5.02021-11-25T12:34:31ZTemplates/ModulesUPSLiebert_GXT4_UPSLiebert_GXT4_UPSTemplate Module ICMP PingUPSBattery informationBattery InputBattery OutputSystem InformationUPS Healthy- Firmware versionSNMP_AGENT.1.3.6.1.2.1.33.1.1.3.0lgpAgentDeviceFirmwareVersion24h0CHARSystem Information
- Manufacture dateSNMP_AGENT.1.3.6.1.4.1.476.1.42.2.4.2.1.8.1lgpAgentDeviceManufactureDate24h0CHARSystem Information
- ModelSNMP_AGENT.1.3.6.1.2.1.33.1.1.2.0lgpAgentDeviceModel24h0CHARSystem Information
- Number of current alarmSNMP_AGENT.1.3.6.1.2.1.33.1.6.1.0upsAlarmsPresentAlarmThe present number of active alarm conditions
A list of alarm table entries. The table contains
zero, one, or many rows at any moment, depending upon
the number of alarm conditions in effect. The table
is initially empty at agent startup. The agent
creates a row in the table each time a condition is
detected and deletes that row when that condition no
longer pertains. The agent creates the first row with
upsAlarmId equal to 1, and increments the value of
upsAlarmId each time a new row is created, wrapping to
the first free value greater than or equal to 1 when
the maximum value of upsAlarmId would otherwise be
exceeded. Consequently, after multiple operations,
the table may become sparse, e.g., containing entries
for rows 95, 100, 101, and 203 and the entries should
not be assumed to be in chronological order because
upsAlarmId might have wrapped.
Alarms are named by an AutonomousType (OBJECT
IDENTIFIER), upsAlarmDescr, to allow a single table to
reflect well known alarms plus alarms defined by a
particular implementation, i.e., as documented in the
private enterprise MIB definition for the device. No
two rows will have the same value of upsAlarmDescr,
since alarms define conditions. In order to meet this
requirement, care should be taken in the definition of
alarm conditions to insure that a system cannot enter
the same condition multiple times simultaneously.
The number of rows in the table at any given time is
reflected by the value of upsAlarmsPresent.UPS Healthy{last(,0)}>=1An alarm has been detected, please checkhttp://pth-rack03-ups.corescan.net.au/default.html?devId=4WARNINGLogin to the ups Web UI and check for any alarms there.
- Battery statusSNMP_AGENT.1.3.6.1.2.1.33.1.2.1.0upsBatteryStatusThe indication of the capacity remaining in the UPS
system's batteries. A value of batteryNormal
indicates that the remaining run-time is greater than
upsConfigLowBattTime. A value of batteryLow indicates
that the remaining battery run-time is less than or
equal to upsConfigLowBattTime. A value of
batteryDepleted indicates that the UPS will be unable
to sustain the present load when and if the utility
power is lost (including the possibility that the
utility power is currently absent and the UPS is
unable to sustain the output).
INTEGER {unknown(1),
batteryNormal(2),
batteryLow(3),
batteryDepleted(4)
}Battery informationapcBatteryStatus{last(,0)}=4Battery DepletedAVERAGE{unknown(1),
batteryNormal(2),
batteryLow(3),
batteryDepleted(4)
}{last(,0)}=3Battery LowWARNING{unknown(1),
batteryNormal(2),
batteryLow(3),
batteryDepleted(4)
}
- Battery voltageSNMP_AGENT.1.3.6.1.2.1.33.1.2.5.0upsBatteryVoltageVoltsThe magnitude of the present battery voltage.Battery information
- Charge remainingSNMP_AGENT.1.3.6.1.2.1.33.1.2.4.0upsEstimatedChargeRemaining%An estimate of the battery charge remaining expressed
as a percent of full chargeBattery information
- Estimated time remaining on batterySNMP_AGENT.1.3.6.1.2.1.33.1.2.3.0upsEstimatedMinutesRemaininguptimeAn estimate of the time to battery charge depletion
under the present load conditions if the utility power
is off and remains off, or if it were to be lost and
remain off.Battery information{last(,0)}=5Battery will turn in 5 minAVERAGE{last(,0)}=15Battery will turn in 15 minWARNING
- Input currentSNMP_AGENT.1.3.6.1.2.1.33.1.3.3.1.4.1upsInputCurrentVoltsThe magnitude of the present input current.Battery Input
- Input FrequencySNMP_AGENT.1.3.6.1.2.1.33.1.3.3.1.2.1upsInputFrequencyThe present input frequency.Battery Input
- Input voltageSNMP_AGENT.1.3.6.1.2.1.33.1.3.3.1.3.1upsInputVoltageVoltsThe magnitude of the present input voltageBattery Input
- Output currentSNMP_AGENT.1.3.6.1.2.1.33.1.4.4.1.3.1upsOutputCurrentVoltsThe present output currentBattery Output
- Output frequencySNMP_AGENT.1.3.6.1.2.1.33.1.4.2.0upsOutputFrequencyThe present output frequency.Battery Output
- UPS power capacity presently being usedSNMP_AGENT.1.3.6.1.2.1.33.1.4.4.1.5.1upsOutputPercentLoad% of VAThe percentage of the UPS power capacity presently
being used on this output line, i.e., the greater of
the percent load of true power capacity and the
percent load of VA.Battery Output
- Output powerSNMP_AGENT.1.3.6.1.2.1.33.1.4.4.1.4.1upsOutputPowerVoltsThe present output true powerBattery Output
- Output sourceSNMP_AGENT.1.3.6.1.2.1.33.1.4.1.0upsOutputSourceThe present source of output power. The enumeration
none(2) indicates that there is no source of output
power (and therefore no output power), for example,
the system has opened the output breakerBattery OutputTripplite Output Source
- Output voltageSNMP_AGENT.1.3.6.1.2.1.33.1.4.4.1.2.1upsOutputVoltageVoltsThe present output voltageBattery Output
- Time on batterySNMP_AGENT.1.3.6.1.2.1.33.1.2.2.0upsSecondsOnBatteryuptimeIf the unit is on battery power, the elapsed time
since the UPS last switched to battery power, or the
time since the network management subsystem was last
restarted, whichever is less. Zero shall be returned
if the unit is not on battery power.apcBatteryStatus
- UPS test resultsSNMP_AGENT.1.3.6.1.2.1.33.1.7.4.0upsTestResultsDetail0CHARAdditional information about upsTestResultsSummary.
If no additional information available, a zero length
string is returnedUPS Healthy
- UPS last test performedSNMP_AGENT.1.3.6.1.2.1.33.1.7.3.0upsTestResultsSummaryThe results of the current or last UPS diagnostics
test performed. The values for donePass(1),
doneWarning(2), and doneError(3) indicate that the
test completed either successfully, with a warning, or
with an error, respectively. The value aborted(4) is
returned for tests which are aborted by setting the
value of upsTestId to upsTestAbortTestInProgress.
Tests which have not yet concluded are indicated by
inProgress(5). The value noTestsInitiated(6)
indicates that no previous test results are available,
such as is the case when no tests have been run since
the last reinitialization of the network management
subsystem and the system has no provision for non-
volatile storage of test results
INTEGER {donePass(1),
doneWarning(2),
doneError(3),
aborted(4),
inProgress(5),
noTestsInitiated(6)
}UPS HealthyUPS_Test_Summary{last(,0)}=2Last test performed reported a warning, please checkhttp://pth-rack03-ups.corescan.net.au/default.html?devId=4WARNINGINTEGER {donePass(1),
doneWarning(2),
doneError(3),
aborted(4),
inProgress(5),
noTestsInitiated(6)
}{last(,0)}=3Last test performed reported with error, please checkhttp://pth-rack03-ups.corescan.net.au/default.html?devId=4AVERAGEINTEGER {donePass(1),
doneWarning(2),
doneError(3),
aborted(4),
inProgress(5),
noTestsInitiated(6)
}
Template Module ICMP PingTemplate Module ICMP PingTemplate Module ICMP Ping version: 0.12Templates/ModulesStatus- ICMP pingSIMPLEicmpping601wStatusService state{max(#3)}=0Unavailable by ICMP pingHIGHLast value: {ITEM.LASTVALUE1}.
Last three attempts returned timeout. Please check device connectivity.
- ICMP lossSIMPLEicmppingloss601wFLOAT%Status{min(5m)}>{$ICMP_LOSS_WARN} and {min(5m)}<100High ICMP ping lossWARNINGUnavailable by ICMP ping{Template Module ICMP Ping:icmpping.max(#3)}=0
- ICMP response timeSIMPLEicmppingsec601wFLOATsStatus{avg(5m)}>{$ICMP_RESPONSE_TIME_WARN}High ICMP ping response timeWARNINGHigh ICMP ping loss{Template Module ICMP Ping:icmppingloss.min(5m)}>{$ICMP_LOSS_WARN} and {Template Module ICMP Ping:icmppingloss.min(5m)}<100Unavailable by ICMP ping{Template Module ICMP Ping:icmpping.max(#3)}=0
{$ICMP_LOSS_WARN}20{$ICMP_RESPONSE_TIME_WARN}0.15apcBatteryStatus1unknown2batteryNormal3batteryLow4batteryDepletedService state0Down1UpTripplite Output Source1other2none3normal4bypass5battery6booster7reducerUPS_Test_Summary1donePass2doneWarning3doneError4aborted5inProgress6noTestsInitiated