zabbix_export: version: '5.4' date: '2021-11-21T21:57:20Z' groups: - uuid: e960332b3f6c46a1956486d4f3f99fce name: 'Templates/Server hardware' templates: - uuid: eb7e20d89272496a8b24b8f73c2f76bd template: 'Raritan PDU PX3' name: 'Raritan PDU PX3' description: | ## Description Zabbix monitoring template for Raritan PDU PX3-5466R This template was tested only on Zabbix 4.4 and PX3-5466R devices but may work on other models too. The sensor discovery is simplistic and many assumptions were made, which might require little changes to make it work on other models. The discovery rules are set to 1 minute interval and the discovered items are also set to 1 minute interval in order to allow quick tests. For real deployments you should create your own template, link this template to your own template and override the discovery intervals with values that make sense for you. For example, we use 1 day interval for the discovery rules because our power topology is pretty static and once the first discovery is done there is no need to keep discovery rules running often. The triggers are defined based on the sensor states in order to respect the thresholds defined in each PDU, and for that reason the actual PDU thresholds don't show in the graphs. ## Overview Zabbix monitoring template for Raritan PDU PX3-5466R ==================================================== This template was tested only on **Zabbix 4.4** and **PX3-5466R** devices but may work on other models too. The sensor discovery is simplistic and many assumptions were made, which might require little changes to make it work on other models. The discovery rules are set to 1 minute interval and the discovered items are also set to 1 minute interval in order to allow quick tests. **For real deployments you should create your own template, link this template to your own template and override the discovery intervals with values that make sense for you**. For example, we use 1 day interval for the discovery rules because our power topology is pretty static and once the first discovery is done there is no need to keep discovery rules running often. The triggers are defined based on the sensor states in order to respect the thresholds defined in each PDU, and for that reason the actual PDU thresholds don't show in the graphs. Suggestions and corrections are welcome, see Inspired in [https://share.zabbix.com/power-ups/legrand-inform/raritan-px-pdu](power-ups/legrand-inform/raritan-px-pdu) ## Author Tiago TT groups: - name: 'Templates/Server hardware' discovery_rules: - uuid: 69b8d2f8d6304fd1b8ca35c1062b28f4 name: 'Details Discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#PDU_DETAILS_MANUFACTURER},.1.3.6.1.4.1.13742.6.3.2.1.1.2,{#PDU_DETAILS_MODEL},.1.3.6.1.4.1.13742.6.3.2.1.1.3,{#PDU_DETAILS_SERIAL},.1.3.6.1.4.1.13742.6.3.2.1.1.4,{#PDU_DETAILS_VOLTAGE},.1.3.6.1.4.1.13742.6.3.2.1.1.5,{#PDU_DETAILS_CURRENT},.1.3.6.1.4.1.13742.6.3.2.1.1.6,{#PDU_DETAILS_FREQUENCY},.1.3.6.1.4.1.13742.6.3.2.1.1.7,{#PDU_DETAILS_POWER},.1.3.6.1.4.1.13742.6.3.2.1.1.8,{#PDU_DETAILS_DIAGRAM_URL},.1.3.6.1.4.1.13742.6.3.2.1.1.9]' key: pdu.details item_prototypes: - uuid: a5541a147ae1455083716220cc30b237 name: 'PDU {#PDU_DETAILS_MANUFACTURER} - {#PDU_DETAILS_MODEL} Serial Number' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.3.2.1.1.4.{#SNMPINDEX}' key: 'pdu.details.pdu[{#SNMPINDEX}]' delay: 1d trends: '0' value_type: TEXT description: | Serial number of the PDU with the following details: Manufacturer: {#PDU_DETAILS_MANUFACTURER} Model: {#PDU_DETAILS_MODEL} Rated Voltage: {#PDU_DETAILS_VOLTAGE} Rated Current: {#PDU_DETAILS_CURRENT} Rated Frequency: {#PDU_DETAILS_FREQUENCY} Rated Apparent Power: {#PDU_DETAILS_POWER} Diagram URL: {#PDU_DETAILS_DIAGRAM_URL} tags: - tag: Application value: System - uuid: 176064f1092f4734997e80907ea5c34f name: 'Power Inlet Discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#PDU_INLET_ID},.1.3.6.1.4.1.13742.6.3.3.3.1.2.1,{#PDU_INLET_NAME},.1.3.6.1.4.1.13742.6.3.3.3.1.3.1,{#PDU_INLET_RATED_VOLTAGE},.1.3.6.1.4.1.13742.6.3.3.3.1.6.1,{#PDU_INLET_RATED_CURRENT},.1.3.6.1.4.1.13742.6.3.3.3.1.7.1,{#PDU_INLET_SOCKET},.1.3.6.1.4.1.13742.6.3.3.3.1.12.1]' key: pdu.inlet item_prototypes: - uuid: 2a0aeedfe5d0470b902ac7ac5443f2b9 name: 'Active Power on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.2.3.1.6.1.{#SNMPINDEX}.5' key: 'pdu.inlet.active_power[{#SNMPINDEX}]' value_type: FLOAT units: W description: | Active Power sensor from the PDU inlet with the following details: ID: {#PDU_INTLET_ID} Name: {#PDU_INLET_NAME} Rated Voltage: {#PDU_INLET_RATED_VOLTAGE} Rated Current: {#PDU_INLET_RATED_CURRENT} Socket: {#PDU_INLET_SOCKET} tags: - tag: Application value: 'Inlet Power' - uuid: e80517ea4acc41e5a4cf9b07e3295c83 name: 'Active Power State on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.2.3.1.3.1.{#SNMPINDEX}.5' key: 'pdu.inlet.active_power_state[{#SNMPINDEX}]' value_type: FLOAT description: | Active Power sensor from the PDU inlet with the following details: ID: {#PDU_INTLET_ID} Name: {#PDU_INLET_NAME} Rated Voltage: {#PDU_INLET_RATED_VOLTAGE} Rated Current: {#PDU_INLET_RATED_CURRENT} Socket: {#PDU_INLET_SOCKET} valuemap: name: 'Raritan PDU State Enumeration' tags: - tag: Application value: State - uuid: 92ec55c7d2b84c77927dde709c8587f5 name: 'Apparent Power on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.2.3.1.6.1.{#SNMPINDEX}.6' key: 'pdu.inlet.apparent_power[{#SNMPINDEX}]' value_type: FLOAT units: VA description: | Apparent Power sensor from the PDU inlet with the following details: ID: {#PDU_INTLET_ID} Name: {#PDU_INLET_NAME} Rated Voltage: {#PDU_INLET_RATED_VOLTAGE} Rated Current: {#PDU_INLET_RATED_CURRENT} Socket: {#PDU_INLET_SOCKET} tags: - tag: Application value: 'Inlet Apparent Power' - uuid: d0c07c8c9f574404928d83479c6ecf50 name: 'Apparent Power State on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.2.3.1.3.1.{#SNMPINDEX}.6' key: 'pdu.inlet.apparent_power_state[{#SNMPINDEX}]' value_type: FLOAT description: | Apparent Power sensor from the PDU inlet with the following details: ID: {#PDU_INTLET_ID} Name: {#PDU_INLET_NAME} Rated Voltage: {#PDU_INLET_RATED_VOLTAGE} Rated Current: {#PDU_INLET_RATED_CURRENT} Socket: {#PDU_INLET_SOCKET} valuemap: name: 'Raritan PDU State Enumeration' tags: - tag: Application value: State - uuid: 1709b30fad9741dab411c89e9b066d65 name: 'Frequency on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.2.3.1.6.1.{#SNMPINDEX}.23' key: 'pdu.inlet.frequency[{#SNMPINDEX}]' value_type: FLOAT units: Hz description: | Frequency sensor from the PDU inlet with the following details: ID: {#PDU_INTLET_ID} Name: {#PDU_INLET_NAME} Rated Voltage: {#PDU_INLET_RATED_VOLTAGE} Rated Current: {#PDU_INLET_RATED_CURRENT} Socket: {#PDU_INLET_SOCKET} preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Application value: 'Inlet Frequency' - uuid: fa2e485e374e4a2ca13c79cf8134f689 name: 'Frequency State on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.2.3.1.3.1.{#SNMPINDEX}.23' key: 'pdu.inlet.frequency_state[{#SNMPINDEX}]' value_type: FLOAT description: | Frequency sensor from the PDU inlet with the following details: ID: {#PDU_INTLET_ID} Name: {#PDU_INLET_NAME} Rated Voltage: {#PDU_INLET_RATED_VOLTAGE} Rated Current: {#PDU_INLET_RATED_CURRENT} Socket: {#PDU_INLET_SOCKET} valuemap: name: 'Raritan PDU State Enumeration' tags: - tag: Application value: State - uuid: 66c901e1afda4edaab513293a3f0a6be name: 'Power Factor on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.2.3.1.6.1.{#SNMPINDEX}.7' key: 'pdu.inlet.power_factor[{#SNMPINDEX}]' value_type: FLOAT description: | Power Factor sensor from the PDU inlet with the following details: ID: {#PDU_INTLET_ID} Name: {#PDU_INLET_NAME} Rated Voltage: {#PDU_INLET_RATED_VOLTAGE} Rated Current: {#PDU_INLET_RATED_CURRENT} Socket: {#PDU_INLET_SOCKET} preprocessing: - type: MULTIPLIER parameters: - '0.01' tags: - tag: Application value: 'Inlet Power Factor' - uuid: a53d8416d9d6439fb1347e919cacbc14 name: 'Power Factor State on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.2.3.1.3.1.{#SNMPINDEX}.7' key: 'pdu.inlet.power_factor_state[{#SNMPINDEX}]' value_type: FLOAT description: | Power Factor sensor from the PDU inlet with the following details: ID: {#PDU_INTLET_ID} Name: {#PDU_INLET_NAME} Rated Voltage: {#PDU_INLET_RATED_VOLTAGE} Rated Current: {#PDU_INLET_RATED_CURRENT} Socket: {#PDU_INLET_SOCKET} valuemap: name: 'Raritan PDU State Enumeration' tags: - tag: Application value: State - uuid: 5c6ccb8774af4ed79241bea5917a5bc8 name: 'RMS Current on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.2.3.1.6.1.{#SNMPINDEX}.1' key: 'pdu.inlet.rms_current[{#SNMPINDEX}]' value_type: FLOAT units: A description: | RMS Current sensor from the PDU inlet with the following details: ID: {#PDU_INTLET_ID} Name: {#PDU_INLET_NAME} Rated Voltage: {#PDU_INLET_RATED_VOLTAGE} Rated Current: {#PDU_INLET_RATED_CURRENT} Socket: {#PDU_INLET_SOCKET} preprocessing: - type: MULTIPLIER parameters: - '0.001' tags: - tag: Application value: 'Inlet Current' - uuid: ca4d7e60b76d4a7ca5abc9e04d7f7fad name: 'RMS Current State on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.2.3.1.3.1.{#SNMPINDEX}.1' key: 'pdu.inlet.rms_current_state[{#SNMPINDEX}]' value_type: FLOAT description: | RMS Current sensor from the PDU inlet with the following details: ID: {#PDU_INTLET_ID} Name: {#PDU_INLET_NAME} Rated Voltage: {#PDU_INLET_RATED_VOLTAGE} Rated Current: {#PDU_INLET_RATED_CURRENT} Socket: {#PDU_INLET_SOCKET} valuemap: name: 'Raritan PDU State Enumeration' tags: - tag: Application value: State - uuid: ddf418b6bf684576804645c51f5e2725 name: 'RMS Voltage on INlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.2.3.1.6.1.{#SNMPINDEX}.4' key: 'pdu.inlet.rms_voltage[{#SNMPINDEX}]' value_type: FLOAT units: V description: | RMS Voltage sensor from the PDU inlet with the following details: ID: {#PDU_INTLET_ID} Name: {#PDU_INLET_NAME} Rated Voltage: {#PDU_INLET_RATED_VOLTAGE} Rated Current: {#PDU_INLET_RATED_CURRENT} Socket: {#PDU_INLET_SOCKET} tags: - tag: Application value: 'Inlet Voltage' - uuid: d06140ffc3e043819dfcfa7f8ca4821f name: 'RMS Voltage State on INlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.2.3.1.3.1.{#SNMPINDEX}.4' key: 'pdu.inlet.rms_voltage_state[{#SNMPINDEX}]' value_type: FLOAT description: | RMS Voltage sensor from the PDU inlet with the following details: ID: {#PDU_INTLET_ID} Name: {#PDU_INLET_NAME} Rated Voltage: {#PDU_INLET_RATED_VOLTAGE} Rated Current: {#PDU_INLET_RATED_CURRENT} Socket: {#PDU_INLET_SOCKET} valuemap: name: 'Raritan PDU State Enumeration' tags: - tag: Application value: State trigger_prototypes: - uuid: 4406a6ca4c9c453388fd44aa45e406d0 expression: 'last(/Raritan PDU PX3/pdu.inlet.active_power_state[{#SNMPINDEX}])=6 or last(/Raritan PDU PX3/pdu.inlet.apparent_power_state[{#SNMPINDEX}])=6 or last(/Raritan PDU PX3/pdu.inlet.frequency_state[{#SNMPINDEX}])=6 or last(/Raritan PDU PX3/pdu.inlet.power_factor_state[{#SNMPINDEX}])=6 or last(/Raritan PDU PX3/pdu.inlet.rms_current_state[{#SNMPINDEX}])=6 or last(/Raritan PDU PX3/pdu.inlet.rms_voltage_state[{#SNMPINDEX}])=6' name: 'High Critical State on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}' opdata: 'Check individual inlet sensor state to find which sensor is reporting a problem.' priority: HIGH description: | High Critical state detected from at least one sensor of the PDU inlet with the following details: ID: {#PDU_INTLET_ID} Name: {#PDU_INLET_NAME} Rated Voltage: {#PDU_INLET_RATED_VOLTAGE} Rated Current: {#PDU_INLET_RATED_CURRENT} Socket: {#PDU_INLET_SOCKET} Check individual inlet sensor state to find which sensor is reporting a problem. - uuid: 57aa6b4fe88b4f80baf376247d0f6d08 expression: 'last(/Raritan PDU PX3/pdu.inlet.active_power_state[{#SNMPINDEX}])=5 or last(/Raritan PDU PX3/pdu.inlet.apparent_power_state[{#SNMPINDEX}])=5 or last(/Raritan PDU PX3/pdu.inlet.frequency_state[{#SNMPINDEX}])=5 or last(/Raritan PDU PX3/pdu.inlet.power_factor_state[{#SNMPINDEX}])=5 or last(/Raritan PDU PX3/pdu.inlet.rms_current_state[{#SNMPINDEX}])=5 or last(/Raritan PDU PX3/pdu.inlet.rms_voltage_state[{#SNMPINDEX}])=5' name: 'High Warning State on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}' opdata: 'Check individual inlet sensor state to find which sensor is reporting a problem.' priority: WARNING description: | High Warning state detected from at least one sensor of the PDU inlet with the following details: ID: {#PDU_INTLET_ID} Name: {#PDU_INLET_NAME} Rated Voltage: {#PDU_INLET_RATED_VOLTAGE} Rated Current: {#PDU_INLET_RATED_CURRENT} Socket: {#PDU_INLET_SOCKET} Check individual inlet sensor state to find which sensor is reporting a problem. - uuid: 8330591425084b15a069212e31578834 expression: 'last(/Raritan PDU PX3/pdu.inlet.active_power_state[{#SNMPINDEX}])=2 or last(/Raritan PDU PX3/pdu.inlet.apparent_power_state[{#SNMPINDEX}])=2 or last(/Raritan PDU PX3/pdu.inlet.frequency_state[{#SNMPINDEX}])=2 or last(/Raritan PDU PX3/pdu.inlet.power_factor_state[{#SNMPINDEX}])=2 or last(/Raritan PDU PX3/pdu.inlet.rms_current_state[{#SNMPINDEX}])=2 or last(/Raritan PDU PX3/pdu.inlet.rms_voltage_state[{#SNMPINDEX}])=2' name: 'Low Critical State on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}' opdata: 'Check individual inlet sensor state to find which sensor is reporting a problem.' priority: HIGH description: | Low Critical state detected from at least one sensor of the PDU inlet with the following details: ID: {#PDU_INTLET_ID} Name: {#PDU_INLET_NAME} Rated Voltage: {#PDU_INLET_RATED_VOLTAGE} Rated Current: {#PDU_INLET_RATED_CURRENT} Socket: {#PDU_INLET_SOCKET} Check individual inlet sensor state to find which sensor is reporting a problem. - uuid: ac3cd5cd0f754407983a8fadfe916338 expression: 'last(/Raritan PDU PX3/pdu.inlet.active_power_state[{#SNMPINDEX}])=3 or last(/Raritan PDU PX3/pdu.inlet.apparent_power_state[{#SNMPINDEX}])=3 or last(/Raritan PDU PX3/pdu.inlet.frequency_state[{#SNMPINDEX}])=3 or last(/Raritan PDU PX3/pdu.inlet.power_factor_state[{#SNMPINDEX}])=3 or last(/Raritan PDU PX3/pdu.inlet.rms_current_state[{#SNMPINDEX}])=3 or last(/Raritan PDU PX3/pdu.inlet.rms_voltage_state[{#SNMPINDEX}])=3' name: 'Low Warning State on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}' opdata: 'Check individual inlet sensor state to find which sensor is reporting a problem.' priority: WARNING description: | Low Warning state detected from at least one sensor of the PDU inlet with the following details: ID: {#PDU_INTLET_ID} Name: {#PDU_INLET_NAME} Rated Voltage: {#PDU_INLET_RATED_VOLTAGE} Rated Current: {#PDU_INLET_RATED_CURRENT} Socket: {#PDU_INLET_SOCKET} Check individual inlet sensor state to find which sensor is reporting a problem. - uuid: fefed5dc619444739b72d9d866a34f31 expression: 'last(/Raritan PDU PX3/pdu.inlet.active_power_state[{#SNMPINDEX}])=-1 or last(/Raritan PDU PX3/pdu.inlet.apparent_power_state[{#SNMPINDEX}])=-1 or last(/Raritan PDU PX3/pdu.inlet.frequency_state[{#SNMPINDEX}])=-1 or last(/Raritan PDU PX3/pdu.inlet.power_factor_state[{#SNMPINDEX}])=-1 or last(/Raritan PDU PX3/pdu.inlet.rms_current_state[{#SNMPINDEX}])=-1 or last(/Raritan PDU PX3/pdu.inlet.rms_voltage_state[{#SNMPINDEX}])=-1' name: 'Unavailable State on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}' opdata: 'Check individual inlet sensor state to find which sensor is reporting a problem.' priority: INFO description: | Unavailable state detected from at least one sensor of the PDU inlet with the following details: ID: {#PDU_INTLET_ID} Name: {#PDU_INLET_NAME} Rated Voltage: {#PDU_INLET_RATED_VOLTAGE} Rated Current: {#PDU_INLET_RATED_CURRENT} Socket: {#PDU_INLET_SOCKET} Check individual inlet sensor state to find which sensor is reporting a problem. graph_prototypes: - uuid: 6a9480ecedbd4a98bf3e39942cb8a709 name: 'Frequency on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}' graph_items: - color: 1A7C11 item: host: 'Raritan PDU PX3' key: 'pdu.inlet.frequency[{#SNMPINDEX}]' - uuid: 4372518b9c294714bfda2209158ad14a name: 'Power Factor on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}' graph_items: - color: 1A7C11 item: host: 'Raritan PDU PX3' key: 'pdu.inlet.power_factor[{#SNMPINDEX}]' - uuid: cb51226062fe4ad0abd0b9d23dee9df3 name: 'Power on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}' graph_items: - color: 1A7C11 item: host: 'Raritan PDU PX3' key: 'pdu.inlet.active_power[{#SNMPINDEX}]' - sortorder: '1' color: F63100 item: host: 'Raritan PDU PX3' key: 'pdu.inlet.apparent_power[{#SNMPINDEX}]' - uuid: e5b970f751b64ecead25f0ba7639e746 name: 'RMS Current on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}' graph_items: - color: 1A7C11 item: host: 'Raritan PDU PX3' key: 'pdu.inlet.rms_current[{#SNMPINDEX}]' - uuid: 50ad3da6023d430eb943a510b7d6912c name: 'RMS Voltage on INlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}' graph_items: - color: 1A7C11 item: host: 'Raritan PDU PX3' key: 'pdu.inlet.rms_voltage[{#SNMPINDEX}]' - uuid: e54f473887014ba5ab1d717d418fb606 name: 'Power Outlet Discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#PDU_OUTLET_ID},.1.3.6.1.4.1.13742.6.3.5.3.1.2.1,{#PDU_OUTLET_NAME},.1.3.6.1.4.1.13742.6.3.5.3.1.3.1,{#PDU_OUTLET_RATED_VOLTAGE},.1.3.6.1.4.1.13742.6.3.5.3.1.6.1,{#PDU_OUTLET_RATED_CURRENT},.1.3.6.1.4.1.13742.6.3.5.3.1.7.1,{#PDU_OUTLET_SOCKET},.1.3.6.1.4.1.13742.6.3.5.3.1.29.1]' key: pdu.outlet item_prototypes: - uuid: c7dd1c850a324558bf14a9ebcaead744 name: 'Active Power on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.4.3.1.6.1.{#PDU_OUTLET_ID}.5' key: 'pdu.outlet.active_power[{#PDU_OUTLET_ID}]' value_type: FLOAT units: W description: | Active Power sensor from the PDU outlet with the following details: ID: {#PDU_OUTLET_ID} Name: {#PDU_OUTLET_NAME} Rated Voltage: {#PDU_OUTLET_RATED_VOLTAGE} Rated Current: {#PDU_OUTLET_RATED_CURRENT} Socket: {#PDU_OUTLET_SOCKET} tags: - tag: Application value: 'Outlet Power' - uuid: d321e14afb094b5eb086a8a0e75c32c8 name: 'Active Power State on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.4.3.1.3.1.{#PDU_OUTLET_ID}.5' key: 'pdu.outlet.active_power_state[{#PDU_OUTLET_ID}]' value_type: FLOAT description: | Active Power sensor from the PDU outlet with the following details: ID: {#PDU_OUTLET_ID} Name: {#PDU_OUTLET_NAME} Rated Voltage: {#PDU_OUTLET_RATED_VOLTAGE} Rated Current: {#PDU_OUTLET_RATED_CURRENT} Socket: {#PDU_OUTLET_SOCKET} valuemap: name: 'Raritan PDU State Enumeration' tags: - tag: Application value: State - uuid: cffd2083766d4b0aac14583064869269 name: 'Apparent Power on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.4.3.1.6.1.{#PDU_OUTLET_ID}.6' key: 'pdu.outlet.apparent_power[{#PDU_OUTLET_ID}]' value_type: FLOAT units: VA description: | Apparent Power sensor from the PDU outlet with the following details: ID: {#PDU_OUTLET_ID} Name: {#PDU_OUTLET_NAME} Rated Voltage: {#PDU_OUTLET_RATED_VOLTAGE} Rated Current: {#PDU_OUTLET_RATED_CURRENT} Socket: {#PDU_OUTLET_SOCKET} tags: - tag: Application value: 'Outlet Apparent Power' - uuid: 6d7c419763184d9391207e0b4cb929f3 name: 'Apparent Power State on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.4.3.1.3.1.{#PDU_OUTLET_ID}.6' key: 'pdu.outlet.apparent_power_state[{#PDU_OUTLET_ID}]' value_type: FLOAT description: | Apparent Power sensor from the PDU outlet with the following details: ID: {#PDU_OUTLET_ID} Name: {#PDU_OUTLET_NAME} Rated Voltage: {#PDU_OUTLET_RATED_VOLTAGE} Rated Current: {#PDU_OUTLET_RATED_CURRENT} Socket: {#PDU_OUTLET_SOCKET} valuemap: name: 'Raritan PDU State Enumeration' tags: - tag: Application value: State - uuid: 3ac0092010e34ffd98c9cb5d1947e6fc name: 'Frequency on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.4.3.1.6.1.{#PDU_OUTLET_ID}.23' key: 'pdu.outlet.frequency[{#PDU_OUTLET_ID}]' value_type: FLOAT units: Hz description: | Frequency sensor from the PDU outlet with the following details: ID: {#PDU_OUTLET_ID} Name: {#PDU_OUTLET_NAME} Rated Voltage: {#PDU_OUTLET_RATED_VOLTAGE} Rated Current: {#PDU_OUTLET_RATED_CURRENT} Socket: {#PDU_OUTLET_SOCKET} preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Application value: 'Outlet Frequency' - uuid: c92b6d0d495f45a7a4388578e92dd620 name: 'Frequency State on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.4.3.1.3.1.{#PDU_OUTLET_ID}.23' key: 'pdu.outlet.frequency_state[{#PDU_OUTLET_ID}]' value_type: FLOAT description: | Frequency sensor from the PDU outlet with the following details: ID: {#PDU_OUTLET_ID} Name: {#PDU_OUTLET_NAME} Rated Voltage: {#PDU_OUTLET_RATED_VOLTAGE} Rated Current: {#PDU_OUTLET_RATED_CURRENT} Socket: {#PDU_OUTLET_SOCKET} valuemap: name: 'Raritan PDU State Enumeration' tags: - tag: Application value: State - uuid: c941864fdd824d3dbcce0cf9271e71f2 name: 'Power Factor on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.4.3.1.6.1.{#PDU_OUTLET_ID}.7' key: 'pdu.outlet.power_factor[{#PDU_OUTLET_ID}]' value_type: FLOAT description: | Power Factor sensor from the PDU outlet with the following details: ID: {#PDU_OUTLET_ID} Name: {#PDU_OUTLET_NAME} Rated Voltage: {#PDU_OUTLET_RATED_VOLTAGE} Rated Current: {#PDU_OUTLET_RATED_CURRENT} Socket: {#PDU_OUTLET_SOCKET} preprocessing: - type: MULTIPLIER parameters: - '0.01' tags: - tag: Application value: 'Outlet Power Factor' - uuid: 0115082ca8384e5d9f6b2bf928cb0707 name: 'Power Factor State on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.4.3.1.3.1.{#PDU_OUTLET_ID}.7' key: 'pdu.outlet.power_factor_state[{#PDU_OUTLET_ID}]' value_type: FLOAT description: | Power Factor sensor from the PDU outlet with the following details: ID: {#PDU_OUTLET_ID} Name: {#PDU_OUTLET_NAME} Rated Voltage: {#PDU_OUTLET_RATED_VOLTAGE} Rated Current: {#PDU_OUTLET_RATED_CURRENT} Socket: {#PDU_OUTLET_SOCKET} valuemap: name: 'Raritan PDU State Enumeration' tags: - tag: Application value: State - uuid: fecdacfe5fd44738af57bf3abbf5fd9f name: 'RMS Current on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.4.3.1.6.1.{#PDU_OUTLET_ID}.1' key: 'pdu.outlet.rms_current[{#PDU_OUTLET_ID}]' value_type: FLOAT units: A description: | RMS Current sensor from the PDU outlet with the following details: ID: {#PDU_OUTLET_ID} Name: {#PDU_OUTLET_NAME} Rated Voltage: {#PDU_OUTLET_RATED_VOLTAGE} Rated Current: {#PDU_OUTLET_RATED_CURRENT} Socket: {#PDU_OUTLET_SOCKET} preprocessing: - type: MULTIPLIER parameters: - '0.001' tags: - tag: Application value: 'Outlet Current' - uuid: aade315b2dca4aa79a137718dc56b2c6 name: 'RMS Current State on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.4.3.1.3.1.{#PDU_OUTLET_ID}.1' key: 'pdu.outlet.rms_current_state[{#PDU_OUTLET_ID}]' value_type: FLOAT description: | RMS Current sensor from the PDU outlet with the following details: ID: {#PDU_OUTLET_ID} Name: {#PDU_OUTLET_NAME} Rated Voltage: {#PDU_OUTLET_RATED_VOLTAGE} Rated Current: {#PDU_OUTLET_RATED_CURRENT} Socket: {#PDU_OUTLET_SOCKET} valuemap: name: 'Raritan PDU State Enumeration' tags: - tag: Application value: State - uuid: 67e5b14f90fd46c783d14884f77623e3 name: 'RMS Voltage on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.4.3.1.6.1.{#PDU_OUTLET_ID}.4' key: 'pdu.outlet.rms_voltage[{#PDU_OUTLET_ID}]' value_type: FLOAT units: V description: | RMS Voltage sensor from the PDU outlet with the following details: ID: {#PDU_OUTLET_ID} Name: {#PDU_OUTLET_NAME} Rated Voltage: {#PDU_OUTLET_RATED_VOLTAGE} Rated Current: {#PDU_OUTLET_RATED_CURRENT} Socket: {#PDU_OUTLET_SOCKET} tags: - tag: Application value: 'Outlet Voltage' - uuid: 33e57c57e3894a239986665b22426295 name: 'RMS Voltage State on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.4.3.1.3.1.{#PDU_OUTLET_ID}.4' key: 'pdu.outlet.rms_voltage_state[{#PDU_OUTLET_ID}]' value_type: FLOAT description: | RMS Voltage sensor from the PDU outlet with the following details: ID: {#PDU_OUTLET_ID} Name: {#PDU_OUTLET_NAME} Rated Voltage: {#PDU_OUTLET_RATED_VOLTAGE} Rated Current: {#PDU_OUTLET_RATED_CURRENT} Socket: {#PDU_OUTLET_SOCKET} valuemap: name: 'Raritan PDU State Enumeration' trigger_prototypes: - uuid: bff7bdfaf5414c6eb421b1b721ea02a9 expression: | last(/Raritan PDU PX3/pdu.outlet.active_power_state[{#PDU_OUTLET_ID}])=6 or last(/Raritan PDU PX3/pdu.outlet.apparent_power_state[{#PDU_OUTLET_ID}])=6 or last(/Raritan PDU PX3/pdu.outlet.frequency_state[{#PDU_OUTLET_ID}])=6 or last(/Raritan PDU PX3/pdu.outlet.power_factor_state[{#PDU_OUTLET_ID}])=6 or last(/Raritan PDU PX3/pdu.outlet.rms_current_state[{#PDU_OUTLET_ID}])=6 or last(/Raritan PDU PX3/pdu.outlet.rms_voltage_state[{#PDU_OUTLET_ID}])=6 name: 'High Critical State on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}' opdata: 'Check individual outlet sensor state to find which sensor is reporting a problem.' priority: HIGH description: | High Critical state detected from at least one sensor of the PDU outlet with the following details: ID: {#PDU_OUTLET_ID} Name: {#PDU_OUTLET_NAME} Rated Voltage: {#PDU_OUTLET_RATED_VOLTAGE} Rated Current: {#PDU_OUTLET_RATED_CURRENT} Socket: {#PDU_OUTLET_SOCKET} Check individual outlet sensor state to find which sensor is reporting a problem. - uuid: fcc0020857b94093b4b84ede21dc6cfa expression: | last(/Raritan PDU PX3/pdu.outlet.active_power_state[{#PDU_OUTLET_ID}])=5 or last(/Raritan PDU PX3/pdu.outlet.apparent_power_state[{#PDU_OUTLET_ID}])=5 or last(/Raritan PDU PX3/pdu.outlet.frequency_state[{#PDU_OUTLET_ID}])=5 or last(/Raritan PDU PX3/pdu.outlet.power_factor_state[{#PDU_OUTLET_ID}])=5 or last(/Raritan PDU PX3/pdu.outlet.rms_current_state[{#PDU_OUTLET_ID}])=5 or last(/Raritan PDU PX3/pdu.outlet.rms_voltage_state[{#PDU_OUTLET_ID}])=5 name: 'High Warning State on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}' opdata: 'Check individual outlet sensor state to find which sensor is reporting a problem.' priority: WARNING description: | High Warning state detected from at least one sensor of the PDU outlet with the following details: ID: {#PDU_OUTLET_ID} Name: {#PDU_OUTLET_NAME} Rated Voltage: {#PDU_OUTLET_RATED_VOLTAGE} Rated Current: {#PDU_OUTLET_RATED_CURRENT} Socket: {#PDU_OUTLET_SOCKET} Check individual outlet sensor state to find which sensor is reporting a problem. - uuid: 0c65f6eda3ec47dfab2dea9338ae8f9e expression: | last(/Raritan PDU PX3/pdu.outlet.active_power_state[{#PDU_OUTLET_ID}])=2 or last(/Raritan PDU PX3/pdu.outlet.apparent_power_state[{#PDU_OUTLET_ID}])=2 or last(/Raritan PDU PX3/pdu.outlet.frequency_state[{#PDU_OUTLET_ID}])=2 or last(/Raritan PDU PX3/pdu.outlet.power_factor_state[{#PDU_OUTLET_ID}])=2 or last(/Raritan PDU PX3/pdu.outlet.rms_current_state[{#PDU_OUTLET_ID}])=2 or last(/Raritan PDU PX3/pdu.outlet.rms_voltage_state[{#PDU_OUTLET_ID}])=2 name: 'Low Critical State on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}' opdata: 'Check individual outlet sensor state to find which sensor is reporting a problem.' priority: HIGH description: | Low Critical state detected from at least one sensor of the PDU outlet with the following details: ID: {#PDU_OUTLET_ID} Name: {#PDU_OUTLET_NAME} Rated Voltage: {#PDU_OUTLET_RATED_VOLTAGE} Rated Current: {#PDU_OUTLET_RATED_CURRENT} Socket: {#PDU_OUTLET_SOCKET} Check individual outlet sensor state to find which sensor is reporting a problem. - uuid: 01bf149396284742851105fe789a461f expression: | last(/Raritan PDU PX3/pdu.outlet.active_power_state[{#PDU_OUTLET_ID}])=3 or last(/Raritan PDU PX3/pdu.outlet.apparent_power_state[{#PDU_OUTLET_ID}])=3 or last(/Raritan PDU PX3/pdu.outlet.frequency_state[{#PDU_OUTLET_ID}])=3 or last(/Raritan PDU PX3/pdu.outlet.power_factor_state[{#PDU_OUTLET_ID}])=3 or last(/Raritan PDU PX3/pdu.outlet.rms_current_state[{#PDU_OUTLET_ID}])=3 or last(/Raritan PDU PX3/pdu.outlet.rms_voltage_state[{#PDU_OUTLET_ID}])=3 name: 'Low Warning State on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}' opdata: 'Check individual outlet sensor state to find which sensor is reporting a problem.' priority: WARNING description: | Low Warning state detected from at least one sensor of the PDU outlet with the following details: ID: {#PDU_OUTLET_ID} Name: {#PDU_OUTLET_NAME} Rated Voltage: {#PDU_OUTLET_RATED_VOLTAGE} Rated Current: {#PDU_OUTLET_RATED_CURRENT} Socket: {#PDU_OUTLET_SOCKET} Check individual outlet sensor state to find which sensor is reporting a problem. - uuid: 08a71e5d64424bb8bf2e0594aa74ea4a expression: | last(/Raritan PDU PX3/pdu.outlet.active_power_state[{#PDU_OUTLET_ID}])=-1 or last(/Raritan PDU PX3/pdu.outlet.apparent_power_state[{#PDU_OUTLET_ID}])=-1 or last(/Raritan PDU PX3/pdu.outlet.frequency_state[{#PDU_OUTLET_ID}])=-1 or last(/Raritan PDU PX3/pdu.outlet.power_factor_state[{#PDU_OUTLET_ID}])=-1 or last(/Raritan PDU PX3/pdu.outlet.rms_current_state[{#PDU_OUTLET_ID}])=-1 or last(/Raritan PDU PX3/pdu.outlet.rms_voltage_state[{#PDU_OUTLET_ID}])=-1 name: 'Unavailable State on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}' opdata: 'Check individual outlet sensor state to find which sensor is reporting a problem.' priority: INFO description: | Unavailable state detected from at least one sensor of the PDU outlet with the following details: ID: {#PDU_OUTLET_ID} Name: {#PDU_OUTLET_NAME} Rated Voltage: {#PDU_OUTLET_RATED_VOLTAGE} Rated Current: {#PDU_OUTLET_RATED_CURRENT} Socket: {#PDU_OUTLET_SOCKET} Check individual outlet sensor state to find which sensor is reporting a problem. graph_prototypes: - uuid: 5735ab2e7fa94b5c9f8e5c9cd5892969 name: 'Frequency on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}' graph_items: - color: 1A7C11 item: host: 'Raritan PDU PX3' key: 'pdu.outlet.frequency[{#PDU_OUTLET_ID}]' - uuid: 65db8cc006914b59b5bc6399efde4a83 name: 'Power Factor on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}' graph_items: - color: 1A7C11 item: host: 'Raritan PDU PX3' key: 'pdu.outlet.power_factor[{#PDU_OUTLET_ID}]' - uuid: 566806b257e449138422b11b214d7efa name: 'Power on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}' graph_items: - color: 1A7C11 item: host: 'Raritan PDU PX3' key: 'pdu.outlet.active_power[{#PDU_OUTLET_ID}]' - sortorder: '1' color: F63100 item: host: 'Raritan PDU PX3' key: 'pdu.outlet.apparent_power[{#PDU_OUTLET_ID}]' - uuid: 75b65580a7ce47f9bc8555adeef78045 name: 'RMS Current on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}' graph_items: - color: 1A7C11 item: host: 'Raritan PDU PX3' key: 'pdu.outlet.rms_current[{#PDU_OUTLET_ID}]' - uuid: dda8a48e345e4490ac974272a5b1066c name: 'RMS Voltage on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}' graph_items: - color: 1A7C11 item: host: 'Raritan PDU PX3' key: 'pdu.outlet.rms_voltage[{#PDU_OUTLET_ID}]' - uuid: dd6056d9e550463a82243f1d07216b34 name: 'Over Current Protector Discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#PDU_PROTECTOR_LABEL},.1.3.6.1.4.1.13742.6.3.4.3.1.2.1,{#PDU_PROTECTOR_NAME},.1.3.6.1.4.1.13742.6.3.4.3.1.3.1,{#PDU_PROTECTOR_RATED_CURRENT},.1.3.6.1.4.1.13742.6.3.4.3.1.5.1]' key: pdu.protector item_prototypes: - uuid: 941fab3a446248129c6feca1e7b3f9af name: 'RMS Current on Over Current Protector {#PDU_PROTECTOR_LABEL} - {#PDU_PROTECTOR_NAME}' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.3.3.1.6.1.{#SNMPINDEX}.1' key: 'pdu.protector.current[{#SNMPINDEX}]' value_type: FLOAT units: A description: | RMS Current sensor from the PDU over current protector the following details: Label: {#PDU_PROTECTOR_LABEL} Name: {#PDU_PROTECTOR_NAME} Rated Current: {#PDU_PROTECTOR_RATED_CURRENT} preprocessing: - type: MULTIPLIER parameters: - '0.001' tags: - tag: Application value: 'Protector Current' - uuid: c32a3855d6bd496692a42047bbc484ec name: 'RMS Current State on Over Current Protector {#PDU_PROTECTOR_LABEL} - {#PDU_PROTECTOR_NAME}' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.3.3.1.3.1.{#SNMPINDEX}.1' key: 'pdu.protector.current_state[{#SNMPINDEX}]' value_type: FLOAT description: | RMS Current sensor from the PDU over current protector the following details: Label: {#PDU_PROTECTOR_LABEL} Name: {#PDU_PROTECTOR_NAME} Rated Current: {#PDU_PROTECTOR_RATED_CURRENT} valuemap: name: 'Raritan PDU State Enumeration' tags: - tag: Application value: State trigger_prototypes: - uuid: 9f55b952eff54a6a9016c370d46e0a11 expression: 'last(/Raritan PDU PX3/pdu.protector.current_state[{#SNMPINDEX}])=6' name: 'High Critical State on Over Current Protector {#PDU_PROTECTOR_LABEL} - {#PDU_PROTECTOR_NAME}' opdata: 'Check individual protector sensor state to find which sensor is reporting a problem.' priority: HIGH description: | High Critical state detected from at least one sensor of the PDU over current protector the following details: Label: {#PDU_PROTECTOR_LABEL} Name: {#PDU_PROTECTOR_NAME} Rated Current: {#PDU_PROTECTOR_RATED_CURRENT} Check individual protector sensor state to find which sensor is reporting a problem. - uuid: fa143c74c3c647cb8e706b94521e73c3 expression: 'last(/Raritan PDU PX3/pdu.protector.current_state[{#SNMPINDEX}])=5' name: 'High Warning State on Over Current Protector {#PDU_PROTECTOR_LABEL} - {#PDU_PROTECTOR_NAME}' opdata: 'Check individual protector sensor state to find which sensor is reporting a problem.' priority: WARNING description: | High Warning state detected from at least one sensor of the PDU over current protector the following details: Label: {#PDU_PROTECTOR_LABEL} Name: {#PDU_PROTECTOR_NAME} Rated Current: {#PDU_PROTECTOR_RATED_CURRENT} Check individual protector sensor state to find which sensor is reporting a problem. - uuid: 861bac8c536c4049a739bbe06f79cf2f expression: 'last(/Raritan PDU PX3/pdu.protector.current_state[{#SNMPINDEX}])=2' name: 'Low Critical State on Over Current Protector {#PDU_PROTECTOR_LABEL} - {#PDU_PROTECTOR_NAME}' opdata: 'Check individual protector sensor state to find which sensor is reporting a problem.' priority: HIGH description: | Low Critical state detected from at least one sensor of the PDU over current protector the following details: Label: {#PDU_PROTECTOR_LABEL} Name: {#PDU_PROTECTOR_NAME} Rated Current: {#PDU_PROTECTOR_RATED_CURRENT} Check individual protector sensor state to find which sensor is reporting a problem. - uuid: 377f80e57be64805b97b47392172dd7f expression: 'last(/Raritan PDU PX3/pdu.protector.current_state[{#SNMPINDEX}])=3' name: 'Low Warning State on Over Current Protector {#PDU_PROTECTOR_LABEL} - {#PDU_PROTECTOR_NAME}' opdata: 'Check individual protector sensor state to find which sensor is reporting a problem.' priority: WARNING description: | Low Warning state detected from at least one sensor of the PDU over current protector the following details: Label: {#PDU_PROTECTOR_LABEL} Name: {#PDU_PROTECTOR_NAME} Rated Current: {#PDU_PROTECTOR_RATED_CURRENT} Check individual protector sensor state to find which sensor is reporting a problem. - uuid: 7c876e682bea4920a4b5d5f1be7dccee expression: 'last(/Raritan PDU PX3/pdu.protector.current_state[{#SNMPINDEX}])=-1' name: 'Unavailable State on Over Current Protector {#PDU_PROTECTOR_LABEL} - {#PDU_PROTECTOR_NAME}' opdata: 'Check individual protector sensor state to find which sensor is reporting a problem.' priority: INFO description: | Unavailable state detected from at least one sensor of the PDU over current protector the following details: Label: {#PDU_PROTECTOR_LABEL} Name: {#PDU_PROTECTOR_NAME} Rated Current: {#PDU_PROTECTOR_RATED_CURRENT} Check individual protector sensor state to find which sensor is reporting a problem. - uuid: ed394792c56542d0aaab52c04508d53d name: 'Trip Sensor on Over Current Protector {#PDU_PROTECTOR_LABEL} - {#PDU_PROTECTOR_NAME}' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.3.3.1.6.1.{#SNMPINDEX}.15' key: 'pdu.protector.trip[{#SNMPINDEX}]' description: | Trip sensor from the PDU over current protector the following details: Label: {#PDU_PROTECTOR_LABEL} Name: {#PDU_PROTECTOR_NAME} Rated Current: {#PDU_PROTECTOR_RATED_CURRENT} tags: - tag: Application value: 'Protector Trip' - uuid: 727001d35d6c4b3bb9b34552a1346877 name: 'Trip Sensor State on Over Current Protector {#PDU_PROTECTOR_LABEL} - {#PDU_PROTECTOR_NAME}' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.3.3.1.3.1.{#SNMPINDEX}.15' key: 'pdu.protector.trip_state[{#SNMPINDEX}]' value_type: FLOAT description: | Trip sensor from the PDU over current protector the following details: Label: {#PDU_PROTECTOR_LABEL} Name: {#PDU_PROTECTOR_NAME} Rated Current: {#PDU_PROTECTOR_RATED_CURRENT} valuemap: name: 'Raritan PDU State Enumeration' tags: - tag: Application value: State trigger_prototypes: - uuid: de35571978e04318a3fc65c15c316e1d expression: | last(/Raritan PDU PX3/pdu.protector.trip[{#SNMPINDEX}])<>0 or last(/Raritan PDU PX3/pdu.protector.trip_state[{#SNMPINDEX}])<>1 name: 'Trip on Over Current Protector {#PDU_PROTECTOR_LABEL} - {#PDU_PROTECTOR_NAME}' opdata: 'This Over Current Protector tripped or the sensor is broken,' priority: DISASTER description: | Trip sensor of the PDU over current protector the following details: Label: {#PDU_PROTECTOR_LABEL} Name: {#PDU_PROTECTOR_NAME} Rated Current: {#PDU_PROTECTOR_RATED_CURRENT} graph_prototypes: - uuid: 1e8ab6279fce4a8d87cba81fea62287b name: 'RMS Current State on Over Current Protector {#PDU_PROTECTOR_LABEL} - {#PDU_PROTECTOR_NAME}' graph_items: - color: 1A7C11 item: host: 'Raritan PDU PX3' key: 'pdu.protector.current[{#SNMPINDEX}]' - uuid: c5918ff5e9714ed9a3ef1fa1f1198e4c name: 'Humidity Sensor Discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#PDU_SENSOR_TYPE},.1.3.6.1.4.1.13742.6.3.6.3.1.2.1,{#PDU_SENSOR_SERIAL},.1.3.6.1.4.1.13742.6.3.6.3.1.3.1,{#PDU_SENSOR_NAME},.1.3.6.1.4.1.13742.6.3.6.3.1.4.1]' key: pdu.sensor.humidity filter: conditions: - macro: '{#PDU_SENSOR_TYPE}' value: '11' formulaid: A item_prototypes: - uuid: a92a9a665cc444d89b23988f55c36b54 name: 'Humidity Sensor' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.5.3.1.4.1.{#SNMPINDEX}' key: 'pdu.sensor.humidity.sensor[{#SNMPINDEX}]' units: '%' description: | PDU Humidity Sensor details: Name: {#PDU_SENSOR_NAME} Serial number: {#PDU_SENSOR_SERIAL} tags: - tag: Application value: Humidity - uuid: d39ab501d4744c288462fcbb648f489e name: 'Humidity State' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.5.3.1.3.1.{#SNMPINDEX}' key: 'pdu.sensor.humidity.state[{#SNMPINDEX}]' value_type: FLOAT description: | PDU Humidity State details: Name: {#PDU_SENSOR_NAME} Serial number: {#PDU_SENSOR_SERIAL} valuemap: name: 'Raritan PDU State Enumeration' tags: - tag: Application value: State trigger_prototypes: - uuid: 1728425353074021a6fa4fc9e952bdba expression: 'last(/Raritan PDU PX3/pdu.sensor.humidity.state[{#SNMPINDEX}])=6' name: 'High Critical State on Humidity Sensor' priority: HIGH description: | PDU Humidity State details: Name: {#PDU_SENSOR_NAME} Serial number: {#PDU_SENSOR_SERIAL} - uuid: 7657fbcb73d2493cbe1305aada291024 expression: 'last(/Raritan PDU PX3/pdu.sensor.humidity.state[{#SNMPINDEX}])=5' name: 'High Warning State on Humidity Sensor' priority: WARNING description: | PDU Humidity State details: Name: {#PDU_SENSOR_NAME} Serial number: {#PDU_SENSOR_SERIAL} - uuid: e1e0d99c39954c17a2f4593c0c92f789 expression: 'last(/Raritan PDU PX3/pdu.sensor.humidity.state[{#SNMPINDEX}])=2' name: 'Low Critical State on Humidity Sensor' priority: HIGH description: | PDU Humidity State details: Name: {#PDU_SENSOR_NAME} Serial number: {#PDU_SENSOR_SERIAL} - uuid: 6f17630e30264a3792753aea5be1bd98 expression: 'last(/Raritan PDU PX3/pdu.sensor.humidity.state[{#SNMPINDEX}])=3' name: 'Low Warning State on Humidity Sensor' priority: WARNING description: | PDU Humidity State details: Name: {#PDU_SENSOR_NAME} Serial number: {#PDU_SENSOR_SERIAL} - uuid: f4efa1199b644dbe93cc8f761a0f0a29 expression: 'last(/Raritan PDU PX3/pdu.sensor.humidity.state[{#SNMPINDEX}])=-1' name: 'Unavailable State on Humidity Sensor' priority: INFO description: | PDU Humidity State details: Name: {#PDU_SENSOR_NAME} Serial number: {#PDU_SENSOR_SERIAL} graph_prototypes: - uuid: 8e4f0a6fe53d41ad9c76dc0a48a4dde0 name: 'Humidity ({#PDU_SENSOR_NAME})' graph_items: - color: 1A7C11 item: host: 'Raritan PDU PX3' key: 'pdu.sensor.humidity.sensor[{#SNMPINDEX}]' - uuid: 16dc560826d944c0b200dfaf91c08a5c name: 'Temperature Sensor Discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#PDU_SENSOR_TYPE},.1.3.6.1.4.1.13742.6.3.6.3.1.2.1,{#PDU_SENSOR_SERIAL},.1.3.6.1.4.1.13742.6.3.6.3.1.3.1,{#PDU_SENSOR_NAME},.1.3.6.1.4.1.13742.6.3.6.3.1.4.1]' key: pdu.sensor.temperature filter: conditions: - macro: '{#PDU_SENSOR_TYPE}' value: '10' formulaid: A item_prototypes: - uuid: 21d652bd19064c82bec7e7fe104c2771 name: 'Temperature Sensor' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.5.3.1.4.1.{#SNMPINDEX}' key: 'pdu.sensor.temperature.sensor[{#SNMPINDEX}]' value_type: FLOAT units: 'degrees C' description: | PDU Temperature Sensor details: Name: {#PDU_SENSOR_NAME} Serial number: {#PDU_SENSOR_SERIAL} preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Application value: Temperature - uuid: d4be4dde14b143a78a2d44a015d7346a name: 'Temperature State' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.5.3.1.3.1.{#SNMPINDEX}' key: 'pdu.sensor.temperature.state[{#SNMPINDEX}]' value_type: FLOAT description: | PDU Temperature State details: Name: {#PDU_SENSOR_NAME} Serial number: {#PDU_SENSOR_SERIAL} valuemap: name: 'Raritan PDU State Enumeration' tags: - tag: Application value: State trigger_prototypes: - uuid: ff21a0bb62dc4781afe5d82cdac8a7c3 expression: 'last(/Raritan PDU PX3/pdu.sensor.temperature.state[{#SNMPINDEX}])=6' name: 'High Critical State on Temperature Sensor' priority: HIGH description: | PDU Temperature State details: Name: {#PDU_SENSOR_NAME} Serial number: {#PDU_SENSOR_SERIAL} - uuid: 88bee181add248ce8a077f8bb19ccf0e expression: 'last(/Raritan PDU PX3/pdu.sensor.temperature.state[{#SNMPINDEX}])=5' name: 'High Warning State on Temperature Sensor' priority: WARNING description: | PDU Temperature State details: Name: {#PDU_SENSOR_NAME} Serial number: {#PDU_SENSOR_SERIAL} - uuid: 4147c65a8630441c82ddfa084df3e590 expression: 'last(/Raritan PDU PX3/pdu.sensor.temperature.state[{#SNMPINDEX}])=2' name: 'Low Critical State on Temperature Sensor' priority: HIGH description: | PDU Temperature State details: Name: {#PDU_SENSOR_NAME} Serial number: {#PDU_SENSOR_SERIAL} - uuid: ca5ebd7f49ef483e9be2a02be5a48e29 expression: 'last(/Raritan PDU PX3/pdu.sensor.temperature.state[{#SNMPINDEX}])=3' name: 'Low Warning State on Temperature Sensor' priority: WARNING description: | PDU Temperature State details: Name: {#PDU_SENSOR_NAME} Serial number: {#PDU_SENSOR_SERIAL} - uuid: 829d6c0c73574a68b586b04b15ac1735 expression: 'last(/Raritan PDU PX3/pdu.sensor.temperature.state[{#SNMPINDEX}])=-1' name: 'Unavailable State on Temperature Sensor' priority: INFO description: | PDU Temperature State details: Name: {#PDU_SENSOR_NAME} Serial number: {#PDU_SENSOR_SERIAL} graph_prototypes: - uuid: 60cf1b3056b1473ba66cbda6fb01ac42 name: 'Temperature ({#PDU_SENSOR_NAME})' graph_items: - color: 1A7C11 item: host: 'Raritan PDU PX3' key: 'pdu.sensor.temperature.sensor[{#SNMPINDEX}]' - uuid: 973a23c8b8744241af86a6159b53f131 name: 'System Discovery' type: SNMP_AGENT snmp_oid: 'discovery[{#PDU_SYSTEM_CONTACT},.1.3.6.1.2.1.1.4,{#PDU_SYSTEM_LOCATION},.1.3.6.1.2.1.1.6,{#PDU_SYSTEM_NAME},.1.3.6.1.2.1.1.5,{#PDU_SYSTEM_DESCRIPTION},.1.3.6.1.2.1.1.1]' key: pdu.system item_prototypes: - uuid: e3771a1962964b3490c735723721b48f name: 'System {#PDU_SYSTEM_NAME} Uptime' type: SNMP_AGENT snmp_oid: '.1.3.6.1.2.1.1.3.{#SNMPINDEX}' key: 'pdu.system.uptime[{#SNMPINDEX}]' units: uptime description: | System uptime of device with the following system properties: Name: {#PDU_SYSTEM_NAME} Location: {#PDU_SYSTEM_LOCATION} Contact: {#PDU_SYSTEM_CONTACT} Description: {#PDU_SYSTEM_DESCRIPTION} preprocessing: - type: MULTIPLIER parameters: - '0.01' tags: - tag: Application value: System macros: - macro: '{$SNMP_COMMUNITY}' value: e3b56dd2ad99199 dashboards: - uuid: ac1d78b1707d402285cb7ecabf429ccb name: 'External Sensors' pages: - widgets: - type: GRAPH_PROTOTYPE width: '12' height: '5' fields: - type: INTEGER name: source_type value: '2' - type: INTEGER name: columns value: '1' - type: INTEGER name: rows value: '1' - type: GRAPH_PROTOTYPE name: graphid value: name: 'Temperature ({#PDU_SENSOR_NAME})' host: 'Raritan PDU PX3' - type: GRAPH_PROTOTYPE x: '12' width: '12' height: '5' fields: - type: INTEGER name: source_type value: '2' - type: INTEGER name: columns value: '1' - type: INTEGER name: rows value: '1' - type: GRAPH_PROTOTYPE name: graphid value: name: 'Humidity ({#PDU_SENSOR_NAME})' host: 'Raritan PDU PX3' - uuid: 4bbecf9d78744c23b7d7ffca49800099 name: Inlets pages: - widgets: - type: GRAPH_PROTOTYPE width: '5' height: '5' fields: - type: INTEGER name: source_type value: '2' - type: INTEGER name: columns value: '1' - type: INTEGER name: rows value: '1' - type: GRAPH_PROTOTYPE name: graphid value: name: 'Power on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}' host: 'Raritan PDU PX3' - type: GRAPH_PROTOTYPE x: '5' width: '5' height: '5' fields: - type: INTEGER name: source_type value: '2' - type: INTEGER name: columns value: '1' - type: INTEGER name: rows value: '1' - type: GRAPH_PROTOTYPE name: graphid value: name: 'Power Factor on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}' host: 'Raritan PDU PX3' - type: GRAPH_PROTOTYPE x: '10' width: '5' height: '5' fields: - type: INTEGER name: source_type value: '2' - type: INTEGER name: columns value: '1' - type: INTEGER name: rows value: '1' - type: GRAPH_PROTOTYPE name: graphid value: name: 'RMS Current on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}' host: 'Raritan PDU PX3' - type: GRAPH_PROTOTYPE x: '15' width: '5' height: '5' fields: - type: INTEGER name: source_type value: '2' - type: INTEGER name: columns value: '1' - type: INTEGER name: rows value: '1' - type: GRAPH_PROTOTYPE name: graphid value: name: 'RMS Voltage on INlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}' host: 'Raritan PDU PX3' - type: GRAPH_PROTOTYPE x: '20' width: '4' height: '5' fields: - type: INTEGER name: source_type value: '2' - type: INTEGER name: columns value: '1' - type: INTEGER name: rows value: '1' - type: GRAPH_PROTOTYPE name: graphid value: name: 'Frequency on Inlet {#PDU_INLET_ID} - {#PDU_INLET_NAME}' host: 'Raritan PDU PX3' - uuid: aab05ea6ee7e40189dfa81fa7bb54b5c name: Outlets pages: - widgets: - type: GRAPH_PROTOTYPE width: '5' height: '5' fields: - type: INTEGER name: source_type value: '2' - type: INTEGER name: columns value: '1' - type: INTEGER name: rows value: '1' - type: GRAPH_PROTOTYPE name: graphid value: name: 'Power on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}' host: 'Raritan PDU PX3' - type: GRAPH_PROTOTYPE x: '5' width: '5' height: '5' fields: - type: INTEGER name: source_type value: '2' - type: INTEGER name: columns value: '1' - type: INTEGER name: rows value: '1' - type: GRAPH_PROTOTYPE name: graphid value: name: 'Power Factor on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}' host: 'Raritan PDU PX3' - type: GRAPH_PROTOTYPE x: '10' width: '5' height: '5' fields: - type: INTEGER name: source_type value: '2' - type: INTEGER name: columns value: '1' - type: INTEGER name: rows value: '1' - type: GRAPH_PROTOTYPE name: graphid value: name: 'RMS Current on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}' host: 'Raritan PDU PX3' - type: GRAPH_PROTOTYPE x: '15' width: '5' height: '5' fields: - type: INTEGER name: source_type value: '2' - type: INTEGER name: columns value: '1' - type: INTEGER name: rows value: '1' - type: GRAPH_PROTOTYPE name: graphid value: name: 'RMS Voltage on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}' host: 'Raritan PDU PX3' - type: GRAPH_PROTOTYPE x: '20' width: '4' height: '5' fields: - type: INTEGER name: source_type value: '2' - type: INTEGER name: columns value: '1' - type: INTEGER name: rows value: '1' - type: GRAPH_PROTOTYPE name: graphid value: name: 'Frequency on Outlet {#PDU_OUTLET_ID} - {#PDU_OUTLET_NAME}' host: 'Raritan PDU PX3' - uuid: 531027253c5a469fbbf687c1da846869 name: Protectors pages: - widgets: - type: GRAPH_PROTOTYPE width: '24' height: '5' fields: - type: INTEGER name: source_type value: '2' - type: INTEGER name: columns value: '1' - type: INTEGER name: rows value: '1' - type: GRAPH_PROTOTYPE name: graphid value: name: 'RMS Current State on Over Current Protector {#PDU_PROTECTOR_LABEL} - {#PDU_PROTECTOR_NAME}' host: 'Raritan PDU PX3' valuemaps: - uuid: 72a1c7c6ee2549159720f8cc4aec6de4 name: 'Raritan PDU State Enumeration' mappings: - value: '-1' newvalue: Unavailable - value: '0' newvalue: Open - value: '1' newvalue: Closed - value: '2' newvalue: BelowLowerCritical - value: '3' newvalue: BelowLowerWarning - value: '4' newvalue: Normal - value: '5' newvalue: AboveUpperWarning - value: '6' newvalue: AboveUpperCritical - value: '7' newvalue: 'On' - value: '8' newvalue: 'Off' - value: '9' newvalue: Detected - value: '10' newvalue: NotDetected - value: '11' newvalue: Alarmed - value: '12' newvalue: OK - value: '14' newvalue: Fail - value: '15' newvalue: 'Yes' - value: '16' newvalue: 'No' - value: '17' newvalue: Standby - value: '20' newvalue: InSync - value: '21' newvalue: OutOfSync - value: '26' newvalue: Fault - value: '27' newvalue: Warning - value: '28' newvalue: Critical - value: '29' newvalue: SelfTest - value: '30' newvalue: NonRedundant