5.02021-11-25T12:35:10ZTemplatesTemplates/ModulesUPSNetAgent UPSNetAgent UPSTemplate Module ICMP PingTemplatesUPSinformation(s)Operational- UPS battery statusSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.2.1.1.0netagent.battery.status30mOperationalapcBatteryStatus{last(,30m)}=1 or {last(,30m)}=4RECOVERY_EXPRESSION{last(,30m)}=2UPS NetAgent - Batteries are unable to sustain the present load or are degradedHIGHYES{last(,15m)}=3RECOVERY_EXPRESSION{last(,15m)}=2UPS NetAgent - Remaining battery run-time is poorAVERAGEBattery is lowYES
- UptimeSNMP_AGENT.1.3.6.1.2.1.1.3.0sysUpTimeuptimeStatusMULTIPLIER0.01
- UPS time on batterySNMP_AGENT.1.3.6.1.4.1.935.1.1.1.2.1.2.0upsBaseBatteryTimeOnBattery60s7dsThe elapsed time in seconds since the UPS has switched
to battery power.
Прошедшее время в секундах с момента переключения ИБП
на батареи.OperationalMULTIPLIER0.01
- UPS Battery Last Replace DateSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.2.1.3.0upsBaseLBatteryLastReplaceDate1h0TEXTThe date when the UPS system's batteries were last replaced
in mm/dd/yy format. For UPS models, this value is originally
set in the factory. When the UPS batteries are replaced,
this value should be reset by the administrator
Дата последней замены батарей системы ИБП
в формате мм / дд / гг. Это значение изначально установлено на заводе. Когда батареи ИБП заменены, это значение должно быть сброшено администраторомinformation(s)
- UPS statusSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.4.1.1.0upsBaseOutputStatus30sThe current state of the UPS. If the UPS is unable
to determine the state of the UPS this variable is set
to unknown(1).OperationalUPS NetAgent Status
- UPS battery capacity (%)SNMP_AGENT.1.3.6.1.4.1.935.1.1.1.2.2.1.0upsSmartBatteryCapacity60s7dFLOAT%The remaining battery capacity expressed in
percent of full capacity.
Оставшаяся емкость аккумулятора выражена в
процентов от полной емкости.Operational
- UPS battery temperatureSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.2.2.3.0upsSmartBatteryTemperature60s°CThe current internal UPS temperature expressed in tenths of
a Celsius degree.
Текущая внутренняя температура ИБП, выраженная в десятых долях
градус Цельсия.OperationalMULTIPLIER0.1
- UPS Firmware RevisionSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.1.2.1.0upsSmartIdentFirmwareRevision30s0TEXTinformation(s)
- UPS input voltageSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.3.2.1.0upsSmartInputLineVoltage30sFLOATVACOperationalMULTIPLIER0.1
- UPS output frequencySNMP_AGENT.1.3.6.1.4.1.935.1.1.1.4.2.2.0upsSmartOutputFrequency30sHzThe current input frequency to the UPS system in 1/10 Hz.OperationalMULTIPLIER0.1
- UPS output load (%)SNMP_AGENT.1.3.6.1.4.1.935.1.1.1.4.2.3.0upsSmartOutputLoad60s%The current UPS load expressed in percent
of rated capacity.Operational
- UPS output voltageSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.4.2.1.0upsSmartOutputVoltage30sVACThe output voltage of the UPS system in 1/10 VACOperationalMULTIPLIER0.1
Template Module ICMP PingTemplate Module ICMP PingTemplate Module ICMP Ping version: 0.12Templates/ModulesStatus- ICMP pingSIMPLEicmpping601wStatusService state{max(#3)}=0Unavailable by ICMP pingHIGHLast value: {ITEM.LASTVALUE1}.
Last three attempts returned timeout. Please check device connectivity.
- ICMP lossSIMPLEicmppingloss601wFLOAT%Status{min(5m)}>{$ICMP_LOSS_WARN} and {min(5m)}<100High ICMP ping lossWARNINGUnavailable by ICMP ping{Template Module ICMP Ping:icmpping.max(#3)}=0
- ICMP response timeSIMPLEicmppingsec601wFLOATsStatus{avg(5m)}>{$ICMP_RESPONSE_TIME_WARN}High ICMP ping response timeWARNINGHigh ICMP ping loss{Template Module ICMP Ping:icmppingloss.min(5m)}>{$ICMP_LOSS_WARN} and {Template Module ICMP Ping:icmppingloss.min(5m)}<100Unavailable by ICMP ping{Template Module ICMP Ping:icmpping.max(#3)}=0
{$ICMP_LOSS_WARN}20{$ICMP_RESPONSE_TIME_WARN}0.15apcBatteryStatus1unknown2batteryNormal3batteryLowService state0Down1UpUPS NetAgent Status1unknown2onLine3onBattery4onBoost5sleeping6onBypass7rebooting8standBy9onBuck