zabbix_export: version: '6.0' date: '2021-11-25T12:34:23Z' groups: - uuid: 82c45661a4a0486da7f49dae76fa78f2 name: Powercom - uuid: 57b7ae836ca64446ba2c296389c009b7 name: Templates/Modules templates: - uuid: 5792fc6f9be6432b860f6393725c65de template: PowerCom name: PowerCom templates: - name: 'Template Module ICMP Ping' groups: - name: Powercom items: - uuid: 339546c275c441678324ebcca4594abb name: 'PowerCom: Battery Capacity (%)' type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.2.4.0 key: BatteryCapacity delay: 30s history: 7d value_type: FLOAT units: '%' tags: - tag: Application value: 'Batary Data' - uuid: 2945c385c8454bfba0536fc3f370f076 name: 'PowerCom: Battery Status' type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.2.1.0 key: BatteryStatus delay: 30s history: 7d value_type: FLOAT tags: - tag: Application value: 'Batary Data' triggers: - uuid: 33138bfe32bb45f894ad634fc58197b3 expression: last(/PowerCom/BatteryStatus)<>2 name: 'PowerCom: Battary Status' priority: DISASTER description: | unknown (1), batteryNormal (2), batteryLow (3), batteryDepleted (4) - uuid: 8834e3ac1431460db0a63ed216d74524 name: 'PowerCom: Battery Voltage' type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.2.5.0 key: BatteryVoltage delay: 30s history: 7d value_type: FLOAT units: V tags: - tag: Application value: 'Batary Data' - uuid: 07e0aa5f49344d62a0231cdec2d42858 name: 'PowerCom: Firmware Version UPS' type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.1.3.0 key: FirmwareUPS delay: 40320s history: 7d trends: '0' value_type: TEXT tags: - tag: Application value: 'Inventory Data' - uuid: 22c2e0ac9b8e4aa5b922665a3ce2715b name: 'PowerCom: Firmware Version Card' type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.1.4.0 key: FirmwareVersionCard delay: 40320s history: 7d trends: '0' value_type: TEXT tags: - tag: Application value: 'Inventory Data' - uuid: fd1e6d0061634d5a86c8d3e91e8a8e81 name: 'PowerCom: Input Frequency' type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.3.3.1.2.1 key: InputFrequency delay: 30s history: 7d value_type: FLOAT units: dHz tags: - tag: Application value: 'Batary Data' - uuid: 96dbd905cb954cefad3379370a860974 name: 'PowerCom: Input Voltage' type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.3.3.1.3.1 key: InputVoltage delay: 30s history: 7d value_type: FLOAT units: V tags: - tag: Application value: 'Batary Data' triggers: - uuid: d00819e5b3b34258a28e2b441f3746e1 expression: last(/PowerCom/InputVoltage)<180 name: 'PowerCom: No Input Voltage' priority: DISASTER - uuid: 1d97db6f378c40c79286b3e265dd4eab name: 'PowerCom: Model' type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.1.2.0 key: ModelUPS delay: 40320s history: 7d trends: '0' value_type: TEXT tags: - tag: Application value: 'Inventory Data' - uuid: 464eb10531214276a25d6ecc8f96e8db name: 'PowerCom: Output Frequency' type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.4.2.0 key: OutputFrequency delay: 30s history: 7d value_type: FLOAT units: dHz tags: - tag: Application value: 'Batary Data' - uuid: 19bfd8679957498dbb86ba9eb03f374a name: 'PowerCom: Output Load (%)' type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.4.4.1.5.1 key: OutputLoad delay: 30s history: 7d value_type: FLOAT units: '%' tags: - tag: Application value: 'Batary Data' triggers: - uuid: 255fc2c52ed943aeba748f7b9ff96484 expression: last(/PowerCom/OutputLoad)>80 name: 'PowerCom: Output Load Too High - {HOST.NAME}' priority: WARNING - uuid: 06dcacc7adc444ff852dc3cfae74f727 name: 'PowerCom: Output Power' type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.4.4.1.4.1 key: OutputPower delay: 5s history: 7d status: DISABLED value_type: FLOAT units: W tags: - tag: Application value: 'Batary Data' - uuid: 4c3505b05db944e0ac5d9d7d568c4862 name: 'PowerCom: Output Voltage' type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.4.4.1.2.1 key: OutputVoltage delay: 30s history: 7d value_type: FLOAT units: V tags: - tag: Application value: 'Batary Data' - uuid: 7d461bf7084043e383fef9c4faa271bd name: 'PowerCom: Run Time Remaining' type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.2.3.0 key: RunTimeRemaining delay: 30s history: 7d value_type: FLOAT units: Min tags: - tag: Application value: 'Batary Data' triggers: - uuid: b48d0e7d174e4d499c50dd3427bd1c5e expression: 'max(/PowerCom/RunTimeRemaining,60s)<5' name: 'PowerCom: Battary ieft: < 5 minutes - {HOST.NAME}' priority: DISASTER - uuid: 18866a9657184196a8e0196b30a63305 expression: 'max(/PowerCom/RunTimeRemaining,120s)<10' name: 'PowerCom: Battary ieft: < 10 minutes - {HOST.NAME}' priority: HIGH - uuid: 3d1b227d38e04758b0824cb270370423 name: 'PowerCom: SysUpTime' type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.1.3.0 key: SysUpTime delay: 30s history: 7d status: DISABLED value_type: FLOAT tags: - tag: Application value: 'Batary Data' - uuid: c96485cf85b0455db4e3b476810c0007 name: 'PowerCom: Temperature' type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.2.7.0 key: Temperature delay: 30s history: 7d value_type: FLOAT units: C tags: - tag: Application value: 'Batary Data' triggers: - uuid: 6300e370f6cb45a3bc91efa760980f52 expression: last(/PowerCom/Temperature)>=70 name: 'PowerCom: MAX Temperature Overhead - {HOST.NAME}' priority: DISASTER - uuid: eea8cbaee4044afcb3b7bc95503b4067 name: 'PowerCom: TimeOnBattery' type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.2.2.0 key: TimeOnBattery delay: 30s history: 7d value_type: FLOAT units: Min tags: - tag: Application value: 'Batary Data' - uuid: 37e5eb5606bc4abba66c8b20381a1e8a template: 'Template Module ICMP Ping' name: 'Template Module ICMP Ping' description: 'Template Module ICMP Ping version: 0.12' groups: - name: Templates/Modules items: - uuid: db5a94f6cea14deba957202b2f014469 name: 'ICMP ping' type: SIMPLE key: icmpping delay: '60' history: 1w valuemap: name: 'Service state' tags: - tag: Application value: Status triggers: - uuid: b030876299434f3ba43e11c584104a81 expression: 'max(/Template Module ICMP Ping/icmpping,#3)=0' name: 'Unavailable by ICMP ping' priority: HIGH description: | Last value: {ITEM.LASTVALUE1}. Last three attempts returned timeout. Please check device connectivity. - uuid: 04b21adaf422473a88df2c52786474ed name: 'ICMP loss' type: SIMPLE key: icmppingloss delay: '60' history: 1w value_type: FLOAT units: '%' tags: - tag: Application value: Status triggers: - uuid: 42c4b0310aaf4b9c8cb502542b7dea90 expression: 'min(/Template Module ICMP Ping/icmppingloss,5m)>{$ICMP_LOSS_WARN} and min(/Template Module ICMP Ping/icmppingloss,5m)<100' name: 'High ICMP ping loss' priority: WARNING dependencies: - name: 'Unavailable by ICMP ping' expression: 'max(/Template Module ICMP Ping/icmpping,#3)=0' - uuid: a79e33e5fd264725b934f603fa071555 name: 'ICMP response time' type: SIMPLE key: icmppingsec delay: '60' history: 1w value_type: FLOAT units: s tags: - tag: Application value: Status triggers: - uuid: 32b4d8f3eba34bd380803410111d4b7f expression: 'avg(/Template Module ICMP Ping/icmppingsec,5m)>{$ICMP_RESPONSE_TIME_WARN}' name: 'High ICMP ping response time' priority: WARNING dependencies: - name: 'High ICMP ping loss' expression: 'min(/Template Module ICMP Ping/icmppingloss,5m)>{$ICMP_LOSS_WARN} and min(/Template Module ICMP Ping/icmppingloss,5m)<100' - name: 'Unavailable by ICMP ping' expression: 'max(/Template Module ICMP Ping/icmpping,#3)=0' macros: - macro: '{$ICMP_LOSS_WARN}' value: '20' - macro: '{$ICMP_RESPONSE_TIME_WARN}' value: '0.15' valuemaps: - uuid: bdb5d65d925542eaa61c302dc40fbfe8 name: 'Service state' mappings: - value: '0' newvalue: Down - value: '1' newvalue: Up