5.02021-11-21T21:30:46ZTemplatesUPS_Inform-flexipowerUPS_Inform-flexipower## Overview
This template was tested on Zabbix 3.4 and work for Inform Flexipower 10KVA equiped with snmp card NetAgent II.
## Author
Hamdi Ben Abdallah
TemplatesBatteryEnvironmentalInformationPower- Probe humiditySNMP_AGENT.1.3.6.1.4.1.318.1.1.10.2.3.2.1.6.1iemStatusProbeCurrentHumid30DISABLED%Environmental
- Probe temperatureSNMP_AGENTenterprises.935.1.1.10.2.3.2.1.4.1iemStatusProbeCurrentTemp30CEnvironmental{avg(30)}>40Ambient temperature criticalHIGH{avg(30)}>30Ambient temperature highWARNING{avg(30)}<15Ambient temperature too lowAVERAGE
- Battery voltageSNMP_AGENTenterprises.935.1.1.1.2.2.8.0upsAdvBatteryActualVoltage180VBattery
- Battery chargeSNMP_AGENTenterprises.935.1.1.1.2.2.1.0upsAdvBatteryCapacity30%Battery{last(0)}<20Battery charge critically lowHIGH{last(0)}<50Battery charge lowWARNING
- Battery replacement statusSNMP_AGENTenterprises.935.1.1.1.2.2.4.0upsAdvBatteryReplaceIndicator180BatteryAPC Battery Replacement Status{last()}=4Battery failedHIGH{last()}=6Battery needs replacementWARNING{last()}=5Battery overheatHIGH{last()}=2No batteryWARNING
- Runtime remainingSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.2.2.3.0upsAdvBatteryRunTimeRemaining30sBatteryMULTIPLIER0.01
- Battery temperatureSNMP_AGENTenterprises.935.1.1.1.2.2.2.0upsAdvBatteryTemperature30CBattery
- UPS serial numberSNMP_AGENTenterprises.935.1.1.1.1.2.3.0upsAdvIdentSerialNumber36000CHARSERIALNO_AInformation
- Input frequencySNMP_AGENTenterprises.935.1.1.1.3.2.4.0upsAdvInputFrequency180HzPowerMULTIPLIER0.1
- Input voltageSNMP_AGENTenterprises.935.1.1.1.3.2.1.0upsAdvInputLineVoltage30VPowerMULTIPLIER0.1{avg(30)}<190Input voltage lowWARNING{avg(30)}>250Input voltage too highWARNING{avg(30)}=0No power inputHIGHInput voltage is zero
- Output load currentSNMP_AGENTenterprises.935.1.1.1.4.2.4.0upsAdvOutputCurrent30APower
- Output frequencySNMP_AGENTenterprises.935.1.1.1.4.2.2.0upsAdvOutputFrequency180HzPowerMULTIPLIER0.1
- Output loadSNMP_AGENTenterprises.935.1.1.1.4.2.3.0upsAdvOutputLoad30%Power{avg(90)}>85OverloadAVERAGE
- Output voltageSNMP_AGENTenterprises.935.1.1.1.4.2.1.0upsAdvOutputVoltage30VPowerMULTIPLIER0.1
- Battery replaced onSNMP_AGENTenterprises.935.1.1.1.2.1.3upsBasicBatteryLastReplaceDate36000TEXTInformation
- Battery statusSNMP_AGENTenterprises.935.1.1.1.2.1.1.0upsBasicBatteryStatus180BatteryAPC Battery Status
- UPS modelSNMP_AGENTenterprises.935.1.1.1.1.1.1.0upsBasicIdentModel36000CHARMODELInformation
- UPS nameSNMP_AGENT.1.3.6.1.2.1.33.1.1.5.0upsIdentName36000CHARInformation
- UPS software versionSNMP_AGENT1.3.6.1.2.1.33.1.1.3.0upsIdentUPSSoftwareVersion36000CHARInformation
APC Battery Replacement Status1unknown2notInstalled3ok4failed5highTemperature6replaceImmediately7lowCapacityAPC Battery Status1unknown2batteryNormal3batteryLow