5.02021-11-25T12:34:55ZTemplatesTemplates/ModulesTemplate Module ICMP PingTemplate Module ICMP PingTemplate Module ICMP Ping version: 0.12Templates/ModulesStatus- ICMP pingSIMPLEicmpping601wStatusService state{max(#3)}=0Unavailable by ICMP pingHIGHLast value: {ITEM.LASTVALUE1}.
Last three attempts returned timeout. Please check device connectivity.
- ICMP lossSIMPLEicmppingloss601wFLOAT%Status{min(5m)}>{$ICMP_LOSS_WARN} and {min(5m)}<100High ICMP ping lossWARNINGUnavailable by ICMP ping{Template Module ICMP Ping:icmpping.max(#3)}=0
- ICMP response timeSIMPLEicmppingsec601wFLOATsStatus{avg(5m)}>{$ICMP_RESPONSE_TIME_WARN}High ICMP ping response timeWARNINGHigh ICMP ping loss{Template Module ICMP Ping:icmppingloss.min(5m)}>{$ICMP_LOSS_WARN} and {Template Module ICMP Ping:icmppingloss.min(5m)}<100Unavailable by ICMP ping{Template Module ICMP Ping:icmpping.max(#3)}=0
{$ICMP_LOSS_WARN}20{$ICMP_RESPONSE_TIME_WARN}0.15Vertiv EXS UPSVertiv EXS UPSTemplate Module ICMP PingTemplatesInformation(s)Operational- ContactSNMP_AGENTSNMPv2-MIB::sysContact.0sysContact607d0CHARCONTACTInformation(s)
- Software version (full)SNMP_AGENTSNMPv2-MIB::sysDescr.0sysDescr607d0CHAROS_FULLInformation(s)
- Device LocationSNMP_AGENTSNMPv2-MIB::sysLocation.0sysLocation607d0CHARLOCATIONInformation(s)
- Device NameSNMP_AGENTSNMPv2-MIB::sysName.0sysName607d0CHARNAMEInformation(s)
- UptimeSNMP_AGENTSNMPv2-MIB::sysUpTime.0sysUpTime6031duptimeInformation(s)MULTIPLIER0.01
- UPS battery capacity (%)SNMP_AGENT.1.3.6.1.2.1.33.1.2.4.0upsAdvBatteryCapacity607dFLOAT%Operational{last(#1)}<99Battery Capacity on {HOST.NAME}HIGH
- UPS input voltage L1SNMP_AGENT.1.3.6.1.2.1.33.1.3.3.1.3.1upsAdvInputVoltage1607dFLOATVACOperational
- UPS input voltage L2SNMP_AGENT.1.3.6.1.2.1.33.1.3.3.1.3.2upsAdvInputVoltage2607dFLOATVACOperational
- UPS input voltage L3SNMP_AGENT.1.3.6.1.2.1.33.1.3.3.1.3.3upsAdvInputVoltage3607dFLOATVACOperational
- UPS output current L1SNMP_AGENT.1.3.6.1.2.1.33.1.4.4.1.3.1upsAdvOutputCurrent1607dFLOATAOperationalMULTIPLIER0.1
- UPS output current L2SNMP_AGENT.1.3.6.1.2.1.33.1.4.4.1.3.2upsAdvOutputCurrent2607dFLOATAOperationalMULTIPLIER0.1
- UPS output current L3SNMP_AGENT.1.3.6.1.2.1.33.1.4.4.1.3.3upsAdvOutputCurrent3607dFLOATAOperationalMULTIPLIER0.1
- UPS output load (%)SNMP_AGENT.1.3.6.1.2.1.33.1.4.4.1.5.1upsAdvOutputLoad607dFLOAT%Operational{last(0)}>95Output load Critical on {HOST.NAME}HIGH{last(0)}>90Output load High on {HOST.NAME}WARNING
- UPS output power L1SNMP_AGENT.1.3.6.1.2.1.33.1.4.4.1.4.1upsAdvOutputPower1607dFLOATWOperational
- UPS output power L2SNMP_AGENT.1.3.6.1.2.1.33.1.4.4.1.4.2upsAdvOutputPower2607dFLOATWOperational
- UPS output power L3SNMP_AGENT.1.3.6.1.2.1.33.1.4.4.1.4.3upsAdvOutputPower3607dFLOATWOperational
- UPS output voltage L1SNMP_AGENT.1.3.6.1.2.1.33.1.4.4.1.2.1upsAdvOutputVoltage1607dFLOATVACOperational
- UPS output voltage L2SNMP_AGENT.1.3.6.1.2.1.33.1.4.4.1.2.2upsAdvOutputVoltage2607dFLOATVACOperational
- UPS output voltage L3SNMP_AGENT.1.3.6.1.2.1.33.1.4.4.1.2.3upsAdvOutputVoltage3607dFLOATVACOperational
- UPS battery statusSNMP_AGENT.1.3.6.1.2.1.33.1.2.1.0upsBasicBatteryStatus607dOperationalVertivUPS-BatterieStatus{last(0)}=3The battery power is too low to support the load on {HOST.NAME}DISASTER
- UPS time on batterySNMP_AGENT1.3.6.1.2.1.33.1.2.2.0upsBasicBatteryTimeOnBattery607dsOperationalMULTIPLIER0.01
- UPS battery time remainingSNMP_AGENT.1.3.6.1.2.1.33.1.2.3.0upsBatteryTimeRemaining607dminOperational
- UPS Inlet air temperatureSNMP_AGENT1.3.6.1.4.1.476.1.42.3.9.20.1.20.1.2.1.4291upsInletAirTemperature607d°COperational{last()}>34High inlet air temperature on {HOST.NAME}HIGH
- UPS system statusSNMP_AGENT.1.3.6.1.4.1.476.1.42.3.9.20.1.20.1.3.20.1.4123upsSystemStatus607dOperationalVertivUPS-SystemStatus{last()}>8System status on {HOST.NAME}HIGH
Battery statusFIXEDBOLD_LINEC80000- Vertiv EXS UPSupsBasicBatteryStatus
UPS CurrentFIXEDBOLD_LINEB71C1C- Vertiv EXS UPSupsAdvOutputCurrent1
1BOLD_LINE43A047- Vertiv EXS UPSupsAdvOutputCurrent2
2BOLD_LINE4444FF- Vertiv EXS UPSupsAdvOutputCurrent3
UPS Input VoltageBOLD_LINEB71C1C- Vertiv EXS UPSupsAdvInputVoltage1
1BOLD_LINE43A047- Vertiv EXS UPSupsAdvInputVoltage2
2BOLD_LINE4444FF- Vertiv EXS UPSupsAdvInputVoltage3
UPS LoadFIXEDFIXEDGRADIENT_LINE4444FF- Vertiv EXS UPSupsAdvOutputLoad
UPS Output PowerFIXEDBOLD_LINEB71C1C- Vertiv EXS UPSupsAdvOutputPower1
1BOLD_LINE43A047- Vertiv EXS UPSupsAdvOutputPower2
2BOLD_LINE4444FF- Vertiv EXS UPSupsAdvOutputPower3
UPS Output VoltageBOLD_LINEB71C1C- Vertiv EXS UPSupsAdvOutputVoltage1
1BOLD_LINE43A047- Vertiv EXS UPSupsAdvOutputVoltage2
2BOLD_LINE4444FF- Vertiv EXS UPSupsAdvOutputVoltage3
UPS TemperatureFIXED14000FF- Vertiv EXS UPSupsInletAirTemperature
Service state0Down1UpVertivUPS-BatterieStatus1Unknown2Normal3Low4DepletedVertivUPS-SystemStatus1Normal Operation2StartUp8Normal with Warning16Normal with Alarm32Abnormal Operation