zabbix_export: version: '5.4' date: '2021-11-21T21:30:00Z' groups: - uuid: 0e60ac85bc3941e2a1d66a048ff164da name: UPS templates: - uuid: b1863813fa894647bf81b8a7277c4ff3 template: 'EATON Mistral' name: 'EATON Mistral' description: | ## Overview Import and enjoy tested with EATON 9PX 6000i model Should work with other models too. Triggers for temperature and humidity are also added. Created in zabbix v3.2.x ## Author Nijaz Sehic groups: - name: UPS items: - uuid: 916163ab41554c5fb7b1691c4cd78f22 name: UPS-Location type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.1.6.0 key: SNMP-UPS-Location delay: '30' trends: '0' value_type: TEXT - uuid: fd39301ec12048fbb3c0106322b3c04b name: UPS-Name type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.1.1.0 key: SNMP-UPS-Name delay: '30' trends: '0' value_type: TEXT - uuid: 88a3f860ea1249f4a80b51e4133fc949 name: UPS-ACNormal-Voltage type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.5.3.1.2.1 key: UPS-ACNormal-Voltage delay: '30' trends: '0' value_type: TEXT triggers: - uuid: 239e10c3af114bb0b43c84de56de3033 expression: 'last(/EATON Mistral/UPS-ACNormal-Voltage,#1:now-0)<120' name: 'NO ELECTRICITY on {HOST.NAME}' priority: DISASTER type: MULTIPLE - uuid: c98d21e9cf1b41c0af20396379ff1514 name: UPS-BatteryChargerFault type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.705.1.5.15.0 key: UPS-BatteryChargerFault delay: '30' trends: '0' value_type: TEXT triggers: - uuid: b740d5f3af614387bc600b92db95661b expression: 'last(/EATON Mistral/UPS-BatteryChargerFault)=1' name: 'UPS Battery Charger Fault on {HOST.NAME}' priority: HIGH - uuid: b5476e0f91b245618eeadefa758461b6 name: UPS-BatteryChargeStatus type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.2.4.0 key: UPS-BatteryChargeStatus delay: '30' trends: '0' value_type: TEXT - uuid: 4cd58bbdb05d4d9b87cbc3ce36990a2e name: UPS-BatteryFaultBattery type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.705.1.5.9.0 key: UPS-BatteryFaultBattery delay: '30' trends: '0' value_type: TEXT triggers: - uuid: afdf148766d142f8a6cb8d9de8b23ad8 expression: 'last(/EATON Mistral/UPS-BatteryFaultBattery)=1' name: 'UPS Battery Fault on {HOST.NAME}' priority: HIGH - uuid: c6b2ce34b5a9491c92291cd3390d4e20 name: UPS-BatteryMinutesRemaining type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.2.3.0 key: UPS-BatteryMinutesRemaining delay: '30' trends: '0' value_type: TEXT triggers: - uuid: 712f8088523c4cbabc4addd18a2bd468 expression: 'last(/EATON Mistral/UPS-BatteryMinutesRemaining,#1:now-0)<20' name: 'LESS than 20 minutest battery remaining on {HOST.NAME}' priority: DISASTER type: MULTIPLE - uuid: cdfb6c2934fd42378b1c33ca11bba98e expression: 'last(/EATON Mistral/UPS-BatteryMinutesRemaining,#1:now-0)<65' name: 'LESS than 65 minutest battery remaining on {HOST.NAME}' status: DISABLED priority: INFO type: MULTIPLE - uuid: d84f29c4cc27466eae441187ce817434 name: UPS-ConfigOutputVoltage type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.9.3.0 key: UPS-ConfigOutputVoltage delay: '30' trends: '0' value_type: TEXT - uuid: bec24700f0ba4096b0e5df96a950cb6e name: UPS-Humidity type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.705.1.8.7.1.6.1 key: UPS-Humidity delay: '30' trends: '0' value_type: TEXT - uuid: 39c6ce8618944b4c9f02dd2dcb8e0c85 name: UPS-Humidity-High type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.705.1.8.7.1.8.1 key: UPS-Humidity-High delay: '30' trends: '0' value_type: TEXT triggers: - uuid: 8c7d314b73cd41ecb20a0fecda6554ca expression: 'last(/EATON Mistral/UPS-Humidity-High)=1' name: 'Humidity is to High on {HOST.NAME}' priority: HIGH description: 'Humidity is to High in Server room' - uuid: c575bc13abf949719ee5ac936b81971f name: UPS-Humidity-Low type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.705.1.8.7.1.7.1 key: UPS-Humidity-Low delay: '30' trends: '0' value_type: TEXT triggers: - uuid: a06c717f647a4355a5f5086ae742d24d expression: 'last(/EATON Mistral/UPS-Humidity-Low)=1' name: 'Humidity is to Low on {HOST.NAME}' priority: AVERAGE description: 'Humidity is to Low in server room' - uuid: bc53dd78e01c4020a26f7999591e19cf name: UPS-Manufacturer type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.1.1.0 key: UPS-Manufacturer delay: '30' trends: '0' value_type: TEXT - uuid: ec8e76402aff494c9cce772e44ad3922 name: UPS-OutputPowerSource type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.705.1.7.3.0 key: UPS-OutputPowerSource delay: '30' trends: '0' value_type: TEXT triggers: - uuid: e86ae7ceae274e40a164e339e31c032b expression: 'last(/EATON Mistral/UPS-OutputPowerSource)=1' name: 'SERVER room is powered by UPS Battery on {HOST.NAME}' priority: DISASTER - uuid: f9cc6451f0434ab9baf2d04b38fc0a4b name: UPS-Temperature-High type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.705.1.8.7.1.5.1 key: UPS-Temperature-High delay: '30' trends: '0' value_type: TEXT triggers: - uuid: a73a58f886034e72ae5af3e5e034e970 expression: 'last(/EATON Mistral/UPS-Temperature-High)=1' name: 'Temperature is to High' priority: HIGH description: 'Temperature is to High in server room' - uuid: f4c90b9c23f340e9be687b0159fea95e name: UPS-Temperature-Low type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.705.1.8.7.1.4.1 key: UPS-Temperature-Low delay: '30' trends: '0' value_type: TEXT triggers: - uuid: 74491f58da2d40a0b4ee566386fd7063 expression: 'last(/EATON Mistral/UPS-Temperature-Low)=1' name: 'Temperature is to Low' priority: AVERAGE description: 'Temperature is to Low in server room' - uuid: 4111ff67e06149aaa30f1cf151644212 name: UPS-TemperatureLevel type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.534.1.6.1.0 key: UPS-TemperatureLevel delay: '30' trends: '0' value_type: TEXT triggers: - uuid: 51267cb5f3dc4d7d90b60384bbb7521d expression: 'last(/EATON Mistral/UPS-TemperatureLevel)>28' name: 'Temperature is above 28C on {HOST.NAME}' priority: HIGH - uuid: 6074cb448e244f69a724fc547987ee02 expression: 'last(/EATON Mistral/UPS-TemperatureLevel)<15' name: 'Temperature is below 15C on {HOST.NAME}' priority: HIGH