5.02021-11-21T21:46:42ZUPSUPS CyberPower PR1000RT2UUPS CyberPower PR1000RT2U## Overview
I didn't see any templates for Cyberpower UPS systems so I made a quick and simple one.
Hope this can help someone else!
## Author
Adam Loghides
UPSUPS EnvironmentUPS Fault StatusUPS InformationUPS Power Status- UPS-BatteryLevelPercentSNMP_AGENT1.3.6.1.4.1.3808.1.1.1.2.2.1.0UPS-BatteryLevelPercent30s%UPS Power Status
- UPS-BatteryMinutesRemainingSNMP_AGENT1.3.6.1.4.1.3808.1.1.1.2.2.4.0UPS-BatteryMinutesRemaining30sminutesUPS Fault StatusMULTIPLIER.0001666666666666667{last(,0)}<20LESS than 20 minutes battery remaining on {HOST.NAME}DISASTERYES
- UPS-BatteryReplaceStatusSNMP_AGENT1.3.6.1.4.1.3808.1.1.1.2.2.5.0UPS-BatteryReplaceStatus30sUPS Fault StatusCyberPower UPS Battery Replacement Indicator{last()}=2UPS Battery Replacement NeededDISASTERYES
- UPS-BatteryVoltageSNMP_AGENT1.3.6.1.4.1.3808.1.1.1.2.2.2.0UPS-BatteryVoltage30sVoltsUPS Power Status
- UPS-CurrentRatingSNMP_AGENT1.3.6.1.4.1.3808.1.1.1.1.2.8.0UPS-CurrentRating12hampUPS Information
- UPS-DateLastReplacedBatterySNMP_AGENT1.3.6.1.4.1.3808.1.1.1.2.1.3.0UPS-DateLastReplaced30s0TEXTUPS Information
- UPS-FailCauseSNMP_AGENT1.3.6.1.4.1.3808.1.1.1.3.2.5.0UPS-FailCause30sDESCRIPTION
"The reason of UPS power failure.
This value is set to:
- noTransfer(1), if UPS is in utility mode.
- highLineVoltage(2), if UPS switch to battery mode by reason of
input voltage over the high transfer vloltage.
- brownout(3), if UPS switch to battery mode by reason of
input voltage under the low transfer vloltage.
- selfTest(4), if the UPS was commanded to do a self test."UPS Fault StatusCyberPower UPS InputLineFailCause
- UPS-FirmwareRevisionSNMP_AGENT1.3.6.1.4.1.3808.1.1.1.1.2.1.0UPS-FirmwareRevision12h0CHARUPS Information
- UPS-InputFrequencySNMP_AGENT1.3.6.1.4.1.3808.1.1.1.3.2.4.0UPS-InputFrequency30sHzUPS Power StatusMULTIPLIER.1
- UPS-InputStatusSNMP_AGENT1.3.6.1.4.1.3808.1.1.1.3.2.6.0UPS-InputStatus30s1 ⇒ normal
2 ⇒ overVoltage
3 ⇒ underVoltage
4 ⇒ frequencyFailure
5 ⇒ blackoutUPS Power StatusCyberPower UPS Input Status{last()}=5Blackout on {HOST.NAME}DISASTERYES{last()}=4Frequency Failure on {HOST.NAME}DISASTERYES{last()}=3Under Voltage on {HOST.NAME}DISASTERYES
- UPS-InputVoltageSNMP_AGENT1.3.6.1.4.1.3808.1.1.1.3.2.1.0UPS-InputVoltage30sVoltsUPS Power StatusMULTIPLIER.1{last(,0)}<50No Electricity on {HOST.NAME}DISASTERYES
- UPS-LoadPowerSNMP_AGENT1.3.6.1.4.1.3808.1.1.1.1.2.7.0UPS-LoadPower12hWattsUPS Information
- UPS-ModelSNMP_AGENT1.3.6.1.4.1.3808.1.1.1.1.1.1.0UPS-Model12h0CHARUPS Information
- UPS-NameSNMP_AGENT1.3.6.1.4.1.3808.1.1.1.1.1.2.0UPS-Name12h0CHARUPS Information
- UPS-OutputCurrentSNMP_AGENT1.3.6.1.4.1.3808.1.1.1.4.2.4.0UPS-OutputCurrent60sampsUPS Power Status
- UPS-OutputFrequencySNMP_AGENT1.3.6.1.4.1.3808.1.1.1.4.2.2.0UPS-OutputFrequency60sHzUPS Power StatusMULTIPLIER.1
- UPS-OutputLoadSNMP_AGENT1.3.6.1.4.1.3808.1.1.1.4.2.3.0UPS-OutputLoad30sWattsUPS Power Status{last()}>900UPS OverloadedHIGHYES
- UPS-OutputPowerSNMP_AGENT1.3.6.1.4.1.3808.1.1.1.4.2.5.0UPS-OutputPower60sVAUPS Power Status
- UPS-OutputStatusSNMP_AGENT1.3.6.1.4.1.3808.1.1.1.4.1.1UPS-OutputStatus60s1 ⇒ unknown
2 ⇒ onLine
3 ⇒ onBattery
4 ⇒ onBoost
5 ⇒ onSleep
6 ⇒ off
7 ⇒ rebootingUPS Power StatusCyberPower UPS Output Status{last()}=3Output is power by UPS Battery on {HOST.NAME}DISASTERYES
- UPS-OutputVoltageSNMP_AGENT1.3.6.1.4.1.3808.1.1.1.4.2.1.0UPS-OutputVoltage60sVoltsUPS Power StatusMULTIPLIER.1
- UPS-OutputWorkingFreqSNMP_AGENT1.3.6.1.4.1.3808.1.1.1.4.1.3.0UPS-OutputWorkingFreq60s0CHARUPS Information
- UPS-PowerRatingSNMP_AGENT1.3.6.1.4.1.3808.1.1.1.1.2.6.0UPS-PowerRating12hWattsUPS Information
- UPS-SerialNumberSNMP_AGENT1.3.6.1.4.1.3808.1.1.1.1.2.3.0UPS-SerialNumber12h0CHARUPS Information
- UPS-TemperatureSNMP_AGENT1.3.6.1.4.1.3808.1.1.1.2.2.3.0UPS-TemperatureLevel30sC1.3.6.1.4.1.3808.1.1.1.2.2.3.0UPS Environment{last()}>32Temperature is above 90F on {HOST.NAME}DISASTERYES
- UPS-TemperatureLevelFCALCULATEDUPS-TemperatureLevelF30sF(last("UPS-TemperatureLevel")*1.8+32)UPS Environment{last()}>82Temperature is above 82F on {HOST.NAME}HIGHYES{last()}<59Temperature is below 59F on {HOST.NAME}HIGHYES
- UPS-TimeOnBatterySNMP_AGENT1.3.6.1.4.1.3808.1.1.1.2.1.2.0UPS-TimeOnBattery30s0CHARUPS Fault Status
UPS Info120UPS Load and Battery RemainingUPS CyberPower PR1000RT2U50010000110000030UPS Battery Time RemainingUPS CyberPower PR1000RT2U5001000111000003UPS Battery Time Remaining33FF33- UPS CyberPower PR1000RT2UUPS-BatteryMinutesRemaining
UPS Load and Battery RemainingFILLED_REGION1A7C11- UPS CyberPower PR1000RT2UUPS-BatteryLevelPercent
1DASHED_LINE66FF66- UPS CyberPower PR1000RT2UUPS-OutputLoad
CyberPower UPS Battery Replacement Indicator1Battery Healthy2Battery Needs ReplacementCyberPower UPS InputLineFailCause1noTransfer2highLineVoltage3brownout4selfTestCyberPower UPS Input Status1normal2overVoltage3underVoltage4frequencyFailure5blackoutCyberPower UPS Output Status1unknown2onLine3onBattery4onBoost5onSleep6off7rebooting