5.02021-11-21T21:52:19ZUPSSOCOMEC UPSSOCOMEC UPS## Overview
This templase include some info and trigger such as:
- Battery
- Temperature
- Output
- Alarms
You just edit the SNMP\_COMMUNITY value into the template
## Author
diablofight89
UPSAlarmBatteryInformationInputOutputTemperature- Ping checkSIMPLEicmpping30s45d120dAlarmService state{sum(#3)}=0 or ({TRIGGER.VALUE}=1 and {sum(#3)}<>3){HOSTNAME} - Network unavailableDISASTER
- Alarm - Battery TemperatureSNMP_AGENT.1.3.6.1.4.1.4555.1.1.7.1.6.3.16.0upsAlarmBatteryTemperature.07d"Battery Temperature Alarm. (A020)"Alarm
- Alarm - Fan FaultSNMP_AGENT.1.3.6.1.4.1.4555.1.1.7.1.6.3.32.0upsAlarmFansFailure.07d"Fans failure. (A054)"Alarm{last()}<>0{HOSTNAME} - Fan FaultAVERAGE{HOSTNAME} - Network unavailable{SOCOMEC UPS:icmpping.sum(#3)}=0 or ({TRIGGER.VALUE}=1 and {SOCOMEC UPS:icmpping.sum(#3)}<>3)
- Alarm - UPS LowBatterySNMP_AGENT.1.3.6.1.4.1.4555.1.1.7.1.6.3.14.0upsAlarmLowBattery.07d"The remaining battery run-time is less than or equal to battery low threshold. (A018)"Alarm
- Alarm - UPS OnBattery PowerSNMP_AGENT.1.3.6.1.4.1.4555.1.1.7.1.6.3.15.0upsAlarmOnBattery7d"The UPS is drawing power from the batteries. (A019)"Alarm{last()}<>0{HOSTNAME} - On Battery PowerHIGH{HOSTNAME} - Network unavailable{SOCOMEC UPS:icmpping.sum(#3)}=0 or ({TRIGGER.VALUE}=1 and {SOCOMEC UPS:icmpping.sum(#3)}<>3){HOSTNAME} - No Input Power{SOCOMEC UPS:upsInputFrequency.0.last()}<45
- Alarm - UPS OnBypassSNMP_AGENT.1.3.6.1.4.1.4555.1.1.7.1.6.3.55.0upsAlarmOnBypass.07d"Load supplied by automatic bypass.
Load not protected."Alarm{last()}<>0{HOSTNAME} - OnBypass ModeAVERAGE{HOSTNAME} - Network unavailable{SOCOMEC UPS:icmpping.sum(#3)}=0 or ({TRIGGER.VALUE}=1 and {SOCOMEC UPS:icmpping.sum(#3)}<>3)
- Alarm - UPS OverloadSNMP_AGENT.1.3.6.1.4.1.4555.1.1.7.1.6.3.2.0upsAlarmOverload.07d"The output load exceeds the UPS output capacity. (A001)"Alarm
- Alarm Present QuantitySNMP_AGENT.1.3.6.1.4.1.4555.1.1.7.1.6.1.0upsAlarmsPresent.07d"The present number of active alarm conditions."Alarm{last()}<>0{HOSTNAME} - Active AlarmsHIGHCheck on the UPS the issue{HOSTNAME} - Ambient temperature critical{SOCOMEC UPS:upsAmbientTemperature.0.avg(30)}>40{HOSTNAME} - Ambient temperature High{SOCOMEC UPS:upsAmbientTemperature.0.avg(30)}>37{HOSTNAME} - Ambient temperature low{SOCOMEC UPS:upsAmbientTemperature.0.avg(30)}<17{HOSTNAME} - Ambient temperature too low{SOCOMEC UPS:upsAmbientTemperature.0.avg(30)}<15{HOSTNAME} - Battery Charge Critical{SOCOMEC UPS:upsEstimatedChargeRemaining.0.last()}<15{HOSTNAME} - Battery Charge Low{SOCOMEC UPS:upsEstimatedChargeRemaining.0.last()}<30{HOSTNAME} - Battery Error{SOCOMEC UPS:upsBatteryStatus.0.last()}=1 or {SOCOMEC UPS:upsBatteryStatus.0.last()}=8 or {SOCOMEC UPS:upsBatteryStatus.0.last()}=9{HOSTNAME} - Fan Fault{SOCOMEC UPS:upsAlarmFansFailure.0.last()}<>0{HOSTNAME} - Network unavailable{SOCOMEC UPS:icmpping.sum(#3)}=0 or ({TRIGGER.VALUE}=1 and {SOCOMEC UPS:icmpping.sum(#3)}<>3){HOSTNAME} - No Input Power{SOCOMEC UPS:upsInputFrequency.0.last()}<45{HOSTNAME} - On Battery Power{SOCOMEC UPS:upsAlarmOnBattery.last()}<>0{HOSTNAME} - OnBypass Mode{SOCOMEC UPS:upsAlarmOnBypass.0.last()}<>0{HOSTNAME} - Output overloaded{SOCOMEC UPS:upsOutputLoadRate.0.avg(30)}>80
- Ambient TemperatureSNMP_AGENT.1.3.6.1.4.1.4555.1.1.7.1.2.7.0upsAmbientTemperature.07d°C"The ambient temperature inside the UPS in 0.1 degree"TemperatureMULTIPLIER0.1{avg(30)}>40{HOSTNAME} - Ambient temperature criticalHIGHExternal Temperature Critical{HOSTNAME} - Network unavailable{SOCOMEC UPS:icmpping.sum(#3)}=0 or ({TRIGGER.VALUE}=1 and {SOCOMEC UPS:icmpping.sum(#3)}<>3){avg(30)}>37{HOSTNAME} - Ambient temperature HighAVERAGEExternal Temperature High{HOSTNAME} - Ambient temperature critical{SOCOMEC UPS:upsAmbientTemperature.0.avg(30)}>40{HOSTNAME} - Network unavailable{SOCOMEC UPS:icmpping.sum(#3)}=0 or ({TRIGGER.VALUE}=1 and {SOCOMEC UPS:icmpping.sum(#3)}<>3){avg(30)}<17{HOSTNAME} - Ambient temperature lowAVERAGEExternal Temperature Low{HOSTNAME} - Ambient temperature too low{SOCOMEC UPS:upsAmbientTemperature.0.avg(30)}<15{HOSTNAME} - Network unavailable{SOCOMEC UPS:icmpping.sum(#3)}=0 or ({TRIGGER.VALUE}=1 and {SOCOMEC UPS:icmpping.sum(#3)}<>3){avg(30)}<15{HOSTNAME} - Ambient temperature too lowHIGHExternal Temperature Too Low{HOSTNAME} - Network unavailable{SOCOMEC UPS:icmpping.sum(#3)}=0 or ({TRIGGER.VALUE}=1 and {SOCOMEC UPS:icmpping.sum(#3)}<>3)
- Battery StatusSNMP_AGENT.1.3.6.1.4.1.4555.1.1.7.1.2.1.0upsBatteryStatus.07d"The present battery status"BatterySocomec - BatteryStatus{last()}=1 or {last()}=8 or {last()}=9{HOSTNAME} - Battery ErrorHIGH{HOSTNAME} - Network unavailable{SOCOMEC UPS:icmpping.sum(#3)}=0 or ({TRIGGER.VALUE}=1 and {SOCOMEC UPS:icmpping.sum(#3)}<>3)
- Battery VoltageSNMP_AGENT.1.3.6.1.4.1.4555.1.1.7.1.2.5.0upsBatteryVoltage.07dV"The magnitude of the present battery voltage in 0.1 Volt DC."Battery
- Battery PercentSNMP_AGENT.1.3.6.1.4.1.4555.1.1.7.1.2.4.0upsEstimatedChargeRemaining.07dFLOAT%"An estimate of the battery charge remaining expressed as a percent of full charge."Battery{last()}<15{HOSTNAME} - Battery Charge CriticalHIGH{HOSTNAME} - Network unavailable{SOCOMEC UPS:icmpping.sum(#3)}=0 or ({TRIGGER.VALUE}=1 and {SOCOMEC UPS:icmpping.sum(#3)}<>3){last()}<30{HOSTNAME} - Battery Charge LowAVERAGE{HOSTNAME} - Battery Charge Critical{SOCOMEC UPS:upsEstimatedChargeRemaining.0.last()}<15{HOSTNAME} - Network unavailable{SOCOMEC UPS:icmpping.sum(#3)}=0 or ({TRIGGER.VALUE}=1 and {SOCOMEC UPS:icmpping.sum(#3)}<>3)
- Battery Time RemainingSNMP_AGENT.1.3.6.1.4.1.4555.1.1.7.1.2.3.0upsEstimatedMinutesRemaining.07d!min"An estimate of the time to battery charge depletion under the present load conditions. Compute when UPS is on battery power"BatterySocomec - BatteryStatus
- Firmware VersionSNMP_AGENT1.3.6.1.2.1.33.1.1.4.0upsfirmware.01d7d0TEXTOSInformation
- ModelSNMP_AGENT.1.3.6.1.4.1.4555.1.1.7.1.1.1.0upsIdentModel.01d7d0TEXTMODELInformation
- Serial NumberSNMP_AGENT.1.3.6.1.4.1.4555.1.1.7.1.1.2.0upsIdentSerialNumber.01d7d0TEXTSERIALNO_AInformation
- Input FrequencySNMP_AGENT.1.3.6.1.4.1.4555.1.1.7.1.3.2.0upsInputFrequency.07dHz"The current input frequency to the UPS system in 0.1 HZ."InputMULTIPLIER0.1{last()}<45{HOSTNAME} - No Input PowerHIGH{HOSTNAME} - Network unavailable{SOCOMEC UPS:icmpping.sum(#3)}=0 or ({TRIGGER.VALUE}=1 and {SOCOMEC UPS:icmpping.sum(#3)}<>3){HOSTNAME} - Output status changed{SOCOMEC UPS:upsOutputSource.0.last()}<>3
- Output FrequencySNMP_AGENT.1.3.6.1.4.1.4555.1.1.7.1.4.2.0upsOutputFrequency.07dHz"The current output frequency of the UPS system in 0.1 of HZ."OutputMULTIPLIER0.1
- Output LoadSNMP_AGENT.1.3.6.1.4.1.4555.1.1.7.1.4.7.0upsOutputLoadRate.07dFLOAT%"Output global Load Rate."Output{avg(30)}>80{HOSTNAME} - Output overloadedAVERAGE{HOSTNAME} - Network unavailable{SOCOMEC UPS:icmpping.sum(#3)}=0 or ({TRIGGER.VALUE}=1 and {SOCOMEC UPS:icmpping.sum(#3)}<>3)
- Output StatusSNMP_AGENT.1.3.6.1.4.1.4555.1.1.7.1.4.1.0upsOutputSource.07d"The present source of output power."OutputSocomec - OutputSource{last()}<>3{HOSTNAME} - Output status changedAVERAGE{HOSTNAME} - Network unavailable{SOCOMEC UPS:icmpping.sum(#3)}=0 or ({TRIGGER.VALUE}=1 and {SOCOMEC UPS:icmpping.sum(#3)}<>3)
{$SNMP_COMMUNITY}afLpogHP16EWSOCOMEC - UPS Status220Ambient TemperatureSOCOMEC UPS50010000110000030Battery ChargeSOCOMEC UPS50010010110000030Output LoadSOCOMEC UPS5001000111000003110500100111100000https://monitoring.cartierecarrara.mobi/zabbix/image.php?imageid=2033Ambient Temperature50NOFIXEDFIXED0040FF- SOCOMEC UPSupsAmbientTemperature.0
Battery ChargeFIXEDFIXED1A7C11- SOCOMEC UPSupsEstimatedChargeRemaining.0
OnBattery Power1FIXEDFIXED2774A4- SOCOMEC UPSupsAlarmOnBattery
Output LoadFIXEDFIXED1A7C11- SOCOMEC UPSupsOutputLoadRate.0
Output Status19FIXEDFIXED0040FF- SOCOMEC UPSupsOutputSource.0
Service state0Down1UpSocomec - BatteryStatus1unknown2batteryNormal3batteryCharging4batteryTest5batteryDischarging6batteryLow7batteryDepleted8batteryFailure9batteryDisconnectedSocomec - OutputSource1unknown2onMaintenBypass3onInverter4normalMode5ecoMode6onBypass7standby8upsOff