5.02021-11-21T21:58:59ZTemplates/UPSHuawei 10K UPSHuawei 10K UPS## Overview
This template for **Huawei UPS 2000**
Protocol SNMP v2
Items 95 with low discovery
**Triggers**:
Battery charge < {$BATTERY\_CHARGE}% on {HOST.NAME}
Battery backup time < {$BACKUP\_TIME} on {HOST.NAME}
Battery is discharging on {HOST.NAME}
**Macros****:**
{$BACKUP\_TIME} - Remaining critical battery life in minutes
{$BATTERY\_CHARGE} - The critical battery percentage
Template on my [GitHub](https://github.com/pgalonza/Notes/blob/master/administration/zabbix/templates/Template%20Huawei%2010K%20UPS.xml) repository
MIBs on my [GitHub](https://github.com/pgalonza/Notes/tree/master/administration/huawei/ups2000/snmp) repository
## Author
P.V. Galonza
Templates/UPSBatteryBypassControlCtrlDeviceGeneralInputOutput- Number of active alarmsSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.12.2.0huawei-ups.hwUpsAlarmCurrActiveNum5m30dNumber of active alarms, ranging from 0 to 8000.GeneralPOST
- Alarm synchronization IDSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.12.1.0huawei-ups.hwUpsAlarmSynchronNum10m30dAlarm synchronization ID. The value ranges from 0 to 4294967295. This value is used by the NetEco to obtain the active alarm synchronization ID and synchronize alarms.GeneralPOST
- Ambient humiditySNMP_AGENT1.3.6.1.4.1.2011.6.174.1.1.1.7.0huawei-ups.hwUpsEnvHumidity30d%Ambient humidity. An integer ranging from 0 to 100. The value is accurate to one decimal place on the NetEco. The unit is %.GeneralPOST
- Ambient temperature.SNMP_AGENT1.3.6.1.4.1.2011.6.174.1.1.1.6.0huawei-ups.hwUpsEnvTemper30d°CAmbient temperature. An integer ranging from -50 to 120. The value is accurate to one decimal place on the NetEco. The unit is °C.GeneralPOST
- Number of parallel systemsSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.1.1.5.0huawei-ups.hwUpsParallelSysNum1h30dNumber of parallel systems. An integer ranging from 0 to 63.GeneralPOST
- Site time UTCSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.11.1.0huawei-ups.hwUpsSiteTimeUTC10m30dsUTC time, ranging from 0 to 4294967295. The unit is seconds.GeneralPOST
- Number of devices in the systemSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.1.1.4.0huawei-ups.hwUpsSysDeviceNum1h30dNumber of devices in the system. An integer ranging from 0 to 63.GeneralPOST
- System interface protocol versionSNMP_AGENT.1.3.6.1.4.1.2011.6.174.1.1.1.3.0huawei-ups.hwUpsSysInerProtVersion6h30d0TEXTVersion number of the system interface protocol between the NetEco and NEs. A string of characters.GeneralPOST
- System main device ESNSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.1.1.1.0huawei-ups.hwUpsSystemMainDeviceESN6h30d0TEXTESN of the master device used for setting up a NetEco model. A string of characters.GeneralPOST
- System typeSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.1.1.2.0huawei-ups.hwUpsSystemType6h30d0TEXTName of the UPS system. A string of characters. Configurable.GeneralPOST
DeviceSNMP_AGENTdiscovery[{#HWUPSDEVICEID},1.3.6.1.4.1.2011.6.174.1.2.100.1.1, {#HWUPSDEVICETYPE}, 1.3.6.1.4.1.2011.6.174.1.2.100.1.2]huawei-ups.hwUpsDeviceIdRack ID, ranging from 1 to 100. This node is referenced as an index node by hwUpsDeviceIdentTable, hwUpsDeviceOperInfoTable, hwUpsInputTable, and hwUpsBattScheduleTestTable.{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} battery auto testSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.103.101.1.1.{#HWUPSDEVICEID}huawei-ups[hwUpsBattAutoTest.{#HWUPSDEVICEID}]10m30dScheduled shallow discharge test enabled or disabled. Enumeration value.
The value 1 indicates that the test is disabled.
The value 2 indicates that the test is enabled.ControlHUAWEI-UPS-MIB::hwUpsBattAutoTestPOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} battery auto test discharge rateSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.103.101.1.4.{#HWUPSDEVICEID}huawei-ups[hwUpsBattAutoTestDischargeRate.{#HWUPSDEVICEID}]10m30dShallow discharge test discharge ratio. An integer ranging from 10 to 50.ControlPOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} battery maximum discharge timeSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.103.101.1.5.{#HWUPSDEVICEID}huawei-ups[hwUpsBattAutoTestEndVol.{#HWUPSDEVICEID}]10m30dV/CellMaximum battery discharge time. An integer ranging from 160 to 195. The value is accurate to one decimal place on the NetEco. The unit is V/Cell.ControlPOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} battery auto test time intervalSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.103.101.1.3.{#HWUPSDEVICEID}huawei-ups[hwUpsBattAutoTestTimeInterval.{#HWUPSDEVICEID}]10m30ddScheduled shallow discharge test interval. An integer ranging from 30 to 90. The unit is days.ControlPOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} battery auto test time limitSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.103.101.1.2.{#HWUPSDEVICEID}huawei-ups[hwUpsBattAutoTestTimeLimit.{#HWUPSDEVICEID}]10m30dScheduled shallow discharge test time. Enumeration value.
Value 1 indicates 00:00 to 06:00.
Value 2 indicates 06:00 to 12:00.
Value 3 indicates 12:00 to 18:00.
Value 4 indicates 18:00 to 00:00.ControlHUAWEI-UPS-MIB::hwUpsBattAutoTestTimeLimitPOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} battery backup timeSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.6.100.1.4.{#HWUPSDEVICEID}huawei-ups[hwUpsBatteryBackupTime.{#HWUPSDEVICEID}]10s30dsBattery Backup Time. Value range: 0 to 172800, Unit: S, and the value is an integer.BatteryDISCARD_UNCHANGED_HEARTBEAT5mPOST{last()}<{$BACKUP_TIME}RECOVERY_EXPRESSION{last()}>{prev()}Battery backup time < {$BACKUP_TIME} on {HOST.NAME}HIGHlast value: {ITEM.LASTVALUE}{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} battery capacity leftSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.6.100.1.3.{#HWUPSDEVICEID}huawei-ups[hwUpsBatteryCapacityLeft.{#HWUPSDEVICEID}]10s30d%Battery Capacity Left. Value range: 0 to 100, Unit: %, and the value is an integer.BatteryDISCARD_UNCHANGED_HEARTBEAT5mPOST{last()}<{$BATTERY_CHARGE}RECOVERY_EXPRESSION{last()}>{prev()}Battery charge < {$BATTERY_CHARGE}% on {HOST.NAME}HIGHlast value: {ITEM.LASTVALUE}{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} battery currentSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.6.100.1.2.{#HWUPSDEVICEID}huawei-ups[hwUpsBatteryCurrent.{#HWUPSDEVICEID}]5m30dFLOATABattery Total Current. It is a real-time analog parameter. Value range: -60000 to 60000, Unit: A, and the value is accurate to one decimal place (.1).BatteryMULTIPLIER0.1POST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} battery row statusSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.6.100.1.100.{#HWUPSDEVICEID}huawei-ups[hwUpsBatteryRowStatus.{#HWUPSDEVICEID}]5m30dRowStatus of UPS battery information table.BatteryHUAWEI-UPS-MIB::RowStatusPOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} battery temperatureSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.6.100.1.6.{#HWUPSDEVICEID}huawei-ups[hwUpsBatterytemperature.{#HWUPSDEVICEID}]5m30dFLOAT°CBattery temperature.Value range: -20 to 80, Unit:°C, and the value is accurate to one decimal place (.1).BatteryMULTIPLIER0.1POST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} battery voltageSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.6.100.1.1.{#HWUPSDEVICEID}huawei-ups[hwUpsBatteryVoltage.{#HWUPSDEVICEID}]5m30dFLOATVBattery Voltage. It is a real-time analog parameter. Value range: 0 to 20000, Unit: V, and the value is accurate to one decimal place (.1).BatteryMULTIPLIER0.1POST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} battery schedule rest row statusSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.103.101.1.100.{#HWUPSDEVICEID}huawei-ups[hwUpsBattScheduleTestRowStatus/{#HWUPSDEVICEID}]5m30dRowStatus of UPS Battery control table.ControlHUAWEI-UPS-MIB::RowStatusPOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} battery testSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.103.101.1.6.{#HWUPSDEVICEID}huawei-ups[hwUpsBattTest.{#HWUPSDEVICEID}]10m30dIf you set the value to shallowDsgTest(4), you can perform a shallow discharge test; if you set the value to verifyDsgTest(5), you can perform a capacity test; if you set the value to stopTest(2), you can stop the test. Other settings are invalid. If you start a test when other tests are in progress, error code 4 is returned.
During test, you can use this node to obtain the current or previous test type.
If you have never started the battery test sheduleTest(3), shallowDsgTest(4), or verifyDsgTest(5), this node returns noTestInit(1).ControlHUAWEI-UPS-MIB::hwUpsBattTestPOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} bypass input frequencySNMP_AGENT1.3.6.1.4.1.2011.6.174.1.5.100.1.4.{#HWUPSDEVICEID}huawei-ups[hwUpsBypassInputFrequency.{#HWUPSDEVICEID}]5m30dFLOATHzBypass input frequency. The value ranges from 0 to 10000 The value is accurate to two decimal place on the NetEco. The unit is Hz.BypassMULTIPLIER0.01POST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} bypass input voltage phase ASNMP_AGENT1.3.6.1.4.1.2011.6.174.1.5.100.1.1.{#HWUPSDEVICEID}huawei-ups[hwUpsBypassInputVoltageA.{#HWUPSDEVICEID}]5m30dFLOATVBypass input voltage phase A. The value ranges from 0 to 10000 The value is accurate to one decimal place on the NetEco. The unit is VBypassMULTIPLIER0.1POST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} bypass input voltage phase BSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.5.100.1.2.{#HWUPSDEVICEID}huawei-ups[hwUpsBypassInputVoltageB.{#HWUPSDEVICEID}]5m30dFLOATVBypass input voltage phase B. The value ranges from 0 to 10000 The value is accurate to one decimal place on the NetEco. The unit is VBypassMULTIPLIER0.1POST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} bypass input voltage phase CSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.5.100.1.3.{#HWUPSDEVICEID}huawei-ups[hwUpsBypassInputVoltageC.{#HWUPSDEVICEID}]5m30dFLOATVBypass input voltage phase C. The value ranges from 0 to 10000 The value is accurate to one decimal place on the NetEco. The unit is VBypassMULTIPLIER0.1POST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} bypass row statusSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.5.100.1.100.{#HWUPSDEVICEID}huawei-ups[hwUpsBypassRowStatus.{#HWUPSDEVICEID}]5m30dRowStatus of UPS bypass information table.BypassHUAWEI-UPS-MIB::RowStatusPOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} battery end testSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.102.100.1.19.{#HWUPSDEVICEID}huawei-ups[hwUpsCtrlBatteryEndTest.{#HWUPSDEVICEID}]10m30dBattery End Test,Enumeration type.
Value 1 indicates enabled.
Value 2 indicates unknownControlHUAWEI-UPS-MIB::hwUpsCtrlBatteryEndTestPOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} battery manual boost chargeSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.102.100.1.15.{#HWUPSDEVICEID}huawei-ups[hwUpsCtrlBatteryManualBoostCharge.{#HWUPSDEVICEID}]10m30dBattery Manual to Boost Charge,Enumeration type.
Value 1 indicates enabled.
Value 2 indicates disabled.ControlHUAWEI-UPS-MIB::hwUpsCtrlBatteryManualBoostChargePOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} battery manual float chargeSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.102.100.1.16.{#HWUPSDEVICEID}huawei-ups[hwUpsCtrlBatteryManualFloatCharge.{#HWUPSDEVICEID}]10m30dBattery Manual to Float Charge,Enumeration type.
Value 1 indicates enabled.
Value 2 indicates unknownControlHUAWEI-UPS-MIB::hwUpsCtrlBatteryManualFloatChargePOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} battery shallow testSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.102.100.1.17.{#HWUPSDEVICEID}huawei-ups[hwUpsCtrlBatteryShallowTest.{#HWUPSDEVICEID}]10m30dBattery Shallow Test,Enumeration type.
Value 1 indicates enabled.
Value 2 indicates unknownControlHUAWEI-UPS-MIB::hwUpsCtrlBatteryShallowTestPOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} battery stop test stateSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.102.100.1.14.{#HWUPSDEVICEID}huawei-ups[hwUpsCtrlBatteryStopTestState.{#HWUPSDEVICEID}]5m30dBattery Stop Test State,Enumeration type.
Value 1 indicates enabled.
Value 2 indicates disabled.ControlHUAWEI-UPS-MIB::hwUpsCtrlBatteryStatePOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} battery to boost stateSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.102.100.1.11.{#HWUPSDEVICEID}huawei-ups[hwUpsCtrlBatteryToBoostState.{#HWUPSDEVICEID}]5m30dBattery Change to Boost Charge State,Enumeration type.
Value 1 indicates enabled.
Value 2 indicates disabled.ControlHUAWEI-UPS-MIB::hwUpsCtrlBatteryStatePOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} battery to float stateSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.102.100.1.12.{#HWUPSDEVICEID}huawei-ups[hwUpsCtrlBatteryToFloatState.{#HWUPSDEVICEID}]5m30dBattery Change to Float Charge State,Enumeration type.
Value 1 indicates enabled.
Value 2 indicates disabled.ControlHUAWEI-UPS-MIB::hwUpsCtrlBatteryStatePOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} battery to test stateSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.102.100.1.13.{#HWUPSDEVICEID}huawei-ups[hwUpsCtrlBatteryToTestState.{#HWUPSDEVICEID}]5m30dBattery Change to Test State,Enumeration type.
Value 1 indicates enabled.
Value 2 indicates disabled.ControlHUAWEI-UPS-MIB::hwUpsCtrlBatteryStatePOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} battery verify cap testSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.102.100.1.18.{#HWUPSDEVICEID}huawei-ups[hwUpsCtrlBatteryVerifyCapTest.{#HWUPSDEVICEID}]10m30dBattery Verify Cap Test,Enumeration type.
Value 1 indicates enabled.
Value 2 indicates unknownControlHUAWEI-UPS-MIB::hwUpsCtrlBatteryVerifyCapTestPOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} ECO switchSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.102.100.1.1.{#HWUPSDEVICEID}huawei-ups[hwUpsCtrlECOSwitch.{#HWUPSDEVICEID}]10m30dECO settings. Enumeration type. The default value is 1.
Value 1 indicates ECO mode.
Value 2 indicates Non ECO mode.ControlHUAWEI-UPS-MIB::hwUpsCtrlECOSwitchPOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} EPOSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.102.100.1.21.{#HWUPSDEVICEID}huawei-ups[hwUpsCtrlEPO.{#HWUPSDEVICEID}]10m30dEPO. Enumeration type.
Value 1 indicates EPO .
Value 255 indicates invalid.ControlHUAWEI-UPS-MIB::hwUpsCtrlEPOPOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} input standardSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.102.100.1.8.{#HWUPSDEVICEID}huawei-ups[hwUpsCtrlInputStandard.{#HWUPSDEVICEID}]10m30dInput Standard,Enumeration type.
Value 1 indicates single phase.
Value 2 indicates three phase.ControlHUAWEI-UPS-MIB::hwUpsCtrlInputStandardPOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} model capacitySNMP_AGENT1.3.6.1.4.1.2011.6.174.1.102.100.1.20.{#HWUPSDEVICEID}huawei-ups[hwUpsCtrlModelCapacity.{#HWUPSDEVICEID}]10m30dModel Capacity.The value ranges from 0 to 200, The value is accurate to one decimal place on the NetEco. The unit is kVA.ControlPOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} model TypeSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.102.100.1.7.{#HWUPSDEVICEID}huawei-ups[hwUpsCtrlModelType.{#HWUPSDEVICEID}]6h30dModel type,Enumeration type.
Value 17 indicates 6K.
Value 33 indicates 10K.
Value 65 indicates 20K.ControlHUAWEI-UPS-MIB::hwUpsCtrlModelTypeMULTIPLIER0.1POST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} output standardSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.102.100.1.9.{#HWUPSDEVICEID}huawei-ups[hwUpsCtrlOutputStandard.{#HWUPSDEVICEID}]10m30dOutput Standard,Enumeration type.
Value 1 indicates single phase.
Value 2 indicates three phase.ControlHUAWEI-UPS-MIB::hwUpsCtrlOutputStandardPOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} power offSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.102.100.1.3.{#HWUPSDEVICEID}huawei-ups[hwUpsCtrlPowerOff.{#HWUPSDEVICEID}]5m30dPower off settings. Enumeration type.
Value 1 indicates power off .
Value 2 indicates unknow.ControlHUAWEI-UPS-MIB::hwUpsCtrlPowerOffPOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} power onSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.102.100.1.2.{#HWUPSDEVICEID}huawei-ups[hwUpsCtrlPowerOn.{#HWUPSDEVICEID}]5m30dPower on settings. Enumeration type.
Value 1 indicates power on .
Value 2 indicates unknow.ControlHUAWEI-UPS-MIB::hwUpsCtrlPowerOnPOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} power on stateSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.102.100.1.10.{#HWUPSDEVICEID}huawei-ups[hwUpsCtrlPowerOnState.{#HWUPSDEVICEID}]5m30dPower On State,Enumeration type.
Value 1 indicates power off.
Value 2 indicates booting.
Value 3 indicates failed to power on.
Value 4 indicates succeed tp power on.ControlHUAWEI-UPS-MIB::hwUpsCtrlPowerOnStatePOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} row statusSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.102.100.1.100.{#HWUPSDEVICEID}huawei-ups[hwUpsCtrlRowStatus.{#HWUPSDEVICEID}]5m30dRowStatus of UPS rack control tableControlHUAWEI-UPS-MIB::RowStatusPOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} battery statusSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.2.101.1.3.{#HWUPSDEVICEID}huawei-ups[hwUpsDeviceBatteryState.{#HWUPSDEVICEID}]10s30dBattery status. Enumeration type.
Value 1 indicates that no battery is connected.
Value 2 indicates that the battery is not charging or discharging.
Value 3 indicates hibernation.
Value 4 indicates float charging.
Value 5 indicates equalized charging.
Value 6 indicates discharging.DeviceHUAWEI-UPS-MIB::hwUpsDeviceBatteryStateDISCARD_UNCHANGED_HEARTBEAT5mPOST{last()}=6Battery is discharging on {HOST.NAME}HIGHlast value: {ITEM.LASTVALUE}{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} current flow statusSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.2.101.1.5.{#HWUPSDEVICEID}huawei-ups[hwUpsDeviceEnergyFloatState.{#HWUPSDEVICEID}]5m30dCurrent flow status. An integer ranging from 0 to 70000.DevicePOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} ESNSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.2.100.1.5.{#HWUPSDEVICEID}huawei-ups[hwUpsDeviceESN.{#HWUPSDEVICEID}]6h30d0TEXTESN. A string of characters.DevicePOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} row statusSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.2.100.1.100.{#HWUPSDEVICEID}huawei-ups[hwUpsDeviceIdentRowStatus.{#HWUPSDEVICEID}]5m30dRowStatus of UPS device Identification table.DeviceHUAWEI-UPS-MIB::RowStatusPOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} interface protocolSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.2.100.1.4.{#HWUPSDEVICEID}huawei-ups[hwUpsDeviceInerProtVersion.{#HWUPSDEVICEID}]6h30d0TEXTInterface protocol version number for the current device. A string of characters.DevicePOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} running row statusSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.2.101.1.101.{#HWUPSDEVICEID}huawei-ups[hwUpsDeviceOperInfoRowStatus.{#HWUPSDEVICEID}]5m30dRowStatus of UPS device running information table.DeviceHUAWEI-UPS-MIB::RowStatusPOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} parallel IDSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.2.100.1.7.{#HWUPSDEVICEID}huawei-ups[hwUpsDeviceParaSysIndex.{#HWUPSDEVICEID}]6h30dID of the parallel system that the current device belongs to. An integer ranging from 0 to 63.DevicePOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} power ratingSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.2.100.1.6.{#HWUPSDEVICEID}huawei-ups[hwUpsDevicePowerRating.{#HWUPSDEVICEID}]6h30dSystem capacity. Enumeration type. The default value is 5. The unit is kVA.
Value 1 indicates 80 kVA
Value 2 indicates 100 kVA.
Value 3 indicates 120 kVA.
Value 4 indicates 160 kVA.
Value 5 indicates 200 kVA.DeviceHUAWEI-UPS-MIB::hwUpsDevicePowerRatingPOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} power supply modeSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.2.101.1.1.{#HWUPSDEVICEID}huawei-ups[hwUpsDevicePowerSupplyMethod.{#HWUPSDEVICEID}]5m30dDevice power supply mode. Enumeration type.
Value 1 indicates no power supply.
Value 2 indicates bypass mode.
Value 3 indicates normal mode.
Value 4 indicates battery mode.
Value 5 indicates combined mode.
Value 6 indicates mains ECO mode.
Value 7 indicates battery ECO mode.DeviceHUAWEI-UPS-MIB::hwUpsDevicePowerSupplyMethodPOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} redundant numberSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.2.101.1.6.{#HWUPSDEVICEID}huawei-ups[hwUpsDeviceRedundantNumber.{#HWUPSDEVICEID}]1h30dRedundant number of the parallel system. An integer ranging from 0 to 3.DevicePOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} soft version numberSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.2.100.1.3.{#HWUPSDEVICEID}huawei-ups[hwUpsDeviceSoftVersion.{#HWUPSDEVICEID}]6h30d0TEXTDevice software version number. A string of characters.DevicePOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} temperatureSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.2.101.1.4.{#HWUPSDEVICEID}huawei-ups[hwUpsDeviceTemperature.{#HWUPSDEVICEID}]5m30dFLOAT°CMaximum temperature of the modules in the current device. An integer ranging from 0 to 300.DeviceMULTIPLIER0.1POSTDevice model with ID {#HWUPSDEVICEID}SNMP_AGENT1.3.6.1.4.1.2011.6.174.1.2.100.1.2.{#HWUPSDEVICEID}huawei-ups[hwUpsDeviceType.{#HWUPSDEVICEID}]6h30d0TEXTDevice model. A string of characters.DevicePOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} input frequencySNMP_AGENT1.3.6.1.4.1.2011.6.174.1.3.100.1.4.{#HWUPSDEVICEID}huawei-ups[hwUpsInputFrequency.{#HWUPSDEVICEID}]5m30dFLOATHzInput frequency. The value ranges from 0 to 10000. The value is accurate to two decimal place on the NetEco. The unit is Hz.InputMULTIPLIER0.01POST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} input row statusSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.3.100.1.100.{#HWUPSDEVICEID}huawei-ups[hwUpsInputRowStatus.{#HWUPSDEVICEID}]5m30dRowStatus of UPS input information table.InputHUAWEI-UPS-MIB::RowStatusPOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} input voltage phase ASNMP_AGENT1.3.6.1.4.1.2011.6.174.1.3.100.1.1.{#HWUPSDEVICEID}huawei-ups[hwUpsInputVoltageA.{#HWUPSDEVICEID}]5m30dFLOATVInput voltage phase A. The value ranges from 0 to 10000. The value is accurate to one decimal place on the NetEco. The unit is V.InputMULTIPLIER0.1POST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} input voltage phase BSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.3.100.1.2.{#HWUPSDEVICEID}huawei-ups[hwUpsInputVoltageB.{#HWUPSDEVICEID}]5m30dFLOATVInput voltage phase B. The value ranges from 0 to 10000. The value is accurate to one decimal place on the NetEco. The unit is V.InputMULTIPLIER0.1POST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} input voltage phase CSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.3.100.1.3.{#HWUPSDEVICEID}huawei-ups[hwUpsInputVoltageC.{#HWUPSDEVICEID}]5m30dFLOATVInput voltage phase C. The value ranges from 0 to 10000. The value is accurate to one decimal place on the NetEco. The unit is V.InputMULTIPLIER0.1POST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} output active power phase ASNMP_AGENT1.3.6.1.4.1.2011.6.174.1.4.100.1.8.{#HWUPSDEVICEID}huawei-ups[hwUpsOutputActivePowerA.{#HWUPSDEVICEID}]5m30dkWRack phase A output active power. The value ranges from -12000 to 12000. The value is accurate to one decimal place on the NetEco. The unit is kW.OutputMULTIPLIER0.1POST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} output active power phase BSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.4.100.1.9.{#HWUPSDEVICEID}huawei-ups[hwUpsOutputActivePowerB.{#HWUPSDEVICEID}]5m30dkWRack phase B output active power. The value ranges from -12000 to 12000. The value is accurate to one decimal place on the NetEco. The unit is kW.OutputMULTIPLIER0.1POST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} output active power phase CSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.4.100.1.10.{#HWUPSDEVICEID}huawei-ups[hwUpsOutputActivePowerC.{#HWUPSDEVICEID}]5m30dkWRack phase C output active power. The value ranges from -12000 to 12000. The value is accurate to one decimal place on the NetEco. The unit is kW.OutputMULTIPLIER0.1POST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} output appearance power phase ASNMP_AGENT1.3.6.1.4.1.2011.6.174.1.4.100.1.11.{#HWUPSDEVICEID}huawei-ups[hwUpsOutputAppearancePowerA.{#HWUPSDEVICEID}]5m30dFLOATkVARack phase A output apparent power. The value ranges from -12000 to 12000. The value is accurate to one decimal place on the NetEco. The unit is kVA.OutputMULTIPLIER0.1POST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} output appearance power phase BSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.4.100.1.12.{#HWUPSDEVICEID}huawei-ups[hwUpsOutputAppearancePowerB.{#HWUPSDEVICEID}]5m30dFLOATkVARack phase B output apparent power. The value ranges from -12000 to 12000. The value is accurate to one decimal place on the NetEco. The unit is kVA.OutputMULTIPLIER0.1POST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} output appearance power phase CSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.4.100.1.13.{#HWUPSDEVICEID}huawei-ups[hwUpsOutputAppearancePowerC.{#HWUPSDEVICEID}]5m30dFLOATkVARack phase C output apparent power. The value ranges from -12000 to 12000. The value is accurate to one decimal place on the NetEco. The unit is kVA.OutputMULTIPLIER0.1POST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} output current phase ASNMP_AGENT1.3.6.1.4.1.2011.6.174.1.4.100.1.4.{#HWUPSDEVICEID}huawei-ups[hwUpsOutputCurrentA.{#HWUPSDEVICEID}]5m30dFLOATARack phase A output current. The value ranges from 0 to 10000. The value is accurate to one decimal place on the NetEco. The unit is A.OutputMULTIPLIER0.1POST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} output current phase BSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.4.100.1.5.{#HWUPSDEVICEID}huawei-ups[hwUpsOutputCurrentB.{#HWUPSDEVICEID}]5m30dFLOATARack phase B output current. The value ranges from 0 to 10000. The value is accurate to one decimal place on the NetEco. The unit is A.OutputMULTIPLIER0.1POST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} output current phase CSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.4.100.1.6.{#HWUPSDEVICEID}huawei-ups[hwUpsOutputCurrentC.{#HWUPSDEVICEID}]5m30dFLOATARack phase C output current. The value ranges from 0 to 10000. The value is accurate to one decimal place on the NetEco. The unit is A.OutputMULTIPLIER0.1POST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} output frequencySNMP_AGENT1.3.6.1.4.1.2011.6.174.1.4.100.1.7.{#HWUPSDEVICEID}huawei-ups[hwUpsOutputFrequency.{#HWUPSDEVICEID}]5m30dFLOATHzRack output frequency. The value ranges from 0 to 10000. The value is accurate to two decimal place on the NetEco. The unit is Hz.OutputMULTIPLIER0.01POST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} output load phase ASNMP_AGENT1.3.6.1.4.1.2011.6.174.1.4.100.1.14.{#HWUPSDEVICEID}huawei-ups[hwUpsOutputLoadA.{#HWUPSDEVICEID}]5m30dFLOAT%Rack phase A output load ratio. The value ranges from 0 to 5000 The value is accurate to one decimal place on the NetEco.OutputMULTIPLIER0.1POST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} output load phase BSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.4.100.1.15.{#HWUPSDEVICEID}huawei-ups[hwUpsOutputLoadB.{#HWUPSDEVICEID}]5m30dFLOAT%Rack phase B output load ratio. The value ranges from 0 to 5000 The value is accurate to one decimal place on the NetEco.OutputMULTIPLIER0.1POST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} output load phase CSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.4.100.1.16.{#HWUPSDEVICEID}huawei-ups[hwUpsOutputLoadC.{#HWUPSDEVICEID}]5m30dFLOAT%Rack phase C output load ratio. The value ranges from 0 to 5000 The value is accurate to one decimal place on the NetEco.OutputMULTIPLIER0.1POST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} output row statusSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.4.100.1.100.{#HWUPSDEVICEID}huawei-ups[hwUpsOutputRowStatus.{#HWUPSDEVICEID}]5m30dRowStatus of UPS output information table.OutputHUAWEI-UPS-MIB::RowStatusPOST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} output voltage phase ASNMP_AGENT1.3.6.1.4.1.2011.6.174.1.4.100.1.1.{#HWUPSDEVICEID}huawei-ups[hwUpsOutputVoltageA.{#HWUPSDEVICEID}]5m30dFLOATVRack phase A output voltage. The value ranges from 0 to 10000. The value is accurate to one decimal place on the NetEco. The unit is V.OutputMULTIPLIER0.1POST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} output voltage phase BSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.4.100.1.2.{#HWUPSDEVICEID}huawei-ups[hwUpsOutputVoltageB.{#HWUPSDEVICEID}]5m30dFLOATVRack phase B output voltage. The value ranges from 0 to 10000. The value is accurate to one decimal place on the NetEco. The unit is V.OutputMULTIPLIER0.1POST{#HWUPSDEVICETYPE}-{#HWUPSDEVICEID} output voltage phase CSNMP_AGENT1.3.6.1.4.1.2011.6.174.1.4.100.1.3.{#HWUPSDEVICEID}huawei-ups[hwUpsOutputVoltageC.{#HWUPSDEVICEID}]5m30dFLOATVRack phase C output voltage. The value ranges from 0 to 10000. The value is accurate to one decimal place on the NetEco. The unit is V.OutputMULTIPLIER0.1POSTPOST{$BACKUP_TIME}15m{$BATTERY_CHARGE}80HUAWEI-UPS-MIB::hwUpsBattAutoTest1disable2enalbeHUAWEI-UPS-MIB::hwUpsBattAutoTestTimeLimit1from0to62from6to123from12to184from18to24HUAWEI-UPS-MIB::hwUpsBattTest1noTestInit2stopTest3scheduleTest4shallowDsgTest5verufyDsgTestHUAWEI-UPS-MIB::hwUpsCtrlBatteryEndTest1toEndTest255unknownHUAWEI-UPS-MIB::hwUpsCtrlBatteryManualBoostCharge1toBoostCharge255unknownHUAWEI-UPS-MIB::hwUpsCtrlBatteryManualFloatCharge1toFloatCharge255unknownHUAWEI-UPS-MIB::hwUpsCtrlBatteryShallowTest1toShallowTest255unknownHUAWEI-UPS-MIB::hwUpsCtrlBatteryState1enable2disableHUAWEI-UPS-MIB::hwUpsCtrlBatteryVerifyCapTest1toVerifyCapTest255unknownHUAWEI-UPS-MIB::hwUpsCtrlECOSwitch1noECO2ecoHUAWEI-UPS-MIB::hwUpsCtrlEPO1epo255unknownHUAWEI-UPS-MIB::hwUpsCtrlInputStandard1singlePhase2threePhaseHUAWEI-UPS-MIB::hwUpsCtrlModelType17model6K33mode110K65model20KHUAWEI-UPS-MIB::hwUpsCtrlOutputStandard1singlePhase2threePhaseHUAWEI-UPS-MIB::hwUpsCtrlPowerOff1powerOff255unknownHUAWEI-UPS-MIB::hwUpsCtrlPowerOn1powerOn255unknownHUAWEI-UPS-MIB::hwUpsCtrlPowerOnState1powerOff2powerOn3powerOnFail4powerOnCompleteHUAWEI-UPS-MIB::hwUpsDeviceBatteryState1notExist2temperaryMode3sleep4floatCharge5boostCharge6dischargeHUAWEI-UPS-MIB::hwUpsDevicePowerRating1level802level1003level1204level1605level2006level307level408level609level24010level25011level28012level300HUAWEI-UPS-MIB::hwUpsDevicePowerSupplyMethod1noOutput2bypass3normal4battery5sourceShare6normalECO7batteryECOHUAWEI-UPS-MIB::RowStatus1active2notInService3notReady4createAndGo5createAndWait6destroy