1.705.1.8.7.1.6.1UPS-Humidity300TEXT
- UPS-Humidity-HighSNMP_AGENT.1.3.6.1.4.1.705.1.8.7.1.8.1UPS-Humidity-High300TEXT{last()}=1Humidity is to High on {HOST.NAME}HIGHHumidity is to High in Server room
- UPS-Humidity-LowSNMP_AGENT.1.3.6.1.4.1.705.1.8.7.1.7.1UPS-Humidity-Low300TEXT{last()}=1Humidity is to Low on {HOST.NAME}AVERAGEHumidity is to Low in server room
- UPS-ManufacturerSNMP_AGENT.1.3.6.1.2.1.33.1.1.1.0UPS-Manufacturer300TEXT
- UPS-OutputPowerSourceSNMP_AGENT.1.3.6.1.4.1.705.1.7.3.0UPS-OutputPowerSource300TEXT{last()}=1SERVER room is powered by UPS Battery on {HOST.NAME}DISASTER
- UPS-Temperature-HighSNMP_AGENT.1.3.6.1.4.1.705.1.8.7.1.5.1UPS-Temperature-High300TEXT{last()}=1Temperature is to HighHIGHTemperature is to High in server room
- UPS-Temperature-LowSNMP_AGENT.1.3.6.1.4.1.705.1.8.7.1.4.1UPS-Temperature-Low300TEXT{last()}=1Temperature is to LowAVERAGETemperature is to Low in server room
- UPS-TemperatureLevelSNMP_AGENT.1.3.6.1.4.1.534.1.6.1.0UPS-TemperatureLevel300TEXT{last()}>28Temperature is above 28C on {HOST.NAME}HIGH{last()}<15Temperature is below 15C on {HOST.NAME}HIGH