zabbix_export: version: '6.0' date: '2021-11-21T21:44:19Z' groups: - uuid: 0e60ac85bc3941e2a1d66a048ff164da name: UPS templates: - uuid: 0d121b79ef3c4cbc8e42951325ca1f39 template: 'HP R5000 SNMP' name: 'HP R5000 SNMP' description: | ## Description HP R5000 UPS SNMP Made bu Ennio ## Overview ### Monitor power parametrs: frequency, power, voltage, current, temp. Full control for Input, Output (Segment), Battery, Bypass. I used CPQPOWER1.76.MIB and UPS-MIB.mib ## Author Ennio groups: - name: UPS items: - uuid: 3d63cb5733c14bcbaed32d6c12fb6d70 name: 'System Uptime' type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.1.3.0 key: .1.3.6.1.2.1.1.3.0 units: uptime preprocessing: - type: MULTIPLIER parameters: - '0.01' tags: - tag: Application value: Information - uuid: 2d6146f17d8849f6b589adde7c200a82 name: 'Running On Battery' type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.2.2.0 key: .1.3.6.1.2.1.33.1.2.2.0 delay: 30s units: s tags: - tag: Application value: Information - uuid: ff221585a4e3416486c7afe4b27e7697 name: 'Battery Temperature' type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.2.7.0 key: .1.3.6.1.2.1.33.1.2.7.0 status: DISABLED units: T tags: - tag: Application value: Battery - uuid: 0984152a45104f57bbbd9c9e1b7bf593 name: 'Bypass Current' type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.5.3.1.3.1 key: .1.3.6.1.2.1.33.1.5.3.1.3.1 delay: 30s tags: - tag: Application value: Bypass - uuid: 4395005e929f45639b6300a18c24fa85 name: 'Bypass Power' type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.5.3.1.4.1 key: .1.3.6.1.2.1.33.1.5.3.1.4.1 delay: 30s tags: - tag: Application value: Bypass - uuid: aa4158d57b064d4d8b8f2c24e23633f9 name: 'Alarm Present' type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.6.1.0 key: .1.3.6.1.2.1.33.1.6.1.0 delay: 30s status: DISABLED tags: - tag: Application value: Information triggers: - uuid: 9e47777f57cc40fd8ecc75a8e0e85628 expression: 'last(/HP R5000 SNMP/.1.3.6.1.2.1.33.1.6.1.0)<>0' name: '{HOST.NAME} Allarm = {ITEM.VALUE}' priority: HIGH - uuid: 1bd4723c25ef4433b567130869146104 name: 'Test Start Time' type: SNMP_AGENT snmp_oid: .1.3.6.1.2.1.33.1.7.5.0 key: .1.3.6.1.2.1.33.1.7.5.0 delay: 30s units: uptime preprocessing: - type: MULTIPLIER parameters: - '0.01' tags: - tag: Application value: Information - uuid: ce02917692b649e296254e012873461e name: Model type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.1.1.5.0 key: .1.3.6.1.4.1.232.165.1.1.5.0 delay: 1d trends: '0' value_type: TEXT tags: - tag: Application value: Information - uuid: cbfee1db4a3e40c98c9c72aa83c41480 name: P/N type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.1.2.6.0 key: .1.3.6.1.4.1.232.165.1.2.6.0 delay: 1d trends: '0' value_type: TEXT tags: - tag: Application value: Information - uuid: 36cf75d2d98a47be9a53fd66c89a6308 name: S/N type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.1.2.7.0 key: .1.3.6.1.4.1.232.165.1.2.7.0 delay: 1d trends: '0' value_type: TEXT tags: - tag: Application value: Information - uuid: 458293c4e2574df3b581022ded0855b4 name: MAC type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.1.2.8.0 key: .1.3.6.1.4.1.232.165.1.2.8.0 delay: 1d trends: '0' value_type: TEXT tags: - tag: Application value: Information - uuid: 36d858423bbf49d892fb113893674f3a name: 'Software Version' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.3.1.3.0 key: .1.3.6.1.4.1.232.165.3.1.3.0 delay: 1d trends: '0' value_type: TEXT tags: - tag: Application value: Information - uuid: 6f42d4b4799542f5b4d616580f80d729 name: 'Remaining Backup Time' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.3.2.1.0 key: .1.3.6.1.4.1.232.165.3.2.1.0 delay: 30s units: s tags: - tag: Application value: Information - uuid: 3dc67c767cae4ebb96fec040515a17ee name: 'Battery Voltage' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.3.2.2.0 key: .1.3.6.1.4.1.232.165.3.2.2.0 delay: 30s units: V tags: - tag: Application value: Battery - uuid: a49ca291765b45b180111a2d697c0311 name: 'Battery Current' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.3.2.3.0 key: .1.3.6.1.4.1.232.165.3.2.3.0 delay: 30s units: A description: | Battery Current as reported by the UPS metering. Current is positive when discharging, negative when recharging the battery. tags: - tag: Application value: Battery - uuid: 4d9b19baf67a4e77a08bac208c9c9456 name: 'Battery Capacity' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.3.2.4.0 key: .1.3.6.1.4.1.232.165.3.2.4.0 delay: 30s units: '%' tags: - tag: Application value: Battery - uuid: d5011d1065ae4ab7b470618d304105e6 name: 'Battery Status' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.3.2.5.0 key: .1.3.6.1.4.1.232.165.3.2.5.0 delay: 30s description: | Gives the status of the Advanced Battery Management; batteryFloating(3) status means that the charger is temporarily charging the battery to its float voltage; batteryResting(4) is the state when the battery is fully charged and none of the other actions (charging/discharging/floating) is being done. valuemap: name: 'HP R5000 Battery Status' tags: - tag: Application value: Battery triggers: - uuid: 7bf40f8b8c724caeb7f86f903d558280 expression: 'last(/HP R5000 SNMP/.1.3.6.1.4.1.232.165.3.2.5.0)<>3' name: '{HOST.NAME} Battery Status = {ITEM.VALUE}' priority: HIGH - uuid: 4e19c8d169d644449706c2ef5156d342 name: 'Input Frequency' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.3.3.1.0 key: .1.3.6.1.4.1.232.165.3.3.1.0 delay: 30s value_type: FLOAT units: Hz preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Application value: Input triggers: - uuid: d0aea5c1e85046fbb251e19149a82547 expression: 'last(/HP R5000 SNMP/.1.3.6.1.4.1.232.165.3.3.1.0)>50 or last(/HP R5000 SNMP/.1.3.6.1.4.1.232.165.3.3.1.0)<49' name: '{HOST.NAME} Input Frequency = {ITEM.VALUE}' priority: INFO - uuid: ba149c8a3ad44afc94198033e716f4cf name: 'Input Line Bads' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.3.3.2.0 key: .1.3.6.1.4.1.232.165.3.3.2.0 delay: 30s description: | The number of times the Input was out of tolerance in voltage or frequency. tags: - tag: Application value: Input - uuid: 0c1d6f76fe614373b1adb63d1acc0c9b name: 'Input Voltage' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.3.3.4.1.2.1 key: .1.3.6.1.4.1.232.165.3.3.4.1.2.1 delay: 30s units: V tags: - tag: Application value: Input triggers: - uuid: 9712c212d48b4115aaa4051990b5eb44 expression: 'last(/HP R5000 SNMP/.1.3.6.1.4.1.232.165.3.3.4.1.2.1)<200' name: '{HOST.NAME} Input Voltage is OFF = {ITEM.VALUE}' priority: DISASTER description: 'Входное напряжение пропало, включить автомат питания, проверить напряжение вводов АВР' - uuid: 8a3c2c137a4544128445017de03b9038 name: 'Input Current' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.3.3.4.1.3.1 key: .1.3.6.1.4.1.232.165.3.3.4.1.3.1 delay: 30s units: A tags: - tag: Application value: Input - uuid: 4ed71c5fa52942b78c7ab95673d55415 name: 'Output Load' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.3.4.1.0 key: .1.3.6.1.4.1.232.165.3.4.1.0 delay: 30s units: '%' tags: - tag: Application value: Output triggers: - uuid: a02eff1dc34843d88a4067b820c89b3d expression: 'last(/HP R5000 SNMP/.1.3.6.1.4.1.232.165.3.4.1.0)>70' name: '{HOST.NAME} Danger Load Level = {ITEM.VALUE}' priority: AVERAGE - uuid: 76b0245b36cf464f97135ba18d7f2bc4 expression: 'last(/HP R5000 SNMP/.1.3.6.1.4.1.232.165.3.4.1.0)>50' name: '{HOST.NAME} Higth Load Level = {ITEM.VALUE}' priority: INFO - uuid: b7eb91c294544ad596f992678c83ca24 expression: 'last(/HP R5000 SNMP/.1.3.6.1.4.1.232.165.3.4.1.0)>60' name: '{HOST.NAME} VERY Higth Load Level = {ITEM.VALUE}' priority: WARNING - uuid: 4a3ff95d0329420bb0ebb0ad5b056847 name: 'Output Frequency' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.3.4.2.0 key: .1.3.6.1.4.1.232.165.3.4.2.0 delay: 30s units: Hz preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Application value: Output triggers: - uuid: 62e42243096242058b78e4c3c7d13b82 expression: 'last(/HP R5000 SNMP/.1.3.6.1.4.1.232.165.3.4.2.0)>50 or last(/HP R5000 SNMP/.1.3.6.1.4.1.232.165.3.4.2.0)<49' name: '{HOST.NAME} Output Frequency = {ITEM.VALUE}' priority: INFO - uuid: a66b3e3b65f14ed2a4dd833bb5327c69 name: 'Output Voltage' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.3.4.4.1.2.1 key: .1.3.6.1.4.1.232.165.3.4.4.1.2.1 delay: 30s units: V tags: - tag: Application value: Output triggers: - uuid: 0d095ab6fa38442baf945b6eb074a339 expression: 'last(/HP R5000 SNMP/.1.3.6.1.4.1.232.165.3.4.4.1.2.1)<200' name: '{HOST.NAME} Output Voltage is OFF = {ITEM.VALUE}' priority: DISASTER description: 'Выходное напряжение пропало, включить ИБП' - uuid: eb7c73b45fb640f69ee26ac3bebfaf96 name: 'Output Current' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.3.4.4.1.3.1 key: .1.3.6.1.4.1.232.165.3.4.4.1.3.1 delay: 30s units: A tags: - tag: Application value: Output - uuid: 95fb6f5c68e747ea8ddc1be5dcc4ea84 name: 'Output Power' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.3.4.4.1.4.1 key: .1.3.6.1.4.1.232.165.3.4.4.1.4.1 delay: 30s units: W tags: - tag: Application value: Output - uuid: 57500e72b28f44068cb79a43b685b718 name: 'Output Source' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.3.4.5.0 key: .1.3.6.1.4.1.232.165.3.4.5.0 delay: 30s description: | The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker. valuemap: name: 'HP R5000 Output Source' tags: - tag: Application value: Output triggers: - uuid: e482f5b0d9b34a55a0b27c0df420d19d expression: 'last(/HP R5000 SNMP/.1.3.6.1.4.1.232.165.3.4.5.0)<>3' name: '{HOST.NAME} Output Source = {ITEM.VALUE}' priority: HIGH - uuid: 60abce71bbeb4f59bfb94ee494818b23 name: 'Bypass Frequency' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.3.5.1.0 key: .1.3.6.1.4.1.232.165.3.5.1.0 delay: 30s tags: - tag: Application value: Bypass - uuid: ad26913675494302b8f1ca4250d977bd name: 'Bypass Voltage' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.3.5.3.1.2.1 key: .1.3.6.1.4.1.232.165.3.5.3.1.2.1 delay: 30s tags: - tag: Application value: Bypass - uuid: 5f10e7f3e135437491b949d89327011e name: 'Ambient Temperature' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.3.6.1.0 key: .1.3.6.1.4.1.232.165.3.6.1.0 units: c° tags: - tag: Application value: Information triggers: - uuid: 7585da30563c40f49f89c89936fdf618 expression: 'last(/HP R5000 SNMP/.1.3.6.1.4.1.232.165.3.6.1.0)>30' name: '{HOST.NAME} Ambinet Temperature = {ITEM.VALUE}' priority: WARNING - uuid: 4b5b8c9c4cb04ec69587d7e56cfa470f name: 'Battery Test Status' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.3.7.2.0 key: .1.3.6.1.4.1.232.165.3.7.2.0 valuemap: name: 'HP R5000 Battary Test Status' tags: - tag: Application value: Battery triggers: - uuid: b0a7e7e2beb44540973e39a59324d596 expression: 'last(/HP R5000 SNMP/.1.3.6.1.4.1.232.165.3.7.2.0)<>2' name: '{HOST.NAME} Battery Test Status = {ITEM.VALUE}' priority: WARNING - uuid: c03fe7c73c12493aaae3ca226d485a55 name: 'Segment #1' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.3.10.2.1.2.1 key: .1.3.6.1.4.1.232.165.3.10.2.1.2.1 delay: 30s valuemap: name: 'HP R5000 Segment Status' tags: - tag: Application value: Output triggers: - uuid: d020b0c6580a48ef8babfaaad6a9e1c4 expression: 'last(/HP R5000 SNMP/.1.3.6.1.4.1.232.165.3.10.2.1.2.1)<>1' name: '{HOST.NAME} Output Segment #1 = {ITEM.VALUE}' priority: HIGH - uuid: 3716062b2df0461e96fcb1c218de00d9 name: 'Segment #2' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.232.165.3.10.2.1.2.2 key: .1.3.6.1.4.1.232.165.3.10.2.1.2.2 delay: 30s valuemap: name: 'HP R5000 Segment Status' tags: - tag: Application value: Output triggers: - uuid: 5af9eea691f44995b67fc7d79f5e58ae expression: 'last(/HP R5000 SNMP/.1.3.6.1.4.1.232.165.3.10.2.1.2.2)<>1' name: '{HOST.NAME} Output Segment #2 = {ITEM.VALUE}' priority: HIGH macros: - macro: '{$SNMP_COMMUNITY}' valuemaps: - uuid: ae2f4f66060446919497e77ac6fd2834 name: 'HP R5000 Battary Test Status' mappings: - value: '1' newvalue: unknown - value: '2' newvalue: passed - value: '3' newvalue: failed - value: '4' newvalue: inProgress - value: '5' newvalue: notSupported - value: '6' newvalue: inhibited - value: '7' newvalue: scheduled - uuid: 20bb1dbfeaba4d578b06a4c881ec307b name: 'HP R5000 Battery Status' mappings: - value: '1' newvalue: Charging - value: '2' newvalue: Discharging - value: '3' newvalue: Floating - value: '4' newvalue: Resting - uuid: b6d314329c764cad934207c290bfd0d3 name: 'HP R5000 Output Source' mappings: - value: '1' newvalue: other - value: '2' newvalue: none - value: '3' newvalue: normal - value: '4' newvalue: bypass - value: '5' newvalue: battery - value: '6' newvalue: booster - value: '7' newvalue: reducer - value: '8' newvalue: parallelCapacity - value: '9' newvalue: parallelRedundant - value: '10' newvalue: highEfficiencyMode - uuid: fcd5cad2d4824296b63ef11b9b3aadf5 name: 'HP R5000 Segment Status' mappings: - value: '1' newvalue: 'on' - value: '2' newvalue: 'off' - value: '3' newvalue: pendingOff - value: '4' newvalue: pendingOn - value: '5' newvalue: unknown triggers: - uuid: 92ce766ac262420088af766c7193c224 expression: 'last(/HP R5000 SNMP/.1.3.6.1.2.1.33.1.5.3.1.3.1)>0 or last(/HP R5000 SNMP/.1.3.6.1.2.1.33.1.5.3.1.4.1)>0' name: '{HOST.NAME} Bypass is Activated I={ITEM.VALUE1}, P={ITEM.VALUE2}' priority: HIGH graphs: - uuid: ebf65cda2a6a410d81b0759163d79db6 name: 'All in ONE' graph_items: - sortorder: '1' color: 2774A4 item: host: 'HP R5000 SNMP' key: .1.3.6.1.4.1.232.165.3.2.2.0 - sortorder: '2' color: 6C59DC item: host: 'HP R5000 SNMP' key: .1.3.6.1.4.1.232.165.3.4.4.1.2.1 - sortorder: '3' color: F7941D item: host: 'HP R5000 SNMP' key: .1.3.6.1.4.1.232.165.3.2.1.0 - sortorder: '4' color: FC6EA3 item: host: 'HP R5000 SNMP' key: .1.3.6.1.2.1.33.1.2.2.0 - sortorder: '5' color: 6C59DC item: host: 'HP R5000 SNMP' key: .1.3.6.1.4.1.232.165.3.2.4.0 - uuid: d8cfb39631ef4ffab256233978117557 name: Voltage graph_items: - color: 4000FF item: host: 'HP R5000 SNMP' key: .1.3.6.1.4.1.232.165.3.4.4.1.2.1 - sortorder: '1' color: F63100 item: host: 'HP R5000 SNMP' key: .1.3.6.1.4.1.232.165.3.2.2.0 - sortorder: '2' color: 2774A4 item: host: 'HP R5000 SNMP' key: .1.3.6.1.4.1.232.165.3.3.4.1.2.1