5.02021-11-21T21:46:14ZTemplatesTemplates/Network devicesSNMP Minuteman UPSSNMP Minuteman UPS## Overview
Basic SNMP v1 monitoring template for the Minuteman UPS
TemplatesTemplates/Network devicesAvailabilityEnvironmentGeneral- Battery TemperatureSNMP_AGENT.1.3.6.1.4.1.2254.2.4.7.9.0upsAdvBatteryTemperature307d°CEnvironment{last(0)}>43Battery Temp HighAVERAGE
- Output Load (%)SNMP_AGENT.1.3.6.1.4.1.2254.2.4.5.7.0upsAdvOutputLoad307dFLOAT%Availability{last(0)}>75Output Load HighAVERAGEOutput Load Too High{SNMP Minuteman UPS:upsAdvOutputLoad.last(0)}>90{last(0)}>90Output Load Too HighHIGH
- Battery Test ResultsSNMP_AGENT.1.3.6.1.4.1.2254.2.4.8.2.0upsAdvReplaceBatteryIndicator6007dEnvironmentMinuteman Battery Test Results{last()}=2Battery Test In ProgressINFO{last(0)}>2Replace BatteryHIGH
- Battery StatusSNMP_AGENT.1.3.6.1.4.1.2254.2.4.7.2.0upsBasicBatteryStatus307dAvailabilityMinuteman Battery Status{last()}=2RECOVERY_EXPRESSION{max(#3)}=0Battery Status DepletedHIGH{last()}=1Battery Status LowAVERAGE{last(0)}<>0Battery Status Not NormalHIGH
- Time On BatterySNMP_AGENT.1.3.6.1.4.1.2254.2.4.7.4.0upsBasicBatteryTimeOnBattery307dsAvailabilityMULTIPLIER0.01
- Model IdentSNMP_AGENT.1.3.6.1.4.1.2254.2.4.1.2.0upsBasicIdentModel864007d0CHARTYPEGeneral
- IdentSNMP_AGENT.1.3.6.1.4.1.2254.2.4.1.5.0upsBasicIdentName864007d0CHARNAMEGeneral
- Battery Output StatusSNMP_AGENT.1.3.6.1.4.1.2254.2.4.5.1.0upsBasicOutputStatus607dAvailabilityMinutemanUPS Output Status{last()}>1RECOVERY_EXPRESSION{max(#3)}=0Abnormal Power Status, current state - {ITEM.LASTVALUE1}INFO{last()}=1RECOVERY_EXPRESSION{sum(#5)}=0On Battery, current state - {ITEM.LASTVALUE1}HIGH
- Battery ChargeSNMP_AGENT1.3.6.1.4.1.2254.2.4.7.8.0upsBatteryCharge307d%Availability{last(0)}<25Battery Charge < 25%: {ITEM.LASTVALUE1}HIGH{last(0)}<50Battery Charge < 50 %: {ITEM.LASTVALUE1}DISASTERBattery Charge < 25%: {ITEM.LASTVALUE1}{SNMP Minuteman UPS:upsBatteryCharge.last(0)}<25{last(0)}<75Battery Charge < 75%: {ITEM.LASTVALUE1}WARNINGBattery Charge < 50 %: {ITEM.LASTVALUE1}{SNMP Minuteman UPS:upsBatteryCharge.last(0)}<50
- Input FreqSNMP_AGENT.1.3.6.1.4.1.2254.2.4.4.2.0upsInputFreq30Input frequency at CPSEnvironment{avg(#5)}>650 or {avg(#5)}<550Power Input Frequency out of rangeWARNINGYES
- Input VoltageSNMP_AGENT.1.3.6.1.4.1.2254.2.4.4.3.0upsInputVoltage30Environment{avg(#3)}>1220Input Voltage HighWARNING{avg(#3)}<1090Input Voltage LowWARNING
- Runtime RemainingSNMP_AGENT.1.3.6.1.4.1.2254.2.4.7.5.0upsRuntimeRemaining30s7d30dmEnvironment{last()}<1Runtime less than 1 MinutesDISASTER{last()}<5Runtime less than 5 MinutesHIGHRuntime less than 1 Minutes{SNMP Minuteman UPS:upsRuntimeRemaining.last()}<1{last()}<10Runtime less than 10 MinutesWARNINGRuntime less than 5 Minutes{SNMP Minuteman UPS:upsRuntimeRemaining.last()}<5
PowerStats00C800- SNMP Minuteman UPSupsInputFreq
1C80000- SNMP Minuteman UPSupsInputVoltage
Minuteman Battery Status0Ok1Low2DepletedMinuteman Battery Test Results0No Tests Initiated1Pass2In Progress3General Fail4Battery Fail5Deep test failureMinutemanUPS Output Status0Normal1On battery2On Bypass3Reducing Voltage4Boosting Voltage5Manual Bypass6Other7No Status