zabbix_export: version: '5.4' date: '2021-11-21T21:48:18Z' groups: - uuid: 02b5701d3ed04e15ab0499bf0449519d name: PDU templates: - uuid: 60cabf63f1be45488d2ac88ee688aef1 template: 'Monitoring PDU' name: 'Monitoring PDU' description: | ## Overview Hi, Here is a template for HP PDU's There are mostly traps items but also some polling items. SNMPv2. Triggers are also include. You need to put your SNMP community in macro. Thanks. ## Author Vincent MATIAS groups: - name: PDU items: - uuid: 4da3b53de61e471592dd2464244c37c4 name: 'Load Segment 1' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.2.3.2.1.3.1.1 key: breakerCurrent.1.1 delay: 30s history: 2d status: DISABLED tags: - tag: Application value: Load - uuid: 5c3246cb4a8543dcb1de633dc59b81b6 name: 'Load Segment 2' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.2.3.2.1.3.1.2 key: breakerCurrent.1.2 delay: 30s history: 2d status: DISABLED tags: - tag: Application value: Load - uuid: 743b0a2a4082419a860161b571014d31 name: 'Load Segment 3' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.2.3.2.1.3.1.3 key: breakerCurrent.1.3 delay: 30s history: 2d status: DISABLED tags: - tag: Application value: Load - uuid: bb70081ecb974271b8d35d83e12ca9a2 name: 'Percent Load Segment 1' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.2.3.2.1.4.1.1 key: breakerPercentLoad.1.1 delay: 30s history: 2d status: DISABLED tags: - tag: Application value: Load - uuid: 3146fd8f10b440a497b1fb0650346dca name: 'Percent Load Segment 2' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.2.3.2.1.4.1.2 key: breakerPercentLoad.1.2 delay: 30s history: 2d status: DISABLED tags: - tag: Application value: Load - uuid: 81087b4825304bae9aaab68c33641c92 name: 'Percent Load Segment 3' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.2.3.2.1.4.1.3 key: breakerPercentLoad.1.3 delay: 30s history: 2d status: DISABLED tags: - tag: Application value: Load - uuid: d94034b42f144196bf2fe588f6f893cc name: 'Voltage Segment 1' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.2.3.2.1.2.1.1 key: breakerVoltage.1.1 delay: 30s history: 2d status: DISABLED tags: - tag: Application value: Voltage - uuid: 5713031c41f84a7d89afba32e8c45fc2 name: 'Voltage Segment 2' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.2.3.2.1.2.1.2 key: breakerVoltage.1.2 delay: 30s history: 2d status: DISABLED tags: - tag: Application value: Voltage - uuid: 986ed53221dd4881a03391bc0a45b87a name: 'Voltage Segment 3' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.2.3.2.1.2.1.3 key: breakerVoltage.1.3 delay: 30s history: 2d status: DISABLED tags: - tag: Application value: Voltage - uuid: 524f14275ddf4ec0994f29a2235541b0 name: 'PDU Name' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.2.1.2.1.2.1 key: pduName.1 delay: 1h history: 2d trends: '0' status: DISABLED value_type: TEXT tags: - tag: Application value: Informations - uuid: e0875c202a134f7dbb2feb6333508e8a name: 'Total Heat' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.2.3.1.1.3.1 key: pduOutputHeat.1 delay: 30s history: 2d status: DISABLED tags: - tag: Application value: Total triggers: - uuid: c139a175aadc452e948212d1f25ddb58 expression: 'min(/Monitoring PDU/pduOutputHeat.1,#3)>37704' name: 'Total Heat Critical on {HOST.NAME}' status: DISABLED priority: AVERAGE - uuid: 75a301d8b6554e7db55201a763fa4012 expression: 'min(/Monitoring PDU/pduOutputHeat.1,#3)>30163' name: 'Total Heat Warning on {HOST.NAME}' status: DISABLED priority: AVERAGE - uuid: e287e3f90fa244fb9c67d7f222d2694b name: 'Total Load' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.2.3.1.1.2.1 key: pduOutputLoad.1 delay: 30s history: 2d status: DISABLED tags: - tag: Application value: Total triggers: - uuid: c44d4e2c3b824d7c9c5c90307e9b2cfa expression: 'min(/Monitoring PDU/pduOutputLoad.1,#3)>50' name: 'Total Load above 50% on {HOST.NAME}' status: DISABLED priority: INFO - uuid: c97e45e5bcf44a35bc7cbfc98319cfd3 expression: 'min(/Monitoring PDU/pduOutputLoad.1,#3)>80' name: 'Total Load above 80% on {HOST.NAME}' status: DISABLED priority: WARNING - uuid: 8075cebcf964445eb2b78940309b624c expression: 'min(/Monitoring PDU/pduOutputLoad.1,#3)>100' name: 'Total Load above 100% on {HOST.NAME}' status: DISABLED priority: AVERAGE - uuid: f430e0761eaa426d89576f158907cc13 name: 'Total Power' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.2.3.1.1.4.1 key: pduOutputPower.1 delay: 30s history: 2d status: DISABLED tags: - tag: Application value: Total triggers: - uuid: eeba7f6771634befbfaf83d683d33ed8 expression: 'min(/Monitoring PDU/pduOutputPower.1,#3)>11040' name: 'Total Power Critical on {HOST.NAME}' status: DISABLED priority: AVERAGE - uuid: 3f491dc299ae46afbc003b34f9b306d2 expression: 'min(/Monitoring PDU/pduOutputPower.1,#3)>8832' name: 'Total Power Warning on {HOST.NAME}' status: DISABLED priority: WARNING - uuid: 6b780674819544bfbfb57e62cd9a1ee1 name: '{HOST.NAME} Status' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.2.1.2.1.8.1 key: pduStatus.1 history: 2d valuemap: name: 'CPQSINFO-MIB::status' tags: - tag: Application value: Informations triggers: - uuid: 56ed9273a5324b54b01971b907c46290 expression: 'nodata(/Monitoring PDU/pduStatus.1,3m)=1' name: 'Pas de données sur le statut de {HOST.NAME} pendant plus de 3 minutes.' priority: AVERAGE - uuid: 62738997c2b44a36a4df82740565ddd8 name: 'Trap fallback' type: SNMP_TRAP key: snmptrap.fallback delay: '0' history: 2d trends: '0' value_type: LOG tags: - tag: Application value: Trap triggers: - uuid: 06e1278dd6ec460899ac727af49c4309 expression: 'length(last(/Monitoring PDU/snmptrap.fallback))>1' name: 'Unknown trap received from {HOST.NAME}' priority: AVERAGE manual_close: 'YES' dependencies: - name: 'Pas de données sur le statut de {HOST.NAME} pendant plus de 3 minutes.' expression: 'nodata(/Monitoring PDU/pduStatus.1,3m)=1' - uuid: f2d490b859854ed1a87f046bf724c0a9 name: 'Trap Current Critical' type: SNMP_TRAP key: 'snmptrap["Current Critical"]' delay: '0' history: 2d trends: '0' value_type: LOG description: 'Current has exceeded the breaker rating level. The addition of any new load could overload or trip the breaker' tags: - tag: Application value: Trap triggers: - uuid: 98eff7f449f04589b4c39bd63972ba88 expression: 'find(/Monitoring PDU/snmptrap["Current Critical"],,"like","CPQPOWER-MIB::trapCritical")=1' recovery_mode: RECOVERY_EXPRESSION recovery_expression: 'find(/Monitoring PDU/snmptrap["Current Critical"],,"like","CPQPOWER-MIB::trapCleared")=1' name: 'Current Critical on {HOST.NAME}' priority: AVERAGE description: 'Current has exceeded the breaker rating level. The addition of any new load could overload or trip the breaker' dependencies: - name: 'Pas de données sur le statut de {HOST.NAME} pendant plus de 3 minutes.' expression: 'nodata(/Monitoring PDU/pduStatus.1,3m)=1' - uuid: 607533d8b2c14d3a8308b80185d2ae45 name: 'Trap Current Warning' type: SNMP_TRAP key: 'snmptrap["Current Warning"]' delay: '0' history: 2d trends: '0' value_type: LOG description: 'Current has reached the rating level for this breaker, the addition of any new load could overload or trip the breaker' tags: - tag: Application value: Trap triggers: - uuid: 859f06fd8cb6492aa56c709b31006b84 expression: 'find(/Monitoring PDU/snmptrap["Current Warning"],,"like","CPQPOWER-MIB::trapWarning")=1' recovery_mode: RECOVERY_EXPRESSION recovery_expression: 'find(/Monitoring PDU/snmptrap["Current Warning"],,"like","CPQPOWER-MIB::trapCleared")=1' name: 'Current Warning on {HOST.NAME}' priority: WARNING description: 'Current has reached the rating level for this breaker, the addition of any new load could overload or trip the breaker' dependencies: - name: 'Current Critical on {HOST.NAME}' expression: 'find(/Monitoring PDU/snmptrap["Current Critical"],,"like","CPQPOWER-MIB::trapCritical")=1' recovery_expression: 'find(/Monitoring PDU/snmptrap["Current Critical"],,"like","CPQPOWER-MIB::trapCleared")=1' - name: 'Pas de données sur le statut de {HOST.NAME} pendant plus de 3 minutes.' expression: 'nodata(/Monitoring PDU/pduStatus.1,3m)=1' - uuid: 803f452dee03447cb6932f5d7658fc51 name: 'Trap Load Critical' type: SNMP_TRAP key: 'snmptrap["Load Critical"]' delay: '0' history: 2d trends: '0' value_type: LOG description: 'The rated capacity of the breaker has been exceeded. There is a high risk of tripping the breaker' tags: - tag: Application value: Trap triggers: - uuid: 4c260fc44feb4260a96a5bba6d4b7453 expression: 'find(/Monitoring PDU/snmptrap["Load Critical"],,"like","CPQPOWER-MIB::trapCritical")=1' recovery_mode: RECOVERY_EXPRESSION recovery_expression: 'find(/Monitoring PDU/snmptrap["Load Critical"],,"like","CPQPOWER-MIB::trapCleared")=1' name: 'Load Critical on {HOST.NAME}' priority: AVERAGE description: 'The rated capacity of the breaker has been exceeded. There is a high risk of tripping the breaker' dependencies: - name: 'Pas de données sur le statut de {HOST.NAME} pendant plus de 3 minutes.' expression: 'nodata(/Monitoring PDU/pduStatus.1,3m)=1' - uuid: 8b44d55aeeae444e86aee27c918a5ae2 name: 'Trap Load Warning' type: SNMP_TRAP key: 'snmptrap["Load Warning"]' delay: '0' history: 2d trends: '0' value_type: LOG description: 'Load has reached the rating level for this breaker, the addition of any new load could overload or trip the breaker' tags: - tag: Application value: Trap triggers: - uuid: 05b0495463e24b2b817db1c87b4d429d expression: 'find(/Monitoring PDU/snmptrap["Load Warning"],,"like","CPQPOWER-MIB::trapWarning")=1' recovery_mode: RECOVERY_EXPRESSION recovery_expression: 'find(/Monitoring PDU/snmptrap["Load Warning"],,"like","CPQPOWER-MIB::trapCleared")=1' name: 'Load Warning on {HOST.NAME}' priority: WARNING description: 'Load has reached the rating level for this breaker, the addition of any new load could overload or trip the breaker' dependencies: - name: 'Load Critical on {HOST.NAME}' expression: 'find(/Monitoring PDU/snmptrap["Load Critical"],,"like","CPQPOWER-MIB::trapCritical")=1' recovery_expression: 'find(/Monitoring PDU/snmptrap["Load Critical"],,"like","CPQPOWER-MIB::trapCleared")=1' - name: 'Pas de données sur le statut de {HOST.NAME} pendant plus de 3 minutes.' expression: 'nodata(/Monitoring PDU/pduStatus.1,3m)=1' - uuid: a383c3ca5a1b40188068fdb99aa28c74 name: 'Trap PDU Communication Lost' type: SNMP_TRAP key: 'snmptrap["PDU Communication Lost"]' delay: '0' history: 2d trends: '0' value_type: LOG description: 'Connection between the daisy-chained PDUs is lost.' tags: - tag: Application value: Trap triggers: - uuid: 9c81f1a0d4aa4d289618ad7e08d3a58b expression: 'find(/Monitoring PDU/snmptrap["PDU Communication Lost"],,"like","CPQPOWER-MIB::trapWarning")=1' recovery_mode: RECOVERY_EXPRESSION recovery_expression: 'find(/Monitoring PDU/snmptrap["PDU Communication Lost"],,"like","CPQPOWER-MIB::trapCleared")=1' name: 'PDU Communication Lost on {HOST.NAME}' priority: WARNING description: 'Connection between the daisy-chained PDUs is lost.' dependencies: - name: 'Pas de données sur le statut de {HOST.NAME} pendant plus de 3 minutes.' expression: 'nodata(/Monitoring PDU/pduStatus.1,3m)=1' - uuid: 68d7eb6c33b64aa3a5ef9c5ca695193c name: 'Trap Total Heat Critical' type: SNMP_TRAP key: 'snmptrap["Total Heat Critical"]' delay: '0' history: 2d trends: '0' value_type: LOG description: 'The heat created by the load attached to this PDU has exceeded the set threshold' tags: - tag: Application value: Trap triggers: - uuid: 748c3b5d34214956b0554d76883210af expression: 'find(/Monitoring PDU/snmptrap["Total Heat Critical"],,"like","CPQPOWER-MIB::trapCritical")=1' recovery_mode: RECOVERY_EXPRESSION recovery_expression: 'find(/Monitoring PDU/snmptrap["Total Heat Critical"],,"like","CPQPOWER-MIB::trapCleared")=1' name: 'Total Heat Critical on {HOST.NAME}' priority: AVERAGE description: 'The heat created by the load attached to this PDU has exceeded the set threshold' dependencies: - name: 'Pas de données sur le statut de {HOST.NAME} pendant plus de 3 minutes.' expression: 'nodata(/Monitoring PDU/pduStatus.1,3m)=1' - uuid: 83e36769639e432e95a81b772e4001af name: 'Trap Total Heat Warning' type: SNMP_TRAP key: 'snmptrap["Total Heat Warning"]' delay: '0' history: 2d trends: '0' value_type: LOG description: 'The heat created by the load attached to this PDU has reached a threshold' tags: - tag: Application value: Trap triggers: - uuid: e3ad666483434576a4fb31bce8af50a4 expression: 'find(/Monitoring PDU/snmptrap["Total Heat Warning"],,"like","CPQPOWER-MIB::trapWarning")=1' recovery_mode: RECOVERY_EXPRESSION recovery_expression: 'find(/Monitoring PDU/snmptrap["Total Heat Warning"],,"like","CPQPOWER-MIB::trapCleared")=1' name: 'Total Heat Warning on {HOST.NAME}' priority: WARNING description: 'The heat created by the load attached to this PDU has reached a threshold' dependencies: - name: 'Pas de données sur le statut de {HOST.NAME} pendant plus de 3 minutes.' expression: 'nodata(/Monitoring PDU/pduStatus.1,3m)=1' - name: 'Total Heat Critical on {HOST.NAME}' expression: 'find(/Monitoring PDU/snmptrap["Total Heat Critical"],,"like","CPQPOWER-MIB::trapCritical")=1' recovery_expression: 'find(/Monitoring PDU/snmptrap["Total Heat Critical"],,"like","CPQPOWER-MIB::trapCleared")=1' - uuid: d81a244a67254c4384bf309b7a89d37b name: 'Trap Total Load Critical' type: SNMP_TRAP key: 'snmptrap["Total Load Critical"]' delay: '0' history: 2d trends: '0' value_type: LOG description: 'The rated capacity of the PDU has been exceeded. There is a risk of tripping the branch circuit protection' tags: - tag: Application value: Trap triggers: - uuid: 35edede575394d54a5986993a3ac66b5 expression: 'find(/Monitoring PDU/snmptrap["Total Load Critical"],,"like","CPQPOWER-MIB::trapCritical")=1' recovery_mode: RECOVERY_EXPRESSION recovery_expression: 'find(/Monitoring PDU/snmptrap["Total Load Critical"],,"like","CPQPOWER-MIB::trapCritical")=1' name: 'Total Load Critical on {HOST.NAME}' priority: AVERAGE description: 'The rated capacity of the PDU has been exceeded. There is a risk of tripping the branch circuit protection' dependencies: - name: 'Pas de données sur le statut de {HOST.NAME} pendant plus de 3 minutes.' expression: 'nodata(/Monitoring PDU/pduStatus.1,3m)=1' - uuid: d1da217ecb6e41b79630092828301632 name: 'Trap Total Load Warning' type: SNMP_TRAP key: 'snmptrap["Total Load Warning"]' delay: '0' history: 2d trends: '0' value_type: LOG description: 'The rated capacity for PDU has reached the rating level. There is a risk of tripping the branch circuit protection' tags: - tag: Application value: Trap triggers: - uuid: a905528c0d2e454ab1a65de49560d2d0 expression: 'find(/Monitoring PDU/snmptrap["Total Load Warning"],,"like","CPQPOWER-MIB::trapWarning")=1' recovery_mode: RECOVERY_EXPRESSION recovery_expression: 'find(/Monitoring PDU/snmptrap["Total Load Warning"],,"like","CPQPOWER-MIB::trapWarning")=1' name: 'Total Load Warning on {HOST.NAME}' priority: WARNING description: 'The rated capacity of the PDU has been exceeded. There is a risk of tripping the branch circuit protection' dependencies: - name: 'Pas de données sur le statut de {HOST.NAME} pendant plus de 3 minutes.' expression: 'nodata(/Monitoring PDU/pduStatus.1,3m)=1' - name: 'Total Load Critical on {HOST.NAME}' expression: 'find(/Monitoring PDU/snmptrap["Total Load Critical"],,"like","CPQPOWER-MIB::trapCritical")=1' recovery_expression: 'find(/Monitoring PDU/snmptrap["Total Load Critical"],,"like","CPQPOWER-MIB::trapCritical")=1' - uuid: 345123edfbad439abc7d9d079da02134 name: 'Trap Total Power Critical' type: SNMP_TRAP key: 'snmptrap["Total Power Critical"]' delay: '0' history: 2d trends: '0' value_type: LOG description: 'The rated capacity of the PDU has been exceeded. There is a risk of tripping the branch circuit protection' tags: - tag: Application value: Trap triggers: - uuid: d7f16335d0c442f4a5fb016680c1e5af expression: 'find(/Monitoring PDU/snmptrap["Total Power Critical"],,"like","CPQPOWER-MIB::trapCritical")=1' recovery_mode: RECOVERY_EXPRESSION recovery_expression: 'find(/Monitoring PDU/snmptrap["Total Power Critical"],,"like","CPQPOWER-MIB::trapCleared")=1' name: 'Total Power Critical on {HOST.NAME}' priority: AVERAGE description: 'The rated capacity of the PDU has been exceeded. There is a risk of tripping the branch circuit protection' dependencies: - name: 'Pas de données sur le statut de {HOST.NAME} pendant plus de 3 minutes.' expression: 'nodata(/Monitoring PDU/pduStatus.1,3m)=1' - uuid: f0fa9cd6c1194e5d9fa02b4bbd73c436 name: 'Trap Total Power Warning' type: SNMP_TRAP key: 'snmptrap["Total Power Warning"]' delay: '0' history: 2d trends: '0' value_type: LOG description: 'The rated capacity for PDU has reached rating level. There is a risk of tripping the branch circuit protection' tags: - tag: Application value: Trap triggers: - uuid: 7c8acd1747464a68af1c239995912415 expression: 'find(/Monitoring PDU/snmptrap["Total Power Warning"],,"like","CPQPOWER-MIB::trapWarning")=1' recovery_mode: RECOVERY_EXPRESSION recovery_expression: 'find(/Monitoring PDU/snmptrap["Total Power Warning"],,"like","CPQPOWER-MIB::trapCleared")=1' name: 'Total Power Warning on {HOST.NAME}' priority: WARNING description: 'The rated capacity for PDU has reached rating level. There is a risk of tripping the branch circuit protection' dependencies: - name: 'Pas de données sur le statut de {HOST.NAME} pendant plus de 3 minutes.' expression: 'nodata(/Monitoring PDU/pduStatus.1,3m)=1' - name: 'Total Power Critical on {HOST.NAME}' expression: 'find(/Monitoring PDU/snmptrap["Total Power Critical"],,"like","CPQPOWER-MIB::trapCritical")=1' recovery_expression: 'find(/Monitoring PDU/snmptrap["Total Power Critical"],,"like","CPQPOWER-MIB::trapCleared")=1' - uuid: 90264bac0ed4449084600f0685eac555 name: 'Trap Voltage High Critical' type: SNMP_TRAP key: 'snmptrap["Voltage High Critical"]' delay: '0' history: 2d trends: '0' value_type: LOG description: 'The PDU has detected an input line voltage that is more than 20% ABOVE the expected voltage' tags: - tag: Application value: Trap triggers: - uuid: 541f8e28acf54d0087add5a424c7c0f3 expression: 'find(/Monitoring PDU/snmptrap["Voltage High Critical"],,"like","CPQPOWER-MIB::trapCritical")=1' recovery_mode: RECOVERY_EXPRESSION recovery_expression: 'find(/Monitoring PDU/snmptrap["Voltage High Critical"],,"like","CPQPOWER-MIB::trapCleared")=1' name: 'Voltage High Critical on {HOST.NAME}' priority: AVERAGE description: 'The PDU has detected an input line voltage that is more than 20% ABOVE the expected voltage' dependencies: - name: 'Pas de données sur le statut de {HOST.NAME} pendant plus de 3 minutes.' expression: 'nodata(/Monitoring PDU/pduStatus.1,3m)=1' - uuid: 80998c8200024bc59b7c7fd89f77b317 name: 'Trap Voltage High Warning' type: SNMP_TRAP key: 'snmptrap["Voltage High Warning"]' delay: '0' history: 2d trends: '0' value_type: LOG description: 'The PDU has detected an input line voltage that is more than 10% ABOVE the expected voltage' tags: - tag: Application value: Trap triggers: - uuid: e6fc90c1521048c5a65a91963e5069bb expression: 'find(/Monitoring PDU/snmptrap["Voltage High Warning"],,"like","CPQPOWER-MIB::trapWarning")=1' recovery_mode: RECOVERY_EXPRESSION recovery_expression: 'find(/Monitoring PDU/snmptrap["Voltage High Warning"],,"like","CPQPOWER-MIB::trapCleared")=1' name: 'Voltage High Warning on {HOST.NAME}' priority: WARNING description: 'The PDU has detected an input line voltage that is more than 10% ABOVE the expected voltage' dependencies: - name: 'Pas de données sur le statut de {HOST.NAME} pendant plus de 3 minutes.' expression: 'nodata(/Monitoring PDU/pduStatus.1,3m)=1' - name: 'Voltage High Critical on {HOST.NAME}' expression: 'find(/Monitoring PDU/snmptrap["Voltage High Critical"],,"like","CPQPOWER-MIB::trapCritical")=1' recovery_expression: 'find(/Monitoring PDU/snmptrap["Voltage High Critical"],,"like","CPQPOWER-MIB::trapCleared")=1' - uuid: efe668378265468e96cf218399510960 name: 'Trap Voltage Low Critical' type: SNMP_TRAP key: 'snmptrap["Voltage Low Critical"]' delay: '0' history: 2d trends: '0' value_type: LOG description: 'The PDU has detected a very low input line voltage more than 20% BELOW the expected voltage, or the breaker may have tripped.' tags: - tag: Application value: Trap triggers: - uuid: 1d45a47222d4459d902dcbcd0c75f763 expression: 'find(/Monitoring PDU/snmptrap["Voltage Low Critical"],,"like","CPQPOWER-MIB::trapCritical")=1' recovery_mode: RECOVERY_EXPRESSION recovery_expression: 'find(/Monitoring PDU/snmptrap["Voltage Low Critical"],,"like","CPQPOWER-MIB::trapCleared")=1' name: 'Voltage Low Critical on {HOST.NAME}' priority: AVERAGE description: 'The PDU has detected a very low input line voltage more than 20% BELOW the expected voltage, or the breaker may have tripped.' dependencies: - name: 'Pas de données sur le statut de {HOST.NAME} pendant plus de 3 minutes.' expression: 'nodata(/Monitoring PDU/pduStatus.1,3m)=1' - uuid: 973e2724af4847e8a409f7b3e008a688 name: 'Trap Voltage Low Warning' type: SNMP_TRAP key: 'snmptrap["Voltage Low Warning"]' delay: '0' history: 2d trends: '0' value_type: LOG description: 'The PDU has detected an input line voltage that is more than 10% BELOW the expected voltage' tags: - tag: Application value: Trap triggers: - uuid: fa1ef8336bec4c279013bd1263d5c00e expression: 'find(/Monitoring PDU/snmptrap["Voltage Low Warning"],,"like","CPQPOWER-MIB::trapWarning")=1' recovery_mode: RECOVERY_EXPRESSION recovery_expression: 'find(/Monitoring PDU/snmptrap["Voltage Low Warning"],,"like","CPQPOWER-MIB::trapCleared")=1' name: 'Voltage Low Warning on {HOST.NAME}' priority: WARNING description: 'The PDU has detected an input line voltage that is more than 10% BELOW the expected voltage' dependencies: - name: 'Pas de données sur le statut de {HOST.NAME} pendant plus de 3 minutes.' expression: 'nodata(/Monitoring PDU/pduStatus.1,3m)=1' - name: 'Voltage Low Critical on {HOST.NAME}' expression: 'find(/Monitoring PDU/snmptrap["Voltage Low Critical"],,"like","CPQPOWER-MIB::trapCritical")=1' recovery_expression: 'find(/Monitoring PDU/snmptrap["Voltage Low Critical"],,"like","CPQPOWER-MIB::trapCleared")=1' macros: - macro: '{$SNMP_COMMUNITY}' valuemaps: - uuid: 72e8fbd32e8a4a449e42bb0f3bf72ebb name: 'CPQSINFO-MIB::status' mappings: - value: '1' newvalue: other - value: '2' newvalue: ok - value: '3' newvalue: degraded - value: '4' newvalue: failed