zabbix_export: version: '5.4' date: '2021-11-21T21:50:28Z' groups: - uuid: 7df96b18c230490a9a0a9e2307226338 name: Templates templates: - uuid: f23c1bace4e54be6ac4d681d7a87179f template: 'Raritan PDU' name: 'Raritan PDU' description: | ## Overview Works with Raritan PDU PX2 / PX3 and ATS PX3 products Discovery rules: - Inlets - Outlets - Overcurrent Protectors - Sensors With advanced power function (See for more info) ## Author eric_at_2037 groups: - name: Templates items: - uuid: bf23bddae2a64284a3897ee799631914 name: 'Device reachability using ICMP' type: SIMPLE key: icmpping delay: '3600' trends: 1825d valuemap: name: 'Host status' preprocessing: - type: BOOL_TO_DECIMAL parameters: - '' tags: - tag: Application value: Information(s) triggers: - uuid: 6daff4b8812b4f3ebf0aa60dd9837f9c expression: 'last(/Raritan PDU/icmpping)=0' name: '{HOST.NAME} is UNREACHABLE or DOWN' priority: DISASTER - uuid: 5de26d0c865b479da6dd6c181ceb53b6 name: 'Inlet Controller number' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.13742.6.3.2.2.1.5.1 key: inletControllerCount delay: '3600' trends: 1825d tags: - tag: Application value: Information(s) - uuid: e7a3ef34ac644bad86c4f54fb2c65916 name: 'Inlet number' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.13742.6.3.2.2.1.2.1 key: inletCount delay: '3600' trends: 1825d tags: - tag: Application value: Information(s) - uuid: f6818418baee4fa899ded803e053df52 name: 'Device Manufacter Name' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.13742.6.3.2.1.1.2.1 key: Manufacturer.PDU delay: '3600' trends: '0' value_type: CHAR inventory_link: TAG tags: - tag: Application value: Information(s) - uuid: 6e84eddea980499096f5285a41b7febc name: 'Outlet Controller number' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.13742.6.3.2.2.1.6.1 key: outletControllerCount delay: '3600' trends: 1825d tags: - tag: Application value: Information(s) - uuid: c6758093e8ee4d4abb143e83537a7259 name: 'Outlet number' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.13742.6.3.2.2.1.4.1 key: outletCount delay: '3600' trends: 1825d tags: - tag: Application value: Information(s) - uuid: 3a042a17641244e0a05bcf9274a1f44b name: 'Overcurrent Protector number' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.13742.6.3.2.2.1.3.1 key: overCurrentProtectorCount delay: '3600' trends: 1825d tags: - tag: Application value: Information(s) - uuid: 240a2df9a25a42379f6bf064e99cfed5 name: 'Device Model Name' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.13742.6.3.2.1.1.3.1 key: pduBasicIdentModel delay: '3600' trends: '0' value_type: CHAR inventory_link: TYPE tags: - tag: Application value: Information(s) - uuid: 499fda66622a4299bc0d3441aa122cb6 name: 'Device Current' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.13742.6.3.2.1.1.6.1 key: pduRatedCurrent delay: '3600' trends: '0' value_type: CHAR tags: - tag: Application value: Information(s) - uuid: 68f03fa8b1ce4f81a66638f8127b5697 name: 'Device Frequency' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.13742.6.3.2.1.1.7.1 key: pduRatedFrequency delay: '3600' trends: '0' value_type: CHAR tags: - tag: Application value: Information(s) - uuid: c0626e9ef6ef492b8413a69746d6bf78 name: 'Device Power Capability' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.13742.6.3.2.1.1.8.1 key: pduRatedVA delay: '3600' trends: '0' value_type: CHAR tags: - tag: Application value: Information(s) - uuid: 80a439e281e341969938ff73b9ef96c7 name: 'Device Voltage' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.13742.6.3.2.1.1.5.1 key: pduRatedVoltage delay: '3600' trends: '0' value_type: CHAR tags: - tag: Application value: Information(s) - uuid: 07a4a70f5a12403084b969976be6bc97 name: 'Device Serial Number' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.13742.6.3.2.1.1.4.1 key: pduSerialNumber delay: '3600' trends: '0' value_type: CHAR inventory_link: SERIALNO_A tags: - tag: Application value: Information(s) - uuid: 7e18e85a230c46d3a3c8d1a7b03cc732 name: Contact type: SNMP_AGENT snmp_oid: 'SNMPv2-MIB::sysContact.0' key: sysContact delay: '3600' trends: '0' value_type: CHAR inventory_link: CONTACT tags: - tag: Application value: Information(s) - uuid: 2c8bc8bcb1724dc09088fcb08f7092ce name: 'Software version (full)' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.13742.6.3.2.3.1.6.1.1.1 key: sysDescr delay: '3600' trends: '0' value_type: CHAR inventory_link: OS_FULL tags: - tag: Application value: Information(s) - uuid: c7d5466676204b65b60aa3419325ec20 name: 'Device Location' type: SNMP_AGENT snmp_oid: 'SNMPv2-MIB::sysLocation.0' key: sysLocation delay: '3600' trends: '0' value_type: CHAR inventory_link: LOCATION tags: - tag: Application value: Information(s) - uuid: 30db102e247a4797a8f1d45446f03cac name: 'Device Name' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.13742.6.3.2.2.1.13.1 key: sysName delay: '3600' trends: '0' value_type: CHAR inventory_link: NAME tags: - tag: Application value: Information(s) - uuid: ae9bd5a2c319491881f16904c79f2525 name: Uptime type: SNMP_AGENT snmp_oid: 'SNMPv2-MIB::sysUpTime.0' key: sysUpTime delay: '300' trends: 1825d units: uptime preprocessing: - type: MULTIPLIER parameters: - '0.01' tags: - tag: Application value: Information(s) triggers: - uuid: 735532e6db414fa58b1a37d5a06404e1 expression: 'last(/Raritan PDU/sysUpTime)<86400' name: 'Uptime is too low on {HOST.NAME}' priority: INFO - uuid: adaa24260ee84b26b366b65f7acbf37b expression: 'last(/Raritan PDU/sysUpTime)<3600' name: '{HOST.NAME} has just been restarted' priority: HIGH discovery_rules: - uuid: 499051dd71d344f3a02dd31410d92cea name: Sensors type: SNMP_AGENT snmp_oid: 'discovery[{#SNMPVALUE},.1.3.6.1.4.1.13742.6.3.6.3.1.4.1]' key: externalSensor delay: '3600' filter: conditions: - macro: '{#SNMPVALUE}' value: '.*' formulaid: A lifetime: 7d item_prototypes: - uuid: f1cf39579f53463b929d2d6a2e51a745 name: 'Sensor DecimalDigits of External Sensor $1' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.3.6.3.1.17.1.{#SNMPINDEX}' key: 'externalSensorDecimalDigits[{#SNMPVALUE}]' delay: '3600' value_type: FLOAT preprocessing: - type: JAVASCRIPT parameters: - 'return (Math.pow(0.1, value))' tags: - tag: Application value: Sensors - uuid: 73daac82d4c645c5bc273448d8cea32d name: 'Serial Number of External Sensor $1' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.3.6.3.1.3.1.{#SNMPINDEX}' key: 'externalSensorSerialNumber[{#SNMPVALUE}]' delay: '3600' trends: '0' value_type: CHAR tags: - tag: Application value: Sensors - uuid: 4bb392bc361d4684b41542edd303fc30 name: 'Type of External Sensor $1' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.3.6.3.1.2.1.{#SNMPINDEX}' key: 'externalSensorType[{#SNMPVALUE}]' delay: '3600' tags: - tag: Application value: Sensors - uuid: ab5c6f42384749519ee366c659388959 name: 'Unit of External Sensor $1' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.3.6.3.1.16.1.{#SNMPINDEX}' key: 'externalSensorUnits[{#SNMPVALUE}]' delay: '3600' valuemap: name: 'Raritan PDU Units Enumeration' tags: - tag: Application value: Sensors - uuid: 54b40ba2822f473fb1645d2daf622f7f name: 'RAW Value of Sensor $1' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.5.3.1.4.1.{#SNMPINDEX}' key: 'measurementsExternalSensorRAWValue[{#SNMPVALUE}]' delay: '60' trends: 1825d value_type: FLOAT tags: - tag: Application value: Sensors - uuid: 35c34a1df8d24bbd8e7b4b53e471a7e4 name: 'State of External Sensor $1' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.5.3.1.3.1.{#SNMPINDEX}' key: 'measurementsExternalSensorState[{#SNMPVALUE}]' delay: '60' trends: 1825d valuemap: name: 'Raritan PDU State Enumeration' tags: - tag: Application value: Sensors trigger_prototypes: - uuid: fb7f019f86db4151845cd127fc02217b expression: 'last(/Raritan PDU/measurementsExternalSensorState[{#SNMPVALUE}])<>4' name: 'Sensor problem on {#SNMPVALUE}' priority: AVERAGE - uuid: 7f2fc06bd2ab4be7bb1911a8f5ba4c91 expression: 'last(/Raritan PDU/measurementsExternalSensorState[{#SNMPVALUE}])=6' name: 'Sensor problem on {#SNMPVALUE} is too high' priority: HIGH - uuid: 66c18a64ecaf4fb8831de63d0272c9d2 expression: 'last(/Raritan PDU/measurementsExternalSensorState[{#SNMPVALUE}])=2' name: 'Sensor problem on {#SNMPVALUE} is too low' priority: HIGH - uuid: aff7b2e75c9d42238677fff011285c8d name: 'Value of Sensor {#SNMPVALUE}' type: CALCULATED key: 'measurementsExternalSensorUsableValue[{#SNMPVALUE}]' delay: '60' value_type: FLOAT params: 'last(//measurementsExternalSensorRAWValue[{#SNMPVALUE}])*last(//externalSensorDecimalDigits[{#SNMPVALUE}])' tags: - tag: Application value: Sensors graph_prototypes: - uuid: 3a2a02be2bc74acd883937058e17e0fa name: 'Value of Sensor {#SNMPVALUE}' graph_items: - color: '000000' item: host: 'Raritan PDU' key: 'measurementsExternalSensorUsableValue[{#SNMPVALUE}]' - uuid: c60e3d956ecd4ee29addc8f9cad865b9 name: 'Overcurrent Protectors' type: SNMP_AGENT snmp_oid: 'discovery[{#SNMPVALUE},.1.3.6.1.4.1.13742.6.3.4.3.1.2.1]' key: overCurrentProtector delay: '3600' filter: conditions: - macro: '{#SNMPVALUE}' value: '.*' formulaid: A lifetime: 7d item_prototypes: - uuid: 0a6e7f6c457642a1ac4dcaad5adeb619 name: 'State of Overcurrent Protector $1' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.3.3.1.3.1.{#SNMPINDEX}.1' key: 'measurementsOverCurrentProtectorSensorStatermsCurrent[{#SNMPVALUE}]' delay: '60' valuemap: name: 'Raritan PDU State Enumeration' tags: - tag: Application value: 'Overcurrent Protectors' trigger_prototypes: - uuid: 29f1025ad83842f394c1f14323f0686a expression: 'last(/Raritan PDU/measurementsOverCurrentProtectorSensorStatermsCurrent[{#SNMPVALUE}])=6' name: 'Current problem too high on Overcurrent Protector {#SNMPVALUE}' priority: HIGH - uuid: 85defbe5183a4771baaab50aafd79d4f expression: 'last(/Raritan PDU/measurementsOverCurrentProtectorSensorStatermsCurrent[{#SNMPVALUE}])=2' name: 'Current problem too low on Overcurrent Protector {#SNMPVALUE}' priority: HIGH - uuid: 6e51e79d39b143dda7d5a624292ca0db expression: 'last(/Raritan PDU/measurementsOverCurrentProtectorSensorStatermsCurrent[{#SNMPVALUE}])<>4' name: 'State of Overcurrent Protector {#SNMPVALUE}' priority: AVERAGE - uuid: d4d4762697904430994d5a85b2d2a0aa name: 'Current of Overcurrent Protector $1' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.3.3.1.4.1.{#SNMPINDEX}.1' key: 'measurementsOverCurrentProtectorSensorValuermsCurrent[{#SNMPVALUE}]' delay: '60' value_type: FLOAT preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Application value: 'Overcurrent Protectors' - uuid: c9b1f2439e6e4f6cbc63307694ca33a9 name: 'Name of Overcurrent Protector $1' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.3.4.3.1.3.1.{#SNMPINDEX}' key: 'overCurrentProtectorName[{#SNMPVALUE}]' delay: '3600' trends: '0' value_type: CHAR tags: - tag: Application value: 'Overcurrent Protectors' - uuid: c2b2548ada134a7da77ead2c445e38de name: 'Capability of Overcurrent Protector $1' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.3.4.3.1.5.1.{#SNMPINDEX}' key: 'overCurrentProtectorRatedCurrent[{#SNMPVALUE}]' delay: '3600' trends: '0' value_type: CHAR tags: - tag: Application value: 'Overcurrent Protectors' - uuid: 65e38bacb5204d7b90d91a7f3e3b85a0 name: 'Type of Overcurrent Protector $1' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.3.4.3.1.4.1.{#SNMPINDEX}' key: 'overCurrentProtectorType[{#SNMPVALUE}]' delay: '3600' trends: '0' value_type: CHAR tags: - tag: Application value: 'Overcurrent Protectors' graph_prototypes: - uuid: 056e331f8d3e467ba5d909d74ddaf6f5 name: 'Current of Overcurrent Protector {#SNMPVALUE}' graph_items: - color: FF0000 item: host: 'Raritan PDU' key: 'measurementsOverCurrentProtectorSensorValuermsCurrent[{#SNMPVALUE}]' - uuid: 37108349f92b4f678d04aedaae55f09d name: Inlets type: SNMP_AGENT snmp_oid: 'discovery[{#SNMPVALUE},.1.3.6.1.4.1.13742.6.3.3.3.1.2.1]' key: pduInlet delay: '3600' filter: conditions: - macro: '{#SNMPVALUE}' value: '.*' formulaid: A lifetime: 7d item_prototypes: - uuid: 93c0b5abc6d74d68b8797df1d0c54946 name: 'Name of Inlet $1' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.3.3.3.1.3.1.{#SNMPINDEX}' key: 'InletName[{#SNMPVALUE}]' delay: '3600' history: 7d trends: '0' value_type: CHAR tags: - tag: Application value: Inlets - uuid: f8bc7cafae164150aba68db8b3f79e22 name: 'Type of Inlet $1' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.3.3.3.1.12.1.{#SNMPINDEX}' key: 'inletPlugDescriptor[{#SNMPVALUE}]' delay: '3600' history: 7d trends: '0' value_type: CHAR tags: - tag: Application value: Inlets - uuid: 28bdcb0903f94fe6831c66b09cc40985 name: 'Current Capability of Inlet $1' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.3.3.3.1.7.1.{#SNMPINDEX}' key: 'inletRatedCurrent[{#SNMPVALUE}]' delay: '3600' history: 7d trends: '0' value_type: CHAR tags: - tag: Application value: Inlets - uuid: 1d55f8f82b4f4a249e12c32703906b20 name: 'Volatage Capability of Inlet $1' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.3.3.3.1.6.1.{#SNMPINDEX}' key: 'inletRatedVoltage[{#SNMPVALUE}]' delay: '3600' history: 7d trends: '0' value_type: CHAR tags: - tag: Application value: Inlets - uuid: 38ef3add4cb746bca0d193ffbb003513 name: 'Current DecimalDigits of Inlet $1' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.3.3.4.1.7.1.{#SNMPINDEX}.1' key: 'inletSensorDecimalDigitsrmsCurrent[{#SNMPVALUE}]' delay: '3600' value_type: FLOAT preprocessing: - type: JAVASCRIPT parameters: - 'return (Math.pow(0.1, value))' tags: - tag: Application value: Inlets - uuid: 4abffda55b124193b7e035fb3afb4cec name: 'RAW Current of Inlet $1' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.2.3.1.4.1.{#SNMPINDEX}.1' key: 'measurementsInletSensorRAWValuermsCurrent[{#SNMPVALUE}]' delay: '60' trends: 1825d value_type: FLOAT tags: - tag: Application value: Inlets - uuid: 29882051e4a14c1ca35723b6dd9ad337 name: 'State of Frequency on Inlet $1' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.2.3.1.3.1.{#SNMPINDEX}.23' key: 'measurementsInletSensorStateFrequency[{#SNMPVALUE}]' delay: '60' trends: 1825d valuemap: name: 'Raritan PDU State Enumeration' tags: - tag: Application value: Inlets trigger_prototypes: - uuid: 85674c09f7524cffb4c2f16872f28a29 expression: 'last(/Raritan PDU/measurementsInletSensorStateFrequency[{#SNMPVALUE}])<>4' name: 'Frequency problem on Inlet {#SNMPVALUE}' priority: AVERAGE - uuid: 767607fda3fc46fe85470180e1ef6228 expression: 'last(/Raritan PDU/measurementsInletSensorStateFrequency[{#SNMPVALUE}])=6' name: 'Frequency problem too high on Inlet {#SNMPVALUE}' priority: HIGH - uuid: 0dbc8247e7ee4fa386327ddbe4eb91ba expression: 'last(/Raritan PDU/measurementsInletSensorStateFrequency[{#SNMPVALUE}])=2' name: 'Frequency problem too low on Inlet {#SNMPVALUE}' priority: HIGH - uuid: 52b877e062e04b8aae25e301b98fe291 name: 'State of activeEnergy on Inlet $1' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.2.3.1.3.1.{#SNMPINDEX}.8' key: 'measurementsInletSensorStatermsactiveEnergy[{#SNMPVALUE}]' delay: '60' trends: 1825d valuemap: name: 'Raritan PDU State Enumeration' tags: - tag: Application value: Inlets trigger_prototypes: - uuid: 6fdedf020ac948018e2750558795773d expression: 'last(/Raritan PDU/measurementsInletSensorStatermsactiveEnergy[{#SNMPVALUE}])<>4' name: 'activeEnergy problem on Inlet {#SNMPVALUE}' priority: AVERAGE - uuid: 8b613929a5d04659898c9095a7149008 name: 'State of activePower on Inlet $1' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.2.3.1.3.1.{#SNMPINDEX}.5' key: 'measurementsInletSensorStatermsactivePower[{#SNMPVALUE}]' delay: '60' trends: 1825d valuemap: name: 'Raritan PDU State Enumeration' tags: - tag: Application value: Inlets trigger_prototypes: - uuid: b9c29db0d4f549c5bc641a8ef9dadc89 expression: 'last(/Raritan PDU/measurementsInletSensorStatermsactivePower[{#SNMPVALUE}])<>4' name: 'activePower problem on Inlet {#SNMPVALUE}' priority: AVERAGE - uuid: 99d7194a0ac64b17bea5a296042ee208 name: 'State of apparentPower on Inlet $1' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.2.3.1.3.1.{#SNMPINDEX}.6' key: 'measurementsInletSensorStatermsapparentPower[{#SNMPVALUE}]' delay: '60' trends: 1825d valuemap: name: 'Raritan PDU State Enumeration' tags: - tag: Application value: Inlets trigger_prototypes: - uuid: d935818849384a2dac4f920b17814b97 expression: 'last(/Raritan PDU/measurementsInletSensorStatermsapparentPower[{#SNMPVALUE}])<>4' name: 'apparentPower problem on Inlet {#SNMPVALUE}' priority: AVERAGE - uuid: 614ef2a2b433464aaca87e632e2f51e5 name: 'State of Current on Inlet $1' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.2.3.1.3.1.{#SNMPINDEX}.1' key: 'measurementsInletSensorStatermsCurrent[{#SNMPVALUE}]' delay: '60' trends: 1825d valuemap: name: 'Raritan PDU State Enumeration' tags: - tag: Application value: Inlets trigger_prototypes: - uuid: f1b210ecd8424916a134878d0092a547 expression: 'last(/Raritan PDU/measurementsInletSensorStatermsCurrent[{#SNMPVALUE}])<>4' name: 'Current problem on Inlet {#SNMPVALUE}' priority: AVERAGE - uuid: 015c685c7588453e99c6344712e77843 expression: 'last(/Raritan PDU/measurementsInletSensorStatermsCurrent[{#SNMPVALUE}])=6' name: 'Current problem too high on Inlet {#SNMPVALUE}' priority: HIGH - uuid: 2e1ead221c2843e9babb6a5bc6b94aef expression: 'last(/Raritan PDU/measurementsInletSensorStatermsCurrent[{#SNMPVALUE}])=2' name: 'Current problem too low on Inlet {#SNMPVALUE}' priority: HIGH - uuid: 644487059af247c6bfc705275591adbc name: 'State of powerFactor on Inlet $1' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.2.3.1.3.1.{#SNMPINDEX}.7' key: 'measurementsInletSensorStatermspowerFactor[{#SNMPVALUE}]' delay: '60' trends: 1825d valuemap: name: 'Raritan PDU State Enumeration' tags: - tag: Application value: Inlets trigger_prototypes: - uuid: 5ea60129569c49d5b33ce67a357ae36b expression: 'last(/Raritan PDU/measurementsInletSensorStatermspowerFactor[{#SNMPVALUE}])<>4' name: 'powerFactor problem on Inlet {#SNMPVALUE}' priority: AVERAGE - uuid: ad38012137e94b86a0167df9c6da83b0 name: 'State of Voltage on Inlet $1' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.2.3.1.3.1.{#SNMPINDEX}.4' key: 'measurementsInletSensorStatermsVoltage[{#SNMPVALUE}]' delay: '60' trends: 1825d valuemap: name: 'Raritan PDU State Enumeration' tags: - tag: Application value: Inlets trigger_prototypes: - uuid: 09c9cec9b9fe486891675faea3ba2934 expression: 'last(/Raritan PDU/measurementsInletSensorStatermsVoltage[{#SNMPVALUE}])<>4' name: 'Voltage problem on Inlet {#SNMPVALUE}' priority: AVERAGE - uuid: 2052ed315252498db1dc80d689e4bec4 expression: 'last(/Raritan PDU/measurementsInletSensorStatermsVoltage[{#SNMPVALUE}])=6' name: 'Voltage problem too high on Inlet {#SNMPVALUE}' priority: HIGH - uuid: c0bf538c9032415780d52e11cb8ab456 expression: 'last(/Raritan PDU/measurementsInletSensorStatermsVoltage[{#SNMPVALUE}])=2' name: 'Voltage problem too low on Inlet {#SNMPVALUE}' priority: HIGH - uuid: edd7b7013e2d4c68b627b0a9628698f1 name: 'Current of Inlet $1' type: CALCULATED key: 'measurementsInletSensorUsableValuermsCurrent[{#SNMPVALUE}]' delay: '60' trends: 1825d value_type: FLOAT units: A params: 'last(//measurementsInletSensorRAWValuermsCurrent[{#SNMPVALUE}])*last(//inletSensorDecimalDigitsrmsCurrent[{#SNMPVALUE}])' tags: - tag: Application value: Inlets - uuid: e4d79af9dd1840259b2141a77c2ff8f9 name: 'Frequency of Inlet $1' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.2.3.1.4.1.{#SNMPINDEX}.23' key: 'measurementsInletSensorValueFrequency[{#SNMPVALUE}]' delay: '60' trends: 1825d value_type: FLOAT units: Hz preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Application value: Inlets - uuid: 1e3ca14ff2ec4162af3c36eaa718cd1b name: 'activeEnergy of Inlet $1' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.2.3.1.4.1.{#SNMPINDEX}.8' key: 'measurementsInletSensorValuermsactiveEnergy[{#SNMPVALUE}]' delay: '60' trends: 1825d value_type: FLOAT units: kWh preprocessing: - type: MULTIPLIER parameters: - '0.001' tags: - tag: Application value: Inlets - uuid: daf26864b2ff460b80000482b1892a5a name: 'activePower of Inlet $1' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.2.3.1.4.1.{#SNMPINDEX}.5' key: 'measurementsInletSensorValuermsactivePower[{#SNMPVALUE}]' delay: '60' trends: 1825d units: W tags: - tag: Application value: Inlets - uuid: 1938e1bd1f6d4d33a11c898984065ad4 name: 'apparentPower of Inlet $1' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.2.3.1.4.1.{#SNMPINDEX}.6' key: 'measurementsInletSensorValuermsapparentPower[{#SNMPVALUE}]' delay: '60' trends: 1825d units: VA tags: - tag: Application value: Inlets - uuid: 8dfd6d90abcd4eb182158385af77636a name: 'powerFactor of Inlet $1' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.2.3.1.4.1.{#SNMPINDEX}.7' key: 'measurementsInletSensorValuermspowerFactor[{#SNMPVALUE}]' delay: '60' trends: 1825d value_type: FLOAT preprocessing: - type: MULTIPLIER parameters: - '0.01' tags: - tag: Application value: Inlets - uuid: b08ac56ae26243e6a58a6c3e9a79b9b0 name: 'Voltage of Inlet $1' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.2.3.1.4.1.{#SNMPINDEX}.4' key: 'measurementsInletSensorValuermsVoltage[{#SNMPVALUE}]' delay: '60' trends: 1825d units: V tags: - tag: Application value: Inlets graph_prototypes: - uuid: 0ee94315a7214d39bf96e575a2c774de name: 'Inlet {#SNMPVALUE}' graph_items: - color: FF0000 item: host: 'Raritan PDU' key: 'measurementsInletSensorUsableValuermsCurrent[{#SNMPVALUE}]' - sortorder: '1' color: FF8000 yaxisside: RIGHT item: host: 'Raritan PDU' key: 'measurementsInletSensorValueFrequency[{#SNMPVALUE}]' - sortorder: '2' color: B4B4B4 item: host: 'Raritan PDU' key: 'measurementsInletSensorValuermspowerFactor[{#SNMPVALUE}]' - sortorder: '3' color: 0040FF yaxisside: RIGHT item: host: 'Raritan PDU' key: 'measurementsInletSensorValuermsVoltage[{#SNMPVALUE}]' - uuid: 40501cfba55b497a840ee7d6483661f7 name: Outlets type: SNMP_AGENT snmp_oid: 'discovery[{#SNMPVALUE},.1.3.6.1.4.1.13742.6.3.5.3.1.2.1]' key: pduOutlet delay: '3600' filter: conditions: - macro: '{#SNMPVALUE}' value: '.*' formulaid: A lifetime: 7d item_prototypes: - uuid: be925868e99944f6a6b270e8af74842e name: 'OnOff Status of Outlet $1' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.5.4.3.1.4.1.{#SNMPINDEX}.14' key: 'OnOffStatus[{#SNMPVALUE}]' delay: '300' tags: - tag: Application value: Outlets - uuid: a06c2fd0f9294bbd88e80db9aa0c0295 name: 'Current Capability of Outlet $1' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.3.5.3.1.7.1.{#SNMPINDEX}' key: 'OutletCurrent[{#SNMPVALUE}]' delay: '300' history: 7d trends: '0' value_type: CHAR tags: - tag: Application value: Outlets - uuid: 30b85f0bf6a04cf986f3e970da50cc4c name: 'Name of Outlet $1' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.3.5.3.1.3.1.{#SNMPINDEX}' key: 'OutletName[{#SNMPVALUE}]' delay: '3600' trends: '0' value_type: CHAR tags: - tag: Application value: Outlets - uuid: 88cbf46db7b24ac6b758af9f41b33ec3 name: 'Type of Outlet $1' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.3.5.3.1.29.1.{#SNMPINDEX}' key: 'outletReceptacleDescriptor[{#SNMPVALUE}]' delay: '3600' history: 7d trends: '0' value_type: CHAR tags: - tag: Application value: Outlets - uuid: ec7f7801601c477fbf196144c47b7a8f name: 'Voltage Capability of Outlet $1' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.13742.6.3.5.3.1.6.1.{#SNMPINDEX}' key: 'OutletVolts[{#SNMPVALUE}]' delay: '300' history: 7d trends: '0' value_type: CHAR tags: - tag: Application value: Outlets valuemaps: - uuid: 1fb7799dfa324164b2262f8f56008455 name: 'Host status' mappings: - value: '0' newvalue: Up - value: '2' newvalue: Unreachable - uuid: 1aa964c2caea4e93ae79ea6e9d91df67 name: 'Raritan PDU State Enumeration' mappings: - value: '-1' newvalue: Unavailable - value: '0' newvalue: Open - value: '1' newvalue: Closed - value: '2' newvalue: BelowLowerCritical - value: '3' newvalue: BelowLowerWarning - value: '4' newvalue: Normal - value: '5' newvalue: AboveUpperWarning - value: '6' newvalue: AboveUpperCritical - value: '7' newvalue: 'On' - value: '8' newvalue: 'Off' - value: '9' newvalue: Detected - value: '10' newvalue: NotDetected - value: '11' newvalue: Alarmed - value: '12' newvalue: OK - value: '14' newvalue: Fail - value: '15' newvalue: 'Yes' - value: '16' newvalue: 'No' - value: '17' newvalue: Standby - value: '20' newvalue: InSync - value: '21' newvalue: OutOfSync - value: '26' newvalue: Fault - value: '27' newvalue: Warning - value: '28' newvalue: Critical - value: '29' newvalue: SelfTest - value: '30' newvalue: NonRedundant - uuid: 1e31bd42758f41bb99c6bb72ccf1496b name: 'Raritan PDU Units Enumeration' mappings: - value: '-1' newvalue: None - value: '0' newvalue: Other - value: '1' newvalue: Volt - value: '2' newvalue: Ampere - value: '3' newvalue: Watt - value: '4' newvalue: VA - value: '5' newvalue: WattHour - value: '6' newvalue: VAHour - value: '7' newvalue: 'Degree C' - value: '8' newvalue: Hertz - value: '9' newvalue: Percent - value: '10' newvalue: Meterpersec - value: '11' newvalue: Pascal - value: '12' newvalue: PSI - value: '13' newvalue: G - value: '14' newvalue: 'Degree F' - value: '15' newvalue: Feet - value: '16' newvalue: Inch - value: '17' newvalue: CM - value: '18' newvalue: Meters - value: '19' newvalue: RPM - value: '20' newvalue: Dgrees - value: '21' newvalue: LUX - value: '22' newvalue: Grampercubicmeter - value: '23' newvalue: var