5.02021-11-21T21:51:08ZDC-power systemsFlatpack SEltek Flatpack S## Description
Eltek Flatpack S DC-power system. Template for 2 rectifiers, 1 battery set. No solar power. No wind. No generator. Version 0.3 - Kari Karvonen <kari.karvonen@kasenet.fi> Eltek mibs available ftp://ftp.eltek.com. Ask your dealer or support for username and pass.
## Overview
Basic monitoring template for Eltek Flatpack / SmartPack S. 48VDC power system. 2 inverters. One batttery set. No solar power. No generator.
Template is for Zabbix 4.4.0rc1
Items
Power System Company
Power System Site
Power System Model
Power System Serial Number
Rectifiers Temperature Value
Rectifier 1 Input Voltage
Rectifier 2 Input Voltage
Rectifier 1 Output Current Value
Rectifier 2 Output Current Value
Rectifier 1 Status
Rectifier 2 Status
Battery 1 Status
Battery 1 Temperature Value
Battery 1 Total Capacity Value
Battery 1 Voltage Value
Battery 1 Remaining Capacity Value
Battery 1 Current Value
Main Control Unit Temperature Value
Mains Outage Total
Mains Voltage Status L1
Mains Voltage Status L2
Mains Voltage Value L1
Mains Voltage Value L2
Triggers
Lost mains power L1
Lost mains power L2
Battery high temperature
Battery low temperature
Battery 1 low remaining capacity
## Author
Kari Karvonen
DC-power systemsBatteryGeneralLoadMainsRectifier- Battery 1 Current ValueSNMP_AGENT.1.3.6.1.4.1.12148.10.10.6.5.0batteryCurrentsValue.0FLOATABatteryMULTIPLIER0.1
- Battery 1 Remaining Capacity ValueSNMP_AGENT.1.3.6.1.4.1.12148.10.10.9.5.0batteryRemainingCapacityValue.0AhBattery{last()}<{$BATTERY_CAPACITY_LOW_CRITICAL}Battery 1 low remaining capacity < {$BATTERY_CAPACITY_LOW_CRITICAL}HIGH
- Battery 1 StatusSNMP_AGENT.1.3.6.1.4.1.12148.10.10.1.0batteryStatus.0error (0)
normal (1)
minorAlarm (2)
majorAlarm (3)
disabled (4)
disconnected (5)
notPresent (6)
minorAndMajor (7)
majorLow (8)
minorLow (9)
majorHigh (10)
minorHigh (11)
event (12)
valueVolt (13)
valueAmp (14)
valueTemp (15)
valueUnit (16)
valuePerCent (17)
critical (18)
warning (19)BatteryEltek value mapping
- Battery 1 Temperature ValueSNMP_AGENT.1.3.6.1.4.1.12148.10.10.7.5.0batteryTemperaturesValue.0°CBattery{last()}>{$BATTERY_TEMP_HIGH_CRITICAL}Battery high temperature > {$BATTERY_TEMP_HIGH_CRITICAL}HIGH{last()}>{$BATTERY_TEMP_HIGH_WARNING}Battery high temperature > {$BATTERY_TEMP_HIGH_WARNING}WARNINGBattery high temperature > {$BATTERY_TEMP_HIGH_CRITICAL}{Flatpack S:batteryTemperaturesValue.0.last()}>{$BATTERY_TEMP_HIGH_CRITICAL}{last()}<{$BATTERY_TEMP_LOW_CRITICAL}Battery low temperature < {$BATTERY_TEMP_LOW_CRITICAL}HIGH{last()}<{$BATTERY_TEMP_LOW_WARNING}Battery low temperature < {$BATTERY_TEMP_LOW_WARNING}WARNINGBattery low temperature < {$BATTERY_TEMP_LOW_CRITICAL}{Flatpack S:batteryTemperaturesValue.0.last()}<{$BATTERY_TEMP_LOW_CRITICAL}
- Battery 1 Total Capacity ValueSNMP_AGENT.1.3.6.1.4.1.12148.10.10.11.5.0batteryTotalCapacityValue.01h0AhBattery
- Battery 1 Voltage ValueSNMP_AGENT.1.3.6.1.4.1.12148.10.10.5.5.0batteryVoltageValue.0FLOATVBatteryMULTIPLIER0.01
- Load Current ValueSNMP_AGENT.1.3.6.1.4.1.12148.10.9.2.5.0loadCurrentValue.0ALoadMULTIPLIER0.1
- Output powerCALCULATEDLoadOutputPower.0Wlast("loadVoltageValue.1")*last("loadCurrentValue.0")Load
- Load StatusSNMP_AGENT.1.3.6.1.4.1.12148.10.9.1.0loadStatus.0LoadEltek value mapping
- Load 1 Voltage ValueSNMP_AGENT.1.3.6.1.4.1.12148.10.9.9.1.6.1.1loadVoltageValue.1VLoadMULTIPLIER0.01
- Main Control Unit Temperature ValueSNMP_AGENT.1.3.6.1.4.1.12148.10.13.11.2.1.6.1.1mainControlUnitTemperatureValue°CGeneral
- Mains Outage TotalSNMP_AGENTSP2-MIB::mainsOutageTotal.0mainsOutageTotal.0counterMains
- Mains StatusSNMP_AGENT.1.3.6.1.4.1.12148.10.3.1.0mainsStatus.0MainsEltek value mapping
- Mains Voltage Status L1SNMP_AGENT.1.3.6.1.4.1.12148.10.3.4.1.2.1mainsVoltageStatus.1error (0)
normal (1)
minorAlarm (2)
majorAlarm (3)
disabled (4)
disconnected (5)
notPresent (6)
minorAndMajor (7)
majorLow (8)
minorLow (9)
majorHigh (10)
minorHigh (11)
event (12)
valueVolt (13)
valueAmp (14)
valueTemp (15)
valueUnit (16)
valuePerCent (17)
critical (18)
warning (19)MainsEltek value mapping
- Mains Voltage Status L2SNMP_AGENT.1.3.6.1.4.1.12148.10.3.4.1.2.2mainsVoltageStatus.2error (0)
normal (1)
minorAlarm (2)
majorAlarm (3)
disabled (4)
disconnected (5)
notPresent (6)
minorAndMajor (7)
majorLow (8)
minorLow (9)
majorHigh (10)
minorHigh (11)
event (12)
valueVolt (13)
valueAmp (14)
valueTemp (15)
valueUnit (16)
valuePerCent (17)
critical (18)
warning (19)MainsEltek value mapping
- Mains Voltage Value L1SNMP_AGENT.1.3.6.1.4.1.12148.10.3.4.1.6.1mainsVoltageValue.1VMains{last()}<80Lost mains power L1WARNING
- Mains Voltage Value L2SNMP_AGENT.1.3.6.1.4.1.12148.10.3.4.1.6.2mainsVoltageValue.2VMains{last()}<80Lost mains power L2WARNING
- Power System CompanySNMP_AGENT.1.3.6.1.4.1.12148.10.2.4.0powerSystemCompany.01h0TEXTGeneral
- Power System ModelSNMP_AGENT.1.3.6.1.4.1.12148.10.2.6.0powerSystemModel.01h0TEXTGeneral
- Power System Serial NumberSNMP_AGENT.1.3.6.1.4.1.12148.10.2.7.0powerSystemSerialNumber.01h0TEXTGeneral
- Power System SiteSNMP_AGENT.1.3.6.1.4.1.12148.10.2.5.0powerSystemSite.01h0TEXTGeneral
- Power System StatusSNMP_AGENT.1.3.6.1.4.1.12148.10.2.1.0powerSystemStatus.0GeneralEltek value mapping
- Rectifier 1 Input VoltageSNMP_AGENT.1.3.6.1.4.1.12148.10.5.6.1.4.1rectifierInputVoltageValue.1VRectifier
- Rectifier 2 Input VoltageSNMP_AGENT.1.3.6.1.4.1.12148.10.5.6.1.4.2rectifierInputVoltageValue.2VRectifier
- Rectifier 1 Output Current ValueSNMP_AGENT.1.3.6.1.4.1.12148.10.5.6.1.3.1rectifierOutputCurrentValue.1FLOATARectifierMULTIPLIER0.1
- Rectifier 2 Output Current ValueSNMP_AGENT.1.3.6.1.4.1.12148.10.5.6.1.3.2rectifierOutputCurrentValue.2FLOATARectifierMULTIPLIER0.1
- Rectifier 1 StatusSNMP_AGENT.1.3.6.1.4.1.12148.10.5.6.1.2.1rectifierStatus.1error (0)
normal (1)
minorAlarm (2)
majorAlarm (3)
disabled (4)
disconnected (5)
notPresent (6)
minorAndMajor (7)
majorLow (8)
minorLow (9)
majorHigh (10)
minorHigh (11)
event (12)
valueVolt (13)
valueAmp (14)
valueTemp (15)
valueUnit (16)
valuePerCent (17)
critical (18)
warning (19)RectifierEltek value mapping
- Rectifier 2 StatusSNMP_AGENT.1.3.6.1.4.1.12148.10.5.6.1.2.2rectifierStatus.2error (0)
normal (1)
minorAlarm (2)
majorAlarm (3)
disabled (4)
disconnected (5)
notPresent (6)
minorAndMajor (7)
majorLow (8)
minorLow (9)
majorHigh (10)
minorHigh (11)
event (12)
valueVolt (13)
valueAmp (14)
valueTemp (15)
valueUnit (16)
valuePerCent (17)
critical (18)
warning (19)RectifierEltek value mapping
- Rectifiers Temperature ValueSNMP_AGENT.1.3.6.1.4.1.12148.10.5.18.5.0rectifiersTemperatureValue.0°CRectifier
{$BATTERY_CAPACITY_LOW_CRITICAL}5Amper hours capacity left before alarm{$BATTERY_TEMP_HIGH_CRITICAL}40{$BATTERY_TEMP_HIGH_WARNING}25{$BATTERY_TEMP_LOW_CRITICAL}-20{$BATTERY_TEMP_LOW_WARNING}0{$SNMP_COMMUNITY}publicSNMPv2 read only communityBattery capacityFIXED1A7C11- Flatpack SbatteryRemainingCapacityValue.0
1F63100- Flatpack SbatteryTotalCapacityValue.0
Battery current, voltage and tempFC6EA3- Flatpack SbatteryVoltageValue.0
11A7C11- Flatpack SbatteryCurrentsValue.0
22774A4- Flatpack SbatteryTemperaturesValue.0
Power Mains250FIXEDFIXED1A7C11- Flatpack SmainsVoltageValue.1
1F63100- Flatpack SmainsVoltageValue.2
Rectifier input voltages250FIXEDFIXED1A7C11- Flatpack SrectifierInputVoltageValue.1
12774A4- Flatpack SrectifierInputVoltageValue.2
Eltek value mapping0error1normal2minorAlarm3majorAlarm4disabled5disconnected6notPresent7minorAndMajor8majorLow9minorLow10majorHigh11minorHigh12event13valueVolt14valueAmp15valueTemp16valueUnit17valuePerCent18critical19warning