5.02021-11-21T21:57:17ZTemplates/Server hardwareRaritan PDU PX3Raritan PDU PX3## Description
Zabbix monitoring template for Raritan PDU PX3-5466R This template was tested only on Zabbix 4.4 and PX3-5466R devices but may work on other models too. The sensor discovery is simplistic and many assumptions were made, which might require little changes to make it work on other models. The discovery rules are set to 1 minute interval and the discovered items are also set to 1 minute interval in order to allow quick tests. For real deployments you should create your own template, link this template to your own template and override the discovery intervals with values that make sense for you. For example, we use 1 day interval for the discovery rules because our power topology is pretty static and once the first discovery is done there is no need to keep discovery rules running often. The triggers are defined based on the sensor states in order to respect the thresholds defined in each PDU, and for that reason the actual PDU thresholds don't show in the graphs.
## Overview
Zabbix monitoring template for Raritan PDU PX3-5466R
====================================================
This template was tested only on **Zabbix 4.4** and **PX3-5466R** devices but may work on other models too. The sensor discovery is simplistic and many assumptions were made, which might require little changes to make it work on other models.
The discovery rules are set to 1 minute interval and the discovered items are also set to 1 minute interval in order to allow quick tests. **For real deployments you should create your own template, link this template to your own template and override the discovery intervals with values that make sense for you**. For example, we use 1 day interval for the discovery rules because our power topology is pretty static and once the first discovery is done there is no need to keep discovery rules running often.
The triggers are defined based on the sensor states in order to respect the thresholds defined in each PDU, and for that reason the actual PDU thresholds don't show in the graphs.
Suggestions and corrections are welcome, see <https://github.com/BrandwatchLtd/zabbix-templates/tree/master/raritan-pdu-px3>
Inspired in [https://share.zabbix.com/power-ups/legrand-inform/raritan-px-pdu](power-ups/legrand-inform/raritan-px-pdu)
## Author
Tiago TT
Templates/Server hardwareHumidityInlet Apparent PowerInlet CurrentInlet FrequencyInlet PowerInlet Power FactorInlet VoltageOutlet Apparent PowerOutlet CurrentOutlet FrequencyOutlet PowerOutlet Power FactorOutlet VoltageProtector CurrentProtector TripStateSystemTemperatureDetails DiscoverySNMP_AGENTdiscovery[{#PDU_DETAILS_MANUFACTURER},.1.3.6.1.4.1.13742.6.3.2.1.1.2,{#PDU_DETAILS_MODEL},.1.3.6.1.4.1.13742.6.3.2.1.1.3,{#PDU_DETAILS_SERIAL},.1.3.6.1.4.1.13742.6.3.2.1.1.4,{#PDU_DETAILS_VOLTAGE},.1.3.6.1.4.1.13742.6.3.2.1.1.5,{#PDU_DETAILS_CURRENT},.1.3.6.1.4.1.13742.6.3.2.1.1.6,{#PDU_DETAILS_FREQUENCY},.1.3.6.1.4.1.13742.6.3.2.1.1.7,{#PDU_DETAILS_POWER},.1.3.6.1.4.1.13742.6.3.2.1.1.8,{#PDU_DETAILS_DIAGRAM_URL},.1.3.6.1.4.1.13742.6.3.2.1.1.9]pdu.detailsPDU {#PDU_DETAILS_MANUFACTURER} - {#PDU_DETAILS_MODEL} Serial NumberSNMP_AGENT.1.3.6.1.4.1.13742.6.3.2.1.1.4.{#SNMPINDEX}pdu.details.pdu[{#SNMPINDEX}]1d0TEXTSerial number of the PDU with the following details:
Manufacturer: {#PDU_DETAILS_MANUFACTURER}
Model: {#PDU_DETAILS_MODEL}
Rated Voltage: {#PDU_DETAILS_VOLTAGE}
Rated Current: {#PDU_DETAILS_CURRENT}
Rated Frequency: {#PDU_DETAILS_FREQUENCY}
Rated Apparent Power: {#PDU_DETAILS_POWER}
Diagram URL: {#PDU_DETAILS_DIAGRAM_URL}SystemPower Inlet DiscoverySNMP_AGENTdiscovery[{#PDU_INLET_ID},.1.3.6.1.4.1.13742.6.3.3.3.1.2.1,{#PDU_INLET_NAME},.1.3.6.1.4.1.13742.6.3.3.3.1.3.1,{#PDU_INLET_RATED_VOLTAGE},.1.3.6.1.4.1.13742.6.3.3.3.1.6.1,{#PDU_INLET_RATED_CURRENT},.1.3.6.1.4.1.13742.6.3.3.3.1.7.1,{#PDU_INLET_SOCKET},.1.3.6.1.4.1.13742.6.3.3.3.1.12.1]pdu.inletActive Power on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}SNMP_AGENT.1.3.6.1.4.1.13742.6.5.2.3.1.6.1.{#SNMPINDEX}.5pdu.inlet.active_power[{#SNMPINDEX}]FLOATWActive Power sensor from the PDU inlet with the following details:
ID: {#PDU_INTLET_ID}
Name: {#PDU_INLET_NAME}
Rated Voltage: {#PDU_INLET_RATED_VOLTAGE}
Rated Current: {#PDU_INLET_RATED_CURRENT}
Socket: {#PDU_INLET_SOCKET}Inlet PowerActive Power State on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}SNMP_AGENT.1.3.6.1.4.1.13742.6.5.2.3.1.3.1.{#SNMPINDEX}.5pdu.inlet.active_power_state[{#SNMPINDEX}]FLOATActive Power sensor from the PDU inlet with the following details:
ID: {#PDU_INTLET_ID}
Name: {#PDU_INLET_NAME}
Rated Voltage: {#PDU_INLET_RATED_VOLTAGE}
Rated Current: {#PDU_INLET_RATED_CURRENT}
Socket: {#PDU_INLET_SOCKET}StateRaritan PDU State EnumerationApparent Power on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}SNMP_AGENT.1.3.6.1.4.1.13742.6.5.2.3.1.6.1.{#SNMPINDEX}.6pdu.inlet.apparent_power[{#SNMPINDEX}]FLOATVAApparent Power sensor from the PDU inlet with the following details:
ID: {#PDU_INTLET_ID}
Name: {#PDU_INLET_NAME}
Rated Voltage: {#PDU_INLET_RATED_VOLTAGE}
Rated Current: {#PDU_INLET_RATED_CURRENT}
Socket: {#PDU_INLET_SOCKET}Inlet Apparent PowerApparent Power State on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}SNMP_AGENT.1.3.6.1.4.1.13742.6.5.2.3.1.3.1.{#SNMPINDEX}.6pdu.inlet.apparent_power_state[{#SNMPINDEX}]FLOATApparent Power sensor from the PDU inlet with the following details:
ID: {#PDU_INTLET_ID}
Name: {#PDU_INLET_NAME}
Rated Voltage: {#PDU_INLET_RATED_VOLTAGE}
Rated Current: {#PDU_INLET_RATED_CURRENT}
Socket: {#PDU_INLET_SOCKET}StateRaritan PDU State EnumerationFrequency on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}SNMP_AGENT.1.3.6.1.4.1.13742.6.5.2.3.1.6.1.{#SNMPINDEX}.23pdu.inlet.frequency[{#SNMPINDEX}]FLOATHzFrequency sensor from the PDU inlet with the following details:
ID: {#PDU_INTLET_ID}
Name: {#PDU_INLET_NAME}
Rated Voltage: {#PDU_INLET_RATED_VOLTAGE}
Rated Current: {#PDU_INLET_RATED_CURRENT}
Socket: {#PDU_INLET_SOCKET}Inlet FrequencyMULTIPLIER0.1Frequency State on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}SNMP_AGENT.1.3.6.1.4.1.13742.6.5.2.3.1.3.1.{#SNMPINDEX}.23pdu.inlet.frequency_state[{#SNMPINDEX}]FLOATFrequency sensor from the PDU inlet with the following details:
ID: {#PDU_INTLET_ID}
Name: {#PDU_INLET_NAME}
Rated Voltage: {#PDU_INLET_RATED_VOLTAGE}
Rated Current: {#PDU_INLET_RATED_CURRENT}
Socket: {#PDU_INLET_SOCKET}StateRaritan PDU State EnumerationPower Factor on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}SNMP_AGENT.1.3.6.1.4.1.13742.6.5.2.3.1.6.1.{#SNMPINDEX}.7pdu.inlet.power_factor[{#SNMPINDEX}]FLOATPower Factor sensor from the PDU inlet with the following details:
ID: {#PDU_INTLET_ID}
Name: {#PDU_INLET_NAME}
Rated Voltage: {#PDU_INLET_RATED_VOLTAGE}
Rated Current: {#PDU_INLET_RATED_CURRENT}
Socket: {#PDU_INLET_SOCKET}Inlet Power FactorMULTIPLIER0.01Power Factor State on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}SNMP_AGENT.1.3.6.1.4.1.13742.6.5.2.3.1.3.1.{#SNMPINDEX}.7pdu.inlet.power_factor_state[{#SNMPINDEX}]FLOATPower Factor sensor from the PDU inlet with the following details:
ID: {#PDU_INTLET_ID}
Name: {#PDU_INLET_NAME}
Rated Voltage: {#PDU_INLET_RATED_VOLTAGE}
Rated Current: {#PDU_INLET_RATED_CURRENT}
Socket: {#PDU_INLET_SOCKET}StateRaritan PDU State EnumerationRMS Current on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}SNMP_AGENT.1.3.6.1.4.1.13742.6.5.2.3.1.6.1.{#SNMPINDEX}.1pdu.inlet.rms_current[{#SNMPINDEX}]FLOATARMS Current sensor from the PDU inlet with the following details:
ID: {#PDU_INTLET_ID}
Name: {#PDU_INLET_NAME}
Rated Voltage: {#PDU_INLET_RATED_VOLTAGE}
Rated Current: {#PDU_INLET_RATED_CURRENT}
Socket: {#PDU_INLET_SOCKET}Inlet CurrentMULTIPLIER0.001RMS Current State on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}SNMP_AGENT.1.3.6.1.4.1.13742.6.5.2.3.1.3.1.{#SNMPINDEX}.1pdu.inlet.rms_current_state[{#SNMPINDEX}]FLOATRMS Current sensor from the PDU inlet with the following details:
ID: {#PDU_INTLET_ID}
Name: {#PDU_INLET_NAME}
Rated Voltage: {#PDU_INLET_RATED_VOLTAGE}
Rated Current: {#PDU_INLET_RATED_CURRENT}
Socket: {#PDU_INLET_SOCKET}StateRaritan PDU State EnumerationRMS Voltage on INlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}SNMP_AGENT.1.3.6.1.4.1.13742.6.5.2.3.1.6.1.{#SNMPINDEX}.4pdu.inlet.rms_voltage[{#SNMPINDEX}]FLOATVRMS Voltage sensor from the PDU inlet with the following details:
ID: {#PDU_INTLET_ID}
Name: {#PDU_INLET_NAME}
Rated Voltage: {#PDU_INLET_RATED_VOLTAGE}
Rated Current: {#PDU_INLET_RATED_CURRENT}
Socket: {#PDU_INLET_SOCKET}Inlet VoltageRMS Voltage State on INlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}SNMP_AGENT.1.3.6.1.4.1.13742.6.5.2.3.1.3.1.{#SNMPINDEX}.4pdu.inlet.rms_voltage_state[{#SNMPINDEX}]FLOATRMS Voltage sensor from the PDU inlet with the following details:
ID: {#PDU_INTLET_ID}
Name: {#PDU_INLET_NAME}
Rated Voltage: {#PDU_INLET_RATED_VOLTAGE}
Rated Current: {#PDU_INLET_RATED_CURRENT}
Socket: {#PDU_INLET_SOCKET}StateRaritan PDU State Enumeration{Raritan PDU PX3:pdu.inlet.active_power_state[{#SNMPINDEX}].last()}=6 or {Raritan PDU PX3:pdu.inlet.apparent_power_state[{#SNMPINDEX}].last()}=6 or {Raritan PDU PX3:pdu.inlet.frequency_state[{#SNMPINDEX}].last()}=6 or {Raritan PDU PX3:pdu.inlet.power_factor_state[{#SNMPINDEX}].last()}=6 or {Raritan PDU PX3:pdu.inlet.rms_current_state[{#SNMPINDEX}].last()}=6 or {Raritan PDU PX3:pdu.inlet.rms_voltage_state[{#SNMPINDEX}].last()}=6High Critical State on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}Check individual inlet sensor state to find which sensor is reporting a problem.HIGHHigh Critical state detected from at least one sensor of the PDU inlet with the following details:
ID: {#PDU_INTLET_ID}
Name: {#PDU_INLET_NAME}
Rated Voltage: {#PDU_INLET_RATED_VOLTAGE}
Rated Current: {#PDU_INLET_RATED_CURRENT}
Socket: {#PDU_INLET_SOCKET}
Check individual inlet sensor state to find which sensor is reporting a problem.{Raritan PDU PX3:pdu.inlet.active_power_state[{#SNMPINDEX}].last()}=5 or {Raritan PDU PX3:pdu.inlet.apparent_power_state[{#SNMPINDEX}].last()}=5 or {Raritan PDU PX3:pdu.inlet.frequency_state[{#SNMPINDEX}].last()}=5 or {Raritan PDU PX3:pdu.inlet.power_factor_state[{#SNMPINDEX}].last()}=5 or {Raritan PDU PX3:pdu.inlet.rms_current_state[{#SNMPINDEX}].last()}=5 or {Raritan PDU PX3:pdu.inlet.rms_voltage_state[{#SNMPINDEX}].last()}=5High Warning State on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}Check individual inlet sensor state to find which sensor is reporting a problem.WARNINGHigh Warning state detected from at least one sensor of the PDU inlet with the following details:
ID: {#PDU_INTLET_ID}
Name: {#PDU_INLET_NAME}
Rated Voltage: {#PDU_INLET_RATED_VOLTAGE}
Rated Current: {#PDU_INLET_RATED_CURRENT}
Socket: {#PDU_INLET_SOCKET}
Check individual inlet sensor state to find which sensor is reporting a problem.{Raritan PDU PX3:pdu.inlet.active_power_state[{#SNMPINDEX}].last()}=2 or {Raritan PDU PX3:pdu.inlet.apparent_power_state[{#SNMPINDEX}].last()}=2 or {Raritan PDU PX3:pdu.inlet.frequency_state[{#SNMPINDEX}].last()}=2 or {Raritan PDU PX3:pdu.inlet.power_factor_state[{#SNMPINDEX}].last()}=2 or {Raritan PDU PX3:pdu.inlet.rms_current_state[{#SNMPINDEX}].last()}=2 or {Raritan PDU PX3:pdu.inlet.rms_voltage_state[{#SNMPINDEX}].last()}=2Low Critical State on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}Check individual inlet sensor state to find which sensor is reporting a problem.HIGHLow Critical state detected from at least one sensor of the PDU inlet with the following details:
ID: {#PDU_INTLET_ID}
Name: {#PDU_INLET_NAME}
Rated Voltage: {#PDU_INLET_RATED_VOLTAGE}
Rated Current: {#PDU_INLET_RATED_CURRENT}
Socket: {#PDU_INLET_SOCKET}
Check individual inlet sensor state to find which sensor is reporting a problem.{Raritan PDU PX3:pdu.inlet.active_power_state[{#SNMPINDEX}].last()}=3 or {Raritan PDU PX3:pdu.inlet.apparent_power_state[{#SNMPINDEX}].last()}=3 or {Raritan PDU PX3:pdu.inlet.frequency_state[{#SNMPINDEX}].last()}=3 or {Raritan PDU PX3:pdu.inlet.power_factor_state[{#SNMPINDEX}].last()}=3 or {Raritan PDU PX3:pdu.inlet.rms_current_state[{#SNMPINDEX}].last()}=3 or {Raritan PDU PX3:pdu.inlet.rms_voltage_state[{#SNMPINDEX}].last()}=3Low Warning State on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}Check individual inlet sensor state to find which sensor is reporting a problem.WARNINGLow Warning state detected from at least one sensor of the PDU inlet with the following details:
ID: {#PDU_INTLET_ID}
Name: {#PDU_INLET_NAME}
Rated Voltage: {#PDU_INLET_RATED_VOLTAGE}
Rated Current: {#PDU_INLET_RATED_CURRENT}
Socket: {#PDU_INLET_SOCKET}
Check individual inlet sensor state to find which sensor is reporting a problem.{Raritan PDU PX3:pdu.inlet.active_power_state[{#SNMPINDEX}].last()}=-1 or {Raritan PDU PX3:pdu.inlet.apparent_power_state[{#SNMPINDEX}].last()}=-1 or {Raritan PDU PX3:pdu.inlet.frequency_state[{#SNMPINDEX}].last()}=-1 or {Raritan PDU PX3:pdu.inlet.power_factor_state[{#SNMPINDEX}].last()}=-1 or {Raritan PDU PX3:pdu.inlet.rms_current_state[{#SNMPINDEX}].last()}=-1 or {Raritan PDU PX3:pdu.inlet.rms_voltage_state[{#SNMPINDEX}].last()}=-1Unavailable State on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}Check individual inlet sensor state to find which sensor is reporting a problem.INFOUnavailable state detected from at least one sensor of the PDU inlet with the following details:
ID: {#PDU_INTLET_ID}
Name: {#PDU_INLET_NAME}
Rated Voltage: {#PDU_INLET_RATED_VOLTAGE}
Rated Current: {#PDU_INLET_RATED_CURRENT}
Socket: {#PDU_INLET_SOCKET}
Check individual inlet sensor state to find which sensor is reporting a problem.Frequency on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}1A7C11- Raritan PDU PX3pdu.inlet.frequency[{#SNMPINDEX}]
Power Factor on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}1A7C11- Raritan PDU PX3pdu.inlet.power_factor[{#SNMPINDEX}]
Power on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}1A7C11- Raritan PDU PX3pdu.inlet.active_power[{#SNMPINDEX}]
1F63100- Raritan PDU PX3pdu.inlet.apparent_power[{#SNMPINDEX}]
RMS Current on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}1A7C11- Raritan PDU PX3pdu.inlet.rms_current[{#SNMPINDEX}]
RMS Voltage on INlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}1A7C11- Raritan PDU PX3pdu.inlet.rms_voltage[{#SNMPINDEX}]
Power Outlet DiscoverySNMP_AGENTdiscovery[{#PDU_OUTLET_ID},.1.3.6.1.4.1.13742.6.3.5.3.1.2.1,{#PDU_OUTLET_NAME},.1.3.6.1.4.1.13742.6.3.5.3.1.3.1,{#PDU_OUTLET_RATED_VOLTAGE},.1.3.6.1.4.1.13742.6.3.5.3.1.6.1,{#PDU_OUTLET_RATED_CURRENT},.1.3.6.1.4.1.13742.6.3.5.3.1.7.1,{#PDU_OUTLET_SOCKET},.1.3.6.1.4.1.13742.6.3.5.3.1.29.1]pdu.outletActive Power on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}SNMP_AGENT.1.3.6.1.4.1.13742.6.5.4.3.1.6.1.{#PDU_OUTLET_ID}.5pdu.outlet.active_power[{#PDU_OUTLET_ID}]FLOATWActive Power sensor from the PDU outlet with the following details:
ID: {#PDU_OUTLET_ID}
Name: {#PDU_OUTLET_NAME}
Rated Voltage: {#PDU_OUTLET_RATED_VOLTAGE}
Rated Current: {#PDU_OUTLET_RATED_CURRENT}
Socket: {#PDU_OUTLET_SOCKET}Outlet PowerActive Power State on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}SNMP_AGENT.1.3.6.1.4.1.13742.6.5.4.3.1.3.1.{#PDU_OUTLET_ID}.5pdu.outlet.active_power_state[{#PDU_OUTLET_ID}]FLOATActive Power sensor from the PDU outlet with the following details:
ID: {#PDU_OUTLET_ID}
Name: {#PDU_OUTLET_NAME}
Rated Voltage: {#PDU_OUTLET_RATED_VOLTAGE}
Rated Current: {#PDU_OUTLET_RATED_CURRENT}
Socket: {#PDU_OUTLET_SOCKET}StateRaritan PDU State EnumerationApparent Power on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}SNMP_AGENT.1.3.6.1.4.1.13742.6.5.4.3.1.6.1.{#PDU_OUTLET_ID}.6pdu.outlet.apparent_power[{#PDU_OUTLET_ID}]FLOATVAApparent Power sensor from the PDU outlet with the following details:
ID: {#PDU_OUTLET_ID}
Name: {#PDU_OUTLET_NAME}
Rated Voltage: {#PDU_OUTLET_RATED_VOLTAGE}
Rated Current: {#PDU_OUTLET_RATED_CURRENT}
Socket: {#PDU_OUTLET_SOCKET}Outlet Apparent PowerApparent Power State on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}SNMP_AGENT.1.3.6.1.4.1.13742.6.5.4.3.1.3.1.{#PDU_OUTLET_ID}.6pdu.outlet.apparent_power_state[{#PDU_OUTLET_ID}]FLOATApparent Power sensor from the PDU outlet with the following details:
ID: {#PDU_OUTLET_ID}
Name: {#PDU_OUTLET_NAME}
Rated Voltage: {#PDU_OUTLET_RATED_VOLTAGE}
Rated Current: {#PDU_OUTLET_RATED_CURRENT}
Socket: {#PDU_OUTLET_SOCKET}StateRaritan PDU State EnumerationFrequency on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}SNMP_AGENT.1.3.6.1.4.1.13742.6.5.4.3.1.6.1.{#PDU_OUTLET_ID}.23pdu.outlet.frequency[{#PDU_OUTLET_ID}]FLOATHzFrequency sensor from the PDU outlet with the following details:
ID: {#PDU_OUTLET_ID}
Name: {#PDU_OUTLET_NAME}
Rated Voltage: {#PDU_OUTLET_RATED_VOLTAGE}
Rated Current: {#PDU_OUTLET_RATED_CURRENT}
Socket: {#PDU_OUTLET_SOCKET}Outlet FrequencyMULTIPLIER0.1Frequency State on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}SNMP_AGENT.1.3.6.1.4.1.13742.6.5.4.3.1.3.1.{#PDU_OUTLET_ID}.23pdu.outlet.frequency_state[{#PDU_OUTLET_ID}]FLOATFrequency sensor from the PDU outlet with the following details:
ID: {#PDU_OUTLET_ID}
Name: {#PDU_OUTLET_NAME}
Rated Voltage: {#PDU_OUTLET_RATED_VOLTAGE}
Rated Current: {#PDU_OUTLET_RATED_CURRENT}
Socket: {#PDU_OUTLET_SOCKET}StateRaritan PDU State EnumerationPower Factor on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}SNMP_AGENT.1.3.6.1.4.1.13742.6.5.4.3.1.6.1.{#PDU_OUTLET_ID}.7pdu.outlet.power_factor[{#PDU_OUTLET_ID}]FLOATPower Factor sensor from the PDU outlet with the following details:
ID: {#PDU_OUTLET_ID}
Name: {#PDU_OUTLET_NAME}
Rated Voltage: {#PDU_OUTLET_RATED_VOLTAGE}
Rated Current: {#PDU_OUTLET_RATED_CURRENT}
Socket: {#PDU_OUTLET_SOCKET}Outlet Power FactorMULTIPLIER0.01Power Factor State on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}SNMP_AGENT.1.3.6.1.4.1.13742.6.5.4.3.1.3.1.{#PDU_OUTLET_ID}.7pdu.outlet.power_factor_state[{#PDU_OUTLET_ID}]FLOATPower Factor sensor from the PDU outlet with the following details:
ID: {#PDU_OUTLET_ID}
Name: {#PDU_OUTLET_NAME}
Rated Voltage: {#PDU_OUTLET_RATED_VOLTAGE}
Rated Current: {#PDU_OUTLET_RATED_CURRENT}
Socket: {#PDU_OUTLET_SOCKET}StateRaritan PDU State EnumerationRMS Current on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}SNMP_AGENT.1.3.6.1.4.1.13742.6.5.4.3.1.6.1.{#PDU_OUTLET_ID}.1pdu.outlet.rms_current[{#PDU_OUTLET_ID}]FLOATARMS Current sensor from the PDU outlet with the following details:
ID: {#PDU_OUTLET_ID}
Name: {#PDU_OUTLET_NAME}
Rated Voltage: {#PDU_OUTLET_RATED_VOLTAGE}
Rated Current: {#PDU_OUTLET_RATED_CURRENT}
Socket: {#PDU_OUTLET_SOCKET}Outlet CurrentMULTIPLIER0.001RMS Current State on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}SNMP_AGENT.1.3.6.1.4.1.13742.6.5.4.3.1.3.1.{#PDU_OUTLET_ID}.1pdu.outlet.rms_current_state[{#PDU_OUTLET_ID}]FLOATRMS Current sensor from the PDU outlet with the following details:
ID: {#PDU_OUTLET_ID}
Name: {#PDU_OUTLET_NAME}
Rated Voltage: {#PDU_OUTLET_RATED_VOLTAGE}
Rated Current: {#PDU_OUTLET_RATED_CURRENT}
Socket: {#PDU_OUTLET_SOCKET}StateRaritan PDU State EnumerationRMS Voltage on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}SNMP_AGENT.1.3.6.1.4.1.13742.6.5.4.3.1.6.1.{#PDU_OUTLET_ID}.4pdu.outlet.rms_voltage[{#PDU_OUTLET_ID}]FLOATVRMS Voltage sensor from the PDU outlet with the following details:
ID: {#PDU_OUTLET_ID}
Name: {#PDU_OUTLET_NAME}
Rated Voltage: {#PDU_OUTLET_RATED_VOLTAGE}
Rated Current: {#PDU_OUTLET_RATED_CURRENT}
Socket: {#PDU_OUTLET_SOCKET}Outlet VoltageRMS Voltage State on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}SNMP_AGENT.1.3.6.1.4.1.13742.6.5.4.3.1.3.1.{#PDU_OUTLET_ID}.4pdu.outlet.rms_voltage_state[{#PDU_OUTLET_ID}]FLOATRMS Voltage sensor from the PDU outlet with the following details:
ID: {#PDU_OUTLET_ID}
Name: {#PDU_OUTLET_NAME}
Rated Voltage: {#PDU_OUTLET_RATED_VOLTAGE}
Rated Current: {#PDU_OUTLET_RATED_CURRENT}
Socket: {#PDU_OUTLET_SOCKET}Raritan PDU State Enumeration{Raritan PDU PX3:pdu.outlet.active_power_state[{#PDU_OUTLET_ID}].last()}=6
or {Raritan PDU PX3:pdu.outlet.apparent_power_state[{#PDU_OUTLET_ID}].last()}=6
or {Raritan PDU PX3:pdu.outlet.frequency_state[{#PDU_OUTLET_ID}].last()}=6
or {Raritan PDU PX3:pdu.outlet.power_factor_state[{#PDU_OUTLET_ID}].last()}=6
or {Raritan PDU PX3:pdu.outlet.rms_current_state[{#PDU_OUTLET_ID}].last()}=6
or {Raritan PDU PX3:pdu.outlet.rms_voltage_state[{#PDU_OUTLET_ID}].last()}=6High Critical State on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}Check individual outlet sensor state to find which sensor is reporting a problem.HIGHHigh Critical state detected from at least one sensor of the PDU outlet with the following details:
ID: {#PDU_OUTLET_ID}
Name: {#PDU_OUTLET_NAME}
Rated Voltage: {#PDU_OUTLET_RATED_VOLTAGE}
Rated Current: {#PDU_OUTLET_RATED_CURRENT}
Socket: {#PDU_OUTLET_SOCKET}
Check individual outlet sensor state to find which sensor is reporting a problem.{Raritan PDU PX3:pdu.outlet.active_power_state[{#PDU_OUTLET_ID}].last()}=5
or {Raritan PDU PX3:pdu.outlet.apparent_power_state[{#PDU_OUTLET_ID}].last()}=5
or {Raritan PDU PX3:pdu.outlet.frequency_state[{#PDU_OUTLET_ID}].last()}=5
or {Raritan PDU PX3:pdu.outlet.power_factor_state[{#PDU_OUTLET_ID}].last()}=5
or {Raritan PDU PX3:pdu.outlet.rms_current_state[{#PDU_OUTLET_ID}].last()}=5
or {Raritan PDU PX3:pdu.outlet.rms_voltage_state[{#PDU_OUTLET_ID}].last()}=5High Warning State on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}Check individual outlet sensor state to find which sensor is reporting a problem.WARNINGHigh Warning state detected from at least one sensor of the PDU outlet with the following details:
ID: {#PDU_OUTLET_ID}
Name: {#PDU_OUTLET_NAME}
Rated Voltage: {#PDU_OUTLET_RATED_VOLTAGE}
Rated Current: {#PDU_OUTLET_RATED_CURRENT}
Socket: {#PDU_OUTLET_SOCKET}
Check individual outlet sensor state to find which sensor is reporting a problem.{Raritan PDU PX3:pdu.outlet.active_power_state[{#PDU_OUTLET_ID}].last()}=2
or {Raritan PDU PX3:pdu.outlet.apparent_power_state[{#PDU_OUTLET_ID}].last()}=2
or {Raritan PDU PX3:pdu.outlet.frequency_state[{#PDU_OUTLET_ID}].last()}=2
or {Raritan PDU PX3:pdu.outlet.power_factor_state[{#PDU_OUTLET_ID}].last()}=2
or {Raritan PDU PX3:pdu.outlet.rms_current_state[{#PDU_OUTLET_ID}].last()}=2
or {Raritan PDU PX3:pdu.outlet.rms_voltage_state[{#PDU_OUTLET_ID}].last()}=2Low Critical State on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}Check individual outlet sensor state to find which sensor is reporting a problem.HIGHLow Critical state detected from at least one sensor of the PDU outlet with the following details:
ID: {#PDU_OUTLET_ID}
Name: {#PDU_OUTLET_NAME}
Rated Voltage: {#PDU_OUTLET_RATED_VOLTAGE}
Rated Current: {#PDU_OUTLET_RATED_CURRENT}
Socket: {#PDU_OUTLET_SOCKET}
Check individual outlet sensor state to find which sensor is reporting a problem.{Raritan PDU PX3:pdu.outlet.active_power_state[{#PDU_OUTLET_ID}].last()}=3
or {Raritan PDU PX3:pdu.outlet.apparent_power_state[{#PDU_OUTLET_ID}].last()}=3
or {Raritan PDU PX3:pdu.outlet.frequency_state[{#PDU_OUTLET_ID}].last()}=3
or {Raritan PDU PX3:pdu.outlet.power_factor_state[{#PDU_OUTLET_ID}].last()}=3
or {Raritan PDU PX3:pdu.outlet.rms_current_state[{#PDU_OUTLET_ID}].last()}=3
or {Raritan PDU PX3:pdu.outlet.rms_voltage_state[{#PDU_OUTLET_ID}].last()}=3Low Warning State on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}Check individual outlet sensor state to find which sensor is reporting a problem.WARNINGLow Warning state detected from at least one sensor of the PDU outlet with the following details:
ID: {#PDU_OUTLET_ID}
Name: {#PDU_OUTLET_NAME}
Rated Voltage: {#PDU_OUTLET_RATED_VOLTAGE}
Rated Current: {#PDU_OUTLET_RATED_CURRENT}
Socket: {#PDU_OUTLET_SOCKET}
Check individual outlet sensor state to find which sensor is reporting a problem.{Raritan PDU PX3:pdu.outlet.active_power_state[{#PDU_OUTLET_ID}].last()}=-1
or {Raritan PDU PX3:pdu.outlet.apparent_power_state[{#PDU_OUTLET_ID}].last()}=-1
or {Raritan PDU PX3:pdu.outlet.frequency_state[{#PDU_OUTLET_ID}].last()}=-1
or {Raritan PDU PX3:pdu.outlet.power_factor_state[{#PDU_OUTLET_ID}].last()}=-1
or {Raritan PDU PX3:pdu.outlet.rms_current_state[{#PDU_OUTLET_ID}].last()}=-1
or {Raritan PDU PX3:pdu.outlet.rms_voltage_state[{#PDU_OUTLET_ID}].last()}=-1Unavailable State on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}Check individual outlet sensor state to find which sensor is reporting a problem.INFOUnavailable state detected from at least one sensor of the PDU outlet with the following details:
ID: {#PDU_OUTLET_ID}
Name: {#PDU_OUTLET_NAME}
Rated Voltage: {#PDU_OUTLET_RATED_VOLTAGE}
Rated Current: {#PDU_OUTLET_RATED_CURRENT}
Socket: {#PDU_OUTLET_SOCKET}
Check individual outlet sensor state to find which sensor is reporting a problem.Frequency on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}1A7C11- Raritan PDU PX3pdu.outlet.frequency[{#PDU_OUTLET_ID}]
Power Factor on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}1A7C11- Raritan PDU PX3pdu.outlet.power_factor[{#PDU_OUTLET_ID}]
Power on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}1A7C11- Raritan PDU PX3pdu.outlet.active_power[{#PDU_OUTLET_ID}]
1F63100- Raritan PDU PX3pdu.outlet.apparent_power[{#PDU_OUTLET_ID}]
RMS Current on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}1A7C11- Raritan PDU PX3pdu.outlet.rms_current[{#PDU_OUTLET_ID}]
RMS Voltage on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}1A7C11- Raritan PDU PX3pdu.outlet.rms_voltage[{#PDU_OUTLET_ID}]
Over Current Protector DiscoverySNMP_AGENTdiscovery[{#PDU_PROTECTOR_LABEL},.1.3.6.1.4.1.13742.6.3.4.3.1.2.1,{#PDU_PROTECTOR_NAME},.1.3.6.1.4.1.13742.6.3.4.3.1.3.1,{#PDU_PROTECTOR_RATED_CURRENT},.1.3.6.1.4.1.13742.6.3.4.3.1.5.1]pdu.protectorRMS Current on Over Current Protector {#PDU_PROTECTOR_LABEL} - {#PDU_PROTECTOR_NAME}SNMP_AGENT.1.3.6.1.4.1.13742.6.5.3.3.1.6.1.{#SNMPINDEX}.1pdu.protector.current[{#SNMPINDEX}]FLOATARMS Current sensor from the PDU over current protector the following details:
Label: {#PDU_PROTECTOR_LABEL}
Name: {#PDU_PROTECTOR_NAME}
Rated Current: {#PDU_PROTECTOR_RATED_CURRENT}Protector CurrentMULTIPLIER0.001RMS Current State on Over Current Protector {#PDU_PROTECTOR_LABEL} - {#PDU_PROTECTOR_NAME}SNMP_AGENT.1.3.6.1.4.1.13742.6.5.3.3.1.3.1.{#SNMPINDEX}.1pdu.protector.current_state[{#SNMPINDEX}]FLOATRMS Current sensor from the PDU over current protector the following details:
Label: {#PDU_PROTECTOR_LABEL}
Name: {#PDU_PROTECTOR_NAME}
Rated Current: {#PDU_PROTECTOR_RATED_CURRENT}StateRaritan PDU State Enumeration{last()}=6High Critical State on Over Current Protector {#PDU_PROTECTOR_LABEL} - {#PDU_PROTECTOR_NAME}Check individual protector sensor state to find which sensor is reporting a problem.HIGHHigh Critical state detected from at least one sensor of the PDU over current protector the following details:
Label: {#PDU_PROTECTOR_LABEL}
Name: {#PDU_PROTECTOR_NAME}
Rated Current: {#PDU_PROTECTOR_RATED_CURRENT}
Check individual protector sensor state to find which sensor is reporting a problem.{last()}=5High Warning State on Over Current Protector {#PDU_PROTECTOR_LABEL} - {#PDU_PROTECTOR_NAME}Check individual protector sensor state to find which sensor is reporting a problem.WARNINGHigh Warning state detected from at least one sensor of the PDU over current protector the following details:
Label: {#PDU_PROTECTOR_LABEL}
Name: {#PDU_PROTECTOR_NAME}
Rated Current: {#PDU_PROTECTOR_RATED_CURRENT}
Check individual protector sensor state to find which sensor is reporting a problem.{last()}=2Low Critical State on Over Current Protector {#PDU_PROTECTOR_LABEL} - {#PDU_PROTECTOR_NAME}Check individual protector sensor state to find which sensor is reporting a problem.HIGHLow Critical state detected from at least one sensor of the PDU over current protector the following details:
Label: {#PDU_PROTECTOR_LABEL}
Name: {#PDU_PROTECTOR_NAME}
Rated Current: {#PDU_PROTECTOR_RATED_CURRENT}
Check individual protector sensor state to find which sensor is reporting a problem.{last()}=3Low Warning State on Over Current Protector {#PDU_PROTECTOR_LABEL} - {#PDU_PROTECTOR_NAME}Check individual protector sensor state to find which sensor is reporting a problem.WARNINGLow Warning state detected from at least one sensor of the PDU over current protector the following details:
Label: {#PDU_PROTECTOR_LABEL}
Name: {#PDU_PROTECTOR_NAME}
Rated Current: {#PDU_PROTECTOR_RATED_CURRENT}
Check individual protector sensor state to find which sensor is reporting a problem.{last()}=-1Unavailable State on Over Current Protector {#PDU_PROTECTOR_LABEL} - {#PDU_PROTECTOR_NAME}Check individual protector sensor state to find which sensor is reporting a problem.INFOUnavailable state detected from at least one sensor of the PDU over current protector the following details:
Label: {#PDU_PROTECTOR_LABEL}
Name: {#PDU_PROTECTOR_NAME}
Rated Current: {#PDU_PROTECTOR_RATED_CURRENT}
Check individual protector sensor state to find which sensor is reporting a problem.Trip Sensor on Over Current Protector {#PDU_PROTECTOR_LABEL} - {#PDU_PROTECTOR_NAME}SNMP_AGENT.1.3.6.1.4.1.13742.6.5.3.3.1.6.1.{#SNMPINDEX}.15pdu.protector.trip[{#SNMPINDEX}]Trip sensor from the PDU over current protector the following details:
Label: {#PDU_PROTECTOR_LABEL}
Name: {#PDU_PROTECTOR_NAME}
Rated Current: {#PDU_PROTECTOR_RATED_CURRENT}Protector TripTrip Sensor State on Over Current Protector {#PDU_PROTECTOR_LABEL} - {#PDU_PROTECTOR_NAME}SNMP_AGENT.1.3.6.1.4.1.13742.6.5.3.3.1.3.1.{#SNMPINDEX}.15pdu.protector.trip_state[{#SNMPINDEX}]FLOATTrip sensor from the PDU over current protector the following details:
Label: {#PDU_PROTECTOR_LABEL}
Name: {#PDU_PROTECTOR_NAME}
Rated Current: {#PDU_PROTECTOR_RATED_CURRENT}StateRaritan PDU State Enumeration{Raritan PDU PX3:pdu.protector.trip[{#SNMPINDEX}].last()}<>0
or {Raritan PDU PX3:pdu.protector.trip_state[{#SNMPINDEX}].last()}<>1Trip on Over Current Protector {#PDU_PROTECTOR_LABEL} - {#PDU_PROTECTOR_NAME}This Over Current Protector tripped or the sensor is broken,DISASTERTrip sensor of the PDU over current protector the following details:
Label: {#PDU_PROTECTOR_LABEL}
Name: {#PDU_PROTECTOR_NAME}
Rated Current: {#PDU_PROTECTOR_RATED_CURRENT}RMS Current State on Over Current Protector {#PDU_PROTECTOR_LABEL} - {#PDU_PROTECTOR_NAME}1A7C11- Raritan PDU PX3pdu.protector.current[{#SNMPINDEX}]
Humidity Sensor DiscoverySNMP_AGENTdiscovery[{#PDU_SENSOR_TYPE},.1.3.6.1.4.1.13742.6.3.6.3.1.2.1,{#PDU_SENSOR_SERIAL},.1.3.6.1.4.1.13742.6.3.6.3.1.3.1,{#PDU_SENSOR_NAME},.1.3.6.1.4.1.13742.6.3.6.3.1.4.1]pdu.sensor.humidity{#PDU_SENSOR_TYPE}11AHumidity SensorSNMP_AGENT.1.3.6.1.4.1.13742.6.5.5.3.1.4.1.{#SNMPINDEX}pdu.sensor.humidity.sensor[{#SNMPINDEX}]%PDU Humidity Sensor details:
Name: {#PDU_SENSOR_NAME}
Serial number: {#PDU_SENSOR_SERIAL}HumidityHumidity StateSNMP_AGENT.1.3.6.1.4.1.13742.6.5.5.3.1.3.1.{#SNMPINDEX}pdu.sensor.humidity.state[{#SNMPINDEX}]FLOATPDU Humidity State details:
Name: {#PDU_SENSOR_NAME}
Serial number: {#PDU_SENSOR_SERIAL}StateRaritan PDU State Enumeration{last()}=6High Critical State on Humidity SensorHIGHPDU Humidity State details:
Name: {#PDU_SENSOR_NAME}
Serial number: {#PDU_SENSOR_SERIAL}{last()}=5High Warning State on Humidity SensorWARNINGPDU Humidity State details:
Name: {#PDU_SENSOR_NAME}
Serial number: {#PDU_SENSOR_SERIAL}{last()}=2Low Critical State on Humidity SensorHIGHPDU Humidity State details:
Name: {#PDU_SENSOR_NAME}
Serial number: {#PDU_SENSOR_SERIAL}{last()}=3Low Warning State on Humidity SensorWARNINGPDU Humidity State details:
Name: {#PDU_SENSOR_NAME}
Serial number: {#PDU_SENSOR_SERIAL}{last()}=-1Unavailable State on Humidity SensorINFOPDU Humidity State details:
Name: {#PDU_SENSOR_NAME}
Serial number: {#PDU_SENSOR_SERIAL}Humidity ({#PDU_SENSOR_NAME})1A7C11- Raritan PDU PX3pdu.sensor.humidity.sensor[{#SNMPINDEX}]
Temperature Sensor DiscoverySNMP_AGENTdiscovery[{#PDU_SENSOR_TYPE},.1.3.6.1.4.1.13742.6.3.6.3.1.2.1,{#PDU_SENSOR_SERIAL},.1.3.6.1.4.1.13742.6.3.6.3.1.3.1,{#PDU_SENSOR_NAME},.1.3.6.1.4.1.13742.6.3.6.3.1.4.1]pdu.sensor.temperature{#PDU_SENSOR_TYPE}10ATemperature SensorSNMP_AGENT.1.3.6.1.4.1.13742.6.5.5.3.1.4.1.{#SNMPINDEX}pdu.sensor.temperature.sensor[{#SNMPINDEX}]FLOATdegrees CPDU Temperature Sensor details:
Name: {#PDU_SENSOR_NAME}
Serial number: {#PDU_SENSOR_SERIAL}TemperatureMULTIPLIER0.1Temperature StateSNMP_AGENT.1.3.6.1.4.1.13742.6.5.5.3.1.3.1.{#SNMPINDEX}pdu.sensor.temperature.state[{#SNMPINDEX}]FLOATPDU Temperature State details:
Name: {#PDU_SENSOR_NAME}
Serial number: {#PDU_SENSOR_SERIAL}StateRaritan PDU State Enumeration{last()}=6High Critical State on Temperature SensorHIGHPDU Temperature State details:
Name: {#PDU_SENSOR_NAME}
Serial number: {#PDU_SENSOR_SERIAL}{last()}=5High Warning State on Temperature SensorWARNINGPDU Temperature State details:
Name: {#PDU_SENSOR_NAME}
Serial number: {#PDU_SENSOR_SERIAL}{last()}=2Low Critical State on Temperature SensorHIGHPDU Temperature State details:
Name: {#PDU_SENSOR_NAME}
Serial number: {#PDU_SENSOR_SERIAL}{last()}=3Low Warning State on Temperature SensorWARNINGPDU Temperature State details:
Name: {#PDU_SENSOR_NAME}
Serial number: {#PDU_SENSOR_SERIAL}{last()}=-1Unavailable State on Temperature SensorINFOPDU Temperature State details:
Name: {#PDU_SENSOR_NAME}
Serial number: {#PDU_SENSOR_SERIAL}Temperature ({#PDU_SENSOR_NAME})1A7C11- Raritan PDU PX3pdu.sensor.temperature.sensor[{#SNMPINDEX}]
System DiscoverySNMP_AGENTdiscovery[{#PDU_SYSTEM_CONTACT},.1.3.6.1.2.1.1.4,{#PDU_SYSTEM_LOCATION},.1.3.6.1.2.1.1.6,{#PDU_SYSTEM_NAME},.1.3.6.1.2.1.1.5,{#PDU_SYSTEM_DESCRIPTION},.1.3.6.1.2.1.1.1]pdu.systemSystem {#PDU_SYSTEM_NAME} UptimeSNMP_AGENT.1.3.6.1.2.1.1.3.{#SNMPINDEX}pdu.system.uptime[{#SNMPINDEX}]uptimeSystem uptime of device with the following system properties:
Name: {#PDU_SYSTEM_NAME}
Location: {#PDU_SYSTEM_LOCATION}
Contact: {#PDU_SYSTEM_CONTACT}
Description: {#PDU_SYSTEM_DESCRIPTION}SystemMULTIPLIER0.01{$SNMP_COMMUNITY}e3b56dd2ad99199External Sensors2120Temperature ({#PDU_SENSOR_NAME})Raritan PDU PX3500100001100000120Humidity ({#PDU_SENSOR_NAME})Raritan PDU PX35001001011000001Inlets5120Power on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}Raritan PDU PX3200100001100000120Power Factor on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}Raritan PDU PX3200100101100000120RMS Current on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}Raritan PDU PX3200100201100000120RMS Voltage on INlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}Raritan PDU PX3200100301100000120Frequency on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}Raritan PDU PX32001004011000001Outlets5120Power on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}Raritan PDU PX3200100001100000120Power Factor on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}Raritan PDU PX3200100101100000120RMS Current on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}Raritan PDU PX3200100201100000120RMS Voltage on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}Raritan PDU PX3200100301100000120Frequency on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}Raritan PDU PX32001004011000001Protectors1120RMS Current State on Over Current Protector {#PDU_PROTECTOR_LABEL} - {#PDU_PROTECTOR_NAME}Raritan PDU PX35001000011000003Raritan PDU State Enumeration-1Unavailable0Open1Closed2BelowLowerCritical3BelowLowerWarning4Normal5AboveUpperWarning6AboveUpperCritical7On8Off9Detected10NotDetected11Alarmed12OK14Fail15Yes16No17Standby20InSync21OutOfSync26Fault27Warning28Critical29SelfTest30NonRedundant